3
Copyright © EverExceed Corporation. All rights reserved. Modular Max AGM Range VRLA VRLA Container M 8 x 20-6G Terminal Cover Macromolecule glue MR 2-600 Max VALVE REGULATED LEAD ACID VALVE REGULATED LEAD ACID 2V FLAT PASTED PLATE 2V FLAT PASTED PLATE BATTERY BATTERY Innovative Features Valve Regulated Lead Acid (V.R.L.A.) design Fully tank formed plates Never needs addition of water Spill-proof and leak-proof Proprietary Fixed Orifice Plate Pasting technology applying active materials on both sides of the grid for consistent cell-to-cell performance, higher capacity and uniform grid protection. Operates at a low internal pressure For use in vertical or horizontal position Each cell has a low pressure safety release venting system Standard: Reinforced ABS (UL 94HB) container and cover. Optional: Flame-retardant reinforced ABS container and cover compliant with U.L.94 V-0 with an Oxygen limiting Index of greater than 28% Nano-Carbon enhanced active material to maximize cycle performance and PSoC operation Low calcium Lead/Tin alloy plates for efficient gas recombination for long life in both cycling and float applications Performance Specifications Normal Voltage 2V Capacity 600 Ah @ 10hr to 1.80V per cell @ 20 o C (68 o F) Dimension Length x Width x Height x Total Height: 225 x 181 x 346 x 365 (mm) Weight Approx. 35.5 kg (78.3 lbs) Internal Resistance Approx. 0.28 mΩ Short Circuit Current 4860 A Self Discharge @ 25 o C (77 o F) No more than 3% after 30 days storage Applicable Operating Temperature Range -40 o C~70 o C (40 o F~158 o F ) Ideal Operating Temperature Range 20 o C~30 o C (68 o F~86 o F) Maximum Charge Current 120 A Charging Voltage @ 25 o C (77 o F) Float: 2.23V, Temps coefficient -3 mV/ o C Cycle: 2.30V Contain Materials ABS Terminal Type F-M8 Capacity Affected by Temperature 105% @ 40 o C 85% @ 0 o C 60% @ -20 o C

MR 2-600 Max - Пульсар Лимитед Acid Battery/Modular Max Ran…Copyright © EverExceed Corporation. All rights reserved. Modular Max AGM Range VRLA VRLA Container M 8

Embed Size (px)

Citation preview

Page 1: MR 2-600 Max - Пульсар Лимитед Acid Battery/Modular Max Ran…Copyright © EverExceed Corporation. All rights reserved. Modular Max AGM Range VRLA VRLA Container M 8

Copyright © EverExceed Corporation. All rights reserved.

Modular Max AGM Range VRLA

VRLA

Container

M 8 x 20-6G

Terminal

Cover

Macromolecule glue

MR 2-600 Max

VALVE REGULATED LEAD ACIDVALVE REGULATED LEAD ACID

2V FLAT PASTED PLATE 2V FLAT PASTED PLATE

BATTERYBATTERY

Innovative Features

Valve Regulated Lead Acid (V.R.L.A.) design

Fully tank formed plates

Never needs addition of water

Spill-proof and leak-proof

Proprietary Fixed Orifice Plate Pasting technology applying active materials on

both sides of the grid for consistent cell-to-cell performance, higher capacity

and uniform grid protection.

Operates at a low internal pressure

For use in vertical or horizontal position

Each cell has a low pressure safety release venting system

Standard: Reinforced ABS (UL 94HB) container and cover.

Optional: Flame-retardant reinforced ABS container and cover compliant with

U.L.94 V-0 with an Oxygen limiting Index of greater than 28%

Nano-Carbon enhanced active material to maximize cycle performance and

PSoC operation

Low calcium Lead/Tin alloy plates for efficient gas recombination for long life in

both cycling and float applications

Performance Specifications

Normal Voltage 2V

Capacity 600 Ah @ 10hr to 1.80V per cell

@ 20oC (68

oF)

Dimension Length x Width x Height x Total Height:

225 x 181 x 346 x 365 (mm)

Weight Approx. 35.5 kg (78.3 lbs)

Internal Resistance Approx. 0.28 mΩ

Short Circuit Current 4860 A

Self Discharge

@ 25oC (77

oF)

No more than 3% after 30 days storage

Applicable Operating

Temperature Range -40

oC~70

oC (40

oF~158

oF )

Ideal Operating

Temperature Range 20

oC~30

oC (68

oF~86

oF)

Maximum Charge Current 120 A

Charging Voltage

@ 25oC (77

oF)

Float: 2.23V, Temps coefficient -3 mV/oC

Cycle: 2.30V

Contain Materials ABS

Terminal Type F-M8

Capacity Affected

by Temperature

105% @ 40oC

85% @ 0oC

60% @ -20oC

Page 2: MR 2-600 Max - Пульсар Лимитед Acid Battery/Modular Max Ran…Copyright © EverExceed Corporation. All rights reserved. Modular Max AGM Range VRLA VRLA Container M 8

Copyright © EverExceed Corporation. All rights reserved.

Modular Max AGM Range VRLA

VRLA

Constant Current Discharge Characteristics - Watts Per Cell @ 20oC (68

oF)

Final VPC 1.5hr 2hr 3hr 4hr 5hr 6hr 8hr 10hr 12hr 20hr 24hr

1.85 472 394 294 230 192 168 136 113 96.2 79 52.7

1.80 496 415 310 243 202 177 144 119 101 83 55.7

1.75 511 428 320 251 209 183 149 123 105 86 57.7

Constant Power Discharge Characteristics - Amperes Per Cell @ 20oC (68

oF)

Final VPC 1.5hr 2hr 3hr 4hr 5hr 6hr 8hr 10hr 12hr 20hr 24hr

1.85 245 204 151 117 97.4 84.9 68.6 56.6 48.1 29.6 26.3

1.80 260 216 160 125 103 90.0 72.8 60.0 51.0 31.4 28.0

1.75 271 225 167 130 108 93.9 75.9 62.6 53.2 32.7 29.1

0

1000

2000

3000

4000

5000

6000

7000 6300

5800

2100

1200800

Cyc

leT

ime

s

% Depth of Discharge (D.O.D)

Cycle Life vs Depth of Discharge Based on IEC 896-2

Page 3: MR 2-600 Max - Пульсар Лимитед Acid Battery/Modular Max Ran…Copyright © EverExceed Corporation. All rights reserved. Modular Max AGM Range VRLA VRLA Container M 8

Copyright © EverExceed Corporation. All rights reserved.

Modular Max AGM Range VRLA

VRLA