Output Doc

Embed Size (px)

Citation preview

  • 8/2/2019 Output Doc

    1/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Project documentation

    created with

    SIMARIS design

    Version: 6.0.0 (25-11-2010)Subrevision: 1852

    SIEMENS AG 2010. All rights reserved.

    http://www.siemens.com/simaris

    Master data

    Project name: New [email protected]

    Project description: new

    Editor: Kushtrim MALA

    Planning office: Cef Kushtrim MALA

    Created at: Tuesday, April 10, 2012

    Changed at: Tuesday, April 10, 2012

    Customer data

    City: Drenas

    Customer: NEW-CO-FERRONICELI

    Comment:

    Page 1/12

    http://www.siemens.com/simarishttp://www.siemens.com/simaris
  • 8/2/2019 Output Doc

    2/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Network parameters:

    GeneralStandard IECAttitude of Site < 1000 m

    Medium Voltage

    Rated voltage 6 kVAmbient temperature 40 CVoltage factor c max 1.1Voltage factor c min 1Max./Min short-circuit power 250 / 100 MVANeutral System Low-resistanceRelation R1/X1 min 0.2

    Low Voltage

    Rated voltage 450 VSystem configuration TN-SFrequency 50 HzTolerable touch voltage 50 VAmbient temperature of devices 45 CVoltage factor c max 1.1Voltage factor c min 0.95Base point of voltage drop calulation Transformer-primary terminalsRelative operating voltage at reference point 100 %

    Max. permissible voltage drop in network 14 %

    Page 2/12

  • 8/2/2019 Output Doc

    3/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Defined network modes for calculation and dimensioning:

    Operating mode:

    Page 3/12

  • 8/2/2019 Output Doc

    4/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    List of devices:

    Sources of feeding:

    Transformers:

    Designation Type Sn [kVA] ukr [%] Uprim[kV]/Usec [V]

    Pk [kW] P0 [kW] Vector group u_transformer [%]

    Catalog Reference

    Transformer 1.1A.1 GEAFOL 100 4 6/450

    1.85 0.44 Dyn5 2.825 4GB50363DY001AA2

    Output u_transformer [%] is independent from defined reference point for voltage drop calculation.

    Page 4/12

  • 8/2/2019 Output Doc

    5/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Switches/Fuses:

    Medium voltage switch disconnectors:

    Place Designation Type Catalog Referencefuse

    In fuse [A] In disconnector [A] Quantity

    LVMD 1.1A.1 MV-SD 1.1A.1 Switch-disconnector withfuses, MV

    SIB:3009813.20 20 200 3

    Circuit Breaker/Miniature circuit-breaker:

    Place Designation Catalog Reference In [A] Icu/Icn [kA] Icu/Icn [kA]required

    Release type/characteristics

    Quantity

    LVMD 1.1A.1 LV-CB 1.1A.1b 3VL27161SB330AA0 160 25 3.016 ETU10 1

    GS 1.1A.1 CB 1.1A.1a 3VL17121DD330AA0 125 18 2.859 TM 1

    Motor-starter combinations:

    Place Designation Starter type Inmotor[A]

    Catalog Reference Device Pmech[kW]

    Coordination type

    Quantity

    GS 1.1A.1 MC-CB-DS1.1A.1.1a

    Direct-on-linestarter

    25.456 3RV10314EA103RT10341AP00

    Circuit-breakerContactor

    15 1 1

    GS 1.1A.1 MC-CB-DS1.1A.1.2a

    Direct-on-linestarter

    25.456 3RV10314EA103RT10341AP00

    Circuit-breakerContactor

    15 1 1

    GS 1.1A.1 MC-CB-DS

    1.1A.1.3a

    Direct-on-line

    starter

    25.456 3RV10314EA10

    3RT10341AP00

    Circuit-breaker

    Contactor

    15 1 1

    GS 1.1A.1 MC-CB-DS1.1A.1.4a

    Direct-on-linestarter

    25.456 3RV10314EA103RT10341AP00

    Circuit-breakerContactor

    15 1 1

    Page 5/12

  • 8/2/2019 Output Doc

    6/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Connections and line distribution:

    Cable/Conductor Medium voltage:

    Designation Type/ Profile[mm]

    Starting point /Target point

    Ib [A] Iz[A]

    Material Length[m]

    Isolation Installationtype

    ftot u [C] / Ikmax

    [C] / Ikmin [C]

    MV-C/L 1.1A.1 NYFGY3x25 LVMD 1.1A.1

    7.637105

    Cu 40 PVC-cable Air 1 552080

    Cable/Conductor Low voltage:

    Designation

    Type/Profile[mm]

    Startingpoint /Target

    point

    Ib [A] Iz [A] Material Length[m]

    Isolation Installation type

    ftot u [%] / u [%]

    u [C] / Ikmax

    [C] /

    Ikmin [C]

    Numberof runs

    LV-C/L1.1A.1

    e.g. NYY,NYCWY,NYCY,NYKY3x50/50/25

    LVMD1.1A.1LVMD 1.1A

    101.825144

    Cu 60 PVC70 C 1 0.9293.754

    552080

    1

    C/L1.1A.1.1

    e.g. NYY,NYCWY,NYCY,NYKY3x35/-/35

    GS 1.1A.1M 1.1A.1.1

    25.456119

    Cu 200 PVC70 C 1 1.0694.823

    552080

    1

    C/L

    1.1A.1.2

    e.g. NYY,

    NYCWY,NYCY,NYKY3x10/-/10

    GS 1.1A.1

    M 1.1A.1.2

    25.456

    57

    Cu 80 PVC70 C 1 1.414

    5.168

    55

    2080

    1

    C/L1.1A.1.3

    e.g. NYY,NYCWY,NYCY,NYKY3x6/-/6

    GS 1.1A.1M 1.1A.1.3

    25.45641

    Cu 40 PVC70 C 1 1.1664.920

    552080

    1

    C/L1.1A.1.4

    e.g. NYY,NYCWY,NYCY,NYKY3x10/-/10

    GS 1.1A.1M 1.1A.1.4

    25.45657

    Cu 70 PVC70 C 1 1.2374.992

    552080

    1

    Page 6/12

  • 8/2/2019 Output Doc

    7/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Load:

    Motors:

    Designation Pmech [kW]In [A]

    Un [V]cos

    ai Phaseconnection

    Ia/In Trip class Method of Starting

    Ikre Quantity

    M 1.1A.1.1 1525.456

    4500.84

    1 L1-L2-L3 5 Class 10 Motor starter combination

    1 0.9 1

    M 1.1A.1.2 1525.456

    4500.84

    1 L1-L2-L3 5 Class 10 Motor starter combination

    1 0.9 1

    M 1.1A.1.3 1525.456

    4500.84

    1 L1-L2-L3 5 Class 10 Motor starter combination

    1 0.9 1

    M 1.1A.1.4 1525.456

    4500.84

    1 L1-L2-L3 5 Class 10 Motor starter combination

    1 0.9 1

    Page 7/12

  • 8/2/2019 Output Doc

    8/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Messages

    Designation Message

    GS 1.1A.1 Overload protection not fulfilled. IR = 100A < Ibs = 101.825A

    Page 8/12

  • 8/2/2019 Output Doc

    9/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Personal protection against electric shock

    All circuits of the project have a permissable break time ta-req > ta-cur and therefor fulfill the requirements for Personal protection against

    electric shock.

    Disclaimer:

    Dimensioned protection devices inside tap-off units of busbar trunking systems may not correspond to the actual availabledevices for those components. Please verify the dimensioning results in the device lists and correct them accordingly.

    Page 9/12

  • 8/2/2019 Output Doc

    10/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Symbols legend:

    Symbol [Unit] Description

    ai Load factor

    cos Power factor

    ftot Derating factor

    Ia/In Inrush current relation

    Ib [A] Iz [A] Operating current / allowed load capacity

    Icu(fuse) [kA] Rated ultimate short-circuit breaking capacity - fuse

    Icu [kA]Icn [kA]

    Rated ultimate short-circuit breaking capacity according to IEC 60947-2Rated short-circuit breaking capacity according to IEC 60898-1

    Icu/Icn [kA] required the required breaking capacity of the protection device at installation location

    Icw 1s [kA] Rated short-time withstand current 1s

    I n [mA] Residual current - RCD

    Ik1max Maximum single phase short-circuit current

    Ik1min Minimum single phase short-circuit current

    Ik3max Maximum three phase short-circuit current

    Ik3min Minimum three phase short-circuit current

    Ik1D [kA] single pole uninterrupted short-circuit current

    Ik3D [kA] three pole uninterrupted short-circuit current

    Ikmax/Ikmin Relation of maximum and minimum short-circuit current

    Ikre Short-circuit current recovery factor

    In [A] Nominal current

    P0 [kW] No-load losses

    Pk [kW] Short-circuit losses

    Pmech [kW] mechan. Power

    Pn [kW] Active power

    R0 N [m] Zero phase-sequence resistance phase-neutral conductor

    R0 PE(N) [m] Zero phase-sequence resistance phase-PE(N) conductor

    R0/R1 Resistance relation positive / zero phase-sequence system

    r1 [%] Relative value of positive phase-sequence resistance

    R1 [m] Positive phase-sequence resistance

    Sn [kVA] Nominal apparent power

    ukr [%] Short-circuit voltage

    Un [V] Nominal voltage

    Uprim [kV] Primary voltage

    Usec [V] Secondary voltage

    Page 10/12

  • 8/2/2019 Output Doc

    11/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    X0 N [m] Zero phase-sequence reactance phase-neutral conductor

    X0 PE(N) [m] Zero phase-sequence reactance phase-PE(N) conductor

    X0/X1 Reactance relation positive / zero phase-sequence system

    X1 [m] Positive phase-sequence reactance

    xd'' [%] Subtransient reactance

    Z1 max Maximum impedance in positive phase-sequence system

    Z1 min Minimum impedance in positive phase-sequence system

    Zs Faulted circuit impedance

    Zs max Maximum faulted circuit impedance

    Zs min Minimum faulted circuit impedance

    u [%] / u [%]voltage drop between beginning and end of a section / cumulated voltage drop from the transformer primary/secondary clamps to the specified point

    u [C] / Ikmax [C] / Ikmin [C]

    Conductor temperature of MV cable / Conductor temperature of LV cablefor voltage drop / on beginning of short circuit / for disconnection

    Efficiency

    [] Phase angle

    1 min/max [] Phase angle at Ik1 min/max

    3 min/max [] Phase angle at Ik3 min/max

    Page 11/12

  • 8/2/2019 Output Doc

    12/12

    newNEW-CO-FERRONICELI Apr 10, 2012 / Kushtrim MALA

    Standards for computation:

    Title IEC HD EN DIN VDE

    Low-voltage electrical installations * 60364-16 384 0100 100...710

    Short-circuit currents in three-phase a.c. systems Calculation of currents 60909 60909 0102

    Short-circuit currents calculation of effectsDefinitions and calculation methods

    60865 60865 0103

    Low-voltage switchgear and controlgear Circuit-breakers 60947-2 60947-2 0660 101

    Low-voltage switchgear and controlgear assemblies 60439 60439-15 0660 500505

    A method of temperature-rise assessment by extrapolation for partially type-tested assemblies (PTTA) of low-voltage switchgear and controlgear

    60890+C 528 S2 0660 507

    Electrical installations of buildings Part 5-52: Selection and erection of electrical

    equipment Wiring systems 60364-5-52 384 0298 4

    Electrical accessories Circuit-breakers for overcurrent protection for householdand similar installations Circuit-breakers for a.c. operation

    60898-1 60898-1 0641 11

    High-voltage switchgear and controlgear Alternating Current switch-fusecombinations

    62271 62271 0671 105

    Electrical installations of buildings Selection and erection of electricalequipment Isolation, switching and control

    60364-5-53 60364-5-534 0100-534

    Low-voltage electrical installations Protection for safety Protection againstvoltage disturbances and electromagnetic disturbances

    60364-4-44 60364-4-443 0100-443

    Protection against lightning Part 14 62305-14 0185 14

    Low-voltage surge protective devices - Surge protective devices connected tolow-voltage power systems; Requirements and tests 61643-11 0675-6-11

    *) Special national conditions and deviations from IEC 60364-4-41: 2005 are not implemented and need to be considered!

    Page 12/12