Upload
hsiung-cheng-lin
View
216
Download
4
Embed Size (px)
Citation preview
On Line Internet-BasedMulti-Location PowerSystem Harmonics Analysisand Monitoring
HSIUNG CHENG LIN
Department of Automation Engineering, Chienkuo Technology University, No. 1, Chieh-Shou N. Road,
Changhua 500, Taiwan
Received 10 April 2007; accepted 4 July 2007
ABSTRACT: Traditional methods to measure power system harmonics employ the power
harmonic analyzer or a software package, such as Matlab or others, but they do have certain
limitations in the graphical programming environment, applications for remote monitoring
and control performance and for multi-point harmonic measurement. In this paper, a PC-based
virtual instrument (VI) based on Fast Fourier Transform (FFT) to implement a remote multi-
point power system harmonics analysis and monitoring using LabVIEW is proposed. The
nearby PC (Server) can collect real-time waveform data from different multi-locations and
transmit it to remote PCs (Clients) for on line harmonic analysis and monitoring via the
Internet. The history of Total Harmonic Distortion (THD) in the waveform signals from remote
locations can be also recorded and tracked in the data base. The strategies and guidelines
are also developed to enhance teaching and/or learning the basics of operating Internet-based
systems. Experimental results have testified its well performance and remote Web-based
capability. � 2009 Wiley Periodicals, Inc. Comput Appl Eng Educ 17: 241�252, 2009; Published online in
Wiley InterScience (www.interscience.wiley.com); DOI 10.1002/cae.20175
Keywords: FFT; TCP/IP; THD; VI; power system harmonics; Internet
INTRODUCTION
When the extensive use of power electronic devices is
added to an industrial distribution power system, it is an
important engineering practice to design a model of
harmonic measurement and analysis approach in power
systems [1�8]. Power system harmonics are caused by
transformers, motors, and rectifiers; they have been
detected as early as the 1920s and 1930s [9]. A system
can still function adequately in the presence of limited
amounts of harmonics, and in the past amounts injected
into systems were generally considered insignificant.
Today, however, increased industrial and consumer
dependence on equipment with non-linear components
is aggravating the situation. Harmonics in a power systemCorrespondence to H. C. Lin ([email protected]).
� 2009 Wiley Periodicals Inc.
241
can result in communication interference, transformer
over heating, or the malfunction of solid-state devices,
and so on [10�12]. Current harmonics induced by non-
linear power electronic loads also present inefficient
operations of local and global power supply systems.
Harmonic measurements in industrial power
systems are essential to achieve three objectives.
Firstly, for the identification of the sources and
characteristics (magnitude, frequency, and location)
of the harmonics. Secondly, for the design and
installation of a filtering system to reduce the harmonic
impacts to the power system. Thirdly, to ensure that
total harmonic distortion, after compensation, will be in
compliance with the regulatory requirements such as
IEEE Standard 519�1992 [13]. Currently, general
purpose power spectrum instruments introduce a wide
variety of possible measurements from the proper
modes chosen. Some special purpose power system
harmonic analyzers give fewer modes for measure-
ments. The above analyzers have, however, a complex
control circuit system, limited frequency domain
display, and high operating cost.
This study proposes an alternative technique to
measure line current harmonics using human graphical
interface as well as remote harmonic analysis and Web
viewing from different checking points. The proposed
system is constructed by LabVIEW package using Fast
Fourier Transform (FFT) and TCP/IP communication
techniques [14�21]. Hence, it can implement on line
remote operation of the power system harmonics
measurement and monitoring between distant locations
via the Internet. This paper is organized as follows.
Background of Power System Harmonics Section gives
a background of power system harmonics. Structure of
the System Hardware Section provides the proposed
system hardware structure. In Description of the System
Software Section, the system software for data acquisi-
tion, transmission and analysis using LabVIEW
are provided. Internet Connections Section presents the
illustration of Internet connections. Experimental
Results With TCP/IP and Web Connection Section
provided the experimental results with TCP/IP and Web
connections. Conclusions and recommendations for
further application are given in Conclusions Section.
BACKGROUND OF POWERSYSTEM HARMONICS
The research focused on the distorted source line
current is now getting more attention as harmonic
problems have caused increasing concerns in power
systems in recent years. Using Fourier series expan-
sion, the periodic and distorted (non-sinusoidal)
source current isðtÞ can be expressed as a series of
sinusoidal harmonics, therefore the response to
each harmonic can be determined by the following
equations.
isðtÞ ¼ Idc þX1
n¼1;2;3;:::
ðancos not þ bnsin notÞ ð1Þ
where
Idc ¼1
2p
Z2p
0
isðtÞdot; an
¼ 1
p
Z2
0
isðtÞsin notdot; bn ¼ 1
p
Z2p
0
isðtÞcosnotdot
Usually there is symmetry, so Idc¼ 0, and isðtÞcan be expressed as
isðtÞ ¼X1
n¼1;2;3;:::
ffiffiffi2
pisnsinðnot þ jnÞ ð2Þ
where
jn ¼ tan�1 an
bn
; isn ¼ 1ffiffiffi2
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffia2
n þ b2n
q
The r.m.s. value of source current is defined as
follows.
is ¼D
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1
2p
Z2p
0
isðtÞ½ 2dot
vuuut
¼
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1
2p
Z2p
0
X1n¼1;2;3;:::
ffiffiffi2
pisnsinðnot þ jnÞ
" #2
dot
vuuut
¼ffiffiffiffiffiffiffiffiffiffiffiffiffiX1n¼1
i2sn
s¼
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffii2s1 þ i2s2 þ i2s3 þ . . .
qð3Þ
ih ¼�
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffii2s2 þ i2
s3 þ i2s4 þ . . .
qð4Þ
which is the r.m.s. value of input harmonic current.
The total harmonic distortion (THD) factor is the
ratio of the r.m.s. value of all the harmonic
components together to the r.m.s. amplitude of the
fundamental component as following definition.
Mathematically,
THD¼Dffiffiffiffiffiffiffiffiffiffiffiffiffiffii2s � i2s1
pis1
¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiP1
n¼2 i2sn
pis1
¼ ih
is1
ð5Þ
242 LIN
The power factor (PF) of a load fed from an AC
supply is defined as
PF¼D mean power
vsisð6Þ
Normally, the supply phase voltage can be taken as
being sinusoidal, hence there will be no power
associated with the harmonic current as follows.
mean power ¼ vs1is1cosj ð7Þ
Therefore in the usual AC supply system where
the current is sinusoidal, the power factor is the cosine
of the angle between current and voltage. The
converter circuit, however, draws non-sinusoidal
current from the AC system, hence the power factor
can not be defined simply as the cosine of the
displacement angle.
For a sinusoidal voltage supply, substituting the
Equation (7) into the Equation (6) yields.
PF ¼ vs1is1cosjvsis
¼ is1
is
cosj ¼ is1 cosjffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffii2s1 þ i2
s2 þ i2s3 þ . . .
pð8Þ
where vs1 ¼ vs without source voltage distortion.
When the supply voltage is sinusoidal, which is
generally true, the above PF can be defined as the ratio
of the fundamental component of current and the
total value of the current, multiplied by cosj where
j is the phase-angle difference (displacement angle)
between the fundamental components of the voltage
and current. The ideal value of this power factor is
unity. However, the current which contains harmonic
components results in its overall r.m.s. value being
higher than the r.m.s. value of its fundamental
component, that is, PF<cosj gets lower in this
case. For instance, variable-speed drives constructed
with semiconductor switches inevitably introduce
harmonics into AC system. Accordingly, the power
factor will be always further degraded than the ideal
case when there are harmonic components existing in
the supply current because the controlled hardware
system has been loaded into power systems.
STRUCTURE OF THE SYSTEM HARDWARE
The system hardware is shown as Figure 1. It can
perform remote on line harmonic detection and
monitoring by certified clients (remote PCs) simulta-
neously. The Server is to collect the waveform data
acquired from the DAQ card (National Instrument
PCI-6014) via the Current Waveform probe. Upon the
receipt of data transmitted from the Server (nearby
PC) via TCP/IP, the Client A then carries out the
instant harmonics analysis. The Client B is authorized
to view the harmonic analysis results from the
Web Site, that is, Internet Explorer, immediately.
The control of VI panel can be transferred to the
Client B under the protection of Fire wall. There are
up to 16 channels available for receiving various
waveform data that may contain serious harmonics at
different locations (checking points). The number of
clients can be also extended as necessary.
The basic facilities or modules required for the
proposed system are as follows.
(1) Three PCs. One works as a Server for the
collection of current waveform data, and the
other two PCs are as the clients (A and B)
through TCP/IP and Web connection. Client A
is to perform the remote real-time harmonic
analysis, and Client B is to view its instant
analysis results obtained from Client A by the
Web Site.
(2) LabVIEW software package.
(3) One Data Acquire (DAQ) card (PCI-6014)
produced by National Instrument.
(4) Non-Linear Load (DC variable-speed motor or
other non-liner loads).
Figure 1 Structure of the proposed system hardware.
INTERNET-BASED POWER HARMONICS ANALYSIS 243
(5) Shunt (Current Waveform Sensing Probe).
(6) Amplifier (IC LM741).
DESCRIPTION OF THESYSTEM SOFTWARE
Besides the hardware system, the system software
using LabVIEW programming is needed to operate
the proposed system, described as follows.
Flowchart of the Server Programming
In the Server (nearby PC), it is to collect the waveform
data from the DAQ card, and then send the data to the
Client A for further signal processing. Figure 3 shows
its programming flowchart. The main programming
procedure is briefly described as follows.
(a) Initialize Analog Input (AI) Acquire Wave-
form.vi for acquiring waveform data from the
DAQ card. Detailed sub-vi is shown in Figure 2
and described as below.
(1) Device is assigned as 1 to the DAQ device
during configuration.
(2) Channel identifies the analog input channel
to measure. The input is set as channel
0�15.
(3) Number of samples is the number of
single-channel samples the VI acquires
before the acquisition completes. This
parameter is set as 1,000 samples.
(4) Sample rate is the requested number of
samples per second the VI acquires from
the specified channel. This parameter is set
as a rate of 1,000 samples/s. Note that the
sampling rate must be chosen higher than
the Nyquist sampling rate (twice the high-
est harmonic in the sampled data sequence)
[2]. For further information in the sampling
rate selection, please refer to the Refs.
[22�26].
(b) Activate the TCP/IP connection with Client A.
(c) Set the number of measured channels.
(d) Read waveform data from the assigned
channel of DAQ card.
(e) Display the current waveform signal in the
waveform chart.
(f) Send the waveform data to Client A via the
TCP/IP.
(g) Go back to step(d) until all checking points are
measured completely.
(h) Go back to step(c) until the TCP/IP is
disconnected (Fig. 3).
Flowchart of the Client A Programming
In Client A (remote PC), it receives the waveform data
from the Server, and analyze its harmonics instantly.
Its flowchart is shown in Figure 4.
The main programming procedure is briefly
described as follows.
(a) Initialize the TCP/IP connection with the
Server.
(b) Set the number (¼N) to read waveform data
from the Server.
(c) Read the waveform data transmitted from the
Server via the TCP/IP.
(d) Display the current waveform signal in the
waveform chart.
(e) Harmonic analysis using FFT.
(f) Go back to step(c) until every predefined
channel data is read completely. Note that the
number of the channel data (N) is the same as
the Server’s configuration.
(g) Display instant THD history and record it in
the data base.
(h) Go back to step(b) until the TCP/IP is
disconnected.
Flowchart of the Client B Programming
In Client B (remote PC), it views the harmonic
analysis results same as Client A by the Web Site
(Internet Explorer) simultaneously. Its flowchart is
shown in Figure 5.
Figure 2 AI Acquire Waveform.vi. [Color figure can be viewed in the online issue,
which is available at www.interscience. wiley.com.]
244 LIN
Figure 3 Flowchart of the Server programming. [Color
figure can be viewed in the online issue, which is available
at www.interscience.wiley.com.]
Figure 4 Flowchart of the Client A programming. [Color
figure can be viewed in the online issue, which is available
at www.interscience.wiley.com.]
INTERNET-BASED POWER HARMONICS ANALYSIS 245
The main programming procedure is briefly
described as follows.
(a) Publish the front panel of Client A to Web Site.
Details will be discussed in World Wide Web
Connection Between the Client A and Client B
Section.
(b) Check if the TCP/IP is authorized by Client A
until the TCP/IP is approved.
(c) View the front panel of the Client A via the
Internet Explorer.
(d) Go back to step(b) until the Web connection is
disconnected.
INTERNET CONNECTIONS
For simplicity, there are only three checking points
involved to demonstrate the proposed scheme in this
case. However, the number of checking points can be
easily extended up to sixteen as needed. Two kind
of Internet connections required in the system are
described as follows.
TCP/IP Connection Between the Serverand Client A
In the Server side, initially set Port Number to listen
for connection and set time out limit of 5 s. Send data
to the TCP port specified once a connection has been
detected. Numeric data is cast into string data and sent
via TCP Write. The first TCP Write sets the amount
of data to send and second TCP Write sends the
data. Error checking the loop will stop the loop if a
connection error occurs. Close connection once the
waveform data has been sent. Convert connection
errors to warnings and check for additional errors. The
program (Block Diagram) for TCP/IP connection is
shown in Figure 6.
In the Client A side, open connection with port
and IP address. Read the data at the port specified and
the data into a numeric representation. First TCP Read
acquires the size of the data and the second TCP
Read reads the data and passes it to the chart. Error
checking in the loop will stop the loop if a connection
error occurs. Close connection when the reading
procedure is done. Convert connection errors to
warnings and check for additional errors. The main
program for TCP/IP connection as well as waveform
spectrum using FFT is shown in Figure 7.
World Wide Web Connection Between theClient A and Client B
In Client A, LabVIEW front panel displays its
working status on line, as shown in Figure 8. Every
waveform and its spectrum can be viewed in the
graph, including the individual frequency and its
amplitude. The waveform THD (%) is also presented
immediately and recorded in the data file, that is,
a:\IO.txt. Once the THD (%) is over the predefined
limit, for example 25%, the warning LED will be
operated (on).
Figure 5 Flowchart of the Client B programming. [Color
figure can be viewed in the online issue, which is available
at www.interscience.wiley.com.]
246 LIN
Figure 6 TCP/IP connection program for Server. [Color figure can be viewed in the
online issue, which is available at www.interscience.wiley.com.]
Figure 7 TCP/IP connection program for Client A. [Color figure can be viewed in the
online issue, which is available at www.interscience.wiley.com.]
Figure 8 VI panel of the Client A. [Color figure can be viewed in the online issue, which
is available at www.interscience. wiley.com.]
The VI panel is published to World Wide Web
that can be viewed by Client B via Internet Explorer.
Figure 9 shows the Web Publishing Tool to display the
VI front panel. The document is then saved within
the web Server’s root directory. The URL should be
created to access this page from a browser, shown as
in Figure 10.
Note that m513-lin in the URL path (shown
in Fig. 10) should be replaced by the Server’s IP
address, for example 163.23.59.150, to be viewed and
Figure 9 VI panel for web publishing tool. [Color figure can be viewed in the online
issue, which is available at www.interscience.wiley.com.]
Figure 10 VI panel for URL access. [Color figure can be viewed in the online issue,
which is available at www.interscience.wiley.com.]
248 LIN
controlled by the client B (remote PC) via World Wide
Web. For security considerations, the Fire wall has
been set up to avoid a stranger (or hacker) invasion,
shown as in Figure 11.
As can be seen, only the certified IP address,
that is, 163.23.59.135 and 163.23.59.142, can be
permitted to view the system simultaneously,
and all others are prohibited. Note that IP
(163.23.59.135) is also allowed to control the system
via Web Site.
EXPERIMENTAL RESULTS WITHTCP/IP AND WEB CONNECTION
The proposed system under on line real-time per-
formance via TCP/IP as well as Web connection was
Figure 11 VI panel for Brower access. [Color figure can be viewed in the online issue,
which is available at www.interscience.wiley.com.]
Figure 12 VI panel of the Server. [Color figure can be viewed in the online issue, which
is available at www.interscience.wiley.com.]
INTERNET-BASED POWER HARMONICS ANALYSIS 249
implemented successfully. The front panel of the
Server was illustrated in Figure 12. It was to collect
and display the waveform data from the checking
points via the DAQ card.
Figure 13 showed the VI panel of the Client A.
The three waveforms were displayed in the waveform
charts, respectively. The individual VI panel showed
not only the waveform’s THD but also its individual
frequency and amplitude. The path to save the THD
history in the data base was set up in the system. A
warning sign was switched on if the THD was
beyond the predefined limit. As can be seen, there
Figure 13 VI panel of the Client A. [Color figure can be viewed in the online issue,
which is available at www.interscience.wiley.com.]
Figure 14 Web front panel of the Client B. [Color figure can be viewed in the online
issue, which is available at www.interscience.wiley.com.]
250 LIN
were up to 50 THD results (THD history) displayed in
the waveform chart for all checking points at the
same time. The preset THD limit is shown in the chart
for easily investigating the THD status.
From the World Wide Web, the Client B can view
the VI panel that is the same front panel as the VI
panel of the Client A, as shown in Figure 14. In
particular, the control of VI panel can be transferred to
the client with the protection of Fire wall. Therefore,
the Client B can be allowed to take over the Server to
carry out a remote monitoring and control function.
The waveform’s THD was recorded once for
every 30 min (i.e., time delay) so that its history can be
easily tracked by the data base. For simplification,
there are only 18 THD records shown in Table I. Note
that time delay can be varied according to the user’s
requirement.
The proposed Internet-based algorithm using FFT
has been applied successfully to multi-location
power system harmonics analysis and monitoring,
particularly perfect for stationary signals as above.
However, the FFT analysis in non-stationary signals
may lead to incorrect results because of the problem
of leakage effect. Accordingly, this approach should
add a data window such as Hanning window function
for reducing the spectral leakage for non-stationary
signals in advanced industrial applications [10].
CONCLUSIONS
The objective of this paper is to introduce the
background needed for electrical/automation engi-
neering students in understanding system harmonics
as well as the Internet extension to multi-location
power harmonic measurement using graphic pro-
gramming. Particularly, this paper introduced illus-
trative techniques for waveform data transmission
between the server and the clients via TCP/IP. The
paper also presented the potential capability of
graphical programming and Internet connection that
is easy for extension to on line applications.
These techniques, in fact, are becoming more
important to develop learning skills about advanced
ideas in the electrical engineering and automated
industry fields.
REFERENCES
[1] H. C. Lin, An intelligent neural network based adaptive
power line conditioner for real-time harmonics filter-
ing, IEE Proc Gener Transm Distrib 151 (2004),
561�567.
[2] H. C. Lin, Fast tracking of time-varying power
system frequency and harmonics using iterative-loop
approaching algorithm, IEEE Trans Ind Electron
54 (2007), 974�983.
[3] J. H. Marks and T. C. Green, Predictive transient-
following control of shunt and series active power
filters, IEEE Trans Power Electr 17 (2002), 574�584.
[4] M. Ali Akcayol and T Yigit, A Tuncay A computer-
based educational tool for pulse width modulator for
static converters, Comput Appl Eng Educ 12(2004),
215�223.
[5] C. Depcik and D. N. Assanis, Graphical user interfaces
in an engineering educational environment, Comput
Appl Eng Educ 13 (2005), 48�59.
Table I THD History
Iteration Date Time THD0 (%) Status THD1 (%) Status THD2 (%) Status
0 2007/2/19 00:00 PM 17.79 Norm. 6.09 Norm. 9.06 Norm.
1 2007/2/19 00:30 PM 27.31 High 19.81 Norm. 8.71 Norm.
2 2007/2/19 01:00 PM 22.57 Norm. 5.07 Norm. 7.84 Norm.
3 2007/2/19 01:30 PM 23.53 Norm. 13.27 Norm. 5.97 Norm.
4 2007/2/19 02:00 PM 16.68 Norm. 10.69 Norm. 9.12 Norm.
5 2007/2/19 02:30 PM 27.74 High 9.59 Norm. 8.93 Norm.
6 2007/2/19 03:00 PM 21.75 Norm. 6.41 Norm. 10.79 Norm.
7 2007/2/19 03:30 PM 6.10 Norm. 5.55 Norm. 5.95 Norm.
8 2007/2/19 04:00 PM 17.74 Norm. 13.74 Norm. 5.70 Norm.
9 2007/2/19 04:30 PM 29.61 High 10.79 Norm. 10.92 Norm.
10 2007/2/19 05:00 PM 26.46 High 4.35 Norm. 5.14 Norm.
11 2007/2/19 05:30 PM 29.50 High 15.74 Norm. 7.13 Norm.
12 2007/2/19 06:00 PM 5.57 Norm. 7.73 Norm. 7.90 Norm.
13 2007/2/19 06:30 PM 27.35 High 10.59 Norm. 4.85 Norm.
14 2007/2/19 07:00 PM 30.10 High 15.76 Norm. 4.90 Norm.
15 2007/2/19 07:30 PM 25.62 High 20.17 Norm. 4.50 Norm.
16 2007/2/19 08:00 PM 8.74 Norm. 19.43 Norm. 5.71 Norm.
17 2007/2/19 08:30 PM 25.00 High 12.00 Norm. 5.91 Norm.
INTERNET-BASED POWER HARMONICS ANALYSIS 251
[6] O. Montero-Hernandez, A. Rugerio De La Rosa,
D. Baez-Lopez, R. Alejos, and E. Enrıquez, Power
Lab: A tool to learn electrical machines and power
electronics, Comput Appl Eng Educ 7 (1999),
213�220.
[7] J. Sanchez, S. Dormido, and F. Esquembre, The
learning of control concepts using interactive tools,
Comput Appl Eng Educ 13 (2005), 84�98.
[8] G. Jovanovic-Dolecek, RANDEMO-educational soft-
ware for random signal analysis, Comput Appl Eng
Educ 5 (1997), 93�97.
[9] IEEE Working Group on Power Systems Harmonics,
Power Systems Harmonics: An Overview, IEEE Trans
Power App Syst PAS 102(1983), 2455�2460.
[10] C. S. Moo and Y. N. Chang, Group-harmonic
identification in power systems with nonstationary
waveforms, IEE Proc Gener Transm Distrib
142 (1995), 517�522.
[11] H. C. Lin, Intelligent neural network based fast power
system harmonic detection, IEEE Trans Ind Electron
54 (2007), 43�52.
[12] H. C. Lin, Intelligent neural network based adaptive
power line conditioner for real-time harmonics filter-
ing, IEE Proc Gener Transm Distrib 151 (2004),
561�567.
[13] IEEE recommended practices and requirements for
harmonic control in electrical power system, ANSI/
IEEE Standard 519 (1992).
[14] H. C. Lin, An Internet based graphical programming
tool for teaching power system harmonics measure-
ment, IEEE Trans Educ 49 (2006), 404�414.
[15] H. C. Lin, An interactive framework for power system
harmonics measurement using graphical programming
and the Internet, Comput Appl Eng Educ (2006),
14:44�52.
[16] H. C. Lin, A remote monitoring and control based
precise multi-location riveting system, Comput Appl
Eng Educ 13 (2005), 316�323.
[17] H. C. Lin, An interactive framework for Internet-
based monitoring and control using a precise riveting
system, J Chinese Soc Mech Eng 27 (2006), 223�227.
[18] J.-H. Teng, S.-Y. Chan, J.-C. Lee, and R. Lee, A
LabVIEW based virtual instrument for power analy-
sers, IEEE Int Conf Pow Syst Technol 1 (2000),
179�184.
[19] H. J. W. Spoelder, Virtual instrumentation and virtual
environments, IEEE Instru Meas Mag 2 (1999),
14�19.
[20] L. Cristaldi, A. Ferrero, and V. Piuri, Programmable
instruments, virtual instruments, and distributed meas-
urement systems: What is really useful, innovative and
technically sound, IEEE Instru Meas Mag 2 (1999),
20�27.
[21] H. C. Lin, Precise riveting systems using networked
PLCs for remote monitoring and control via the
Internet, Mater Science Forum 505�507 (2006),
457�462.
[22] G. Jovanovic-Dolecek, Use of computers for learning
basic concepts of sampling rate alteration, Comput
Appl Eng Educ 8 (2000), 191�195.
[23] X. Feng and G. Lei, Stabilizability, uncertainty and
the choice of sampling rate, Proceedings of the 39th
IEEE Conference on Decision and Control, 1 (2000),
695�699.
[24] P. Hall and Y. Jiying, Nonuniform sequential sampling
for signal analysis, IEEE Trans Inf Theory 50 (2004),
2081�2088.
[25] M. Moy and D. B. Stewart, An engineering approach to
determining sampling rates for switches and sensors in
real-time systems, Proceedings of the sixth IEEE Real-
Time Technology and Applications Symposium, 31
(2000), 34�45.
[26] C. Zhenwei and G. Ledwich, Tracking variable
periodic signals with fixed sampling rate, Proceedings
of the 40th IEEE Conference on Decision and Control,
5 (2001), 4885�4890, 4848.
BIOGRAPHY
Hsiung Cheng Lin was born in Chang
Hua in Taiwan on September 3, 1962. He
graduated from National Taiwan Normal
University for his bachelor degree in 1986,
Taiwan. He received Master and PhD degrees
from Swinburne University of Technology,
Australia, in 1995 and 2002 respectively.
His employment experience included lec-
turer and associate professor at Chung
Chou Institute of Technology, Taiwan. He is currently a professor
in the Department of Automation Engineering at Chienkuo
Technology University (CTU), Taiwan. He was honored with an
excellent teaching award from CTU in 2005, 2006 and 2007. He was
also nominated and included in the First Edition of Who’s Who in
Asia 2007 and 10th Who’s Who in Science and Engineering 2007.
His special fields of interest include power electronics, neural
network, network supervisory system and adaptive filter design.
252 LIN