Upload
vanxuyen
View
258
Download
1
Embed Size (px)
Citation preview
Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services
MOVIDRIVE® MDX61BDFD11B Fieldbus InterfaceDeviceNet
Manual
FA361530
Edition 11/200411284412 / EN
SEW-EURODRIVE – Driving the world
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet 3
1 Important Notes...................................................................................................... 4
2 Introduction ............................................................................................................ 5
3 Assembly / Installation Instructions..................................................................... 73.1 Installing the DFD11B option card ................................................................. 73.2 Connection and terminal assignment............................................................. 93.3 Setting the DIP switches .............................................................................. 113.4 Display of operating status DFD11B option card ......................................... 12
4 Project Planning and Startup.............................................................................. 144.1 Startup of the drive inverter.......................................................................... 144.2 Building the DeviceNet network with the RSNetWorx software ................... 174.3 Process data exchange ............................................................................... 184.4 Parameter data exchange............................................................................ 224.5 Return codes for parameter setting.............................................................. 28
5 Sample Application with PLC Type SLC500...................................................... 295.1 Exchange of polled I/O (process data)......................................................... 315.2 Exchange of bit-strobe I/O ........................................................................... 345.3 Exchanging explicit messages (parameter data) ......................................... 35
6 Technical Data...................................................................................................... 406.1 DFD11B option ............................................................................................ 40
7 Appendix............................................................................................................... 417.1 General error codes (error messages)......................................................... 417.2 Statement of Conformance .......................................................................... 427.3 Definitions of terminology............................................................................. 51
8 Index...................................................................................................................... 52
00
I
Pi
fkVA
Hz
n
4
1 mportant Notes
Handbuch1 Important Notes
Documentation • Read through this manual carefully before you start installation and startup ofMOVIDRIVE® drive inverters with the DeviceNet DFD11B option card.
• This manual assumes that the user has access to and is familiar with theMOVIDRIVE® documentation, in particular the MOVIDRIVE® MDX60B/61B systemmanual.
• In this manual, cross references are marked with "→". For example, (→ Sec. X.X)means: Further information can be found in section X.X of this manual.
• A requirement of fault-free operation and fulfillment of any rights to claim underguarantee is that you observe the information in the documentation.
Bus systems General safety notes on bus systems:
This communication system allows you to adjust the MOVIDRIVE® drive inverter to yourspecific application very accurately. As with all bus systems, there is a danger of invisi-ble, external (as far as the inverter is concerned) modifications to the parameters whichgive rise to changes in the inverter behavior. This may result in unexpected (not uncon-trolled) system behavior.
Safety and warning notes
Always observe the safety and warning instructions contained in this publication!
• This manual does not replace the detailed operating instructions!
• Only specialists are allowed to perform installation and startup observingrelevant accident prevention regulations and the MOVIDRIVE® MDX60B/61Boperating instructions!
Electrical hazardPossible consequences: Severe or fatal injuries.
Hazard Possible consequences: Severe or fatal injuries.
Hazardous situationPossible consequences: Slight or minor injuries.
Harmful situationPossible consequences: Damage to the unit and the environ-ment.
Tips and useful information.
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
2Introduction
2 IntroductionContents of this manual
This user manual describes how to install the DeviceNet DFD11B option card in theMOVIDRIVE® MDX61B drive inverter and how to start up MOVIDRIVE® with theDeviceNet fieldbus system.
Besides explaining all settings on the fieldbus option card, this document also coversthe various DeviceNet connection variants in the form of brief startup examples.
Additional documentation
For a simple and effective connection of MOVIDRIVE® to the DeviceNet fieldbussystem, you should request the following publications from SEW-EURODRIVE aboutthe fieldbus technology in addition to this manual:
• MOVIDRIVE® Fieldbus Unit Profile manual
• MOVIDRIVE® MDX60/61B system manual
The manual for the MOVIDRIVE® fieldbus unit profile describes the fieldbus parametersand their coding, as well as explaining the whole range of control concepts and applica-tion options in the form of brief examples.
The parameter list is a list of all drive inverter parameters that can be read and writtenvia various communication interfaces such as RS-485, SBus and even the fieldbusinterface.
MOVIDRIVE® and DeviceNet
The MOVIDRIVE® MDX61B drive inverter together with the DFD11B option and its high-performance universal fieldbus interface enable the connection to higher-level automa-tion systems via the open and standardized DeviceNet fieldbus system.
Unit profile The performance of the inverter, referred to as the unit profile, that forms the basis forthe DeviceNet operation, is fieldbus-independent and, therefore, uniform. This allowsthe user to develop fieldbus-independent drive applications. This makes it much easierto change to other bus systems, such as PROFIBUS (DFP 21B option) or INTERBUS(DFI11B option).
Drive parameters MOVIDRIVE® offers you direct access to all drive parameters and functions via theDeviceNet interface. The drive inverter is controlled via the fast, cyclical process data.Via this process data channel, you have the opportunity of entering setpoints such asthe setpoint speed, ramp generator time for acceleration/deceleration, etc. as well astriggering various drive functions such as enable, control inhibit, standard stop, rapidstop, etc.
At the same time you can also use this channel to read back actual values from the driveinverter, such as actual speed, current, unit status, error number or reference signals.
Polled I/O and Bit Strobe I/O
The parameters of the inverter are set exclusively using Explicit Messages, whereas theprocess data exchange is replicated on the DeviceNet services Polled I/O andBit-Strobe I/O. This parameter data exchange enables you to implement applications inwhich all the important drive parameters are stored in the master programmable control-ler, so that there is no need to make manual parameter settings on the drive inverter it-self.
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
56
2 ntroduction
Startup Every DFD11B DeviceNet option card is designed so that the fieldbus-specific MAC-IDand baud rate settings are made using hardware switches on the option card. This man-ual setting means the drive inverter can be integrated into the DeviceNet system andswitched on quickly.
The parameter setting process can be performed in a completely automated process bythe DeviceNet master (parameter download). This forward-looking variant shortens thesystem startup time and simplifies the documentation of your application programbecause all the important drive parameters can now be stored directly in your controlprogram.
Monitoring functions
The use of a fieldbus system requires additional drive system monitoring such as timemonitoring of the fieldbus (fieldbus timeout) or even special emergency stop concepts.The MOVIDRIVE® MDX61B monitoring functions can be customized to your applica-tion. You can determine, for instance, which of the drive inverter error responses shouldbe triggered in the event of a bus error. A rapid stop is a good idea for many applications,although this can also be achieved by "freezing" the last setpoints so the drive continuesoperating with the most recently valid setpoints (for example, conveyor belt). As thefunctions of the control terminals are still active in fieldbus operation, you can still imple-ment fieldbus-independent emergency stop concepts via the terminals of the driveinverter.
Diagnostics The MOVIDRIVE® MDX61B drive inverter offers numerous diagnostic options for start-up and service.
For example, you can use the integrated fieldbus monitor to check both the setpointssent by the master control and the actual values. The MOVITOOLS® software packageoffers a convenient diagnostic option that allows for a detailed display of fieldbus anddevice state information in addition to the settings of all drive parameters (including field-bus parameters).
55215AXXFigure 1: DeviceNet with MOVIDRIVE® MDX61B and PLC
SPS
4
1 2 3
5 6
7 8 9
+/- 0 .
MOVIDRIVE® MDX61B
MOVIDRIVE®
Communication Interface
Node_4
[4]
4
1 2 3
5 6
7 8 9
+/- 0 .
4
1 2 3
5 6
7 8 9
+/- 0 .
MOVIDRIVE® MDX61B MOVIDRIVE® MDX61B
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3Installing the DFD11B option cardAssembly / Installation Instructions
3 Assembly / Installation Instructions3.1 Installing the DFD11B option card
The DFD11B option card must be plugged into the fieldbus slot [1].
Before you begin Observe the following notes before installing or removing an option card:
• Disconnect the inverter from power. Switch off the 24 VDC and the supply voltage.
• Take appropriate measures to protect the option card from electrostatic charge (usedischarge strap, conductive shoes, etc.) before touching it.
• Before installing the option card, remove the keypad and the front cover.
• After installing the option card, replace the front cover and the keypad.
• Keep the option card in its original packaging until immediately before you are readyto install it.
• Hold the option card by its edges only. Do not touch any components.
• MOVIDRIVE® MDX61B must have firmware status 824 854 0.11 or above. You candisplay the firmware status using parameter P076.
• Only SEW-EURODRIVE engineers can install or remove option cards forMOVIDRIVE® MDX61B size 0.
• Option cards can only be installed and removed for MOVIDRIVE® MDX61Bsizes 1 to 6.
54703AXX
[1]
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
78
3 nstalling the DFD11B option cardssembly / Installation Instructions
Basic procedure for installation/removing an option card
1. Remove the retaining screws holding the card retaining bracket. Pull the cardretaining bracket out evenly from the slot (do not twist!).
2. Remove the retaining screws of the black cover plate on the card retaining bracket.Remove the black cover plate.
3. Position the option card onto the retaining bracket so that the retaining screws fit intothe corresponding bores on the card retaining bracket.
4. Insert the retaining bracket with installed option card into the slot, pressing slightly soit is seated properly. Secure the card retaining bracket with the retaining screws.
5. To remove the option card, follow the instructions in reverse order.
53001AXXFigure 2: Installing an option card in MOVIDRIVE® MDX61B sizes 1 to 6 (schematic diagram)
1.
3.
4.
2.
IA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3Connection and terminal assignmentAssembly / Installation Instructions
3.2 Connection and terminal assignment
Part number DeviceNet fieldbus interface type DFD11B: 824 972 5
The "DeviceNet interface type DFD11B" option is only possible in conjunction withMOVIDRIVE® MDX61B, not with MDX60B.
The DFD11B option must be plugged into the fieldbus slot.
Front view of DFD11B
DescriptionDIP switchTerminal
Function
54193AXX
Mod/Net = Module/network statusPIO - Polled I/OBIO - Bit-Strobe I/OBUSOFF
The two-color LEDs display the current status of the fieldbus interface and the DeviceNet system:
Six DIP switches for setting of the MAC-ID
Five DIP switches for setting the process data length
Two DIP switches for setting the baud rate
F1 ... F3: No Function
NA(5) ... NA(0)
PD(4) ... PD(0)
DR(1) ... DR(0)
Setting the MAC-ID (Media Access Control Identi-fier)
Setting the process data length (1 ... 10 words)
Setting the baud rate:00 = 125 kBaud01 = 250 kBaud10 = 500 kBaud11 = Invalid
X30: DeviceNet connection X30:1X30:2X30:3X30:4X30:5
V–CAN_LDRAINCAN_HV+
DFD 11B
MOD/Net
BUS-OFF
0 1
PIO
NA(5)NA(4)NA(3)NA(2)NA(1)
DR(1)DR(0)PD(4)PD(3)PD(2)PD(1)PD(0)F3F2F1
1
2
3
4
5
NA(0)
S1
S2
X30
BIO
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
910
3 onnection and terminal assignmentssembly / Installation Instructions
Pin assignment The assignment of connecting terminals is described in the DeviceNet specification(Volume I, Appendix A).
The DFD11B option card is opto-decoupled on the driver side in accordance with theDeviceNet specification (Volume I, Chapter 9). This means the CAN bus driver must bepowered with 24 V voltage via the bus cable. The cable to be used is also described inthe DeviceNet specification (Volume I, Appendix B). The connection must be madeaccording to the color code specified in the following table.
Shielding and routing of bus cables
The DeviceNet interface supports RS-485 communications protocol and requires cabletype A specified for DeviceNet in accordance with EN 50170 as shielded, twisted-paircable for the physical connection.
Correct shielding of the bus cable attenuates electrical interference that may occur inindustrial environments. The following measures ensure the best possible shielding:
• Tighten the mounting screws on the connectors, modules and equipotential bondingconductors by hand.
• Attach the shielding of the bus line over a large surface on both sides.
• Do not route signal and bus cables parallel to power cables (motor leads). They mustbe routed in separate cable ducts.
• Use metallic, grounded cable racks in industrial environments.
• Route the signal cable and the corresponding equipotential bonding in close proxim-ity using the shortest way possible.
• Avoid using plug connectors to extend bus cables.
• Route the bus cables closely along existing grounding surfaces.
Bus termination In order to avoid disruptions in the bus system due to reflections, each DeviceNet seg-ment must be terminated with 120 Ω bus terminating resistors at the first and last phys-ical station. Connect the bus terminating resistor between connections 2 and 4 of thebus plug.
54075AXX
Pin no. Signal Meaning Color coding
1 V– 0V24 BK
2 CAN_L CAN_L BU
3 DRAIN DRAIN Bright
4 CAN_H CAN_H WH
5 V+ 24 V RD
DFD11B
1
2
3
4
5
DFD11B
X30
In case of fluctuations in the earth potential, a compensating current may flow via thebilaterally connected shield that is also connected to the protective earth (PE). Makesure you supply adequate equipotential bonding according to relevant VDE regulationsin such a case.
CA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3Setting the DIP switchesAssembly / Installation Instructions
3.3 Setting the DIP switches
Setting the MAC-ID
The MAC-ID (Media Access Control Identifier) is set on the DFD11B option card withDIP switches S1-NA0...S1-NA5. The MAC-ID represents the node address of theDFD11B. MOVIDRIVE® supports the address range 0 ... 63.
Setting the baud rate
The baud rate is set with DIP switches S2-DR0 and S2-DR1.
Setting the pro-cess data length
Up to ten DeviceNet data words can be exchanged between the DeviceNet interfacemodule and the DFD11B; these data words can be distributed to the process data chan-nel with DIP switches S2-PD0 to S2-PD4.
Before changing a DIP switch setting, disconnect the drive inverter from power (supplyvoltage and 24 V backup operation). The DIP switch settings are adopted during initial-ization of the driver inverter only.
DIP switch S2Baud rate
DR1 DR0
0 0 125 kBaud
0 1 250 kBaud
1 0 500 kBaud
1 1 Obsolete
[1] Setting the MAC-ID
[2] Setting the baud rate
[3] Setting the process data length
[4] No Function
The figure depicts the following settings:
MAC-ID: 4
Baud rate: 125 kBaud
Process data length: 8 PD
54078AXX
0 1NA5NA4NA3NA2NA1NA0
S1
DR1DR0PD4PD3PD2PD1
S2
PD0
[1]
[2]
[3]
F3F2F1
[4]
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
1112
3 isplay of operating status DFD11B option cardssembly / Installation Instructions
3.4 Display of operating status DFD11B option card
The DFD11B option card is equipped with four two-color LEDs for diagnostics of theDeviceNet system; these indicate the current status of the DFD11B and the DeviceNetsystem.
LED Mod/Net The function of the LED Mod/Net described in the following table is contained in theDeviceNet specification.
PIO LED The PIO LED checks the polled I/O connection.
LED abbreviation Complete LED designation
Mod/Net Module/Network Status
PIO Polled I/O
BIO Bit-Strobe IO
BUS-OFF BusOff
State Status Meaning
Off Not switched on / OffLine • Unit is offline• Unit is performing DUP-MAC check• Unit is switched off
Flashes green(1 s cycle)
Online and in operational mode
• The unit is online and no connection has been established
• DUP-MAC check was performed successfully• A connection has not yet been established with a
master• Missing, incorrect or incomplete configuration
Green light Online, operational mode and connected
• Online• Connection has been established with a master• Connection is active (established state)
Flashes red(1 s cycle)
Minor fault or connection timeout
• A correctable error has occurred• Polled I/O or/and bit-strobe I/O connections are in
timeout state• DUP-MAC check has detected an fault
Red light Critical fault or critical link failure
• A correctable error has occurred• BusOff• DUP-MAC check has detected an fault
State Status Meaning
Flashes green(125 ms cycle)
DUP-MAC check Unit is performing DUP-MAC check
Off Not switched on / offline but not DUP-MAC check
• Unit is offline• Unit is switched off
Flashes green(1 s cycle)
Online and in operational mode
• Unit is online• DUP-MAC check was performed successfully• A PIO connection is being established with a master
(configuring state)• Missing, incorrect or incomplete configuration
Green light Online, operational mode and connected
• Online• A PIO connection has been established (established
state)
Flashes red(1 s cycle)
Minor fault or connection timeout
• A correctable error has occurred• Polled I/O connection is in timeout state
Red light Critical fault or critical link failure
• A non-correctable fault has occurred• BusOff• DUP-MAC check has detected an fault
DA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3Display of operating status DFD11B option cardAssembly / Installation Instructions
LED BIO The BIO LED checks the bit-strobe I/O connection.
BUS-OFF LED The BUS-OFF LED displays the physical status of the bus node.
State Status Meaning
Flashes green(125 ms cycle)
DUP-MAC check Unit is performing DUP-MAC check
Off Not switched on / offline but not DUP-MAC check
• Unit is offline• Unit is switched off
Flashes green(1 s cycle)
Online and in operational mode
• Unit is online• DUP-MAC check was performed successfully• A BIO connection is being established with a master
(configuring status)• Missing, incorrect or incomplete configuration
Green light Online, operational mode and connected
• Online• A BIO connection has been established (established
state)
Flashes red(1 s cycle)
Minor fault or connection timeout
• A correctable error has occurred• Bit-strobe I/O connection is in timeout state
Red light Critical fault or critical link failure
• A non-correctable fault has occurred• BusOff• DUP-MAC check has detected an fault
State Status Meaning
Off NO ERROR The number of bus errors is in the normal range (error active status).
Flashes red(125 ms cycle)
BUS WARNING
The unit is performing a DUP-MAC check and cannot send any messages because no other stations are connected to the bus (error passive state).
Flashes red(1 s cycle)
The number of physical bus errors is too high. No more error telegrams are actively written to the bus (error pas-sive state).
Red light BUS ERROR • BusOff status• The number of physical bus errors has increased
despite a switch to the error-passive state. Access to the bus is deactivated.
Yellow light POWER OFF External voltage supply has been turned off or is not con-nected.
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
1314
4 tartup of the drive inverterroject Planning and Startup
4 Project Planning and StartupThis section describes how to configure and start up the MOVIDRIVE® MDX61B driveinverter with the DFD11B option.
4.1 Startup of the drive inverter
You can immediately configure the MOVIDRIVE® drive inverter after installation of theDFD11B option and setting of the baud rate and MAC-ID via the fieldbus system withoutadditional manual settings. In this way, you can download all drive parameters from themaster programmable controller directly via DeviceNet after the power is switched on.
However, to control the drive inverter via the DeviceNet system, you must first switchthe drive inverter to the control signal source and setpoint source = FIELDBUS. TheFIELDBUS setting means the inverter parameters are set for control and setpoint trans-fer from the fieldbus. The drive inverter then responds to the process output data sentby the master programmable controller.
Activation of the control signal source/setpoint source FIELDBUS is signaled to thehigher-level controller using the "Fieldbus mode active" bit in the status word. For safetyreasons, the drive inverter must also be enabled at the terminals for control via the field-bus system. Consequently, the terminals must be wired or programmed in such a waythat the inverter is enabled via the input terminals.
The simplest way of enabling the drive inverter at the terminals is to connect the DIØØ(function /CONTROLLER INHIBIT) input terminal to a +24 V signal and to program inputterminals DIØ1 ... DIØ5 to NO FUNCTION. The following illustration shows by way ofexample how to startup the MOVIDRIVE® drive inverter with fieldbus interface.
SP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Startup of the drive inverterProject Planning and Startup
Procedure for startup of the MOVIDRIVE® MDX61B
1. Enable the power output stage at the terminals.
Connect the input terminal DIØØ / X13.1 (function /CONTROLLER INHIBIT) to a+24 V signal (for example, using a device jumper).
2. Turn on the external 24 V voltage supply (not mains voltage supply!).
You can now configure the drive inverter.
3. Setpoint source = FIELDBUS / control signal source = FIELDBUS.
Set the setpoint source and control signal source parameters to FIELDBUS to controlthe drive inverter via a fieldbus.
4. Input terminals DIØ1 ... DIØ5 = NO FUNCTION.
Set the function of the input terminals to NO FUNCTION.
For more information on startup and control of the MOVIDRIVE® drive inverter, refer tothe "MOVIDRIVE® Fieldbus Unit Profile" manual.
DI00 = Controller inhibit
DI01 = no function
DI02 = no function
DI03 = no function
DI04 = no function
DI05 = no function
DCOM = Reference X13:DI00 ... DI05
VO24 = + 24 V
DGND = Reference pot. for binary signals
ST11 = RS-485 +
ST12 = RS-485 -
TF1 = TF input
DGND = Reference pot. for binary signals
DB00 = Brake
DO01-C = Relay contact
DO01-NO = Normally open contact relay
DO01-NC = Normally closed contact relay
DO02 = /Malfunction
VO24 = + 24 V
VI24 = + 24 V (external supply)
DGND = Reference pot. for binary signals
Enabling the power output stage via unit jumper [1]54095AXX
P100 Setpoint source = FIELDBUS
P101 Control signal source = FIELDBUS
P600 Terminal programming DIØ1 = NO FUNCTION
P601 Terminal programming DIØ2 = NO FUNCTION
P602 Terminal programming DIØ3 = NO FUNCTION
P603 Terminal programming DIØ4 = NO FUNCTION
P604 Terminal programming DIØ5 = NO FUNCTION
+
-
X13:
DI00DI01DI02DI03DI04DI05DCOMVO24DGNDST11ST12
24 V ext.
---
TF1DGNDDB00DO01-CDO01-NODO01-NCDO02VO24VI24DGND
X10:
[1]
1234567891011
12345678910
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
15
16
4 tartup of the drive inverterroject Planning and Startup
Power-UP test A power-up test of all LEDs takes place once the drive inverter has been switched on.The LEDs are switched on in the following sequence as part of the test:
Time in [ms] LED Mod/Net PIO LED LED BIO BUS-OFF LED
0 Green Off Off Off
250 red Off Off Off
500 Off Green Off Off
750 Off red Off Off
1000 Off Off Green Off
1250 Off Off red Off
1500 Off Off Off Green
1750 Off Off Off red
2000 Off Off Off Off
If there is no 24 V supply voltage at the fieldbus (X30:1, X30:5), the LED BUS-OFF willbe yellow (→ Operating displays of DFD11B option).
SP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Building the DeviceNet network with the RSNetWorx softwareProject Planning and Startup
4.2 Building the DeviceNet network with the RSNetWorx software
Installing the EDS file
Install the following files with the RSNetWorx software to build the DeviceNet networkwith the DFD11B option:
• EDS file: DFD11B.eds
• Icon file: DFD11B.ico
Proceed as follows:
• Select the menu item <Tools/EDS-Wizard> in RSNetWorx. You will be prompted toenter the names of the EDS and Icon file.
• The files will be installed. More details on the installation of the EDS file can be foundin the Allen Bradley documentation for RSNetWorx.
• After installation, the device is available in the device list under the entry SEW DeviceProfile/SEW-EURODRIVE DFD11B.
Connecting the device to an existing network
All EDS files are automatically read in after the RSNetWorx software is started. Thedevice list contains all devices which have been defined by an EDS file.
54173AXXFigure 3: EDS file list
Additional information on current EDS files as well as information on DeviceNet areavailable at the following Internet addresses:
• SEW-EURODRIVE: www.sew-eurodrive.com
• Allen Bradley: www.ab.com
• Open Device Net Vendor Association: www.odva.org
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
17
18
4 rocess data exchangeroject Planning and Startup
4.3 Process data exchange
Polled I/O The polled I/O messages correspond to the process data telegrams of the SEW fieldbusprofile. Up to ten process data words can be exchanged between the control and theinverter in this case. The process data length is set via DIP switches S2-PD0 ... S2-PD4.
Configuration for 1 ... 10 process data words
The process data length for the process data configuration is set to 3 at the factory. Thevalue can be set via DIP switches S2-PD0 ... S2-PD4.
This setting is displayed via the parameters DeviceNet PD configuration = 3PD or 3PD+ Param in MOVITOOLS® or via the DBG60B keypad. This means three process datawords (6 bytes) are processed in the inverter and three process input data words aresent to the control.
No process data are processed or sent back if the control transmits more than ten pro-cess output data words.
Three process data words are processed and three process input data words are sentfrom the inverter to the control if the control transmits three process output data words.
The set process data length influences the process data lengths of both the polled I/Oand the bit-strobe I/O messages.
The process data length of the bit-strobe I/O messages can include up to four processdata words. If the value for the process data length set via DIP switches is less than four,it will be accepted. If the value set via DIP switches is greater than four, the process datalength will be automatically limited to four.
54191AENFigure 4: Three process data words in the PLC memory
4
1 2 3
5 6
7 8 9
+/- 0 .
MOVIDRIVE® MDX61B
...
...
PLC
address range
Output file
Input file
O:3.10 PD 1
PD 2
PD 3
PD 1
PD 2
PD 3
O:3.11
O:3.12
I:3.10
I:3.11
I:3.12
PD 1 PD 2 PD 3 PD 10
PD 1 PD 2 PD 3 PD 10
PP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Process data exchangeProject Planning and Startup
The process output data are stored in the output file of the PLC and the process inputdata of the PLC are stored in the input file. In the example above, the output data wordsO:3.10, O:3.11 and O:3.12 are copied to process output data words 1, 2 and 3 and pro-cessed by the inverter. The inverter sends back three process input data words that arecopied into input data words I:3.10, I:3.11 and I:3.12 of the PLC.
Timeout response with polled I/O
The timeout is triggered by the DFD11B option. The timeout time must be set by themaster after the connection has been established. The DeviceNet specification refers toan "expected packet rate" rather than a timeout time in this case. The expected packetrate is calculated on the basis of the timeout interval using the following formula:
tTimeout_inverter = tTimeout interval_PolledIO = 4 x tExpected_Packet_Rate_PolledIO
The expected packet rate can be set using the connection object class 5, instance 2,attribute 9. The range of values runs from 0 ms to 65535 ms in 5 ms steps.
The expected packet rate for the polled I/O connection is converted into the timeoutinterval and displayed in the device and the timeout interval in parameter P819.
This timeout interval is retained in the device whenever the polled I/O connection isdropped, and the device switches to timeout status after the timeout interval haselapsed.
The timeout interval must not be altered in the inverter using MOVITOOLS® or theDBG60B keypad, because it can only be activated via the bus.
If a timeout occurs for the polled I/O messages, this connection type enters timeoutstatus. Incoming polled I/O messages are no longer accepted.
The timeout causes the timeout reaction set in the inverter to be carried out.
The timeout can be reset with DeviceNet by means of the reset service of the connectionobject (class 0x05, instance 0x02, undetermined attribute), by disconnecting theconnection, by means of the reset service of the identity object (class 0x01, instance0x01, undetermined attribute) or with the reset bit in the control word.
Bit-strobe I/O Bit-strobe I/O messages are not contained in the SEW fieldbus profile. The messagesrepresent a DeviceNet-specific process data exchange. The master sends a broadcastmessage that is 8 bytes (= 64 bits) long. One bit in this message is assigned to eachstation in accordance with its station address. The value of this bit may be 0 or 1, andthereby trigger two different reactions in the recipient.
If you select a different process data length, you will have the expand the memory to bemanaged in the PLC as well. If the process data length is set to 10, you will have toconfigure 10 process output data words and 10 process input data words.
Bit value
Meaning LED BIO
0 Send back the process input data only Green light
1 Trigger fieldbus timeout reaction and send back process input data Green light
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
19
20
4 rocess data exchangeroject Planning and Startup
The following table shows the data area of the bit-strobe request telegram which repre-sents the allocation of stations (= station address) to data bits.
Example: For example, the station with station address (MAC-ID) 16 only processes bit0 in data byte 2.
In the example above, the bit-strobe I/O message is stored in memory words O:3.10 toO:3.13. The inverter sends three process input data words to the PLC; these are storedin the input file in input data words I:3.10 to I:3.12.
Important:
The BIO LED on the front of the DFD11B option can be used for distinguishing betweenthe timeout triggered by the bit-strobe telegram and a real timeout in the connection. Itremains continuously green if the timeout is triggered by the bit-strobe telegram.
If the BIO LED flashes red, this means there is a timeout in the bit-strobe connection andno more bit-strobe telegrams are accepted. Each station that has received this bit-strobeI/O message responds with its current process input data. The length of the process in-put data corresponds to the process data length for the polled I/O connection. The pro-cess input data length can be up to four process data.
Byte off-set
7 6 5 4 3 2 1 0
0 ID 7 ID 6 ID 5 ID 4 ID 3 ID 2 ID 1 ID 0
1 ID 15 ID 14 ID 13 ID 12 ID 11 ID 10 ID 9 ID 8
2 ID 23 ID 22 ID 21 ID 20 ID 19 ID 18 ID 17 ID 16
3 ID 31 ID 30 ID 29 ID 28 ID 27 ID 26 ID 25 ID 24
4 ID 39 ID 38 ID 37 ID 36 ID 35 ID 34 ID 33 ID 32
5 ID 47 ID 46 ID 45 ID 44 ID 43 ID 42 ID 41 ID 40
6 ID 55 ID 54 ID 53 ID 52 ID 51 ID 50 ID 49 ID 48
7 ID 63 ID 62 ID 61 ID 60 ID 59 ID 58 ID 57 ID 56
54192AENFigure 5: Bit-strobe I/O messages
1
1
PLC
address range
Output file
Input file
O:3.10
Bit 16O:3.11
O:3.12
O:3.13
I:3.10I:3.11
I:3.12
PD 1 PD 2
PD 3
PD 1 PD 2 PD 3
Stationaddress
(MAC-ID) = 16
4
1 2 3
5 6
7 8 9
+/- 0 .
Important:
The process data length set via DIP switches influences the process data lengths of boththe polled I/O and the bit-strobe I/O messages. The process data length of the bit-strobeI/O messages can include up to four process data words.
PP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Process data exchangeProject Planning and Startup
Timeout response with bit-strobe I/O
The timeout is triggered by the DFD11B option. The timeout time must be set by themaster after the connection has been established. The DeviceNet specification refers toan "expected packet rate" rather than a timeout time in this case. The expected packetrate is calculated on the basis of the timeout interval using the following formula:
tTimeout_BitStrobeIO = 4 x tExpected_Packet_Rate_BitStrobeIO
It can be set using connection object class 5, instance 3, attribute 9. The range of valuesruns from 0 ms to 65535 ms in 5 ms steps.
If a timeout occurs for the bit-strobe I/O messages, this connection type enters timeoutstatus. Incoming bit-strobe I/O messages are no longer accepted. The timeout is notpassed on to the inverter.
The timeout reset takes place as follows:
• via DeviceNet with the reset service of the connection object (class 0x05, instance0x03, undetermined attribute)
• by interrupting the connection
• via reset service of the identity object (class 0x01, instance 0x01, undeterminedattribute)
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
21
22
4 arameter data exchangeroject Planning and Startup
4.4 Parameter data exchange
The SEW parame-ter data channel
The SEW parameter data channel represents a connection you can use to change orread parameters in the inverter. It is represented on the DFD11B option in form ofExplicit Messages.
Access to the SEW parameter data channel is by means of the register object (class 7)and the parameter object (class 15).
Register object class (class 7)
You address the SEW parameter data channel with the Get_Attribute_Single andSet_Attribute_Single services. The following possibilities for addressing the parameterdata channel derive from the way the register object is specified by DeviceNet so thatINPUT objects can only be read and OUTPUT objects can be read and written.
Instance INPUT / OUTPUTResulting MOVILINK® service with
Get_Attribut_Single Set_Attribut_Single
1 INPUT READ Invalid
2 OUTPUT READ WRITE
3 OUTPUT READ WRITE VOLATILE
4 INPUT READ MINIMUM Invalid
5 INPUT READ MAXIMUM Invalid
6 INPUT READ DEFAULT Invalid
7 INPUT READ SCALING Invalid
8 INPUT READ ATTRIBUTE Invalid
9 INPUT READ EEPROM Invalid
PP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Parameter data exchangeProject Planning and Startup
54185AENFigure 6: Description of the parameter channel
READ EEPROM
Get_Attribut_Single READ
READ MINIMUM
READ MAXIMUM
READ DEFAULT
READ SCALING
READ ATTRIBUTE
WRITE
WRITE VOLATILE
Get_Attribut_Single
Get_Attribut_Single
Set_Attribut_Single
Set_Attribut_Single
Get_Attribut_Single
Get_Attribut_Single
Get_Attribut_Single
Get_Attribut_Single
Get_Attribut_Single
Input
(Instance 1)
Input
(Instance 4)
Input
(Instance 5)
Input
(Instance 6)
Input
(Instance 7)
Input
(Instance 8)
Get_Attribut_Single Input
(Instance 9)
Output
(Instance 2)
Output
(Instance 3)
DeviceNet SEW fieldbus profile
DPRAM
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
23
24
4 arameter data exchangeroject Planning and Startup
The following table shows the attributes (column "Attribute") of the eight instances (col-umn "Instance") of the register object.
Class Instance Attribute Get Set Type Type/Value Meaning
0x07 0x01(Read)
1 X BOOL 0/1 Bad Flag
2 X BOOL 0 (Input) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x02(Read /Write)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 48 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x03(Read/Write-Volatile)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x04(Read Minimum)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x05(Read Maximum)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x06(Read Default)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x07(Read Scaling)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x08(Read Attribute)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
0x09(Read EEPROM)
1 X BOOL 0/1 Bad Flag
2 X BOOL 1 (Output) Direction
3 X UINT 16 bit Size
4 X X ARRAYBITS
2 byte index4 byte data
Data
PP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Parameter data exchangeProject Planning and Startup
Explanation of attributes
• Attribute 1 Bad flag signals whether an error occurred in the previous service.
• Attribute 2 represents the direction of the instance
• Attribute 3 indicates the data length in bits
• Attribute 4 represents the parameter data. They are made up of the index (2 bytes)and the data (4 bytes).
You transmit the values with the Get_Attribute_Single and Set_Attribute_Single servic-es.
Example Parameter Setpoint description PO1 (index 8304 = 2070hex) is to receive the valueCONTROL WORD1 (9). The following table shows the file format for the parameter re-quest telegram.
The following table shows the file format for the parameter response telegram.
Service Coding Meaning
Get_Attribut_Single 0x0E Read attribute
Set_Attribut_Single 0x10 Write attribute
Byte offset
0 1 2 3 4 5 6 7 8 9 10
Function MAC-ID Service Class Instance Attributes
Index Data
Signifi-cance
Low High LSB MSB
Exam-ple
01hex 10hex 07hex 02hex 04hex 70hex 20hex 09hex 00hex 00hex 00hex
Byte offset
0 1 2 3 4 5 6 7
Function MAC-ID Service Index Data
Significance Low High LSB MSB
Example 01hex 90hex 70hex 20hex 09hex 00hex 00hex 00hex
54183AENFigure 7: Parameter data exchange
Input data
4
1 2 3
5 6
7 8 9
+/- 0 .
Header(Service, Class...)
Index = 2070h
Data Low-word=0009h
Data High-word=0000h
Index
Index
Data Low-Word
Data
Data High-Word
Header(Service, Class...)
Index = 2070h
Data Low-word=0009h
Data High-word=0000h
PLCaddress range
Output data
Header
Index
Data Low-Word
Data High-Word
Header
Header
Index DataHeader
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
25
26
4 arameter data exchangeroject Planning and Startup
Parameter object class (class 15)
The fieldbus parameters of the inverter can be addressed directly via the instance withthe parameter object. The data format for these instances deviates from the SEW field-bus profile to meet the DeviceNet specification. It is possible to address all parametersof the inverter via the parameter object. Instances 1 to 9 have been reserved for thispurpose.
General SEW parameter data channel
You can use the RSNetWorx software to set the inverter parameters via the parameterobject. Because not all parameters are listed in the EDS file, instances have beendefined in the parameter object 2 that emulate the SEW parameter data channel with itsMOVILINK® services.
You will first have to write the desired index to the SEW-Param.-Index before you canread or write a parameter. You can then read or write the SEW parameter data viainstance 2. That means you have to perform two services to read or write a parameter.
The file format of the SEW-Read/Write, SEW-Read/WriteVo, SEW-Minimum,SEW-Maximum, SEW-Default, SEW-Scaling and SEW-Attribute services correspondsto the SEW communication profile MOVILINK®.
Writing or read-ing the fieldbus parameters
The parameters required for operating the fieldbus have been directly incorporated intothe parameter object. They can be addressed directly via the instance.
R = Read only
No.
Group Name Comment
1 SEW Parameter Channel SEW param. index Index of the parameter
2 SEW Parameter Channel SEW-Read/Write Read or write the value of the parameter
No. Group Name Meaning
3R
Device parameter
Device Identification Part number device
4 Control source Control signal source
5 Setpoint source Setpoint source
6R PD configuration Process data configuration
7 Setp.descr.PO1 Process output data assignment for PD1
8 Setp.descr.PO2 Process output data assignment for PD2
9 Setp.descr.PO3 Process output data assignment for PD3
10 Act.v.descr. PI1 Process input data assignment for PD1
11 Act.v.descr. PI2 Process input data assignment for PD2
12 Act.v.descr. PI3 Process input data assignment for PD3
13 PO Data Enable Enable process data
14 Timeout response Timeout response
15R Fieldbus type Fieldbus type
16R Baud rate Baud rate via DIP switches
17R Station address MAC-ID via DIP switches
PP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4Parameter data exchangeProject Planning and Startup
Process output data monitor (PO monitor)
Use these parameters to monitor the process output data sent by the control.
R = Read only
Process input data monitor (PI monitor)
Use these parameters to monitor the process input data sent to the control.
R = Read only
Scaling and representation within the telegram correspond to the DeviceNet specifica-tion and are identical to the SEW communication profile.
No. Group Name Meaning
18R
PO monitor
PO1 setpoint Monitor of process output data word 1
19R PO2 setpoint Monitor of process output data word 2
20R PO3 setpoint Monitor of process output data word 3
21R PO4 setpoint Monitor of process output data word 4
22R PO5 setpoint Monitor of process output data word 5
23R PO6 setpoint Monitor of process output data word 6
24R PO7 setpoint Monitor of process output data word 7
25R PO8 setpoint Monitor of process output data word 8
26R PO09 setpoint Monitor of process output data word 9
27R PO10 setpoint Monitor of process output data word 10
No. Group Name Meaning
28R
PI monitor
PI1 actual value Monitor of process input data word 1
29R PI2 actual value Monitor of process input data word 2
30R PI3 actual value Monitor of process input data word 3
31R PI4 actual value Monitor of process input data word 4
32R PI5 actual value Monitor of process input data word 5
33R PI6 actual value Monitor of process input data word 6
34R PI7 actual value Monitor of process input data word 7
35R PI8 actual value Monitor of process input data word 8
36R PI9 actual value Monitor of process input data word 9
37R PI10 actual value Monitor of process input data word 10
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
00
I
27
28
4 eturn codes for parameter settingroject Planning and Startup
4.5 Return codes for parameter setting
SEW-specific return codes
The return codes which the inverter sends back in the event of incorrect parameter set-ting are described in the manual for the "SEW Fieldbus Device Profile" and do not formpart of this documentation. However, the return codes are sent back in a different formatin conjunction with DeviceNet. The following table shows the data format for a parameterresponse telegram.
• The Service code of an error telegram is always 94hhex
• The General Error Code of an inverter-specific return code is always 1Fhex = propri-etary error
• The additional code is identical to the additional code described in the SEW fieldbusdevice profile manual.
• The table shows the proprietary error10hex = Illegal parameter index.
Return codes from DeviceNet
DeviceNet-specific return codes are sent in the error telegram if the data format is notmaintained during the transfer or if a service is performed which has not been imple-mented. The coding of these return codes is described in the DeviceNet specification(→ section " Appendix").
Timeout of explicit mes-sages
The timeout is triggered by the DFD11B option. The timeout time must be set by themaster after the connection has been established. The DeviceNet specification refers toan expected packet rate" rather than a timeout time in this case. The expected packetrate is calculated on the basis of the timeout interval using the following formula:
tTimeout_ExplicitMessages = 4 x tExpected_Packet_Rate_ExplicitMessages
It can be set using connection object class 5, instance 1, attribute 9. The range of valuesruns from 0 ms to 65535 ms in 5 ms steps.
If a timeout is triggered for the explicit messages, the connection for the explicit messag-es is automatically dropped providing the polled I/O or bit-strobe I/O connections are notin the ESTABLISHED state. This is the default setting for DeviceNet. The connection forexplicit messages must be re-established to communicate with these messages again.The timeout is not forwarded to the inverter.
Byte offset
0 1 2 3
Function MAC-ID Service code [=94hex] General Error Code Additional code
Example 01hex 94hex 1Fhex 10hex
RP
00
I
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Return codes for parameter settingSample Application with PLC Type SLC500
5 Sample Application with PLC Type SLC500
The following devices are employed:
54179AENFigure 8: PLC equipment configuration
MAC-ID1
MAC-ID11
1
MAC-ID10
4
1 2 3
5 6
7 8 9
+/- 0 .
4
1 2 3
5 6
7 8 9
+/- 0 .
4
1 2 3
5 6
7 8 9
+/- 0 .
RSLogic500 for SLC9324-RL0300END
PC PCRS232C
1747-CP3RS232C
1747-CP3
16outputs
16inputs Adapter
16inputs Adapter
16inputs
DeviceNetScannerSLC500Power section
1746-P2
1485A-C2
Terminatingresistor
1485A-C2
Terminatingresistor
1747-SDN 1746-IB16 1794-ADN 1794-IB16 1794-ADN 1794-OV161746-OB161747-L542
DeviceNet (remote line 1485C-P1-A50)
Cha
ssis
174
6-A
7
Power section
System configurationDeviceNet
Terminal m
odule1794-T
B2
Terminal m
odule1794-T
B2
MAC-ID0
MAC-ID8
MAC-ID4
Device MAC-ID
SLC5/04 -
DeviceNet scanner 1747-SDN 1
INPUT module with 32 inputs -
OUTPUT module with 32 outputs -
DeviceNet adapter with input module with 16 inputs 11
DeviceNet with output module 16 outputs 10
MOVIDRIVE® MDX61B with DFD11B 8
MOVIDRIVE® MDX61B with DFD11B 0
MOVIDRIVE® MDX61B with DFD11B 4
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
2930
5 eturn codes for parameter settingample Application with PLC Type SLC500
The following memory areas have been specified with the DeviceNet manager software:
The Bit-Strobe data are contrasted to the Polled I/O data in bold.
*******************************************************************
1747-SDN Scanlist Map
******************************************************************
Discrete Input Map:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
I:3,000 R R R R R R R R R R R R R R R R Status word of the scanner
I:3,001 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 Process data from device 11
I:3,002 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 Process data from device 11
I:3,003 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Process data from device 10
I:3,004 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Process data from device 10
I:3,005 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID1 device 8 Polled IO
I:3,006 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID2 device 8 Polled IO
I:3,007 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID3 device 8 Polled IO
I:3,008 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID1 device 8 Bit-Strobe I/O
I:3,009 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID2 device 8 Bit-Strobe I/O
I:3,010 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 PID3 device 8 Bit-Strobe I/O
I:3,011 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID1 device 0 Polled IO
I:3,012 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID2 device 0 Polled IO
I:3,013 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID3 device 0 Polled IO
I:3,014 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID1 device 0 Bit-Strobe I/O
I:3,015 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID2 device 0 Bit-Strobe I/O
I:3,016 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 PID3 device 0 Bit-Strobe I/O
I:3,017 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID1 device 4 Polled IO
I:3,018 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID2 device 4 Polled IO
I:3,019 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID3 device 4 Polled IO
I:3,020 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID1 device 4 Bit-Strobe I/O
I:3,021 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID2 device 4 Bit-Strobe I/O
I:3,022 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 PID3 device 4 Bit-Strobe I/O
Discrete Output Map:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
O:3,000 R R R R R R R R R R R R R R R R Status word of the scanner
O:3,001 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 Process data to device 11
O:3,002 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Process data to device 10
O:3,003 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 POD1 device 8 Polled IO
O:3,004 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 POD2 device 8 Polled IO
O:3,005 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08 POD3 device 8 Polled IO
O:3,006 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 POD1 device 0 Polled IO
O:3,007 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 POD2 device 0 Polled IO
O:3,008 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 POD3 device 0 Polled IO
O:3,009 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 POD1 device 4 Polled IO
O:3,010 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 POD2 device 4 Polled IO
O:3,011 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 04 POD3 device 4 Polled IO
O:3,012 .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. Bit-Strobe for device 8
RS
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Exchange of polled I/O (process data)Sample Application with PLC Type SLC500
5.1 Exchange of polled I/O (process data)
Objective In the following program, process data are to be sent to a MOVIDRIVE® MDX61B andthe motor should run at a different speed. The program sequence is shown in the follow-ing figure.
The parameters listed in the following table must be set in the MOVIDRIVE® MDX61Bdrive inverter for exchange of the process data.
MOVIDRIVE® MDX61B now works in fieldbus mode and can receive process data. Theprogram can now be written for the SLC500.
54178AENFigure 9: Program sequence
Menu no. Index Parameter Value
100 8461 Setpoint source Fieldbus
101 8462 Control signal source Fieldbus
870 8304 Process output data description 1 Control word 1
871 8305 Process output data description 2 Speed
872 8306 Process output data description 3 No function
873 8307 Process output data description 1 Status word 1
874 8308 Process output data description 2 Speed
875 8309 Process output data description 3 No function
876 8622 PO data enable YES
START
Cycle 0
Cycle 1
Cycle 2
Cycle 3
Speed = 1000 rpm,Enable
Speed = 0 rpm,Rapid stop
Speed = 0 rpm,Rapid stop
Speed = -400 rpm,Enable
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3132
5 xchange of polled I/O (process data)ample Application with PLC Type SLC500
Output bit O:3.0/0 is set in rung 0 (program line 0), thereby starting DeviceNet commu-nication (→ description of the DeviceNet scanner).
Rungs 1 and 3 implement the status engine with which states 0... 3 are implemented.The current status is written to the outputs O:1.0 of the output module of the SLC500 inrung 2.
The process data values are output to the scanner memory area in the following figure.
01912AEN
Status engine for control of sense of rotation
Output of the status engine
If status > 3, change to status 0
Start DeviceNet communication
01913AEN
If status > 3, change to status 0
Status 0: Start motor, speed = 1000 rpm
Status 1: Stop motor
ES
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Exchange of polled I/O (process data)Sample Application with PLC Type SLC500
Status 0 is created in rung 4. In this status, a 6 (ENABLE) is written to memory areaO:3.3 which represents process output data word 1. A 5000 is written to memory areaO:3.4 (process output data word 2), which represents 1000 min–1. This means the motorruns at 1000 revolutions.
Status 1 is created in rung 5. In this status, a 0 (RAPID STOP) is written to memory areaO:3.3 which represents process output data word 1. A 0 is written to memory area O:3.4(process output data word 2), which represents the value 0 min–1. This means the motoris stopped with the rapid stop. States 2 and 3 are treated similarly to states 0 and 1, andare thus not explained any further.
In the figure above, the current actual value of the device with address 8, which is locat-ed in memory area I:3.6 (process input data word 2), is multiplied by a constant factor(in this case, by 1) and written to output memory area O:3.7 (process output data word2 of the device with address 0).
In addition, the value 6 (ENABLE) is written to the process output data word 1 of thedevice with address 0 (O:3.6). Thus, the device with address 0 follows the actual speedwith enable signal from the device with address 8.
01914AEN
Transmit actual position from motor 1 to motor 2
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3334
5 xchange of bit-strobe I/Oample Application with PLC Type SLC500
5.2 Exchange of bit-strobe I/O
Objective In the following program the process input data are to be requested from theMOVIDRIVE® drive inverter. Set the parameters listed in the following table in the invert-er for process data exchange.
MOVIDRIVE® now works in fieldbus mode and can receive process data. The programcan now be written for the PLC of the SLC500.
DeviceNet communication is enabled again in rung 0.
In rung 1, the strobe-bit of device 8 is set in relationship to the input bit I:3.2/0 (from theDeviceNet input module).
In rung 2, process input data word 1 (I:3.8) is copied to the DeviceNet output module viamemory word O:3.12 and process input data word 2 (I:3.9) is copied to the SLC500 out-put module via memory word O:1.0.
Menu no. Index Parameter Value
100 8461 Setpoint source Fieldbus
101 8462 Control signal source Fieldbus
870 8304 Process output data description 1 Control word 1
871 8305 Process output data description 2 Speed
872 8306 Process output data description 3 No function
873 8307 Process output data description 1 Status word 1
874 8308 Process output data description 2 Speed
875 8309 Process output data description 3 No function
876 8622 PO data enable YES
831 8610 Response FIELDBUS TIMEOUT Rapid st. / Warn.
01915AEN
Start DeviceNet communication
Set / reset Strobe bit
Transmit actual values from the device to the output module
Send Bit-Strobe message
ES
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Exchanging explicit messages (parameter data)Sample Application with PLC Type SLC500
5.3 Exchanging explicit messages (parameter data)
Objective In this program, parameter data are exchanged between the control and the inverter.
Exchange of parameter data between inverter and SLC500 takes place via M-Files (→Installations instructions on DeviceNet scanner module).
A memory area from word 224 to 255 in these M-files is reserved for explicit messages.The structure of this memory area is shown in the following figure.
This memory area is split up into two areas:
• Transmission header (three words)
• Explicit message body
The memory areas in the M-Files are described in more detail in the following overview.
54172AEN
Memory area Function Length Value Description
Transmission header cmd/status
1/2 word each
→ follow-ing table
cmd: Entry of command codestatus: Entry of transmission status
TXID 1 ... 255 During creation or downloading of a request to the scanner, the contact plan program of the SLC5 processor assigns a TXID to the transfer.
Size 3 ... 29 Size of the explicit message body (in bytes!)
Connec-tion
0 DeviceNet connection (= 0)
Service 0Ehex10hex05hexetc.
Get_Attribute_Single (Read)Set_Attribute_Single (Write)Resetsee DeviceNet specification for more services
Explicit message body Class
1 word each 0 ... 255
DeviceNet class
Instance DeviceNet instance
Attributes DeviceNet attribute
Data 0 ... 26 words 0 ... 65535 Data content
Class
Instance
Attribute
Tran
smis
sion
head
erE
xplic
it M
essa
ge B
ody
Word 224TXID cmd/status
Connection Size
Service MAC-ID
Data
Word 225
Word 226
Word 227
Word 228
Word 229
Word 230
...
Word 255
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3536
5 xchanging explicit messages (parameter data)ample Application with PLC Type SLC500
The following overviews offer a description of the command and status codes.
Command codes:
Status codes:
Command code (cmd)
Description
0 Ignore transmission block
1 Execute transmission block
2 Receive transmission status
3 Reset all client/server transmissions
4 Delete transmission from queue
5 ... 255 Reserved
Network node status (sta-tus)
Description
0 Ignore transmission block
1 Transmission completed successfully
2 Transmission in progress
3 Error – Slave device not in the scan list
4 Error – Slave is offline
5 Error – DeviceNet network connection deactivated (offline)
6 Error – Unknown transmission TXID
7 Not used
8 Error – Invalid command code
9 Error – Scanner buffer full
10 Error – Other client/server transmission in progress
11 Error – No connection to slave device
12 Error – Response data are too long for the block
13 Error – Invalid connection
14 Error – Invalid size specified
15 Error – Busy
16 ... 255 Reserved
ES
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Exchanging explicit messages (parameter data)Sample Application with PLC Type SLC500
The M-files are divided into a request file (M0-file) and a response file (M1-file). Datatransmission takes place as shown in the following figure.
Register object class (7hex) must be used in order to read (instance 1 to 9) or write (in-stance 2 and 3) parameters from the inverter via the SEW parameter data channel. Thedata range is divided into the index (1 word) and the parameter data (2 words).
54175AENFigure 10: Transmission of an explicit message
4
1 2 3
5 6
7 8 9
+/- 0 .
MOVIDRIVE® MDX61B
PLC
SLC500 Scanner 1747-SDN
Request of atransmission
block
Contact plan scanning
Response of atransmission
block
1.M0-File
4.M1-File
Scannerrequest
waiting loop
Scannerresponse
waiting loop
Process requests and responses
Exec
ute
Rea
dyor
Err
or
2. DeviceNet Explicit Message Request
3. DeviceNet Explicit Message Response
54177AEN
Class
Instance
Attribute
Tran
sim
issi
onhe
ader
Exp
licit
Mes
sage
Bod
y
Word 224TXID cmd/status
Connection Size
Service MAC-ID
Index
Data word Low (HEX)
Data word High (HEX)
Word 225
Word 226
Word 227
Word 228
Word 229
Word 230
Word 231
Word 232
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3738
5 xchanging explicit messages (parameter data)ample Application with PLC Type SLC500
In the sample program, a data area is reserved in the integer file (N-file, following figure),into which the data of the M0/M1 files are written.
The data telegram to be used is written in N7:0 to N7:8. N7:10 to N7:15 hold the datathat are to be received.
02149AXX
Word length Request
Function Value
1TXID 1
cmd: 1 = Start
2Connection 0
Size 8
3Service Ehex = Read Request
MAC_ID 8
4 Class 7
5 Instance 1
6 Attributes 4
7 Data 1 2070hex
8 Data 2 0hex
9 Data 3 0
Word length Response
Function Value
1TXID 1
status 1 = successful
2Connection 0
Size 6
3Service 8hex = Read Response
MACID 8
4 Data 1 2070hex
5 Data 2 9hex
6 Data 3 0
ES
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
5Exchanging explicit messages (parameter data)Sample Application with PLC Type SLC500
The SEW parameter data channel can be addressed via Class 7, Instance 1 ... 9 andAttribute 4 (→ Statement of Conformance).
In rung 5, the 9 bytes starting from N7:0 are copied into the M0-file with a rising edge ofbit B3:0/1. This starts the reading of parameter 8304 (2070hex). In rung 6, the systemwaits for the rising edge of scanner bit I:3.0/15. I:3.0/15 shows that the data are present.Request profile B3:0/1 can then be reset.
At this point, the received data still have to be written into the N-file. To this end, ninewords of the M1-files N7:10...19 are written.
01921AEN
Write transmit data
Read receive data
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
3940
6 FD11B optionechnical Data
6 Technical Data6.1 DFD11B option
DFD11B option
Part number 824 972 5
Power consumption P = 3 W
Communication protocol Master/slave connection set acc. to DeviceNet specification version 2.0
Number of process data words
Adjustable via DIP switches:• 1 ... 10 process data words• 1 ... 4 process data words with Bit-Strobe I/O
Baud rate 125, 250 or 500 kBaud, to be set via DIP switches
Bus cable length For thick cable according to DeviceNet specification 2.0 Appendix B• 500 m at 125 kbaud• 250 m at 250 kbaud• 100 m at 500 kbaud
Transmission level ISO 11 98 - 24 V
Connection technology • 2-wire bus and 2-wire supply voltage 24 VDC with 5-pole Phoenix terminal
• Pin assignment acc. to DeviceNet specification
MAC-ID 0 ... 63, can be set using DIP switchMax. 64 stations
Supported services • Polled I/O: 1 ... 10 words• Bit-Strobe I/O: 1 ... 4 words• Explicit messages:
– Get_Attribute_Single– Set_Attribute_Single– Reset– Allocate_MS_Connection_Set– Release_MS_Connection_Set
Tools for startup • MOVITOOLS® software package from version 4.20• DBG60B keypad
Firmware status of MOVIDRIVE® MDX61B
Firmware status 824 854 0.11 or above (→ display with P076)
DT
Pi
fkVA
Hz
n
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7General error codes (error messages)Appendix
7 Appendix7.1 General error codes (error messages)
General error code (hex)
Error name Description
00 - 01 Reserved for DeviceNet
02 Resource unavailable The source required for performing the service is unavailable
03 - 07 Reserved for DeviceNet
08 Service not supported The service is not supported for the selected class/instance
09 Invalid attribute value Invalid attribute data have been sent
0A Reserved for DeviceNet
0B Already in requested mode/state
The selected object is already in the requested mode/state
0C Object state conflict The selected object cannot perform the service in its current status
0D Reserved for DeviceNet
0E Attribute not settable It is not possible to access the selected object for writing.
0F Pivilege violation Violation of access entitlement
10 Device state conflict The current status of the device makes it impossible to perform the required service
11 Reply data too large The length of the transmitted data is longer than the size of the receive buffer
12 Reserved for DeviceNet
13 Not enough data The length of the transferred data is too short for the service to be performed
14 Attribute not supported The selected attribute is not supported
15 Too much data The length of the transferred data is too long for the service to be performed
16 Object does not exist The selected object is not implemented in the device
17 Reserved for DeviceNet
18 No stored attribute data The requested data have not been stored previously
19 Store operation failure The data could not be stored because an error occurred while saving them
1A - 1E Reserved for DeviceNet
1F Vendor specific error Vendor specific error (→Manual"SEW Fieldbus Device Profile")
20 invalid parameter Invalid parameterThis error message is used when a parameter does not satisfy the requirements of the specification and/or the requirements of the application.
21 - CF Future extensions Reserved by DeviceNet for additional definitions
D0 - DF Reserved for Object Class and service errors
Use this area if an occurring error cannot be entered in one of the error groups listed above.
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4142
7 tatement of Conformanceppendix
7.2 Statement of Conformance
54129AXX
Device Net Statement of Conformance
SOC data as of 6 - 3 - 2004
Fill in the blank or X the appropriate box
General Conforms to DeviceNet Specification Volume I - Release 2.0 Volume II - Release 2.0 Device Errata Data Vendor Name SEW Eurodrive GmbH
Device Profile Vendor SpecificProduct Name SEW-MOVIDRIVE-DFD11BProduct Code 10Product Revision 1.01
DeviceNet Physical Network Power Consumption (Max) 0,4 A @ 11V dc (worst case)Conformance Data
Connector Style Open-Hardwired Sealed-Mini
Open-Pluggable X Sealed-Micro
Isolated Physical Layer YesNo
LEDs Supported Module Combo Mod/Net X None Network I/O
MAC ID Setting DIP Switch X Software SettableOther
Default MAC ID 63
Communication Rate Setting DIP Switch X Software SettableOther
Communication Rates Supported 125k bit/s X 500k bit/s X250k bit/s X
DeviceNet Device Network Behavior Group 2 Client Group 2 Only Client
Communication Check All That Apply Group 2 Server Group 2 Only Server X
Data Peer-To-Peer Tool (not a Device)
UCMM Explicit Message Groups Supported Group 1 Group 2 Group 3
Dynamic I/O Message Groups (Peer to Peer) Group 1 Group 2 Group 3
Default I/O Data Address Path Input: Class 4 Inst. 64 Attr. 3
Output: Class 4 Inst. 64 Attr. 3
Fragmented Explicit Messaging Supported Yes No
If yes, Acknowledge TimeOut 1000 ms
Typical Target AddressesConsumption Service 16 Class 1 Inst. 1 Attr. 7Production Service 14 Class 1 Inst. 1 Attr. 7
1 of 9
SA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7Statement of ConformanceAppendix
54130AXX
Device Net Statement of Conformance
DeviceNet Identity Object 0x01Required Object Class ID Description Get Set Value Limits
Object Attributes Open 1 RevisionImplementation 2 Max instance
X None Supported 3 Number of Instances4 Optional attributes list
5 Optional services list
6 Max Id of class attributes7 Max Id of instance attributes
DeviceNet Services Parameter OptionsServices Get_Attributes_All
Reset
X None Supported Get_Attribute_SingleFind_Next_Object_instance
Object Instance ID Description Get Set Value LimitsAttributes Open 1 Vendor X =(315)
2 Device type X =(100)3 Product code X =(10)4 Revision X =(1.01)5 Status (bits supported) X6 Serial number X7 Product name X SEW-MOVIDRIVE-DFD11B
8 State9 Config. Consistency Value
10 Heartbeat Interval
DeviceNet Services Parameter OptionsServices Get_Attributes_All
X Reset 0
X Get_Attribute_SingleSet_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 2 of 9
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4344
7 tatement of Conformanceppendix
54132AXX
Device Net Statement of Conformance
DeviceNet Message Router Object 0x02Required Object Class ID Description Get Set Value Limits
Object Attributes Open 1 RevisionImplementation 2 Max instance
X None Supported 3 Number of Instances4 Optional attribute list5 Optional service list
6 Max ID of class attributes
7 Max ID of instance attributes
DeviceNet Services Parameter OptionsServices Get_Attributes_All
Get_Attribute_Single
X None SupportedObject Instance ID Description Get Set Value LimitsAttributes Open 1 Object list
2 Maximum connections supported
X None Supported 3 Number of active connections
4 Active connections list
DeviceNet Services Parameter OptionsServices Get_Attributes_All
Get_Attribute_Single
X None Supported Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 3 of 9
SA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7Statement of ConformanceAppendix
54133AXX
Device Net Statement of Conformance
DeviceNet DeviceNet Object 0x03Required Object Class ID Description Get Set Value Limits
Object Attributes Open 1 Revision X =(2)Implementation 2 Max instance
None Supported 3 Number of Instances
4 Optional attribute list5 Optional service list
6 Max ID of class attributes
7 Max ID of instance attributes
DeviceNet Services Parameter OptionsServices Get_Attribute_Single
X None SupportedObject Instance ID Description Get Set Value LimitsAttributes Open 1 MAC ID X =(0..63)
2 Baud rate X =(0..2) None Supported 3 BOI X =(0)
4 Bus-off counter X X =(0..255)
5 Allocation information X6 MAC ID switch changed X =(0)7 Baud rate switch changed X =(0)8 MAC ID switch value X =(0..63)9 Baud rate switch value X =(0..2)
DeviceNet Services Parameter OptionsServices X Get_Attribute_Single
X Set_Attribute_Single None Supported X Allocate M/S connection set
X Release M/S connection set
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 4 of 9
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4546
7 tatement of Conformanceppendix
54134AXX
Device Net Statement of Conformance
DeviceNet Connection Object 0x05Required Object Class ID Description Get Set Value LimitsObject Attributes Open 1 RevisionImplementation X None Supported 2 Max instance
3 Number of InstancesComplete this sheet for 4 Optional attribute listeach connection supported. 5 Optional service list
6 Max ID of class attributes7 Max ID of instance attributes
DeviceNet Services Parameter OptionsX None Supported Reset
CreateDeleteGet_Attribute_SingleFind_Next_Object_Instance
Object Instance Connection Type Max Connection InstancesM/S Explicit Message 1 Server Client 1 Total
Complete this section for Production trigger(s) Cyclic COS App. trig.Dynamic I/O connections Transport type(s) Server X Client
Transport class(es) 2 X 3
ID Description Get Set Value LimitsAttributes Open 1 State X
2 Instance type X3 Transport Class trigger X4 Produced connection ID X5 Consumed connection ID X6 Initial comm. characteristics X7 Produced connection size X8 Consumed connection size X9 Expected packet rate X X =(0..65530)
12 Watchdog time-out action X13 Produced connection path len X14 Produced connection path X15 Consumed connection path len X16 Consumed connection path X17 Production inhibit time X =(0)
DeviceNet Services Parameter OptionsServices X Reset
DeleteApply_Attributes
X Get_Attribute_Single
X Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 5 of 9
SA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7Statement of ConformanceAppendix
54135AXX
Device Net Statement of Conformance
DeviceNet Connection Object 0x05Required Object Class ID Description Get Set Value LimitsObject Attributes Open 1 RevisionImplementation X None Supported 2 Max instance
3 Number of InstancesComplete this sheet for 4 Optional attribute listeach connection supported. 5 Optional service list
6 Max ID of class attributes7 Max ID of instance attributes
DeviceNet Services Parameter OptionsX None Supported Reset
CreateDeleteGet_Attribute_SingleFind_Next_Object_Instance
Object Instance Connection Type Max Connection InstancesM/S Poll 1 Server Client 1 Total
Complete this section for Production trigger(s) Cyclic COS App. trig.Dynamic I/O connections Transport type(s) Server X Client
Transport class(es) 2 X 3
ID Description Get Set Value LimitsAttributes Open 1 State X
2 Instance type X3 Transport Class trigger X4 Produced connection ID X5 Consumed connection ID X6 Initial comm. characteristics X7 Produced connection size X8 Consumed connection size X9 Expected packet rate X X =(0..65530)
12 Watchdog time-out action X13 Produced connection path len X14 Produced connection path X15 Consumed connection path len X16 Consumed connection path X17 Production inhibit time X =(0)
DeviceNet Services Parameter OptionsServices X Reset
DeleteApply_Attributes
X Get_Attribute_Single
X Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 6 of 9
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4748
7 tatement of Conformanceppendix
54136AXX
Device Net Statement of Conformance
DeviceNet Connection Object 0x05Required Object Class ID Description Get Set Value LimitsObject Attributes Open 1 RevisionImplementation X None Supported 2 Max instance
3 Number of InstancesComplete this sheet for 4 Optional attribute listeach connection supported. 5 Optional service list
6 Max ID of class attributes7 Max ID of instance attributes
DeviceNet Services Parameter OptionsX None Supported Reset
CreateDeleteGet_Attribute_SingleFind_Next_Object_Instance
Object Instance Connection Type Max Connection InstancesM/S Bit Strobe 1 Server Client 1 Total
Complete this section for Production trigger(s) Cyclic COS App. trig.Dynamic I/O connections Transport type(s) Server X Client
Transport class(es) 2 X 3
ID Description Get Set Value LimitsAttributes Open 1 State X
2 Instance type X3 Transport Class trigger X4 Produced connection ID X5 Consumed connection ID X6 Initial comm. characteristics X7 Produced connection size X8 Consumed connection size X9 Expected packet rate X X =(0..65530)
12 Watchdog time-out action X13 Produced connection path len X14 Produced connection path X15 Consumed connection path len X16 Consumed connection path X17 Production inhibit time X =(0)
DeviceNet Services Parameter OptionsServices X Reset
DeleteApply_Attributes
X Get_Attribute_Single
X Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 7 of 9
SA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7Statement of ConformanceAppendix
54137AXX
Device Net Statement of Conformance
DeviceNet Register Object 0x07Required Object Class ID Description Get Set Value Limits
Object Attributes Open 1 RevisionImplementation 2 Max instance
X None Supported 3 Number of Instances
4 Optional attribute list
5 Optional service list6 Max ID of class attributes7 Max ID of instance attributes
DeviceNet Services Parameter Options
Services Get_Attribute_Single
X None Supported
Object Instance ID Description Get Set Value Limits
Attributes Open 1 Bad Flag X2 Direction X
None Supported 3 Size X4 Data X X
DeviceNet Services Parameter OptionsServices X Get_Attribute_Single 84520000000000
None Supported X Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No XX Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 8 of 9
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
4950
7 tatement of Conformanceppendix
54138AXX
Device Net Statement of Conformance
DeviceNet Parameter Object 0x0FRequired Object Class ID Description Get Set Value Limits
Object Attributes Open 1 RevisionImplementation 2 Max instance X
None Supported 3 Number of Instances4 Optional attribute list5 Optional service list
6 Max ID of class attributes
7 Max ID of instance attributes8 Parameter class descriptor X9 Configuration assembly instanceX10 Native language
DeviceNet Services Parameter OptionsServices Get_Attributes_All
Reset
None Supported X Get_Attribute_SingleSet_Attribute_SingleRestore Save
Object Instance ID Description Get Set Value LimitsAttributes Open 1 Parameter value X X =(0..4294967294)
2 Link Path size X None Supported 3 Link path X
4 Descriptor X5 Data type X6 Data size X =(4)7 Parameter name string8 Units string9 Help string
10 Minimum value11 Maximum value12 Default value13 Scaling multiplier14 Scaling divisor15 Scaling base16 Scaling offset17 Multiplier link
18 Divisor link
19 Base link20 Offset link21 Decimal precision
DeviceNet Services
Services Get_Attribute_All
None Supported X Get_Attribute_Single X Set_Attribute_Single
Vendor Specific Additions Yes If yes, fill out the Vendor Specific Additions form. No X
X Get indicates attribute value is returned by the Get_Attribute_Single service.X Set indicates attribute value is written to by the Set_Attribute_Single service. 9 of 9
SA
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
7Definitions of terminologyAppendix
7.3 Definitions of terminology
Term Description
Allocate Provides a service for setting up a connection.
Attributes Attribute of an object class or instance. Describes the characteristics of the object class or instance in more detail.
BIO - Bit-Strobe I/O All stations can be addressed with a broadcast telegram. The addressed stations respond with the process input data.
Class DeviceNet object class
Device-Net scanner Plug-in module for the Allen Bradley PLC which connects the PLC fieldbus to the peripheral devices.
DUP-MAC check Duplicate MAC-ID test
Explicit message body Includes the class no., instance no., attribute no. and the data.
Explicit message Parameter data message; assists in addressing the DeviceNet objects.
Get_Attribute_Single Read service for a parameter.
Instance Instance of an object class. Divides the object classes into additional sub-groups.
MAC-ID Media Access Control identifier: node address of the device.
M-file Provides the data range between the PLC and the scanner module.
Mod/Net Module/Network
Node ID Node address = MAC-ID
PIO - Polled I/O Process data channel of DeviceNet; allows process output data to be sent and process input data to be received.
Release Provides a service for setting up a connection.
Reset Provides a service for resetting an error.
Rung SLC500 program line
Service Service performed via bus, e.g. read service, write service, etc.
Set_Attribute_Single Write service for a parameter.
SLC500 Allen Bradley PLC
Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
518
52 Manual – MOVIDRIVE® MDX61B DFD11B Fieldbus Interface DeviceNet
Index
8 IndexAAdditional documentation ......................................5
BBaud rate ..................................................... 11, 40Building the DeviceNet network with RSNetWorx ...17Bus terminating resistor ......................................10BUS-OFF LED ....................................................13
CConnection and terminal assignment DFD11B .....9
DDefinitions of Terminology ..................................51Display of operating status DFD11B option card 12
EError messages ...................................................41
IImportant Notes ....................................................4Installing the DFD11B option card ........................7Installing the DFE11B option card
Basic procedure ..............................................8
LLED BIO ..............................................................13LED Mod/Net ......................................................12
NNotes on routing of bus cables ...........................10
OOperating displays of DFD11B option card
LED BIO .......................................................13LED Mod/Net ................................................12PIO LED .......................................................12
PParameter data exchange ...................................22PCP length ..........................................................11Pin assignment ...................................................10PIO LED ..............................................................12Process data exchange ......................................18
Bit-strobe I/O ................................................19Polled I/O ......................................................18Timeout response with bit-strobe I/O ............21Timeout response with polled I/O .................19
Process data length ............................................11
RReturn codes for parameter setting ....................28
SSafety Notes .........................................................4Safety notes on bus systems ................................4Sample Application with PLC Type SLC500 .......29
Setting the DIP switches .................................... 11Setting the baud rate ................................... 11Setting the MAC-ID ...................................... 11Setting the process data length ................... 11
SEW parameter data channel ............................ 22Startup of the drive inverter ................................ 14
Power-UP test .............................................. 16Statement of Conformance ................................ 42
TTechnical data DFD11B ..................................... 40
Address List
Address ListGermany
HeadquartersProductionSales
Bruchsal SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 42 D-76646 BruchsalP.O. BoxPostfach 3023 · D-76642 Bruchsal
Tel. +49 7251 75-0Fax +49 7251 75-1970http://[email protected]
Service Competence Center
Central Gear units / Motors
SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 1 D-76676 Graben-Neudorf
Tel. +49 7251 75-1710Fax +49 7251 [email protected]
Central Electronics
SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 42 D-76646 Bruchsal
Tel. +49 7251 75-1780Fax +49 7251 [email protected]
North SEW-EURODRIVE GmbH & Co KGAlte Ricklinger Straße 40-42 D-30823 Garbsen (near Hannover)
Tel. +49 5137 8798-30Fax +49 5137 [email protected]
East SEW-EURODRIVE GmbH & Co KGDänkritzer Weg 1D-08393 Meerane (near Zwickau)
Tel. +49 3764 7606-0Fax +49 3764 [email protected]
South SEW-EURODRIVE GmbH & Co KGDomagkstraße 5D-85551 Kirchheim (near München)
Tel. +49 89 909552-10Fax +49 89 [email protected]
West SEW-EURODRIVE GmbH & Co KGSiemensstraße 1D-40764 Langenfeld (near Düsseldorf)
Tel. +49 2173 8507-30Fax +49 2173 [email protected]
Drive Service Hotline / 24 Hour Service +49 180 5 SEWHELP+49 180 5 7394357
Additional addresses for service in Germany provided on request!
France
ProductionSalesService
Haguenau SEW-USOCOME 48-54, route de Soufflenheim B. P. 20185F-67506 Haguenau Cedex
Tel. +33 3 88 73 67 00 Fax +33 3 88 73 66 00http://[email protected]
AssemblySalesService
Bordeaux SEW-USOCOME Parc d’activités de Magellan62, avenue de Magellan - B. P. 182F-33607 Pessac Cedex
Tel. +33 5 57 26 39 00Fax +33 5 57 26 39 09
Lyon SEW-USOCOME Parc d’Affaires RooseveltRue Jacques TatiF-69120 Vaulx en Velin
Tel. +33 4 72 15 37 00Fax +33 4 72 15 37 15
Paris SEW-USOCOME Zone industrielle 2, rue Denis Papin F-77390 Verneuil I’Etang
Tel. +33 1 64 42 40 80Fax +33 1 64 42 40 88
Additional addresses for service in France provided on request!
Algeria
Sales Alger Réducom 16, rue des Frères ZaghnounBellevue El-Harrach16200 Alger
Tel. +213 21 8222-84Fax +213 21 8222-84
Argentina
AssemblySalesService
Buenos Aires SEW EURODRIVE ARGENTINA S.A.Centro Industrial Garin, Lote 35Ruta Panamericana Km 37,51619 Garin
Tel. +54 3327 4572-84Fax +54 3327 [email protected]
11/2004 53
Address List
54
Australia
AssemblySalesService
Melbourne SEW-EURODRIVE PTY. LTD.27 Beverage DriveTullamarine, Victoria 3043
Tel. +61 3 9933-1000Fax +61 3 9933-1003http://[email protected]
Sydney SEW-EURODRIVE PTY. LTD.9, Sleigh Place, Wetherill Park New South Wales, 2164
Tel. +61 2 9725-9900Fax +61 2 [email protected]
Austria
AssemblySalesService
Wien SEW-EURODRIVE Ges.m.b.H. Richard-Strauss-Strasse 24A-1230 Wien
Tel. +43 1 617 55 00-0Fax +43 1 617 55 00-30http://[email protected]
Belgium
AssemblySalesService
Brüssel CARON-VECTOR S.A.Avenue Eiffel 5B-1300 Wavre
Tel. +32 10 231-311Fax +32 10 231-336http://[email protected]
Brazil
ProductionSalesService
Sao Paulo SEW-EURODRIVE Brasil Ltda.Avenida Amâncio Gaiolli, 50Caixa Postal: 201-07111-970Guarulhos/SP - Cep.: 07251-250
Tel. +55 11 6489-9133Fax +55 11 6480-3328http://[email protected]
Additional addresses for service in Brazil provided on request!
Bulgaria
Sales Sofia BEVER-DRIVE GmbHBogdanovetz Str.1BG-1606 Sofia
Tel. +359 2 9532565Fax +359 2 [email protected]
Cameroon
Sales Douala Electro-ServicesRue Drouot AkwaB.P. 2024Douala
Tel. +237 4322-99Fax +237 4277-03
Canada
AssemblySalesService
Toronto SEW-EURODRIVE CO. OF CANADA LTD. 210 Walker Drive Bramalea, Ontario L6T3W1
Tel. +1 905 791-1553Fax +1 905 791-2999http://[email protected]
Vancouver SEW-EURODRIVE CO. OF CANADA LTD.7188 Honeyman Street Delta. B.C. V4G 1 E2
Tel. +1 604 946-5535Fax +1 604 [email protected]
Montreal SEW-EURODRIVE CO. OF CANADA LTD.2555 Rue Leger Street LaSalle, Quebec H8N 2V9
Tel. +1 514 367-1124Fax +1 514 [email protected]
Additional addresses for service in Canada provided on request!
Chile
AssemblySalesService
Santiago de Chile
SEW-EURODRIVE CHILE LTDA.Las Encinas 1295Parque Industrial Valle GrandeLAMPARCH-Santiago de ChileP.O. BoxCasilla 23 Correo Quilicura - Santiago - Chile
Tel. +56 2 75770-00Fax +56 2 [email protected]
China
ProductionAssemblySalesService
Tianjin SEW-EURODRIVE (Tianjin) Co., Ltd.No. 46, 7th Avenue, TEDA Tianjin 300457
Tel. +86 22 25322612Fax +86 22 [email protected]://www.sew.com.cn
11/2004
Address List
AssemblySalesService
Suzhou SEW-EURODRIVE (Suzhou) Co., Ltd.333, Suhong Middle RoadSuzhou Industrial ParkJiangsu Province, 215021P. R. China
Tel. +86 512 62581781Fax +86 512 [email protected]
Colombia
AssemblySalesService
Bogotá SEW-EURODRIVE COLOMBIA LTDA. Calle 22 No. 132-60Bodega 6, Manzana BSantafé de Bogotá
Tel. +57 1 54750-50Fax +57 1 [email protected]
Croatia
SalesService
Zagreb KOMPEKS d. o. o.PIT Erdödy 4 IIHR 10 000 Zagreb
Tel. +385 1 4613-158Fax +385 1 [email protected]
Czech Republic
Sales Praha SEW-EURODRIVE CZ S.R.O.Business Centrum Praha Luná 591CZ-16000 Praha 6 - Vokovice
Tel. +420 a220121236Fax +420 220121237http://[email protected]
Denmark
AssemblySalesService
Kopenhagen SEW-EURODRIVEA/SGeminivej 28-30, P.O. Box 100DK-2670 Greve
Tel. +45 43 9585-00Fax +45 43 9585-09http://[email protected]
Estonia
Sales Tallin ALAS-KUUL ASPaldiski mnt.125EE 0006 Tallin
Tel. +372 6593230Fax +372 [email protected]
Finland
AssemblySalesService
Lahti SEW-EURODRIVE OYVesimäentie 4FIN-15860 Hollola 2
Tel. +358 201 589-300Fax +358 3 780-6211http://[email protected]
Gabon
Sales Libreville Electro-ServicesB.P. 1889Libreville
Tel. +241 7340-11Fax +241 7340-12
Great Britain
AssemblySalesService
Normanton SEW-EURODRIVE Ltd.Beckbridge Industrial Estate P.O. Box No.1GB-Normanton, West- Yorkshire WF6 1QR
Tel. +44 1924 893-855Fax +44 1924 893-702http://[email protected]
Greece
SalesService
Athen Christ. Boznos & Son S.A.12, Mavromichali StreetP.O. Box 80136, GR-18545 Piraeus
Tel. +30 2 1042 251-34 Fax +30 2 1042 251-59http://[email protected]
Hong Kong
AssemblySalesService
Hong Kong SEW-EURODRIVE LTD.Unit No. 801-806, 8th FloorHong Leong Industrial ComplexNo. 4, Wang Kwong Road Kowloon, Hong Kong
Tel. +852 2 7960477 + 79604654Fax +852 2 [email protected]
China
11/2004 55
Address List
56
Hungary
SalesService
Budapest SEW-EURODRIVE Kft.H-1037 BudapestKunigunda u. 18
Tel. +36 1 437 06-58Fax +36 1 437 [email protected]
India
AssemblySalesService
Baroda SEW-EURODRIVE India Pvt. Ltd.Plot No. 4, GidcPor Ramangamdi · Baroda - 391 243Gujarat
Tel. +91 265 2831086Fax +91 265 [email protected]
Technical Offices Bangalore SEW-EURODRIVE India Private Limited308, Prestige Centre Point7, Edward RoadBangalore
Tel. +91 80 22266565Fax +91 80 [email protected]
Mumbai SEW-EURODRIVE India Private Limited312 A, 3rd Floor, Acme PlazaAndheri Kurla Road, Andheri (E)Mumbai
Tel. +91 22 28348440Fax +91 22 [email protected]
Ireland
SalesService
Dublin Alperton Engineering Ltd. 48 Moyle RoadDublin Industrial EstateGlasnevin, Dublin 11
Tel. +353 1 830-6277Fax +353 1 830-6458
Israel
Sales Tel-Aviv Liraz Handasa Ltd. Ahofer Str 34B / 22858858 Holon
Tel. +972 3 5599511Fax +972 3 [email protected]
Italy
AssemblySalesService
Milano SEW-EURODRIVE di R. Blickle & Co.s.a.s.Via Bernini,14 I-20020 Solaro (Milano)
Tel. +39 2 96 9801Fax +39 2 96 [email protected]
Ivory Coast
Sales Abidjan SICASte industrielle et commerciale pour l’Afrique165, Bld de MarseilleB.P. 2323, Abidjan 08
Tel. +225 2579-44Fax +225 2584-36
Japan
AssemblySalesService
Toyoda-cho SEW-EURODRIVE JAPAN CO., LTD 250-1, Shimoman-no,Toyoda-cho, Iwata gunShizuoka prefecture, 438-0818
Tel. +81 538 373811Fax +81 538 [email protected]
Korea
AssemblySalesService
Ansan-City SEW-EURODRIVE KOREA CO., LTD. B 601-4, Banweol Industrial Estate Unit 1048-4, Shingil-DongAnsan 425-120
Tel. +82 31 492-8051Fax +82 31 [email protected]
Latvia
Sales Riga SIA Alas-KuulKatlakalna 11CLV-1073 Riga
Tel. +371 7139386Fax +371 [email protected]
Lebanon
Sales Beirut Gabriel Acar & Fils sarlB. P. 80484Bourj Hammoud, Beirut
Tel. +961 1 4947-86 +961 1 4982-72+961 3 2745-39Fax +961 1 4949-71 [email protected]
11/2004
Address List
Lithuania
Sales Alytus UAB IrsevaMerkines g. 2ALT-4580 Alytus
Tel. +370 315 79204Fax +370 315 [email protected]
Luxembourg
AssemblySalesService
Brüssel CARON-VECTOR S.A.Avenue Eiffel 5B-1300 Wavre
Tel. +32 10 231-311Fax +32 10 231-336http://[email protected]
Malaysia
AssemblySalesService
Johore SEW-EURODRIVE SDN BHD No. 95, Jalan Seroja 39, Taman Johor Jaya81000 Johor Bahru, JohorWest Malaysia
Tel. +60 7 3549409Fax +60 7 [email protected]
Morocco
Sales Casablanca S. R. M.Société de Réalisations Mécaniques 5, rue Emir Abdelkader05 Casablanca
Tel. +212 2 6186-69 + 6186-70 + 6186-71Fax +212 2 [email protected]
Netherlands
AssemblySalesService
Rotterdam VECTOR Aandrijftechniek B.V. Industrieweg 175 NL-3044 AS RotterdamPostbus 10085NL-3004 AB Rotterdam
Tel. +31 10 4463-700Fax +31 10 4155-552http://[email protected]
New Zealand
AssemblySalesService
Auckland SEW-EURODRIVE NEW ZEALAND LTD. P.O. Box 58-428 82 Greenmount driveEast Tamaki Auckland
Tel. +64 9 2745627Fax +64 9 [email protected]
Christchurch SEW-EURODRIVE NEW ZEALAND LTD. 10 Settlers Crescent, FerrymeadChristchurch
Tel. +64 3 384-6251Fax +64 3 [email protected]
Norway
AssemblySalesService
Moss SEW-EURODRIVE A/SSolgaard skog 71N-1599 Moss
Tel. +47 69 241-020Fax +47 69 [email protected]
Peru
AssemblySalesService
Lima SEW DEL PERU MOTORES REDUCTORES S.A.C.Los Calderos, 120-124Urbanizacion Industrial Vulcano, ATE, Lima
Tel. +51 1 3495280Fax +51 1 [email protected]
Poland
AssemblySalesService
Lodz SEW-EURODRIVE Polska Sp.z.o.o.ul. Techniczna 5 PL-92-518 Lodz
Tel. +48 42 67710-90Fax +48 42 67710-99http://[email protected]
Portugal
AssemblySalesService
Coimbra SEW-EURODRIVE, LDA. Apartado 15 P-3050-901 Mealhada
Tel. +351 231 20 9670Fax +351 231 20 3685http://[email protected]
Romania
SalesService
Bucuresti Sialco Trading SRL str. Madrid nr.4 011785 Bucuresti
Tel. +40 21 230-1328Fax +40 21 230-7170 [email protected]
11/2004
57ddress List
58
Russia
Sales St. Petersburg ZAO SEW-EURODRIVE P.O. Box 263 RUS-195220 St. Petersburg
Tel. +7 812 5357142 +812 5350430Fax +7 812 5352287http://[email protected]
Senegal
Sales Dakar SENEMECA Mécanique GénéraleKm 8, Route de Rufisque B.P. 3251, Dakar
Tel. +221 849 47-70Fax +221 849 [email protected]
Serbia and Montenegro
Sales Beograd DIPAR d.o.o.Kajmakcalanska 54SCG-11000 Beograd
Tel. +381 11 3046677Fax +381 11 [email protected]
Singapore
AssemblySalesService
Singapore SEW-EURODRIVE PTE. LTD. No 9, Tuas Drive 2 Jurong Industrial Estate Singapore 638644
Tel. +65 68621701Fax +65 [email protected]
Slovakia
Sales Sered SEW-Eurodrive SK s.r.o.Trnavska 920SK-926 01 Sered
Tel. +421 31 7891311Fax +421 31 [email protected]
Slovenia
SalesService
Celje Pakman - Pogonska Tehnika d.o.o.UI. XIV. divizije 14SLO – 3000 Celje
Tel. +386 3 490 83-20Fax +386 3 490 [email protected]
South Africa
AssemblySalesService
Johannesburg SEW-EURODRIVE (PROPRIETARY) LIMITEDEurodrive House Cnr. Adcock Ingram and Aerodrome RoadsAeroton Ext. 2Johannesburg 2013P.O.Box 90004Bertsham 2013
Tel. +27 11 248-7000Fax +27 11 [email protected]
Capetown SEW-EURODRIVE (PROPRIETARY) LIMITED Rainbow ParkCnr. Racecourse & Omuramba RoadMontague GardensCape TownP.O.Box 36556Chempet 7442 Cape Town
Tel. +27 21 552-9820Fax +27 21 552-9830Telex 576 [email protected]
Durban SEW-EURODRIVE (PROPRIETARY) LIMITED2 Monaceo PlacePinetownDurbanP.O. Box 10433, Ashwood 3605
Tel. +27 31 700-3451Fax +27 31 [email protected]
Spain
AssemblySalesService
Bilbao SEW-EURODRIVE ESPAÑA, S.L. Parque Tecnológico, Edificio, 302E-48170 Zamudio (Vizcaya)
Tel. +34 9 4431 84-70Fax +34 9 4431 [email protected]
Sweden
AssemblySalesService
Jönköping SEW-EURODRIVE ABGnejsvägen 6-8S-55303 JönköpingBox 3100 S-55003 Jönköping
Tel. +46 36 3442-00Fax +46 36 3442-80http://[email protected]
A
11/2004
Address List
Switzerland
AssemblySalesService
Basel Alfred lmhof A.G.Jurastrasse 10 CH-4142 Münchenstein bei Basel
Tel. +41 61 41717-17Fax +41 61 41717-00http://[email protected]
Thailand
AssemblySalesService
Chon Buri SEW-EURODRIVE (Thailand) Ltd.Bangpakong Industrial Park 2700/456, Moo.7, Tambol DonhuarohMuang DistrictChon Buri 20000
Tel. +66 38 454281Fax +66 38 [email protected]
Tunisia
Sales Tunis T. M.S. Technic Marketing Service7, rue Ibn EI Heithem Z.I. SMMT2014 Mégrine Erriadh
Tel. +216 1 4340-64 + 1 4320-29Fax +216 1 4329-76
Turkey
AssemblySalesService
Istanbul SEW-EURODRIVE Hareket Sistemleri Sirketi Bagdat Cad. Koruma Cikmazi No. 3 TR-34846 Maltepe ISTANBUL
Tel. +90 216 4419163 + 216 4419164 + 216 3838014Fax +90 216 [email protected]
USA
ProductionAssemblySalesService
Greenville SEW-EURODRIVE INC. 1295 Old Spartanburg Highway P.O. Box 518Lyman, S.C. 29365
Tel. +1 864 439-7537Fax Sales +1 864 439-7830Fax Manuf. +1 864 439-9948Fax Ass. +1 864 439-0566Telex 805 550 http://[email protected]
AssemblySalesService
San Francisco SEW-EURODRIVE INC. 30599 San Antonio St.Hayward, California 94544-7101
Tel. +1 510 487-3560Fax +1 510 [email protected]
Philadelphia/PA SEW-EURODRIVE INC. Pureland Ind. Complex 2107 High Hill Road, P.O. Box 481Bridgeport, New Jersey 08014
Tel. +1 856 467-2277Fax +1 856 [email protected]
Dayton SEW-EURODRIVE INC.2001 West Main Street Troy, Ohio 45373
Tel. +1 937 335-0036Fax +1 937 [email protected]
Dallas SEW-EURODRIVE INC.3950 Platinum Way Dallas, Texas 75237
Tel. +1 214 330-4824Fax +1 214 [email protected]
Additional addresses for service in the USA provided on request!
Venezuela
AssemblySalesService
Valencia SEW-EURODRIVE Venezuela S.A.Av. Norte Sur No. 3, Galpon 84-319Zona Industrial Municipal NorteValencia, Estado Carabobo
Tel. +58 241 832-9804Fax +58 241 [email protected]@cantv.net
11/2004
59How we’re driving the world
With people who
think fast and
develop the
future with you.
With a worldwide
service network that is
always close at hand.
With drives and controls
that automatically
improve your productivity.
With comprehensive
knowledge in virtually
every branch of
industry today.
With uncompromising
quality that reduces the
cost and complexity of
daily operations.
With a global presence
that offers responsive
and reliable solutions.
Anywhere.
With innovative
technology that solves
tomorrow’s problems
today.
With online information
and software updates, via
the Internet, available
around the clock.
Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services
SEW-EURODRIVEDriving the world
SEW-EURODRIVE GmbH & Co KG
P.O. Box 3023 · D-76642 Bruchsal / Germany
Phone +49 7251 75-0 · Fax +49 7251 75-1970
→ www.sew-eurodrive.com