    Option #1: DX SPLIT SYSTEM

  • 7/29/2019 Off Peak Cooling Chw

    3/15

    Simulation Assumptions

    Type of Occupancy : Church

    Operation time = 1354 hours/year (3.4 hours/day)

    Week End Days = Saturdays and Sundays Average Full Occupancy = 90%

    Week Days = Minimal time and office work only Average Occupancy = 15%

    Maximum no. of People = 60

    Lighting Load = 2 watts / sq. foot (21.5 watts/m2)

    Area = 280 square meters (W = 12m; L = 23.5 m), approx. Room Design temp. = 24 C

    Weather Data = Metro Manila

  • 7/29/2019 Off Peak Cooling Chw

    4/15

    Activity Areas Allocation

  • 7/29/2019 Off Peak Cooling Chw

    5/15

    Church Operation Schedule

  • 7/29/2019 Off Peak Cooling Chw

    6/15

    Results DX Split System

    Calculated Total Capacity = 15 TR (peak load)

    Split type qty. = 15 / 3 = 5 units of 3TR Split Units

    Space Cooling power consumptions = 12,600 kWH/yr

    Ventilation Fans = 240 kWH/yr

    Lightings = 9,820 kWH/yr

  • 7/29/2019 Off Peak Cooling Chw

    7/15

    DX Split Units Daytime Operation

    Lighting = 9,820 kWH/yr

    Space Cooling = 12,600 kWH/yr

    5 TR Maximum Size of each Split Unit

    Vent Fans = 240 kWH/yr

  • 7/29/2019 Off Peak Cooling Chw

    8/15

    DX SPLIT TYPE A/C

    OUTDOOR UNIT(S)

    INDOOR UNITS

    Control

    15 TR CAPACITY OPERATING DURING THE DAY

  • 7/29/2019 Off Peak Cooling Chw

    9/15

    Option #2 : CHILLED WATER SYSTEM

    Thermal Storage

  • 7/29/2019 Off Peak Cooling Chw

    10/15

    Assumptions

    Type of Occupancy : Church

    Operation time = 1354 hours/year (3.4 hours/day)

    Week End Days = Saturdays and Sundays Average Full Occupancy = 90%

    Week Days = Minimal time and office work only Average Occupancy = 15%

    Maximum no. of People = 60

    Lighting Load = 2 watts / sq. foot (21.5 watts/m2)

    Area = 280 square meters (W = 12m; L = 23.5 m), approx. Room Design temp. = 24 C

    Weather Data = Metro Manila

  • 7/29/2019 Off Peak Cooling Chw

    11/15

    Results

    Calculated Total Capacity = 15 TR (peak load)

    Selected Unit Capacity = 6 TR w/ storage tank(s)

    Packaged Unit 2-ckts = 1 Unit ducted

    Or Multi-Fan-coil Unit = 15 / 3 = 5 units free blow

    Space Cooling power consumptions = 11,360 kWH/yr

    Ventilation Fans = 240 kWH/yr

    Lightings = 9,820 kWH/yr

  • 7/29/2019 Off Peak Cooling Chw

    12/15

    CHILLED WATER DUCTED or FREE BLOWConstant Volume

    Lighting = 9,820 kWH/yr

    Space Cooling = 11,360 kWH/yr

    Vent Fans = 240 kWH/yr

  • 7/29/2019 Off Peak Cooling Chw

    13/15

    CHILLED WATER THERMAL STORAGE

    Outdoor Unit

    NIGHTIME OPERATION DAYTIME OPERATION

    6-TR CAPACITY TO OPERATE

    WHEN TANK CHARGING IS

    REQUIRED.

    Indoor Units

  • 7/29/2019 Off Peak Cooling Chw

    14/15

    Split Unit vs. Chilled Water Storage

    Conventional DX Split System Chilled Water Storage

    Cooling Capacity, TR 11 15 11 - 15

    Operation Time:

    Outdoor (ACCU) Daytime Night time (9PM-8AM)

    Indoor Unit (FCU) Daytime Daytime

    Cooling medium Refrigerant Chilled Water

    Approximate Annual power

    consumption, kWH

    12,600 11,360 (about

  • 7/29/2019 Off Peak Cooling Chw

    15/15

    Sample Calc Peak vs. Off-Peak RatesDX Split Type

    (Peak Rates)

    Chilled Water

    (Off Peak Rates)

    Chilled Water Peak

    Rates

    kWH/year

    Peak 12600 1640 10,360

    Off Peak 0 9720 0

    Cost/Year, Peso

    Peak = 12600 x 10

    = 126,000

    = 1640 x (6.3 + 1.01)

    = 11,988 + 342*

    = 12,331

    = 10,360 x 10

    = 103,600

    Off Peak 0 = 9720 x (3.09 + 1.01)

    = 39,852 + 343*

    = 40,195

    0

    Total = 126,000 = 52,526 = 103,600