Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Electro Industries/GaugeTech™
The Leader in Power Monitoring and Smart Grid Solutions™
www.
electr
oind
.com
Metering and Communication
• MultilevelCyberSecureEncryptedConfiguration
• AdvancedWebServerwithWaveformAnalysisTools
• Upto1024SamplesperCycle-basedMeasurements
• 0.06%EnergyAccuracyOverWideDynamicMeasurementRange
• HighlyAccurateandStableMeasurementsUsingMulti-Gain™Sensing
• 6AvailableCommunicationPorts,IncludingModbusandDNP3.0Protocols
• TwoIndependentEthernetPorts,withUniqueIPAddressing
Advanced Power Quality Analysis
• ClassAIEC61000-4-30Edition3PowerQualityMeasurements
• IEC61000-4-15FlickerMeasurements
• IEC61000-4-7HarmonicMeasurements
• EN50160PowerQualityReports
• NewCORE™LoggingArchitecture
• Easy-installTransducerandSeparateDisplay
• DirectPhysicalRetrofittoNexus®125XSeriesMeter/TransducerwithGreaterFunctionality
• Separate3LineLEDDisplays
Nexus®1450 Cyber Secure Energy Panel Meter with Advanced Power Quality & Multiport Communication
Nexus® 1450 Meter P40N+ Remote Multifunction Display
NewNew
Introduction
ElectroIndustries’Nexus®1450meterisapowerfulenergymeterthatprovidesaccurateelectricalenergymeasurementsandoffersadvancedcapabilitiesforpowerqualityanalysisanddeterminingelectricalpowerreliability.Themeterisatransducerbasewithaseparatedisplay.ThetransducerbaseretrofitstoexistingElectroIndustries’Nexus®1250and1252meters.TheNexus®1450meterisidealforexistingswitchboardpanels,sinceitcanbeinstalledwithoutcuttingpaneldoors.Theseparatedisplaymountsintoexistinganalogmeterknockouts.
TheNexus®1450meterisprotectedwithamulti-levelCyberSecureconfigurationwith10highlysecureencrypteduserIDsandpasswordsthathelppreventtamperingandhackingofyourpowersystemdata.Themeter'sbuiltinWebView™EnergyDashboardallowsyoutoanalyzemeteringdatawithoutneedingsoftware.Youcannavigateeasilythroughmultiplewebpageviewsandgetdetailedinformationonenergyusageandpowerquality:viewrealtimedata,analyzestoredhistorylogs,viewalarmsandwaveformrecords.
With6simultaneouslyoperatingcommunicationports,themeterisacommunicationhubtomultiplesoftwaresystems.TheNexus®1450meterhas4serialportsthatspeakModbusandDNP3.0protocols.ItalsohastwoindependentEthernetports,consistingofa10/100BaseTcopperRJ45connectorandanSTTerminated100BaseFXFiberOpticEthernetport.EachEthernetporthasauniqueIPaddress.Throughthemeter's6ports,auserisabletocommunicatetomultiplecomputer-basedsystems,providingdatatoentitiesthroughoutanenterprise.
Themeteralsoexcelsatmeasuringpowerquality,includingwaveformrecordingandIEC61000-4-7,IEC61000-4-15,andIEC61000-4-30ClassAcompliance.TheNexus®1450meterletsyoulookatthereliabilityoftheelectricalpowercircuittodeterminecausesoffaults,voltagesurgesandsags,andharmonics.
Multi-Gain™ Sensing Provides Superior Accuracy
TheNexus®1450meterutilizesEIG’slatestmeasurement-sensingtechnology-Multi-Gain™.Multi-Gain™technologyusestwosensorsonthecurrentinputs-ahighgainsensorandalowergainsensor.Eachsensorsimultaneouslymeasuresthecurrentsignalcomingfromtheexternalcurrenttransformers.Themeter’sintelligentprocessinglooksatthesignallevelanddeterminestheoptimalsensingcircuitforthehighestaccuracymeasurement.Withthistechnique,themeterhas0.06%accuracythroughoutanextendedmeasurementrange,whichisadefiningtraitofNexus®Seriesmeters.
Themeter’sstandardpickuprangestartsaslowas1mA,andhighaccuracyisattainedat25mA.Multi-Gain™metrologyallowsthesamemetertobeusedonboth5Asecondaryand1AsecondaryCTs.Themetershouldmaintainhighaccuracymeasurementthroughoutitsinstalledlife.Refertotheaccuracychartonthenextpage,fordetails.
Multi-Gain™MetrologyallowstheNexus®1450metertohavehighlyrepeatableandstablemeasurementsthroughoutrange
Typicalaccuracycharts
2
Meter Accuracy Specification
Measurement
VoltageL-N 0.04%ofreading
VoltageL-L 0.04%ofreading
Current 0.04%ofreading
NeutralCurrent 0.1%
Frequency 0.004Hz
Watts 0.06%ofreading
Watt-hour* 0.06%ofreading
VAR 0.15%ofreading
VARh 0.15%ofreading
VA 0.06%ofreading
PowerFactor 0.15%ofreading
THD 2.5%ofreading Precision Crystal Time Reference: TheNexus®1450meterisequippedwithaninternalclockcrystalaccurateto3.5PPMoverthefulloperatingtemperaturerangeand5PPMatovertenyearsofuse.Thishighlyaccuratetrimmedclockdesignallowsuserstomaintainaccuratetimewhenrunningoncrystalsynchronization.Themeter'sclockcrystalwilldriftlessthan6secondspermonthfrom(0-40)°C.Additionaltimesyncmethodsinclude:
• Modbustimesync.
• DNP3.0timesync.
• IRIG-Btimesync.
• SNTPtimesync.
Advanced Energy Meter for Primary Loads
TheNexus®1450unitisanelectricalenergymeterdesignedtobeusedforanyimportantapplication.Inadditiontohighlyaccurateenergymeasurement,themeterfeatures:
• Full4quadrantmetering.
• Max/Minrecordingwithtimestamp.
• Extensiveloggingwith8logsofprogrammablehistoricalprofiles.
• Built-inCORE™logforwebtrending.
• TransformerandLineLosscompensation:forbothironandcopper,andtotalsubstationlosses.
• CTandPTcompensation:tocorrectinstrumenttransformererrors.
• Coincidentalreadings:e.g.,PForVARsattimeofPeakDemand.
• Loadaggregation/universalmetering:pulseinputscanbeusedtoaggregateoraccumulatedifferentloads.Utilitycommoditiessuchasgasandwatercanalsobeaccumulated.
On-board Time of Use Measurements:
TheNexus®1450meterusesaperpetualTimeofUse(TOU)calendarthatonlyneedstobesetuponce.TheTOUimplementationallowstheusertosetupmultipletariffstomeetanycontractualobligations.ItalsoallowstheusertocustomizeanyenergyparameterforTOU.The16availableTOUregisterscanbeconfigurednotonlyforTOUbuilt-inenergyreadings,butalsoforanystoreddatafrompulsesorotherreadingsthatneedTOUfunctionality.
• Uptofourseasons-seasonscanbecustomized.
• Flexiblebillingperiods/rates/holidays/schedulessetup.
• Cumulativeandcontinuouscumulativedemandareavailable.
*(0.025Ato20AatPF=1);fullaccuracyspecificationsaregivenintheNexus® 1450 Meter Installation and Operation Manual.
Measurement
VoltageL-N 0.04%ofreading
VoltageL-L 0.04%ofreading
Current 0.04%ofreading
NeutralCurrent 0.1%
Frequency 0.004Hz
Watts 0.06%ofreading
Watt-hour* 0.06%ofreading
VAR 0.15%ofreading
VARh 0.15%ofreading
VA 0.06%ofreading
PowerFactor 0.15%ofreading
THD 2.5%ofreading
EasilyConfigureAlmostanyTimeofUseUsageProfile
3
1800ShamesDrive,Westbury,NY115901-877-EIMETER(1-877-346-3837) Tel:516-334-0870Fax:516-338-4741Email:[email protected]
Electro Industries/GaugeTech™The Leader in Power Monitoring and Smart Grid Solutions™
E171702010918V.1.02
Ordering InformationNexus® Base
MeterControl Power
Frequency Range
Virtual Switch
Option Numbers:
Example: Nexus 1450 D2 60 V1
Nexus® 1450 Meter
D2Universal(96-276)V@50/60HzorDC
60 60Hz
V1StandardNexus®1450Meter512MBmemorylogging/
512s/c
D (18-60)VDC
50 50Hz
V2V1+1200MB
memorylogging/1024s/c
Specifications
Voltage Input Range:
• (20to720)VAC
• Pickupvoltage:5VAC
Isolation:
• VoltageInputsisolatedto2500VAC
Current Input Range:
• SupportsClass2andClass20inoneinputconfiguration
• ProgrammabletoanyCTratio
• Faultcurrentrecordingto+/-80Apeak
• Pick-upcurrent:1mA
Current Input Withstand Capability (at 23 °C):
• 100Afor10seconds
• 300Afor3seconds
• 500Afor1second
Burden:
• VoltageInputs:5Mohmspervoltageinput
• CurrentInputs:0.028VAperphasemaxat20A
Frequency Range:
• (42.5–69.5)Hz
Environmental:
• Operatingtemp:(-25to+70)°C
• Storagetemp:(-40to+70)°C
• Humidity:Upto95%RHnon-condensing
• ProtectionClass:IP30
Measurement Method:
• Upto1024samplespercycle(programmable)
• 16BitA/Dresolution–multiplesimultaneousconverters
• Multi-Gain™sensingmethod
• TrueRMS
Accuracy Ratings:
• Energymeasurementaccuracyat0.06%(0.025Ato20AatPF=1)
• FullaccuracyspecificationsavailableinNexus®1450meterUserManual
• Timeclock:3.5ppmfor(-25to+70)°C-lessthan10secondsdriftpermonthoncrystalsync;2.0ppmTypicalfrom0to+40°C-lessthan6secondspermonthdrift
Update Rate:
• 1Second-HighAccuracyreadings
• 1Cycle-FastUpdatereadings
• Customizablehigh-speedreadings-updateratefrom2to20cyclesRMS
Control Power Requirements:
• D2Option:(96-276)V@50/60HzorDC
• DOption:(18-60)VDC
• Burden:20VAmaxw/oI/Oordisplay;40VAmaxwithI/Oanddisplay
Communication:
• Baudrateupto115200bps
• Programmableparityandstopbits
• SerialCommunicationprotocols:ModbusASCII/RTU,DNP3.0
• Ethernet:ModbusTCP,DNP3.0,SNTP,HTTP,andHTTPS
• RJ45Ethernetport10/100BaseT
• FiberOpticport100BaseFX
• 4RS485ports
• RS232port(shared)
• RS485Serialportshave18VDCoutputforI/O
• OptionalP40N+displayoffersUSBTypeBcommunication
Shipping:
• Totalshippingweight:approx.5lbs(2.2kgs)
• Shippingcontainerdimensions:14"x10"x6"(35.6cmx25.4cmx15.2cm)
• DisplaysandI/Omodulesshipinseparatecontainers.
Compliance:
• EUDirective2014/32/EU(MeasuringInstrumentsDirective)
• EUDirective2011/65/EU(RoHS2Directive)
• REACHRegulation(EC)No1907/2006
• ULListed
• ANSIC12.1ElectricMetersCodeForElectricityMetering
• ANSIC12.20ElectricityMeters0.2and0.5AccuracyClasses
• ANSI(IEEE)C37.90.1(SurgeWithstand)
• ANSIC62.41(Burst)
• IEC60068-2-1EnvironmentalTesting:TestA:Cold
• IEC60068-2-2EnvironmentalTesting:TestB:DryHeat
• IEC60068-2-30EnvironmentalTesting:TestDb:Dampheat,cycle(12h+12hcycle)
• IEC61000-4-2Electromagneticcompat-ibility(EMC).Testingandmeasurementtechniques.Electrostaticdischargeimmunitytest
• IEC61000-4-3Electromagneticcompatibility(EMC).Radiated,radio-frequency,electromagneticfieldimmunitytest
• IEC61000-4-4Electricalfasttransient/burstimmunitytest
• IEC61000-4-5Surgeimmunitytest
• IEC61000-4-6Immunitytoconducted
disturbances,inducedbyradio-frequencyfields
• IEC61000-4-7Generalguideonharmonicsandinterharmonicmeasurementsandinstrumentation
• IEC61000-4-30Powerqualitymeasurementmethods
• IEC62052-11Generalrequirements,testsandtestconditions-Meteringequipment
• IEC62053-22ParticularRequirements-Staticmetersforactiveenergy(Classes0,2Sand0,5S)
• IEC62053-23,Staticmetersforreactiveenergy(Classes2and3)
• IEEE519RecommendedPracticesandRequirementsforHarmonicControlinElectricalPowerSystems
External I/O Modules:
• 1mAON4:4AnalogOutputs,0±1mA
• 1mAON8:8AnalogOutputs,0±1mA
• 20mAON4:4AnalogOutputs,4-20mA
• 20mAON8:8AnalogOutputs,4-20mA
• 8AI1:8AnalogInputs,0±1mA
• 8AI2:8AnalogInputs,4-20mA
• 8AI3:8AnalogInputs,0±5VDC
• 8AI4:8AnalogInputs,0±10VDC
• 4RO1:4RelayOutputs
• 4PO1:4SolidStatePulseOutputs
• 8DI1:8DigitalStatusInputs
• PSIO:PowerSupplyforupto4additionalI/Omodules
• MBIO:I/Omountingbracket(mustbeorderedwithexternalI/Omodule)
Note:PleaseseetheNexus® 1450 meter Installation and Operation Manualforcomprehensivespecifications.
AccessoriesSoftware
COMEXT4P1Y CommunicatorEXT4.0SoftwareforWindowsSingle-ComputerLicense(OneYear)
Displays
P40N+ P41N+ P43N+
MultifunctionLEDDisplay/MasterAmpDisplaySlaveWatt/VAR/PFDisplaySlave
I/O Modules
1mAON4 1mAON8 20mAON4 20mAON8 8AI1 8AI2 8AI3 8AI4 4RO1 4PO1 8DI1 PSIO *MBIO E171103
4AnalogOutputs,0±1mA8AnalogOutputs,0±1mA4AnalogOutputs,4-20mA8AnalogOutputs,4-20mA8AnalogInputs,0±1mA8AnalogInputs,4-20mA8AnalogInputs,0±5VDC8AnalogInputs,0±10VDC4RelayOutputs4SolidStatePulseOutputs8DigitalStatusInputsPowerSupplyforAdditionalI/OModulesI/OMountingBracketDINRailMountKitforNexus®1450meter
Accessories Note:*MustbeorderedwithanexternalI/Omodule.
-
-
-
-
-
-
Nexus® 1450 web page: