Mini-Link Troubleshooting and Power Analysis.pdf

Embed Size (px)

Citation preview

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    1/68

    PAGE 1

    Copyright

    Copyright Task Force Managed Services EID

    Disclaimer

    No part of this document may be reproduced in any form without the written permission ofthe copyright owner.

    Content

    1 Abstract ..........................................................................................2

    1.1 Task Force Output...........................................................................3

    2 Guideline on Trouble Shooting of MINI-LINK Equipment ..........4

    2.1 Prerequisite......................................................................................5

    2.2 Preparation ......................................................................................6

    2.3 TOC .................................................................................................8

    3 Guideline on Trouble Shooting of Power Related Problem ....27

    3.1 Prerequisite....................................................................................28

    3.2 Preparation ....................................................................................29

    3.3 TOC ...............................................................................................31

    4 Enclosure .....................................................................................58

    4.1 Transmission AND RBS Data Report............................................59

    4.2 Power Data Report ........................................................................63

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    2/68

    PAGE 2

    ABSTRACT

    After analysis of trouble ticket trend for over 6 months, Managed Services deliveryteam notices a pattern of recurring problem related to MINI-LINK and power relatedissue.

    In an effort to reduce the recurring problem, a task force focusing on the issueswere set up, with a goal to find the root cause of the recurring problem.

    The type of MINI-LINK recurring problem that were focused on included:

    NPU hanging (stuck in boot process) for AMM 2p B

    RSL with measurement of -20dBPerformance degrading on sites with antenna over 1.2mHigh temperature leading to MINILINK software hanging in TN R2

    Power related problem investigation was focused circuit breaker (MCB) trippingdue to:Unbalanced power consumptionInsufficient commercial power capacityLow voltage from commercial powerPhase failure

    As an outcome of the investigation, this document is produced as a guideline tohelp field maintenance technicians & engineers for troubleshooting similar problem

    Ericsson official documentation for MINI-LINK operational and maintenanceguideline should always be the main reference for any operational activities. Thisdocument is to be used specific for the problem described above.

    1

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    3/68

    PAGE 3

    1.1 Task Force Output

    DOWNTIME CONTRIBUTOR

    8,835 in December (1044 less compared to November)920 less power related problem; due to battery replacement, faster response onRST alarm

    144 less problem for other issue, mainly transmission, MCB trip cases; due totask force activity that focused on recurring transmission problem and MCB tripcases

    TT Type: December 2009

    Pow er Outage,

    7982, 91%

    Access Issue,

    34, 0%

    RNC, 1, 0%

    Lease Line, 22,

    0%

    Transmission,

    157, 2%

    BTS, 210, 2%

    CME, 308, 4%

    Power Outage CM E 3rd Party Pro ject

    BSC Others Transmission BTS

    NODE-B Access Issue RNC Lease Line

    0.367%

    0.395%

    0.440%

    0.590%

    0.531%

    0.704%

    0.504%

    1.086%

    0.228%

    0.557%

    0.150%

    0.791%

    0.575%

    0.442%

    0.290%

    0.634%

    0.292%

    0.654%

    0.589%

    0.426%

    0.372%

    0.473%

    0.213%

    0.572%

    0.000%

    0.200%

    0.400%

    0.600%

    0.800%

    1.000%

    1.200%

    1.400%

    1.600%

    Wk

    43

    Wk

    44

    Wk

    45

    Wk

    46

    Wk

    47

    Wk

    48

    Wk

    49

    Wk

    50

    Wk

    51

    Wk

    52

    Wk

    53

    Wk 1

    Downtime contributor

    % - EID % - External

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    4/68

    PAGE 4

    Guideline on Trouble shooting of MINI-LINKEquipment

    2

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    5/68

    PAGE 5

    2.1 PREREQUISITES

    This chapter describes the hardware tools & software programs that are neededwhen trouble shooting shall be done for MINI-LINK equipments. Engineer alwaysneeded to bring the right tools for working with troubleshooting on sites. Pleasedo not forget to prepare the required sites permit and necessary coordination tomake sure our activities on sites will be done smoothly.

    Tools that are needed:

    a. Notebook and accessories cables (USB, Ethernet, and RS232).

    b. MSS (MINI-LINK Service Software) installed in the notebook.

    c. Correct SW version for all equipment if upgrades are necessary (include

    the latest software baseline).

    d. Basic Tools: digital Volt-meter, LED, screw-driver sets, DDF punch tools,wrist-stripe, etc

    e. HSE Tools

    f. If required, always bring BER meter for checking E1 / STM-1 performance.

    g. If needed, always bring HW spares (Ex MMU, TRU, NPU, RAU anddummy) that might need to be replaced.

    h. If needed, always bring RAU connectors, electrical insulating tape, butylsealing compound for water protect the RAU connector/cable.

    Access Permit & Coordination procedures that are needed;

    a. Working permit and site key access.

    b. Customer approval for equipment down time if needed

    c. Always Coordinate with Customer NOC / OMC

    d. Approvals from NOC before and after enter the site.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    6/68

    PAGE 6

    2.2 PREPARATION

    Considering most of trouble-shootings will be done on existing (with live traffic)sites, we should follow our Network Interruption process.

    Picture 1 Network Interruption process

    Prepare

    Request Form

    to Enter

    Customer Site

    Information on the request form (Day H)

    1.Site name2.SOW activity on site

    3.Person in charge From EID organzation4.Site access (related with the request for Key

    arrangement and Supervisor from Customer)

    5. Time frame of the activity

    The Form send toCustomer for

    approval1.Customer give approval by signing the

    request form (Day H+1)

    Engineer Received

    Key and information

    on PIC fromCustomer Spv

    All data

    approved byCustomer

    Revisedataonthe

    form

    No

    Yes

    Engineer

    arrived on site

    Anything

    Unusual on

    Site

    Before enter the site

    Call OMC

    1.Identify yourself to OMC and Gave information regardingthe task

    2. Ask if Site has alarm or not

    3.Show / give the letter of assignement ot the spv of the

    sites if one exist .Such as IBS (in building solution )site

    Call /report to

    OMC

    1. Check Sorrounding of the site for anything unusual

    Such as Grounding missing;Fence broken etc.

    2..Check Inside the shelter , Save alarm or status of the

    RBS related to Engineers work

    3.Take Foto for unusual conditional

    Engineer doingthe Activity

    Engineer

    completing the

    activity+ Clean Up

    site

    Call OMCbefore left the

    sites

    1. Make sure that the site is clean

    2. Make sure the RBS status has the sama or less alarm

    status compare before engineer enter the shelter

    Give notification to OMC that you already completed theactivity on related site

    Confirmation on the status site from OMC

    Return Sheter Keyto Custome by

    filling the report

    end

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    7/68

    PAGE 7

    General key-points before starting our trouble-shooting main activities:

    a. Inform Customer NOC team about our activity on site, especially if traffic

    interruption will be done, before and after our activity.b. Check surrounding condition if any Unusual Condition found, such as;

    Grounding missing, broken KWH, abnormal indoor temperature, etc.If needed, take capture / picture as evidences and inform to NOC Team.

    c. Check Physical condition of ML equipments especially for LED Status andInput DC voltage

    If we found RED Light or strange Status, check details by LCT forverification, and take/save Capture & Logs.For more information, see LED Descriptions MINI-LINK TNOperating Instructions,Reference [4]

    Measure the Input Vdc using a Digital Voltmeter, and compare it withthe specification

    Never Turn-Off / Reset the ML equipments before verifying and takingrequired information.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    8/68

    PAGE 8

    2.3 Table of Content

    1 Troubleshooting Procedure ......................................................9

    1.1 Received Alarm / Fault Description.............................................. 9

    1.2 Troubleshooting MLTN............................................................... 10

    1.2.1 SW troubleshooting MLTN ......................................................... 10

    1.2.2 Data Collection MLTN ................................................................ 11

    1.3 Troubleshooting MLHC .............................................................. 11

    1.3.1 SW troubleshooting MLHC on site ............................................. 11

    1.3.2 Data Collection MLHC................................................................ 12

    1.4 Hardware Installation Check ...................................................... 12

    2 Example problem found in Transmission ..............................13

    2.1 Hardware Faulty......................................................................... 13

    2.1.1 RAU with RSL 20 dBm............................................................ 13

    2.1.2 AMM 2p B faulty......................................................................... 14

    2.2 Low RSL..................................................................................... 15

    2.3 Switching 1+1 HS failed (MMU2 D)............................................ 18

    2.4 HCC/RCC Alarm ........................................................................ 20

    3 Problem analysis & Escalation Process ................................23

    4 Replacement Faulty Module....................................................24

    5 Clos ing Preparat ion .................................................................25

    6 Reporting ..................................................................................25

    7 Reference..................................................................................26

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    9/68

    PAGE 9

    1. TROUBLESHOOTING PROCEDURE

    Please follow our general Technical Trouble-shootingprocess:

    Picture 2 General trouble-shooting process

    1.1 Received Alarm / Fault Descript ion

    The receiver alarm / fault description should include details about the following:

    a. Exact date and time of the problem.The time shall be given in relation with the time setting in the affectedNEs.

    b. Effect of the problem.Explain the fault events as they occurred, step by step. Specify slotpositions when applicable.

    c. Events that might have lead to the fault.

    d. Frequency of the fault.e. Software Baseline (SBL) running on the NE when the fault occurred.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    10/68

    PAGE 10

    1.2 Troubleshooting of MLTN

    1.2.1 SW Troubleshooting MLTN on site

    Please follow below procedure of trouble-shooting MLTN:

    a. Connect to the MLTN (using Ethernet or USB cable)

    b. Check the event / alarms / fault to evaluate what the problem is

    See more details information in documents of:

    Fault Management Operations MINI-LINK TN ETSI, Reference [6]

    Alarm Descriptions MINI-LINK TN ETSI Description, Reference [7]

    Event Descriptions MINI-LINK TN ETSI Description, Reference [8]

    c. Verifying Radio Link Configuration ParametersVerify that all hop setup parameters are set and correspond to the value inSID / PQR, such as: RSL (Received Signal Level), Tx power, Switching

    mode, Frequency setting, etc.d. Checking for RF Interference

    If the Radio Link reports unexpectedly bad BER performance but RF inputlevel is normal, the receiver might be interfered by external RF sources.Check RF interference using Far-end Tx-off procedure.

    e. Use a loop on the unit that having problem to trace the fault (i.e.: RF Loop,IF Loop, etc).

    f. Use built-in BERT (Bit Error Ratio Tester) or external BER meter to verifyor trace the fault.

    g. Restarting the NE (Network Element)In some cases, if required, we can do a Warm or Cold Restart of the NE.

    A cold restart w il l d isturb the traff ic .

    Always col lect Logs before restart ing the NE since the alarm andevent logs, as well as power cycling information, are deleted atboth cold and warm restarts and potentially valuable information islost.

    h. Take capture of specific problems.

    i. Check and (if required) perform SW upgrade if its an older SW-baselineversion.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    11/68

    PAGE 11

    The SW version should be checked with O&M to synchronize that theMINI-LINK has the same SW baseline in all MLTN.

    Please perform a software upgrade to the new software baseline accordingto the MINI-LINK TN ETSI Operating Instruction, Reference [2] or MINI-LINK Craft User Interface Descriptions, Reference [3], chapter SoftwareUpgrade.

    For details about recommended upgrade paths of MLTN, please also seethe Compatibility Information and Release Note documents.

    1.2.2 Data Collection MLTN

    Take following data from MLTN terminals for any further technical analysis orescalation:

    a. Error log file and Event log / historyAlways collect alarm logs and event log before any warm/cold restart orpower cycling.

    b. Alarm list (needs to be done before power reset)

    c. Get the configuration file and saved report if you dont have the latest file

    d. Collect PM (Performance Management) data if PDH/SDH MMUs is used(Near & Far end)

    1.3 Troubleshooting of MLHC

    1.3.1 SW Troubleshooting MLHC on site

    Please follow below procedure of trouble-shooting MLHC:

    a. Connect to the MLHC (using Ethernet or Serial OM cable)

    b. Take Capture of existing parameters needed and Save Configuration forbackup purposes

    c. Check the alarms to evaluate what the problem is.

    d. Always upload the Alarm logs of MLHC

    e. Verifying Radio Link Configuration Parameters refer to SID / PQR

    f. Checking for RF Interference

    g. Use loops to trace were the problem is (example : RF Loop, IF Loop, SPILoop)

    h. If necessary, use external BER meter to verify or trace the fault.

    i. Always take capture of specific problems.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    12/68

    PAGE 12

    j. Make a save before any power cycling.

    Note: If you have not save before power cycle and you have made

    any changes the

    TRU will go back to the latest saved configuration.

    k. Perform SW upgrade if its an older SW version. This should be checkedfrom the O&M what version that shall be used.

    1.3.2 Data Collection MLHC

    Take following data from MLHC terminals for any further technical analysis andescalation:

    a. Alarm logs from (Near-end and Far-end). Needs to be collected beforepower reset.

    b. Performance log (monitoring data) from Near-end and Far-end.

    If performance data is not available, follow the performance setup inas document of Settings for performance measurements in Mini-LinkHigh Capacity, Reference [13]

    c. Inventory data (Near-end and Far-end)

    d. Configuration file

    1.4 Hardware Installation CheckAside checking the software status, in some conditions we need to check physicalinstallation also:

    a. FAN unit correctly installed on MLTN / MLHC.

    b. Dummy fronts installed (MLTN).

    c. Grounding completely & properly installed according to the installationmanuals

    d. Traffic and DC Cabling/Connectors properly installed.

    See more details in document of Installing Indoor Equipment MINI-LINK TNETSI Installation Instructions, Reference [1].

    e. Radio cable and the connectors properly installed.(See more details in document of Radio Cable Check[13].

    f. All connectors tightened (DC/traffic/radio)

    g. Check power distribution (battery, DC power level and MCB Ampere).

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    13/68

    PAGE 13

    h. Modem units correctly inserted and tightened

    i. If the problem is still intermittent, check interfaces on front and thebackplanes for broken or damage pins

    2. Example Problem found in Transmission

    2.1 Hardware Faulty

    2.2 Low RSL

    2.3 Switching 1+1 HS failed (MMU2 D)

    2.4 HCC/RCC Alarm

    2.1 Hardware Faulty

    2.1.1 RAU wi th RSL -20 dBm

    In the Radio Link Alarm, we found the RSL of the RAU is 20 dBm. In 1+1 HSconfiguration, sometimes the switch can not work caused by this problem. There isa known problem with a component handling the attenuation on the RAU.

    The following steps must follow to solve the problem;

    1. Prepare RAU with same product code.

    2. Unplug jumper cable on MMU.

    3. Replacement RAU with the new one.

    4. Plug jumper Cable onto MMU.

    5. Reset Performance in Near End and Far End

    6. Send the RAU to Ware House with BLUE TAG FORM.

    Note: Write in Remark Column; RAU faulty with RSL 20 dBm.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    14/68

    PAGE 14

    2.1.2 AMM 2p B Faulty

    AMM 2p B faulty with problem NPU stuck in Boot Process. There is a knownproblem with a bad soldering of the component in the backplane. The Fault LED inNPU was ON.

    The following steps must follow to solve this problem;

    1. Prepare new AMM 2p B

    2. Turn off DC Source. Unplug DC cable from AMM 2p B (faulty).

    3. Unplug some modules from AMM 2p B: NPU3, MMU and FAU4.

    4. Uninstall AMM 2p B (faulty).

    5. Install new AMM 2p B.

    6. Plug in some modules into new AMM 2p B: NPU3, MMU and FAU4.

    7. Plug in DC Cable to AMM 2p B.

    8. Turn ON DC Source then pressing the BR button of NPU (2-3 secondsafter Turn ON DC source).

    9. The LED BR in the NPU will flash. It means, the NPU in Installation modestatus.

    10. Log in to ML TN with your laptop.

    11. Activate the configuration from RMM card.

    12. If AMM 2p B does not have RMM, You have to activate configuration withLOAD CONFIGURATION FILE from your laptop.

    13. Otherwise, you should create configuration by manually.

    14. Call NOC to check the status of our equipment (RBS and Transmission).

    15. Send AMM 2p B to ware house with BLUE TAG FORM.

    Note: Write in remark column; AMM faulty with problem NPU stuck in BootProcess.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    15/68

    PAGE 15

    2.2 Low RSL

    Low RSL can cause performance degradation in our link. The RSL of the Linkhave to follow the value from the PQR. The tolerance value is +- 4 dB fromPQR. Otherwise we have to realignment the antenna to get expected RSL or

    reroute the link if the link get obstacle path.

    Sometime, Low RSL can happened cause by shifted antenna especially forantenna over than 1.2 m which do not have properly for side strut installation ofantenna. Please see picture below;

    Picture 3 Improperly side strut installation on Tower

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    16/68

    PAGE 16

    Picture 4 Improperly side strut installation on Pole

    The following steps must follow to solve this problem (Low RSL caused byShifted antenna);

    1. We have to make sure position of antenna in NE and FE site canallow installation side strut with the right way. Please see picturebelow ;

    Picture 5 Proper angle for attaching the side strut

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    17/68

    PAGE 17

    2. If needed we have to reinstall antenna on NE and FE;

    a. Change leg of tower for attaching antenna

    b. Change handle of antenna from right to left side or vice

    versa.

    3. If antenna attaching in pole we need install additional mounting forattaching side strut.

    4. Then realignment antenna to get expected RSL (PQR).

    5. Install side strut refer from standard installation document.

    6. Coordination to NOC to check our equipment status.

    Note: For above activity, it shall cause traffic disturbance for 4 5 hours. So, please make coordination with thecustomer for permit activity.

    Please see the picture below for properly side strut installation;

    Picture 6 Properly side strut installation on tower

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    18/68

    PAGE 18

    Picture 7 Properly side strut installation on pole

    2.3 Switching 1+1 HS failed (MMU2 D)

    When the RAU N has used for MMU2 D, The switching protection in 1+1HS does not work. It is caused by software compatibility in the RAU N.

    Note: If using RAU N with MMU2 D, software of RAU have to over thanR2X.

    The following steps must follow to solve this problem;

    1. Log in to ML TN

    2. Go to the inventory Tab then Check software of the RAU N in NEand FE.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    19/68

    PAGE 19

    Picture 8 RAU Software in inventory list

    Note: RAU in Slot 4 is OK, over than R2XRAU in Slot 5 is not OK, below than R2X

    3. Upgrade software for RAU N with Software RAU over than R2X,example R3C.

    4. Testing switch protection to verify the switch is working.

    5. Coordination with NOC to check our equipment status.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    20/68

    PAGE 20

    2.4 HCC/RCC Alarm

    HCC Alarm means communication is lost on Hop Communication Channel,between MMU and far-end MMU.

    RCC Alarm means Communication is lost on the Radio CommunicationChannel (RCC), between MMU and RAU.

    Those problems were caused by bad connection between MMU and RAU or themodules are fault.

    Picture 9 Radio Link Alarm

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    21/68

    PAGE 21

    Picture 10 Alarm List

    The following steps must follow to solve this problem;

    1. Log In to ML TN.

    2. Go to Radio Link Alarm Tab then found which slot have problem RCC.

    3. Check installation of connector coaxial at near end and far end.

    4. If needed, reinstall connector coaxial with the right way.

    5. Coordination with NOC to check our equipment status.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    22/68

    PAGE 22

    Please see the picture below for bad installation;

    Picture 11 Coaxial connector withoutfold grounding cable and2.5mm of the dielectric

    Picture 12 Coaxial connector without 2.5mm jacket isolation of dielectric

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    23/68

    PAGE 23

    Please see the picture below for good installation;

    Picture 13 GOOD installation

    3. PROBLEM ANALYSIS & ESCALATION PROCESS

    After getting enough information from sites, we need to analyze it to get the

    correct solution.

    Please always refer to:

    a. Ericsson Mini-Link technical documentations.

    Some of those as listed in the Reference chapter at page 11, or more

    complete documents in Alex / Ericsson CPI documents.

    b. Check to the previous applicable technical report.

    The purpose is to minimize our trouble-shooting duration. Search any

    similar and applicable report that can be reused in our problem. We can

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    24/68

    PAGE 24

    get those from previous Trouble-shooting Report, CSR report, Service

    Advice document, as well as some sharing experiences in Ericsson

    Knowledge Based.

    In case of internal team can not solve the problem, especially which related with

    competence and product issue, we can escalate it to higher level support.

    Any escalation to 1stor 2

    ndline support will need a CSR (Customer Support

    Request). A CSR is primarily used in situations of a non-emergency nature,

    indicating a software or hardware design-related problem. It is also used to ask

    general questions of a technical nature. An emergency request is normally

    taken care of in another routine, but it is always registered as a CSR afterwards

    for follow-up reasons. Usually, only one issue can be addressed per CSR.

    We shall enclose relevant and complete troubleshooting data shall in the CSR

    as the required procedure. See Data Collection Guidelines MLTN Operating

    Directions, Reference [5].

    4. REPLACEMENT FAULTY MODULE

    In case there is/are faulty module/s found based on the fault tracing phase, we

    can replace that plug-in unit/s accordingly. Please take below precaution and

    procedure carefully:

    a. Identifying Current Hardware and Software

    b. Checking the Compatibility

    c. Uploading Configuration File when Replacing a NPU or RMM

    d. Required Tools and Equipment

    e. Prepare for Software Upgrade: FTP server and SBL firmware

    f. Procedure to replace the Hardware module

    g. Concluding Routines of checking any active alarms, handling faulty unit,

    etc

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    25/68

    PAGE 25

    See details in Replacing a Radio or Plug-In Unit MLTN Operating Instruction,

    Reference [11]

    5. CLOSING PREPARATION

    After activities had been done, ensure that the following actions have beenperformed:

    a. Reset Performance Log (if needed to monitor performance link for fewdays)

    b. Reset alarm list and Event history (if needed to monitor performancelink for a few days)

    c. Inform customer NOC team that our activity had been done.

    d. Get confirmation from NOC that all equipments are back to normaloperation and there are no active alarms caused by our activity.

    e. Clean up the site for any trashes from our activity.

    f. Lock all doors and leave the site.

    6. REPORTING

    After activities had been done, spare your time to make report to yoursupervisor such as;

    a. Create a Troubleshooting Report.

    b. Complete raw data (alarm list, even log, error log, save report and anycapture) as evidence.

    c. Collect Photo as evidence (if required).

    d. Fill BLUE TAG Form for any HW Faulty and send to the ware house.

    e. Please fill-in completely as described in HWS RDN (Repair deliveryNote), Reference [12]

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    26/68

    PAGE 26

    7. REFERENCE

    [1] Indoor Installation Instruction Mini-link TN ETSI, 1531-CSH 109 32/1-S1 Uen

    [2] Operating Instruction Mini-link TN R3, 1543-CSH 109 32/1-V1 Uen

    [3] MINI-LINK Craft User Interface Descriptions, ML Craft 2.2, 7/1551-CSH 109 32/1-V1Uen

    [4] LED Description MINI-LINK TN ETSI, 24/1543-CSH 109 32/1-V1 Uen

    [5] Data Collection Guidelines MLTN Operating Directions, 34/1543-CSH 109 32/1-V1Uen

    [6] Fault Management Operations MINI-LINK TN ETSI, 4/1543-CSH 109 32/1-V1 Uen

    [7] Alarm Descriptions MINI-LINK TN ETSI Description, 5/1543-CSH 109 32/1-V1 Uen

    [8] Event Descriptions MINI-LINK TN ETSI Description, 9/1551-CSH 109 32/1-V1 Uen

    [9] Troubleshooting MINI-LINK TN ETSI Operating Guideline, 5/154 43-CSH 109 32/1-V1Uen

    [10] Troubleshooting Guideline by EID/OP/MR Ronny Stralhed

    [11] Replacing a Radio or Plug-In Unit MLTN Operating Instruction, 11/1543-CSH 10932/1-V1 Uen

    [12] HWS RDN (Repair delivery Note), 2/1546-FAP 130 495 Uen

    [13] Settings for performance measurements in Mini-Link HC, EAB/FBM/LG-07:001 Uen

    [14] Radio Cable Check by MO/EAB/JT/GG EMWCRM

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    27/68

    PAGE 27

    Guideline on Trouble Shooting of Power RelatedProblem

    3

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    28/68

    PAGE 28

    3.1 PREREQUISITES

    This chapter describes the hardware tools & software programs that are neededwhen trouble shooting shall be done for MINI-LINK equipments. Engineer alwaysneeded to bring the right tools for working with troubleshooting on sites. Please donot forget to prepare the required sites permit and necessary coordination to makesure our activities on sites will be done smoothly.

    Tools that are needed:

    a. Notebook and accessories cables (USB, Ethernet, and RS232).

    b. Correct SW version for all equipment if upgrades are necessary (includethe latest software baseline).

    c. Basic Tools: digital Volt-meter, LED, screw-driver sets, DDF punch tools, ,

    etc

    d. HSE Tools

    e. If needed, always bring HW spares (power & grounding cable, MCB etc a)that might need to be replaced.

    Access Permit & Coordination procedures that are needed;

    a. Working permit and site key access.

    b. Customer approval for equipment down time if needed

    c. Always Coordinate with Customer NOC / OMC

    d. Approval from NOC before & after enter site

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    29/68

    PAGE 29

    3.2 PREPARATION

    Considering most of trouble-shootings will be done on existing (with live traffic)sites, we should follow our Network Interruption process.

    Picture 1 Network Interruption process

    Prepare

    Request Form

    to Enter

    Customer Site

    Information on the request form (Day H)

    1.Site name2.SOW activity on site

    3.Person in charge From EID organzation4.Site access (related with the request for Key

    arrangement and Supervisor from Customer)

    5. Time frame of the activity

    The Form send toCustomer for

    approval1.Customer give approval by signing the

    request form (Day H+1)

    Engineer Received

    Key and information

    on PIC fromCustomer Spv

    All data

    approved byCustomer

    Revisedataonthe

    form

    No

    Yes

    Engineer

    arrived on site

    Anything

    Unusual on

    Site

    Before enter the site

    Call OMC

    1.Identify yourself to OMC and Gave information regardingthe task

    2. Ask if Site has alarm or not

    3.Show / give the letter of assignement ot the spv of the

    sites if one exist .Such as IBS (in building solution )site

    Call /report to

    OMC

    1. Check Sorrounding of the site for anything unusual

    Such as Grounding missing;Fence broken etc.

    2..Check Inside the shelter , Save alarm or status of the

    RBS related to Engineers work

    3.Take Foto for unusual conditional

    Engineer doingthe Activity

    Engineer

    completing the

    activity+ Clean Up

    site

    Call OMCbefore left the

    sites

    1. Make sure that the site is clean

    2. Make sure the RBS status has the sama or less alarm

    status compare before engineer enter the shelter

    Give notification to OMC that you already completed theactivity on related site

    Confirmation on the status site from OMC

    Return Sheter Keyto Custome by

    filling the report

    end

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    30/68

    PAGE 30

    General key-points before starting our trouble-shooting main activities:

    a. Inform Customer NOC team about our activity on site, especially if traffic

    interruption will be done, before and after our activity.b. Check surrounding condition if any Unusual Condition found, such as;

    Grounding missing, broken KWH, abnormal indoor temperature, etc.If needed, take capture / picture as evidences and inform to NOC Team.

    c. Check Physical condition of ML equipments especially for LED Status andInput DC voltage

    If we found RED Light or strange Status, check details by LCT forverification, and take/save Capture & Logs.For more information, see LED Descriptions MINI-LINK TNOperating Instructions,Reference [4]

    Measure the Input Vdc using a Digital Voltmeter, and compare it withthe specification

    Never Turn-Off / Reset the ML equipments before verifying and takingrequired information.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    31/68

    PAGE 31

    3.3 Table of Content

    1 Mini Circuit Breaker (MCB).................................................................32

    1.1 Definition MCB.......................................................................................32

    1.1.1 PLN MCB...............................................................................................32

    1.1.2 ACPDB MCB .........................................................................................33

    1.1.2.1 Main MCB ACPDB ................................................................................33

    1.1.2.2 Utility MCB ACPDB ...............................................................................33

    1.1.3 DCPDB MCB.........................................................................................34

    1.1.3.1 Main MCB Rectifier................................................................................34

    1.1.3.2 Utility MCB Rectifier / PBC 6500...........................................................34

    1.1.3.3 Battery MCB Rectifier............................................................................35

    1.1.3.4 19 Rack MCB / DCPDU .......................................................................35

    2 Power Root Cause Analysis ...............................................................36

    2.1 MCB Trip Problem Identification............................................................36

    2.2 Cause of MCB Trip................................................................................36

    2.2.1 Trip of MCB PLN ...................................................................................362.2.2 MCB PLN & Main ACPDB.....................................................................36

    2.2.3 Trip of MCB Utility ACPDB....................................................................37

    2.2.4 MCB DCPDB.........................................................................................37

    2.3 Analysis .................................................................................................37

    2.3.1 Short Circuit...........................................................................................37

    2.3.2 Unbalance Power Consumption............................................................37

    2.3.3 Air Conditioning Problem.......................................................................38

    2.3.4 Insufficiency PLN Capacity....................................................................38

    2.3.5 PLN Problem; Phase Failure, Low Voltage...........................................42

    2.3.6 Short Circuit at Air Conditioning Controller ...........................................43

    2.3.7 Short Circuit at Air Conditioning ............................................................44

    2.3.8 MCB Trip at DOU for MCB DCPDU (19 rack)......................................443 Action Taken Recommendation.........................................................46

    3.1 Check Installation..................................................................................46

    3.2 Balancing Power Consumption .............................................................46

    3.2.1 Indoor ....................................................................................................46

    3.2.2 Outdoor..................................................................................................47

    3.3 PLN Capacity.........................................................................................49

    3.3.1 PLN Capacity Indoor Sites ....................................................................49

    3.3.2 PLN Capacity Outdoor Sites .................................................................50

    3.4 Air Conditioning Maintenance ...............................................................53

    3.4.1 Measurement AC Current for Air Conditioning......................................53

    3.4.2 Air Conditioning Phase Controller.........................................................53

    3.5 Power Source for DCPDB at 19 Rack..................................................54

    3.6 Exhaust Fan Status ...............................................................................56

    4 Reference .............................................................................................57

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    32/68

    PAGE 32

    1 Mini Circui t Breaker (MCB)

    1.1 Defin ition MCB

    1.1.1 PLN MCB

    Location : KWH panel

    Type : Blue toggle; CL curve

    Band : Merlin Gerin, ABB, Vyckler, J&P, Okachi

    MCB 1 phase 1 pole

    MCB 3 phase 1 pole

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    33/68

    PAGE 33

    1.1.2 ACPDB MCB

    1.1.2.1 Main MCB ACPDB

    Location : ACPDB panel

    Type : Black toggle; C curve; MCB 3 phase-1 pole

    Band : Merlin Gerin, ABB

    1.1.2.2 Utili ty MCB ACPDB

    Location : ACPDB panel

    Type : Black toggle; C curve; MCB 1 phase-1 pole

    Band : Merlin Gerin, ABB

    Outdoor ACPDB

    Indoor ACPDB

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    34/68

    PAGE 34

    1.1.3 DCPDB MCB

    1.1.3.1 Main MCB Rectifier

    Location : Rectifier

    Type : Black toggle; C curve; MCB 1 phase-1 pole

    Band : Merlin Gerin, ABB, Nader

    1.1.3.2 Utili ty MCB Rectif ier/PBC 6500

    Location : Rectifier or PBC 6500Type : Black toggle; C curve; MCB 1 pole

    Band : Merlin Gerin, ABB, Nader

    Main MCB Rectifier

    Utility MCB Rectifier Utility MCB PBC6500

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    35/68

    PAGE 35

    1.1.3.3 Battery MCB Recti fier

    Location : Rectifier or PBC 6500

    Type : Black toggle; C curve; MCB -1 pole

    Band : Merlin Gerin, ABB, Nader

    1.1.3.4 19 Rack MCB / DCPDU

    Location : 19 Rack

    Type : Black toggle; C curve; MCB -1 pole

    Band : Merlin Gerin, ABB, Nader

    DCPDU : for Transmission equipment

    DCPDB RBS : for RBS

    DCPDB RBS for RBS

    DCPDU - Transmission

    MCB Battery Rectifier MCB Battery PBC 6500

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    36/68

    PAGE 36

    2 Power Root Cause Analysis

    2.1 MCB Trip Problem Identif ication

    Base on data trouble ticket week 39-40, percentage of MCB trip:a. MCB PLN : 60% (14 times)b. MCB PLN & Main ACPDB : 26% (6 times)c. MCB Utility ACPDB : 9% (2 times)d. MCB DCPDB : 5% (1 times)

    2.2 Cause of MCB Trip

    2.2.1 Trip of MCB PLN

    A. Cause MCB trip Indoor Sitesa. Short Circuitb. Unbalance power consumptionc. Air Conditioning problem; high AC current (out off manufacture standard)d. Insufficient PLN capacitye. PLN Problem :Low Voltage PLN, Phase failure

    B. Cause MCB Outdoor Sitesa. Unbalance power consumptionb. Insufficient PLN capacityc. PLN Problem :Low Voltage PLN, Phase failure

    2.2.2 MCB PLN & Main ACPDB

    A. Cause MCB trip Indoor Sitesa. Short Circuitb. Unbalance power consumptionc. Air Conditioning problem; high AC current (out off manufacture standard)d. Insufficient PLN capacitye. PLN Problem :Low Voltage PLN, Phase failure

    B. Cause MCB Outdoor Sitesa. Unbalance power consumptionb. Insufficient PLN capacityc. PLN Problem :Low Voltage PLN, Phase failure

    Location : ACPDB Indoor sites

    Cause MCB Trip :a. Short circuit at MCB use for Air Conditioning controller.b. Short circuit at MCB use for Air Conditioning

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    37/68

    PAGE 37

    2.2.3 Trip of MCB Utili ty ACPDB

    Location : ACPDB Indoor sites

    Cause MCB Trip :

    a. Short circuit at MCB use for Air Conditioning controller.b. Short circuit at MCB use for Air Conditioning

    2.2.4 MCB DCPDB

    Location : Rectifier/PBC 6500 Indoor sites

    Cause MCB Trip : Insufficiency rate of MCB DCPDU (19 rack) .

    2.3 Analysis

    2.3.1 Short Circuit

    A short circuit between phase - neutral due to the destruction of AC Contactor,outdoor unit, lamp, dc fan, rectifier or all equipment that connected to power.

    This resultsin an excessive electric current (over current), and potentially causescircuit damage, overheating, fire or explosion

    In mainscircuits, short circuits are most likely to occur between two phases,between a phase and neutral or between a phase and earth (ground). Such shortcircuits are likely to result in a very high current and therefore quickly trigger anover current protection device.

    2.3.2 Unbalance Power Consumption

    Indoor:Configuration of connecting power Air Conditioning, Rectifier/PBC moduleunbalance to all phase, It is making power for each phases are not same orhigher than MCB PLN

    Unbalancing Configuration of power - Indoor

    Phase

    R S T Remark

    Air conditioning

    Rectifier / PBC 2 unit 1 unit 1 unit

    Lamp, others Note: = power connection

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    38/68

    PAGE 38

    Outdoor:Configuration of connecting power PSU module unbalance to all phase, It ismaking power for each phases are not same or higher than MCB PLN

    Unbalancing Configuration o f power - Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 2 unit 1 unit 1 unit

    PSU RBS 3G 1 unit 1 unit 1 unit

    Lamp, others Note: = power connection

    2.3.3 Air Conditioning Problem

    Some problems with the Air Conditioning are:

    The high AC current Air Conditioning cause by problem at Air Conditioningoutdoor unit.Short circuit Air Conditioning outdoor unit

    The high AC current Air Conditioning has make insufficiency PLN MCBm andshort circuit make PLN MCB and Air Conditioning MCB trip

    2.3.4 Insuf fic iency PLN Capacity

    Indoor

    Location : sites with PBC 6500

    Cause : Insufficiency PLN capacity

    Description :Indoor site use PBC 6500o PSU : 4x1400 watto Battery : 3x100Aho PLN : 10.6 kVA (MCB 3x16A)o Air Conditioning : non Inverter

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    39/68

    PAGE 39

    Configuration of power Indoor

    Phase

    R S T Remark

    Air conditioning

    PBC 6500 1 unit 1 unit 2 unit

    Lamp, others

    Current Analysis Full load

    Phase

    R S T Unit

    Air Conditioning 1892 1892 VA

    RBS 2116 1879 1879 3757 VA

    Lamp 125 VA

    Voltage 210 210 210 Volt

    Total18 18 18 Amp

    PLN MCB 16 16 16 Amp

    Note: Will be trip at full consumption

    Outdoor

    Location : sites with 2G RBS 2116

    Cause : Insufficiency PLN capacity due 4 installed PSU

    Description :

    Outdoor site RBS 2G 2116o PSU : 4x1520 watto Battery : 4x100Aho PLN capacity : 10.6 kVA (MCB PLN 3x16A)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    40/68

    PAGE 40

    Configuration of power - Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 2 unit 1 unit 1 unit

    Lamp, others

    Current Analysis Full load

    Phase

    R S T Unit

    RBS 2116 3757 1879 1879 VA

    Lamp 125 VA

    Voltage210

    210 210 Volt

    Total 18 9 10 Amp

    PLN MCB 16 16 16 Amp

    Note: Will be trip at full consumption

    2.

    Location : sites with 2G 3G (RBS 2116 + RBS 3116/3107)

    Cause : 4 installed PSU

    Description :

    Outdoor site RBS 2G 3G (RBS 2116 + RBS 3116)o PSU RBS 2G : 4x1520 watto Battery RBS 2G : 4x100Aho PSU RBS 3G : 3x1400 watto Battery RBS 3G : 2x100Aho PLN capacity : 13.2 kVA (MCB PLN 3x20A)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    41/68

    PAGE 41

    Configuration of power - Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 2 unit 1 unit 1 unit

    PSU RBS 3G 1 unit 1 unit 1 unit

    Lamp, others

    Current Analysis Full load

    Phase

    R S T Unit

    RBS 2116 3757 1879 1879 VA

    RBS 3116 1730 1730 1730 VALamp 125 VA

    Voltage210 210 210 Volt

    Total 26 17 18 Amp

    PLN MCB 20 20 20 Amp

    Note: Will be trip at full consumption

    3

    Location : sites with 2G RBS 2116

    Cause : Insufficiency PLN capacity due 4 installed PSU 2G Description:

    Outdoor site (RBS 2116 + RBS 3116+ Nobi TRM)o PSU RBS 2G : 3x1520 watto Battery RBS 2G : 4x100Aho PSU RBS 3G : 3x1400 watto Battery RBS 3G : 2x100Aho Nobi TRM : 2x2000 watto Battery Nobi TRM : 2x100Aho PLN capacity : 13.2 kVA (MCB PLN 3x20A)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    42/68

    PAGE 42

    Configuration of power Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 1 unit 1 unit 1 unit

    PSU RBS 3G 1 unit 1 unit 1 unit

    Rectifier Nobi TRM 1 unit 1 unit

    Lamp, others

    Current Analysis Full load

    Phase

    R S T Unit

    RBS 2116 1879 1879 1879 VA

    RBS 3107 1730 1730 1730 VA

    Nobi TRM 1167 1167 0 VA

    Lamp 125 VA

    Voltage 210 210 210 Volt

    Total23 23 17 Amp

    PLN MCB 20 20 20 Amp

    Note: Will be trip at full consumption

    2.3.5 PLN Problem; Phase Failure, Low Voltage

    Cause : PLN voltage drop bellow 190V AC

    Description :

    PLN Voltage drop (Below 190V AC) led to increase AC current andPLN capacity is not sufficient to make power requirement.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    43/68

    PAGE 43

    Current Analysis Full load(Nominal Voltage)

    Current Analysis Full load(Under Voltage)

    PhasePhase

    R S T Unit R S T Unit

    RBS 2116 1879 1879 1879 VA RBS 2116 1879 1879 1879 VA

    RBS 3116 1730 1730 1730 VA RBS 3116 1730 1730 1730 VA

    Lamp 125 VA Lamp 125 VA

    Voltage 210 210 210 Volt Voltage 180 180 180 Volt

    Total 17 17 18 Amp Total 20 20 21 Amp

    PLN MCB 20 20 20 Amp PLN MCB 20 20 20 Amp

    - High AC Current at under voltage, makes PLN MCB not sufficient.

    - PLN MCB will be trip

    2.3.6 Short Circuit at Air Conditioning Controller

    Short circuit location : Air Conditioning controller using relay Omron MY 2

    Cause : the connection R phase and S phase as controller toclose

    Description:

    There are Air Conditioning controller designs:

    a. Air Conditioning controller relay 1-phaseb. Air Conditioning controller relay 2-phase using relay Omron MY 2c. Air Conditioning controller relay 2-phase using CAD 32 M7

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    44/68

    PAGE 44

    Air Conditioning controller using relay Omron willing to use 2-phase for the workof Air Conditioning. The advantage using 2-phase controller is if one phase is offthe other phase will be backup. Since use 2-phase to controller Air Conditioningthan there will be 2 voltages into relay.

    The relay Omron found connection 2-phase is to narrow, and if the 2-phase arestart at the same time it cause short circuit than MCB Air Conditioning will trip

    2.3.7 Short Circuit at Air Conditioning

    Short circuit location : Air Conditioning outdoor unit

    Cause : Short of body Air Conditioning

    Description :

    Short circuit because Air Conditioning often switch off

    2.3.8 MCB Trip at DOU for MCB DCPDU (19 rack)

    Location MCB Trip : DOU 2x10A

    Cause : Insufficient of MCB rate as power source DCPDU (19 rack)

    Description :

    Power Line Connection:

    Relay Omron MY 2 CAD 32 M7

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    45/68

    PAGE 45

    DOU 1x125A connected to DCPDB RBS-----Connected to RBS 2G

    DOU 2x10A connected to TRM 19 rack (via DCPDU)

    o Connected AMM20p

    o

    Connected exhaust fanPower Analysis:

    Total Power consumption = 500 watt ( -48V; 11 Amp)

    TRM Amm20p (5 radio) = 300 watt

    DC fan = 200 watt

    Picture: Power cable connection

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    46/68

    PAGE 46

    3 Action Taken Recommendation

    3.1 Check Installation

    Check tightened of power cable connection

    Check for short circuit:

    Use buzzer (AVO meter) to no short circuit at the system KWH, ACPDB

    Measure at MCB Air Conditioning, MCB Lamp, etc

    Connection one probes to neutral bar and other toon top MCB connection

    biiiiiiiiip sound mean there are short circuit

    3.2 Balancing Power Consumption

    3.2.1 Indoor

    Connected Air Conditioning power cable to R phase and S phase

    Maximum 4 unit PSU/Rectifier module and connected with configuration; 1unit at R phase, 1 unit at S phase, 2 unit at T phase

    Configuration of power Indoor

    Phase

    R S T Remark

    Air conditioning

    PBC 6500 / Rectifier 1 unit 1 unit 2 unit

    Lamp, others

    Procedure to balancing power consumption:

    Turn on both Air Conditioning, wait until outdoor unit are working

    Measure current and voltage for R phase, S phase and T phase

    Check power connection of Air Conditioning:

    o 1 unit at R phase, 1 unit at S phase, 1 unit at T phase (if available)

    Check power connection of rectifier module or PBC 6500 PSU :

    o Maximum 4 unit PSU/Rectifier

    o Configuration; 1 unit at R phase, 1 unit at S phase, 2 unit at T phase

    o If available 5 PSU/module removed or unplug, make sure no alarm appear

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    47/68

    PAGE 47

    3.2.2 Outdoor

    Maximum number PSU at RBS 2G and 3G are = 3 unit

    Incase there Nobi rectifier enclosure the maximum rectifier module = 3 unit

    Table configuration PSU connection

    Configuration of power Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 1 unit 1 unit 1 unit

    PSU RBS 3G 1 unit 1 unit 1 unit

    Rectifier Nobi TRM 1 unit 1 unit

    Lamp, others

    Procedure balancing power

    Using Clamp- Ampere Meter to measure AC current for R phase, Sphase and T phase

    Check PLN MCB ratting (PLN Capacity)

    Check power connection of rectifier module or RBS PSU:

    o PLN 6,6 kVA (MCB 3x10A),

    RBS 2G (3 PSU) or

    Nobi TRM (2-3 mdl)

    o PLN 10.6 kVA (MCB 3x16A),

    RBS 2G (3 PSU) + Nobi TRM (2 mdl)

    o PLN 13.2 kVA (MCB 3x20A),

    RBS 2G (4 PSU),

    RBS 2G (3 PSU) + RBS 3G (3 PSU)

    o PLN 16.5 kVA (MCB 3x25A),

    RBS 2G (3 PSU) + RBS 3G (3 PSU) +Nobi Rectifier (3 PSU)

    Check MCB ratting at ACPDB

    o MCB for RBS 2G, RBS 3G and Nobi Rectifier

    o MCB 3x16A (minimum)

    o MCB 3x20A (recommendation)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    48/68

    PAGE 48

    Site 2G 3G with PLN capacity 13.2 kVA, RBS 2G have 4 PSU, astemporary solution do unplug 1PSU (PSU number 4), with no alarmappear

    Site 2G 3G Nobi Rectifier and Nobi TRM with PLN capacity 13.2 kVA, astemporary solution do unplug 1PSU RBS 2G (PSU number 1) andUnplug 1 PSU RBS 3G (PSU number 2), with no alarm appear

    Configuration of power Outdoor

    Phase

    R S T Remark

    PSU RBS 2G 0 unit 1 unit 1 unit

    PSU RBS 3G 1 unit 0 unit 1 unit

    Rectifier Nobi TRM 1 unit 1 unit 1 unit

    Lamp, others

    Current Analysis Full load

    Phase

    R S T Unit

    RBS 2G 1879 1879 0 VA

    RBS 3G 1730 0 1730 VA

    Nobi TRM 0 1167 1167 VA

    Lamp 0 VA

    Voltage 208 200 198 Volt

    Total 17 15 15 Amp

    PLN MCB 20 20 20 Amp

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    49/68

    PAGE 49

    3.3 PLN Capacity

    3.3.1 PLN Capacity Indoor Sites

    1. PLN 10.6 kVA (MCB PLN 3x16A)

    a. Air Conditioning : 2 PK inverter (AC current 7.4A ; 220V AC)

    b. Rectifier : 2x200 watt or 3x2000 watt

    Current Analysis Full load

    Phase

    R S T Unit

    Air Conditioning 1628 1628 VA

    Rectifier 1069 1069 1069 VA

    Lamp 125 VA

    Voltage 210 210 210 Volt

    Total 13 13 6 Amp

    PLN MCB 16 16 16 Amp

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    50/68

    PAGE 50

    2. PLN 13.2 kVA (MCB PLN 3x20A)

    a. Air Conditioning : 2 PK non inverter (AC current 10.6A ; 220V AC)

    b. Rectifier or PBC 6500 : maximum 4 unit

    Current Analysis Full load

    Phase

    R S T Unit

    Air Conditioning 2438 2438 VA

    Rectifier 1069 1069 2138 VA

    Lamp 125 VA

    Voltage 210 210 210 Volt

    Total 17 17 11 Amp

    PLN MCB 20 20 20 Amp

    3.3.2 PLN Capacity Outdoor Sites

    1. PLN 6.6 kVA (MCB 3x10A),

    RBS 2G (3 PSU) or

    Nobi TRM (2-3 mdl)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    51/68

    PAGE 51

    Configuration of power Outdoor Current Analysis Full load

    Phase Phase

    R S T R S T Unit

    PSU RBS 2G 1 unit 1 unit 1 unit RBS 2116 1879 1879 1879 VA

    Lamp, others Lamp 125 VA

    Voltage 210 210 210 Volt

    Total 9 9 9 Amp

    PLN MCB 10 10 10 Amp

    2. PLN 10.6 kVA (MCB 3x16A),

    RBS 2G (3 PSU) + Nobi TRM (2 mdl)

    Configuration of power Outdoor Current Analysis Full load

    Phase Phase

    R S T R S T Unit

    PSU RBS 2G 1 unit 1 unit 1 unit RBS 2116 1879 1879 1879 VA

    Nobi TRM 1 unit 1 unit Nobi TRM 1297 1297 VA

    Lamp, others Lamp 125 VA

    Voltage 210 210 210 Volt

    Total 15 15 10 AmpPLN MCB 16 16 16 Amp

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    52/68

    PAGE 52

    3. PLN 13.2 kVA (MCB 3x20A),

    RBS 2G (4 PSU),

    RBS 2G (3 PSU) + RBS 3G (3 PSU)

    Configuration of power Outdoor Current Analysis Full load

    Phase Phase

    R S T R S T Unit

    PSU RBS 2G 1 unit 1 unit 1 unit RBS 2116 1879 1879 1879 VA

    PSU RBS 3G 1 unit 1 unit 1 unit RBS 3116 1370 1370 1370 VA

    Lamp, others Lamp 125 VA

    Voltage 210 210 210 Volt

    Total 18 18 18 Amp

    PLN MCB 20 20 20 Amp

    4. PLN 16.5 kVA (MCB 3x25A),

    RBS 2G (3 PSU) + RBS 3G (3 PSU) + Nobi Rectifier (3 PSU)

    Configuration of power Outdoor Current Analysis Full load

    Phase Phase

    R S T R S T Unit

    PSU RBS 2G 1 unit 1 unit 1 unit RBS 2116 1879 1879 1879 VA

    PSU RBS 3G 1 unit 1 unit 1 unit RBS 3116 1370 1370 1370 VA

    Nobi TRM 1 unit 1 unit Nobi TRM 1297 1297 125 VA

    Lamp, others Voltage 210 210 210 Volt

    Total 24 24 18 Amp

    PLN MCB 25 25 25 Amp

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    53/68

    PAGE 53

    3.4 Air Conditioning Maintenance

    3.4.1 Measurement AC current for Air Conditioning

    Procedure:

    Turn on Air Conditioning, wait until the outdoor unit is working

    Take Clamp-Ampere Meter to measure AC current at line for Air Conditioningonly

    AC Current allowed

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    54/68

    PAGE 54

    Wiring diagram

    3.5 Power Source for DCPDU at 19 Rack

    Power capacity for DCPDU at 19 rack:

    MCB ratting at Rectifier / PBC 6500:

    MCB 2x25A (minimum)

    MCB 2x32A (recommendation)

    Recommendation for Indoor site configuration:

    DC Power source : PBC 6500

    PSU : 4x1400 watt

    Battery : 3x100Ah

    DOU : DOU 1x125A + DOU 2x10A

    Load :

    o RBS 2G RBS 2216/2206

    o TRM Amm20p

    o Exhaust fan

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    55/68

    PAGE 55

    Procedure:

    o Change power source for TRM 19 rack to DOU 1x125A

    DOU 1x125A connected to DCPDB RBS

    Connected to RBS 2G Connected to DCPDU TRM

    Connected AMM20p

    Connected Exhaust fan

    o Exhaust fan and EAS connected power to DOU 2x10A

    DOU 2x10A connected to:

    Exhaust fan

    o Wiring Power connection

    Recommendation Power Connection

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    56/68

    PAGE 56

    3.6 Exhaust Fan Status

    Problem : High Temperature

    Cause : Exhaust fan not working properly due external alarm panel is

    brokenDescription :

    Exhaust fan is the emergency fan to circulate the hot air out of shelter when theAir Conditioning is not working properly.The exhaust fan is trigger by temperature sensor at external alarm system (EAS),if the sensor detection high temperatures (set 30oC) in the shelter than the fanwill working and send alarm to NOC (Alarm high temperature)

    Temporary Recommendation:

    If in the site found EAS is broken

    1. Use phase failure as trigger working of the exhaust fan

    Procedure:

    o Removed power connection for exhaust fan from relay EAS to relayphase failure

    o Use relay R phase failure and connection DC power of exhaust fan

    R-phase

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    57/68

    PAGE 57

    Recommendation Solution:

    Additional thermostat for triggering exhaust fan start relay

    The thermostat will bet at 30C for trigger the relay and send alarm high

    temperature

    4 Reference

    2008-09-16 - 198/1551-LZA 701 0001 Uen A Technical Description RBS 2111EID-08:013998 Uen Rev. A Petunjuk Instalasi RBS 2000 Ericsson IndonesiaEID-08:017130 Uen Rev. A Petunjuk Instalasi RBS 3000 Ericsson IndonesiaEID-09:010738 Uen Rev. A Configuration of Sites Using The Outdoor Enclosure(NOBI)

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    58/68

    PAGE 58

    Enclosure

    4

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    59/68

    PAGE 59

    4.1 TRANSMISSION AND RBS DATA REPORT

    SITE BUKIT PAMULANG MEGAH

    NTS Project

    Contents

    1 Abstract ................................................................................................60

    2 Problem.................................................................................................60

    3 Alarm & Data Capture ...........................................................................60

    3.1 Alarm & Data Capture Transmission.....................................................60

    3.2 Alarm & Data Capture RBS...................................................................61

    4 Actual Configuration ..............................................................................61

    4.1 Actual Configuration Transmission........................................................61

    4.2 Actual Configuration RBS......................................................................61

    5 Analyze..................................................................................................62

    6 Solution Recommendation ....................................................................62

    7 Supporting Document............................................................................62

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    60/68

    PAGE 60

    1. Abstract

    This document describes reporting site BTTG005 Bukit Pamulang Megah.

    2. Problem

    BFU Problem: (from TT-20090923-00068).Action Taken by MS: FM replaced BFU module.

    3. Alarm and Data Capture

    3.1 Alarm and Data Capture Transmission

    Alarm List Capture;

    Picture 1 RSL Capture

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    61/68

    PAGE 61

    3.2 Alarm and Data Capture RBS

    Alarm List Capture;

    Picture 2 Alarm List

    4. Actual Configuration

    4.1 Actual Configuration Transmission

    AMM Type : AMM 2p

    Configuration network : 1+0 ML TN 18 GHz

    Hop Name : BTTG005 B Pamulang Megah to JBKD052Wr Poncol.

    Software Baseline : R7M06 (Release 2.4.10)

    4.2 Actual Configuration RBS

    RBS Type : 2116

    Configuration network : 2/2/2

    Site Name : BTTG005 Bukit Pamulang Megah.

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    62/68

    PAGE 62

    5. Analyze

    Transmission: No Transmission problem found.

    RBS: When BFU Module was fault, The RBS do not have Battery backup system.And DC source to transmission equipment was disconnected. It is hardware faulty.

    6. Solution Recommendation

    FM already changed the BFU with the new one. Now, The RBS have been inservice and have stable condition.

    7. Supporting Document

    BTTG005 B Pamulang Megah (TRM).rar

    BTTG005 B Pamulang Megah (RBS).rar

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    63/68

    PAGE 63

    4.3 POWER DATA REPORT

    SITE BUKIT PAMULANG MEGAH

    NTS Project

    Contents

    1 Introduction....................................................................................................641.1 Purpose.........................................................................................................64

    1.2 Reference......................................................................................................64

    1.3 Site Location .................................................................................................64

    2 Power Data....................................................................................................65

    2.1 kWh Panel.....................................................................................................65

    2.2 ACPDB..........................................................................................................65

    2.3 Power Supply................................................................................................66

    3 Problem Identification....................................................................................66

    4 Analysis.........................................................................................................67

    4.1 Check Balancing Power................................................................................67

    5 Recommendation Solution............................................................................68

    6 Supporting Document ...................................................................................68

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    64/68

    PAGE 64

    1 Introduction

    1.1 Purpose

    This document explains about root cause analysis of site problem

    1.2 Reference

    EID-08:013998 Uen Rev. A Petunjuk Instalasi RBS 2000 Ericsson IndonesiaEID-08:017130 Uen Rev. A Petunjuk Instalasi RBS 3000 Ericsson Indonesia

    1.3 Site Location

    Site Name : BTTG 005, Bukit Pamulang Megah

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    65/68

    PAGE 65

    2 Power Data

    2.1 KWh Panel

    Description ValueMCBInputBrandandCapacity MG;3xCL20A

    SurgeProtection

    OBOtypeB/3+1

    ( 3X255VAC50kA&

    1XC255VAC125kA)

    SinglePhaseMainsInputVoltage(RN/SN/TN) 209.4/217.3/210.2

    ThreePhaseMainsInputVoltage(RS/ST/RT) 361.8/382.6/3721.9

    NGVoltage 0.4V

    CurrentforPhaseR 2.1A

    CurrentforPhaseS 2.5A

    CurrentforPhaseT 2.0A

    2.2 ACPDB

    Description ValueACPDBPANELCheckMCBInputBrandandCapacity MG;3x63A

    CheckSurgeProtectionOBOtypeC/3+1

    (3XV20C&1XC25B+C)

    CheckMCBInputCapacityforRBSOutdoorRphase 32A

    CheckMCBInputCapacityforRBSOutdoorSphase 32A

    CheckMCBInputCapacityforRBSOutdoorTphase 32A

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    66/68

    PAGE 66

    2.3 Power Supply

    Description ValueRectifierType(brand,typeofPowerSystem) 2G:PSURBS2116

    RectifierCapacity(qtymodulexcapacitypermodule) 2G:3xPSU1520watt

    MCBInput(QtyxRattingMCB,Brand/TypeinACPDB) 3X32AMERLINGERIN

    MCBInput(QtyxRattingMCB,Brand/TypeinRectifier) NA

    SurgeProtectionTypeandCondition(arresterbrand/type) NA

    InputCurrentPhaseR(ACPDBtoRectifier) 2.1A

    InputCurrentPhaseS(ACPDBtoRectifier) 2.5A

    InputCurrentPhaseT(ACPDBtoRectifier) 2.0A

    LoadConfiguration

    (RBS/TRM/DXX)

    RBS

    2G

    AMM2P

    LoadCurrentTotal 6.7A

    BatteryBrandandType FiammFIT100

    BatteryCapacity(qtybankxcapacityAh) 4X100Ah

    MCBbattery 1(Brand,ratting) BFU+24/250A

    MCBbattery 2(Brand,ratting) NA

    MCBbattery 3(Brand,ratting) NA

    MCBbattery 4(Brand,ratting) NA

    3 Problem Identification

    No power issue

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    67/68

    PAGE 67

    4 Analysis

    4.1 Check Balancing Power

    Configuration Load

    Rebalancing Configuration of power

    Phase

    R S T Remark

    PSU RBS 2116 1 psu 1 psu 1 psu

    Lamp

    Power balancing analysis average load:

    Current Analysis average loadPhase

    R S T Unit

    PSU RBS 2116 2.1 2.5 2.0 Amp

    Lamp Amp

    Total 2.1 2.5 2.0 Amp

    PLN MCB 20 20 20 Amp

    Power balancing analysis full load:

    Current Analysis Full load

    Phase

    R S T Unit

    RBS 2116 1879 1879 1879 VA

    Lamp 125 VA

    Voltage 210 217 210 Volt

    Total 9 9 9 Amp

    PLN MCB 20 20 20 Amp

  • 7/22/2019 Mini-Link Troubleshooting and Power Analysis.pdf

    68/68

    5 Recommendation Solution

    Keep balancing phase R, phase S, phase T with changing connection phasepower PSU module

    Connected PSUs RBS 2116 with configuration; 1 module at R phase, 1module at S phase, 1 module at T phase

    Rebalancing Configuration of power

    Phase

    R S T Remark

    PSU RBS 2116 1 mdl 1 mdl 1 mdl

    PSU RBS 3116 1 mdl 1 mdl 1 mdl

    Lamp

    6 Supporting Document

    BTTG 005 Bukit Pamulang Megah (Power).rar