3
Economical, energy-efficient eco-friendly  airconditioning for larger areas  Energy-efficient Inverter heating/cooling for larger areas Available in sizes from 24 000 BTU to 48 000 BTU Single and 3-phase models 75m piping length to outdoor unit/30m elevation • Environmentally-friendl y R410A gas Supported nationwide by Samsung Air Inverter 4-Way Cassette

MS-samsung-inverter-4way-cassette.pdf

Embed Size (px)

Citation preview

Page 1: MS-samsung-inverter-4way-cassette.pdf

8/10/2019 MS-samsung-inverter-4way-cassette.pdf

http://slidepdf.com/reader/full/ms-samsung-inverter-4way-cassettepdf 1/2

E c o n o m i c a l , e n e r g y - e f f i c i e n t e c o - f r i e n d l y  

a i r c o n d i t i o n i n g f o r l a r g e r a r e a s  

• Energy-efficient Inverter heating/cooling for larger areas

• Available in sizes from 24 000 BTU to 48 000 BTU

• Single and 3-phase models

• 75m piping length to outdoor unit/30m elevation

• Environmentally-friendly R410A gas

• Supported nationwide by Samsung Air

Inverter 4-Way Cassette

Page 2: MS-samsung-inverter-4way-cassette.pdf

8/10/2019 MS-samsung-inverter-4way-cassette.pdf

http://slidepdf.com/reader/full/ms-samsung-inverter-4way-cassettepdf 2/2

Gauteng & Pretoria Western, Eastern & Kwa-Zulu Natal

Central region (012) 661-2002 Northern Cape (031) 579-1895

(011) 704-6320 (021) 556-8292www.samsungair .co.za

Due to Samsung's policy of constant improvement, specifications are subject to change without notice. E&OE 

W  ith electricity prices constantly on the increase, the modern trend is 

towards Inverter technology. The range of Samsung Inverter 4-Way Cassettes 

is the quality route to airconditioning of larger upmarket domestic areas or 

commercial applications.

1. Nominal cooling capacities are based on: Indoor temp: 27 ° CDB, 19 ° CWB; Outdoor temp: 35 ° CDB, 24 ° CWB; Equivalent ref. piping: 7.5m. Level differences: 0m 

2. Nominal heating capacities are based on: Indoor temp: 20 ° CDB, 15 ° CWB; Outdoor temp: 7 ° CDB, 6 °  CWB; Equivalent ref. piping: 7.5m. Level differences: 0m.

3. Sound pressure acquired in a dead room; actual noise level may differ depending on installation conditions.

E c o n o m i c a l , e n e r g y - e f f i c i e n t e c o - f r i e n d l y  a i r c o n d i t i o n i n g f o r l a r g e r a r e a s  

Inverter 4-Way Cassette

CH070EAV1

UH070EAV1

2,100/7,100/8,400

2,000/8,000/11,600

510/2,120/2,700

500/2,190/3,750

3.35(A)

3.65(A)

2.8/9.3/12.1

2.6/9.6/16.9

6.35(1/4)

15.88(5/8)

1/220-240/50

CH070EAV1

P4SMA 

TURBO FAN

17.2

840x218x840

926x280x925

31/35

950x35x950

1,042x103x1,042

7.0/10.3

36/30

DEFAULT

UH070EAV1

TWIN BLDC

R410A 

880x798x310

1,038x861x413

57/61

52

-15~43

-20~24

1,900

50

30

5

30

Capacity (Min./Standard/Max) Cooling *1) Watts

Heating *2) Watts

Power Input (Min./Standard/Max) Cooling Watts

Heating Watts

E.E.R   Cooling W/W

Heating W/W

Running Current   Cooling Amps

(Min./Standard/Max.) Heating Amps

Piping Connection   L iquid mm (inch)

Gas mm (inch)

Power Supply   Ø/V/Hz

INDOOR UNIT

Model

Panel

Fan Type

Air Flow Rate   m3 /min

Set   Dimension (Net) WxHxD mm

Dimension (Gross) WxHxD mm

Weight (Net/Gross) kg

Panel   Dimension (Net) WxHxD mm

Dimension (Gross) WxHxD mm

Weight (Net/Gross) kg

Sound Pressure Level *3) High/Low dB(A)

Indoor Filter

OUTDOOR UNIT

Model

Compressor

Refrigerant   Type

Set   Dimension (Net) WxHxD mm

Dimension (Gross) WxHxD mm

Weight (Net/Gross) kg

Sound Pressure Level   dB(A)

Temperature Range   Cooling ºC

Heating ºC

Quantity of Ref.   g

Extension Length (total)   m

Extension Length (elevation)   m

Standard   m

Additional Ref.   g/m

SPEC I F I CAT I ONS

Indoor unit

Outdoor unit

CH090EAV

UH090EAV

3,200/9,000/10,000

3,000/10,000/13,900

750/2,800/3,200

580/2,770/4,660

3.21(A)

3.61(A)

3.5/12.5/14.1

2.8/12.2/20.6

9.52(3/8)

15.88(5/8)

1/220-240/50

CH090EAV

P4SMA 

TURBO FAN

24

840x298x840

925x360x925

29/35

950x35x950

1,042x103x1,042

7.0/10.3

39/32

DEFAULT

UH090EAV

TWIN BLDC

R410A 

932x1,128x375

1,091x1,286x472

95/110

56

-15~50

-20~24

2,600

75

30

7.5

40

CH105EAV

UH105EAV

3,200/10,500/12,000

2,600/11,200/15,500

700/3,270/3,800

580/3,100/5,600

3.21(A)

3.61(A)

3.3/14.5/16.8

3.6/13.7/24.3

9.52(3/8)

15.88(5/8)

1/220-240/50

CH105EAV

P4SMA 

TURBO FAN

25.7

840x298x840

925x360x925

29/35

950x35x950

1,042x103x1,042

7.0/10.3

40/33

DEFAULT

UH105EAV

TWIN BLDC

R410A 

932x1,128x375

1,091x1,286x472

95/110

56

-15~50

-20~24

2,800

75

30

7.5

40

CH140EAV

UH140EAV

3,800/14,000/15,400

3,450/16,000/18,500

900/4,650/5,400

750/4,690/5,800

3.01(B)

3.41(B)

4/20.6/23.5

3.6/20.8/26.5

9.52(3/8)

19.05(3/4)

1/220-240/50

CH140EAV

P4SMA 

TURBO FAN

30

840x298x840

925x360x925

29/35

950x35x950

1,042x103x1,042

7.0/10.3

45/38

DEFAULT

UH140EAV

TWIN BLDC

R410A 

932x1,128x375

1,091x1,286x472

105/120

59

-15~50

-20~24

3,100

75

30

7.5

40

CH140EAV

UH140GAV

3,800/14,000/15,400

3,450/16,000/18,500

900/4,650/5,400

750/4,690/5,800

3.01(B)

3.41(B)

1.4/7.2/8.5

1.3/7.3/10.2

9.52(3/8)

19.05(3/4)

3/380-415/50

CH140EAV

P4SMA 

TURBO FAN

28/30

840x298x840

925x360x925

29/35

950x35x950

1,042x103x1,042

7.0/10.3

45/38

DEFAULT

UH140GAV

TWIN BLDC

R410A 

932x1,128x375

1,091x1,286x472

105/120

59

-15~50

-20~24

2,800

75

30

7.5

40

CH105EAV

UH105GAV

3,200/10,500/12,000

2,600/11,200/15,500

700/3,270/3,800

580/3,100/5,600

3.21(A)

3.61(A)

1.3/5.0/6.0

1.1/5.0/8.6

9.52(3/8)

15.88(5/8)

3/380-415/50

CH105EAV

P4SMA 

TURBO FAN

22.2/25.7

840x298x840

925x360x925

29/35

950x35x950

1,042x103x1,042

7.0/10.3

40/33

DEFAULT

UH105GAV

TWIN BLDC

R410A 

932x1,128x375

1,091x1,286x472

88/93

56

-15~50

-20~24

2,800

75

30

7.5

40

Model

Sold and suppor ted nat ionwide by :