Upload
neelakandan-masilamani
View
226
Download
1
Embed Size (px)
Citation preview
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
1/65
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Non-Direct ion al Overcurrent
and Earth Fault Protec t ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
2/65
> Non-Directional Overcurrent and Earth Fault Protection2
Overcurrent Protect ion: Purpose of Protect ion
Detect abnormal conditions
Isolate faulty part of the system
Speed
Fast operation to minimise damage and danger
Discrimination
Isolate only the faulty section
Dependability / reliability
Security / stability
Cost of protection / against cost of potential hazards
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
3/65
> Non-Directional Overcurrent and Earth Fault Protection3
Overcu rrent Protect ion Co-ord inat ion
F3
2
1
Co-ordinate protection so that relay nearest to fault
operates first
Minimise system disruption due to the fault
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
4/65
> Non-Directional Overcurrent and Earth Fault Protection4
Fuses
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
5/65
> Non-Directional Overcurrent and Earth Fault Protection5
Overcu rrent Protect ion Fuses
Simple
Can provide very fast fault clearance
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
6/65
> Non-Directional Overcurrent and Earth Fault Protection6
Overcu rrent Protect ion Fuses - disadvantages
Problematic co-ordination
IFAapprox 2 x IFB
Limited sensitivity to earth faults
Single phasing
Fixed characteristic
Need replacing following fault clearance
Fuse A Fuse B
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
7/65> Non-Directional Overcurrent and Earth Fault Protection7
Tr ipp ing Methods
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
8/65> Non-Directional Overcurrent and Earth Fault Protection8
Overcu rrent Protect ion Direct Act ing AC Trip
AC series trip
common for electromechanical O/C relays
51
IF
Trip Coil
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
9/65> Non-Directional Overcurrent and Earth Fault Protection9
Overcu rrent Protect ion Direct Act ing AC Trip
Capacitor discharge trip
used with static relays where no secure DC supply is
available
IF'
SensitiveTrip
Coil
51
+
-
IF
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
10/65> Non-Directional Overcurrent and Earth Fault Protection10
Overcu rrent Protect ion DC Shun t Trip
Requires secure DC auxiliary
No trip if DC fails
IF'
DCBATTERY
SHUNTTRIP COIL
51
IF
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
11/65> Non-Directional Overcurrent and Earth Fault Protection11
No Volt Trip Coil: Relay Un-Operated
Used for fail-safe tripping on motor feeders
No Volt
ReleaseTrip Coil
51
V
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
12/65> Non-Directional Overcurrent and Earth Fault Protection12
No Volt Trip Coil: Relay Operated
Used for fail-safe tripping on motor feeders
No Volt
ReleaseTrip Coil
51
V
IF
IF'
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
13/65> Non-Directional Overcurrent and Earth Fault Protection13
Overcurrent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
14/65> Non-Directional Overcurrent and Earth Fault Protection14
Overcu rrent Protect ion Principles
Operating Speed
Instantaneous
Time delayed
DiscriminationCurrent setting
Time setting
Current and time
Cost
Generally cheapest form of protection relay
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
15/65> Non-Directional Overcurrent and Earth Fault Protection15
Overcu rrent Protect ion Ins tantaneous Relays
Current settings chosen so that relay closest to fault
operates
Problem
Relies on there being a difference in fault level between the
two relay locations
Cannot discriminate if IF1= IF2
IF1IF250
B
50
A
IF2 IF1
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
16/65> Non-Directional Overcurrent and Earth Fault Protection16
Overcur rent Protect ion Definite (Independent)
Time Relays
TOP
TIME
IS Applied Current
(Relay Current Setting)
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
17/65> Non-Directional Overcurrent and Earth Fault Protection17
Overcur rent Protect ion Definite (Independent)
Time Relays
Operating time is independent of current
Relay closest to fault has shortest operating time
Problem
Longest operating time is at the source where fault level is
highest
51
0.9 sec 0.5 sec
5151
0.9 sec 0.5 sec
51
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
18/65> Non-Directional Overcurrent and Earth Fault Protection18
Overcu rrent Pro tect ion IDMT
TIME
Applied Current(Relay Current Setting)
IS
Inverse Definite Minimum Time characteristic
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
19/65> Non-Directional Overcurrent and Earth Fault Protection19
Overcu rrent Protect ion Disc Type O/C Relays
Current setting via plug bridge
Time multiplier setting via disc
movement
Single characteristic
Consider 2 ph & EF or 3 ph plus
additional EF relay
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
20/65> Non-Directional Overcurrent and Earth Fault Protection20
Overcu rrent Protect ion Stat ic Relay
Electronic, multi characteristic
Fine settings, wide range
Integral instantaneous elements
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
21/65> Non-Directional Overcurrent and Earth Fault Protection21
Overcu rrent Protect ion Numerical Relay
Multiple characteristics and stages Current settings in primary or secondary values
Additional protection elements
Current
Time
I
>1
I>2
I>3
I>4
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
22/65> Non-Directional Overcurrent and Earth Fault Protection22
Co-ordinat ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
23/65
> Non-Directional Overcurrent and Earth Fault Protection23
Overcu rrent Protect ion Co-ordinat ion Princ iple
Relay closest to fault
must operate first
Other relays must have
adequate additional
operating time to
prevent them operating
Current setting chosen
to allow FLC
Consider worst caseconditions, operating
modes and current
flows
T
IS1IS2 MaximumFaultLevel
I
R2R1
IF1
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
24/65
> Non-Directional Overcurrent and Earth Fault Protection24
Overcu rrent Protect ion Co-ordinat ion Example
C AB
0.01
0.1
1
10
Operatingtime(s)
Current (A) FLB FLC FLD
ED
C
B
DE C AB
0.01
0.1
1
10
Operatingtime(s)
Current (A) FLB FLC FLD
ED
C
B
DE
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
25/65
> Non-Directional Overcurrent and Earth Fault Protection25
Overcu rrent Protect ion IEC Character ist ics
SI t = 0.14
(I0.02-1)
VI t = 13.5
(I2-1)
EI t = 80
(I2-1)
LTI t = 120(I- 1)
Current (Multiples of Is)
0.1
1
10
100
1000
1
1000
O
p
a
n
T
m
e
s
VI
EI
SI
LTI
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
26/65
> Non-Directional Overcurrent and Earth Fault Protection26
Overcur rent Protect ion Operat ing Time Sett ing -
Terms Used
Relay operating times can be
calculated using relay
characteristic charts
Published characteristics are
drawn against a multiple of
current setting or Plug SettingMultiplier
Therefore characteristics can be
used for any application
regardless of actual relay
current setting
e.g at 10x setting (or PSM of 10)
SI curve op time is 3sCurrent (Multiples of Is)
0.1
1
10
100
1000
1
1000
O
p
a
n
T
m
e
s
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
27/65
> Non-Directional Overcurrent and Earth Fault Protection27
Overcu rrent Protect ion Current Sett ing
Set just above full load currentallow 10% tolerance
Allow relay to reset if fault is cleared by downstream
device
consider pickup/drop off ratio (reset ratio)
relay must fully reset with full load current flowing
PU/DO for static/numerical = 95%
PU/DO for EM relay = 90%
e.g for numerical relay, Is = 1.1 x IFL/0.95
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
28/65
> Non-Directional Overcurrent and Earth Fault Protection28
Overcu rrent Protect ion Current Sett ing
Current grading
ensure that if upstream relay has started downstream relay has
also started
Set upstream device current setting greater than downstream relay
e.g. IsR1 = 1.1 x IsR2
R1 R2 IF1
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
29/65
> Non-Directional Overcurrent and Earth Fault Protection29
Overcu rrent Protect ion Grading Margin
Operating time difference between two devices to ensure
that downstream device will clear fault before upstream
device trips
Must include
breaker opening time
allowance for errors
relay overshoot time
safety margin
GRADING
MARGIN
O t P t t i G di M i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
30/65
> Non-Directional Overcurrent and Earth Fault Protection30
Overcu rrent Protect ion Grading Margin -
between relays
Traditional
breaker op time - 0.1
relay overshoot - 0.05
allow. For errors - 0.15
safety margin - 0.1
Total 0.4s
Calculate using formula
R2R1
O t P t t i G di M i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
31/65
> Non-Directional Overcurrent and Earth Fault Protection31
Overcu rrent Protect ion Grading Margin -
between relays
Formula
t = (2Er + Ect) t/100 + tcb + to + ts
Er = relay timing error
Ect = CT measurement error
t = op time of downstream relay
tcb = CB interupting time
to = relay overshoot time
ts = safety margin
Op time of Downstream Relay t = 0.5s
0.375s margin for EM relay, oil CB
0.24s margin for static relay, vacuum CB
O t P t t i G di M i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
32/65
> Non-Directional Overcurrent and Earth Fault Protection32
Overcu rrent Protect ion Grading Margin -
relay w ith fuse
Grading Margin = 0.4Tf + 0.15s over whole characteristic
Assume fuse minimum operating time = 0.01s
Use EI or VI curve to grade with fuse
Current setting of relay should be 3-4 x rating of fuse to
ensure co-ordination
O erc rrent Protect ion Grading Margin
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
33/65
> Non-Directional Overcurrent and Earth Fault Protection33
Overcu rrent Protect ion Grading Margin -
relay w i th upstream fuse
1.175Tr + 0.1 + 0.1 = 0.6Tf
or
Tf= 2Tr + 0.33s
Allowance for CTand relay error
CB Safety margin Allowance forfuse error (fast)
Tf
Tr
IFMAX
Overcu rrent Protect ion Time Mult ip l ier Setting
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
34/65
> Non-Directional Overcurrent and Earth Fault Protection34
Overcu rrent Protect ion Time Mult ip l ier Setting
Used to adjust the
operating time of an
inverse characteristic
Not a time setting but a
multiplier
Calculate TMS to give
desired operating time
in accordance with the
grading margin
Current (Multiples of Is)
0.1
1
10
100
1
1000
O
p
a
n
T
m
e
s
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
35/65
> Non-Directional Overcurrent and Earth Fault Protection35
Overcur rent Protect ion
Time Mult ip l ier Sett ing - Calculat ion
Calculate relay operating time required, Treq
consider grading margin
fault level
Calculate op time of inverse characteristic with
TMS = 1, T1
TMS = Treq/T1
Overcu rrent Protect ion Co ord inat ion Procedu re
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
36/65
> Non-Directional Overcurrent and Earth Fault Protection36
Overcu rrent Protect ion Co-ord inat ion - Procedu re
Calculate required operating current
Calculate required grading margin
Calculate required operating time Select characteristic
Calculate required TMS
Draw characteristic, check grading over whole
curve
Grading curves should be drawn to a common
voltage base to aid comparison
Overcu rrent Protect ion Co ordinat ion Example
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
37/65
> Non-Directional Overcurrent and Earth Fault Protection37
Overcu rrent Protect ion Co-ordinat ion Example
Grade relay B with relay A
Co-ordinate at max fault level seen by both
relays = 1400A
Assume grading margin of 0.4s
Is = 5 Amp; TMS = 0.05, SI
IFMAX= 1400 Amp
B A
200/5 100/5
Is = 5 Amp
Overcu rrent Protect ion Co ordinat ion Example
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
38/65
> Non-Directional Overcurrent and Earth Fault Protection38
Overcu rrent Protect ion Co-ordinat ion Example
Relay B is set to 200A primary, 5A secondary
Relay A set to 100A If (1400A) = PSM of 14
relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13(I0.02-1) (140.02-1)
Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s
Relay A uses SI curve so relay B should also use SI curve
Is = 5 Amp; TMS = 0.05, SI
IFMAX= 1400 Amp
B A
200/5 100/5
Is = 5 Amp
Overcu rrent Protect ion Co ordinat ion Example
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
39/65
> Non-Directional Overcurrent and Earth Fault Protection39
Overcu rrent Protect ion Co-ordinat ion Example
Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s
Relay A uses SI curve so relay B should also use SI curve
Relay B set to 200A If (1400A) = PSM of 7
relay B OP time TMS = 1 = 0.14 x TMS = 0.14 = 3.52s
(I0.02
-1) (70.02
-1) Required TMS = Required Op time = 0.53 = 0.15
Op time TMS=1 3.52
Set relay B to 200A, TMS = 0.15, SI
Is = 5 Amp; TMS = 0.05, SI
I
FMAX= 1400 Amp
B A
200/5 100/5
Is = 5 Amp
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
40/65
> Non-Directional Overcurrent and Earth Fault Protection40
Overcur rent Protect ion
LV Protect ion Co -ord inat ion
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
1
2
3
4
F
350MVA
4
3 3
2
F
11kV
MCGG CB
ACB CTZ61 (Open)TZ61
ACB
MCCB
27MVA
20MVA
oad
Fuse
2 x 1.5MVA
11kV/433V
5.1
K
1
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
41/65
> Non-Directional Overcurrent and Earth Fault Protection41
O e cu e o ec o
LV Protect ion Co -ord inat ion
1000S
100S
10S
1.0S
0.1S
0.01S
0. 1kA 10kA 1000kA
TX damage
Very
inverse
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
42/65
> Non-Directional Overcurrent and Earth Fault Protection42
LV Protect ion Co -ord inat ion
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
1
2
3
4
F
350MVA
4
3 3
2
1
F
11kV
KCGG 142 CB
ACB (Open)CEG 142
ACB
MCCB
27MVA
20MVA
oad
Fuse
2 x 1.5MVA
11kV/433V
5.1
K
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
43/65
> Non-Directional Overcurrent and Earth Fault Protection43
LV Protect ion Co -ord inat ion
1000S
100S
10S
1.0S
0.1S
0.01S
0. 1kA
10kA
1000kA
TX damage
Long time
inverse
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
44/65
> Non-Directional Overcurrent and Earth Fault Protection44
Block ing Schemes
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
45/65
> Non-Directional Overcurrent and Earth Fault Protection45 Manufacturers Technical Update Oct 2010 -
System Grading
Downstream protection must grade with the utility incomer at the maximum
fault level 11kV Supply
Load
LoadLoad
Metering CB(Utility)
0.7s
0.4s
1.0s
0.1s
??s
??s
??s
1.0s
1.0s
(2)Compromised
Grading
0.7s
0.7s
0.4s
0.4s
0.1s
(1)First
Attempt
Bl ki S h P i i l (2)
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
46/65
> Non-Directional Overcurrent and Earth Fault Protection46 Manufacturers Technical Update Oct 2010 -
Blocking Schemes - Principles (2)
Incomer
IF2
IF
Blocking schemes eliminates grading time and will trip the CB after 100ms has elapsed, schemewill remove blocking signal should the CB fail to trip
Ideal application for GOOSE messaging over IEC61850
BLOCK for IF1
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
47/65
> Non-Directional Overcurrent and Earth Fault Protection47 Manufacturers Technical Update Oct 2010 -
IEC61850 Architecture
Agile with
IEC61850
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
48/65
> Non-Directional Overcurrent and Earth Fault Protection48
Delta/Star Trans fo rmers
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
49/65
> Non-Directional Overcurrent and Earth Fault Protection49
Trans former Protection - 2-1-1 Fault Current
A phase-phase fault
on one side of
transformer produces
2-1-1 distribution on
other side
Use an overcurrent
element in each
phase (cover the 2x
phase)
2
& EF relays canbe used provided
fault current > 4x
setting
Iline
0.866If3
Turns Ratio=3 :1
Idelta
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
50/65
> Non-Directional Overcurrent and Earth Fault Protection50
Trans former Protection - 2-1-1 Fault Current
Istar= E-/2Xt = 3 E-n/2Xt
Istar= 0.866 E
-n/Xt
Istar= 0.866 If3
Idelta= Istar/3 = If3/2
Iline= If3
Iline
0.866 If3
TurnsRatio =3 :1
Idelta
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
51/65
> Non-Directional Overcurrent and Earth Fault Protection51
Trans former Protection - 2-1-1 Fault Current
Grade HV relaywith respect to
2-1-1 for -
fault
Not only at max
fault level
51
HV
/51
LV
If386.6%If3
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
52/65
> Non-Directional Overcurrent and Earth Fault Protection52
Use of High Sets
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
53/65
> Non-Directional Overcurrent and Earth Fault Protection53
Ins tantaneous Protect ion
Fast clearance of faults
ensure good operation factor, If>> Is (5 x ?)
Current setting must be co-ordinated to prevent
overtripping
Used to provide fast tripping on HV side of transformers
Used on feeders with Auto Reclose, prevents transient
faults becoming permanent
AR ensures healthy feeders are re-energised
Consider operation due to DC offset - transient overreach
Overcur rent Protect ion
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
54/65
> Non-Directional Overcurrent and Earth Fault Protection54
Ins tantaneous OC on Trans form er Feeders
Set HV inst 130% IfLV
Stable for inrush
No operation for LV fault
Fast operation for HV fault
Reduces op times
required of upstream
relays
CURRENT
HV2 LVHV1
HV2
LVTIME HV1
IF(LV) IF(HV)
1.3IF(LV)
Overcu rrent Protect ion:
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
55/65
> Non-Directional Overcurrent and Earth Fault Protection55
Trans ient Overreach
Ability to ignore DC offset
Low overreach allows los Inst setting to be used
high operation factor
Immunity to LV transformer faults
Overcu rrent Protect ion:
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
56/65
> Non-Directional Overcurrent and Earth Fault Protection56
Trans ient Overreach
Overreach = (I1I2)/I2
Typical values
numerical relay = < 5%
Simple EM relay = >60%
Low overreach allows low
settinghigh operationfactor
High transient overreach
necessitates high settings
poor sensitivity, slow
I1
I1 = steady state rms pickup I2 = rms pickup with fully offset signal
I
2
Overcu rrent Protect ion:
ff
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
57/65
> Non-Directional Overcurrent and Earth Fault Protection57
Part ial Differential Protect ion
Zoned busbarprotection usingovercurrent relays
Bus section relay notrequiredreducedgrading stages
Time delayed trippingfor busbar fault
67
51
67
51
51
51
Overcu rrent Protect ion:
I t l k d OC P t t i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
58/65
> Non-Directional Overcurrent and Earth Fault Protection58
Inter locked OC Protect ion
Problem due to location ofCTs
Feeder circuit fault seenoutside feeder zone butinside busbar zone
Fault remains fed fromremote end will be cleared byremote time delayedprotection
Speed up fault clearance withlocal Interlocked OC relayshort time delay enabled by
BB protection trip
Circuit
Protection
Busbar
Protection
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
59/65
> Non-Directional Overcurrent and Earth Fault Protection59
Earth fau l t Protect ion
Overcur rent Protect ion
E th F lt P t t i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
60/65
> Non-Directional Overcurrent and Earth Fault Protection60
Earth Fault Protect ion
Earth fault current may be limited
Sensitivity and speed requirements may not be met by
overcurrent relays
Use dedicated EF protection relays
Connect to measure residual (zero sequence) current
Can be set to values less than full load current
Co-ordinate as for OC elements
May not be possible to provide co-ordination with fuses
Overcur rent Protect ion
E th F lt R l C t i 3 Wi S t
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
61/65
> Non-Directional Overcurrent and Earth Fault Protection61
Earth Fault Relay Connect ion - 3 Wire System
Combined with OC relays Economise using 2x OC
relays
E/F OC OC OC E/F OC OC
Overcur rent Protect ionE th F lt R l C t i 4 Wi S t
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
62/65
> Non-Directional Overcurrent and Earth Fault Protection62
Earth Fault Relay Connect ion - 4 Wire System
EF relay setting must begreater than normal
neutral current
Independent of neutralcurrent but must use 3 OC
relays for phase to neutral
faults
E/F OC OC OC E/F OC OC OC
Overcur rent Protect ionE th F lt R l C t S tt i
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
63/65
> Non-Directional Overcurrent and Earth Fault Protection63
Earth Fault Relays Cur rent Sett ing
Solid earth
30% Ifull loadadequate
Resistance earth
setting w.r.t earth fault level
special considerations for
impedance earthing -
directional?
Overcur rent Protect ionSens it i e Earth Fa lt Rela s
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
64/65
> Non-Directional Overcurrent and Earth Fault Protection64
Sens it ive Earth Fau lt Relays
Settings down to
0.2% possible
Isolated/high
impedance earth networks
For low settings cannot use residual connection, use
dedicated CT
Advisable to use core balance CT
CT ratio related to earth fault current not line current
Relays tuned to system frequency to reject 3rd harmonic
B
C
E/F
A
Overcur rent Protect ionCore Balance CT Connect ions
7/26/2019 Non-Dir. Overcurrent APPS ALSTOM
65/65
Core Balance CT Connect ions
Need to take care with core
balance CT and armoured
cables
Sheath acts as earth returnpath
Must account for earth
current path in connections
- insulate cable gland
NO OPERATION OPERATION
CABLE
BOX
CABLE GLAND
CABLE GLAND/SHEATHEARTH CONNECTION
E/F
INSULATION