内部公开 Internal Use Only<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE 1 New Site External alarm implementation guide For new site External we have two scenario: 1. ZTE ODU External Alarm Configuration (With Sceco) 2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset) ZTE ODU External Alarm Configuration (With Sceco) Alarm No. Designation DDF SLOT Remarks Connection 1 Door Cabinet Open(WHITE / BLUE) 1 Connected directly to BBU SA Card Sensor - DDF 1 - BBU SA 2 High Temperature(WHITE / ORANGE) 2 Connected directly to BBU SA Card Sensor - DDF 2 - BBU SA 3 Tower Light Failure Alarm(WHITE / GREEN) 3 Connected directly to BBU SA Card Sensor - DDF 3 - BBU SA 4 Rectifier Alarm (WHITE / BROWN) 4 From B201 SIB Board (Power Unit) - X15 port X15 - DDF 4 - BBU SA 5 AC Power Fail(WHITE / GRAY) 5 From B201 SIB Board (Power Unit) - X16 port X16 - DDF 5 - BBU SA 6 Environmental Over Humidity(RED / BLUE) 6 From B201 SIB Board (Power Unit) - X16 port X16 - DDF 6 - BBU SA 7 DC Low Voltage alarm(RED / ORANGE) 7 From B201 SIB Board (Power Unit) - X17 port X17 - DDF 7 - BBU SA 8 SMOKE Alarm(RED / Green) 8 From B201 SIB Board (Power Unit) - X17 port X17 - DDF 8 - BBU SA

New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

Embed Size (px)

Citation preview

Page 1: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 1 页

New Site External alarm implementation guide

For new site External we have two scenario:

1. ZTE ODU External Alarm Configuration (With Sceco)

2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

ZTE ODU External Alarm Configuration (With Sceco)

Alarm

No. Designation

DDF

SLOT Remarks Connection

1 Door Cabinet Open(WHITE /

BLUE)

1 Connected directly to

BBU SA Card

Sensor - DDF 1 - BBU SA

2 High Temperature(WHITE /

ORANGE)

2 Connected directly to

BBU SA Card

Sensor - DDF 2 - BBU SA

3 Tower Light Failure

Alarm(WHITE / GREEN)

3 Connected directly to

BBU SA Card

Sensor - DDF 3 - BBU SA

4 Rectifier Alarm (WHITE /

BROWN)

4 From B201 SIB Board

(Power Unit) - X15 port

X15 - DDF 4 - BBU SA

5 AC Power Fail(WHITE / GRAY) 5 From B201 SIB Board

(Power Unit) - X16 port

X16 - DDF 5 - BBU SA

6 Environmental Over

Humidity(RED / BLUE)

6 From B201 SIB Board

(Power Unit) - X16 port

X16 - DDF 6 - BBU SA

7 DC Low Voltage alarm(RED /

ORANGE)

7 From B201 SIB Board

(Power Unit) - X17 port

X17 - DDF 7 - BBU SA

8 SMOKE Alarm(RED / Green) 8 From B201 SIB Board

(Power Unit) - X17 port

X17 - DDF 8 - BBU SA

Page 2: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 2 页

SA card

(BS8800)

D

D

F

Medium light alarm cable

Door open alarm

DDF Port 1

Rectifier alarm

DDF Port 4

Tower Light Failre Alarm

DDF Port 3

High tep. Alarm

DDF Port 2

Door 1 sensor

AC1(1500W) alarm cable

Smoke alarm

DDF Port 8

DC Low voltage alarm

DDF Port 7

Environmental over humidity alarm

DDF Port 6

AC power fail alarm

DDF Port 5

ODU Cabinet

Door 2 sensor

AC2(1500W) alarm cable

AC3(500W) alarm cable

Smoke sensor

B201 X15 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X17 Port(NC/COM)

B201 Module

Tower

ZTE ODU External Alarm Drawing (With Sceco)

Low light alarm cable

Low light alarm cable

Junction

box

Control

box

B201 X17

Port(NC/COM)

Actual

virtual

B201 X24

Port

NodeB(BS8800) part:

SA card

(BS8800)

D

D

F

For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor

should be connect to SA card through DDF terminal.before connect sensor,please make loop back test

from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.

External alarm connection :

SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor

1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable

Page 3: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 3 页

2.SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable

We used core color(new)

Page 4: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 4 页

3.connection picture:

Page 5: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 5 页

No1. Door Cabinet Open(WHITE / BLUE)(in DOU cabinet)

SA card

(BS8800)

D

D

F

Door open alarm

DDF Port 1

Door 1 sensorODU Cabinet

Door 2 sensor

Door1 and Door2 Sensor cable need parallel connect to DDF port1

Door 1 Sensor :

Door2 Sensor

Door 1&Door 2 Sensor cable :

Page 6: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 6 页

No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet)

SA card

(BS8800)

D

D

F

High tep. Alarm

DDF Port 2

AC1(1500W) alarm cable

ODU Cabinet

AC2(1500W) alarm cable

AC3(500W) alarm cable

AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2

1.AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM)

Page 7: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 7 页

2.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM)

3.AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM)

4.alarm cable in ODU location

Page 8: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 8 页

No 3.Tower Light Failure Alarm(WHITE / GREEN)-on tower

SA card

(BS8800)

D

D

F

Medium light alarm cable

Tower Light Failre Alarm

DDF Port 3

Tower

Low light alarm cable

Low light alarm cable

Junction

box

Control

box

Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3

Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,

From Junction box connect to Control box alarm input terminal, From Control box alarm output

connect to DDF port3 terminal. For detail connection please reference installation and operation

manual in the box.

Page 9: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 9 页

No 4. Rectifier Alarm (WHITE / BROWN)

No 5. AC Power Fail(WHITE / GRAY)

No 6.Environmental Over Humidity(RED / BLUE)

No 7.DC Low Voltage alarm(RED / ORANGE)

SA card

(BS8800)

D

D

F

Rectifier alarm

DDF Port 4

DC Low voltage alarm

DDF Port 7

Environmental over humidity alarm

DDF Port 6

AC power fail alarm

DDF Port 5

B201 X15 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X17 Port(NC/COM)

Rectifier Alarm From X15 NC/COM connect to DDF port4

AC Power Fail From X16 NC/COM connect to DDF port5

Environmental Over Humidity From X16 NC/COM connect to DDF port6

DC Low Voltage alarm From X17 NC/COM connect to DDF port7

Below description detail how to setting external alarm in ZXDU68 B201 system.

About the relay alarm of the ZXDU68B201 power supply system

The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:

shown the board layout.

Page 10: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 10 页

1. Network interface board(IP/SNMP);

2. Modem power board(MPB);

3. Signal interface board(SIB)

And the signal interface board provides external communication interfaces and monitoring

unit signal interfaces. The signal board is shown in figure as below. Refer to table for the

signal board interfaces description.

Figure signal board:

Table signal interface name

Interface Interface name Interface Interface name

X4 Battery 1 temperature X21 RS485 interface

X5 Battery 2 temperature X22 Rs232 interface

X12 Temperature control X23 Flood alarm

X14 Input relays 1,2,3,4 X24 Smoke alarm

X15 Out relays 1,2 X25 Ambient temperature

X16 Out relays 3,4 X26 Intrusion alarm

X17 Out relays 5,6

Then the relays alarm function need to three interface: X15、X16、X17.

So the relays alarm function of the signal interface definition as belowTable-1:

Interface Pin Signal

definition

Signal description Relay alarm definition

(monitor parameters)

X15

Output relays

1,2

1 2NO Relay output 2-NO(normally open) A3

2 2COM Relay output 2-Common end A3

3 2NC Relay output 2-NC(normally closed) A3

Page 11: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 11 页

4 1NO Relay output 1-NO --

5 1COM Relay output 1-Common end --

6 1NC Relay output 1-NC --

X16

Output

relays3,4

1 4NO Relay output 4-NO A5

2 4COM Relay output 4-Common end A5

3 4NC Relay output 4-NC A5

4 3NO Relay output 3-NO A2

5 3COM Relay output 3-Common end A2

6 3NC Relay output 3-NC A2

X17

Output relays

5,6

1 6NO Relay output 6-NO A4

2 6COM Relay output 6-Common end A4

3 6NC Relay output 6-NC A4

4 5NO Relay output 5-NO A5

5 5COM Relay output 5-Common end A5

6 5NC Relay output 5-NC A5

The relays alarm function has two options on the signal board, one relay output-NO(normal open)

and one relay output-NC(normal close). So need to know the BTS interface alarm definition

which it is NO or NC.

If it is ‘NO’, and connect relay alarm cables step:

1、 One group relay out need two signal cables , and one terminal connect with relay out –ON and

relay output –common end on the signal board interface, another terminal connect with the

BTS interface.

DDF

NO

COMMON

2、 Other relays alarm as above the connection step, until it finished.

After finished to connect the signal cables , and set parameters in the monitor.

Step:

1、check the monitor screen, find the CTRL menu.

Page 12: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 12 页

2、press the button ENTER of the monitor.

3、 Entering the password: 0000.

4、 Enter the setup parameter system: 1. Setup Para, press the Enter button.

5、 Find the Alarm Para in the Setup Para.

6、 Enter the Alarm Para menu, find the 1.Set Relay to Enter

7、 And find the relays alarm parameter. According to the relays alarm requirements, set the relay

Page 13: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 13 页

alarm.

Setup procedures:

If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.

So the relay alarm parameter set A2.

Refer to above the Table-1.

Figure (set parameter:

No 8. SMOKE Alarm(RED / Green)

SA card

(BS8800)

D

D

F

Smoke alarm

DDF Port 8

ODU Cabinet

Smoke sensorB201 X17

Port(NC/COM)

B201 X24

Port

Smoke alarm From Smoke sensor first connect to X24,then X17 NC/COM connect to DDF port8

Page 14: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 14 页

ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

Alarm

No. Designation

DDF

SLOT

DRY Contact Alarm

Connection Connection

1 Door Cabinet Open(WHITE / BLUE) 1 Connected directly to BBU SA

Card Sensor - DDF 1 - BBU SA

2 High Temperature(WHITE / ORANGE) 2 Connected directly to BBU SA

Card Sensor - DDF 2 - BBU SA

3 Rectifier Alarm (WHITE / GREEN) 3 From B201 SIB Board

(Power Unit) - X15 port X15 - DDF 3 - BBU SA

4 AC Power Fail(WHITE / BROWN) 4 From B201 SIB Board

(Power Unit) - X16 port X16 - DDF 4 - BBU SA

5 Environmental Over Humidity(WHITE /

GRAY) 5

From B201 SIB Board

(Power Unit) - X16 port X16 - DDF 5 - BBU SA

6 DC Low Voltage alarm(RED / BLUE) 6 From B201 SIB Board

(Power Unit) - X17 port X17 - DDF 6 - BBU SA

7 Generator Fault(RED / ORANGE) 7 From Generator Control Port

connected directly to SA Card Generator Control - DDF 7 - BBU SA

8 Generator Low Fuel(RED / GREEN) 8 From the Storage Tank

Connected directly to SA Card Storage Tank Sensor - DDF 8 - BBU SA

SA card

(BS8800)

D

D

F

Generator

Door open alarm

DDF Port 1

Rectifier alarm

DDF Port 3

Generator Fault

DDF Port 7

High tep. Alarm

DDF Port 2

Door 1 sensor

AC1(1500W) alarm cable

DC Low voltage alarm

DDF Port 6

Environmental over humidity alarm

DDF Port 5

AC power fail alarm

DDF Port 4

ODU Cabinet

Door 2 sensor

AC2(1500W) alarm cable

AC3(500W) alarm cable

B201 X15 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X16 Port(NC/COM)

B201 X17 Port(NC/COM)

B201 Module

Generator

ZTE ODU External Alarm Drawing (With Genset)

Genterator tank

Actual

virtual

Generator Low Fuel

DDF Port 8

Page 15: New Site External alarm implementation guidedocshare01.docshare.tips/files/30747/307473395.pdf · New Site External alarm implementation guide ... 1. ZTE ODU External Alarm ... Below

内部公开 Internal Use Only▲

<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE

第 15 页

For alarm No.1—No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST

(With Sceco) installation.

No7. Generator Fault(RED / ORANGE)

No8 Generator Low Fuel(RED / GREEN)

SA card

(BS8800)

D

D

F

Generator Generator Fault

DDF Port 7

Generator

Genterator tankGenerator Low Fuel

DDF Port 8