Electro Industries/GaugeTech The Leader in Power Monitoring and Smart Grid Solutionswww.electroind.com Metering and Communication Multilevel Cyber Secure Encrypted Configuration Advanced Web Server with Waveform Analysis Tools Up to 1024 Samples per Cycle-based Measurements 0.06% Energy Accuracy Over Wide Dynamic Measurement Range Highly Accurate and Stable Measurements Using Multi-Gain™ Sensing 6 Available Communication Ports, Including Modbus and DNP 3.0 Protocols Two Independent Ethernet Ports, with Unique IP Addressing Advanced Power Quality Analysis Class A IEC 61000-4-30 Edition 3 Power Quality Measurements IEC 61000-4-15 Flicker Measurements IEC 61000-4-7 Harmonic Measurements EN 50160 Power Quality Reports New CORE™ Logging Architecture Easy-install Transducer and Separate Display Direct Physical Retrofit to Nexus® 125X Series Meter/ Transducer with Greater Functionality Separate 3 Line LED Displays Nexus ® 1450 Cyber Secure Energy Panel Meter with Advanced Power Quality & Multiport Communication Nexus® 1450 Meter P40N+ Remote Multifunction Display New New

Metering and Communication Advanced Power Quality Analysis

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Electro Industries/GaugeTech™

The Leader in Power Monitoring and Smart Grid Solutions™

www.

electr

oind

.com

Metering and Communication

• MultilevelCyberSecureEncryptedConfiguration

• AdvancedWebServerwithWaveformAnalysisTools

• Upto1024SamplesperCycle-basedMeasurements

• 0.06%EnergyAccuracyOverWideDynamicMeasurementRange

• HighlyAccurateandStableMeasurementsUsingMulti-Gain™Sensing

• 6AvailableCommunicationPorts,IncludingModbusandDNP3.0Protocols

• TwoIndependentEthernetPorts,withUniqueIPAddressing

Advanced Power Quality Analysis

• ClassAIEC61000-4-30Edition3PowerQualityMeasurements

• IEC61000-4-15FlickerMeasurements

• IEC61000-4-7HarmonicMeasurements

• EN50160PowerQualityReports

• NewCORE™LoggingArchitecture

• Easy-installTransducerandSeparateDisplay

• DirectPhysicalRetrofittoNexus®125XSeriesMeter/TransducerwithGreaterFunctionality

• Separate3LineLEDDisplays

Nexus®1450 Cyber Secure Energy Panel Meter with Advanced Power Quality & Multiport Communication

Nexus® 1450 Meter P40N+ Remote Multifunction Display

NewNew

Introduction

ElectroIndustries’Nexus®1450meterisapowerfulenergymeterthatprovidesaccurateelectricalenergymeasurementsandoffersadvancedcapabilitiesforpowerqualityanalysisanddeterminingelectricalpowerreliability.Themeterisatransducerbasewithaseparatedisplay.ThetransducerbaseretrofitstoexistingElectroIndustries’Nexus®1250and1252meters.TheNexus®1450meterisidealforexistingswitchboardpanels,sinceitcanbeinstalledwithoutcuttingpaneldoors.Theseparatedisplaymountsintoexistinganalogmeterknockouts.

TheNexus®1450meterisprotectedwithamulti-levelCyberSecureconfigurationwith10highlysecureencrypteduserIDsandpasswordsthathelppreventtamperingandhackingofyourpowersystemdata.Themeter'sbuiltinWebView™EnergyDashboardallowsyoutoanalyzemeteringdatawithoutneedingsoftware.Youcannavigateeasilythroughmultiplewebpageviewsandgetdetailedinformationonenergyusageandpowerquality:viewrealtimedata,analyzestoredhistorylogs,viewalarmsandwaveformrecords.

With6simultaneouslyoperatingcommunicationports,themeterisacommunicationhubtomultiplesoftwaresystems.TheNexus®1450meterhas4serialportsthatspeakModbusandDNP3.0protocols.ItalsohastwoindependentEthernetports,consistingofa10/100BaseTcopperRJ45connectorandanSTTerminated100BaseFXFiberOpticEthernetport.EachEthernetporthasauniqueIPaddress.Throughthemeter's6ports,auserisabletocommunicatetomultiplecomputer-basedsystems,providingdatatoentitiesthroughoutanenterprise.

Themeteralsoexcelsatmeasuringpowerquality,includingwaveformrecordingandIEC61000-4-7,IEC61000-4-15,andIEC61000-4-30ClassAcompliance.TheNexus®1450meterletsyoulookatthereliabilityoftheelectricalpowercircuittodeterminecausesoffaults,voltagesurgesandsags,andharmonics.

Multi-Gain™ Sensing Provides Superior Accuracy

TheNexus®1450meterutilizesEIG’slatestmeasurement-sensingtechnology-Multi-Gain™.Multi-Gain™technologyusestwosensorsonthecurrentinputs-ahighgainsensorandalowergainsensor.Eachsensorsimultaneouslymeasuresthecurrentsignalcomingfromtheexternalcurrenttransformers.Themeter’sintelligentprocessinglooksatthesignallevelanddeterminestheoptimalsensingcircuitforthehighestaccuracymeasurement.Withthistechnique,themeterhas0.06%accuracythroughoutanextendedmeasurementrange,whichisadefiningtraitofNexus®Seriesmeters.

Themeter’sstandardpickuprangestartsaslowas1mA,andhighaccuracyisattainedat25mA.Multi-Gain™metrologyallowsthesamemetertobeusedonboth5Asecondaryand1AsecondaryCTs.Themetershouldmaintainhighaccuracymeasurementthroughoutitsinstalledlife.Refertotheaccuracychartonthenextpage,fordetails.

Multi-Gain™MetrologyallowstheNexus®1450metertohavehighlyrepeatableandstablemeasurementsthroughoutrange

Typicalaccuracycharts

2

Meter Accuracy Specification

Measurement

VoltageL-N 0.04%ofreading

VoltageL-L 0.04%ofreading

Current 0.04%ofreading

NeutralCurrent 0.1%

Frequency 0.004Hz

Watts 0.06%ofreading

Watt-hour* 0.06%ofreading

VAR 0.15%ofreading

VARh 0.15%ofreading

VA 0.06%ofreading

PowerFactor 0.15%ofreading

THD 2.5%ofreading Precision Crystal Time Reference: TheNexus®1450meterisequippedwithaninternalclockcrystalaccurateto3.5PPMoverthefulloperatingtemperaturerangeand5PPMatovertenyearsofuse.Thishighlyaccuratetrimmedclockdesignallowsuserstomaintainaccuratetimewhenrunningoncrystalsynchronization.Themeter'sclockcrystalwilldriftlessthan6secondspermonthfrom(0-40)°C.Additionaltimesyncmethodsinclude:

• Modbustimesync.

• DNP3.0timesync.

• IRIG-Btimesync.

• SNTPtimesync.

Advanced Energy Meter for Primary Loads

TheNexus®1450unitisanelectricalenergymeterdesignedtobeusedforanyimportantapplication.Inadditiontohighlyaccurateenergymeasurement,themeterfeatures:

• Full4quadrantmetering.

• Max/Minrecordingwithtimestamp.

• Extensiveloggingwith8logsofprogrammablehistoricalprofiles.

• Built-inCORE™logforwebtrending.

• TransformerandLineLosscompensation:forbothironandcopper,andtotalsubstationlosses.

• CTandPTcompensation:tocorrectinstrumenttransformererrors.

• Coincidentalreadings:e.g.,PForVARsattimeofPeakDemand.

• Loadaggregation/universalmetering:pulseinputscanbeusedtoaggregateoraccumulatedifferentloads.Utilitycommoditiessuchasgasandwatercanalsobeaccumulated.

On-board Time of Use Measurements:

TheNexus®1450meterusesaperpetualTimeofUse(TOU)calendarthatonlyneedstobesetuponce.TheTOUimplementationallowstheusertosetupmultipletariffstomeetanycontractualobligations.ItalsoallowstheusertocustomizeanyenergyparameterforTOU.The16availableTOUregisterscanbeconfigurednotonlyforTOUbuilt-inenergyreadings,butalsoforanystoreddatafrompulsesorotherreadingsthatneedTOUfunctionality.

• Uptofourseasons-seasonscanbecustomized.

• Flexiblebillingperiods/rates/holidays/schedulessetup.

• Cumulativeandcontinuouscumulativedemandareavailable.

*(0.025Ato20AatPF=1);fullaccuracyspecificationsaregivenintheNexus® 1450 Meter Installation and Operation Manual.

Measurement

VoltageL-N 0.04%ofreading

VoltageL-L 0.04%ofreading

Current 0.04%ofreading

NeutralCurrent 0.1%

Frequency 0.004Hz

Watts 0.06%ofreading

Watt-hour* 0.06%ofreading

VAR 0.15%ofreading

VARh 0.15%ofreading

VA 0.06%ofreading

PowerFactor 0.15%ofreading

THD 2.5%ofreading

EasilyConfigureAlmostanyTimeofUseUsageProfile

3

1800ShamesDrive,Westbury,NY115901-877-EIMETER(1-877-346-3837) Tel:516-334-0870Fax:516-338-4741Email:[email protected]

Electro Industries/GaugeTech™The Leader in Power Monitoring and Smart Grid Solutions™

E171702010918V.1.02

Ordering InformationNexus® Base

MeterControl Power

Frequency Range

Virtual Switch

Option Numbers:

Example: Nexus 1450 D2 60 V1

Nexus® 1450 Meter

D2Universal(96-276)V@50/60HzorDC

60 60Hz

V1StandardNexus®1450Meter512MBmemorylogging/

512s/c

D (18-60)VDC

50 50Hz

V2V1+1200MB

memorylogging/1024s/c

Specifications

Voltage Input Range:

• (20to720)VAC

• Pickupvoltage:5VAC

Isolation:

• VoltageInputsisolatedto2500VAC

Current Input Range:

• SupportsClass2andClass20inoneinputconfiguration

• ProgrammabletoanyCTratio

• Faultcurrentrecordingto+/-80Apeak

• Pick-upcurrent:1mA

Current Input Withstand Capability (at 23 °C):

• 100Afor10seconds

• 300Afor3seconds

• 500Afor1second

Burden:

• VoltageInputs:5Mohmspervoltageinput

• CurrentInputs:0.028VAperphasemaxat20A

Frequency Range:

• (42.5–69.5)Hz

Environmental:

• Operatingtemp:(-25to+70)°C

• Storagetemp:(-40to+70)°C

• Humidity:Upto95%RHnon-condensing

• ProtectionClass:IP30

Measurement Method:

• Upto1024samplespercycle(programmable)

• 16BitA/Dresolution–multiplesimultaneousconverters

• Multi-Gain™sensingmethod

• TrueRMS

Accuracy Ratings:

• Energymeasurementaccuracyat0.06%(0.025Ato20AatPF=1)

• FullaccuracyspecificationsavailableinNexus®1450meterUserManual

• Timeclock:3.5ppmfor(-25to+70)°C-lessthan10secondsdriftpermonthoncrystalsync;2.0ppmTypicalfrom0to+40°C-lessthan6secondspermonthdrift

Update Rate:

• 1Second-HighAccuracyreadings

• 1Cycle-FastUpdatereadings

• Customizablehigh-speedreadings-updateratefrom2to20cyclesRMS

Control Power Requirements:

• D2Option:(96-276)V@50/60HzorDC

• DOption:(18-60)VDC

• Burden:20VAmaxw/oI/Oordisplay;40VAmaxwithI/Oanddisplay

Communication:

• Baudrateupto115200bps

• Programmableparityandstopbits

• SerialCommunicationprotocols:ModbusASCII/RTU,DNP3.0

• Ethernet:ModbusTCP,DNP3.0,SNTP,HTTP,andHTTPS

• RJ45Ethernetport10/100BaseT

• FiberOpticport100BaseFX

• 4RS485ports

• RS232port(shared)

• RS485Serialportshave18VDCoutputforI/O

• OptionalP40N+displayoffersUSBTypeBcommunication

Shipping:

• Totalshippingweight:approx.5lbs(2.2kgs)

• Shippingcontainerdimensions:14"x10"x6"(35.6cmx25.4cmx15.2cm)

• DisplaysandI/Omodulesshipinseparatecontainers.

Compliance:

• EUDirective2014/32/EU(MeasuringInstrumentsDirective)

• EUDirective2011/65/EU(RoHS2Directive)

• REACHRegulation(EC)No1907/2006

• ULListed

• ANSIC12.1ElectricMetersCodeForElectricityMetering

• ANSIC12.20ElectricityMeters0.2and0.5AccuracyClasses

• ANSI(IEEE)C37.90.1(SurgeWithstand)

• ANSIC62.41(Burst)

• IEC60068-2-1EnvironmentalTesting:TestA:Cold

• IEC60068-2-2EnvironmentalTesting:TestB:DryHeat

• IEC60068-2-30EnvironmentalTesting:TestDb:Dampheat,cycle(12h+12hcycle)

• IEC61000-4-2Electromagneticcompat-ibility(EMC).Testingandmeasurementtechniques.Electrostaticdischargeimmunitytest

• IEC61000-4-3Electromagneticcompatibility(EMC).Radiated,radio-frequency,electromagneticfieldimmunitytest

• IEC61000-4-4Electricalfasttransient/burstimmunitytest

• IEC61000-4-5Surgeimmunitytest

• IEC61000-4-6Immunitytoconducted

disturbances,inducedbyradio-frequencyfields

• IEC61000-4-7Generalguideonharmonicsandinterharmonicmeasurementsandinstrumentation

• IEC61000-4-30Powerqualitymeasurementmethods

• IEC62052-11Generalrequirements,testsandtestconditions-Meteringequipment

• IEC62053-22ParticularRequirements-Staticmetersforactiveenergy(Classes0,2Sand0,5S)

• IEC62053-23,Staticmetersforreactiveenergy(Classes2and3)

• IEEE519RecommendedPracticesandRequirementsforHarmonicControlinElectricalPowerSystems

External I/O Modules:

• 1mAON4:4AnalogOutputs,0±1mA

• 1mAON8:8AnalogOutputs,0±1mA

• 20mAON4:4AnalogOutputs,4-20mA

• 20mAON8:8AnalogOutputs,4-20mA

• 8AI1:8AnalogInputs,0±1mA

• 8AI2:8AnalogInputs,4-20mA

• 8AI3:8AnalogInputs,0±5VDC

• 8AI4:8AnalogInputs,0±10VDC

• 4RO1:4RelayOutputs

• 4PO1:4SolidStatePulseOutputs

• 8DI1:8DigitalStatusInputs

• PSIO:PowerSupplyforupto4additionalI/Omodules

• MBIO:I/Omountingbracket(mustbeorderedwithexternalI/Omodule)

Note:PleaseseetheNexus® 1450 meter Installation and Operation Manualforcomprehensivespecifications.

AccessoriesSoftware

COMEXT4P1Y CommunicatorEXT4.0SoftwareforWindowsSingle-ComputerLicense(OneYear)

Displays

P40N+ P41N+ P43N+

MultifunctionLEDDisplay/MasterAmpDisplaySlaveWatt/VAR/PFDisplaySlave

I/O Modules

1mAON4 1mAON8 20mAON4 20mAON8 8AI1 8AI2 8AI3 8AI4 4RO1 4PO1 8DI1 PSIO *MBIO E171103

4AnalogOutputs,0±1mA8AnalogOutputs,0±1mA4AnalogOutputs,4-20mA8AnalogOutputs,4-20mA8AnalogInputs,0±1mA8AnalogInputs,4-20mA8AnalogInputs,0±5VDC8AnalogInputs,0±10VDC4RelayOutputs4SolidStatePulseOutputs8DigitalStatusInputsPowerSupplyforAdditionalI/OModulesI/OMountingBracketDINRailMountKitforNexus®1450meter

Accessories Note:*MustbeorderedwithanexternalI/Omodule.

-

-

-

-

-

-

Nexus® 1450 web page: