48
Medical and Life-Safety Systems Balancing Life-Safety and Critical System Reliability PRESENTED BY Michael Fluegeman, PE Principal, PlanNet

Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Medical and Life-Safety Systems

Balancing Life-Safety and Critical System Reliability

PRESENTED BY

Michael Fluegeman, PE Principal,  PlanNet  

Page 2: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Learning Objectives

•  Identify the unique operational aspects of managing medical and life safety facilities

•  Understand what puts life safety systems at odds with reliability

•  Analyze common causes of emergency shut downs

•  Learn about real-world shut down scenarios in a variety of healthcare systems

2

Page 3: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Speaker Background

•  PlanNet since 2007 Ø  A Technology Consulting & Construction Company Ø  Assessments Ø  Strategy/Design/Basis of Design/Specs Ø  Construction/Project Management Ø  Commissioning Ø Operations/Documentation/Training

Ø Litigation support

Prior: Syska Hennessy, Power Management, PRK Emerson/Liebert, Siemens/ITE, Westinghouse

3

Page 4: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Life-Safety Priorities

4

Page 5: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Life-Safety Priorities

Priorities

•  Patient Life-Safety

•  Worker Life-Safety

•  Continual Functionality of Technology Supporting Patient-Care Equipment

5

Page 6: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Life-Safety Risks

Risks

•  Shock, electrocution, arc-flash

•  Smoke, fire, fire detection & fire suppression shutdown of critical equipment

•  Failure of patient-care technology

•  Loss of communications during treatment v Tele-surgery, robotic surgery breakdown v Loss of remote phone / internet support

6

Page 7: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Shock, Electrocution & Arc-flash Risks

7

Page 8: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Shock, Electrocution & Arc-flash Risks

Shock & Electrocution Risks –  Wiring issues

–  Bonding & grounding issues

–  Equipment malfunction

Arc-flash Risks –  Largely affects electricians &

electrical equipment service providers

–  Live “hot” work no longer permitted. Without proper design & redundancy, maintenance & repairs requires critical systems shutdown

8

Page 9: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Wiring Issues

Ground currents & high neutral-ground voltages

•  Wiring code violations –  Ground loops (multiple neutral-ground bonds)

–  Neutral & ground conductors reversed

–  Difficult to troubleshoot

–  The older the building, the more likely these problems persist

•  Insulated, isolated ground systems contribute to problems if not carefully maintained throughout

9

Page 10: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Bonding & Grounding Issues

Bonding •  Code minimum is not good enough for reliability •  Good practices include not relying on conduit grounding, making

home-runs to master ground bars, two-hole lugs, not stacking lugs

10

Grounding  •  The  goal  is  to  achieve  equi-­‐poten9al  grounding  •  Exo9c  chemical  earth  ground  systems  normally  not  required  •  Do  not  violate  code  with  separated  ground  systems  

Page 11: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Grounding Fix

Ideally, root out the problems to reduce N-G potential & ground currents

Isolation transformers are effective electrical band-aids –  Grounding effectively starts over at the transformer output –  With proper wiring & bonding downstream of transformer, N-G

potential and ground currents should be near zero, regardless of the mess upstream

11

Ø  Shock & electrocution risks reduced

Page 12: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Shutdown of Critical Equipment from Smoke,

Fire, Fire Detection & Fire Suppression

12

Page 13: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Smoke & Fire Critical Shutdowns

Most shutdowns are not because of an actual emergency!

Ø Overly sensitive equipment Ø Hair-trigger actuation Ø Operator error Ø Technician error Ø Equipment failure Ø Not designed with uptime as a priority

o EPO triggered by fire alarm

13

Page 14: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Smoke & Fire Critical Shutdowns

Fire & Security design & technician professionals have a shut-down-when-in-doubt approach

Ø Systems cross-wired to shut down

Critical facility design & technician professionals have a shut-down-as-last-resort approach

Ø Eliminate shut down cross wiring unless code-required

14

Page 15: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Smoke & Fire Critical Shutdowns

Fire & Security design & technician professionals design held-closed circuits

Ø Open-circuit will become apparent (alert, alarm) Ø Open-circuit will normally be forgiving

Critical facility design & technician professionals design held-open circuits

Ø Open-circuit is forgiving, but may not become apparent

Ø  Short-circuit can be catastrophic

15

Page 16: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Failure of Patient-Care Technology

16

Page 17: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Failure of Patient-Care Technology

ICU life-support machines require reliable, continuous power

v Mechanical ventilators v Heart-lung bypass machines v Baby incubators

Local UPS units are often included with life-support machines; UPS unit failures can get ignored

Ø  UPS batteries require proactive maintenance

17

Page 18: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Loss of Communications during Treatment

18

Page 19: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Loss of Communications During Treatment

•  Loss of communications during treatment v Tele-surgery, robotic surgery breakdown v Loss of remote phone / internet support v Loss of access to patient records

19

Page 20: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Data Centers & other Critical Facilities

20

Page 21: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Data Centers

Increasingly remote from healthcare facilities

•  Enterprise –  Often poorly located within multi-purpose facility

Ø Water intrusion risks, central-plant dependencies

•  Colocation –  Single-purpose, multi-tenant, focused on data centers

•  Cloud services

•  Hybrid data services

21

Page 22: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

q Telecom rooms q Network equipment rooms q Distribution rooms/closets (MDF, BDF, IDF) q Radiology centers q Emergency Operation Centers (EOC)

22

Page 23: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

ü  Reliable network/telecom/internet/phone system ü  Reliable 24/7 cooling ü  Reliable power: UPS & generator backup ü  Fire protection (upgrades from wet sprinklers) ü  Central-plant dependencies (generator, chilled water, etc.) ü  Regulatory requirements ü  Emergency Power Off (EPO) shutdown systems

23

Telecom/network rooms, MDFs, BDFs, IDFs require or may have:

Page 24: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Reliable network/telecom/internet/phone system

ü  Redundant rooms ü  Redundant electronics ü  Redundant carriers, diversely routed

back to separate PoP sites ü  Reliable network architecture

24

Page 25: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Reliable 24/7 cooling ü  Redundant cooling equipment ü May require backup to central plant (DX, etc.) ü Generator backup for cooling ü  Redundant cooling equipment should be powered from

redundant ATSs

25

Page 26: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Reliable power: Generator backup for long-duration outages. Generator system typically supports:

–  Emergency lighting –  Fire alarm, suppression, pumps, etc. –  Elevators –  Essential medical equipment & treatment areas

Reliable power: UPS backup for short-duration outages –  Telecom/network rooms, radiology equipment –  UPS equipment ideally located outside of critical spaces

Redundant power distribution 26

Page 27: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Generator & UPS Power Back-up Systems

27

Page 28: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Backup Generator Systems

Life-safety generator system –  Supports life-safety systems; may also support a data center

•  Life-safety loads higher priority than data center –  Normally configured as parallel N+1 redundant –  10-second availability required by Code –  Regular load transfer testing required by AHJ –  ATSs normally closed-transition to reduce testing power bumps

Optional standby generator system –  Cannot support life-safety systems –  Supports data centers and other critical operations –  Better to configure as distributed redundant (2N, 3N/2, etc.) –  Regular load transfer testing not required by AHJ –  ATSs normally open-transition to reduce failure risk & complexity

28

Page 29: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Backup Generator Systems

If one generator system supports both life-safety & technology:

Use separate ATSs & breakers

•  Life-­‐safety  ATSs  require  regular  Agency-­‐mandated  transfer  tes9ng  Ø  Closed-­‐transi9on  ATSs  are  beFer  

•  Op9onal-­‐standby  ATSs  do  not  require  Agency-­‐mandated  transfer  tes9ng  Ø  Open-­‐transi9on  ATSs  are  beFer  

29

Page 30: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

UPS Systems

UPS systems provide 5-15 minutes of battery backup •  Healthcare network/MDF room healthcare power typically

configured with A-side UPS/generator; B-side utility o  B-side allows full maintenance bypass of UPS and ATS o  B-side will get bumped during power failures

•  Better to configure A-side UPS/generator/ATS-A; B-side UPS/generator/ATS-B (or at least generator ATS-B) o  No single-point failure risk; no need to rely on straight utility o  No B-side bumps or alerts

•  Lead-acid batteries used for decades; remain inexpensive •  Lithium-ion batteries gaining acceptance

o  Smaller, less weight, much longer life, more reliable

30

Page 31: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Fire protection for telecom/network rooms, MDFs –  Dry-pipe pre-action sprinklers –  Early warning, aspirating smoke detection (VESDA) –  Gas suppression decreasingly used due to cost

31

Page 32: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Central-plant dependencies

•  Central backup generator system with life-safety as priority Ø  Almost never more than N+1 redundant Ø  Small critical rooms can draw from separate, redundant ATSs

•  Chilled water plant Ø  Generally available 24/7 and reliable Ø  Subject to partial or full shutdowns for maintenance & repairs Ø  Small critical AHUs can draw from separate, redundant ATSs

32

Page 33: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

33

Page 34: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Critical Rooms in Healthcare Facilities

Emergency Power Off (EPO) “kill switch” shutdown systems

•  Shutdown mechanism at the computer room exit(s) Ø  Typically a button at all doors

•  Entire room shutdown not normally required Ø  Only power & supply air to IT equipment needs to be shut down Ø  Lighting, UPS & PDU equipment can remain energized

•  Legacy from 1960s mainframe data centers •  Required by national safety codes & Local AHJs •  Only applies to certain types of “computer rooms”

Ø  Generally those with access floors used both for supply air and cabling that is not anchored (flex power cabling)

34

Page 35: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

Everyone has an EPO story.

An unplanned shutdown.

The story almost never involves an actual emergency!

35

Page 36: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

For critical system reliability, the best EPO system is one that not required and is never designed or installed

Ø  Zero EPO systems

The next best EPO system, if required, is a system designed to prevent or limit erroneous activation

Ø  Two EPO systems for A/B power & redundant cooling

A single EPO system presents high risk to reliability

Ø One EPO system requires special care

36

Page 37: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

EPO systems are not normally required in small telecom/network rooms, MDFs, BDFs, IDFs, etc.

An EPO is normally not required for the following: •  Room with no access floor •  With access floor, but not used for supply air •  Access floor for supply air but not for cabling •  Access floor for supply air & cabling but all cabling anchored

Once an EPO is installed, or even part of a design package, it is difficult to remove

37

Page 38: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

q  Code allows two buttons q  Use separate A & B systems wiring, separate j-boxes q  Requires proper signage

38

Dual EPO System

Much  Lower  Risk  

Page 39: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Systems

39

q  Covered, recessed buttons are best q  Consider alarming cover (siren, strobe, etc.) q Maintenance bypass systems allow low-risk testing, changes q  Avoid held-closed designs q  Avoid fire alarm & control interfaces to EPO shutdown q Maintain accurate wiring as-built diagram

Single EPO requires hardening

 High  Risk   High  Risk   Lower  Risk  

Page 40: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

EPO Shutdown Recovery

q Maintain step-by-step recovery procedures q  If buttons are held-locked, provide access to key q Do not disable an EPO system

–  Do not remove shutdown wiring! –  Do not padlock EPO button covers!

q To reconfigure or eliminate an EPO system, do it thoroughly and completely.

Argument: If life-safety (patient-care) technology is supported by the UPS and cooling systems, then patient-care might be better served without an EPO system

40

Page 41: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Reliability Killers

41

Page 42: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Reliability Killers

§  EPO systems §  Circuit breaker nuisance tripping

Ø  Make sure trip settings are adjusted out from minimum Ø  Don’t set ground fault current interrupters (GFCI) too sensitive

§  Generator, switchgear or ATS not in auto mode §  Generator breaker left open §  Generator incorrect software installed §  UPS battery failure

Ø  Monitoring & self-testing can provide false sense of security §  UPS left in bypass §  Maintenance, construction w/o effective MoPs

42

Page 43: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Keys to Reliability

43

Page 44: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Keys to Reliability

§  Design commensurate with reliability requirements Ø  Eliminate or reduce single-point failure risks

§  Effective remote monitoring & controls §  Accurate, maintained as-built construction drawings §  Site-specific operating procedures, maintained §  Continuous operator training §  Preventative maintenance

Ø  Be aware of non-OEM service-provider limitations: UPS

§  Performance testing, commissioning §  Evaluate live facility risk vs. benefit

44

Page 45: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Regulatory Requirements

45

Page 46: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Healthcare Facilities

Regulatory requirements –  NFPA 70, 99 & 110

•  Generator load testing “30% testing” •  Load transfer of operating mechanical, electrical, plumbing, vertical transportation

and clinical systems from normal power to emergency generators and then back to normal power

•  Emergency power supply system (EPS) maintenance

–  The Joint Commission Accredits Healthcare Organizations – 39 month survey –  OSHPD: California's Office of Statewide Health Planning and Development

•  OSHPD also monitors the construction, renovation, and seismic safety of hospitals and skilled nursing facilities and provides loan insurance to assist the capital needs of California's not-for-profit healthcare facilities

•  Special equipment ratings: shake table testing •  Regular EPO testing (bypass, simulation allowed)

46

Page 47: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Healthcare Facilities

Regulatory requirements – Surge Protection Devices (SPDs) –  NEC Article 700.8 requires SPDs on all emergency power system

switchboards and panel boards, added to NEC 2014 –  Special requirements for SPDs with patient care equipment. The National

Electrical Code for Health Care Facilities (NEC Article 517) requires SPDs to protect medical equipment used in general or critical patient care areas. SPDs in these areas also must comply with the requirements of UL-60601 - Medical Electrical Equipment, Part 1: General Requirements for Safety and IEC 60601-1-1 - Medical Electrical Equipment - Part 1: General Requirements for Basic Safety and Essential Performance.

–  NEC 2017, issued in September of 2016, added requirements for SPDs on disconnects supplying emergency systems in Article 620.51(E). This section addresses SPD requirements for elevators, escalators, moving walks, platform lifts, and stairway chair lifts. Where any of the disconnecting means has been designated as supplying an emergency system load, surge protection shall be provided.

47

Page 48: Medical and Life-Safety Systemssystems • Shutdown mechanism at the computer room exit(s) ! Typically a button at all doors • Entire room shutdown not normally required ! Only power

Comments & Questions

Contact:  Michael  Fluegeman,  PE,  Principal  PlanNet  2951  Saturn  St.,  Suite  E,    Brea,  CA  92821    Office  714-­‐982-­‐5836  (rolls  to  mobile)  [email protected]      

48