12
Electro Industries/GaugeTech The Leader in Power Monitoring and Smart Grid SolutionsAdvanced Metering and Communication Constant Calibration™ Architecture Provides Highly Stable Readings, as the Meter Self-calibrates Every 10 Seconds Critical Metering Needs are Met by 0.06% Accuracy in Energy Metrology Color Touchscreen Programmable Display Enhances the Meter's Functionality 6 Available Communication Ports, Including Dual Ethernet Ports Ethernet Ports Offer Secure, Configurable Port Services Control Supported COM Protocols Include Modbus, DNP3, IEC 61850, GOOSE Messaging, and SNMP Superior Recording and Power Quality Analysis Class A IEC 61000-4-30 Edition 3 Power Quality Measurement Class A IEC 61000-4-15 Flicker Measurement Class A IEC 61000-4-7 Harmonics Measurement Supports Customized EN 50160 Power Quality Reporting Offers up to 4 GB of Memory for Storage Offers 50 MHz Transient Capture Speed The Perfect Meter for Co-generation and Independent Power Providers Supports Substation Automation, Grid Monitoring, and Distribution Substation Reliability Measurements Nexus ® 1500+ Next Generation Power Quality Meter for Critical Energy Circuits www.electroind.com

Next Generation Power Quality Meter for Critical Energy .../pdf/brochures/Nexus... · reporting is available via the EN 50160 reporting format, which provides a weekly report of power

  • Upload
    dotu

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Electro Industries/GaugeTech™

The Leader in Power Monitoring and Smart Grid Solutions™

Advanced Metering and Communication

• ConstantCalibration™ArchitectureProvidesHighlyStableReadings,astheMeterSelf-calibratesEvery10Seconds

• CriticalMeteringNeedsareMetby0.06%AccuracyinEnergyMetrology

• ColorTouchscreenProgrammableDisplayEnhancestheMeter'sFunctionality

• 6AvailableCommunicationPorts,IncludingDualEthernetPorts

• EthernetPortsOfferSecure,ConfigurablePortServicesControl

• SupportedCOMProtocolsIncludeModbus,DNP3,IEC61850,GOOSEMessaging,andSNMP

Superior Recording and Power Quality Analysis

• ClassAIEC61000-4-30Edition3PowerQualityMeasurement

• ClassAIEC61000-4-15FlickerMeasurement

• ClassAIEC61000-4-7HarmonicsMeasurement

• SupportsCustomizedEN50160PowerQualityReporting

• Offersupto4GBofMemoryforStorage

• Offers50MHzTransientCaptureSpeed

• ThePerfectMeterforCo-generationandIndependentPowerProviders

• SupportsSubstationAutomation,GridMonitoring,andDistributionSubstationReliabilityMeasurements

Nexus®

1500+ Next Generation Power Quality Meter for Critical Energy Circuits

www.

electr

oind

.com

Introduction

TheNexus®1500+meterisdesignedtobeaprimaryandtestablerevenuemeterthatadditionallyprovidesadvancedpowerqualityanalysisfunctions.Itrecordseveryaspectofelectricalpower,includingpowerqualityandtransients,andgivesyouaccesstothisinformationbothinrealtimeandthroughreportsonthequalityoftheelectricalcircuitincompliancewiththeIEC61000-4-30ClassAEdition3andEN50160in-ternationalstandards.Inthisway,theNexus®1500+meterprovidesyouwithacomprehensivepictureofyourcircuits’powerusageandreliability.

TheNexus®1500+meter’scapabilitiesinsurethatessentialdataiscapturedandstored,sothatcriticalinformationaboutimportantelectricalcircuitsisnotlost.Designedwithsuperiorprocessingpowerthatletsitmeasureenergyusageprecisely,largeamountsofmemoryforrecordingevents,andadvancedpowerqualityreportingcompliance,theNexus®1500+meteristheclearchoiceforyourapplicationswherecriticalmeteringisanabsolutenecessity,beitforpowerutility,industrial,orothercriticalmeteringusage.

Highly Accurate Energy Metrology

TheNexus®1500+meterincorporatesoneofthemostadvancedmetrologiesavailableformeasuringenergy.ProvidinghighlyaccuratemeasurementsexceedingtheANSIC12.20(0.2Class)standardandtheIEC62053-22(0.2SClass)standard,the1500+providesanEnergyClassaccuracyof0.06%,withtypicalshippingaccuraciesof0.02%.Additionally,themeterhasahighlyaccuratefrontpaneltestpulsethatletsyoutestononepulseatlowpulseweight,whichyoucanusetoquicklydetermineaccuracy.Themeteralsofeaturesanewprecisionrealtimeclockthatoffersaccuracyof3.5ppm,orlessthan10secondsper

monthdrift.

New Constant Calibration™ Architecture Increases the Stability of Measurement Accuracy

TheNexus®1500+meterimprovesonexistingNexus®architecturebyprovidingoneofthebestauto-calibrationmethodsavailable.EarlierNexus®modelsreliedonAccuMeasure™technologythatauto-calibratedthemeterevery12hoursor5degreetemperaturechange.ConstantCalibration™architectureimprovessignificantlyonthis,byprovidingconsiderablyfaster,ongoingauto-calibration.

WithConstantCalibration™architecture,themeterutilizesaseparatecalibrationchanneltocalibratetheincomingsignalinrealtimeevery10seconds,therebyinsuringthatthemeterexperiencesminimaldriftinaccuracyovertimeandtemperature.Withthisauto-calibratingcircuit,rightoutoftheboxtheNexus®1500+meterwillstabilizeitsreadingswithin10seconds.Thismeansyounolongerhavetowaitforthemetertostabilizeintemperaturetoachieveoptimalaccuracy.WithConstantCalibration™architecture,themeterwillholditsaccuracythroughoutitsoperationrange.Oncethemeteristested,itwillmaintaintheprecise

accuracyeveniftheoperatingconditionsarelessthanideal.

Typical Meter Accuracy Charts

Typical0.02%AccuracyoverFullRange

Notethattypicalaccuracyis0.02%;however,themeterspecificationshouldbe

consultedforaccuracydetails.

MeterMaintainsAccuracyoverChangingTemperature

Typical Accuracy over Current Range Drift over Temperature

2

Advanced Revenue Meter for Primary Loads

TheNexus®1500+unitisaprimaryrevenuemeterdesignedtobeusedforanyimportantapplications.Inadditiontohighlyaccurateenergymeasurement,themeterfeatures:

• Full4quadrantmetering

• Energyloadprofiling:logvirtuallyunlimitedhistoricaltrending

• TimeofUseperpetualcalendarthatsupportsmultipletariffs

• TransformerandLineLosscompensation:forbothironandcopperandtotalsubstationlosses

• CTandPTcompensation:correctforerrorsincurrentandvoltagetransformers

• Coincidentalreadings:e.g.,PForVARsattimeofPeakDemand,toidentifynumberofcapacitorsneeded,peakinefficiencies,etc.

• Loadaggregation/universalmetering:pulseinputscanbeusedtoaggregateoraccumulatedifferentloads;utilityproductssuchasgasandwatercanalsobeaccumulated

System Events Logging

Theunitprovidesextensiveusageinformationfordetectionofunauthorizedaccess.Theunitrecords:

• Resets

• Programmingchanges.

• Passwordaccesschanges

• Timechanges

• Powerup/down

• ChangeofFirmware

Test Mode and Energy Presets

TheNexus®1500+meteroffersaTestModefortestingmeteraccuracy.TestModeallowsthemetertobetestedforwatt-hourandVAR-houraccuracywithoutaffectingthestoredreadings.UsingTestMode,userscanverifythemeter’sreadingsoverthelifespanofaninstalledmeterwithouthavingtoresetenergyordisturbtheloadprofilinganddemandrecording.

TheEnergyPresetfeatureallowsausertoprogramtheenergyaccumu-latorvaluesuponexitingTestMode.Thisletstheusercompensateforaccumulationsmissedduringtestingtime,oreasilyswapanewmeterforameterbeingreplaced.

Perpetual Time of Use for Complex Metering

TheNexus®1500+meterusesaperpetualTimeofUse(TOU)calendarthatonlyneedstobesetuponce.TheTOUimplementationallowstheusertosetupmultipletariffstomeetanycontractualobligations.ItalsoallowstheusertocustomizeanyenergyparameterforTOU.The16availableTOUregisterscanbeconfigurednotonlyforTOUbuilt-inenergyreadings,butalsoforanystoreddatafrompulsesorRTUMasterreadingsthatmightneedTOUfunctionality.

3

Class A Power Quality Recorder

EIG’sNexus®1500+meterisoneoftheindustry’spremierfaultandvoltagedisturbancerecorders.Thisinstrumentcapturesandstoresacomprehensivepictureofthehistoryofvoltagereliabilityandpowerqualityevents,fordetailedandextensiveforensicengineeringanalysis.TheNexus®1500+meteroffersamultitudeofpowerqualityfunctionalitythathelpstheuseridentifypowerqualityproblems,includingharmonics,sags,swellsandtransients.Powerqualityfeaturesinclude:

IEC 61000-4-30 Class A Ed. 3 Power Quality Meter:

TheNexus®1500+meterisacomprehensiveClassApowerqualityrecorder.DesignedspecificallytomeettherigorousIEC61000-4-30ClassAEdition3standard,itmeasuresandanalyzespowerqualityprecisely.AllreportingisavailableviatheEN50160reportingformat,whichprovidesaweeklyreportofpowerqualityindicessystem-wide.Additionally,thereportcanbefullycustomizedtomeettherequiredapplicationorjurisdictionalneeds.

• IEC61000-4-30Reporting:ClassAReporting–supportsthemoststringentinternationalpowerqualitystandards;theNexus®1500+meteroffersfullreportingofpowerqualityconditionsusingtheIEC61000-4-30ClassAmethodology.

• AutomaticgenerationofEN50160reportsandEN50160reportcustomizationtosupportdifferentjurisdictionalrequirements.

IEC 61000-4-15 Class A Flicker Meter:

• FlickercompliantwiththeIEC61000-4-15ClassAstandard.

• Flickermeasurementoperatesonboth220volt/50Hzand120volt/60Hzthroughoutstandardtestpoints.

IEC 61000-4-7 Class A Harmonics and Interharmonics Analysis:

• Viewharmonicmagnitudestothe511thorderforeachvoltageandcurrentchannel.

• Harmonicmagnitudesandphaseanglesinrealtimeareresolvedtothe127thorder.

• ObtainTHD,TDD,andK-Factor.

• Conductpowerqualityanalysisatthehighendoftheharmonicmagnitudespectrum.

Phasor Analysis:

Themonitorreadsaphaseangleanalysisbetweenthevoltageandcurrentchannels,allowingyoutoanalyzeefficiencyandsystemintegrity.

High-speed Voltage Reliability Measurements:

TheNexus®1500+meterprovidesindustryleadingvoltagemeasurement.

• RealtimesinglecycleRMSmeasurements

• Customizablehigh-speedreadings–canbesetfrom2to20cyclesRMS

Easy-to-UnderstandReportsDisplayingPQCompliance

4

Set Limit Control:

TheNexus®1500+powermonitorprovidestheuserwithprogrammablesetpoints.Thisfeatureallowsausertoconfigurethemetertobeusedasacontroldeviceformanyapplications,suchas:

• Capacitorcontrol

• Loadshedding

• Automatictransferschemes

• Transformermonitoring&control

• Redundantprotection(notdesignedforprimaryover-currentprotection)

• Manyothercontrolfunctions

Alarm Notification:

• TheNexus®1500+meterletsyousetmultipleprogrammablelimitsforanymeasuredvalue,aswellasthosesetupinaBooleanlogictree,andlimitssetupintheIEC61850protocolimplementation.Userscanbenotifiedofalarmconditionsviaemail.

16 Bit Waveform and Fault Recorder:

• Recordupto1024samplespercycle;captureatransientatover800,000samplespercycleorat50MHzsamplingspeed.

• Voltageandcurrentrecordinghaspreandpost-eventanalysis.

• Faultrecordingoffers8timesfullscalecapturecapability.

• 16bitA/Dconverterprovidesprecisewaveformresolution.

• Bothhardwareandsoftwaretriggersareavailable.

High-speed Status Input Triggers:

• Waveformsarerecordedattimeofstatuschange.

• Inputchangeandwaveformrecordingaretime-stampedtoa100microsecondresolution.

• Inputsandwaveformscanbedisplayedtogethertotimebreakersandrelays.

Subcycle 50 MHz Transient Recorder (V3 Option):

Transientsoftencauseintermittent,expensiveperiodsofdowntime.Thesubcycletransientrecorderallowsyouto:

• Recordsubcycletransientsat50MHzresolution.

• Monitorswitchingnoisefromcapacitors,statictransferswitches,SCRs,andotherdevicesthatnegativelyimpactpowerquality.

Thisfeatureisessentialforcriticalapplicationssuchashospitals,wafer-fabsplants,datacentersandotherhighlypowerqualitysensitiveapplications.Independent ITIC/CBEMA Log Plotting:

• Quicklyviewtotalsurges,sags,andaveragedurationintheindependentITIC/CBEMAlog.

• SEMIF47graphingisavailableforpowerqualitycomplianceinthesemi-conductorindustry.

Compatible Waveform Formats

UsingCommunicatorEXT™software,themeterwillprovideallwaveformdataviaCOMTRADEandPQDIFcompatibleformats.ThisallowsthewaveformPQandfaultrecordstobereadbymostthird-partywaveformanalysissoftwareprograms.

• COMTRADE(commonformatfortransientdataexchange)isdefinedbyIEEEStdC37.111.

• PQDIF(powerqualitydatainterchangeformat)isdefinedbyIEEEStd1159.3-2003.

RecordandAnalyzeWaveformFaultandTransientData

5

Multiport Communication

TheNexus®1500+meteroffersupto6simultaneouscommunicationportsandmultipleprotocolstomeetalmosteveryneed.

Hardware Features:

• 2optionalRS485portsspeakingModbusand/orDNP3.0

• USBfrontpanelport

• ANSIopticalfrontpanelport

• 2separatelyaddressableEthernetports

• OptionalFiberorRJ45mediaononeEthernetport

Ethernet Communication Port Capabilities:

• 2Ethernetportsprovidemultiplesimultaneouscommunication

• EachporthasseparateMACaddressandIPaddress

• SupportsModbusTCP/IP,DNP3andIEC61850

• GOOSEmessagingprotocolsupportedforIEC61850

• Upto32ModbusTCP/IPsocketsperEthernetport

• Highlysecureportcontroltodisableunneededservicesandports

• EmailFunction-SMTPemailtoclientonalarm

• PreciseTimeSynchcronization-SNTPTimeSyncprotocol

• FileTransferProtocol-High-speedfiledatatransfer

Industry-Leading DNP3 Level 2 Plus - Complies with DNP Level 1 and Level 2 Certification Requirements:

• Upto136measurements(64BinaryInputs,8BinaryCounters,64AnalogInputs)canbemappedtoDNPstaticpoints.

• Upto16relaysand8resetscanbecontrolledthroughDNP.

• Report-by-exceptionprocessing(DNPEvents)deadbandswithunsolicitedresponseforserialcommunicationissupported.

• 250eventsinfoureventtypes(BinaryInputChange,FrozenCounter,CounterChange,andAnalogChange)areavailable.

SNMP Protocol:

• SNMPprotocolV1andV2csupported

• 40+measurementssupported

• Trapsforlimits,inputchange,andpowerquality

• ColdStarttrapandAuthenticationFailuresupported

• Perfectfordatacentersandothermanageddevicenetworks

8 Built-in Digital High-speed Status Inputs:

• Inputsautomaticallysensewhetherthecircuitisexternallywetted.

• Ifexternallywetted,inputupto150VDCisaccepted.

• Ifinternallywetted,themetersuppliesthenecessaryvoltageforthecontolapplication.

VAUX Input:

• Neutraltogroundorauxvoltagereadings

• Synchronizingschemes,forexample,obtainingthefrequency,magnitude,andphaseangleonbothsidesofaswitchorbetweengeneratorandbusvoltage

Secure Communication

TheNexus®1500+meteroffers9levelsofpasswordsecuritytoprotectthemeterfromunauthorizeduse.Eachlevelcanbeconfiguredtoenablespecificcapabilities,sothataUtilitycancontrolaccesstofunctionsaccordingtothetypeofuser.Forexample,oneuserlevelisabletocreateandchangeTOUcalendars,whileadifferentuserlevelisabletoreadTOUdata,butnotchangeanything.

HighlyCapableCommunicationOptions6

Substation Automation

V-Switch™keylevelsV2andaboveofferanembeddedIEC61850ProtocolServerforseamlessintegrationwithsubstationautomationapplications.FeaturesoftheNexus®1500+meter’sIEC61850implementationinclude:

• TheIEC61850ProtocolServerallowsupto6simultaneousMMSclients.

• EitherEthernetportcanbeconfiguredforIEC61850(onlyoneportatatimecanrunIEC61850).

• GOOSEpublisher/subscriberfunctionalityissupported.

• Bufferedandunbufferedreportsaresupportedforthefollowingtriggers:generalmeterinterrogation,forexample,thereportisgeneratedinresponsetoaquery;meterintegrity,forexample,thereportisgeneratedaccordingtoaprogrammedinterval;anddatachange,forexample,thereportisgeneratedduetoachangeinthecontentsofadataset.

• Filetransferissupported.

• EmbeddedWebProtocolServersupportisavailableforIEC61850CIDfileuploading,IEC61850ProtocolServerstatusandfordisplayingincomingandoutgoingGOOSEmessages.

• MultipleLogicalNodes,whichmapflicker,harmonics,digitalinputs/outputs,limitstate,voltage,current,energyandotherdata,aresupported.

• WaveformcapturecanbetriggeredbystatusinputdatainsideGOOSEmessages.Theusercanprogramupto16statusinputsthatwilltriggerawaveformcapturewhentheinformationisreceivedviaaGOOSEmessage.Thestatusinputsincludedigitalinputs,limitstates,andanyotherstatusinputsupportedbythemeter.

V-Switch™ Key Technology

TheNexus®1500+meterisequippedwithV-Switch™keyupgradetechnologythatletsyouupgrademeterfunctionalityevenafterinstallation.Thismeansyoucanpurchasewhatyouneednowandthenupgradewheneveryouneedtheadditionalfeatures.FollowingaretheavailableV-Switch™keys.

Feature V1 V2 V3

BasicMeasurements * * *

Memory 512MB 1GB 4GB

SamplingSpeed 512 1024 Upto800,000

50MHzTransients *

EN61000-4-30ClassAEdition3

* * *

IEC61850Server * *

IEC61850GOOSE * *

Unique GOOSE Cross Trigger:

• Fault-basedcrosstriggerofwaveformbasedonGOOSEmessage.

• Providessystem-widedistributionfaultanalysisonanevent.

• Timingbetterthan200microsecondsistypical.

• Manydifferentcircuitscanbeviewedafteraneventoccured.

IntelligentSubstationIEC61850DesignCrossTriggerFaultReadingsforSimultaneousStation-wideFaultAnalysis

7

The Meter of Choice for Critical Energy Measurement

DesignedforUsebetweenTwoUtilityTiePointsorforCriticalSCADAData

8

Internal I/O

Pulse Outputs:

485P:DualRS485/PulseOutputCard

• 4KYZpulses-SolidState

• Pulsewidth:5ms

• TwoRS485ports

Relay Outputs:

6RO1:6RelayOutputCard

• 5A,250VAC/30VDC

• FormC(Latching)

Digital Input Status:

16DI1:16StatusInputsCard

• Usedforalarmdetectorpulseaccumulation

• Upto150VDCwettedornon-wetted(24VDCinternallyprovided)

Note: TheNexus®1500+meterprovidesoneI/Oslotforthe485P(Slot1),andtwoI/Oslotsforthe6RO1and16DI1(Slots3and4).

External I/O

Analog Outputs:

• 1mAON4/1mAON8:4or8AnalogOutputs,0-1mA,self-powered,scalable,bidirectional

• 20mAON4/20mAON8:4or8AnalogOutputs,4-20mA,self-powered,scalable

• Wiring:CommonMode

• Accuracy:0.1%ofFullScale

• Calibration:Self-calibrating

• Scaling:Programmable

• Ordering:Upto4AnalogOutputmodules

Analog Inputs:

• 8AI1:8AnalogInputs,0±1mA

• 8AI2:8AnalogInputs,4-20mA

• 8AI3:8AnalogInputs,0±5VDC

• 8AI4:8AnalogInputs,0±20VDC

• Wiring:CommonMode

• Accuracy:0.25%ofFullScale

• Scaling:Programmable

• Ordering:Upto4AnalogInputmodules

Digital Dry Contact Relay Outputs:

• 4RO1:4RelayOutputs,5A,250VAC/30VDC,Form-CLatching

• Ordering:1moduleinadditiontointernalmodules

Digital Solid State Pulse Outputs:

• 4PO1:4SolidStatePulseOutputs,FormAorCKYZpulses

• MaximumPulseSpeed:20pulsespersecond

• Ordering:Upto4DigitalSolidStateOutputmodules

I/O Module Accessories (Required):

• PSIO:PowersupplyrequiredwhenusinganexternalI/Omodule.TheNexus®1500+meterdoesnothaveinternalpowerforexternalI/Omodules.

• MBIO:MountingbracketforexternalI/Omodules.MustbeorderedwithexternalI/Omodule.

Expandable Inputs and Outputs to Extend Measurements

ExpandableExternalI/OModules

9

TheNexus®1500+meterfeaturesanLCDcolordisplaywithtouchscreencapability.ThedisplayusesbrightTFTglasswithahightempera-tureandlonglifeLEDbacklight.LEDissuperiortoCCFLsolutionsduetobettertemperatureandhalf-lifespecifications.Screendisplaysinclude:

• Real-timeviewing(voltage,current,power,demand)

• Accumulatedenergyandtimeofusereadings

• Flickerreadings

• Alarms

• PhasorAnalysis

• Harmonicspectrumanalysisandwaveforms

• Realtimetrending

• Logstatus

• Configurationsettings

• Multi-languagesupport

• Digitalstatusinputs

VaVbVcVnVaux

N/U

CTs

CBA

CBA

Vc

Vb

Va

VaVbVcVnVaux

N/U

CTs

Vc

Vn

Va

PTs

NCBA

NCBA

NCBA

NCBA

VaVbVcVnVaux

CTs

N/U

Vn

Vc

Vb

Va

NCBA

NCBA

VaVbVcVnVaux

Vn

Vc

Vb

Va

PTs

CTs

N/U

Earth Ground

Earth Ground

Earth Ground

CTShortingBlock

Earth Ground

CTShortingBlock

Earth Ground

CTShortingBlock

*

Earth Ground

CTShortingBlock

*

Wiring Diagrams

4-WireWye,2.5Element,3CTsand2PTs

VividColorDisplay

4-WireWye,3Elementwith4CTsand3PTs*Note:OptionalCTforCurrentMeasurementOnly

3-Wire,2ElementDeltaDirectwith2CTs

4-WireWye,3Elementwith4CTsandnoPTs*Note:OptionalCTforCurrentMeasurementOnly

Vibrant LCD Touch Screen Display

10

Specifications

Voltage Input Range:

• (5-347)VAC,LinetoNeutral

• (10-600)VAC,LinetoLine

Voltage Input Withstand Capability:

• VoltageInputsisolatedto2500VAC

Current Input Range:

• ProgrammabletoanyCTratio

• Class2:Nominal1A,with2timesoverrange

• Class2:faultcurrentrecordingto±16Apeak

• Class20:Nominal5A,with4timesoverrange

• Class20:faultcurrentrecordingto±80Apeak

Current Input Withstand Capability (at 23°C):

• 100Afor10seconds

• 300Afor3seconds

• 500Afor1second

Burden:

• VoltageInputs:0.072VA/phasemaxat600volts,0.003VA/phasemaxat120volts

• CurrentInputs:0.008VAperphasemaxat20A

Isolation:

• Allinputstooutputsareisolatedto2500VAC

Temperature Rating:

• Operatingtemperature:(-20to+70)°C

• Storagetemperature:(-30to+80)°C

• Humidity:Upto95%RHnon-condensing

Sensing Method:

• Upto1024samplespercycle(programmable)

• 16BitA/Dresolution–multipleconverters

• ConstantCalibration™technology

• TrueRMS

• Transientat50millionsamplespersecond

Accuracy Rating:

• Energymeasurementaccuracyat0.06%

• FullaccuracyspecificationsavailableinNexus®1500+meterUserManual

• Timeclock:3.5ppmfor(-40to+85)°C-lessthan10secondsdriftpermonthoncrystalsync;2.0ppmtypicalfrom(0to+40)°C-lessthan6secondspermonthdrift

Update Time:

• 1Second-Revenueaccuratereadings

• 1Cycle-Fasterupdatedreadings

• Customizablehigh-speedreadings-from2to20cyclesRMS

Control Power Requirements:

• D2Option:(100–240)VAC@50/60Hzor(100-240)VDC

• 115ACOption:(100-240)VAC@50/60Hz

• DOption:(18-60)VDC(24-48VDCSystems)

• Burden:25VAMax

Frequency Range:

• (45-69.9)Hz

Communication:

• Programmableparityandstopbits

• Communicationprotocols:ModbusTCP/IP,ASCII/RTU;DNP3;IEC61850(V2andabove),SNMP

• ANSIopticalport

• USB1.1/2.0VirtualCOMport

• RJ45Ethernetport10/100BaseT

• Optional2ndEthernetport-RJ45orFiberOptic

• 2RS485ports(optional)

Shipping:

• Totalshippingweight:approx.6.5lbs(2.9kgs)

• Shippingcontainerdimensions:16"x15.5"x11.5"(40.64cmx39.37cmx29.21cm)

Compliance:

• ANSIC12.20(0.2Class)andIEC62053-22(0.2SClass)Accuracy

• ANSIC12.1(CodeforElectricityMetering)

• ANSIC62.41(Burst)

• ANSI/IEEEC37.90.1–SurgeWithstand

• FCCPart15,SubpartB,ClassA

• IEC61000-4-2–ESD

• IEC61000-4-3–RadiatedImmunity

• IEC61000-4-4–FastTransient

• IEC61000-4-5–SurgeImmunity

• IEC61000-4-6-ConductedImmunity

• IEC61000-4-7–Harmonics

• IEC61000-4-15–FlickerMeter

• IEC61000-4-30–ClassAEd.3

• IEC62052-11-GeneralRequirements

• IEC/CISPR14-1-ContinuousEMDisturbance

• CEMarked

• ULandcULListed

External I/O Modules

• 1mAON4:4AnalogOutputs,0±1mA

• 1mAON8:8AnalogOutputs,0±1mA

• 20mAON4:4AnalogOutputs,4-20mA

• 20mAON8:8AnalogOutputs,4-20mA

• 8AI1:8AnalogInputs,0±1mA

• 8AI2:8AnalogInputs,4-20mA

• 8AI3:8AnalogInputs,0±5VDC

• 8AI4:8AnalogInputs,0±10VDC

• 4RO1:4RelayOutputs

• 4PO1:4SolidStatePulseOutputs

• PSIO:PowerSupplyforI/Omodules(mustbeorderedwithexternalI/Omodule)

• MBIO:I/Omountingbracket(mustbeorderedwithexternalI/Omodule)

Note:PleaseseeproductUserManualforcomprehensivespecifications.

Wiring Diagrams

Front Side Back

Dimensional Drawings

4.44”[11.28cm

]

7.6”[19.30cm]

5.94” [15.09cm]

4.44” [11.28cm]

5.04”[12.80cm]

5.73”[14.55cm]

1.87”[4.75cm]

10.74”[27.28cm]

6.96” [17.68cm]

6.74” [17.12cm]

11

To order a Nexus® 1500+ meter:

• Fillouttheoptionsyouwantintheorderchartshownbelow:listaccessoriesseparately.

• SpecifyCommunicatorEXT™4.0software.

• EIGcanalsoprovidecurrentandpotentialtransformers.

• Emailorfaxorderinformationandquantitytotheemailaddressorfaxnumberlistedbelow,orcallthephonenumberlistedbelowtoplaceyourorder.

About Electro Industries: ElectroIndustries/GaugeTechisoneoftheoldestandlargestmanufacturersofmicroprocessor-baseddigitalpowermetersintheUnitedStates.EIG'ssuccessisattributabletoourwillingnesstosupportouruserswithon-stafftechnicalexpertise.Contactusandwewillassistyouinsolvingyourcomplexmeteringapplications.

Nexus® 1500+ web page:http://electroind.com/product-info/nexus-1500_plus-next-generation-power-quality-revenue-meter/

1800ShamesDrive,Westbury,NY115901-877-EIMETER(1-877-346-3837)

Tel:516-334-0870Fax:516-338-4741Email:[email protected]

Ordering InformationNexus®

Base MeterControl Power

Frequency Range

Current Class

Virtual Switch

Communication Expansion/Slot 1

I/O Slot 2

I/O Slot 3

I/O Slot 4

Option Numbers:

Example: Nexus 1500+ D2 60 20 V2 485P NTRJ 6RO1 6RO1

Nexus® 1500+ Meter

115AC (100-240)VAC@50/60Hz

60 60Hz

2020A

V1Standard

Nexus®1500+Meter512MBmemory/512s/c

XNoOption

XNoOption

XNoOption

XNoOption

D2Universal

(100-240)VAC@50/60Hzor(100-240)VDC

50 50Hz

22A

V2V1+1GBmemory/

1024s/cIEC61850

485P2RS485and4PulseOutputs

NTRJSecondRJ45NetworkCard

6RO16RelayOutputs

6RO16RelayOutputs

D(18-60)VDC

V3V2+4GBmemory/

50MHzTransientRecording

NTFOSecondFiberNetworkCard(STterminated)

16DI116StatusInputs

16DI116StatusInputs

Accessory OptionsSoftware

COMEXT4P1Y CommunicatorEXT™4.0SoftwareforWindowsSingle-ComputerLicense(OneSite)

I/O Modules

1mAON4 1mAON8 20mAON4 20mAON8 8AI1 8AI2 8AI3 8AI4 4RO1 4PO1

4AnalogOutputs,0±1mA8AnalogOutputs,0±1mA4AnalogOutputs,4-20mA8AnalogOutputs,4-20mA8AnalogInputs,0±1mA8AnalogInputs,4-20mA8AnalogInputs,0±5VDC8AnalogInputs,0±10VDC4RelayOutputs4SolidStatePulseOutputs

*PSIO

*MBIO

PowerSupplyforExternalI/OModulesI/OMountingBracket

*MustbeorderedwithanexternalI/Omodule.

- - -- -- - -

- - -- -- - -

Electro Industries/GaugeTech™The Leader in Power Monitoring and Smart Grid Solutions™

E154718082118V.1.07