8
OPTIMIZING NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang 1 , Zheliang Chen 1 , Chen Chen 1 , Yansheng Liu 2 1 Department of Building Science, Tsinghua University, Beijing, China 2 Mumaren Software Company ltd., Beijing, China ABSTRACT Natural ventilation is considered an energy efficient measure that can utilize outdoor cool air to achieve free cooling but needs not consume any fan energy. For studying the energy saving potentials of natural ventilation in factory building with design scheme, the building annual energy consumption simulation software DeST Vent+ was used to simulate the cooling load saving potential and fresh outdoor air flow rates of different area of window opening and ventilation shaft to decide the optimal design of opening area. Then the computational fluid dynamics (CFD) software Fluent Airpak was used to verify the air temperature and speed distributions of the optimal design scheme. Simulation results show that with different window areas the natural ventilation can reduce annual cooling consumptions by 10%-60%. The CFD simulation shows that temperature and air speed distributions with stack ventilation are acceptable with maximum temperature difference around 2°C and maximum air speed less than 0.5 m/s. INTRODUCTION Natural ventilation uses the natural forces of wind pressure or stacks effect to drive air to flow in/out a building. Natural ventilation is considered a beneficial measure to realize both energy efficient building operation and healthy built environment because it can achieve free cooling by inducing outdoor cool air but needs not consume any fan energy. Many researchers focus on studying the natural ventilation potential and performance (Chen 2009, Etheridge et al. 2012, Linden et al. 1990, Li 2000, Li and Li 2015, Montazeri et al. 2010, Moosavi et al. 2014). Several researches study the method for simulating the performance of natural ventilation (Bastide et al. 2006, Oropeza- Pereza et al. 2012, Johnson et al. 2012). Energy saving potential of utilizing natural ventilation is studied as well (Huang et al. 2012, Huang 2013, Oropeza-Pereza and Østergaardb 2014, Ramponi et al. 2014). Some researchers studied the active control for natural ventilation to achieve minimum energy use and balanced air flow rate for the rooms at different locations (Dong and Li 2015, Turner and Walker). However, most researches on natural ventilation focuses on residential buildings or office buildings. For the industrial buildings, whose room depths commonly are large, the research on natural ventilation performance and the energy saving potential of using natural ventilation is very few. This paper takes an actual factorial building that will be built at Qinhuangdao city in China as an example to study the natural ventilation performances and energy saving potentials with different opening areas and ventilation shaft areas for the purpose of optimizing the natural ventilation component design to achieve minimum annual cooling energy use. First, the natural ventilation air flow rates and the annual hourly cooling loads with different window areas and shaft areas were simulated using the software DeST (Designer’s Simulation Toolkits) Vent+ (Yan et al. 2008). The optimal design of the natural ventilation components is decided by comparing the annual cooling load of different design schemes. Then the computational fluid dynamics (CFD) software Fluent Airpak was used to verify the air temperature and speed distributions of the optimal design scheme (Fluent inc., 2007). The following sections will respectively describe the example building information, building model built by the energy simulation software DeST, simulation results of energy performance, and the CFD simulation results. The final section summarizes the main conclusions of this study. BUILDING INFORMATION The example building in this study is located in Qinhuangdao city, Hebei Province, China. The building has four stories with 19.7 meters height and 11731.6 square meters floor area. The main function of the building is for manufacturing electronic productions. There are 9 windows at the north wall and 5 windows at the south wall. Additionally, shafts can be built to increase natural ventilation by using stack effect. Figure1 shows the floor plan for the first floor. The plan of second floor to fourth floor is similar to the first floor. The building length is 79.2 meters and width is 35.2 meters. The building orientation is that the upper wall in Figure1 faces to north. Figure2 shows the section of the building. The height of the first story is 4.8 meters and the height of the other three stories is 4.3 meters. Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015. - 1165 -

OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

Embed Size (px)

Citation preview

Page 1: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

OPTIMIZING NATURAL VENTILATION DESIGN IN A LARGE FACTORY

BUILDING USING SIMULATION

Fulin Wang1, Zheliang Chen1, Chen Chen1, Yansheng Liu2

1Department of Building Science, Tsinghua University, Beijing, China 2Mumaren Software Company ltd., Beijing, China

ABSTRACT

Natural ventilation is considered an energy efficient

measure that can utilize outdoor cool air to achieve

free cooling but needs not consume any fan energy.

For studying the energy saving potentials of natural

ventilation in factory building with design scheme, the

building annual energy consumption simulation

software DeST Vent+ was used to simulate the

cooling load saving potential and fresh outdoor air

flow rates of different area of window opening and

ventilation shaft to decide the optimal design of

opening area. Then the computational fluid dynamics

(CFD) software Fluent Airpak was used to verify the

air temperature and speed distributions of the optimal

design scheme. Simulation results show that with

different window areas the natural ventilation can

reduce annual cooling consumptions by 10%-60%.

The CFD simulation shows that temperature and air

speed distributions with stack ventilation are

acceptable with maximum temperature difference

around 2°C and maximum air speed less than 0.5 m/s.

INTRODUCTION

Natural ventilation uses the natural forces of wind

pressure or stacks effect to drive air to flow in/out a

building. Natural ventilation is considered a beneficial

measure to realize both energy efficient building

operation and healthy built environment because it can

achieve free cooling by inducing outdoor cool air but

needs not consume any fan energy. Many researchers

focus on studying the natural ventilation potential and

performance (Chen 2009, Etheridge et al. 2012,

Linden et al. 1990, Li 2000, Li and Li 2015, Montazeri

et al. 2010, Moosavi et al. 2014). Several researches

study the method for simulating the performance of

natural ventilation (Bastide et al. 2006, Oropeza-

Pereza et al. 2012, Johnson et al. 2012). Energy saving

potential of utilizing natural ventilation is studied as

well (Huang et al. 2012, Huang 2013, Oropeza-Pereza

and Østergaardb 2014, Ramponi et al. 2014). Some

researchers studied the active control for natural

ventilation to achieve minimum energy use and

balanced air flow rate for the rooms at different

locations (Dong and Li 2015, Turner and Walker).

However, most researches on natural ventilation

focuses on residential buildings or office buildings.

For the industrial buildings, whose room depths

commonly are large, the research on natural

ventilation performance and the energy saving

potential of using natural ventilation is very few. This

paper takes an actual factorial building that will be

built at Qinhuangdao city in China as an example to

study the natural ventilation performances and energy

saving potentials with different opening areas and

ventilation shaft areas for the purpose of optimizing

the natural ventilation component design to achieve

minimum annual cooling energy use. First, the natural

ventilation air flow rates and the annual hourly cooling

loads with different window areas and shaft areas were

simulated using the software DeST (Designer’s

Simulation Toolkits) Vent+ (Yan et al. 2008). The

optimal design of the natural ventilation components

is decided by comparing the annual cooling load of

different design schemes. Then the computational

fluid dynamics (CFD) software Fluent Airpak was

used to verify the air temperature and speed

distributions of the optimal design scheme (Fluent inc.,

2007). The following sections will respectively

describe the example building information, building

model built by the energy simulation software DeST,

simulation results of energy performance, and the

CFD simulation results. The final section summarizes

the main conclusions of this study.

BUILDING INFORMATION

The example building in this study is located in

Qinhuangdao city, Hebei Province, China. The

building has four stories with 19.7 meters height and

11731.6 square meters floor area. The main function

of the building is for manufacturing electronic

productions. There are 9 windows at the north wall

and 5 windows at the south wall. Additionally, shafts

can be built to increase natural ventilation by using

stack effect. Figure1 shows the floor plan for the first

floor. The plan of second floor to fourth floor is similar

to the first floor. The building length is 79.2 meters

and width is 35.2 meters. The building orientation is

that the upper wall in Figure1 faces to north. Figure2

shows the section of the building. The height of the

first story is 4.8 meters and the height of the other three

stories is 4.3 meters.

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1165 -

Page 2: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

Figure 1 The first floor plan of the example building

Figure 2 the section of the example building

DESIGN SCHEME OPTIMIZATION

Methodology

The natural ventilation airflow and air-conditioning

cooling loads of the building were simulated via DeST

Vent+ software at different sizes of windows and

ventilation shafts. The design scheme with a specific

window and shaft area that can achieve the minimum

annual cooling consumption is selected as the optimal

design. The DeST Vent+ software uses a multi-zone

network airflow model to calculate the natural

ventilation flow rate. It is assumed that air in the same

zone is well mixed and has the same parameters in

steady flow Bernoulli equations. Every zone is linked

by all sorts of air paths to form a fluid flow network

and equation sets are created base on the energy

balance at all branches and mass balance at all zones.

By solving the equations with Newton’s method, air

flow rates for each branch can be generated. By using

the onion computation approach (i.e. at each time step

the ventilation calculation and thermal calculation are

coupled by transferring the each calculation result in

between until the ventilation and thermal calculation

results are in accordance with each other.) DeST

Vent+ couples ventilation and thermal simulation

together (Yan 2008). The reliability of the result of

DeST has been proved with three kinds of methods of

validation, including analytical tests, inter-model

comparisons and empirical validation (Zhang 2004).

Both of inter-model comparisons and experiments

confirm the accuracy of the calculated air flow rates

results by DeST Vent+ (Zhang 2011).

Building and natural ventilation modelling

Building envelope parameters are shown in Table 1.

The working schedule of the building is 7:00~21:00,

there are no cooling load besides this period. The

indoor temperature set region is 18~28°C. So natural

ventilation control strategy is that when outdoor air

temperature is between 18 and 28°C and humidity is

between 30% and 80%, the natural ventilation will

start and it will stop at other outdoor air conditions.

The air path includes windows and ventilation shaft.

The power-exponent function model is used to

calculate the air flow rate, as shown in Equation 1.

𝑄 = 𝐶𝑄 ∙ (∆𝑃)𝑛 (1)

where 𝑄 is the mass flow rate of air (kg/s), 𝑛 is

constant and approximately 0.5, 𝐶𝑄 is coefficient of

discharge (kg·s-1·Pa-0.5 ), ∆𝑃 is the pressure between

insides and outsides (Pa).

The coefficient of discharge 𝐶𝑄 can be expressed as:

𝐶𝑄 = √2𝜌 ∙ 𝑘𝐴 ∙ 𝐶𝑑 (2)

where 𝜌 is the density of air (kg/m3), 𝑘 is the

percentage of openable area (%), 𝐴 is the area of air

paths, 𝐶𝑑 is orifice-metering coefficient determined

by the types of air paths (-).

In the simulation, 𝜌 is approximately 1.2 kg/m3, 𝑘 is

100%. When 𝑘 is 100%, 𝐶𝑑 is approximately 1.244.

According to equation 1, the mass flow of air paths in

parallel can be expressed as:

𝑄1 + 𝑄2 = √2𝜌 ∙ 𝑘(𝐴1 + 𝐴2) ∙ 𝐶𝑑 ∙ (∆𝑃)𝑛 = 𝐶𝑄 ∙ (∆𝑃)

𝑛

(3)

𝐶𝑄 = √2𝜌 ∙ 𝑘(𝐴1 + 𝐴2) ∙ 𝐶𝑑 (4)

So the air paths in the same wall or floor can be

simplified as one air paths base on equation (4).

Time-averaged surface pressures are proportional to

wind velocity pressure 𝑃𝑉 given by Bernoulli's

equation:

𝑃𝑉 =𝜌𝑉𝐻

2 (5)

where 𝑉𝐻 is approach wind speed at upwind wall

height H (m/s), 𝜌 is ambient (outdoor) air density

(kg/m3).

The equation for wind pressure on the building surface

𝑃𝑠 is

𝑃𝑠 = 𝐶𝑝 ∙ 𝑃𝑉 (6)

where 𝐶𝑝 is the local wind pressure coefficient at a

point on the building surface. Figure 3 showed the

wind pressure coefficient input to the model

(ASHRAE., 2009).

The meteorological data used in simulation includes

dry-bulb temperature, humidity, ground temperature,

sky temperature, wind speed, wind direction, radiation.

Figure 4 shows the daily dry-bulb temperature and

humidity ratio for a year. The dry-bulb temperature

ranges from -15.10 to 33.80°C and the humidity ratio

ranges from 0.00 to 22.08 g/kg. Figure 4 is the wind

rose diagram used in the simulation.

Simulation results

The natural ventilation airflow and air-conditioning

cooling loads simulation was conducted for 51

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1166 -

Page 3: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

different ventilation designs. The area ratio of window

to floor ranges from 0.00 to 0.14 while the area ratio

of shaft to window is 0.0~1.0.

Table 1

Building envelope parameters

Building envelope Components heat

resistance

[m2·K/W]

heat transfer

coefficient

[W/(m2·K)]

External

walls

Concrete wall 20mm lime mortar + 200mm reinforced

concrete +50mm Styrofoam + 25mm

marble/ granite/ basalt

0.866 0.977

Internal

walls

Concrete slab 20mm cement mortar + 100mm aerated

concrete +20mm cement mortar

0.329 1.788

Roof Concrete slab 20mm lime mortar + 200mm reinforced

concrete +50mm Styrofoam + 25mm

marble/ granite

1.074 0.812

Floors Reinforced

concrete floor

25mm cement mortar + 80 mm reinforced

concrete + 20mm cement mortar

0.026 N/A

Windows Two layer

regular glass

- - 3.1

Figure 3 wind pressure coefficient

Figure 4 Weather conditions of dry bulb temperature

and humidity ratio

Annual Cooling-load Saving Ratio

Annual Cooling-load Saving Ratio (ACSR) is an

important evaluation index to judge the energy saving

of natural ventilation, as shown in Equation 7.

𝐴𝐶𝑆𝑅 = 1 −𝐶𝐿𝑉

𝐶𝐿𝑁𝑉 (7)

where 𝐶𝐿𝑉 is the cooling load with natural ventilation

(kWh) and 𝐶𝐿𝑁𝑉 is the cooling load without natural

ventilation (kWh).

Figure 5 shows the simulation results of the annual

cooling-load saving ratio with different area ratios of

window to floor (AROWF) and different area ratios

of shaft to window (AROSW).

Figure 5 Annual cooling-load saving ratio with

different area ratios of window to floor (AROWF)

and different area ratios of shaft to window

(AROSW).

As shown in Figure5, the annual cooling-load saving

ratio grows with the area of windows. Meanwhile the

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1167 -

Page 4: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

annual cooling-load saving ratio rises as the area of

shafts increases.

Annual cooling load with different design schemes

The different area of window and ventilation shaft

determines different cooling loads. Figure 6 shows the

simulation results of the annual cooling load with

different area ratios of window to floor (AROWF) and

different area ratios of shaft to window (AROSW).

Figure 6 Annual cooling-load with different area

ratios of window to floor (AROWF) and different

area ratios of shaft to window (AROSW).

It can be found that when the area ratios of window to

floor is 0.03 and the area ratios of shaft to window is

1.0, the annual cooling load with natural-ventilation

reaches the minimum value. It is recommended to

choose 0.03 as the area ratios of window to floor, and

choose as large shafts as possible such as 1.0 .

Figure 7 shows the monthly cooling load with and

without natural ventilation when AROWF = 0.03 and

AROSW = 1.0. Table 2 provides the annual cooling

loads and the annual cooling-load saving ratio.

Figure 7 Monthly cooling load with and without

natural ventilation when AROWF = 0.03 and

AROSW = 1.0

Table 2

Annual cooling loads and the annual cooling-load

saving ratio.

The Annual Cooling Loads (kWh)

with natural ventilation 1.28E+05 without natural ventilation 8.42E+04

The Annual Cooling-Load Saving

Ratio (%)

34.4

AIR TEMPETATURE AND SPEED

DISTRIBUTION AT OPTIMAL DESIGN

Fluent Airpak is used to simulate the air temperature

and speed distribution of the optimal design at a

specific time point. Fluent Airpak is a commonly used

CFD (Computational Fluid Dynamics) software for

artificial environment analysis, especially for HVAC

(Heating, Ventilation and Air Conditioning) field.

Airpak uses ‘object’ based modelling and Fluent

unstructured solver engine, providing a quick and

accurate way for the analysis of ventilation systems.

CFD modelling

The Airpak model is built on the basis of the DeST

model, where the building envelope parameters are

defined according to the DeST model. Interior walls

and shaft walls are built with ‘Partition’ module, and

windows and air inlets on the shafts are built with

‘Opening’ module. Areas of the windows and

ventilation shafts in the Airpak model are set at the

optimal design as in DeST model, which has an

AROWF of 0.03 and an AROSW of 1.0, i.e. the total

window area of each floor is 88 m2 and the total shaft

section area is 88 m2. A total of 10 ventilation shafts

are distributed in the building, each has a square

section and 4 air inlets on the shaft walls on each floor.

Occupants and facilities are simplified as several long

strip ‘Block’ modules on each floor, with a constant

heat dissipation according to DeST model. Figure 8

shows the front view of the Airpak model.

Figure 8 Front view of the Airpak model

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1168 -

Page 5: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

CFD simulation scenario

Consider such a scenario where natural ventilation is

used: in an early summer day, outdoor temperature is

around 30oC after midday, when air conditioning is

needed and indoor air temperature will be kept at the

upper limit 28oC of the set region. In the late afternoon,

outdoor temperature drops below 28oC when natural

ventilation can be utilized to cool down the building

instead of air conditioning. To examine the ventilation

performance under said situation, the simulation time

point is selected as 17:00 June 27th, when the outdoor

air temperature is 24.6oC according to DeST’s weather

data. Before this time point, air conditioning is in use

and the room temperature is 28oC. Outdoor

temperature of the selected day is shown in Figure 9.

In CFD simulation, building external surface

temperatures are determined using the simplified

harmonic response method (Zhao et al. 2009), which

are shown in Table 3. To take into consideration the

heat storage effect of the construction materials,

surface temperatures of the floors and interior walls

are set to the indoor temperature before the simulation

time point, i.e. 28oC in the Airpak model. In this CFD

simulation, only the stack ventilation is considered to

verify the natural ventilation effect.

Table 3

Building external surface temperature

Figure 9 Outdoor temperature of selected day and

time point for CFD simulation

ROOF SOUTH NORTH EAST WEST

t

(oC) 48 37 37 38 42

Figure 10 Indoor air temperature contour (front view)

20.00

22.00

24.00

26.00

28.00

30.00

32.00

12 13 14 15 16 17 18 19 20 21 22 23

Ou

tdo

or

tem

per

atu

re (℃

)

Time

17:00

24.6℃

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1169 -

Page 6: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

Figure 11 Indoor air temperature contour (horizontal view)

Figure 10 and Figure 11 shows the indoor air

temperature distribution contour of the building (white

strips on each floor are the mentioned ‘Blocks’ to

simplify occupants and facilities) respectively on a

front view and a vertical view. Figure 12 shows the

indoor temperature span of each floor’s main office

area. The CFD simulation result shows that indoor air

temperature is around 26oC while the outdoor air

temperature is 24.6oC, which indicates that using

natural ventilation can keep the indoor air temperature

at a suitable range.

Figure 12 Indoor air temperature of each floor

The indoor air speed range and air speed contour are

respectively shown in Figure 13 and Figure 14.

Average indoor air speed is 0.1-0.2 m/s. As shown in

Figure 14, large window area on both south and north

walls guarantees that cool fresh air can reach the main

part of the indoor area to carry away indoor heat and

bring fine indoor air quality. Windows’ stack

ventilation effect is shown in Figure 15. Meanwhile,

the ventilation shafts utilize the air buoyancy effect to

exhaust air in a vertical direction, which can be seen in

Figure 16. The air exhaustion effect of the ventilation

shafts is notable from the CFD simulation result,

which indicates the shafts play a non-ignorable role in

this natural ventilation system. From the Airpak

simulation, windows combined with shafts can

achieve an acceptable natural ventilation performance.

Figure 13 Indoor air speed of each floor

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1170 -

Page 7: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

Figure 14 Indoor air speed contour

Figure 15 Ventilation effect of the windows

Figure 16 Ventilation effect of the ventilation shafts

CONCLUSIONS

This paper describes the optimal design for the natural

ventilation of a factorial building. The annual cooling

load of fifty-one cases of different window and

ventilation shaft area are simulated. The cooling load

simulation results reveals some insights for designing

the factorial buildings:

1. Natural ventilation can reduce the building energy

consumption. The annual cooling-load saving

ratio ranges from 10% to 60%.

2. When the area ratios of window to floor is

approximately 0.03, the annual cooling load of the

construction with natural-ventilation reaches the

bottom.

3. With the area ratios of window to floor increasing,

cooling load reductions by natural-ventilation

increase, but the total cooling loads decrease

firstly and increase afterward due to large window

area causing more heat gain.

CFD simulation is conducted to verify the indoor air

temperature and speed distribution of the optimal

design scheme. Simulation results show that when

under stack ventilation condition, the indoor air

temperature and speed distribution are roughly

uniform and acceptable.

REFERENCES

ASHRAE, 2009. Airflow Around Buildings.

ASHRAE Handbook - Fundamentals (SI Edition),

Chapter 24.

Bastide A., Lauret P., Garde F., Boyer H., 2006.

Building energy efficiency and thermal comfort in

tropical climates. Presentation of a numerical

approach for predicting the percentage of well-

ventilated living spaces in buildings using natural

ventilation, Energy and Build. 38, 1093–1103.

Chen Q., 2009. Ventilation performance prediction for

buildings: a method overview and recent

applications, Build. Environ. 44 (4), 848–858.

Dong Y., Li P., 2015. Natural ventilation of lower-

level floors assisted by the mechanical ventilation

of upper-level floors via a stack, Energy and Build.

92, 296–305

Etheridge D.W., 2012. Natural Ventilation of

Buildings: Theory, Measurement and Design,

John Wiley & Sons, Chichester, UK.

Fluent Inc., 2007. Airpak 3.0 User’s Guide.

Huang, H., 2013. Research on Evaluation Method of

Natural Ventilation Performance of Northern

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1171 -

Page 8: OPTIMIZING NATURAL VENTILATION DESIGN IN A ... NATURAL VENTILATION DESIGN IN A LARGE FACTORY BUILDING USING SIMULATION Fulin Wang1, Zheliang Chen 1, Chen Chen , Yansheng Liu2 1 Department

High-rise Residential Buildings. Master Thesis,

Tsinghua University.

Huang H., Li, X. F., Zhang, M. R., LI, C., 2012.

Simulation Study on Annual Energy

Consumption of Naturally Ventilated Buildings.

Building Science, 28(2), 46-50.

Linden P.F., Lane-Serff G.F., Smeed D.A., 1990.

Emptying filling boxes: the fluid mechanics of

natural ventilation, J. Fluid Mech. 212, 309–335.

Li Y., 2000. Buoyancy-driven natural ventilation in a

thermally stratified one-zone building, Build.

Environ. 35, 207–214.

Li Y, Li X.F., 2015. Natural ventilation potential of

high-rise residential buildings in northern China

using coupling thermal and airflow simulations,

Build. Simu. 8(1), 51-64.

Johnson M., Zhai Z., Krarti M., 2012. Performance

evaluation of network airflow models for natural

ventilation, HVAC&R Research, 18(3):349–365.

Montazeri H., Montazeri F., Azizian R., Mostafavi S.,

2010. Two-sided wind catcher performance

evaluation using experimental, numerical and

analytical modelling, Renew. Energy 35, 1424–

1435

Moosavi L., Mahyuddin N., Ghafar N.A., 2014.

Thermal performance of atria: an overview of

natural ventilation effective designs, Renew.

Sustain. Energy Rev.34, 654–670.

Oropeza-Pereza I., Østergaardb P. A., Remmenb A.,

2012. Model of natural ventilation by using a

coupled thermal-airflow simulation program,

Energy and Build. 49, 388–393

Oropeza-Pereza I., Østergaardb P. A., 2014. Energy

saving potential of utilizing natural ventilation

under warm conditions – A case study of Mexico,

Applied Energy 130, 20–32.

Ramponi R., Angelotti A., Blocken B., 2014. Energy

saving potential of night ventilation: Sensitivity to

pressure coefficients for different European

climates, Applied Energy 123, 185–195

Turner W.J.N., Walker I. S., 2013. Using a ventilation

controller to optimise residential passive

ventilation for energy and indoor air quality,

Build. and Environ. 70, 20-30

Yan D., Xia J., Tang W., Song F., Zhang X., Jiang Y.,

2008. DeST—An integrated building simulation

toolkit Part I: Fundamentals, Building Simulation

Vol. 1 (2), 95-110.

Zhang M., 2011. Study on Coupled Natural

Ventilation Simulation Analysis and Design

Guide, Master thesis, Tsinghua University.

Zhang X., Xie X., Yan D. and Jiang Y., 2004. Building

environment design simulation software DeST(3):

validation of dynamic simulation results of

building thermal progress, HV&AC Vol. 34(9),

37-50.

Zhao R., Fan C., Xue D., Qian Y., 2009. Air

Conditioning (4th Edition), Beijing: China

Architecture and Building Press. (in Chinese)

Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.

- 1172 -