Our energy at your service
GENERATION & NETWORKFeeder Protection IED
NPF915
• Doublebusbarcontrol
• Directionalandvoltageprotection
• Cableenddifferentialprotection
• Low-impedanceREFprotection
• Harmonicsprotectionandcontrol
• 5-shotschemecontrolledautorecloser
• EnergyandPowermeasurementaccuracybetterthanClass1S
The optimal management of electrical power systems is based inparticular on the reliability, availability and communication skills ofprotection,measurementandautomationdevices.
TheNPF915offersamodularfeederprotectionandcontrolsolutionforapplicationsrequiringbothcurrentandvoltagebasedprotectionsalongwithcompletemeasurements.Optionalcards(I/O,communication...)are available for more comprehensive monitoring and controlapplications.
TheNPF915communicatesusingvariousprotocolsincludingIEC61850substationcommunicationstandard.
ANSI CODES
A924B
CHARACTERISTICSProtection functions
• Three-phaseovercurrent,4stagesINST,DTorIDMT[50/51]
• Earth-fault(sensitive),4stagesINST,DTorIDMT[50N/51N(S)]
• Directionalovercurrent,4stagesINST,DTorIDMT[67]• Directionalearth-fault,4stagesINST,DTorIDMT[67N]• Harmonicovercurrent,4stagesINST,DTorIDMT[50H/51H/68H]
• Currentunbalance,4stagesINST,DTorIDMT[46/46R/46L]
• Lowimpedancerestrictedearthfault/cableenddifferential[87N]
• Cablethermalprotection[49L]• Overvoltage,4stagesINST,DTorIDMT[59]• Undervoltage,4stagesINST,DTorIDMT[27]• Zerosequenceovervoltage,4stagesINST,DTorIDMT[59N]
• Positivesequenceunder/overvoltage,negativesequenceovervoltage,4stagesINST,DTorIDMT[59P/27P/47]
• Over/underfrequency,8stagesINSTorDT[81O/81U]• Rateofchangeoffrequency,8stagesINSTorDTorIDMT[81R]
• Vectorjump[78]• Over/Under/Reversepower[32/37/32R]• Breakerfailureprotection[50BF/52BF]• Arcprotection(option)[50ARC]
Measuring and monitoring• Phaseandresidualcurrents(IL1,IL2,IL3,I01,I02)• Voltagemeasurements(UL1-UL3,U12-U31,U0,SS)• Faultlocator[21FL]• Currentandvoltageharmonics(upto31st)• CurrentTHD• Frequency(f)• Power(P,Q,S,pf)• Energy(E+,E-,Eq+,Eq-)• Circuitbreakerwear(CBW)• Disturbancerecorder(3.2kHz)• Currenttransformersupervision(CTS)• Fusefailure(VTS)• Tripcircuitsupervision[74TC]
Control• Controllableobjects:5• Synchrocheck[25]• Autorecloser[79]• Cold-loadpick-upblock[68]• Switchontofaultlogic• 8settinggroups
Hardware• Currentinputs:5• Voltageinputs:4• Digitalinputs:3(standard)• Outputrelays:5+1(standard)
Options (3 slots)• Digitalinputsoptional:+8percard• Digitaloutputsoptional:+5percard(2cardsmax.)• Arcprotection(12sensors+2xHSO+BI)• 2xmAinput+6-8xRTDinput(2cardsmax.)• Communicationmedia(specifiedbelow)
Event recording• Non-volatiledisturbancerecords:100• Non-volatileeventrecords:10000
Communication media• RJ45Ethernet100Mb(frontstandard)• DoubleLCEthernet100Mb(option)• RS232+serialfibrePP/PG/GP/GG(option)
Communication protocols standard• IEC61850• IEC60870-5-103/101/104• ModbusRTU,ModbusTCP/IP• DNP3.0,DNP3.0overTCP/IP• SPA
Case• H,W,Dwithoutterminal177x127x174mm• H,W,Dwithterminal177x127x189mm(casingheight4U,width¼rack,depth210mm)
• H,Woffrontplate177x127mm• H,Wofcutout160x106mm
SMART9 - integrated softwareOur user friendly SMART9 (Setting, Measurement,Analysis,Recording,Time-saving)configurationsoftwarehelpstheusergetthebestfromNP900seriesrelays.