-PUBLIC- N-314 REV. C ENGLISH 12 / 2012 PROPERTY OF PETROBRAS 19 pages, 1 form, Index of Revisions and WG Low-Voltage Panel Motor Control Center Specification This Standard replaces and cancels its previous revision. The CONTEC - Authoring Subcommittee provides guidance on the interpretation of this Standard when questions arise regarding its contents. The Department of PETROBRAS that uses this Standard is responsible for adopting and applying the sections, subsections and enumerates thereof. CONTEC Comissão de Normalização Técnica Technical Requirement: A provision established as the most adequate and which shall be used strictly in accordance with this Standard. If a decision is taken not to follow the requirement (“non-conformity” to this Standard) it shall be based on well-founded economic and management reasons, and be approved and registered by the Department of PETROBRAS that uses this Standard. It is characterized by imperative nature. SC - 06 Recommended Practice: A provision that may be adopted under the conditions of this Standard, but which admits (and draws attention to) the possibility of there being a more adequate alternative (not written in this Standard) to the particular application. The alternative adopted shall be approved and registered by the Department of PETROBRAS that uses this Standard. It is characterized by verbs of a nonmandatory nature. It is indicated by the expression: [Recommended Practice]. Copies of the registered “non-conformities” to this Standard that may contribute to the improvement thereof shall be submitted to the CONTEC - Authoring Subcommittee. Electricity Proposed revisions to this Standard shall be submitted to the CONTEC - Authoring Subcommittee, indicating the alphanumeric identification and revision of the Standard, the section, subsection and enumerate to be revised, the proposed text, and technical/economic justification for revision. The proposals are evaluated during the work for alteration of this Standard. “This Standard is exclusive property of Petróleo Brasileiro S. A. - PETROBRAS, internal application and PETROBRAS Subsidiaries and shall be used by its suppliers of goods and services under contracts or similar under the conditions established in Bidding, Contract, Agreement or similar. The use of this Standard by other companies / organizations / government agencies and individuals is the sole responsibility of the users..” Introduction PETROBRAS Technical Standards are prepared by Working Groups - WG (consisting specialized of Technical Collaborators from Company and its Subsidiaries), are commented by Company Units and its Subsidiaries, are approved by the Authoring Subcommittees - SCs (consisting of technicians from the same specialty, representing the various Company Units and its Subsidiaries), and ratified by the Executive Nucleus (consisting of representatives of the Company Units and its Subsidiaries). A PETROBRAS Technical Standard is subject to revision at any time by its Authoring Subcommittee and shall be reviewed every 5 years to be revalidated, revised or cancelled. PETROBRAS Technical Standards are prepared in accordance with PETROBRAS Technical Standard N-1. For complete information about PETROBRAS Technical Standards see PETROBRAS Technical Standards Catalog.

NI-0314

  • Upload
    nutjedi

  • View
    10

  • Download
    0

Embed Size (px)

DESCRIPTION

Petrobras

Citation preview

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    PROPERTY OF PETROBRAS 19 pages, 1 form, Index of Revisions and WG

    Low-Voltage Panel Motor Control Center

    Specification

    This Standard replaces and cancels its previous revision.

    The CONTEC - Authoring Subcommittee provides guidance on the interpretation of this Standard when questions arise regarding its contents. The Department of PETROBRAS that uses this Standard is responsible for adopting and applying the sections, subsections and enumerates thereof.

    CONTEC Comisso de Normalizao

    Tcnica

    Technical Requirement: A provision established as the most adequate and which shall be used strictly in accordance with this Standard. If a decision is taken not to follow the requirement (non-conformity to this Standard) it shall be based on well-founded economic and management reasons, and be approved and registered by the Department of PETROBRAS that uses this Standard. It is characterized by imperative nature.

    SC - 06

    Recommended Practice: A provision that may be adopted under the conditions of this Standard, but which admits (and draws attention to) the possibility of there being a more adequate alternative (not written in this Standard) to the particular application. The alternative adopted shall be approved and registered by the Department of PETROBRAS that uses this Standard. It is characterized by verbs of a nonmandatory nature. It is indicated by the expression: [Recommended Practice]. Copies of the registered non-conformities to this Standard that may contribute to the improvement thereof shall be submitted to the CONTEC - Authoring Subcommittee.

    Electricity Proposed revisions to this Standard shall be submitted to the CONTEC - Authoring Subcommittee, indicating the alphanumeric identification and revision of the Standard, the section, subsection and enumerate to be revised, the proposed text, and technical/economic justification for revision. The proposals are evaluated during the work for alteration of this Standard.

    This Standard is exclusive property of Petrleo Brasileiro S. A. - PETROBRAS, internal application and PETROBRAS Subsidiaries and shall be used by its suppliers of goods and services under contracts or similar under the conditions established in Bidding, Contract, Agreement or similar. The use of this Standard by other companies / organizations / government agencies and individuals is the sole responsibility of the users..

    Introduction

    PETROBRAS Technical Standards are prepared by Working Groups - WG (consisting specialized of Technical Collaborators from Company and its Subsidiaries), are commented by Company Units and its Subsidiaries, are approved by the Authoring Subcommittees - SCs (consisting of technicians from the same specialty, representing the various Company Units and its Subsidiaries), and ratified by the Executive Nucleus (consisting of representatives of the Company Units and its Subsidiaries). A PETROBRAS Technical Standard is subject to revision at any time by its Authoring Subcommittee and shall be reviewed every 5 years to be revalidated, revised or cancelled. PETROBRAS Technical Standards are prepared in accordance with PETROBRAS Technical Standard N-1. For complete information about PETROBRAS Technical Standards see PETROBRAS Technical Standards Catalog.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    2

    Foreword This Standard is the English version (issued in 11/2013) of PETROBRAS N-314 REV. C 12/2012. In case of doubt, the Portuguese version, which is the valid document for all intents and purposes, shall be used. 1 Scope 1.1 This Standard establishes minimum requirements for purchasing a low-voltage panel Motor Control Center (CCM), with rated voltages up to 1 000 V, for feeding service and motor control in PETROBRAS facilities. 1.2 This Standard is not applied to low voltage panel for installation in potentially explosive atmospheres. 1.3 This Standard applies to procedures beginning from its issue date. 1.4 This Standard contains Technical Requirements and Recommended Practices. 2 Normative References The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document applies.

    PETROBRAS N-898 - Smbolos Grficos e Designaes para Diagramas Eltricos (Graphical Symbols and Designations for Electrical Diagrams); PETROBRAS N-1219 - Cores (Colors); ABNT NBR 5410 - Instalaes Eltricas de Baixa Tenso (Low Voltage Electrical Installations); ABNT NBR IEC 60439-1 - Conjuntos de Manobra e Controle de Baixa Tenso Parte 1: Conjuntos com Ensaio de tipo Totalmente Testados (TTA) e Conjuntos com Ensaio de Tipo Parcialmente Testados (PTTA) (Low-Voltage Switchgear and Controlgear Assemblies - Part 1: Type-Tested [TTA] and Partially Type-Tested [PTTA] Assemblies); ABNT NBR IEC 60529 - Graus de Proteo para Invlucros de Equipamentos Eltricos (cdigo IP) (Degrees of Protection Provided by Enclosures (IP Code)); ABNT NBR IEC 60947-2 - Dispositivos de Manobra e Comando de Baixa Tenso - Parte 2: Disjuntores (Low-voltage Switchgear and Controlgear - Part 2: Circuit-Breakers); ABNT NBR IEC 60947-4-1 - Dispositivo de Manobra e Controle de Baixa Tenso Parte 4-1: Contatores e Partidas de Motores - Contatores e Partidas de Motores Eletromecnicos (Low-Voltage Switchgear and Controlgear Part 4-1: Contactors and Motor-Starters - Electromechanical Contactors and Motor-Starters); IEC 60073 - Basic and Safety Principles for Man-Machine Interface, Marking and Identification - Coding Principles for Indicators and Actuators; IEC 60076-6 - Power Transformers - Part 6: Reactors; IEC 60092-201 - Electrical Installations in Ships - Part 201: System Design - General Fourth Edition; IEC 60092-302 - Electrical Installations in Ships - Part 302: Low-Voltage Switchgear and Controlgear Assemblies Fourth Edition; IEC 60417 Database Snapshots - Graphical Symbols for Use on Equipment;

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    3

    IEC 60445 - Basic and Safety Principles for Man-machine Interface, Marking and Identification - Identification of Equipment Terminals, Conductor Terminations and Conductors; IEC 60533 - Electrical and Electronic Installations in Ships - Electromagnetic Compatibility; IEC 60909 - Short-Circuit Current Calculation in Three-Phase A.C. Systems; IEC 61000-5-2 - Electromagnetic Compatibility (EMC) - Part 5: Installation and Mitigation Guidelines - Section 2: Earthing and Cabling; IEC 61086-1 - Coatings for Loaded Printed wire Boards (Conformal Coatings) - Part 1: Definitions, Classification and General Requirements; IEC 61086-2 - Coatings for Loaded Printed wire Boards (Conformal Coatings) - Part 2: Methods of Test; IEC 61892-3 - Mobile and Fixed Offshore Units - Electrical Installations - Part 3: Equipment; IEC TR 61641 - Enclosed Low Voltage Switchgear and Controlgear Assemblies - Guide for Testing Under Conditions of Arcing Due to Internal Fault; ISO 3864-2 - Graphical Symbols Safety Colours and Safety Signs Part 2: Design Principles for Product Safety Labels; ISO 7010 - Graphical Symbols Safety Colours and Safety Signs Safety Signs Used in Workplaces and Public Area; ASTM F855 - Standard Specifications for Temporary Protective Grounds to Be Used on De-Energized Electric Power Lines and Equipment; ASTM F1166 - Standard Practice for Human Engineering Design for Marine Systems, Equipment and Facilities; ASTM G21 - Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi; ASTM E1934 - Standard Guide for Examining Electrical and Mechanical Equipment with Infrared Thermography; IEEE C 57.16 - Standard Requirements, Terminology, and Test Code for Dry-Type Air-Core Series-Connected Reactors.

    NOTE For documents referred in this Standard and for which only the Portuguese version is

    available, the PETROBRAS department that uses this Standard should be consulted for any information required for the specific application.

    3 Terms and Definitions For purposes of this Standard, the terms and definitions indicated in items 3.1 to 3.14 are adopted. 3.1 compartment closed section or subsection, except for some openings required for interconnection, control or ventilation 3.2 future compartment closed section or subsection, except for some openings required for interconnection, control or ventilation, with structural components and electrical connectors prepared for future installation of functional unit. It shall have all extraction and locking devices, and it only does not have the switch, control, measuring, signaling and protecting devices

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    4

    3.3 assembly (low-voltage switchgear and controlgear assembly) combination of one or more low-voltage switch, control, measuring, signaling, protecting or regulation devices and equipment items, fully mounted, being all electrical and mechanical inner interconnections and structural parts responsibility of the manufacturer 3.4 EMC (Electromagnetic Compatibility) Ability of an equipment item or system work properly in its electromagnetic ambient without introducing unbearable electromagnetic disturbances 3.5 IT network connection system in which all live parts are isolated from ground or where a feeding point is grounded through impedance. Installation masses are grounded in the same feeding ground electrode, if any, or in a separated ground electrode 3.6 FPSO Floating Production Storage and Off-Loading Unit 3.7 FSO Floating Storage and Off-Loading Unit 3.8 mounting plate plate designed to support many components, suitable for installation in an assembly 3.9 section construction unit of an assembly between two successive vertical splits 3.10 tropicalization industrial treatment process against degradation of electronic and mechanical components, aimed at ensuring their proper functional performance when subjected to environmental conditions of tropical areas 3.11 functional nit part of an assembly, covering all electrical, mechanical and electronic elements that contribute to performance of the same function 3.12 spare functional unit functional unit with all electromechanical and electronic components installed to perform a specific function

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    5

    3.13 package unit equipment or part of installation supplied with all internals installed and interconnected, so as to allow its perfect operation, depending only on the supplying of external utilities (electric power, compressed air, etc.) 4 General Conditions 4.1 Any item not sufficiently covered by ABNT Standards shall meet international standards IEC and ISO. The impossibility of meeting any item shall be submitted to PETROBRAS approval during the proposal presentation stage. 4.2 The application of IEC 60092-201, IEC 60092-302 and IEC 61892-3 is limited to offshore facilities. For installation in vessels, (FPSO and FSO), the IEC 60092-201 and IEC 60092-302 have priority over the others. 4.3 Specific characteristics of the panel are indicated on the Data Sheet in Annex A, which is an integral part of the Material Requisition (RM), alongside this Standard. 4.4 Blank items of the Data Sheet in Annex A shall be filled in by the supplier, which shall return it to PETROBRAS, duly certified. The supplier is responsible for all information contained in the given Data Sheet. 4.5 When there are divergences between the Data Sheet in Annex A and this Standard, the information contained in the former prevails. 4.6 Any alternative presented by the proponent shall be clearly indicated in the proposal, in a specific item called DEVIATIONS. 5 Construction Characteristics 5.1 The panel and its components shall be designed and fabricated in accordance with recommendations of the standards indicated on Section 2 of this Standard and on the Data Sheet in Annex A. It shall have electrical interlock and wiring interconnection availability between its sections and interlock prediction between remotely installed devices. 5.2 Unless otherwise indicated in Data Sheet in Annex A, the panels shall be Type-Tested (TTA), in accordance with ABNT NBR IEC 60439-1. 5.3 Classification of Assemblies With Relation to ABNT NBR IEC 60439-1 5.3.1 Panels shall be multi-string-type metallic assemblies. 5.3.2 Unless otherwise indicated in Data Sheet in Annex A, panels shall be suitable for sheltered installation. 5.3.3 Unless otherwise indicated in Data Sheet in Annex A, panels shall be of fixed assembly type.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    6

    5.3.4 Protection Degree 5.3.4.1 The protection degree shall follow at least the Table 1, according to ABNT NBR IEC 60529.

    Table 1 - Protection Degree

    Installation Onshore Offshore

    Sheltered in panel room IP21 IP22

    Sheltered in engine room IP31 IP32

    Covered outdoors IP43 IP56SW

    Uncovered outdoors IP54SW IP56SW

    NOTE The suffix W, when used, means equipment suitable to operation in salted, hot, humid atmosphere with presence of hydrocarbons.

    5.3.4.2 The protection degree between compartments adjacent to panel shall be at least IP21B, according to ABNT NBR IEC 60529. 5.3.4.3 The protection degree shall be kept with functional units in test and isolated positions, and during transfer from a position to another. 5.3.5 Panels shall be made of extractable parts, with the following positions:

    a) connected; b) test; c) extracted (isolated); d) removed.

    NOTE Each functional unit shall have a separated extractable part. Extractable parts shall slide on

    rails or guides. 5.3.6 The protection against electrical shock through direct contact with protective barriers, enclosures and busbar insulations shall be ensured. 5.3.7 The protection against electrical shock through indirect contact shall be ensured by protective circuits (ground busbar). 5.3.8 The assembly shall be designed and organized so as it allows inspections and similar operations made by certified personnel when the assembly is on duty and under voltage.. 5.3.9 Unless otherwise indicated in Data Sheet in Annex A, panels shall be separated in accordance with inner separation 4b.. 5.3.10 Electrical connections from functional units to main inlet circuit, main outlet circuit and auxiliary circuits shall be of extractable type (WWW type).

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    7

    5.3.11 Unless otherwise indicated in Data Sheet in Annex A, panels shall be suitable for installation in electromagnetic compatibility environment level 2, according to ABNT NBR IEC 60439-1. 5.4 Structure 5.4.1 The panel shall be made of self-sustaining steel plates, with structural gauge profiles in accordance with the manufacturers standard, with expansion possibility on both ends. 5.4.2 The panel shall consist of standardized and independent vertical sections, where equipment is to be housed. Each vertical section shall be subdivided at least in the following separated compartments:

    a) busbar; b) switchgears; c) outlet cables.

    5.4.3 Each section shall have, on the front part, doors with hinges. The doors shall have electrical continuity with the panel structure through flexible copper wire. Unless otherwise indicated in Data Sheet in Annex A, the rear access shall be done through a door with hinges, fitted with a lock. 5.4.4 All doors with hinges shall have a locking device when in open position. 5.4.5 For panels installed in floating offshore units, the front and rear parts shall be provided with handrails made of insulation material in the entire panel length. 5.4.6 The panel shall have holes for placement of devices to fix the panel to a base, as well as pad eyes for lifting and handling. The devices shall be supplied by the panel manufacturer. 5.4.7 Panels shall be designed to resist thermal efforts due to bearable short-duration rated current (Icw) for 1 s. Panels shall be designed to resist mechanical efforts due to bearable peak rated current (Ipk). The values of such currents shall be informed in the Data Sheet in Annex A. 5.4.8 The panel shall be fitted with a document holder on its outside in order to file and keep technical documents relevant to panel. 5.4.9 The bearable impulse rated voltage of equipment (1.2/50 s) at 2 000 m shall be at least dimensioned using overvoltage class IV and rated operating voltage for ground of 1 000 Vca RMS, according to ABNT NBR IEC 60439-1. 5.4.10 The minimum distance of air insulation is 14 mm, considering non-homogeneous field, pollution level 3, according to ABNT NBR IEC 60439-1, and bearable rated impulse voltage of equipment as per 5.4.9. 5.4.11 The minimum flow distance is 16 mm, considering pollution level 3, material group III A, according to ABNT NBR IEC 60439-1, and rated insulation voltage of equipment of 1 000 V.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    8

    5.4.12 When required in Data Sheet in Annex A, the panel shall be certified to provide protection to personnel under internal arc conditions, in accordance with IEC TR 61641, complying at least with criteria 1 to 5 of test assessment. The allowable current under arc condition (Ip arc) for test shall be the bearable short-duration rated current (Icw) or more, and the allowable arc duration (tarc) shall be at least 0,3 s. 5.5 Corrosion Supportability 5.5.1 The panel shall be resistant to corrosion caused by moisture and characteristic atmosphere of installation site, as indicated on the Data Sheet in Annex A. If previously approved by PETROBRAS, the use of the manufacturers treatment system and standard painting is allowed. 5.5.2 The final finish color shall comply with the indicated in Data Sheet in Annex A. 5.5.3 The final color of inner faces of doors and mounting plates shall comply with code 1867 of PETROBRAS N-1219 (Munsell 2.5 YR 6/14). 5.5.4 For offshore installations or those subjected to aggressive environment, all material used in hinges, locks, bolts, locking devices, structural fixing elements and nameplates shall have anticorrosive protection, such as double-chrome coating or use of stainless steel AISI 300 series. 5.5.5 Circuits printed in electronic modules of functional units shall be treated for protection against aggressive and salted environments (tropicalization) and corrosive gases (for example, gases containing sulfur or chlorine), consisting of, at least, application of Class 2 reinforced protective, in accordance with IEC 61086-1 and 61086-2, and fungiproof, in accordance to ASTM G21. The manufacturer shall inform in its proposal the processes used for this protection, subjected to PETROBRAS approval. 5.6 Interlocks 5.6.1 If the extraction of drawer with closed doors is required in Data Sheet in Annex A, the extraction up to test position and insertion shall only be performed through a lever, with closed door and the circuit-breaker in the off position. NOTE If an arc monitoring device is required in Data Sheet in Annex A, only criteria 1 and 2 of IEC

    TR 61641 shall be met, and the others shall be skipped. In this case, the arch energy shall not be above 8 cal/cm2.

    5.6.2 All drawers shall allow the use of a padlock, locking them in the off position. In the on position, it shall be impossible to open the compartment door. 5.6.3 There shall be signaling in the front part of the connected, test and extracted positions of functional unit cabinet, through a mechanical device. 5.6.4 Main busbar terminals shall be automatically covered by a packer made of insulating material when the switchgear is extracted, preventing the access to parties with voltage.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    9

    5.7 Erection 5.7.1 All main components of functional units intended for feeding similar equipment (same type and power), such as: busbars, circuit-breakers, contactors, protective relays, etc. shall have the same specification. 5.7.2 The CCM inlet string shall have a service input socket 2 P+T of 127 Vca or 220 Vca, feed by the same external source of heating resistors of panels. This socket is intended for connection of a notebook or handheld device, used to set up the IEDs. 5.7.3 If required in Data Sheet in Annex A, the panels shall be designed so as to allow inspection by infrared thermography with energized panels. It may be provided the use of special displays that allow the thermographic inspection without the previous shutdown of system or the built-in and continuous thermal monitoring with optical-electronic sensing technology. 5.7.4 Panels shall allow access to their busbars and insertion clamps by the rear end, with possibility of access for maintenance in front and rear faces. 5.7.5 When installed in floating platforms and vessels (FPSO and FSO), the panels shall be suitable for operation subjected to variations of slope (static and dynamic), vibrations and accelerations specified by the Classification Society. 5.7.6 When installed in floating platforms and vessels (FPSO and FSO), panels shall be designed to meet the minimum requirements of emission, immunity and performance criteria regarding EMC, established by IEC 60533. 5.7.7 The use category of functional units for feeding of transformers shall be AC-6a, as per ABNT NBR IEC 60947-4-1. 5.7.8 Unless otherwise indicated in Data Sheet in Annex A, the use category of motor-starters shall be AC-3 as per ABNT NBR IEC 60947-4-1. 5.7.9 In test position, the force contacts of functional units shall meet the minimum flow distance and insulation requirements, in accordance with ABNT NBR IEC 60439-1. 5.7.10 For functional units with frequency converters and soft starters, temperature rise tests of these cabinets shall be performed considering the temperature at rated load with closed door. 5.8 Grounding 5.8.1 All metallic parts making up the panel, not provided for current conduction, shall be connected to its ground busbar, using electrical connecting jumpers with cross section, as per Table 3A of ABNT NBR IEC 60439-1. This busbar shall stay in the panel lower inner part, running all over its length and supplied with suitable connectors, not welded type, for naked copper cables, strung 70 mm2 gage for onshore installations and 95 mm2 for offshore installations, on each one of its ends. 5.8.2 When intelligent electronic instruments and devices are provided, each compartment shall have a terminal block ruler or an electronic reference bar, isolated from the structure.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    10

    5.8.3 Grounding and equipotentialization of electronic reference terminals of intelligent electronic instruments and devices shall meet the requirements of IEC 61000-5-2. 5.8.4 Temporary protective grounding facilities shall be provided through a standardized device, as per ASTM F 855. 5.8.5 The manufacturer shall supply, with the panel, 1 temporary protective grounding kit containing at least 1 grounding rod clamp, 3 bar clamps and 1 cable, dimensioned as per ASTM F 855. 5.9 Safety and Product Identification and Graphic Signaling 5.9.1 The panel shall be fitted with a series AISI 300 stainless steel nameplate containing the data provided in ABNT NBR IEC 60439-1. 5.9.2 The panel shall be fitted with a supplementary series AISI 300 stainless steel nameplate containing at least the following data:

    a) Petrleo Brasileiro S.A. - PETROBRAS; b) PETROBRAS department name; c) Project name; d) Panel number (TAG); e) RM number; f) Purchase Order number; h) as an alternative to f) the contract number, in cases of purchase built in global price contract

    (Turn Key, Lump Sum, etc.). 5.9.3 The panel shall be fitted with a supplementary series AISI 300 stainless steel identification plate according to the figure below:

    Figure 1 - Additional Nameplate 5.9.4 Each compartment shall have a black plastic nameplate and engraving in white letters on its outer front face. Equipment number shall be placed in the first line; in the second line (and third if necessary) equipment function shall be placed. These data are indicated in the single line diagram. In spare and empty compartments (future installation) plates shall be supplied without engraving. Each compartment shall have the identification of its functional unit in the rear part and fixed and moving front parts.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    11

    5.9.5 The front and rear faces shall have nameplate of sections. 5.9.6 All components of compartments or functional units shall be identified with nameplates fixed on the mounting plate and on the component. 5.9.7 All equipment items and devices shall be internally identified by tags or nameplates with the same name used in the functional diagram. 5.9.8 In addition to the main and supplementary nameplates, the electric panel shall have their compartments signaled with text and graphic plates with instructions, cautions, warnings and hazard alerts, according to requirements for nameplates of standard ASTM F 1166 and for symbols of IEC 60417 Database Snapshots, ISO 7010 and ISO 3864-2. 5.9.9 The text on every plate and nameplate on panel shall be engraved in Portuguese. 6 Description of Component Parts Equipment listed in the next items, when required in the Data Sheet in Annex A and unless indicated otherwise, shall be supplied in accordance with the specifications described in 6.1 to 6.8. 6.1 Circuit Breakers in Molded Casing 6.1.1 Circuit-breakers shall be fabricated and tested as per ABNT NBR IEC 60947-2 and comply with the characteristics specified in Data Sheet in Annex A. 6.1.2 Circuit Breakers shall be three-pole, manual command by lever, molded casing type. 6.1.3 For non-motoric loads, each breaker shall have a direct action thermomagnetic trigger in each phase. 6.1.4 Breaker command shall be made through a lever, outside and with no need for opening the compartment door. It may only be opened with breaker off, and it is not possible to close the breaker when the compartment door is open. 6.1.5 There shall be an indication on the command lever of the on and off position, and there shall be the possibility of placing a padlock for this position. 6.1.6 Breakers shall be provided with devices neutralizing ambient temperature effects on its triggers. 6.1.7 Opening mechanism shall be free-opening type. 6.1.8 Circuit-breakers from functional units for feeding engines or other loads that do not require selectivity shall have use category A, as per ABNT NBR IEC 60947-2. 6.1.9 Breakers shall be fabricated with provided maintenance, in accordance with ABNT NBR IEC 60947-2.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    12

    6.1.10 Breakers shall be specified for continuous rated load regime, in accordance with NBR IEC 60947-2. 6.2 Contactors 6.2.1 When the use of contactors is specified, the coordination with short-circuit protection devices shall be type 2, as defined in IEC 60947-4-1. The manufacturer shall attach to the technical proposal a certificate of test for each model of functional unit, issued by a recognized laboratory, proving the type of coordination. 6.2.2 Contactor coils shall withstand a 30% rated voltage drop without disconnection of the contacts occurring 6.2.3 The feeding voltage of contactor coils, when used, shall be obtained from auxiliary individual transformers, as per functional diagrams. 6.3 Transformers for Instruments and Auxiliary Transformers 6.3.1 Potential and auxiliary transformers shall be dry and extractable. 6.3.2 Potential and auxiliary transformers shall be protected by fuses or circuit-breaker, with proper breaking capacity on the primary side, and by breakers on the secondary side. Fuses shall be integrated in the extractable assembly, so as the fuses may be removed with no voltage in their terminals. 6.3.3 Current transformers shall be dry. The manufacturer shall provide ways to allow the placement of current transformer secondary in short-circuit when it is required to remove its load. 6.4 Instruments, Protective Relays, Devices and Signaling 6.4.1 Unless otherwise indicated in the Data Sheet in Annex A, functional units of panel shall be provided with intelligent and integrated electronic devices and instruments, interconnected with data communication network. 6.4.2 Each intelligent electronic device shall have a fixed address code to communicate with the safety system and external control. Intelligent electronic devices of the CCM in this specification shall be interlocked so as to prevent the local or remote operation of a functional unit inserted in a place different than the one assigned to this functional unit. 6.4.3 Protective relays of functional units shall meet the protection standards defined in Data Sheet in Annex A and in single line diagrams attached to this Data Sheet. 6.4.4 Software for configuration of digital relays, multi-meters, transducers, transducers, programmable controllers, etc. shall be part of the scope of supply, and shall be supplied with no additional burden, in its most complete version. Software shall be compatible with Microsoft Windows operational system. 6.4.5 If indicated in the Data Sheet in Annex A, the panel shall be fitted with an electric arc monitoring device with activating scheme, so as to de-energize the panel instantaneously.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    13

    6.4.6 When analog instruments and/or transducers are required in the Data Sheet in Annex A, the scale of such instruments and/or transducers shall be selected so as that, in full load, the measured value of parameters is between 50 % and 75 % of the scale. Ammeters for motors shall have shall have a dampening scale. 6.4.7 Displays of multi-meter instruments, protective relays and signaling devices installed in panel compartments shall have brightness according to the recommendation for display brightness of ASTM F 1166, and contrast sufficient to ensure the required information is noted by the operator under all expected conditions of ambient lighting. 6.4.8 Each compartment shall be signaled by LED lamps: red color for indicating equipment on, green color for equipment off, and white color for voltage available in the opening circuit of breakers. The use of other colors in signaling LED lamps shall comply with the general principles of color choice of the IEC 60073. The signaling lamps shall be in the command circuit of their respective breakers. Compartments shall also have switches and auxiliary relays for remote monitoring and supervisory control. 6.4.9 If specified in the Data Sheet in Annex A, the CCM drawer shall be provided with contactor with device able to support transitional voltage drops (Ride Through) for a minimum time of 400 ms. 6.5 Command Switches and Command Buttons 6.5.1 Command switches shall be suited to operation provided in the functional schemes, attached to the Data Sheet in Annex A. 6.5.2 Unless otherwise indicated in the Data Sheet in Annex A, the UPM with contactors shall have only one command button with a non-return off button working on the contactor. Command buttons shall be connected to command circuits of contactors without interposition relays. 6.6 Cables 6.6.1 Conductors shall be of strung copper, operation temperature of 70 C or more, and minimum 1.5-mm2 gage. The minimum gage for secondary circuits of current transformers shall be 2,5 mm2. For all circuits, except for power-type, adequate not-welded type conductors shall be provided. Control cables of each section shall be grouped in terminal block rulers and duly identified. Each terminal block ruler shall have spare terminals for future application (20 % of existing terminals). Terminals shall be of pin type for auxiliary feeding, command, control and signaling circuits, and pad eye type with modular terminals and test cavities for current circuits. The connection shall be made so as not to damage strung conductors. 6.6.2 Electrical cables circuits of each panel compartment, except for power-type ones, shall have separated internal routing and terminal block rulers, as per installation requirements of IEC 61000-5-2. In addition, cables shall have routing and terminal block rulers separated in the following groups:

    a) feeding and control signals; b) analog signals from 4 mA to 20 mA, RTD and mV signals, data transmission signals; c) signals from instrument transformers.

    6.6.3 Control cables in 24 Vcc, analog signal cables from 4 mA to 20 mA, RTD signal cables, mV signal cables, and data transmission cables shall be shielded and meet the criteria of protection against external disturbances, in accordance with IEC 61000-5-2.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    14

    6.6.4 Electrical cables shall run through channels with removable cover to facilitate the access; however, the inner part of channels shall not have any burrs, obstacles or even fixing devices which may damage the insulation integrity. 6.6.5 The panel feeding and outlet to loads shall be performed as defined in the Data Sheet in Annex A, 6.6.6 Cable inlets and outlets shall have fixing devices made of non-magnetic material, so as to avoid circulation of induced currents. 6.6.7 A fixing and supporting device shall be provided for outlet and inlet cables, so as to avoid efforts on insulators, terminals and busbars. 6.7 Heating Resistors 6.7.1 The panel shall be provided with heating resistors, one for each vertical section or compartment, with the voltage defined in the Data Sheet in Annex A, and an external power supply. These resistors shall be automatically controlled by thermostats with a maximum grading range at 60C. There shall be a breaker in the circuit of each resistor in molded casing with thermomagnetic elements intended to break the circuit. The panel shall be provided with an outside outlet for energizing heating circuits during the storage period. 6.7.2 For each panel, at least 2 heating circuits shall be installed, being one for heating of the panel itself, and other for the motors it feeds. 6.7.3 The external auxiliary voltage of 127 Vca or 220 Vca shall supply the heating resistors of motors. Resistors shall be controlled by a contact normally closed of the breaker (or contactor, if any) in case of direct activation of motor, or by an auxiliary contact of the frequency converter, when used, signaling an interrupted motor. There shall be a breaker in the circuit of each resistor in molded casing with thermomagnetic elements intended to break the circuit. For motors installed in area classified as zone 1, heating resistors shall be protected by breakers with integrated thermomagnetic protection with differential of residual current. 6.8 Busbars 6.8.1 The C.C.M. shall have a main busbar, horizontal, with rated current conduction capacity (In) of panel, as specified in the Data Sheet in Annex A, 6.8.2 All busbars shall be three-phase, of electrolytic copper, sized so as to withstand thermal efforts resulting from equivalent thermal short-circuit current (Ith according to IEC 60909) and dynamic efforts resulting from peak short-circuit current (ip according to IEC 60909), in accordance with values indicated in the Data Sheet in Annex A. All compartments shall have complete busbars, including the future compartments. 6.8.3 Each phase of the busbar shall have a permanent identification, using the colors as shown below:

    a) phases (R-S-T): red, white and black, respectively; b) neutral: blue, as per IEC 60445; c) grounding: green and yellow stripes, as per IEC 60445; d) red positive pole and black negative pole for continuous current busbars.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    15

    6.8.4 For IT system grounding (as per ABNT NBR 5410), the minimum cross section of ground busbar shall be 75 mm. Each end shall have non-welded connectors suitable for naked copper cables. 6.8.5 For grounding systems different from IT, the cross section of ground busbar shall meet the requirements of ABNT NBR IEC 60439-1 regarding the section of protective conductors. 6.8.6 When installed in vessels (FPSO and FSO) or other facilities with IT grounding network (as per ABNT NBR 5410), panels shall be design without neutral busbar. 6.8.7 Panels shall have all busbars and connection points of busbars insulated, except for the ground busbar. 6.8.8 The insulation shall completely involve each bar, except on linking points with adjacent units, on connection points with disconnecting devices, or on derivation bars of extractable drawers for TP or Auxiliary Transformer. All bar junctions shall be coated with silver, with minimum thickness of 0,008 mm, so as they ensure a perfect line-up and high-pressure contact. 6.8.9 Temperature rise limits of busbar connections and of other construction materials of panels shall be selected to comply with the temperature rise limits defined in ABNT NBR IEC 60439-1. 6.8.10 Non-hygroscopic, non-flammable materials resistant to polluting agents and to flame propagation shall be used for insulation and supporting of busbars. Celeron materials shall not be accepted. 6.8.11 All busbar connections shall use conical washers (Belleville type) to extend the life cycle of connections undergoing dynamic mechanical efforts due to relative movements and accelerations of the panel. 7 Short-Circuit Current Limiting Reactors 7.1 When required in the Data Sheet, the panel shall be provided with a short-circuit current limiting reactor in series with its inlet circuit, calculated to limit the equivalent thermal short-circuit current (Ith) to 1 s at 18 kA. 7.2 The reactor shall meet the requirements of IEC 60076-6 and IEEE C 57.16. 7.3 The reactor impedance shall be defined iteratively considering short-circuit and power flux studies. 7.4 The reactor shall be installed in the inlet string of panel. The string height shall be the same as the other panel strings, and this string may be deeper than the others. 7.5 The reactor shall be supplied with a moving base so as to allow its removal from enclosure. 7.6 The reactor suitable for sheltered installation shall be dry-type, with air core in magnetic circuit, and cooled through natural convection.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    16

    7.7 The reactor shall present the following electrical characteristics:

    a) copper or aluminum conductor material; b) insulation class F; c) temperature rise limit corresponding to class B; d) quality factor (X/R) between 15 and 20.

    7.8 The reactor shall be designed considering the following tolerance limits:

    a) system voltage variation: 10 %; b) total impedance: - 0 % / + 20 %; c) impedance per phase: 5 % regarding the average value; d) losses: +10 % considering reactor inside the enclosure.

    8 Inspection and Trials The panel and its components shall be inspected and tested in compliance with the listed standards and in the Data Sheet in Annex A. 9 Package and Transport 9.1 The panel shall be stored in a suitable way for the provided transport system. Packages shall completely protect all parts of its content against possible damage during transport, storage, loading and offloading. 9.2 Each volume shall present the following identifications:

    a) identification of storage position; b) identification of PETROBRAS department, with delivery address; c) identification of operating unit; d) identification of the project; e) RM number; f) panel number(s) (TAG); g) name and full address of supplier; h) weight; i) Purchase Order number; j) as an alternative to i) the contract number, in cases of purchase built in global price

    contract (Turn Key, Lump Sum, etc.). 9.3 Compartments with electronic instruments and devices shall contain in their interior, for transport and storage, hygroscopic material kits. 10 Technical Documentation 10.1 The graphic symbology and number code of functions of switchgears, controlgears, and protection devices used in documentation to be submitted by the manufacturer shall follow PETROBRAS N-898. 10.2 Required documents, drawings, manuals shall be prepared in non-recordable and non-erasable digital format and also in printed format. As-purchased and as-built documents submitted in digital format shall be editable.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    17

    10.3 All documents shall be prepared in a legible way, containing at least the following information:

    a) identification of PETROBRAS department; b) identification of operating unit; c) identification of the project; d) RM number; e) panel number(s); f) Purchase Order Number h) as an alternative to f) the contract number, in cases of purchase built in global price

    contract (Turn Key, Lump Sum, etc.). NOTE Drawings, schemes, and diagrams shall be prepared at least in A3 size. 10.4 Minimum documentation to be sent along the proposal for technical analysis:

    a) dimensional drawings of panel font, side views and cross section with approximate sizes, showing the location of overpressure relief devices, if any;

    b) approximate panel weight; c) catalogs of all panel components containing all information and technical characteristics; d) list of spare parts, required for a two-year operation period, with description by unit price; e) price quotation of technical assistance for erection of panel(s); f) price quotation of study of coordination and selectivity of electric protections; g) certificate of test of contactor coordination with breaker, as per IEC 60947-4-1; h) Data Sheet in Annex A signed with the identification of responsible person and all fields

    filled in; i) test and inspection plan, indicating the applicable standards and acceptance values; j) copies of certificates of type tests marked on the Data Sheet, including at least the

    following: check of temperature rise limits by testing; check of dielectric properties by testing; check of bearable short-circuit current by testing; check of effective connection between conducting parts of assembly and protection

    circuit by inspection or resistance measurement; check of bearable short-circuit current of protection circuit by testing; check of insulation and flow distances; check of mechanical operation; check of protection degree; short-duration short-circuit rated current of reactor when installed.

    NOTE Only certificates of tests performed in panels identical to those proposed will be accepted, in

    other words, with the same currents, voltages, number of bars, internal components and sizes. k) for offshore units, in addition to the tests listed in j), at least the copies of the following

    certificates of type tests shall be given: EMC - conducted emission test; EMC - radiated emission test; EMC - low frequency conducted interference; EMC - power supply variation; EMC - voltage surge test; EMC - fast electric transient test; EMC electromagnetic field test; EMC - electrostatic discharge test; EMC radio-frequency conducted interference test;

    l) statement warranting the availability of spare parts given by the supplier, in accordance with 10.4 d);

    m) dimensional drawings of connection compartment of inlet cabinet, with approximate sizes, showing the location of overpressure relief devices, if any.

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    18

    10.5 Minimum documentation to be sent for approval:

    a) list of documents; b) dimensional drawings of views and sections; c) site, sizes and type of devices lifting and fastening the panel to the floor; d) free area for cable inlet and outlet; e) weight and dimensions of each panel sub-assembly to comply with the transport and

    erection logistics; f) total weight and gravity center; g) estimate, informing the thermal dissipation of each string. h) dimensional drawing of bar pipeline inlets, if applicable; i) single-line schemes of panel(s); j) three-line schemes of panel(s); k) functions of each functional unit; l) logical diagrams of each functional unit, when intelligent electronic device is used; m) wiring diagrams (interconnection) indicating all terminal rulers, including those required for

    interconnection with other equipment outside manufacturers supply, clearly showing identified terminals;

    n) full coordination study, if applicable, considering the loads fed by the panel. This study involves the presentation of a technical report with adopted protective philosophy, current curves x log x log time scale, table with adjustment values of many devices used in protection, and technical catalogs of such devices;

    o) list of all applied components and materials, grouped by functional unit; p) packing instructions; q) transport instructions; r) dimensional drawings of connection compartment to bar pipeline, including the connecting

    flange, if any, with approximate sizes, showing the location of overpressure relief devices, if any.

    s) list of name and signal plates; NOTE The panel manufacturer shall supply the current x time characteristic curves of all protective

    devices, even if the manufacturer is not responsible for the coordination study 10.6 Documents to be Sent Along the Panel Erection, operation, training and maintenance manual(s) of panel(s) and auxiliary devices, containing at least the following information:

    a) technical specifications for panel, as well as for all requested components and accessories, of compliance with approved original proposal requirements, including revisions that were made at the time of technical clarifications and/or technical opinion;

    b) Duly completed Data Sheet in Annex A as-purchased and/or as-built"; c) panel storage, lifting and unpacking procedures, as well as of any spare components; d) erection procedures; e) operation procedures, including insertion and extraction of functional units; f) panel preventive and corrective maintenance procedures, as well as for all requested

    accessories; g) thermographic inspection guide, according to ASTM E 1934; h) location and diagnosis guide for typical defects of each functional unit of panel; i) guide with procedures for future expansion under voltage, when a panel with these

    characteristics is requested; j) technical catalogs with all characteristic data of requested accessories as built; k) reports of all routine tests to which the panel has been subjected after fabrication; l) copy of certificates of type tests, in accordance with 9.4; m) copy of certificate of electrical parameter gauge calibration, issued by body certified by

    Inmetro; n) copy of certificate of internal arc test, in accordance with requirements of IEC TR 61641, for a

    minimum short-circuit current value equal to the value indicated in the Data Sheet in Annex A, with minimum test time of 0,3 s;

  • -PUBLIC-

    N-314 REV. C ENGLISH 12 / 2012

    19

    o) tables with configuration parameters of all parameterized components (relays, programmable controllers, frequency converters, soft-starters, multi-meters, etc.), when the commissioning is included in the scope of supply of panel;

    p) list with programming of programmable controllers and MMI (Man-Machine Interfaces). 11 Warranty and After-Sales Technical Assistance 11.1 The manufacturer shall formally ensure the availability of spare parts for any panel component, for a minimum time of 10 years after the delivery date. 11.2 The manufacturer shall inform the list of its certified technical assistances in Brazil and in South America.

  • Data Sheet No. CLIENT: SHEET: 1 of 17 DESIGN: AREA:

    TITLE:

    Low-Voltage Panel Motor Control Center

    Revision Index

    Rev. Description and/or Revised Sheets

    REV. 0 REV. A REV. B REV. C REV. D REV. E REV. F REV. G REV. H DATE DESIGN EXECUTION VERIFICATION APPROVAL THE INFORMATION CONTAINED IN THIS DOCUMENT IS PETROBRAS PROPERTY AND MAY NOT BE USED FOR PURPOSES OTHER THAN THOSE SPECIFICALLY INDICATED HEREIN.

    THIS FORM IS PART OF PETROBRAS STANDARD N-381 REV. K.

  • Data Sheet No. REV. SHEET: 2 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    1 PETROBRAS IDENTIFICATION PN-

    2 ENVIRONMENTAL CHARACTERISTICS

    INSTALLATION SHELTERED IN PANEL ROOM

    MAXIMUM AMBIENT TEMPERATURE C ALTITUDE < 1000m

    NEAR THE SEA YES

    RELATIVE AIR HUMIDITY % POLLUTION DEGREE 3

    EMC ENVIRONMENT CATEGORY 2

    SPECIAL CONDITIONS

    3 MANUFACTURER

    4 TYPE

    SERIAL No.

    5 YEAR OF MANUFACTURE

    6 CHARACTERISTICS OF POWER SUPPLY SYSTEM

    RATED VOLTAGE 480V

    RATED FREQUENCY 60Hz

    NUMBER OF PHASES 3

    SHORT-CIRCUIT CURRENTS (NOTE 1) IEC ANSI/IEEE

    STARTING EFFEC. SYMMETRIC VALUE (NOTE 2) (kA)

    INSTANTANEOUS PEAK VALUE (NOTE 3) (kA)

    EQUILVALENT THERMAL VALUE IN 1s (NOTE 4) (kA)

    X/R RATIO

    SYSTEM GROUNDING

    7 ELECTRIC CHARACTERISTICS OF PANEL

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui kV

    RATED WITHSTAND VOLTAGE OF IMPULSE UImp kV

    RATED VOLTAGE OF AUXILIARY CIRCUIT Ua V

    PRIMARY BUSBAR RATED CURRENT In A

    CIRCUIT PRIMARY GROUND

    SHORT-DURATION RATED WITHSTAND CURRENT Icw / DURATION tk

    kA/1s kA/1s

    PEAK RATED WITHSTAND CURRENT Ipk kA kA

    8 DESIGN AND CONSTRUCTIVE CHARACTERISTICS

    CLASSIFICATION REGARDING TYPE TESTS TTA

    CLASSIFICATION REGARDING MOBILITY FIXED ASSEMBLY

    CLASSIFICATION REGARDING EXTRACTION OF UNITS

    INLET SECTIONS NOT APPLICABLE

    INTERCONNECTION SECTION NOT APPLICABLE

    OUTLET SECTIONS EXTRACTABLE

    CLOSED PORT EXTRACTION

    ENCLOSURE PROTECTION RATE IP-21

    PROTECTION RATE BETWEEN ADJACENT COMPARTMENTS IP-21 B

    FORM OF INTERNAL SEPARATION 4b

    PAINTING STANDARD

    FINAL FINISH COLOR Light gray - Munsel N 6.5

    NUMBER OF INLET SECTIONS 0

    NUMBER OF INTERCONNECTION SECTIONS 0

    POWER CABLE OUTLET BOTTOM

    CONTROL CABLE OUTLET BOTTOM

    THERMOGRAPHIC INSPECTION

    STRUCTURAL PROFILE THICKNESS mm

    WEIGHT kg

    DIMENSIONS

    (WIDTH X DEPTH X HEIGHT) m

    HANDRAIL IN FRONT AND REAR PORTS NO

    REAR ACCESS HINGED DOOR

    PRIMARY BUSBARS

    AMOUNT 1

    MATERIAL ELECTROLYTIC COPPER

    INSULATION HEAT SHRINKABLE

    NUMBER OF BARS PER PHASE

    CROSS SECTION DIMENSION mm x mm

    SECONDARY BUSBARS

    AMOUNT 1

    MATERIAL ELECTROLYTIC COPPER

    RATED CURRENT A

    INSULATION HEAT SHRINKABLE

    NUMBER OF BARS PER PHASE 1

    CROSS SECTION DIMENSION mm x mm

    EARTH BUSBAR

    AMOUNT 1

    MATERIAL ELECTROLYTIC COPPER

    RATED CURRENT A

    NUMBER OF BARS 1

    CROSS SECTION DIMENSION mm x mm

    INTEGRATION WITH AUTOMATION AND CONTROL

    INSTRUMENTS

    IED

    PROGRAMMABLE CONTROLLER

    MAN-MACHINE INTERFACE

    NETWORK SWITCHES

    COMMUNICATION PROTOCOL

    INTERNAL ARC TEST, AS PER IEC TR 61641 NO

    TEST ARC CURRENT Iparc kA

    ARC TEST DURATION tarc 0.3s

    ARC MONITORING DEVICE NO

    MODEL / MANUFACTURER

    ISOLATION SUPERVISOR DEVICE (DSI) NO

    AMOUNT

    MODEL / MANUFACTURER

    GROUND FAULT LOCATOR FOR INSULATED SYSTEM NO

    AMOUNT

    MODEL / MANUFACTURER

    VISUAL SIGNALLING WITH LEDs NO

    AUXILIARY CONTACTS NA FG

    VOLATILE CORROSION INHIBITOR (VCI) NO

    MODEL / MANUFACTURER

    POWER LOST AT FULL LOAD W

    POWER LOST AT HALF LOAD W

    DEHUMIDIFICATION SET PER COLUMN YES

    RESISTOR POWER W

    RATED VOLTAGE VAC EXTERNAL

    THERMOSTAT MODEL

    ADJUSTMENT RANGE C TO C

  • Data Sheet No. REV. SHEET: 3 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    9 INLET SECTIONS

    GENERAL SPECIFICATIONS

    9.1 INLET SECTION

    9.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No.

    LOGICAL No.

    9.3 CIRCUIT BREAKER NO

    TYPE

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY f r 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu kA

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT DELAY RELATING TO Icw s

    CATEGORY OF USE B

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM COIL

    SPRING PRE-LOADED BY ELECTRIC MOTOR YES

    MANUAL DEVICE YES

    ANTI-PUMPING DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    CONTACT CLOSING TIME ms

    OPENING MECHANISM COIL

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    OPENING TIME FOR I > Icw ms

    TEMPERATURE RISE IN CONNECTIONS K

    NO. OF OPERATING CYCLES WITH CURRENT

    AUXILIARY CONTACTS NA NF

    9.4 SHORT-CIRCUIT LIMITER REACTOR YES

    TYPE DRY WITH AIR CORE

    MANUFACTURER

    MODEL OR CATALOG No.

    USE INSIDE PANEL

    ELECTRICAL CHARACTERISTICS

    NUMBER OF PHASES 3

    RATED VOLTAGE UN V

    MAXIMUM OPERATION VOLTAGE Umax V

    RATED FREQUENCY 60Hz

    RATED VOLTAGE OF INSULATION Ui V

    WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    RATED POWER QN VAR

    RATED CURRENT AT CONTINUOUS RATE IN A

    SHORT-DURATION RATED WITHSTAND CURRENT IKN A

    SHORT-DURATION RATED TIME tKN 2s

    PEAK RATED WITHSTAND CURRENT Ipeak kA

    RATED IMPEDANCE AT 40C ZKN (NOTE 5) /PHASE RATED REACTANCE XN (NOTE 5) /PHASE ZERO SEQUENCE REACTANCE X0 /PHASE INDUTANCE mH

    QUALITY FACTOR X/R

    LOSSES AT FULL CHARGE W - C

    CONSTRUCTIVE CHARACTERISTICS

    CONDUCTOR MATERIAL

    INSULATION CLASS F

    MAXIMUM ALLOWABLE TEMPERATURE 130C

    MAXIMUM TEMPERATURE RISE C

    COOLING SYSTEM AIR

    WEIGHT kg

    9.5 CURRENT TRANSFORMERS FOR INSTRUMENTS

    9.5.1 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) M

    MAXIMUM VOLTAGE kV

    9.5.2 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) M

    MAXIMUM VOLTAGE kV

    9.6 POWER TRANSFORMERS FOR INSTRUMENTS

    9.6.1 TYPE: DRY AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION CLASS AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    PURPOSE (NOTE 6) M AT

    MAXIMUM VOLTAGE kV

  • Data Sheet No. REV. SHEET: 4 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    9.6.2 TYPE: DRY AMOUNT MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION CLASS AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    PURPOSE (NOTE 6) M AT

    MAXIMUM VOLTAGE kV

    9.6.3 PRIMARY PROTECTION: C. BREAKER AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    RATED INTERRUPTION CAPACITY kA

    9.6.4 CIRCUIT BREAKER IN SECONDARY AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    9.7 CONTROL SWITCH FOR CIRCUIT BREAKER (52CS) YES

    POSITIONS OFF - NEUTRAL - ON

    POSITION AT REST NEUTRAL

    MANUFACTURER

    MODEL

    9.8 SIGNALING LAMPS LED POWER W

    MODEL

    9.9 SIGNALING LAMP TEST BUTTON YES

    LOCATION 1 BUTTON PER COMPARTMENT

    SWITCH-OFF TIME

    9.10 9.10.1 AUXILIARY RELAYS

    AMOUNT MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    9.10.2 AUXILIARY RELAYS

    AMOUNT

    MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    9.10.3 AUXILIARY RELAYS

    AMOUNT

    MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    9.11 SECTION FEED TYPE

    AMOUNT PER PHASE

    DIMENSIONS

    9.12 DEHUMIDIFICATION SET YES

    9.12.1 HEATING RESISTOR

    MANUFACTURER / MODEL

    RATED VOLTAGE

    POWER W

    FEED EXTERNAL

    9.12.2 HEATING RESISTOR THERMOSTAT YES

    MANUFACTURER / MODEL

    ADJUSTMENT RANGE C - C

    9.13 SURGE SUPRESSOR (DPS) NO

    AMOUNT MANUFACTURER

    MODEL

    PROTECTION LEVEL Up kV

    CONITINUOUS OPERATION MAXIMUM VOLTAGE Uc V

    DISCHARGE RATED CURRENT In kA

    IMPULSE CURRENT I imp kA

    SHORT-CIRCUIT CURRENT WITHSTAND kA 9.14 MEASURING INSTRUMENTS

    9.14.1 VARIABLE VOLTAGE

    TYPE ANALOG AMOUNT

    MANUFACTURER / MODEL

    DIMENSION mm x mm SCALE

    SELECTOR SWITCH YES

    9.14.2 VARIABLE CURRENT

    TYPE ANALOG AMOUNT

    MANUFACTURER / MODEL

    DIMENSION mm x mm SCALE

    SELECTOR SWITCH YES 9.14.3 TRANSDUCER YES

    AMOUNT

    VARIABLE VOLTAGE

    MANUFACTURER / MODEL

    OUTPUT SIGNAL 4-20 mA

    9.15 AUXILIARY INDOOR LIGHTING YES

    POWER W VOLTAGE V

    SOURCE EXTERNAL

    LIMIT SWITCHES IN PORTS YES

    9.16 INTERLOCKS

  • Data Sheet No. REV. SHEET: 5 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    10 INTERCONNECTION SECTIONS

    GENERAL SPECIFICATIONS

    10.1 INTERCONNECTION SECTION

    10.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No.

    LOGICAL No.

    10.3 CIRCUIT BREAKER NO

    TYPE

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY fr 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu kA

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT DELAY RELATING TO Icw s

    CATEGORY OF USE B

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM COIL

    SPRING PRE-LOADED BY ELECTRIC MOTOR YES

    MANUAL DEVICE YES

    ANTI-PUMPING DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    CONTACT CLOSING TIME ms

    OPENING MECHANISM COIL

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    OPENING TIME FOR I > Icw ms

    TEMPERATURE RISE IN CONNECTIONS K

    No. OF OPERATING CYCLES WITH CURRENT

    AUXILIARY CONTACTS NA NF

    10.4 CURRENT TRANSFORMERS FOR INSTRUMENTS

    10.4.1 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) M

    MAXIMUM VOLTAGE kV

    10.4.2 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) M

    MAXIMUM VOLTAGE kV

    10.5 POWER TRANSFORMERS FOR INSTRUMENTS

    10.5.1 TYPE: DRY AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION CLASS AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    PURPOSE (NOTE 6) M AT

    MAXIMUM VOLTAGE kV

    10.5.2 TYPE: DRY AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION CLASS AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    PURPOSE (NOTE 6) M AT

    MAXIMUM VOLTAGE kV

    10.5.3 PRIMARY PROTECTION: C. BREAKER AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    RATED INTERRUPTION CAPACITY kA

    10.5.4 CIRCUIT BREAKER IN SECONDARY AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    10.6 CONTROL SWITCH FOR CIRCUIT BREAKER (52CS) NO

    POSITIONS OFF - NEUTRAL - ON

    POSITION AT REST NEUTRAL

    MANUFACTURER

    MODEL

    10.7 SWITCH

    MANUFACTURER

    MODEL

    DESCRIPTION OF OPERATION

  • Data Sheet No. REV. SHEET: 6 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    10.8 SWITCH

    MANUFACTURER

    MODEL

    DESCRIPTION OF OPERATION

    10.9 SIGNALING LAMPS LED POWER (W)

    MODEL

    10.10 10.10.1 AUXILIARY RELAYS

    AMOUNT

    MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    10.10.2 AUXILIARY RELAYS

    AMOUNT MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    10.10.3 AUXILIARY RELAYS

    AMOUNT

    MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    10.10.4 AUXILIARY RELAYS

    AMOUNT MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    10.11 DEHUMIDIFICATION SET YES

    10.11.1 HEATING RESISTOR

    MANUFACTURER

    MODEL

    RATED VOLTAGE

    POWER W

    FEED EXTERNAL

    10.11.2 HEATING RESISTOR THERMOSTAT YES

    MANUFACTURER

    MODEL

    ADJUSTMENT RANGE C - C

    10.12 AUXILIARY INDOOR LIGHTING YES

    POWER W VOLTAGE V

    SOURCE EXTERNAL

    LIMIT SWITCHES IN PORTS YES

    10.13 INTERLOCKS

  • Data Sheet No. REV. SHEET: 7 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    11 OUTLET SECTIONS WITH CIRCUIT BREAKER FOR NON-MOTOR LOAD

    GENERAL SPECIFICATIONS

    11.1 OUTLET SECTION

    11.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No

    LOGICAL No.

    11.3 CIRCUIT BREAKER YES

    TYPE MOLDED CASING

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY fr 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu A

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT DELAY RELATING TO Icw s

    CATEGORY OF USE A

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM

    MANUAL DEVICE YES

    CONTACT CLOSING TIME ms

    OPENING MECHANISM

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    OPENING TIME FOR I > Icw ms

    TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K

    No. OF OPERATING CYCLES WITH CURRENT

    AUXILIARY CONTACTS NA NF

    PROTECTIONS

    11.4 CURRENT TRANSFORMERS FOR INSTRUMENTS

    11.4.1 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL / CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) P

    MAXIMUM VOLTAGE kV

    11.5 POWER TRANSFORMERS FOR INSTRUMENTS

    11.5.1 TYPE: DRY AMOUNT

    MANUFACTURER

    MODEL OR CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION CLASS AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    PURPOSE (NOTE 6) M AT

    MAXIMUM VOLTAGE kV

    11.5.2 PRIMARY PROTECTION: C. BREAKER AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    RATED INTERRUPTION CAPACITY kA

    11.5.3 CIRCUIT BREAKER IN SECONDARY AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    11.6 SWITCH

    MANUFACTURER

    MODEL

    DESCRIPTION OF OPERATION SEE GENERAL NOTES

    11.7 GROUND FAULT SIGNAL NO

    MODEL / MANUFACTURER

    VISUAL SIGNALING LED

    AUXILIARY CONTACTS NA NF

    11.8 SIGNALING LAMP TEST BUTTON YES

    11.9 11.9.1 AUXILIARY RELAYS

    AMOUNT MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms)

    CONTACT CAPACITY (A) IN V

    NUMBER OF CONTACTS NA NF

    11.10 COMMUNICATION AND PROTECTIVE RELAY (IED) NO

    MANUFACTURER/MODEL

    TYPE

    AUXILIARY VOLTAGE V NETWORK VOLTAGE V

    COMMUNICATION PORTS

    PROTECTIVE FUNCTIONS

    AUXILIARY CONTACTS NA NF

    11.11 RESIDUAL DIFFERENTIAL DEVICE NO

    MANUFACTURER

    MODEL

    TYPE AC

    RATED CURRENT A

    RESIDUAL RATED CURRENT mA

    NUMBER OF POLES TETRAPOLAR

    INTERLOCKS

  • Data Sheet No. REV. SHEET: 8 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    12 OUTLET SECTIONS WITH CIRCUIT BREAKER AND CONTACTOR FOR MOTOR LOAD

    GENERAL SPECIFICATIONS

    12.1 OUTLET SECTION

    12.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No

    LOGICAL No.

    12.3 CIRCUIT BREAKER YES

    TYPE MOLDED CASING

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY fr 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu kA

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT DELAY RELATING TO Icw s

    CATEGORY OF USE A

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM

    MANUAL DEVICE YES

    CONTACT CLOSING TIME ms

    OPENING MECHANISM

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A

    OPENING TIME FOR I > Icw ms

    TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K

    No. OF OPERATING CYCLES WITH CURRENT

    AUXILIARY CONTACTS NA NF

    PROTECTIONS

    12.4 CONTACTOR

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONV. THERMAL CURRENT (OUTDOORS) I th A

    CONV. THERMAL CURRENT IN ENCLOSURE Ithe A

    RATED CURRENT OF OPERATION Ie A

    UNINTERRUPTIBLE RATED CURRENT Iu A

    RATED FREQUENCY fr 60Hz

    LOAD RATE INTERMITTENT

    RATE CLASS

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT INTERRUPTION RATED CAPACITY Icn kA

    CONDITIONAL RATED SHORT-CIRCUIT CURRENT kA

    CATEGORY OF USE AC-3

    COORDINATION WITH CIRCUIT BREAKER TYPE 2

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    INTERRUPTION MEDIUM AIR

    CLOSING MECHANISM (OPERATION METHOD)

    ELECTROMAGNETIC YES

    SPOOL RATED VOLTAGE 120 VAC INTERNAL

    SPOOL POWER W

    TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K

    No. OF OPERATING CYCLES WITH CURRENT

    AUXILIARY CONTACTS NA NF

    12.5 CURRENT TRANSFORMERS FOR INSTRUMENTS

    12.5.1 TYPE: WINDOW AMOUNT

    MANUFACTURER

    MODEL / CATALOG No.

    RATED RATIO

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT)

    PURPOSE (NOTE 6) P M

    MAXIMUM VOLTAGE kV

    12.5.2 TYPE: WINDOW AMOUNT

    NUMBER OF CORES (NOTE 6) P M

    MANUFACTURER

    MODEL / CATALOG No.

    RATED RATIO (NOTE 6) P M

    RATED PRIMARY CURRENT A

    PRECISION AND RATED LOAD (ABNT) (NOTE 6) P

    PRECISION AND RATED LOAD (ABNT) (NOTE 6) M

    MAXIMUM VOLTAGE kV

    12.6 POWER TRANSFORMERS FOR CONTROL

    12.6.1 TYPE: DRY AMOUNT

    MANUFACTURER

    MODEL / CATALOG No.

    RATED RATIO

    RATED PRIMARY VOLTAGE V

    RATED SECONDARY VOLTAGE V

    PRECISION AND RATED LOAD (ABNT)

    RATED THERMAL INPUT VA

    MAXIMUM VOLTAGE kV

  • Data Sheet No. REV. SHEET: 9 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    12.6.2 PRIMARY PROTECTION: C. BREAKER AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    RATED INTERRUPTION CAPACITY kA

    12.6.3 CIRCUIT BREAKER IN SECONDARY AMOUNT

    MANUFACTURER / MODEL

    RATED CURRENT A

    12.7 OFF COMMAND BUTTON WITH DELAY YES

    MANUFACTURER

    MODEL

    12.8 ON COMMAND BUTTON NO

    MANUFACTURER

    MODEL

    12.9 SWITCH

    MANUFACTURER

    MODEL

    DESCRIPTION OF OPERATION

    12.10 SIGNALING LAMPS LED POWER (W)

    MODEL

    12.11 12.11.1 AUXILIARY RELAYS

    AMOUNT MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    12.11.2 AUXILIARY RELAYS

    AMOUNT

    MANUFACTURER

    MODEL

    SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY IN V

    NUMBER OF CONTACTS NA NF

    12.11.3 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE

    COMMUTATION TIME ms

    CONTACT CAPACITY A IN V

    NUMBER OF CONTACTS NA NF

    12.12 SIGNALING LAMP TEST BUTTON YES

    12.13 BIMETALLIC THERMAL PROTECTIVE RELAY NO

    MANUFACTURER/MODEL

    TRIP CLASS (IEC 60947-4-1)

    RESET LOCAL/MANUAL

    ADJUSTMENT RANGE A - A

    12.14 COMMUNICATION AND PROTECTIVE RELAY (IED) YES

    MANUFACTURER/MODEL

    TYPE

    AUXILIARY VOLTAGE V NETWORK VOLTAGE V

    COMMUNICATION PORTS

    PROTECTIVE FUNCTIONS

    AUXILIARY CONTACTS NA NF

    12.15 RIDE THROUGH DEVICE YES

    MANUFACTURER MODEL PRIMARY TERMINAL VOLTAGE 480V

    FEED VOLTAGE 127V

    12.16 INTERLOCKS

  • Data Sheet No. REV. SHEET: 10 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    13 OUTLET SECTIONS WITH CIRCUIT BREAKER, CONTACTOR, AND ELECTRONIC SOFT STARTER

    GENERAL SPECIFICATIONS

    13.1 OUTLET SECTION

    13.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No

    LOGICAL No.

    13.3 CIRCUIT BREAKER YES

    TYPE MOLDED CASING

    MANUFACTURER MODEL OR CATALOG No. ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY fr 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu kA

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT DELAY RELATING TO Icw s CATEGORY OF USE A

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM

    MANUAL DEVICE YES

    CONTACT CLOSING TIME ms OPENING MECHANISM

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A OPENING TIME FOR I > Icw ms TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K No. OF OPERATING CYCLES WITH CURRENT AUXILIARY CONTACTS NA NF PROTECTIONS

    13.4 CONTACTOR

    MANUFACTURER TYPE, MODEL OR CATALOG No. ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue (V) RATED VOLTAGE OF INSULATION Ui (V) WITHSTAND VOLTAGE OF IMPULSE Uimp (kV)

    CONV. THERMAL CURRENT (OUTDOORS) I th A CONV. THERMAL CURRENT IN ENCLOSURE Ithe A RATED CURRENT OF OPERATION Ie A UNINTERRUPTIBLE RATED CURRENT Iu A RATED FREQUENCY fr 60Hz

    LOAD RATE INTERMITTENT

    RATE CLASS

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT INTERRUPTION RATED CAPACITY Icn kA

    CONDITIONAL RATED SHORT-CIRCUIT CURRENT kA

    CATEGORY OF USE AC-3

    COORDINATION WITH CIRCUIT BREAKER TYPE 2

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    INTERRUPTION MEDIUM AR

    CLOSING MECHANISM (OPERATION METHOD)

    ELECTROMAGNETIC YES

    SPOOL RATED VOLTAGE 120 VAC INTERNAL

    SPOOL POWER W TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K No. OF OPERATING CYCLES WITH CURRENT AUXILIARY CONTACTS NA NF

    13.5 CURRENT TRANSFORMERS FOR INSTRUMENTS

    13.5.1 TYPE: WINDOW AMOUNT MANUFACTURER MODEL / CATALOG No. RATED RATIO RATED PRIMARY CURRENT A PRECISION AND RATED LOAD (ABNT) PURPOSE (NOTE 6) P M

    MAXIMUM VOLTAGE kV 13.5.2 TYPE: WINDOW AMOUNT NUMBER OF CORES (NOTE 6) P M

    MANUFACTURER MODEL / CATALOG No. RATED RATIO (NOTE 6) P M RATED PRIMARY CURRENT A PRECISION AND RATED LOAD (ABNT) (NOTE 6) P PRECISION AND RATED LOAD (ABNT) (NOTE 6) M MAXIMUM VOLTAGE kV

    13.6 POWER TRANSFORMERS FOR CONTROL

    13.6.1 TYPE: DRY AMOUNT MANUFACTURER MODEL / CATALOG No. RATED RATIO RATED PRIMARY VOLTAGE V RATED SECONDARY VOLTAGE V PRECISION AND RATED LOAD (ABNT) RATED THERMAL INPUT VA MAXIMUM VOLTAGE kV

  • Data Sheet No. REV. SHEET: 11 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    13.6.2 FUSE IN PRIMARY AMOUNT MANUFACTURER MODEL / CATALOG No. RATED CURRENT (A) RATED INTERRUPTION CAPACITY (kA) 13.6.3 CIRCUIT BREAKER IN SECONDARY AMOUNT MANUFACTURER / MODEL RATED CURRENT (A)

    13.7 OFF COMMAND BUTTON WITH DELAY YES

    MANUFACTURER MODEL

    13.8 ON COMMAND BUTTON NO

    MANUFACTURER MODEL

    13.9 OPERATION CONTROL SWITCH (69LR) NO

    POSITIONS MANUAL/LOCAL ESC/REMOTE

    POSITION AT REST ESC/REMOTE

    MANUFACTURER MODEL DESCRIPTION OF OPERATION

    13.10 SWITCH MANUFACTURER MODEL DESCRIPTION OF OPERATION

    13.11 SWITCH MANUFACTURER MODEL DESCRIPTION OF OPERATION

    13.12 SIGNALING LAMPS POWER (W) MODEL

    13.13 13.13.1 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF 13.13.2 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF

    13.13.3 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF

    13.14 SIGNALING LAMP TEST BUTTON

    LOCATION

    SWITCH-OFF TIME

    13.15 DEHUMIDIFICATION SET NO

    13.15.1 HEATING RESISTOR

    MANUFACTURER MODEL RATED VOLTAGE (V)

    POWER (W) FEED EXTERNAL

    13.15.2 HEATING RESISTOR THERMOSTAT

    MANUFACTURER MODEL ADJUSTMENT RANGE (C) TO

    13.16 INDOOR LIGHTING ASSEMBLY YES

    13.17 COMMUNICATION AND PROTECTIVE RELAY (INTELLIGENT) YES

    MANUFACTURER MODEL TYPE AUXILIARY VOLTAGE (V) NETWORK VOLTAGE (V) COMMUNICATION PORTS COMMUNICATION PROTOCOL PROTECTIVE FUNCTIONS

    AUXILIARY CONTACTS NA NF

    13.18 ELECTRONIC SOFT STARTER

    MANUFACTURER MODEL RATED VOLTAGE (V) RATED CURRENT (A) RAMP TIME ADJUSTMENT RANGE (s) - MAXIMUM CURRENT LIMITER YES

    CURRENT LIMITER ADJUSTMENT RANGE (%) - TORQUE REINFORCEMENT AT START-UP YES

    REINFORCEMENT ADJUSTMENT RANGE (%) - COMMUNICATION INTERFACE PORT YES

    DESCRIPTION BY-PASS CONTACTOR NO

    13.19 INTERLOCKS

  • Data Sheet No. REV. SHEET: 12 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    14 OUTLET SECTIONS WITH CIRCUIT BREAKER, CONTACTOR AND VARIABLE FREQUENCY DRIVE

    GENERAL SPECIFICATIONS

    14.1 OUTLET SECTION

    14.2 ATTACHED DIAGRAMS

    SINGLE LINE No.

    FUNCTIONAL No

    LOGICAL No.

    14.3 CIRCUIT BREAKER YES

    TYPE MOLDED CASING

    MANUFACTURER

    MODEL OR CATALOG No.

    ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue V

    RATED VOLTAGE OF INSULATION Ui V

    RATED WITHSTAND VOLTAGE OF IMPULSE Uimp kV

    CONVENTIONAL THERMAL CURRENT (OUTDOORS) I th A

    CONVENTIONAL THERMAL CURRENT IN ENCLOSURE I the A

    RATED CURRENT IN OPERATION In A

    RATED FREQUENCY fr 60Hz

    LOAD RATE CONTINUOUS

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA SHORT-CIRCUIT MAXIMUM INTERRUIPTION RATED CAPACITY Icu

    SERVICE SHORT-CIRCUIT INTERRUIPTION RATED CAPACITY Ics kA SHORT-DURATION RATED WITHSTAND CURRENT Icw kA SHORT DELAY RELATING TO Icw s

    CATEGORY OF USE A

    CONTROL CIRCUIT VOLTAGE EXTERNAL

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    CLOSING MECHANISM

    MANUAL DEVICE YES

    CONTACT CLOSING TIME ms OPENING MECHANISM

    TYPE FREE OPENING

    MANUAL DEVICE YES

    ELECTRIC MECHANISM CURRENT A OPENING TIME FOR I > Icw ms TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K No. OF OPERATING CYCLES WITH CURRENT AUXILIARY CONTACTS NA NF PROTECTIONS

    14.4 CONTACTOR NO

    MANUFACTURER TYPE, MODEL OR CATALOG No. ELECTRICAL CHARACTERISTICS

    NUMBER OF POLES 3

    CURRENT ALTERNATING

    RATED VOLTAGE OF OPERATION Ue (V) RATED VOLTAGE OF INSULATION Ui (V) WITHSTAND VOLTAGE OF IMPULSE Uimp (kV) CONV. THERMAL CURRENT (OUTDOORS) Ith A

    CONV. THERMAL CURRENT IN ENCLOSURE Ithe A RATED CURRENT OF OPERATION Ie A UNINTERRUPTIBLE RATED CURRENT Iu A RATED FREQUENCY fr 60Hz

    LOAD RATE INTERMITTENT

    RATE CLASS

    SHORT-DURATION RATED WITHSTAND CURRENT Icw kA

    SHORT-CIRCUIT ESTABLISHMENT RATED CAPACITY Icm kA

    SHORT-CIRCUIT INTERRUPTION RATED CAPACITY Icn kA CONDITIONAL RATED SHORT-CIRCUIT CURRENT kA

    CATEGORY OF USE AC-3

    COORDINATION WITH CIRCUIT BREAKER TYPE 2

    DESIGN AND CONSTRUCTION CHARACTERISTICS

    INTERRUPTION MEDIUM AIR

    CLOSING MECHANISM (OPERATION METHOD)

    ELECTROMAGNETIC YES

    SPOOL RATED VOLTAGE 120 VAC INTERNAL

    SPOOL POWER W TEMPERATURE RISE

    TERMINALS FOR CONNECTIONS K No. OF OPERATING CYCLES WITH CURRENT AUXILIARY CONTACTS NA NF

    14.5 CURRENT TRANSFORMERS FOR INSTRUMENTS

    14.5.1 TYPE: WINDOW AMOUNT MANUFACTURER MODEL / CATALOG No. RATED RATIO RATED PRIMARY CURRENT A PRECISION AND RATED LOAD (ABNT) PURPOSE (NOTE 6) P M

    MAXIMUM VOLTAGE kV 14.5.2 Type: WINDOW AMOUNT NUMBER OF CORES (NOTE 6) P M

    MANUFACTURER MODEL / CATALOG No. RATED RATIO (NOTE 6) P M RATED PRIMARY CURRENT A PRECISION AND RATED LOAD (ABNT) (NOTE 6) P PRECISION AND RATED LOAD (ABNT) (NOTE 6) M MAXIMUM VOLTAGE kV

    14.6 POWER TRANSFORMERS FOR CONTROL

    14.6.1 TYPE: DRY AMOUNT MANUFACTURER MODEL / CATALOG No. RATED RATIO RATED PRIMARY VOLTAGE V RATED SECONDARY VOLTAGE V PRECISION AND RATED LOAD (ABNT) RATED THERMAL INPUT VA MAXIMUM VOLTAGE kV

  • Data Sheet No. REV. SHEET: 13 of 17

    TITLE: Low-Voltage Panel Motor Control Center

    14.6.2 FUSE IN PRIMARY AMOUNT MANUFACTURER MODEL / CATALOG No. RATED CURRENT (A) RATED INTERRUPTION CAPACITY (kA) 14.6.3 CIRCUIT BREAKER IN SECONDARY AMOUNT MANUFACTURER / MODEL RATED CURRENT (A)

    14.7 OFF COMMAND BUTTON YES

    MANUFACTURER MODEL

    14.8 ON COMMAND BUTTON NO

    MANUFACTURER MODEL

    14.9 OPERATION CONTROL SWITCH (69LR) NO

    POSITIONS MANUAL/LOCAL ESC/REMOTE

    POSITION AT REST ESC/REMOTE

    MANUFACTURER MODEL DESCRIPTION OF OPERATION

    14.10 SWITCH MANUFACTURER MODEL DESCRIPTION OF OPERATION

    14.11 SWITCH MANUFACTURER MODEL DESCRIPTION OF OPERATION

    14.12 SIGNALING LAMPS POWER (W) MODEL

    14.13 14.13.1 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF 14.13.2 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF 14.13.3 AUXILIARY RELAYS

    AMOUNT MANUFACTURER MODEL SPOOL RATED VOLTAGE (V)

    COMMUTATION TIME (ms) CONTACT CAPACITY (A) IN V NUMBER OF CONTACTS NA NF

    14.14 SIGNALING LAMP TEST BUTTON

    LOCATION

    SWITCH-OFF TIME

    14.15 DEHUMIDIFICATION SET YES

    14.15.1 HEATING RESISTOR

    MANUFACTURER MODEL RATED VOLTAGE (V)

    POWER (W) FEED EXTERNAL

    14.15.2 HEATING RESISTOR THERMOSTAT

    MANUFACTURER MODEL ADJUSTMENT RANGE (C) AT

    14.16 INDOOR LIGHTING ASSEMBLY YES

    14.17 COMMUNICATION AND PROTECTIVE RELAY (INTELLIGENT) YES

    MANUFACTURER MODEL TYPE AUXILIARY VOLTAGE (V) NETWORK VOLTAGE (V) COMMUNICATION PORTS COMMUNICATION PROTOCOL PROTECTIVE FUNCTIONS

    AUXILIARY CONTACTS NA NF

    14.18 VARIABLE FREQUENCY DRIVE

    MANUFACTURER MODEL FREQUENCY VARIATION RANGE (Hz) TO REFERENCE INLET 4 to 20mA

    RATED VOLTAGE (V) RATED CURRENT (A) TYPE OF CONTROL VECTOR

    COMMUNICATION INTERFACE PORT YES