Upload
duongngoc
View
217
Download
1
Embed Size (px)
Citation preview
D.H.C. Toe is senior lecturer in the Faculty of Built Environment, Universiti Teknologi Malaysia, Skudai, Malaysia. S. Sugiyama and S.
Yasufuku are graduate students in the Graduate School for International Development and Cooperation, Hiroshima University,
Hiroshima, Japan. T. Kubota is associate professor in the Graduate School for International Development and Cooperation, Hiroshima University, Hiroshima, Japan.
Numerical Simulation of Passive Cooling
Strategies for Urban Terraced Houses in
Hot-Humid Climate of Malaysia
Doris Hooi Chyee Toe, Dr.Eng. Susumu Sugiyama Satoshi Yasufuku
Universiti Teknologi Malaysia Hiroshima University Hiroshima University
Tetsu Kubota, Dr.Eng.
Hiroshima University
ABSTRACT
The objective of this study was to determine energy-saving modifications through passive cooling to
urban terraced houses in Malaysia. Effects of two strategies, i.e. complete natural ventilation (NV)
strategy and partial air conditioning (AC) strategy, were simulated using TRNSYS and COMIS. The
complete NV strategy relied fully on naturally ventilated condition in the whole house for achieving
thermal comfort in the master bedroom while the partial AC strategy was aimed at reducing the cooling
load in the air-conditioned master bedroom by applying passive cooling techniques to the whole house.
The results revealed that indoor thermal comfort was achieved in complete NV strategy by applying
multiple passive cooling techniques that prevent external heat on the outer building envelope and night
ventilation, even under heated urban climatic conditions. In partial AC strategy reductions of about 39%
to 56% in the sensible cooling load compared to the current scenario were obtained by using several
techniques including night ventilating other spaces and insulating inner surfaces of the master bedroom.
INTRODUCTION
Energy savings are important in the global building sector due to concerns about energy security
and effects of global warming. In hot developing regions such as Southeast Asia, cooling demand in
residential buildings is a major concern since it is predicted to rise sharply in the coming decades in line
with rapid urbanization and population and economic growth (Liu et al., 2010; Sivak, 2009). It can be
seen widely in the region that brick-walled buildings are becoming a common construction for urban
houses in recent years. In Malaysia, a nationwide census in 2010 showed that 85% of the existing urban
houses used brick and another 5% used brick and plank for their outer walls (Department of Statistics
Malaysia, 2012). Unlike traditional lightweight constructions, the high thermal mass building envelope
of brick houses might be difficult to be cooled in the hot-humid climate. It has been reported in 2009 that
space cooling in brick houses accounted for 29% of the annual household energy consumption on
average in the city of Johor Bahru, Malaysia (Kubota et al., 2011). It is thus crucial to apply passive
cooling strategies wherever possible to these urban houses for energy-saving.
Passive cooling encompasses techniques for solar and heat control, heat modulation and heat
30th INTERNATIONAL PLEA CONFERENCE16-18 December 2014, CEPT University, Ahmedabad
1
dissipation using naturally driven phenomena such as natural ventilation, radiative cooling, evaporative
cooling and ground cooling (Santamouris and Kolokotsa, 2013). Passive cooling techniques have been
studied in various climatic regions. However, few comprehensive studies were made outside moderate
and hot-dry climates, including field monitoring and numerical modeling exercises with regard to
existing Malaysian houses (Kubota et al., 2009; Mohd Isa et al., 2010; Sadafi et al., 2011). Some of the
main climatic factors negatively affecting the efficiency of the different cooling approaches are high
night ambient temperature, cloud cover, high humidity and insufficient wind speeds (Dimoudi, 1996).
These conditions are usually prevalent in hot-humid climate. Due to dependency on climatic conditions,
further local studies are required to predict effects of a passive cooling system before implementation.
The objective of this study is to determine energy-saving modifications through passive cooling to
Malaysian urban houses. The target houses are terraced houses, which formed majority (42% as of 2010)
of the existing urban housing stock (Department of Statistics Malaysia, 2012). This study analyses the
effects of two passive cooling strategies, i.e. complete natural ventilation (NV) strategy and partial air
conditioning (AC) strategy, on thermal comfort and cooling load, respectively, through numerical
simulation using TRNSYS and COMIS programs.
METHODS
Description and Modeling of the Case Study Terraced House
One of the case study terraced houses from a previous field experiment (Kubota et al., 2009) was
modeled in this simulation study. The selected terraced house represents typical modern terraced houses
in terms of spatial design and building structures (Toe, 2013). The house measures 6.7 m by 13.1 m with
a total floor area of 155 m2, which is an average sized double-storey terraced house (Figure 1). Floor-to-
ceiling height of rooms is 3.05 m. The total nett air volume of the whole house is 538 m3; that of the
master bedroom is 65 m3. The building was oriented towards northwest, which means that the external
façade of the master bedroom faces northwest. It was constructed of brick and concrete and had single
glazing windows. The entire house was not insulated. Description of the constructional layers of the
terraced house and their reference U-values in the computer model is given in Table 1.
The whole house was modeled as TRNSYS Type 56 ‘Multi-zone Building’ in three dimensions
using the TRNSYS 3D plug-in in Google SketchUp interface (Klein et al., 2012). The building model
comprised 17 thermal zones with corresponding air flow zones in COMIS to represent each partitioned
room or functional space including attic spaces. All protruding elements on the building facades and
immediate surrounding objects, i.e. neighbouring houses, that might shade the studied house were also
modeled in three dimensions. A time base of 1 h was set for the transfer function to represent the thermal
Figure 1 (a) Exterior view and (b) floor plans of the case study terraced house.
(a) (b)
Ground floor
First floor
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
2
mass behavior of the brick walls. The party walls on both sides of the house were modeled as boundary
walls with identical zone temperatures assumed on both sides of the walls. Meanwhile, the boundary
condition for the ground floor was the constant soil temperature assumed to be the average air
temperature at the site over the whole simulation period. Thermal properties of building materials and
parameter/input values for air flows were obtained from Malaysian manufacturers or reference data to
correspond with the local construction (Toe, 2013). Wind pressure coefficients were estimated using a
parametrical model developed by Grosso (1992) known as CPCALC+. Coupling between the TRNSYS
and COMIS models were implemented via Type 157 in TRNSYS so that air flow rates per zone and
zone air temperatures were iterated in each time step until the mass and energy balance per zone reached
convergence.
Model Validation
Empirical validation of the terraced house model was performed using the above-mentioned field
experiment data from June-August 2007 (Kubota et al., 2009). This study focuses on the results in the
master bedroom because existing households used air conditioners mainly in master bedrooms (Kubota
et al., 2009); the study interest is to reduce this cooling energy. Figure 2 shows temporal variations of the
simulation results compared to the measurement data at 1.5 m height above floor in the master bedroom.
Two ventilation conditions, i.e. night ventilation and daytime ventilation, are shown. Overall, the
Table 1. Constructional Layers and Reference U-values of the Terraced House Model.
Building Element Constructional Layers Reference
U-valuea
(W/m2K)
External and internal
walls
20 mm thick cement plaster + 100 mm thick clay brick + 20 mm
thick cement plaster
2.75
Party wall 20 mm thick cement plaster + 200 mm thick clay brick + 20 mm
thick cement plaster
2.07
Ground floor 8 mm thick ceramic tile + 22 mm thick cement screed + 100 mm
thick concrete slab + soil layer
3.75b
First floor (family and
bedroom zones)
15 mm thick timber flooring + 15 mm thick cement screed +
100 mm thick concrete slab + 20 mm thick cement plaster
2.81
First floor (bath
zones)
8 mm thick ceramic tile + 22 mm thick cement screed + 100 mm
thick concrete slab + 20 mm thick cement plaster
3.29
Ceiling (master
bedroom)
6 mm thick ceiling board 4.55
Ceiling (other zones) 3.2 mm thick ceiling board 5.54
Pitched roof 20 mm thick concrete roof tile + 25 mm thick timber batten +
aluminium foil
2.67
Flat roof 22 mm thick cement screed + 100 mm thick concrete slab + 20
mm thick cement plaster
3.37
Window 6 mm thick single layer float glass 5.61 a Includes convective and radiative heat transfer coefficients of 7.7 W/m
2K for inside surface and 25
W/m2K for outside surface.
b Excludes soil layer.
Figure 2 Temporal variations of the simulation and measurement data in the master bedroom in (a)
night ventilation and (b) daytime ventilation conditions.
222426283032343638
Air
Te
mp
. (°C
)
24262830323436
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
Op
era
tiv
e
Te
mp
. (°C
)
13/7 14/7 15/7 16/7 17/7 18/7
Date / Time
Measurement
SimulationOutdoor
Simulation
Measurement
222426283032343638
Air
Te
mp
. (°C
)
24262830323436
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
0:0
0
Op
era
tiv
e
Te
mp
. (°C
)
13/7 14/7 15/7 16/7 17/7 18/7
Date / Time
Measurement
SimulationOutdoor
Simulation
Measurement
(a) (b)
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
3
validation results are satisfactory in terms of air and operative temperatures with root mean square errors
(RMSE) of 0.31-0.55 °C and coefficients of determination (R2) of 0.89-0.96.
Simulation Test Cases and Weather Conditions
Table 2 summarizes the simulation test cases of this study. The techniques were selected by
considering their practicality to be applied to existing terraced houses through relatively simple building
modification and/or behavioural adjustment. In particular, night ventilation is considered a potential
passive cooling technique for brick houses while daytime ventilation emulates the window opening
behavior of the majority of existing households (Kubota et al., 2009). The complete NV strategy relies
fully on naturally ventilated condition in the whole house for achieving thermal comfort in the master
bedroom. Meanwhile, the partial AC strategy attempts to reduce the cooling load in the master bedroom
by applying passive cooling techniques to the whole house. It was assumed that air conditioning was
used only in the master bedroom for nine hours per day (21:00-6:00) with a set temperature of 23 °C.
This study deals with the sensible cooling load only. Internal heat gains from occupants (4 persons;
seated at rest), lighting (5 W/m2) and common household appliances were considered in all simulations.
It is noted that infiltration rates in the master bedroom average 0.1 ACH when no ventilation was applied
for both complete NV and partial AC strategies.
Weather conditions for the simulation were taken from an actual weather data set measured at the
centre of a heat island in Johor Bahru, Malaysia to represent urban climate of typical terraced housing
neighbourhoods (Kubota and Ossen, 2011). The geographical location is 1°29’19” N and 103°45’41” E
at an elevation of 26 m above sea level. A wind velocity profile exponent of 0.25 was used to represent
the urban location (Counihan, 1975). The simulation time step was set to coincide with the weather data
at 10-minute intervals. The simulation was run using the above weather file for two whole months, i.e.
January-February 2010. Subsequently, simulation results for a 10-day period of continuous typical fair
weather days are analysed in this study. As shown in Figure 3, outdoor air temperature ranges from 25-
36 °C while outdoor relative humidity ranges from 50-90% over the period. The analysis period begins
several days after the simulation start time, thus allowing the model to acquire sufficient thermal history.
Output files were generated and post-processed in Excel spreadsheets after the simulation.
Table 2. Simulation Test Cases.
Technique Test Conditions
Natural ventilation (open
window period)
Night ventilation (20:00-8:00); daytime ventilation (8:00-20:00); no
ventilation (0 h); full-day ventilation (24 h)
Forced ventilation 10 ACH or 30 ACH night (20:00-8:00) in master bedroom
Attic ventilation 10 ACH night (20:00-8:00) or 30 ACH full-day (24 h) in attic
Thermal insulation Roof; ceiling; external wall – outside surface; external wall – inside
surface; internal wall; party wall; floor (R-value: 4 m2K/W)
Window shading External shading; internal shading (Shading factor, SF: 0.75)
High reflectivity roof coating Solar reflectance: 0.8, longwave emissivity: 0.9
Window glazing Low-E glass (U-value: 2.54 W/m2K, G-value: 0.44) or heat barrier
film (U-value: 5.73 W/m2K, G-value: 0.48)
Figure 3 Temporal variations of weather data for the simulation analysis period.
0
400
800
1200
528 552 576 600 624 648 672 696 720 744 768
24
26
28
30
32
34
36
Air
Te
mp
. (°
C)
So
lar
Ra
d.
(W/m
²)
Rain period
Date / Time (Hour of the Year)
23/1 24/1 25/1 26/1 27/1 28/1 29/1 30/1 31/1 1/2
50
60
70
80
90
100
RH
(%
)
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
4
RESULTS AND DISCUSSION
Complete Natural Ventilation Strategy
Figure 4 presents the simulated indoor air temperatures in the master bedroom for the four natural
ventilation conditions that represent night ventilation, daytime ventilation, no ventilation and full-day
ventilation. It is noted that temporal variations of indoor temperatures in each simulation have similar
patterns over the 10-day analysis period. Thus, results are shown in statistical summaries for the whole
period. As expected, night ventilation provides the lowest indoor air temperatures among the tested open
window conditions (Figure 4). This is due to the nocturnal ventilative cooling through open windows
and thermal mass effect of the cooled building structures that lowers the night-time and peak indoor
temperatures of the following day. Daily maximum (95th percentile) and minimum (5
th percentile) indoor
air temperatures in night ventilated condition are 1.7 °C and 1.3 °C lower than those of daytime
ventilation, respectively. Nevertheless, the daily minimum air temperature in the night ventiled room is
still 2.7 °C higher than the outdoors.
Further passive cooling techniques are applied consecutively as shown in Figure 5 in addition to
night ventilation and daytime ventilation, respectively. The most effective technique in reducing the
daily maximum air temperature in night ventilated condition is roof insulation; the said temperature is
decreased by 0.9 °C compared to applying night ventilation only (Figure 5a). Most of the solar heat gain
in the master bedroom, which is on the first floor, probably comes through the roof due to its relatively
large surface area and high noon solar altitude at the location. With less heat gain during the day and a
cooler adjacent attic space for the whole day, the building structures maintain cooler and serve to reduce
the minimum air temperature as well. Techniques that reduce solar radiation through roof into the
building would be important. In fact, high reflectivity roof coating reduces the mean indoor air
temperature most among all of the techniques in Figure 5a, i.e. by 0.6 °C. The high reflectivity coating
probably improves nocturnal cooling additionally by virtue of the less heated roof surface on exposure to
the sun and absence of thermal insulation at night. Nevertheless, all of the solar control techniques are
Figure 4 Statistical summary (5
th and 95
th percentiles, mean and ± one standard deviation) of simulated
indoor air temperatures in different natural ventilation conditions for complete NV strategy.
Figure 5 Statistical summary (5
th and 95
th percentiles, mean and ± one standard deviation) of simulated
indoor air temperatures in (a) night ventilated and (b) daytime ventilated conditions with respective passive cooling techniques for complete NV strategy.
25 26 27 28 29 30 31 32 33 34 35
Outdoor
Night ventilation
Daytime ventilation
No ventilation
Full-day ventilation
Air Temperature ( C)
27 28 29 30 31 32
Night ventilation
Roof insulation
High reflectivity roof coating
Ceiling insulation
External shading
Low-E glass
Internal shading
External wall-outside insulation
External wall-inside insulation
Forced ventilation (10 ACH night)
Attic ventilation (10 ACH night)
Air Temperature ( C)
27 28 29 30 31 32 33 34
Daytime ventilation
Roof insulation
High reflectivity roof coating
Ceiling insulation
External shading
Low-E glass
Internal shading
External wall-outside insulation
External wall-inside insulation
Forced ventilation (10 ACH night)
Attic ventilation (10 ACH night)
Air Temperature ( C)
(a) (b)
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
5
less effective in daytime ventilated condition compared to night ventilated condition (Figure 5b). The
inflow of hot outdoor air through open windows during daytime increases the indoor air temperature and
diminishes their cooling effects. On the other hand, forced ventilation with an air change rate of 10 ACH
in the room at night lowers the daily minimum air temperatures most, i.e. by 0.6 °C and 1.4 °C in night
ventilated and daytime ventilated conditions, respectively.
Figure 6a shows the simulated indoor operative temperatures for combinations of the most effective
technique for each of the building elements. The techniques are applied accumulatively and step-by-step
from more effective ones to less effective ones in night ventilated condition. The results are evaluated
for thermal comfort using an adaptive comfort equation (ACE) for naturally ventilated buildings in hot-
humid climates (Toe and Kubota, 2013). The 80% comfortable upper limits predicted using daily mean
outdoor air temperatures of the analysis period average 29.6 °C. Figure 6a indicates that the daily
maximum indoor operative temperature is reduced by 2.2 °C and meets the 80% comfortable upper limit
when roof and external wall-outside surface insulation (R-value 4 m2K/W), and external window
shading (shading factor 0.75) are applied in addition to night ventilation under the heated urban climatic
conditions. Alternatively, the comfort limit is also met by substituting the roof insulation with high
reflectivity roof coating, though daily maximum temperature is higher in the latter. It is implied that
introducing these four techniques to existing urban terraced houses may satisfy indoor thermal comfort
in naturally ventilated condition on fair weather days (Figure 6b).
Partial Air Conditioning Strategy
Figure 7 shows the simulated sensible cooling loads in the air-conditioned master bedroom by
considering different natural ventilation conditions for the master bedroom and other zones. The cooling
load is 50.2 MJ/day when daytime ventilation is applied to the whole house (Case 1), which represents
the current behaviour of most households. By applying night ventilation to the whole house except the
master bedroom, the cooling load is reduced by about 5% even when the master bedroom is daytime
ventilated (Case 5). Building structures that are cooled at night keep adjacent indoor temperature low
and reduce the cooling load indirectly. The highest reduction in cooling load, i.e. 8%, is seen when the
master bedroom receives no natural ventilation and other zones are night ventilated (Case 6).
Further passive cooling techniques are applied consecutively as shown in Figure 8 in addition to the
ventilation conditions of Cases 1 and 6, respectively. For Case 1 the most effective technique in lowering
Figure 6 (a) Thermal comfort evaluation and (b) conceptual illustration of combined passive cooling techniques for complete NV strategy.
Figure 7 Simulated sensible cooling loads in different natural ventilation conditions for partial AC
strategy.
27 28 29 30 31 32
Night ventilation
+ Roof insulation
+ External shading
+ External wall-outside insulation
+ Low-E glass
+ High reflectivity roof coating
+ Forced ventilation (10 ACH)
+ Attic ventilation (10 ACH)
+ Internal shading
Operative Temperature ( C)
ACE 80% comfortable upper limit
0 10 20 30 40 50 60
1
2
3
4
5
6
Cooling Load (MJ/day)
Master bedroom Other zones
Daytime ventilation Daytime ventilation
Daytime ventilation No ventilation
No ventilation No ventilation
No ventilation Daytime ventilation
Daytime ventilation Night ventilation
No ventilation Night ventilation
Case
External shading
Roof insulation
External wall-outside
insulation
Master bedroom
Night ventilation
Night ventilation
(a) (b)
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
6
the cooling load is floor insulation; the reduction is about 8% compared to the current condition (Figure
8a). Applying high reflectivity roof coating and roof or ceiling insulation give reductions of 6% and 5%
each, respectively. For Case 6 ceiling insulation decreases the cooling load most by about 7%, followed
by roof insulation and high reflectivity roof coating (Figure 8b). Besides, wall insulation is more
effective on internal wall, followed by external wall-inside surface. Overall, all of the passive cooling
techniques except floor insulation, party wall insulation and attic ventilation give greater reductions in
the cooling load in Case 6 compared to Case 1, likely due to exclusion of hot outdoor air in closed
window conditions during daytime.
Figure 9a presents the simulated sensible cooling loads for combinations of the most effective
techniques in the ventilation condition of Case 6. As before, the techniques are applied accumulatively in
step-by-step basis. Compared to the current condition (Case 1), the cooling load of the master bedroom
is reduced by about 39% to 30.9 MJ/day when the ceiling, internal wall, external wall-inside surface and
floor are insulated (R-value 4 m2K/W) for Case 6 (Figure 9). The cooling load is lowered by 56% to 21.9
MJ/day when all of the techniques are used simultaneously, although the further reductions by high
reflectivity roof coating, party wall insulation and internal shading are only about 3% or less each.
It is implied from the above simulation results that changing from daytime ventilation to night
ventilation is fundamental to gain better effectiveness of other passive cooling techniques for both
complete NV and partial AC strategies. Due to the intense solar heat gain through the roof, roof
insulation for complete NV strategy and ceiling insulation for partial AC strategy provide the greatest
cooling effects. In particular, for complete NV strategy techniques that prevent external heat on the outer
building envelope are relatively effective to keep the indoors cool (Figure 6b). On the other hand, for
partial AC strategy insulating the inner surfaces is relatively effective to reduce the cooling load (Figure
9b). Since the master bedroom is air-conditioned in this strategy, these techniques aid to prevent the
mechanically cooled indoor air from being transferred outward.
Figure 8 Simulated sensible cooling loads in ventilation conditions of (a) Case 1 and (b) Case 6 with
respective passive cooling techniques for partial AC strategy.
Figure 9 (a) Simulated sensible cooling loads and (b) conceptual illustration of combined passive
cooling techniques for partial AC strategy.
0 10 20 30 40 50 60
Daytime ventilation (all zones)
High reflectivity roof coating
Roof insulation
Ceiling insulation
Attic ventilation (30 ACH full-day)
Floor insulation
Internal wall insulation
External wall-inside insulation
Party wall insulation
External wall-outside insulation
External shading
Heat barrier film
Internal shading
Cooling Load (MJ/day)
0 10 20 30 40 50 60
+ Night ventilation (other zones)
Ceiling insulation
Roof insulation
High reflectivity roof coating
Attic ventilation (30 ACH full-day)
Internal wall insulation
External wall-inside insulation
External wall-outside insulation
Floor insulation
Party wall insulation
External shading
Low-E glass
Internal shading
Cooling Load (MJ/day)
No ventilation (master bedroom)(a) (b)
0 10 20 30 40 50 60
Daytime ventilation (all zones)
+ Ceiling insulation
+ Internal wall insulation
+ External wall-inside insulation
+ Floor insulation
+ Low-E glass
+ External shading
+ High reflectivity roof coating
+ Party wall insulation
+ Internal shading
Cooling Load (MJ/day)
No ventilation (master bedroom) + Night ventilation (other zones)
Case 1
Case 6
Internal wall insulation
Ceiling insulation
External wall-inside insulation
Floor insulation
Night ventilation
AC
Master bedroom
(a) (b) Case 6 No ventilation (master bedroom)
+ Night ventilation (other zones)
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
7
CONCLUSIONS
The simulation results of a typical Malaysian terraced house reveal that indoor thermal comfort
may be achieved in naturally ventilated condition by applying multiple passive cooling techniques that
prevent external heat on the outer building envelope and night ventilation, even under heated urban
climatic conditions. When air conditioning is used in the master bedroom, reductions of about 39% to
56% in the sensible cooling load compared to the current scenario can be reached by using several
techniques including night ventilating other spaces and insulating inner surfaces of the master bedroom.
Further consideration of different building orientations, annual performance, cost-and-benefit
effectiveness, and effects on indoor humidity as well as latent cooling load would be useful to realize
their practical implementation in the urban terraced houses. Such modifications are expected to
contribute largely to energy savings and carbon emission mitigation.
ACKNOWLEDGEMENTS
We gratefully acknowledge financial support from the Nichias Corporation, Ministry of Education
Malaysia and Universiti Teknologi Malaysia for Research University Grant Program 2014 (Vot
Q.J130000.2721.01K22), and The Hitachi Scholarship Foundation.
REFERENCES
Counihan, J. 1975. Adiabatic atmospheric boundary layers: a review and analysis of data from the period
1880-1972. Atmospheric Environment, 9: 871-905.
Department of Statistics Malaysia. 2012. Characteristics of Living Quarters. Population and Housing
Census of Malaysia 2010. Putrajaya: Department of Statistics Malaysia.
Dimoudi, A. 1996. Passive cooling of buildings. In: Santamouris, M., Asimakopoulos, D. (Eds.). Passive
Cooling of Buildings. London: James & James (Science Publishers) Ltd., pp. 35-55.
Grosso, M. 1992. Wind pressure distribution around buildings: a parametrical model. Energy and
Buildings, 18: 101-131.
Klein, S.A. et al. 2012. TRNSYS 17: A Transient System Simulation Program. Madison: Solar Energy
Laboratory, University of Wisconsin. <http://sel.me.wisc.edu/trnsys>.
Kubota, T., Toe, D.H.C., Ahmad, S. 2009. The effects of night ventilation technique on indoor thermal
environment for residential buildings in hot-humid climate of Malaysia. Energy and Buildings,
41(8): 829-839.
Kubota, T., Ossen, D.R. 2011. Analysis of climatic conditions affecting urban heat island intensity in
Johor Bahru, Malaysia. In: Summaries of Technical Papers of Annual Meeting, Architectural
Institute of Japan, 2011, August 23-25, Tokyo, Japan.
Kubota, T., Jeong, S., Toe, D.H.C., Ossen, D.R. 2011. Energy consumption and air-conditioning usage
in residential buildings of Malaysia. Journal of International Development and Cooperation, 17(3),
Special Issue: 61-69.
Liu, F., Meyer, A.S., Hogan, J.F. 2010. Mainstreaming Building Energy Efficiency Codes in Developing
Countries: Global Experiences and Lessons from Early Adopters. World Bank Working Paper No.
204. Washington, D.C.: The World Bank.
Mohd Isa, M.H., Zhao, X., Yoshino, H. 2010. Preliminary study of passive cooling strategy using a
combination of PCM and copper foam to increase thermal heat storage in building façade.
Sustainability, 2: 2365-2381.
Sadafi, N., Salleh, E., Lim, C.H., Jaafar, Z. 2011. Evaluating thermal effects of internal courtyard in a
tropical terrace house by computational simulation. Energy and Buildings, 43: 887-893.
Santamouris, M., Kolokotsa, D. 2013. Passive cooling dissipation techniques for buildings and other
structures: the state of the art. Energy and Buildings, 57: 74-94.
Sivak, M. 2009. Potential energy demand for cooling in the 50 largest metropolitan areas of the world:
implications for developing countries. Energy Policy, 37: 1382-1384.
Toe, D.H.C. 2013. Application of Passive Cooling Techniques to Improve Indoor Thermal Comfort of
Modern Urban Houses in Hot-Humid Climate of Malaysia. Doctoral Dissertation (unpublished).
Hiroshima University, Japan. Toe, D.H.C., Kubota, T. 2013. Development of an adaptive thermal comfort equation for naturally
ventilated buildings in hot-humid climates using ASHRAE RP-884 database. Frontiers of
Architectural Research, 2(3): 278-291.
30th INTERNATIONAL PLEA CONFERENCE 16-18 December 2014, CEPT University, Ahmedabad
8