MONTHLY REPORT OF DMC MANDI
For the month ,January 2012 1.1 GENERAL
1.2 DETAILS OF IMPORTANT TECHNICAL WORK DONE AT LPTs / VLPTs DURING THE MONTH Name of Station
Details of the important technical work done REMARKS
LPT Mandi. 1.GCEL make Power Supply 28V/25A has been repaired by replacing one no DPDT switch 230V/10A. 2.Video Processoe of VLPT Keylong has been repaired by replacing Elect. Cap.220mf/63V & Pot. 100K. 3.DC to DC converter of VLPT Keylong has been repaired by replacing Mosfet BUZ30 -02 nos,DiodeBy127, Elect. Cap.220mf/63 & regulator LM7915 4. Routine mtc. of DD-1 & DD News transmitter done.Faulty cooling fan of DD News Power Supply replaced.
LPT Kullu. Routine maintenance of transmitter done.
LPT Sundernagar.
Routine maintenance of transmitter done.
LPT Manali Routine maintenance of Transmitter done VLPT Jhatingri. Faulty IRD of of the station has been repaired by replacing Processor Card.
All VLPTS Visits for routine maintenance & in case of complaints done at all VLPTs.
1.3 DETAILS OF OFFICERS / STAFF RELIEVED / JOINED FROM / AT DURING THE MONTH DETAILS OF OFFICERS / STAFF JOINED DURING THE MONTH
Name Designation Emp. No. Relieved from Station Relieving Date Joined at Joining date Transfer order No.
and Date ------ ------
DETAILS OF OFFICERS / STAFF RELIEVED DURING THE MONTH
Name Designation Emp. No. Relieved from Station
Relieving Date To join at Transfer order No. and Date
.
1.4 TOUR / LEAVE DETAILS OF ENGG. HEAD OF OFFICE / CONTROLLING OFFICERS DURING THE MONTH
NAME OF OFFICER TOUR DETAILS PERIOD OF E.L./MEDICAL LEAVE ALONGWITH ITS NATURE
Sh.A.N.Jagota Asstt. Director (Engg.)
PERIOD PLACE E.L W.E.F. 01-01-2012 to 27-01-12
------- .
1.5 TRAINING DETAILS OF ENGG. HEAD OF OFFICE / STAFF DURING THE MONTH
NAME OF OFFICER / STAFF DESIGNATION PERIOD PLACE NAME OF COURSE From To
------ ------ ------ ------ ------
------ ------ ------ ------ ------
1.6 DETAILS OF NEW EQUIPMENTS RECEIVED AT DMC / LPTs / VLPTs DURING LAST SIX MONTHS
Name of Station Name of equipment Date of
receipt of equipment
Received from Whether put in to circuit
Performance of equipment
Remarks
DMC Mandi. 2*50 Watts UHF Transmitter Complete.
For VLPT Jhatingri.
05-12 -2011 D-6, Godown,Delhi.
No Yet to be tested
1.5 DETAILS OF SCROLLER
Name of Station Working Status of Scroller-1
Working Status of Scroller-2
Revenue generated in
current month
Progressive revenue generated in current financial
year LPT Mandi OK OK Nil LPT Kullu OK Def Nil LPT Manali
OK OK Nil
LPT Sundernagar
OK OK Nil
1.7 ELECTRIC CONNECTION DETAILS
Name of Station Availability of Electricity
Whether Single Phase / Three
Phase
Sanctioned Load
Power Factor
LPT Mandi Yes Three phase 32.14 kw 0.95 LPT Manali Yes Three phase 19.26 kw 0.97 LPT Kullu Yes Three phase 34.8 kw 0.90 LPT Sundernagar Yes Three phase 16.2 kw 0.90 VLPT Kotli Yes Single Phase 6.68 kw PF meter not available VLPT Chatturbhuja Yes Single Phase 6.8 kw PF meter not availableVLPT Shivabadar, Yes Single Phase ------ PF meter not availableVLPT Sarkaghat Yes Single Phase 3.12 kw PF meter not availableVLPT Banjar Yes Single Phase 2.70 kw PF meter not availableVLPT Diyar Yes Single Phase ------- PF meter not availableVLPT Bijlimahadev Yes Single Phase ------ PF meter not availableVLPT Keylong Yes Single Phase ------ PF meter not availableVLPT Jhalman Yes Single Phase 2.32 kw PF meter not availableVLPT Udaipur Yes Single Phase 2.40 kw PF meter not availableVLPT Nihri Yes Single Phase 2.48 kw PF meter not availableVLPT Jhatingri Yes Single Phase 1.96 kw PF meter not available
1.8 LAND / BUILDING DETAILS
Station Name of Owner of Land Category of Owner
(Deptt. / Govt. / Private)
Type of Building
(Porta Cabin / Permanent)
Is Building / Porta Cabin constructed
departmentally
Rent of Setup (Rs. p.m.)
Availability of Lease Deed
Due Date of
Renewal of Lease
Deed
Due Date of Revision of Rent
Remarks
LPT Mandi Doordarshan Govt. Permanent Costructed by HP Govt before installation
Nil Nil Nil Nil Purchased by Deptt.from HP Govt
LPT Manali HP Govt. Govt. Forest Huts Costructed by HP Govt before installation
Nil Nil Nil Nil On lease
LPT Kullu AIR Govt. Permanent Yes Nil Nil Nil Nil Diverted to Deptt. By HP Govt for relay centre.
LPT Sundernagar Doordarshan Govt. G.I. Portacabin Yes Nil Nil Nil Nil Purchased by Deptt.from HP Govt
VLPT Kotli President Dev Rachera Mandi Kalyan Samiti
Private Permanent No 2178 02-11-2015 02-11-2015
.
VLPT Chatturbhuja President Sudhar Committee
Private Permanent No 2420 08-04-2015 08-04-2015
VLPT Shivabadar, Sh Meena Ram Vill.& PO Shivabadar
Private Portacabin Yes 880 01-09-2012 01-09-2012
Only land hired .
VLPT Sarkaghat Sh Ganno Ram Sharma Vill Samsoh
Private Permanent No 2474 25-04-2015 25-04-2015
VLPT Banjar Sh. Lot Ram Sharma Vill.Gadhiyar
Private Permanent No 2750 01-07-2012 01-07-2012
VLPT Diyar HP Govt. HP Govt. Portacabin Yes Nil Nil Nil Nil Diverted to Deptt. By HP Govt for relay centre.
VLPT Bijlimahadev
Kardar Devta Bijilimahadev
Private Portacabin Yes 1210 01-04-2014 01-04-2014
Only land hired.
VLPT Keylong HP Govt. Govt. Permanent Yes Nil Nil Nil Nil Diverted to Deptt. By HP Govt for relay centre.
VLPT Jhalman Sh.Bhag Ram Gautam P.O Muraing
Private Permanent No 2662 01-02-2013 01-02-2013
VLPT Udaipur Sh.Ram Lal Sharma Vill.Udaipur
Private Permanent No 4235 01-01-2013 01-01-2013
VLPT Nihri Land taken on lease from HP Govt.
HP Govt Portacabin Yes 4668 Per Annum
08-02-2010 08-02-2010
Matter for revision of lease deed is pending in DC Office Mandi .
VLPT Jhatingri HP Govt. Govt. Portacabin Yes Nil Nil Nil Nil Diverted to Deptt. By HP Govt for relay centre.
DMC,Mandi Sh Suraj Singh Kapoor Palace Colony Mandi
Private Permanent No 7513 01-04-2014 01-04-2014
DMC,Mandi Garage
Sh Suraj Singh Kapoor Palace Colony Mandi
Private Permanent No 968 01-01-2013 01-01-2013
2. TECHNICAL
2.1 DETAILS OF WORKING OF TRANSMITTER FOR THE MONTH JANUARY 2012
LPT-Mandi DD-1
LPT Mandi DD-2
LPT Kullu
LPT Manali
LPT-Sundernagar
VLPT Kotli
VLPT Chatturbhuja
VLPT Shivba
dar
VLPT Sarkag
hat
VLPT Banjar
1 Test Hours 06.71
07.75
06.71
06.71
06.71
Nil
Nil
Nil
Nil
Nil
2 Scheduled * Prog. Hours 578.76
589 578.76 578.76 578.76
744 744
744
744
744
3 Gear Breakdown Hrs.
Nil
Nil
Nil
Nil
Nil
Nil
18
Nil
Nil
Nil
4 Power Supply Breakdown Hrs.
0.13
0.13
Nil
0.15
0.40
Nil
Nil
Nil
Nil
Nil
5 Other Causes Breakdown Hrs. Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
6 Total Breakdown Hrs. (3+4+5)
0.13
0.13
Nil
0.15
0.40
Nil 18
Nl
Nil
Nil
7 Prog. Hours Radiated (2-6) 578.63
588.87
578.76
578.61
578.36
744 726
744
744
744
8 Total Hours of Working (1+7)
585.34
596.62
585.47
585.32
585.08
744
726
744
744
744
9
% B/D ={(Total B/D x 100)/ Scheduled Prog. Hrs.)}
0.02%
0.02%
Nil
0.02%
0.06%
Nil
2.47%
Nil
Nil
Nil
VLPT-Diyar
VLPT-Keylong
VLPT-Jhalman
VLPT-Udaipur
VLPT-Bijlimahadev
VLPT-Nihri
VLPT-Jhatingri
1 Test Hours Nil
Nil
Nil
Nil
Nil
Nil
Nil
2 Scheduled * Prog. Hours
744 744
744 744
744
744
744
3 Gear Breakdown Hrs.
Nil
Nil
Nil
96
Nil
Nil
Nil
4 Power Supply Breakdown Hrs.
Nil
Nil
Nil
Nil
Nil
Nil
Nil
5 Other Causes Breakdown Hrs.
Nil
Nil
Nil
Nil
Nil
Nil
Nil
6 Total Breakdown Hrs. (3+4+5)
Nil
Nil
Nil
96
Nil
Nil
Nil
7 Prog. Hours Radiated (2-6)
744 744
744
648
744
744
744
8 Total Hours of Working (1+7)
744 744
744
648
744
744
744
9
% B/D ={(Total B/D x 100)/ Scheduled Prog. Hrs.)}
Nil Nil
Nil
14.81%
Nil Nil
Nil
2.2 PROGRESSIVE TOTAL FROM APRIL OF CURRENT FINANCIAL YEAR
LPT-Mandi DD-1
LPT-Mandi DD-2
LPT-Kullu
LPT-Manali
LPT-Sundernagar
VLPT-Kotli
VLPT-Chatturbhuja
1 Test Hours 66.26
76.30
66.51
66.48
66.10
Nil
Nil
2 Scheduled Prog. Hours
5761.86
5814.00
5761.86
5761.86
5761.86
7344
7344
3 Gear Breakdown Hrs. Nil
Nil
Nil
Nil
0.20
43
100
4 Power Supply Breakdown Hrs.
2.59
2.59
Nil
1.76 6.36
Nil
Nil
5 Other Causes Breakdown Hrs. Nil
Nil
Nil
Nil Nil
Nil Nil
6 Total Breakdown Hrs. (3+4+5) 2.59
2.59
Nil
1.76 6.56
43 100
7 Prog. Hours Radiated (2-6)
5759.27
5811.41
5761.86
5760.09 5755.30
7301 7244
8 Total Hours of Working (1+7) 5825.53
5887.71
5828.37
5826.57 5821.40
7301 7244
9 % B/D ={(Total B/D x 100)/Scheduled Prog. Hrs.)}
0.04%
0.04%
Nil
0.03% 0.11%
0.58 %
1.36%
VLPT-Shivbad
ar
VLPT-Sarkagh
at
VLPT-Banjar
VLPT-Diyar
VLPT-Keylong
VLPT-Jhalman
VLPT-Udaipur
VLPT-Bijlimahadev
VLPT-Nihri
VLPT-Jhating
ri
1 Test Hours Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
Nil
2 Scheduled Prog. Hours
7344
7344
7344
7344 7344 7344
7344 7344
7344 7344
3 Gear Breakdown Hrs.
74 69
40
43
75
Nil
249
42
18
91
4 Power Supply Breakdown Hrs.
Nil Nil
Nil Nil
Nil
Nil Nil
Nil
Nil Nil
5 Other Causes Breakdown Hrs.
Nil Nil
Nil Nil
Nil Nil
Nil Nil
Nil Nil
6 Total Breakdown Hrs. (3+4+5)
74
69
40 43
75
Nil
249
42
18 91
7 Prog. Hours Radiated (2-6)
7270
7275
7304
7301
7269
7344
7095
7302
7326
7253
8 Total Hours of Working (1+7)
7270
7275
7304
7301 7269
7344 7095
7302 7326 7253
9
% B/D ={(Total B/D x 100)/ Scheduled Prog. Hrs.)}
1.01%
0.93 %
0.54% 0.58%
1.03%
Nil
3.39%
0.57%
0.25% 1.23%
2 DETAILS OF POWER OF TRANSMITTER FOR THE MONTH JANUARY 2012
LPT-
Mandi DD-1
LPT Mandi
DD News
LPT-Kullu
LPT-Manali
LPT-Sundernagar
VLPT-Kotli
VLPT-Chaturbhuja
VLPT-Sarkagh
at
VLPT Banjar
VLPT-Diyar
1 Rated Power of Transmitter (in KW / Watts)
100 watts
100 watts
500 watts
100 watts
500 watts
10 watts 10 watts
10 watts 10 watts 10 watts
2
Forward Peak Power of Transmitter
100 watts
100 watts
500 watts
100 watts
500 watts
10 watts 10 watts
10 watts 10 watts 10 watts
Video 100 watts
100 watts
500 watts
100 watts
470 watts
10 watts 10 watts
10 watts 10 watts 10 watts
Audio 10 watts 10 watts
50 watts
10 watts
45 watts
1 watt 1watt 1 watt 1 watt 1 watt
3
Reflected Power 2* watts 0.2 watt
4 watts
0.5 watts
4.5 watts
Negligible
Negligible
Negligible
Negligible
Negligible
Video --Do-- -Do- -Do- -Do- -Do- -Do- -Do- --Do-- -Do- -Do- Audio -- -- --- -- -- --- -- -- -- ---
4 Since when Transmitter is on less than rated power (if applicable)
-- -- --- -- -- --- -- -- -- ---
5 Reasons for less than rated power
-- -- --- -- -- --- -- -- -- ---
6 Reasons for high reflection, if any
**** -- --- -- -- --- -- --- -- ---
VLPT-Keylong
VLPT-Jhalma
n
VLPT-
Udaipur
VLPT-Bijlimahadev
VLPT Nihri
VLPT Jhatingri
VLPT Shivabadar
1 Rated Power of Transmitter (in KW / Watts)
10 watts 10 watts
10 watts
10 watts
50 watts
50 watts 10 watts
2 Forward Peak Power of Transmitter
10 watts 10 watts
10 watts
10 watts
50 watts
50 watts 10 watts
Video 10 watts 10
watts 10
watts 10
watts 50
watts
50 watts 10 watts
Audio 1 watt 1 watt 1 watt 1watt 5 watt
5watts 1watt
3 Reflected Power Negligibl
e Negligi
ble Negligible
Negligible
Negligible
Negligible
Negligible
Video -Do- -Do- -Do- -Do- -Do- -Do- -Do-
Audio -- -- --- -- --- -- --
4 Since when Transmitter is on less than rated power (if applicable)
-- -- --- -- -- -- --
5 Reasons for less than rated power
-- -- --- -- -- -- --
6 Reasons for high reflection, if any
-- -- --- -- -- --
**** Heleos make Tx. Antenna of LPT Mandi ( DD-1) has been repaired number of times. Replacement of this antenna with new antenna MCE Make is reqd. as old antenna gives frequent problems due to complexity of design.
2.4 DETAILS OF LOW POWER RADIATION FROM TRANSMITTER (Sync Peak Video Power less than rated power)
LPT Mandi
DD-1 LPT Mandi DD-News
LPT Kullu
LPT Manali LPT Sundernagar
VLPT Kotli VLPT Chaturbhuja
1 Dates
2 Duration -- -- -- -- -- -- --
3 Power (Radiation) -- -- -- -- -- -- --
4 Reasons -- -- -- -- -- -- --
5 Total duration of Low Power in hours during the month
-- -- -- -- -- -- --
6 No. of occurrences -- -- -- -- -- -- --
7 Progressive total of
occurrences of Low Power Radiation
-- -- -- -- -- -- --
8 Progressive total of duration of Low Power Radiation
-- -- -- -- -- -- --
9 Complaints of reception, if any & Reason of complaints
*** -- -- -- -- -- --
*** During heavy rains reflection increases due to water seepage in Transmitting antenna. So some complaints of signal reception are received.Also due to prolonged operation technical quality of the signal is not so good. Proposal for replacement of Transmitter has already been sent to Zonal Office since it is overdue.
VLPT Sarkaghat
VLPT Shivab
adar
VLPT Banjar
VLPT Diyar
VLPT Keylong
VLPT Jhalman
VLPT Udaipur
VLPT Bijlimah
adev
VLPT Nihri
VLPT Jhatingri
1 Dates
2 Duration -- -- -- -- -- -- -- -- -- --
3 Power (Radiation)
-- -- -- -- -- -- -- -- -- --
4 Reasons -- -- -- -- -- -- -- -- -- --
5
Total duration of Low Power in
hours during the month
-- -- -- -- -- -- -- -- -- --
6 No. of occurrences
-- -- -- -- -- -- -- -- -- --
7
Progressive total of
occurrences of Low Power Radiation
-- -- -- -- -- -- -- -- -- --
8
Progressive total of duration
of Low Power
Radiation
-- -- -- -- -- -- -- -- -- --
9
Complaints of reception, if any
& Reason of complaints
-- -- -- -- -- -- -- -- -- --
2.5 DETAILS OF MAJOR BREAKDOWN DURING THE MONTH (More than 15 minutes in case of LPTs & more than 72 hrs in case of VLPTs)
Name of LPT/VLPT Date Duration Period Resons for B/D
Action taken to solve the B/D
Prevention action taken to avoid such
Breakdowns in future
From To
LPT Mandi DD-1 --- --- --- --- --- ---
LPT Mandi DD-NEWS --- --- --- --- --- --- LPT Kullu --- --- --- --- --- --- LPT Manali --- --- --- --- --- ---
LPT Sundernagar --- --- --- --- --- ---
VLPT Kotli --- --- --- --- --- ---
VLPT Chaturbhuja --- --- --- --- --- ---
VLPT Sarkaghat --- --- --- --- --- ---
VLPT Banjar --- --- --- --- --- --- VLPT Diyar --- --- --- --- --- ---
VLPT Keylong --- --- --- --- --- ---
VLPT Jhlaman --- --- --- --- --- ---
VLPT Udaipur
-----
VLPT Bijlimahadev --- --- --- --- --- ---
VLPT Nihri --- --- --- --- --- --- VLPT Jhatingri --- --- --- --- --- --- VLPT Shivabadar --- --- --- --- ---
2.6 CATEGORY-WISE BREAKDOWN DURING THE MONTH
Name of LPT/VLPT GEAR POWER SUPPLY OTHER CAUSES
Major Minor Major Minor Major Minor No Dur. No Dur. No Dur No Dur. No Dur. No Dur.
LPT Mandi DD-1 -- -- -- -- -- -- 08 0.13 -- -- -- -- LPT Mandi DD News -- -- -- -- -- -- 08 0.13 -- -- -- -- LPT Kullu -- -- -- -- -- -- -- -- -- -- -- -- LPT Manali -- -- -- -- -- -- 09 0.15 -- -- -- -- LPT Sundernagar -- -- ---- --- -- -- 24 0.40 -- -- -- -- VLPT Kotli -- -- -- -- -- -- -- -- -- -- VLPT Chaturbhuja -- -- 01 18 -- -- -- -- -- -- -- -- VLPT Sarkaghat -- -- -- --- -- -- -- -- -- -- -- -- VLPT Banjar -- -- -- -- -- -- -- -- -- -- VLPT Diyar -- --- -- -- -- -- --- -- -- -- -- -- VLPT Keylong -- -- -- -- -- -- -- -- -- -- -- -- VLPT Jhalman -- -- --- --- -- -- -- -- -- -- -- -- VLPT Udaipur 10 96 -- -- -- -- -- -- -- -- VLPT Bijlimahadev -- -- --- -- -- -- -- -- -- -- -- -- VLPT Nihri -- -- --- --- -- -- -- -- -- -- -- -- VLPT Jhatingri -- -- -- --- -- -- - -- -- -- -- -- VLPT Shivabadar -- -- -- -- -- -- -- -- -- --
2.6 CATEGORY-WISE PROGRESSIVE B.D FROM APRIL OF CURRENT FINANCIAL YEAR
Name of LPT/VLPT GEAR POWER SUPPLY OTHER CAUSES
Major Minor Major Minor Major Minor No Dur. No Dur. No Dur No Dur. No Dur. No Dur.
LPT Mandi DD-1 -- -- -- -- -- -- 155 2.59 -- -- LPT Mandi DD News -- -- -- -- -- -- 155 2.59 -- -- -- -- LPT Kullu -- -- -- -- -- -- -- -- -- -- LPT Manali -- -- -- -- -- -- 107 1.76 -- -- LPT Sundernagar -- -- 02 0.20 -- -- 382 6.36 -- -- VLPT Kotli 06 43 -- -- -- -- -- -- VLPT Chaturbhuja -- -- 06 100 -- -- -- -- -- -- VLPT Sarkaghat -- -- 05 69 -- -- -- -- -- -- VLPT Banjar -- -- 08 40 -- -- -- -- -- -- VLPT Diyar -- --- 04 43 -- -- --- -- -- -- VLPT Keylong -- -- 02 75 -- -- -- -- -- -- VLPT Jhalman -- -- -- -- -- -- -- -- -- -- VLPT Udaipur -- -- 13 249 -- -- -- -- -- -- VLPT Bijlimahadev -- -- 03 42 -- -- -- -- -- -- VLPT Nihri -- -- 01 18 -- -- -- -- -- -- VLPT Jhatingri -- -- 05 91 -- -- - -- -- -- VLPT Shivabadar -- -- 06 74 -- -- -- -- -- --
2.7 PERFORMANCE FIGURES OF TRANSMITTER
LPT Mandi DD-1
LPT Mandi
DD News
LPT KULLU
LPT Manali
LPT Sundernagar
VLPT Kotli
VLPT Chaturbhuja
VLPT Sarkag
hat
VLPT Shivab
adar
VLPT Banjar
VLPT Diyar
VLPT Keylon
g
Frequency of Vision Carrier
217.26Mhz
203.24Mhz
175.25Mhz
217.25Mhz
527.26Mhz
224.24Mhz
196.25Mhz
224.24Mhz
189.26Mhz
196.24Mhz
196.26Mhz
182.25Mhz
Frequency of Aural Carrier
222.76Mhz
208.74Mhz
180.75Mhz
222.75Mhz
532.76Mhz
229.74Mhz
201.75Mhz
229.74Mhz
194.76Mhz
201.74Mhz
201.76 Mhz
187.75Mhz
K Factor
(1) K-Bar 1.5% 1% 1.5% 1% 1.5% ---- ---- ---- ----- ----- ----- -----
(2) K Pulse to Bar
2% 2% 2.5% 2% 2% ---- ---- ---- ----- ----- ----- -----
(3) K2T 1.5% 1.5% 1% 1.5% 1.5% ---- ---- ---- ----- ----- ----- -----
Differential Gain
- - - - - ---- ---- ---- ----- ----- ----- -----
Differential Phase
- - - -- --- ---- ---- ---- ----- ----- ----- -----
Signal to Noise Ratio
- - - ---- ---- ---- ---- ---- ----- ----- ----- -----
Vision Peak Pow.
100W 100W 500W 100W 500W 10W 10W 10W 10W 10W 10W 10W
Demodulator is not available at LPT, Sundernagar. VITS Generator is not available at LPT, Sundernagar, Mandi & Manali. DNL meter is not available at LPT, Mandi.
2.8 PERFORMANCE FIGURES OF TRANSMITTER (Contd…….) VLPT-
Udaipur VLPT
BijlimahadevVLPT-Nihri VLPT.Jhatingri VLPT Jhalman Remarks
Frequency of Vision Carrier
182.24Mhz 189.25Mhz 203.26Mhz 519.25Mhz 196.25 MHz
Frequency of Aural Carrier
187.74Mhz 194.75Mhz 208.76Mhz 524.75Mhz 201.75 MHz
K Factor ------ ------ ------ ------ ------
(1) K-Bar ------ ------ ------ ------ ------
(2) K Pulse to Bar ------ ------ ------ ------ ------
(3) K2T ------ ------ ------ ------ ------
Differential Gain ------ ------ ------ ------ ------
Differential Phase ------ ------ ------ ------ ------
Signal to Noise Ratio
------ ------ ------ ------ ------
Vision Peak Power 10W 10W 50W 50W 10 W
2.9 VIDEO FREQUENCY RESPONSE Freq (MHz) -1.25 -0.75 0.0 1.0 1.5 2.0 3.0 4.43 5.0 5.30 5.50 LPT Mandi DD-1 Gain in dB ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
LPT Mandi DD NEWS ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
LPT Kullu. ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
LPT Manali ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
LPT Sundernagar ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Kotli ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Chaturbhuja ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Sarkaghat ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Shivabadar, ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Banjar ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Diyar ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Keylong ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Jhalman ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Udaipur ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Bijlimahadev ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Nihri ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
VLPT Jhatingri ---- ---- ---- ---- --- ---- ---- ----- ----- ----- -----
2.10 AUDIO PERFORMANCE FIGURES
LPT
Mandi DD-1
LPT Mandi
DD News
LPT Kullu
LPT Manali
LPT Sundernagar
VLPTKotli
VLPT Chaturbhuja
VLPT Sarkaghat
VLPT Shivabadar
VLPT Banjar
VLPT Diyar
Aural Carrier
222.76Mhz
208.74Mhz
180.75Mhz
222.75Mz
532.76 Mhz
229.74Mhz
201.75Mhz
229.74Mhz
194.76Mhz
201.75Mhz
201.76Mhz
Frequency response
50 Hz to 15 KHz
---- ---- ---- ---- ---- --- --- ---- ---- --- ---
Distortion Factor
---- ---- ---- ---- ---- --- --- ---- ---- --- ---
F.M. Noise level
---- ---- ---- ---- ---- --- --- ---- ---- --- ---
Frequency Deviation at
100% Modulation
+ -50Khz
+ -50Khz
+ -50Khz
+ -50Khz
+ - 50Khz
2.11 AUDIO PERFORMANCE FIGURES ( Contd…)
VLPT
Keylong VLPT
Jhalman VLPT
Udaipur VLPT-
Bijlimahadev VLPT Nihri
VLPT Jhatingri
Aural Carrier 187.25Mhz
201.75Mhz
187.74Mhz
194.75Mhz 208.76Mhz
524.75Mhz
Frequency response
50 Hz to 15 KHz
---- ----- ----- ------ ---- ----
Distortion Factor ---- ----- ----- ------ ---- ----
F.M. Noise level ---- ----- ----- ------ ---- ----
Frequency Deviation at
100% Modulation
---- ----- ----- ------ ---- ----
2.11 WORKING STATUS OF 500W AUTO MODE TRANSMITTERS (Wherever applicable)
S.No. Name of LPT Xtr. Make,
Model, Channel
Whether Operating on Auto / Manual Mode
Details of Fault occurred
Current Working Status
(in detail)
Remarks
1 LPT Kullu BEL MVV-214, CH 5
Auto Mode ----- OK Sync is compressed in the Output of Demodulator since installation.
2.12 WORKING STATUS OF VLPTs (Wherever applicable) Sr. No.
Name of VLPT Ch. No.
Type of Transmitter
Rated Power
O/P Power
Reflected Power
Ex-1 Ex-2 PA1 PA2 ASU
1 VLPT Keylong CH#6. GCEL -126 10W 10W Negligible OK OK OK OK OK
2 VLPT Chaturbhuja CH#8. GCEL -126 10W 10W Negligible OK OK OK OK OK
3 VLPT Sarkaghat CH#12- GCEL -126 10W 10W Negligible OK OK OK OK OK
4 VLPT Diyar CH#8+ GCEL -126 10W 10W Negligible OK OK OK OK OK
5 VLPT Shivabadar CH#7+. GCEL -126 10W 10W Negligible OK OK OK OK OK
6 VLPT Kotli CH#12- GCEL -126 10W 10W Negligible OK OK OK OK OK
7 VLPT Jhalman CH#8. GCEL -126 10W 10W Negligible OK OK OK OK OK
8 VLPT Udaipur CH#6- GCEL -126 10W 10W Negligible OK OK OK OK OK
9 VLPT Banjar CH#8- GCEL -126 10W 10W Negligible OK OK OK OK OK
10 VLPT Nihri CH#9+ BEL-LVV-159 50W 10W Negligible OK OK OK OK U/R
11 VLPT Bijlimahadev CH#7. GCEL -126 10W 10W Negligible OK OK OK OK OK
12 VLPT Jhatingri CH#27. WEBEL-WML 50W 50W Negligible U/R OK OK OK OK
Sr. No.
Name of VLPT
Batteries (In circuit)
Solar Panel Battery Charger
Charge Controller
Installed Damaged Remark Installed Damaged Remark 1 VLPT
Keylong 12 Nos Nil Mtc. Free Batteries have
completed their normal working life period, new
batteries are reqd.
06 Nos Nil 03 modules have been stolen by the thieves report sent.
CEL make 24V/10A
CEL make
2 VLPT Chaturbhuja
12 Nos 03 Nos ---do-- 06 Nos Nil -- APLAB make,24V/25A
CEL make
3 VLPT Sarkaghat
12 Nos 01 No ---do-- 06 Nos Nil 31 modules have been stolen by the thieves on 14.03.10 ,11-06-2010 & 25-03-11 reportsent.
APLAB make,24V/25A
CEL make
4 VLPT Diyar 12 Nos Nil ---do-- 06 Nos Nil NEXUS make CEL make
5 VLPT Shivabadar
12 Nos 12Nos* ---do-- 06 Nos Nil APLAB make,24V/25A
CEL make
6 VLPT Kotli 24 nos Nil ------- 06 Nos Nil APLAB make,24V/25A
CEL make
7 VLPT Jhalman
12 Nos Nil Mtc. Free Batteries have completed their normal working life period, new
batteries are reqd.
06 Nos Nil APLAB make,24V/25A
CEL make
8 VLPT Udaipur
12 Nos Nil ---do-- 06 Nos Nil APLAB make,24V/25A
CEL make
9 VLPT Banjar 12 Nos Nil ---do-- 06 Nos Nil 16 modules have been installed in
place of stolen one.
APLAB make,24V/25A
CEL make
10 VLPT Nihri 24Nos Nil ------- 06 Nos Nil APLAB make,24V/25A
CEL make
11 VLPT Bijlimahadev
24 Nos Nil --------- 06 Nos Nil APLAB make,24V/25A
CEL make
12 VLPT Jhatingri
36 Nos ---- Mtc. Free Batteries have completed their normal working life period, new
batteries are reqd.
06 Nos Nil APLAB make,24V/25A
CEL make
*At VLPT Shivabadar all installed mtc. Free cells have become defective.Transmitter running on A/C supply. New batteries are reqd. urgently.
2.13 EARTH RESISTANCE (in Ohms)
Station XTr
EARTH PS
EARTH DG Set PDA-1 PDA-2 TOWER Date of
measurement Make, Model and type of Instrument used for measurement
LPT Mandi DD-1 0.2 0.3 0.3 0.53 0.40 ---- 15.01.2012 WACO make
LPT Mandi DD News 0.4 0.2 0.1 1.0 -- 0.3 15.1.2012 ---do--
LPT Kullu 2.0 2.0 2.0 3.5 3.0 3.50 28.08.11 CIE make
LPT Manali 0.85 1.3 1 1.3 1.4 0.5 20.06.11 CIE make
LPT Sundernagar 1.69 2.81 1.69 9.79 11.92 2.75 28.01.12 MOTWANE make
VLPT Kotli 1.5 - - 1.02 --- 5 WACO make
VLPT Chaturbhuja 1.2 -- --- 4.3 --- 2.3 05-10-11 --do--
VLPT Shivabadar 10 --- ---- 28 --- 9 04-10-11 --do--
VLPT Sarkaghat 1.41 ---- --- 4.21 ---- 5.10 --do--
VLPT Banjar 2.5 2.5 ---- 4.5 ---- 2.5 --do-- --do--
VLPT Diyar 3.5 ---- ---- 5.18 ---- 2.95 -do- --do--
VLPT Keylong 6 ---- ---- 6.25 ---- 14 -do-- --do--
VLPT Jhalman 6.5 ---- ---- 6.5 --- 6.8 --do-- --do-- VLPT Udaipur 0.8 ---- ---- 0.9 ---- 0.7 --do-- --do-
VLPT Bijlimahadev 4.90 1.75 ---- 4.9 - --- 4.70 MOTWANE make
VLPT Nihri 4.4 --- ---- 8.8 5.6 06-09-11 Waco Make
VLPT Jhatingri 1.2 ----- --- 1.8 1.9 6.0 05-10-11 --do--
Minimum one new earth pit is required at each LPT Sundernagar & 12 VLPTs.
& SPARES
3.1 REQUIREMENT OF SPARE COMPONENTS Station Name of
Component Part No. Name of Unit of
transmitter for which required
Quantity Required
Qty available at Station
Qty issued to Station during last six months
Justification for requirement
LPT Mandi
RF Tr. UMIL 100A 613510280184 P.A ,50W 08 Nos Nil Nil As spare for 50w P.A RF Tr. MRF329 613510280205 P.A, 50W 06 Nos Nil Nil For repair of P.A Chip Capacitor 470pf/200VDC
---- P.A, 50W 08 Nos Nil Nil As repair of P.A
LPT Kullu
MOSFET IM0365 ---- For Minisat IRD 04 Nos Nil Nil For repair of def. receiver
LPT Sundernagar
MOSFET543W ---- Driver of 300W P.A
02 Nos Nil Nil As spare
MOSFET 544P ---- ----DO--- 02 Nos Nil Nil ----do-- MOSFET 544B ---- ---DO-- 02Nos Nil Nil ----do--- MOSFET MRF377 ---- For P.A 04Nos Nil Nil ----do--
VLPT Nihri MOSFET GIXYA-DSE-160/66/4
101289921 For Battery Charger
06 Nos Nil Nil For repair of Statcon battery charger
Diode BY-321X ----do--- 06 Nos Nil Nil --do--
VLPT Jhatingri
RF Tr. PTB20101 613510700116 For P.A 02Nos Nil Nil For repair of 50W P.A RF Tr. UTV 200 IC HPT/VDA GMC 061
110800002807
For PA 50W For WML Exciter
02 Nos 02Nos
Nil Nil
Nil Nil
---do— For Video Input Processor
DMC Mandi
IC Hybrid Amp. BGY55
For use at VLPTs
06 Nos Nil Nil For 10W P.A
Microprocessor 8085/8255
----do---- 12 Nos Nil Nil For ASU
IC 5407 ----do--- 12 Nos Nil Nil ---do--
3.2 REQUIREMENT OF SPARE EQUIPMENTS / CARDS / MODULES Station Name of Equipment /
Card / Module Part No. Name of Unit of
transmitter for which required
Quantity Required
Qty availab
le at Station
Qty issued to Station
during last six months
Justification for requirement
LPT Mandi.
SMPS 28V/25A For GCEL 121-1 XTr.
03Nos NIL NIL Old linear type PSUs gives frequent troubles.
Synth. Local Oscillator 110600469606 For GCEL EXCITER 129-4
01 Nos NIL NIL Old one faulty since installation
Amplifier Board 110600411608 For 50W PA 02 Nos NIL NIL As spare for PA W/Form Monitor ----- ----- 01Nos NIL NIL Due to very poor display of
old W/FORM MON LPT Sundernagar
Power Amp. 300W UHF Class AB
01 Nos NIL NIL As spare for UHF XTr.
LPT KULLU.
Relay board PCB-1 & PCB-2 & Relay PCB-3 for the SCU bypass unit
11400230579PL
500 W Auto XTr ( 1+1) BEL MVV-214
01 no each
Nil Nil As Spare
PCB Assy SCU Control Board -2 ( PCB-3)
114002973151 PL 500 W Auto XTr ( 1+1) BEL
01 no NIL NIL As spare
PCB Assy RF Switch & PPC ( PCB-1)
114002537718 PL 500 W Auto XTr ( 1+1) BEL
01 no Nil Nil As spare
PCB Assy Key Board –II (PCB-2)
114002526563 PL 500 W Auto XTr ( 1+1) BEL
01 no Nil Nil As spare
VSB Modulator Card
114002289980 500 W Auto XTr ( 1+1) BEL
01 no Nil Nil Spare card may be provided.
AVR Servo, 10KVA ----- ------ 01No Nil Nil Spare AVR not provided.
VLPT Nihri PA Control Card BEL –LVV 159
50 watt PA 01 no Nil Nil In place of defective one
which is beyond repairs. PSU Control Board 1140 024 27429 BEL –LVV 159
50 watt PA 01 no Nil Nil In place of defective one
which is beyond repairs.
LPT Manali Servo AVR, 10 KVA Digital Earth Tester
----
----- 01 no 01 No
NIL Nil
Nil Nil
Old AVR giving problems
LPT Sundernagar
AVR 4KVA for Air conditioner
---- ----- 03 Nos *03 Nos
Nil Two no AVRs are faulty & local repair is not possible.
VLPT Jhatingri
Video Input Processor ------- For WML Exciter
01 No 02 Nos Nil One no module is under repair & spares are not available locally.
3.3 AVAILABILITY OF SPARE –COMPONENT/MODULES/TXR UNITS Spare Components
Station Name of Spare Component
Qty. in Stock Working Status
Spare Transmitter Modules
Station Name of Spare
Transmitter Modules (pallets)
Qty. in stock Working Status
LPT Kullu
Driver Pallet 01Nos OK Hybrid Amp. 01Nos OK
Rectifier Board 01Nos OK VSB Modulator Nil Nil PA Control Card 01 No* Faulty** PA Pallet 360w 01No OK
**Card was sent to Zonal Office for repair but fault still persists.
Spare Transmitter Units Station Name of Spare
Transmitter Unit Qty. in Stock Working Status
LPT Mandi PA 50W 01Nos OK Driver Amp. 10W 01Nos OK
LPT Mandi(DD-News) PA 50W 01Nos Under repair LPT Kullu SMPS Unit 01Nos OK Old 100w BEL XTr 01Nos OK (As Spare) LPT Manali Driver Unit 10W 01 Nos OK PA Unit 50W 01Nos OK VLPT Keylong PA Unit 10W 01Nos OK VLPT Chaturbhuja ---- ---- ---- VLPT Sarkaghat PA Unit 10W 01Nos OK VLPT Diyar PA Unit 10W 01Nos OK VLPT Shivabadar PA Unit 10W 01Nos OK VLPT Kotli PA Unit 10W 01Nos OK VLPT Jhalman PA Unit 10W 01Nos OK VLPT Udaipur PA Unit 10W 01Nos OK VLPT Banjar PA Unit 10W 01Nos OK VLPT Nihri ----- ----- ----- VLPT Bijlimahadev PA Unit 10W 01Nos OK VLPT Jhatingri PA Unit 50w 01Nos U/R
3.3 DETAILS OF DEFECTIVE TRANSMITTER EQUIPMENT
Make & Model of
Transmitter Name of defective
Tx equipment
Since when it is defective
Action taken by Station for the repair
Shortcoming if any, being faced by station for the
repair
Remarks
GCEL 126(VLPT Sarkaghat)
ACS Since 2006 Burnt badly due to lightning beyond repair
Replacement is reqd.
WEBEL Make UHF Txr.(VLPT JHATINGRI)
ACS Video Input Processor
PA 50 Watts CH#27.
Since2007 Since
Aug,2011 Since June
2009
Burnt badly due to lightning beyond repair
IC GMC 061 is reqd. RF TR. UTV 200 & PTB
20101 are reqd.
Spares not available locally.
---Do---
Replacement is reqd.
Replacement may be provided.
--Do-- LPT Mandi. DD News PA 50watts ,CH#9
Since Dec.2010
RF Tr. MRF 329 & Chip Cap. Are reqd.
Spare components not available locally
Req. spares or replacement may be
provided. Synth. Local
oscillator Since
Installation, Sent to ZO workshop ,returned with remarks beyond repair
Replacement may be provided.
3.4 WORKING STATUS OF AVR FOR TRANSMITTER
Station Capacity of AVR
Make and Type Working Condition ( Auto/Manual/def)
Action Taken for repair, if defective
LPT Mandi(DD-1) 05KVA Toshniwal make,SVS 605 Auto* New 10KVA AVR is reqd LPT Mandi (DD News) 10KVA PCI Sylvan Auto --
LPT Kullu 10KVA Sylvan ,Servo type Auto -- LPT Manali 5 KVA Toshniwal, SVS 605 Auto* New 10KVA AVR is reqd.
LPT Sundernagar 15KVA 10KVA
Cybex make PCI make
Auto
-- .
3.5 WORKING STATUS OF DIESEL / PETROL / KEROSENE GENERATOR SETS AT LPTs / VLPTs Station Capacity of Generator Make, Model and Type Working
Condition
Action Taken for repair, if defective
LPT Mandi DD-1&DD News
10KVA 15KVA
Kirloskar HA294
OK --
LPT Kullu 5KVA,12.5KVA,25KVA Kirloskar HA294,HA394
OK --
LPT Manali 10KVA*&5KVA Kirloskar;HA394&TA-2 0K -- --LPT S/nagar 15KVA Kirloskar,HA294-II OK -- VLPT Kotli 2KVA HONDA OK - VLPT C/Bhuja 2KVA HONDA OK - VLPT Shivabadar 2KVA HONDA OK - VLPT Sarkaghat 2KVA HONDA OK - VLPT Banjar 2KVA HONDA OK - VLPT Diyar 2KVA HONDA OK - VLPT Keylong 2KVA HONDA OK - VLPT Jhalman 2KVA HONDA OK - VLPT Udaipur 2KVA HONDA OK - VLPT Bijlimahadev 2KVA HONDA OK -
VLPT Jhatingri 2KVA HONDA OK - VLPT Banjar. 2KVA HONDA OK -
3.6 TVRO ELECTRONICS
Station Make &
Type of IRDs
Total No. available
Total No. Defective
Action taken by Station for
repair
Remarks
LPT Mandi(DD-1) SCOPUS DVB2800
02 Nos Nil
LPT Mandi(DD-N) SCOPUS DVB2800
02 Nos Nil
LPT Kullu SCOPUS DVB2800
04 Nos 01Nos Under repair IRF 0365 is reqd.
LPT Sundernagar SCOPUS DVB2800
02 * Nos Nil *Front end card of one receiver faulty.
LPT Manali. SCOPUS DVB2800
02 Nos Nil
3.7 UPS
Station Make, Model
& Rating of UPS
Total No. available
Total No. Defective
Action taken by Station for
repair
Remarks
LPT Mandi APC 0.5KVA 01 No -- - -- LPT Kullu APC,0.8KVA 03Nos 01No Under repair --
Emerson make ,6KVA
01Nos -- -- -
Emerson,1KVA 01Nos -- -- -- LPT Manali APC 0.5KVA 01 No -- -- --
LPT Sundernagar
APC 0.5KVA 01 No -- -- --
3.8 AIRCONDITIONERS & AVRs
Station Total
No. at Station
Defective Nos.
Make and Model of defective
Date from which
defective
Reason for Being
defective
Action taken by Station for the repair
Airconditioner LPT Mandi. 06 Nos 01 No Sidwal,Widow Type,
27-08-2011.
Compressor faulty.
Being repaired.
AVRs for ACs 05 Nos Nil - -- -- -
Airconditioner LPT Kullu 04 Nos 01 No Split Type,Voltas
20-01-12 No cooling Being repaired
AVRs for ACs 03 Nos Nil - -- -- -
Airconditioner LPT Manali. 04 Nos Nil -- ---- --- --
AVRs for ACs 02 Nos Nil ---- ---- ---- ----
Airconditioner LPT Sundernagar
03 Nos Nil Nil Nil .
AVRs for ACs 03 Nos 02 Nos Electrocom
4 kva -- Spare
components N/A locally
-
3.9 DETAILS OF DEFECTIVE INPUT / MONITORING AND MEASURING EQUIPMENTS
Station Name of defective
equipment
Make and model of defective
equipment
Date from which
defective
Action taken by Station for the repairing
LPT Mandi. Waveform Monitor
Tektronics,528A Since 2007 Sent to Zonal office for repair.Received with
remarks that it is beyond repair
Demodulator BEL Make Demodulator has very poor frequency stability
since its receipt 1.Waveform
Monitor DD News 2.Color Monitor
3.Color TV
Philips make,5665
Sony Make ---do---
Since July 2007 Since
Dec,2009 Nov,2010
Very Low illumination.Graticule
lamps28V/60ma are reqd. Picture tube faulty.
----do----- LPT Kullu Demodulator BEL Make,YUB418 Since
installation Fault was brought to the notice of BEL Engineers, but they could not rectify
it. LPT Manali. GCEL Color
monitor CM-33 GCEL,CM33 Very old & are beyond
repair. SONY make color
Monitor Sony make Since
Dec,2009 One of electron gun
faulty.Replacement of picture tube is reqd.N/A
locally. LPT
Sundernagar Color Stab Amp. BEL,SCSA-2A Intermittent nature of fault
Thru line wattmeter
Bird make 15-09-1998 Local repair is not possible
Color TV Samsung make and BPL make
------ CTV provided have completed their normal
working period,replacement reqd.
3.10 WORKING FIGURES OF DIESEL GENERATORS For LPTs only
LPTMandi LPT Kullu. LPT Manali LPT Sundernagar
DD-1 DD-News
Make Kirloskar make Kirloskar make Kirloskar make Kirloskar make
Capacity 10KVA 15KVA 25KVA 12.5KVA
10KVA 5KVA
15KVA
Utilization for transmission during the month
---- 12.16 Hrs 18.58 Hrs ----- 55.00 hrs 28.25 hrs 11.92 Hrs
Test Hrs. for the month 6.33Hrs 5.33 Hrs 2.53 Hrs ---- 5.17 hrs 5.17 Hrs
5.34 Hrs
Total Working Hrs. for the month
6.33 Hrs 17.49 Hrs 21.11 Hrs ---- 60.17 hrs 33.42 Hrs 17.26Hrs
Progressive utilization for Transmission
8.91 Hrs 45.15Hrs 82.69 Hrs 129.60 hrs 112.37 hrs 153.33Hrs
Occasion of utilization during the month
-------- 06 Nos 15 Nos ----- 22 nos 17 No 27 Nos
Progressive occasion of Utilization
12 no 50Nos 154 Nos ----- 85 nos 54 nos 389 Nos
Breakdown in service due to failure of D/G during the month
-- ----- ---- ----- -------
Average consumption of Diesel
1.5Ltr/Hr 2 Lt/Hrs 2.27 Ltr/Hr ----- 2.09ltr/hr 1.16ltrs/hr 2.05 Lt/Hrs
Date of commissioning of DG set
7-1-89 3.7.2000 16.07.07 14.7.97 Aug 1990 Oct1989 15.09.98
Total Hours of working since date of commissioning
3851.72 Hr 219.69Hr 597.82 Hrs 2859.18 9274.39Hrs 2861.01Hr 3948.55Hrs
Reading of Hour Meter installed at DG Set at the end of month
186.08 1905.91 102.58Hrs 1357.1hr ----- 1574.27Hrs
Reading of Hour Meter installed at LT Panel at the end of month
38465.80 31093.6Hrs ---- 29565 Hrs ----
-----
4. CABLE OPERATORS MONOITORING REPORT Month January ,2012 S.N.
Name of Cable Operator Channel on which DD service given Tech. Qua- -lity
Remarks
Prime Band Channel Non Prime Band Channel DD-
National DD- News
DD- Regional/ Bharati
DD- Sports
DD- Urdu
DD- RS/LS
Gyan Darshan
DD- *Bharti
1. M/s Suket Satellite Transmission Bhojpur ,Sundernagar
Yes Ch#9
Yes Ch#3
Yes Ch#4 (Reg)
Yes 40
Yes S- 20
Yes/Yes Z+1/S-02
Yes S-6
Yes S-4
Ok
2. Rajat Network,Manali Yes Ch#2
Yes Ch#1
Yes Ch#3
Yes S-34
No No/Yes ---/S-3
No --- Ok
3. Sanjha Communication ,Patlikuhal
Yes Ch#3
Yes Ch#2
Yes Ch#10
Yes CH # X
No No/Yes ---/CH #4
Yes CH # 4
---- Ok
4. Bridgeview broadband Network Pvt.Ltd Manali
Yes Ch#3
Yes Ch#2
Yes Ch#4
Yes S#38
No No/Yes ---/E-21
No ---- Ok
5. Navrang cable,Shastri Nagar,Kullu
Yes Ch#2
Yes Ch#7
Yes Ch#12
Yes S-10
No No/No Yes S-32
----- Ok
6. Kullu Communication Kullu
Yes Ch#2
Yes Ch#3
Yes Ch#12
Yes S-32
No No/No Yes S-25
---- Ok
7. Wire Communication System Mandi
Yes Ch#3
Yes Ch#2
Yes /Yes Ch#3/CH#
3
Yes S-42
No No/Yes -/Ch#4
Yes S#3
--- Ok
For specified state / stations where service is available