    Controlmatik abw M5262 - 10/04

    DOSING MEASUREMENT &

    REGULATION EQUIPMENT

    Product information

    Compact swimmingpool

    measurment & regulation

    unit seriesM 5262 C

    General:

    Compact swiimingpool measurment & regulation unit type M 5262 C is designed for

    measurment and control of free chlorine, redox and pH in swimming-pools applications.

    The unit consists of two electrodes (gold and copper - measurement electrodes) measure-

    ment cell with mechanical cleaning and flow armature with pH and redox electrode and with three

    microprocessor controlled display units with with PID regulator build in and with automatictemperature compensation which provides accurate measured signal on the output and is

    shown on the graphical display.

    Each control unit is equipped with PID regulator output and with two galvanically separated4-20 mA signal on the amplifiers output. Unit can control dosing pumps or motor dosing valve

    User can easily communicate with control unit over graphic display and four keys.

    All this guarantees accurate and continuous measurement and regulation.

    on-line free chlorine, pH and redox measurement

    PID regulation for free chlorine and pH included

    galvanicaly separated current outputs

    digital outputs for dosing pumps or motor valve reg.

    Measuring and control

  • 7/30/2019 new_M5262C_1

    2/2

    Order codes :

    M 5262C/

    Contro lmatik abw M5262 - 10/04

    Fajfarjeva 15, 1230 Domzale, SlovenijaTel. +386 1 72 13 552, Fax + 386 1 72 19 360

    E-mail: [email protected]

    Measuring ranges

    Cl - 0-1 mgCl2/l

    pH - 2-12 pH

    Redox - 0 - 1000 mV

    DOSING MEASUREMENT &

    REGULATION EQUIPMENT

    C - Current output sensor (4 - 20 mA)

    D - Communication output - Selecan

    SCH00040

    185

    Electronics unit drawing:

    A - Automatic temperature

    compensation

    Units drawing:

    Data is subject to change without notice.

    Measuring and control

    Technical data :

    Measuring range (M.R.) 0 - 1 mg/l, 2 -12 pH, 0 -1000 mV

    Measured value resolution 0,01 mg/l, 0,1pH, 1 mV

    Deviation of indication, measured value maximum 2% of M.R.

    pH range 6.5...8,5

    Automatic temperature compensation range 0...+50C

    Electrical data :

    Supply voltage 24 VAC20%

    Power 3 x 5 W Maximum

    Isolation voltage 500V (to analog part)

    Current output connector (each electronic):

    Moduls 2

    Current range 4...20 mA

    Load maximum 600 E

    Output range adjustable to (M.R.)

    Output Mode Selectable

    - Free chlorine output, pH output, redox output

    - Temperature

    - Regulator output

    Regulator connector (each electronic):

    Outputs 2 x 24 VAC / 250 mAInputs 2 x 24 VAC

    Mode Selectable

    - Motor Control

    - Pump Control

    General data :

    Ambient temperature -10...+50C

    Relative humidity 10...95 % non-condensating

    Control unit protection IP 65

    Dimensions 300 x 450 x 70

    Weight 5,0 kg

    R - Regulator included