RTU500 series
Multimeter 560CVD11Data sheet
Application
The Multimeter 560CVD11 is used for measuring analog AC in-put signals from three independent phases with addition inputfor neutral current and voltage. For each phase voltage and cur-rent are measured directly and a number of calculated valuesare generated by the module. In addition the module detects thefault current and the over current direction. The module supportsconfigurations with 3 or 4 voltage transformers.
There are several versions available:
Versions Type LO HI 1 A 5 A
560CVD11 R0021 4U4I x x
560CVD11 R0025 4U4I x x
560CVD11 R0041 4U4I x x
560CVD11 R0045 4U4I x x
Characteristics
The Multimeter is a microprocessor-based Intelligent Electron-ic Device (IED) intended for current, voltage, power and energymeasurement. In addition fault current detection and over cur-rent direction are available.
Current and voltage inputs are connected via transformer only(see Wiring). The module supports a configurations with 3 or 4voltage transformers and 3 or 4 current transformes.
Calculated values are scaled by user programmed constants forcurrent and voltage transformers. All values are updated after200 ms.
The fault current is measured up to 20 times nominal current.The current inputs withstand 50 times nominal current for 1 s.
The Multimeter is equipped with two binary output which are notsupported in RTU500 series configurations.
Wiring
Figure 1: 3 phase with 4 voltage and current transformers in 4 wire con-nection
Figure 2: 3 phase with 3 voltage and current transformers in 4 wire con-nection
2 | 1KGT 150 786 V002 1 1 - Multimeter 560CVD11
Meter Operation
The following measured or calculated values are available fromthe module.
Instantaneous Meter Values
Following values are measured by true RMS conversion
Measurement Measuring Path
Neutral voltage Phase 1-N, 2-N, 3-N
Voltage N, Voltage line unbalance
Phase voltage Phase 1-2, 2-3, 1-3
Current Phase 1, 2, 3, N, Unbalance
Fault current Phase 1, 2, 3, N
Active power (Watt) Phase 1, 2, 3, total
Reactive power (Var) Phase 1, 2, 3, total
Apparent power (VA) Phase 1, 2, 3, total
Power factor (PF) Phase 1, 2, 3, total
Phase angle Phase 1, 2, 3, total
Frequency System
Phase rotation Positive/ negative sequence
The Multimeter supports 4 quadrant power values.
Figure 3: Power measurement convention
Energy values
Integrated total (intermediate and end of period readings) are cal-culated for:
– active energy negative– active energy positive
– reactive energy capacitive– reactive energy inductive
Voltage / Current Distortion (THD)
The 560CVD11 provides a measure of the total harmonic distor-tion (THD), in each phase voltage and current waveform, as apercentage deviation from pure 50Hz or 60Hz sine waves. THDis calculated by Fast Fourier Transform algorithm (FFT).
– U1, U2, U3, UN
– I1, I2, I3, IN
Fault current detection
The devices are with three phases and one neutral for over cur-rent detection. The programming of the time current characteris-tics is identical in all application to require establishing the controlvariables: trip time delayed curve, curve multiplier, pickup currentand reset timing.
The curve reference follows ANSI, IEEE, IEC standards (ANSIC37.90, IEEE C37.112-1996, IEC 255-4, BF412).
Directional overcurrent
Detection
Directional overcurrent detection is for the protection of multiplesource feeders to distinguish between faults in different direc-tions. The device incorporates for three phase and neutral over-current detection with a secure 90° as quadrant coordination inphase directional polarization. Thus, a selected polarizing voltageshould have a function to keep reasonable constant, no matterwhat operating status in a non-faulted or faulted system.
Phase directional overcurrent
Phase directional detection, it requires operating current to de-termine whether current flow in each phase is in forward or re-verse direction, as determined by the connection of the phasesource, selected MTA angle, voltage and current phasors.
Multimeter 560CVD11 - 1KGT 150 786 V002 1 1 | 3
Figure 4: Phases directional overcurrent polarization
Neutral directional detection
The neutral directional detection features control as phase ele-ment to discriminate faults between forward or reverse. This de-tection is also to select operation current (Io) to polarizing voltage(Vo) for the directional control factors.
Figure 5: Neutral directional voltage polarization
4 | 1KGT 150 786 V002 1 1 - Multimeter 560CVD11
Technical data
In addition to the RTU500 series general technical data, the fol-lowing applies:
Input channels
Voltage
U1, U2, U3, UN
Measurement range: 10 ... 300 V AC
Load : <0.15 VA at 300 V
Current
I1, I2, I3, IN
Measurement range:
– R00x5: 5 A, max. 6 A
– R00x1: 1 A, max. 1.2 A
– Fault current inputs: 20 x IN
Load: <0.2 VA per phase
Overload withstand:
– 2 x IN continuous
– 25 x IN 2 sec
– 50 x IN 1 sec
Frequency 46 ... 64Hz
Samples 32 samples per cycle
Harmonics Up to 15th harmonic for 50/60 Hz
Data update interval 200 ms
Accuracy
Phase I 0.25 %
Neutral I 0.25 %
Phase I, fault current 3 %
Phase U 0.25%
Ph-Ph U 0.25%
Watt 0.5 %
VA 0.5 %
Var 0.5 %
PF 0.5 %
Frequency 0.5 % rd
AD converting 12 bit + sign bit
Stability
Stability ≤ 100 ppm/°C
(Temperature range: -10 to +50°C)
Power supply input
Power supply voltage R002x (LO) 24/48 V DC ±15%
Power supply voltage R004x (HI) 80… 260 V AC
80… 330 V DC
Power consumption 12 VA AC
5 W DC
Serial Ports
Modbus RTU protocol RS485
Distance: < 1.2 km
Diagnostic Port RS232
Baud Rate Always configure 19.2 kbps
Load Up to 32 units loads
Mechanical Layout
Dimensions 134.8 mm x 70.3 mm x 149.5 (Width
x Hight x Depth)
Housing type Platic housing
Mounting DIN rail mounting EN 50022 TS35: 35
mm x 15 mm or 35 mm x 7.5 mm
Weight
Insulation tests
Dielectric Strength IEC 60255-5 2 kV AC rms, 1 minute
Immunity test
ANSI / IEEE C37.90.1-1989 3 kV SWC
IEC 61000-4-12 Class III SWC
Fast Transient / Burst IEC 61000-4-4 Class IV SWC
Surge Immunity Test IEC 61000-4-5 Class IV Impulse
Environmental conditions
Nominal operating temperature range:
Start up:
Max. operating temperature, max.
96h:
EN 60068-2-1, -2-2, -2-14
-25 ... +70 °C
-40 °C
+85 °C
Relative humidity
EN 60068-2-30
5 ... 95 %
(non condensing)
Ordering information
560CVD11 R0021 1KGT030000R0021
560CVD11 R0025 1KGT030000R0025
560CVD11 R0041 1KGT030000R0041
560CVD11 R0045 1KGT030000R0045
Additional material
Configuration kit for 560CVDxxx (Tool
CD, cable)
560KCA01 R0001
1KGT030800R0001
Multimeter 560CVD11 - 1KGT 150 786 V002 1 1 | 5
ABB AGPower Systems DivisionP.O. Box 10 03 5168128 Mannheim, Germany
www.abb.com/substationautomation
Note:
The specifications, data, design or other information contained in this document
(the “Brochure”) - together: the “Information” - shall only be for information pur-
poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-
serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.
This product is designed to be connected to and to communicate information
and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall es-
tablish and maintain any appropriate measures (such as but not limited to the in-
stallation of firewalls, application of authentication measures, encryption of da-
ta, installation of anti-virus programs, etc) to protect the product, the network,
its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB
AG is not liable for any damages and/or losses related to such security breaches,
any unauthorized access, interference, intrusion, leakage and/or theft of data or
information.
ABB AG shall be under no warranty whatsoever whether express or implied and
assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in con-
nection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be exclud-
ed. In particular ABB AG shall in no event be liable for any indirect, consequen-
tial or special damages, such as – but not limited to – loss of profit, loss of pro-
duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-
ital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in ac-
cordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).
ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.
© Copyright ABB 2014
All rights reserved