National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org MEMORANDUM TO: Technical Committee on Emergency Power Supplies FROM: Kelly Carey, Project Administrator DATE: November 15, 2016 SUBJECT: NFPA 110 First Draft Technical Committee FINAL Ballot Results (A2018) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 30 Members Eligible to Vote 10 Members Not Returned (D’Antona, DeMoss, Everard, Lau, Loomis, Mills, Nash Jr., Patterson, Sappington, Scroggins) 16 Members Voted Affirmative on All Revisions (w/ comment: Hardy, Hunt, Olson, Schroeder, Schubert, Windey) 4 Members Voted Negative on one or more Revisions (Hardy, Hunt, Olson, Windey) 0 Members Abstained on one or more Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections 3.3.4.3.(c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards.

National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

 

M E M O R A N D U M

TO: Technical Committee on Emergency Power Supplies FROM: Kelly Carey, Project Administrator DATE: November 15, 2016 SUBJECT: NFPA 110 First Draft Technical Committee FINAL Ballot Results (A2018)

According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

30 Members Eligible to Vote 10 Members Not Returned (D’Antona, DeMoss, Everard, Lau, Loomis, Mills, Nash Jr., Patterson,

Sappington, Scroggins) 16 Members Voted Affirmative on All Revisions (w/ comment: Hardy, Hunt, Olson, Schroeder, Schubert, Windey) 4 Members Voted Negative on one or more Revisions (Hardy, Hunt, Olson, Windey) 0 Members Abstained on one or more Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision.

To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2/3 of ballots returned. See Sections 3.3.4.3.(c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards.

Page 2: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.

NFPA 1, Fire Code, 2015 2018 edition.

NFPA 70 ® , National Electrical Code ® , 2017 edition.

NFPA 790, Standard for Competency of Third-Party Field Evaluation Bodies, 2018 edition.

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Sep 20 12:14:25 EDT 2016

Committee Statement

Committee Statement: The references were added since the definitions have been extracted from other NFPA standards.

Response Message:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 74 11/15/2016 1:16 PM

Page 1 of 74

Page 3: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 74 11/15/2016 1:16 PM

Page 2 of 74

Page 4: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 30-NFPA 110-2016 [ New Section after 3.3.5.2 ]

3.3.5 Field Evaluation Body (FEB).

An organization, or part of an organization, that performs field evaluations of electrical or other equipment. [ 790, 2018]

3.3.6 Field Labeled (as applied to evaluated products).

Equipment or materials to which has been attached a label, symbol, or other identifying mark of an FEB indicating the equipmentor materials were evaluated and found to comply with requirements as described in an accompanying field evaluation report. [ 70:100]

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 18:40:55 EDT 2016

Committee Statement

Committee Statement: The new definitions are necessary for the terms added in the new exception for Section 5.2.5.

Response Message:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 74 11/15/2016 1:16 PM

Page 3 of 74

Page 5: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 74 11/15/2016 1:16 PM

Page 4 of 74

Page 6: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 2-NFPA 110-2016 [ Section No. 4.4 [Excluding any Sub-Sections] ]

This standard recognizes two levels of for equipment installation, performance, and maintenance requirements .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 11:25:46 EDT 2016

Committee Statement

Committee Statement: The editorial change clarifies the intent of the statement.

Response Message:

Public Input No. 51-NFPA 110-2016 [Section No. 4.4 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 74 11/15/2016 1:16 PM

Page 5 of 74

Page 7: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 74 11/15/2016 1:16 PM

Page 6 of 74

Page 8: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 29-NFPA 110-2016 [ Section No. 5.2.5 ]

5.2.5

The EPS shall be installed in accordance with NFPA 70, National Electrical Code .

Exception: When a listing process is not available for the engine-generator assembly, a field evaluation body acceptable to theauthority having jurisdiction shall be permitted to affix a field label.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 18:25:13 EDT 2016

Committee Statement

CommitteeStatement:

The exception was added since there currently is no listing process for medium voltage stationary engine-generatorassembly.

Response Message:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

1 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 74 11/15/2016 1:16 PM

Page 7 of 74

Page 9: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Windey, Timothy P.

No comment

Negative with Comment

Olson, Gary L.

Since there is no basis of evaluation in the proposed new text, it may be assumed that the criteria for approval is decided by the NRTL. Thiscannot result in an approval that will provide consistent, positive results and is likely to result in even a worse situation. Manufacturers willhave no way to know whether the hardware they provide will be approved, and will be held responsible for whatever requirements arearbitrarily selected. Facility owners and equipment suppliers may be exposed to considerable delays and cost increases. So, the proposedchange does not solve the problem raised in the request for change.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 74 11/15/2016 1:16 PM

Page 8 of 74

Page 10: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 3-NFPA 110-2016 [ Section No. 5.3.5 ]

5.3.5

The ambient air temperature in the EPS equipment room or outdoor housing containing Level I rotating equipment shall be stabilizeat not less than 4.5°C (40°F) when the equipment is not operating .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 13:38:17 EDT 2016

Committee Statement

CommitteeStatement:

The revision clarifies the intent of the section. The temperature requirement is only relevant when the EPS is notoperating.

Response Message:

Public Input No. 45-NFPA 110-2016 [Section No. 5.3.5]

Public Input No. 25-NFPA 110-2016 [Section No. 5.3.5]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 74 11/15/2016 1:16 PM

Page 9 of 74

Page 11: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 74 11/15/2016 1:16 PM

Page 10 of 74

Page 12: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 4-NFPA 110-2016 [ Section No. 5.6.2 ]

5.6.2 Prime Mover Ratings.

Proper derating factors, such as altitudes, ambient temperature, fuel energy content, accessory losses, and site conditions asrecommended by the manufacturer of the generator set engine shall be used in determining whether or not brake power meets theconnected load requirements.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 13:52:47 EDT 2016

Committee Statement

CommitteeStatement:

The authoritative source for actual derating factors is the manufacturer of the prime mover, not the assembler of agenerator set.

Response Message:

Public Input No. 43-NFPA 110-2016 [Section No. 5.6.2]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 74 11/15/2016 1:16 PM

Page 11 of 74

Page 13: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

"altitudes" should be changed to "installation site altitude"

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 74 11/15/2016 1:16 PM

Page 12 of 74

Page 14: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 5-NFPA 110-2016 [ Section No. 5.6.3.6.1 ]

5.6.3.6.1

A battery charger driven by the prime mover shall not be required for Level 2 generators , provided the automatic battery chargerhas a high-low rate capable of fully charging the starting battery during running conditions as specified in 5.6.3.6 within the timeframe required by this standard while powering all loads connected to the starting batteries .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 13:55:05 EDT 2016

Committee Statement

CommitteeStatement:

An AC powered battery charger is less reliable than a mechanically driven DC alternator because the AC-powered systemhas several single points of failure including the incremental wiring, ac protective devices, and the charger itself. So, for criticalapplications it is reasonable to require both DC power sources in the system.

Generators often have significant DC loads when they are operating, in addition to the starting battery recharge duty. Thisaddition makes it clear that the charger for critical applications must be capable of continuous operation with all loadsattached.

ResponseMessage:

Public Input No. 26-NFPA 110-2016 [Section No. 5.6.3.6.1]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 74 11/15/2016 1:16 PM

Page 13 of 74

Page 15: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 74 11/15/2016 1:16 PM

Page 14 of 74

Page 16: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 6-NFPA 110-2016 [ Section No. 5.6.4.2 [Excluding any Sub-Sections] ]

For otto or diesel cycle prime movers, the type and duration of the cranking cycle shall be as specified in Table 5.6.4.2.

Table 5.6.4.2 Starting Equipment Requirements

Starting Equipment Requirements Level 1 Level 2

(a) Battery unit X X

(b) Battery certification X NA

(c) Cycle cranking X or O O

(d) Cranking limiter time-outs

 Cycle crank (3 cycles) 75 sec 75 sec

 Continuous crank 45 sec 45 sec

(e) Float-type battery charger X X

  dc ammeter X X

  dc voltmeter X X

(f) Recharge time 24 hr 36 hr

(g) Low battery voltage alarm contacts X X

X: Required. O: Optional. NA: Not applicable.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 13:58:10 EDT 2016

Committee Statement

CommitteeStatement:

The cranking cycle was changed to only specify "O". Something that is either required or optional will be taken to meanit is optional.

Response Message:

Public Input No. 50-NFPA 110-2016 [Section No. 5.6.4.2 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 74 11/15/2016 1:16 PM

Page 15 of 74

Page 17: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 74 11/15/2016 1:16 PM

Page 16 of 74

Page 18: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 7-NFPA 110-2016 [ Section No. 5.6.4.7 ]

5.6.4.7

All chargers shall include the following characteristics, which are to be accomplished without manual intervention (i.e., manual switchor manual tap changing):

(1) At its rated voltage, the charger shall be capable of delivering energy into a fully discharged battery unit without damaging thebattery.

(2) The charger shall be capable of returning the fully discharged battery to 100 percent of its ampere-hour rating within the timespecified in Table 5.6.4.2, item (f).

(3) As specified in Table 5.6.4.2, item (e), meters with an accuracy within 5 percent of range shall be furnished.

(4) The generator set or charger shall be permanently marked with the following:

(a) Allowable range of battery unit capacity that can be recharged within the time requirements of Table 5.6.4.2

(b) Nominal output current and voltage

(c) Sufficient battery-type data to allow replacement batteries to be obtained

(5) The battery charger output and performance shall be compatible with the batteries furnished.

(6) Battery chargers used in Level 1 systems shall include temperature compensation for charge rate.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 14:00:22 EDT 2016

Committee Statement

CommitteeStatement:

The marking requirements in (4)(a), (b), and (c) are modified to make the requirement more clear.

Temperature compensation is added because battery failure is the most common reason for failure of a generator set to startand pick up loads. Improper charge rate is the most common reason for premature battery failure because proper charge rateis temperature dependent, and without temperature compensation there isn't a good way to assure that a proper charge rate isachieved.

ResponseMessage:

Public Input No. 27-NFPA 110-2016 [Section No. 5.6.4.7]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

17 Affirmative All

3 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 74 11/15/2016 1:16 PM

Page 17 of 74

Page 19: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Schubert, Randy H.

Temperature compensation is great for lead acid batteries but may lead to undercharge for nickel cadmium and generally not recommendedfor ni-cd. If battery compartment is maintained within guideline per this chapter is it needed?

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 74 11/15/2016 1:16 PM

Page 18 of 74

Page 20: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 8-NFPA 110-2016 [ Section No. 5.6.5.1 ]

5.6.5.1

A control panel shall be provided and shall contain the following:

(1) Automatic remote start capability

(2) “Run-off-automatic” mechanical switch

(3) Shutdowns as required by 5.6.5.2(3)

(4) Alarms as required by 5.6.5.2(4)

(5) Controls as required by 5.6.5.2(5)

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 14:24:26 EDT 2016

Committee Statement

Committee Statement: Mechanical was added to ensure direct mechanical control for manual generator starting.

Response Message:

Public Input No. 28-NFPA 110-2016 [Section No. 5.6.5.1]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

16 Affirmative All

1 Affirmative with Comments

3 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 74 11/15/2016 1:16 PM

Page 19 of 74

Page 21: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hartsell, Jonathan

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Hardy, Ross M.

This does not say that the mechanical switch needs to be used to initiate a test. Only that one must be included in the control panel.

Negative with Comment

Hunt, James

"mechanical switch" is too restrictive. some manufacturers may want to perform switching functions as part of a more integrated controlpanel. Possibly in the form of a touch screen or other method. As long as safety and functionality is maintained, the operation mode is notimportant.

Olson, Gary L.

The use of the term "mechanical" may be interpreted as being limited to, for example, a rotary switch with mechanical contacts to signalcontrol operation, which is really not the most reliable means of manually entering information into a control panel. I would suggest replacingthe word "mechanical" with "operator mode select" switch, which would allow for use of a wide range of switches without risk of improperinterpretation.

Windey, Timothy P.

The intent of the submitters PI was to make this more flexible, as modern digital generator controls have HMI membrane panels that includethe switch function. The intent was not to insert the word "mechanical" ahead of the word "switch".

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 74 11/15/2016 1:16 PM

Page 20 of 74

Page 22: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 9-NFPA 110-2016 [ Section No. 5.6.5.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 74 11/15/2016 1:16 PM

Page 21 of 74

Page 23: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

5.6.5.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 74 11/15/2016 1:16 PM

Page 22 of 74

Page 24: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Where a control panel is mounted on the energy converter, it shall be mounted by means of antivibration shock mounts, if required,to maximize reliability. An automatic control and safety panel shall be a part of the EPS containing the following equipment orpossess the following characteristics, or both:

(1) Cranking control equipment to provide the complete cranking cycle described in 5.6.4.2 and required by Table 5.6.4.2

(2) Panel-mounted control switch(es) marked “run–off–automatic” to perform the following functions:

(a) Run: Manually initiate, start, and run prime mover

(b) Off: Stop prime mover or reset safeties, or both

(c) Automatic: Allow prime mover to start or stop by closing operating a remote contact and stop by opening the remotecontact .

(3) Controls to shut down and lock out the prime mover under any of the following conditions:

(a) Failing to start after specified cranking time

(b) Overspeed

(c) Low lubricating-oil pressure

(d) High engine temperature (An automatic engine shutdown device for high lubricating-oil temperature shall not be required.)

(e) Operation of remote manual stop station

(4) Individual alarm indication to annunciate any of the conditions listed in Table 5.6.5.2 and with the following characteristics:

(a) Battery powered

(b) Visually indicated

(c) Have additional contacts or circuits for a common audible alarm that signals locally and remotely when any of the itemizedconditions occurs

(d) Have a lamp test switch(es) to test the operation of all alarm lamps

(5) Controls to shut down the prime mover upon removal of the initiating signal or manual emergency shutdown

(6) The ac instruments listed in 5.6.9.9

Table 5.6.5.2 Safety Indications and Shutdowns

Level 1 Level 2

Indicator Function (at Battery Voltage) CV S RA CV S RA

(a) Overcrank X X X X X O

(b) Low water temperature X NA X X NA O

(c) High engine temperature pre-alarm X NA X O NA NA

(d) High engine temperature X X X X X O

(e) Low lube oil pressure X X X X X O

(f) Overspeed X X X X X O

(g) Low fuel main tank X NA X O NA O

(h) Low coolant level X O X X O X

(i) EPS supplying load X NA NA O NA NA

(j) Control switch not in automatic position X NA X X NA X

(k) High battery voltage X NA NA O NA NA

(l) Low cranking voltage X NA X O NA O

(m) Low voltage in battery X NA NA O NA NA

(n) Battery charger ac failure X NA NA O NA NA

(o) Lamp test X NA NA X NA NA

(p) Contacts for local and remote common alarm X NA X X NA X

(q) Audible alarm silencing switch NA NA X NA NA O

(r) Low starting air pressure X NA NA O NA NA

(s) Low starting hydraulic pressure X NA NA O NA NA

(t) Air shutdown damper when used X X X X X O

(u) Remote emergency stop NA X NA NA X NA

CV: Control panel–mounted visual. S: Shutdown of EPS indication . RA: Remote audible. X: Required. O: Optional. NA: Notapplicable.

Notes:

(1) Item (p) shall be provided, but a separate remote audible signal shall not be required when the regular work site in 5.6.6 is staffed24 hours a day.

(2) Item (b) is not required for combustion turbines.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 74 11/15/2016 1:16 PM

Page 23 of 74

Page 25: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

(3) Item (r) or (s) shall apply only where used as a starting method.

(4) Item (i) EPS ac ammeter shall be permitted for this function.

(5) All required CV functions shall be visually annunciated by a remote, common visual indicator.

(6) All required functions indicated in the RA column shall be annunciated by a remote, common audible alarm as required in5.6.5.2(4).

(7) Item (g) on gaseous systems shall require a low gas pressure alarm.

(8) Item (b) shall be set at 11°C (20°F) below the regulated temperature determined by the EPS manufacturer as required in 5.3.1.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 14:33:15 EDT 2016

Committee Statement

CommitteeStatement:

The change to the start command is in response to changes in the 2017 National Electrical Code. The word "indication"was struck from table legend for clarity.

ResponseMessage:

Public Input No. 48-NFPA 110-2016 [Section No. 5.6.5.2]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 74 11/15/2016 1:16 PM

Page 24 of 74

Page 26: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 74 11/15/2016 1:16 PM

Page 25 of 74

Page 27: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 10-NFPA 110-2016 [ Section No. 5.6.5.5 ]

5.6.5.5

The cranking cycle shall be capable of being initiated by any of the following:

(1) Manual start initiation as specified in 5.6.5.2(2)(a) .

(2) Loss of normal power at any automatic transfer switch (ATS) considered a part of the EPSS. Prime mover shall start uponclosing of a remote switch or contacts and shall stop, after appropriate time delays, when switch or contacts are opened.

(3) Clock exerciser located in an ATS or in the control panel.

(4) Manually operated (test) switch located in each ATS that simulates a loss of power and causes automatic starting and operationuntil this switch is reset, to cause the engine circuit to duplicate its functions in the same manner commercial power is restoredafter a true commercial power failure.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 14:38:38 EDT 2016

Committee Statement

CommitteeStatement:

Remote start circuits for most generator sets will accept either a N.O. or a N.C. contact, so the requirement shouldn't be tiedto just the N.O. case. For example, a NC remote contact must be used when projects require fail-safe genset start/stopwiring.

ResponseMessage:

Public Input No. 49-NFPA 110-2016 [Section No. 5.6.5.5]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 74 11/15/2016 1:16 PM

Page 26 of 74

Page 28: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

It should also be noted that Fire Pump ATS start signals for a generator set are required to be "fail-safe", so the requirement for contactclosure to start would conflict with that requirement.

Windey, Timothy P.

I am the submitter of PI 49. This was handled correctly when it came up in the meeting, but the report got the wording wrong. Please correctthe wording, so it is per the outcome in the panel meeting.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 74 11/15/2016 1:16 PM

Page 27 of 74

Page 29: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 12-NFPA 110-2016 [ Section No. 5.6.5.6 [Excluding any Sub-Sections] ]

All installations shall have a be provided with at least one remote manual stop station of a type to prevent inadvertent orunintentional operation tamperproof emergency stop switch located outside the room housing the prime mover, where so installed,or elsewhere on the premises where the prime mover is located outside the building.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 15:21:49 EDT 2016

Committee Statement

Committee Statement: This revision clarifies the use and location of the stop station required by NFPA 110.

Response Message:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

17 Affirmative All

1 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 74 11/15/2016 1:16 PM

Page 28 of 74

Page 30: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Windey, Timothy P.

No comment

Negative with Comment

Hardy, Ross M.

The emergency stop switch should not be mandated to be tamper proof here in 110. That should be left up to the AHJ depending on theinstallation. The emergency stop switch could be located inside an area that is already secured/ tamper proof.

Olson, Gary L.

The change is unnecessary, since the NEC in article 445.18 (B)(2) now covers this requirement.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 74 11/15/2016 1:16 PM

Page 29 of 74

Page 31: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 11-NFPA 110-2016 [ Section No. 5.6.9.9 ]

5.6.9.9

The generator instrument panel for Level 1 applications shall contain the following:

(1) An ac voltmeter(s) for each phase or a phase selector switch

(2) An ac ammeter(s) for each phase or a phase selector switch

(3) A frequency meter

(4) A voltage-adjusting feature to allow ± 5 percent voltage adjustment

(5) An ac kW meter indicating total load on the generator set

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 14:44:57 EDT 2016

Committee Statement

CommitteeStatement:

In a generator set application an engine has very limited overload capability, and without a kW meter there is no easy way foran operator to visually see when loads are approaching the limits of the engine. Because ammeters don't consider powerfactor, they don't actually indicate impending overload on an engine.

Level 1 systems should have this critical feature. kW meters are now a standard feature in most generator set products usedin Level 1 systems.

ResponseMessage:

Public Input No. 29-NFPA 110-2016 [Section No. 5.6.9.9]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 74 11/15/2016 1:16 PM

Page 30 of 74

Page 32: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 74 11/15/2016 1:16 PM

Page 31 of 74

Page 33: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 13-NFPA 110-2016 [ Section No. 6.2.2.1 ]

6.2.2.1*

Undervoltage-sensing devices shall be provided to monitor all ungrounded lines of the primary normal source of power as follows:

(1) When the voltage on any phase falls below the minimum operating voltage of any load to be served, the transfer switch shallautomatically initiate engine start and the process of transfer to the EPS.

(2)

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 15:59:13 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Public Input No. 3-NFPA 110-2016 [Section No. 6.2.2.1]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

* When the voltage on all phases of the primary normal source returns to within specified limits for a designated period of time,the process of transfer back to primary normal power shall be initiated.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 74 11/15/2016 1:16 PM

Page 32 of 74

Page 34: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 74 11/15/2016 1:16 PM

Page 33 of 74

Page 35: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 14-NFPA 110-2016 [ Section No. 6.2.3 ]

6.2.3* Interlocking.

Mechanical interlocking or an approved alternate method shall prevent the inadvertent interconnection of the primary normal powersupply and the EPS, or any two separate sources of power.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 16:08:59 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 74 11/15/2016 1:16 PM

Page 34 of 74

Page 36: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 74 11/15/2016 1:16 PM

Page 35 of 74

Page 37: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 15-NFPA 110-2016 [ Section No. 6.2.5 ]

6.2.5* Time Delay on Starting of EPS.

A time-delay device shall be provided to delay starting of the EPS. The timer shall prevent nuisance starting of the EPS and possiblesubsequent load transfer in the event of harmless momentary power dips and interruptions of the primary source.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 16:11:25 EDT 2016

Committee Statement

CommitteeStatement:

The word "harmless" was removed from the sentence. If there are momentary power dips and interruptions with the primarysource, we don't really know if they will be harmless. It could be harmless to some loads, but not harmless to others.

ResponseMessage:

Public Input No. 54-NFPA 110-2016 [Section No. 6.2.5]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 74 11/15/2016 1:16 PM

Page 36 of 74

Page 38: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 74 11/15/2016 1:16 PM

Page 37 of 74

Page 39: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 32-NFPA 110-2016 [ Section No. 6.2.8 ]

6.2.8* Time Delay on Retransfer to Primary Source.

An adjustable time-delay device with automatic bypass shall be provided to delay retransfer from the EPS to the primary source ofpower and to allow the primary normal source to stabilize before retransfer of the load.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 14:14:50 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

17 Affirmative All

3 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 74 11/15/2016 1:16 PM

Page 38 of 74

Page 40: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Schroeder, Ronald A.

The first word "primary" was not changed to "normal" as agreed at the committee meeting

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 74 11/15/2016 1:16 PM

Page 39 of 74

Page 41: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 33-NFPA 110-2016 [ Section No. 6.2.9 ]

6.2.9 Time Delay Bypass If EPS Fails.

The time delay shall be automatically bypassed if the EPS fails.

6.2.9.1

The transfer switch shall be permitted to be programmed for a manually initiated retransfer to the primary normal source to providefor a planned momentary interruption of the load.

6.2.9.2

If used, the arrangement in 6.2.9.1 shall be provided with a bypass feature to allow automatic retransfer in the event that the EPSfails and the primary normal source is available.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 14:20:07 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 74 11/15/2016 1:16 PM

Page 40 of 74

Page 42: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 74 11/15/2016 1:16 PM

Page 41 of 74

Page 43: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 34-NFPA 110-2016 [ Section No. 6.2.11.1 ]

6.2.11.1

Transfer switches shall transfer the connected load to the EPS and immediately return to primary normal power automatically incase of an EPS failure.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 14:21:56 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 74 11/15/2016 1:16 PM

Page 42 of 74

Page 44: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 74 11/15/2016 1:16 PM

Page 43 of 74

Page 45: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 35-NFPA 110-2016 [ Section No. 6.2.12 ]

6.2.12 Test Switch.

A test means shall be provided on each ATS that simulates failure of the primary normal power source and then transfers the load tothe EPS.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 14:23:50 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 74 11/15/2016 1:16 PM

Page 44 of 74

Page 46: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 74 11/15/2016 1:16 PM

Page 45 of 74

Page 47: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 36-NFPA 110-2016 [ Section No. 6.2.16.1 ]

6.2.16.1 Interlocking.

Reliable mechanical interlocking or an approved alternate method shall prevent the inadvertent interconnection of theprimary normal power source and the EPS.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 14:25:48 EDT 2016

Committee Statement

CommitteeStatement:

The word "primary" used to describe the power source referenced in this paragraph is not consistent with other NFPAdocuments. NFPA 70 and 99 both use "normal" to describe this power source in multiple places. The word "normal" is also theconventional term used in the electrical power industry and by most equipment manufacturers on their products and literaturedescribing this power source and the transfer switch position.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 74 11/15/2016 1:16 PM

Page 46 of 74

Page 48: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

It would be better if the change to the end 6.3 were changed to "manage the loads to maintain power qualify, and maintain power quality withpriority to critical loads"

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 74 11/15/2016 1:16 PM

Page 47 of 74

Page 49: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 16-NFPA 110-2016 [ Section No. 6.3 ]

6.3 Load Switching (Load Shedding). Requirements for Paralleled Generator Sets.

When two or more engine generator sets are paralleled for emergency power, the paralleled system is the source, and system logicshall be arranged to inhibit connection of EPS-damaging loads manage the loads to maintain power quality .

6.3.1

Each transfer switch shall have a continuous current rating and interrupting rating for all classes of loads to be served.

6.3.2

The transfer switch shall be capable of withstanding the available fault current at the point of installation.

6.3.1

The transfer of loads to the EPS shall be sequenced as follows:

(1) First-priority loads shall be switched to the emergency bus upon sensing the availability of emergency power on the bus.

(2) Each time an additional engine generator set is connected to the bus, a remaining load shall be connected in order of priorityuntil all emergency loads are connected to the bus.

(3) The system shall be designed so that, upon failure of one or more engine generator sets, the load is automatically reduced,starting with the load of least priority and proceeding in ascending priority, so that the last load affected is the highest-priorityload.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 16:13:28 EDT 2016

Committee Statement

CommitteeStatement:

The title "Load Switching (Load Shedding)" was too specific and only described 6.3.3.(3). Section 6.3 and the underlying textare about the requirements for transfer switches used with paralleled generator sets. The last part of the sentence was changedto clarify that the system logic is managing the loads, whether it's priority pickup (when gensets are coming on line), or loadshed (if a genset fails). This revision also clarifies that the paralleled system is the source, so that ATS ratings can be correctlychosen.

The requirements in 6.3.1 and 6.3.2 are deleted since they are already covered 6.1.4 and 6.1.5.

ResponseMessage:

Public Input No. 47-NFPA 110-2016 [Section No. 6.3]

Public Input No. 30-NFPA 110-2016 [Section No. 6.3 [Excluding any Sub-Sections]]

Public Input No. 31-NFPA 110-2016 [Sections 6.3.1, 6.3.2]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

1 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 74 11/15/2016 1:16 PM

Page 48 of 74

Page 50: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Windey, Timothy P.

No comment

Negative with Comment

Olson, Gary L.

This change should be modified slightly to make it clear that it refers to valves external to the generator set package and not devices that areintegral to the generator set. Suggest: Automatically actuated valves shall not be permitted in the fuel oil supply or fuel oil return lines externalto the generator set for Level 1 Emergency Power Supply Systems. There are fuel control valves on a generator set that are necessary toproperly control the generator set.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 74 11/15/2016 1:16 PM

Page 49 of 74

Page 51: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 18-NFPA 110-2016 [ Section No. 7.9.13 ]

7.9.13

Automatically actuated valves shall not be permitted in the fuel oil supply or fuel oil return lines for Level 1 emergency power supplysystems .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 16:36:23 EDT 2016

Committee Statement

CommitteeStatement:

Based on reliability of fusible links or other automatically actuated valves, NFPA 110 Level 2 generators that do not supportlife safety systems should be allowed to use automatically actuated valves to protect network or IT infrastructure from fire.

ResponseMessage:

Public Input No. 57-NFPA 110-2016 [Section No. 7.9.13]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 74 11/15/2016 1:16 PM

Page 50 of 74

Page 52: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 74 11/15/2016 1:16 PM

Page 51 of 74

Page 53: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 19-NFPA 110-2016 [ Section No. 7.11.6 ]

7.11.6*

For systems in seismic risk areas, the EPS, transfer switches, distribution panels, circuit breakers, and associated controls shall becapable of performing their intended function during and after being subjected to the anticipated seismic shock.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 16:41:04 EDT 2016

Committee Statement

CommitteeStatement:

The revision is made to align the seismic requirements in this document with the International Building Codes (IBC). TheIBC requires that generator sets and their support equipment, transfer switches, and switchgear be able to operate after aseismic event.

ResponseMessage:

Public Input No. 46-NFPA 110-2016 [Section No. 7.11.6]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 74 11/15/2016 1:16 PM

Page 52 of 74

Page 54: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 74 11/15/2016 1:16 PM

Page 53 of 74

Page 55: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 20-NFPA 110-2016 [ Section No. 7.12.3 ]

7.12.3

The wiring between the EPS output terminals and the first distribution overcurrent protective device terminals within the EPSSshall be located at a minimal distance to ensure system reliability and safety.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:03:30 EDT 2016

Committee Statement

Committee Statement: This section is redundant with 7.12.1.

Response Message:

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 74 11/15/2016 1:16 PM

Page 54 of 74

Page 56: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 74 11/15/2016 1:16 PM

Page 55 of 74

Page 57: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 21-NFPA 110-2016 [ Section No. 7.13.4.3 [Excluding any Sub-Sections] ]

A load shall be applied for a 2-hour, full-load test. The building load shall be permitted to serve as part or all of the load,supplemented by a load bank of sufficient size to provide a load equal to 100 percent of the nameplate kW rating of the EPS, lessapplicable derating factors for site conditions. With full load applied, the coolant temperature of the generator set shall stabilize at aconstant value relative to outdoor ambient temperature at least 30 minutes prior to completion of the test.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:06:48 EDT 2016

Committee Statement

CommitteeStatement:

In general, a 2-hour full load test is sufficient to verify that a generator will carry rated load successfully. However, in order toverify that high load levels will not cause eventual cooling system failure, the coolant temperature should be observed tostabilize prior to stopping the test.

ResponseMessage:

Public Input No. 34-NFPA 110-2016 [Section No. 7.13.4.3 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 74 11/15/2016 1:16 PM

Page 56 of 74

Page 58: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 74 11/15/2016 1:16 PM

Page 57 of 74

Page 59: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 22-NFPA 110-2016 [ Section No. 7.13.4.5 ]

7.13.4.5

All safeties specified in 5.6.5 and 5.6.6 shall be tested on site as recommended by the manufacturer.

Exception No. 1: It shall be permitted for the manufacturer to test and document overcrank, high engine temperature, low lube oilpressure and overspeed safeties prior to shipment.

Exception No. 2: Where the safety functions are proven to be fail-safe as demonstrated by monitoring of normal conditions onengine metering and demonstration that a failed sensor or circuit will not cause shutdown of the engine, further testing of thesafeties is not required.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:09:09 EDT 2016

Committee Statement

CommitteeStatement:

Engines that utilize analog sensors and verify the operation of protective functions by setting trip points at normaloperating values of parameters demonstrate proper safety shutdown operation.

ResponseMessage:

Public Input No. 35-NFPA 110-2016 [Section No. 7.13.4.5]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 74 11/15/2016 1:16 PM

Page 58 of 74

Page 60: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 74 11/15/2016 1:16 PM

Page 59 of 74

Page 61: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 23-NFPA 110-2016 [ Section No. 8.4.2 ]

8.4.2*

Diesel generator Generator sets in service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of thefollowing methods:

(1) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer

(2) Under operating temperature conditions and at not less than 30 percent of the EPS standby nameplate kW rating

8.4.2.1

The date and time of day for required testing shall be decided by the owner, based on facility operations.

8.4.2.2

Equivalent loads used for testing shall be automatically replaced with the emergency loads in case of failure of the primary source.

8.4.2.3*

Diesel-powered EPS installations that do not meet the requirements of 8.4.2 shall be exercised monthly with the available EPSSload and shall be exercised annually with supplemental loads at not less than 50 percent of the EPS nameplate kW rating for 30continuous minutes and at not less than 75 percent of the EPS nameplate kW rating for 1 continuous hour for a total test duration ofnot less than 1.5 continuous hours.

8.4.2.4

Spark-ignited generator sets shall be exercised at least once a month with the available EPSS load for 30 minutes or until the watertemperature and the oil pressure have stabilized. The date and time of day for required testing shall be decided by the owner, basedon facility operations.

8.4.2.4.1

The date and time of day for required testing shall be decided by the owner, based on facility operations. Equivalent loads used fortesting shall be automatically replaced with the emergency loads in case of failure of the primary source.

8.4.2.4.2

Equivalent loads used for testing shall be automatically replaced with the emergency loads in case of failure of the primary source.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:18:00 EDT 2016

Committee Statement

CommitteeStatement:

Load level on natural gas generator sets can be qualified in the same way that they are for diesel generator sets, with theprimary difference being that the required exhaust gas temperature level is different, and it takes considerably less load toreach that temperature. Separate paragraphs for diesel and natural gas generator sets are not needed.

Preventing damage/degradation in the engine is not the only concern with generator sets: operating them at load helps to drivemoisture out of the electrical portions of the system so they are less likely to fail. So, even if the gas genset may run a fewmore hours a year than might be allowed with the current rules, the effect on the generator is beneficial.

ResponseMessage:

Public Input No. 37-NFPA 110-2016 [Section No. 8.4.2]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 74 11/15/2016 1:16 PM

Page 60 of 74

Page 62: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

Section 8.4.2.4 is completely removed.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 74 11/15/2016 1:16 PM

Page 61 of 74

Page 63: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 24-NFPA 110-2016 [ Section No. 8.4.9.7 ]

8.4.9.7*

Where the test required in 8.4.9 is combined with the annual load bank test, the first 3 hours shall be first portion of the test shall beat not less than the minimum loading required by 8.4.9.5 and , the remaining last hour shall be at not less than 75 percent of thenameplate kW rating of the EPS, and the duration of the test shall be in accordance with 8.4.9.1 and 8.4.9.2 .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:29:19 EDT 2016

Committee Statement

Committee Statement: This revision simplifies and clarifies the requirements of this section.

Response Message:

Public Input No. 15-NFPA 110-2016 [Section No. 8.4.9.7]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 74 11/15/2016 1:16 PM

Page 62 of 74

Page 64: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 74 11/15/2016 1:16 PM

Page 63 of 74

Page 65: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 31-NFPA 110-2016 [ Section No. A.3.3.4 ]

A.3.3.4 Emergency Power Supply System (EPSS).

Where multiple generators are connected together on a common bus, the common bus is considered to be the system source. SeeAnnex B for diagrams of typical systems.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 09 11:42:23 EDT 2016

Committee Statement

CommitteeStatement:

Recognizing the system bus for multiple generator systems will clarify design requirements for things such as groundingand bonding of the system, and selective coordination of the distribution system connected to the generator source.

ResponseMessage:

Public Input No. 24-NFPA 110-2016 [Section No. 3.3.4]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 74 11/15/2016 1:16 PM

Page 64 of 74

Page 66: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 74 11/15/2016 1:16 PM

Page 65 of 74

Page 67: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 25-NFPA 110-2016 [ Section No. A.5.1.1(1) ]

A.5.1.1(1)

The grade of diesel fuel selected for use in a prime mover should be based on recommendations from the diesel enginemanufacturer and ASTM D975, Standard Specification for Diesel Fuel Oils. Where possible, the The purchaser of fuel for the primemover should specify a diesel fuel that does not contain biodiesel, which can accelerate the degradation of the diesel fuel if storedlonger than 6 months. If diesel fuel is stored outside for long-term storage, it can be necessary to use a winter or arctic grade ofdiesel fuel or to take precautions such as insulating and heat-tracing fuel tanks and lines to ensure that fuel will flow to the primemover under the coldest possible conditions.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:32:10 EDT 2016

Committee Statement

Committee Statement: Biodiesel is not recommended in a standby generator set.

Response Message:

Public Input No. 38-NFPA 110-2016 [Section No. A.5.1.1(1)]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 74 11/15/2016 1:16 PM

Page 66 of 74

Page 68: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 74 11/15/2016 1:16 PM

Page 67 of 74

Page 69: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 26-NFPA 110-2016 [ Section No. A.5.6.4.6 ]

A.5.6.4.6

It is intended that the battery charger be factory-built, adjusted, and approved for the specific type, construction, and capacity of thebattery. For lead-acid batteries, the battery charger should be tested for the specific gravity, type, and concentration of grid alloys,such as high or low gravity, high or low antimony, calcium, or none.

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 17:50:30 EDT 2016

Committee Statement

Committee Statement: Section 5.6.4.6 relates to battery chargers not to batteries.

Response Message:

Public Input No. 39-NFPA 110-2016 [Section No. A.5.6.4.6]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 74 11/15/2016 1:16 PM

Page 68 of 74

Page 70: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 74 11/15/2016 1:16 PM

Page 69 of 74

Page 71: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 27-NFPA 110-2016 [ Section No. A.6.2.15 ]

A.6.2.15

ATSs can be provided with accessory controls that provide a signal to operate remote motor controls that disconnect motors prior totransfer and to reconnect them after transfer when the residual voltage has been substantially reduced. Another method is to providein-phase monitors within the ATS in order to prevent retransfer to the primary source until both sources are nearly synchronized. Athird method is to use a programmed neutral position transfer switch. See Section 230.95 of NFPA 70 , National Electrical Code .

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 18:01:31 EDT 2016

Committee Statement

CommitteeStatement:

NEC Section 230.95 describes ground fault protection which has nothing to do with transfer switch operation whenswitching inductive loads.

Response Message:

Public Input No. 41-NFPA 110-2016 [Section No. A.6.2.15]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 74 11/15/2016 1:16 PM

Page 70 of 74

Page 72: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 74 11/15/2016 1:16 PM

Page 71 of 74

Page 73: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

First Revision No. 28-NFPA 110-2016 [ Chapter C ]

Annex C Informational References

C.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections of this standard and are notpart of the requirements of this document unless also listed in Chapter 2 for other reasons.

C.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 2019 edition.

NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 2014 2018 edition.

NFPA 54, National Fuel Gas Code, 2015 2018 edition.

NFPA 56, Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems, 2014 2017edition.

NFPA 58, Liquefied Petroleum Gas Code, 2014 2017 edition.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 70B, Recommended Practice for Electrical Equipment Maintenance, 2013 2016 edition.

NFPA 99, Health Care Facilities Code, 2015 2018 edition.

NFPA 101®, Life Safety Code®, 2015 2018 edition.

NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems, 2016 2019 edition.

C.1.2 Other Publications.

C.1.2.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI C 84.1, Standard for Electric Power Systems and Equipment — Voltage Ratings (60 hertz) , 2006 .

C.1.2.1 ASCE Publications.

American Society of Civil Engineers, 1801 Alexander Bell Drive, Reston, VA 20191.

ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, 2010.

C.1.2.2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshocken Conshohocken , PA 19428-2959.

ASTM D975, Standard Specification for Diesel Fuel Oils,2011b 2015c .

ASTM D1835, Standard Specification for Liquefied Petroleum (LP) Gases,2011 2013 .

C.1.2.3 IEEE Publications.

IEEE, Three Park Avenue, 17th Floor, New York, NY 10016-5997.

ANSI/IEEE 493, Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems, 2007.

C.1.2.4 NEMA Publications.

National Electrical Manufacturers Association, 1300 North 17th Street, Suite, 1847 , Rosslyn 900, Arlington , VA 22209.

ANSI/NEMA C 84.1, Standard for Electric Power Systems and Equipment — Voltage Ratings (60 hertz) , 2011.

ANSI/ NEMA MG 1, Standard for Motors and Generators, 2009 2016 .

ANSI/ NEMA MG 2, Safety Standard and Guide for Selection, Installation and Use of Electric Motors and Generators, 2001,Revision 1, 2007 2014 .

C.1.2.5 NHC Publications.

National Hurricane Center, 11691 SW 17th Street, Miami, FL 33165-2149.

SLOSH (Sea, Lake and Overland Surges from Hurricanes) Model.

C.1.2.6 U.S. Government Publications.

U.S. Government Publishing Office, 732 North Capitol Street, NW, Washington, DC 20401-0001.

FEMA 543, Design Guide for Improving Critical Facility Safety from Flooding and High Winds, 2007.

FEMA 577, Design Guide for Improving Hospital Safety in Earthquakes, Floods, and High Winds, 2007.

C.2 Informational References.

The following documents or portions thereof are listed here as informational resources only. They are not a part of the requirementsof this document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 74 11/15/2016 1:16 PM

Page 72 of 74

Page 74: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

C.2.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2019 edition.

C.3 References for Extracts in Informational Sections. (Reserved)

Submitter Information Verification

Submitter Full Name: Chris Coache

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 07 18:07:23 EDT 2016

Committee Statement

Committee Statement: References are changed to current SDO names, addresses, standard names, numbers, and editions.

Response Message:

Public Input No. 2-NFPA 110-2015 [Chapter C]

Ballot Results

This item has passed ballot

30 Eligible Voters

10 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

D'Antona, Jason

DeMoss, Dennis

Everard, William H.

Lau, Larry

Loomis, Chad E.

Mills, George

Nash, Jr., Hugh O.

Patterson, Ralph E.

Sappington, Steve R.

Scroggins, Rich

Affirmative All

Allen, Ernest E.

Battalora, Raymond J.

Chisholm, Sr., Dan

Cotton, Kenneth A.

Dagenais, David A.

Day, Richard L.

Feller, Louis J.

Gregory, James R. (Skip)

Hardy, Ross M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 74 11/15/2016 1:16 PM

Page 73 of 74

Page 75: National Fire Protection Association Report...First Revision No. 37-NFPA 110-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 2018

Hartsell, Jonathan

Hunt, James

Lang, Michael J.

Manche, Alan

Schroeder, Ronald A.

Schubert, Randy H.

Smidt, Ronald M.

Stanko, Raymond J.

Stymiest, David

Affirmative with Comment

Olson, Gary L.

I agree with the change suggested and justification.

Windey, Timothy P.

No comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...