OUTSULATION® An Exterior Wall Insulation and Finish System

Outsulation System Installation Details

Page 2: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones
Page 3: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

EPS INSULATION

The architecture, engineering and design of the project using the

08/0611DAW

DATE:REV:APPROVED BY:

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED TO

ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER® MESH PRIOR TO

STANDARD MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

®

version.

without notice. Contact Dryvit to insure you have the most recent

1.

NOTE:

and Dryvit specifically disclaims any liability for the use of this

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

detail and for the architecture, design, engineering or workmanship of

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

Dryvit products is the responsibility of the project's design

DRYVIT FINISH

Outsulation System®Outsulation System

DRYVIT OUTSULATION SYSTEM

BY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

HIGH

IMPACT

DRYVIT BASE COAT

PANZER 15 OR 20 REINFORCING

MESH EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

SUBSTRATE

DRYVIT FINISH

SUBSTRATE

DRYVIT ADHESIVE

DRYVIT OUTSULATION SYSTEM

BY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COATNORMAL

IMPACT

DRYVIT BASE COAT

EPS INSULATION

DRYVIT ADHESIVE

OS 0.0.01

Page 4: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

version.

without notice. Contact Dryvit to insure you have the most recent

detail and for the architecture, design, engineering or workmanship of

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

1.professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

Dryvit products is the responsibility of the project's design

®Outsulation System Grade Level - Termination At Concrete Curb

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACE TO RECEIVE SEALANT

19 MM (3/4") MIN.

WRAP DRYVIT DETAIL MESH® 51 MM (2")

MINIMUM AT UNDERSIDE OF EPS

DRYVIT FINISH

FRAMING

DRYVIT ADHESIVE

EPS INSULATION

SUBSTRATE

BY OTHERS DRYVIT OUTSULATION SYSTEM

OS 0.0.02

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED TO

ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER® MESH PRIOR TO

STANDARD MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

®

NOTE:The architecture, engineering and design of the project using the

DAW

APPROVED BY:

10/0612

DATE:REV:

Page 5: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

610 MM (2'-0") Max

(SEE NOTE 2)

NOTE:The architecture, engineering and design of the project using the

08/0611DAW

DATE:REV:APPROVED BY:

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

1.

STOP FINISH APPROXIMATELY 51 MM (2")

BELOW GRADE.does not violate Dryvit's warranty. This detail is subject to change

®

without notice. Contact Dryvit to insure you have the most recent

version.

EXPANSION JOINT IS REQUIRED ALONG TOP

OF FOUNDATION IF 610 MM (2'-0") DIMENSION

IS EXCEEDED. and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

3. SLOPE GRADE AWAY FROM WALL.

4.

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

2.

Outsulation System Foundation - Termination Above Grade®

203 MM (8") MIN. ABOVE

FINISHED GRADE OR AS

REQUIRED BY LOCAL CODE

DRYVIT DRYFLEX™ WATER

RESISTANT BASE COAT

AND DRYVIT FINISH

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

WRAP DRYVIT DETAIL MESH®

51 MM (2") MINIMUM AT

UNDERSIDE OF EPS

DRYVIT COMPATIBLE

SEALANT WITH BOND

BREAKER, BY OTHERS

DRYVIT FINISH

DRYVIT ADHESIVE

EPS INSULATION

SUBSTRATE

FRAMING

BY OTHERS DRYVIT OUTSULATION SYSTEM

OS 0.0.03

Page 6: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

NOTE:

Outsulation® SystemThe architecture, engineering and design of the project using the

05/063RS

APPROVED BY: REV: DATE:

does not violate Dryvit's warranty. This detail is subject to change

®

version.

without notice. Contact Dryvit to insure you have the most recent

DRYVIT AQUAFLASH SHALL EXTEND TO

INTERIOR FACE OF FRAMING.

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF

AQUAFLASH SYSTEM.REFER TO OS 0.0.05, 0.0.06 FOR

INTEGRATION OF SILL FLASHING.

2.

1. 3.

and Dryvit specifically disclaims any liability for the use of this

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

Dryvit products is the responsibility of the project's design

Rough Opening Preparation

STEP #3

APPLY DRYVIT AQUAFLASH

SYSTEM AT HEAD LAPPING

OVER JAMB APPLICATION

(SEE NOTE 3)

APPLY DRYVIT AQUAFLASH

SYSTEM AT JAMBS LAPPING

OVER SILL APPLICATION

(SEE NOTE 3)

APPLY DRYVIT AQUAFLASH® SYSTEM

AT SILL, EXTENDING UP JAMBS

MINIMUM 64 MM (2 12") AND INSTALL

CORNER SPLICES (SEE NOTE 3)

STEP #1 STEP #2

OS 0.0.04

Page 7: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

Outsulation® System

APPROVED BY:

RS 05/064

DATE:REV:

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

DRYVIT FLASHING TAPE SURFACE CONDITIONER™

AND DRYVIT FLASHING TAPE™ MAY BE USED IN

LIEU OF AQUAFLASH SYSTEM.

3.

®

PAN FLASHING SHOULD OVERLAP EIFS MIN. 2 1/2"

MEASURED FROM THE TOP OF THE EPS

PAN FLASHING MUST HAVE WATERTIGHT SEAMS2.

NOTES

1.

INSTALL WINDOW UNIT AND ASSOCIATED

HEAD FLASHING. (SEE DETAIL 0.0.09)

INSTALL EIFS AND APPLY BACKER

ROD AND SEALANT ALONG JAMBS

AND AT SYSTEM TERMINATIONS,

ALSO ALONG EDGES OF FLASHING.

Preparation of Opening for Storefront Window

STEP 3: STEP 4:

64 MM

(2 12") MIN.

PREPARE OPENING AS PER OS 0.0.04. INSTALL

SILL PAN FLASHING AND SECURE TO FRAMING AND

BLOCKING. SHIM UNDERSIDE OF FLASHING TO

ENSURE INCIDENTAL MOISTURE IS DIRECTED TO

THE EXTERIOR FACE OF THE WALL.

(SEE NOTES 1,2 AND 3)

APPLY DRYVIT AQUAFLASH® SYSTEM

SPLICES OVER UPTURNED LEGS OF PAN

FLASHING (SEE NOTE 3)

STEP 1: STEP 2:

(SEE NOTES 1 AND 2)

51 MM (2") MIN.

OS 0.0.05

Page 8: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

(SEE NOTES 1,2 AND 5)

51 MM (2") MIN.

APPLY DRYVIT AQUAFLASH®

SYSTEM AT SILL PER OS 0.0.04

AND SECURE FLASHING TO

FRAMING

(SEE NOTES 1,2,5 AND 7)

INSTALL SILL PAN FLASHING. SHIM

UNDERSIDE OF PAN FLASHING TO

ENSURE WATER RUN OFF

(SEE NOTE 2)

STEP 1: STEP 2:

64 MM

(2 12") MIN.

OS 0.0.06

DATE:APPROVED BY: REV:

RS 4 05/06

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

ADHESIVE ONLY APPLICATION IS

ACCEPTABLE WHEN USING THE

AQUAFLASH SYSTEM

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF

AQUAFLASH SYSTEM. ®

7.

APPLY DRYVIT AQUAFLASH SYSTEM AT

SILL. (SEE DETAIL OS 0.0.04)

6.

5.

INSTALL EIFS AND APPLY BACKER ROD AND

SEALANT ALONG JAMBS AND AT SYSTEM

TERMINATIONS, ALSO ALONG EDGES OF

FLASHING (SEE NOTES 3,4,5 AND 6)

APPLY DRYVIT AQUAFLASH SYSTEM

OVER METAL FLASHING TRANSITION

AND AT JAMBS LAPPING OVER

UPTURNED LEGS OF PAN FLASHING (SEE

NOTES 1,2,5 AND 7)

Preparation of Opening for Nail-On Window

INSTALL WINDOW UNIT AND

ASSOCIATED HEAD FLASHING.

STEP 4: STEP 5:

Outsulation® System

PAN FLASHING SHOULD OVERLAP EIFS MIN. 64

MM (2 1/2") MEASURED FROM THE TOP OF THE

EPS

PAN FLASHING MUST HAVE WATER

TIGHT SEAMS

STEP 3:

MECHANICAL FASTENERS SHOULD BE USED TO

ATTACH SILL TRIM PIECE

EIFS AT SILL SHALL BE SLOPED FOR DRAINAGE.

NOTES

4.

3.

2.

1.

Page 9: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT ADHESIVE

NOTE:The architecture, engineering and design of the project using the

APPROVED BY: REV: DATE:

08/0614RS

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

®

version.

without notice. Contact Dryvit to insure you have the most recent

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF

AQUAFLASH SYSTEM.

2.1.

detail and for the architecture, design, engineering or workmanship of

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

Dryvit products is the responsibility of the project's design

64MM

(2-1/2") MIN.

SILL PAN FLASHING

DETAIL

Outsulation System®

Termination at Sill

12.7MM (1/2")

DRYVIT OUTSULATION SYSTEMBY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

AIR SEAL PER WINDOW MANUFACTURES

REQUIREMENT, BY OTHERS

FRAMING

SUBSTRATE

DRYVIT-COMPATIBLE SEALANT

WITH BOND BREAKER, BY OTHERS

64MM (2 12") MIN.

WRAP DRYVIT DETAIL MESH® 51 MM (2")

MINIMUM AT UNDERSIDE OF EPS.

CONTINUOUS FLASHING, BY OTHERS.

TURN UP 12.7MM (12") MIN. AT JAMBS

(SEE INSET)

DRYVIT AQUAFLASH® SYSTEM

(SEE NOTE 2)

WINDOW SYSTEM

AND SHIMS

OS 0.0.07

Page 10: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT ADHESIVE

DRYVIT OUTSULATION SYSTEM

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT AQUAFLASH® SYSTEM

(SEE NOTE 3)

NOTE:The architecture, engineering and design of the project using the

APPROVED BY: REV: DATE:

08/0613RS

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING TAPE™

MAY BE USED IN LIEU OF AQUAFLASH

SYSTEM.

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

®

version.

without notice. Contact Dryvit to insure you have the most recent

SEALANT SHOULD NOT BE IN DIRECT

CONTACT WITH FLASHING TAPE ADHESIVE;

STAINING COULD OCCUR.detail and for the architecture, design, engineering or workmanship of

3.discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

1. 2.and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

DRYVIT DEMANDIT® OR

COLOR PRIME™ ON SURFACE

TO RECEIVE SEALANT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

Outsulation System®Termination at Jamb

DRYVIT-COMPATIBLE SEALANT

WITH CLOSED CELL BACKER ROD

BY OTHERS (SEE NOTE 2)

19 MM (3/4") MIN

EPS INSULATION

WINDOW SYSTEM

AND SHIMS

AIR SEAL PER WINDOW

MANUFACTURES

REQUIREMENT, BY OTHERS

SUBSTRATE

BY OTHERS

FRAMING

OS 0.0.08

Page 11: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

NOTE:

APPROVED BY: REV: DATE:

14RS 08/06

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

1.

does not violate Dryvit's warranty. This detail is subject to change

®

without notice. Contact Dryvit to insure you have the most recent

version.

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF

AQUAFLASH SYSTEM.

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

2.

AIR SEAL PER WINDOW

MANUFACTURES

REQUIREMENT, BY OTHERS

Outsulation SystemThe architecture, engineering and design of the project using the

Termination at Head®

WINDOW SYSTEM

AND SHIMS

CONTINUOUS FLASHING AND

SEALANT (BY OTHERS)

19 MM (3/4") MIN.

SUBSTRATE

APPLY DRYVIT AQUAFLASH® SYSTEM

OVER LEG OF HEAD FLASHING

(SEE NOTE 2)

DRYVIT AQUAFLASH SYSTEM

(SEE NOTE 2)

DRYVIT DEMANDIT® OR COLOR PRIME™ ON

SURFACE TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

DRYVIT ADHESIVE

OS 0.0.09

DRYVIT OUTSULATION SYSTEMBY OTHERS

FRAMING

Page 12: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACE TO RECEIVE SEALANT

DRYVIT AQUAFLASH SYSTEM

(SEE NOTE 2)

NOTE: Dryvit products is the responsibility of the project's design

DATE:APPROVED BY: REV:

12DAW 08/06

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

®

version.

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF

AQUAFLASH SYSTEM.

1.2.

detail and for the architecture, design, engineering or workmanship of

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

WINDOW SYSTEM

AND BLOCKING

AIR SEAL PER WINDOW

MANUFACTURES

REQUIREMENT, BY OTHERS

®Outsulation SystemThe architecture, engineering and design of the project using the

Termination at Head-Solid Substrate

CONTINUOUS FLASHING AND

SEALANT, BY OTHERS

19 MM (3/4") MIN.

SOLID SUBSTRATE

DRYVIT AQUAFLASH® SYSTEM

OVER LEG OF HEAD FLASHING

(SEE NOTE 2)

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

DRYVIT ADHESIVE

OS 0.0.10

DRYVIT OUTSULATION SYSTEMBY OTHERS

Page 13: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

version.

detail and for the architecture, design, engineering or workmanship of

LOCATE INSULATION BOARDS SUCH THAT

BOARD EDGES DO NOT ALIGN WITH CORNERS

OF PENETRATION.

2.discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

any project. The project design professional determines, in its sole

1. standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

®Outsulation System EPS Preparation at Wall Penetrations

The architecture, engineering and design of the project using the

DRYVIT DETAIL MESH

241 MM (9 1/2") X 305 MM (12") (TYP.)

(SEE NOTE 2)

BACK WRAP INSULATION BOARD

WITH DRYVIT DETAIL MESH®

EPS INSULATION (SEE NOTE 1)

OS 0.0.11

Dryvit products is the responsibility of the project's designNOTES:

DATE:REV:APPROVED BY:

05/06DAW 11

without notice. Contact Dryvit to insure you have the most recent

APPLY A PIECE OF 241 MM (9 1/2") X 305 MM

(12") DETAIL REINFORCING MESH DIAGONALLY

AT EACH CORNER.

®

Page 14: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

version.

EXPANSION JOINT IS INTENDED TO

ACCOMMODATE CROSS GRAIN SHRINKAGE

OF FLOOR BEAMS. detail and for the architecture, design, engineering or workmanship of

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

does not violate Dryvit's warranty. This detail is subject to change

3. LOCATE EXTERNAL SEALANT JOINT WITHIN

51 MM (2") BELOW BREAK IN SHEATHING.

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and2.1.

®Outsulation System Wood Framing - Expansion Joint At Floor Line

The architecture, engineering and design of the project using the

WOOD FRAMING

SUBSTRATE

DRYVIT ADHESIVE

SEE NOTE 3

DRYVIT COMPATIBLE SEALANT

WITH CLOSED CELL BACKER ROD,

BY OTHERS

DRYVIT DEMANDIT® OR

COLOR PRIME™ ON SURFACES

TO RECEIVE SEALANT

SLOPE BOTTOM SURFACE

1/5 MIN. OUTWARD TO DRAIN

19 MM (3/4") MIN.

DRYVIT FINISH

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

OS 0.0.12

DRYVIT OUTSULATION SYSTEMBY OTHERS

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE

OF EPS

NOTE: Dryvit products is the responsibility of the project's design

DATE:REV:APPROVED BY:

DAW 08/0611

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

®

Page 15: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

SLIP TYPE

CONNECTION

19 MM (3/4") MIN.

NOTE: Dryvit products is the responsibility of the project's design

11DAW 08/06

LOCATE EXTERNAL SEALANT JOINT WITHIN

51 MM (2") BELOW BREAK IN SHEATHING.

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

REV:APPROVED BY:

®

DATE:

version.

EXPANSION JOINT IS INTENDED TO

ACCOMMODATE MOVEMENT AT SLIP

CONNECTION.

3.

2.1.

detail and for the architecture, design, engineering or workmanship of

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

®Outsulation SystemThe architecture, engineering and design of the project using the

Light Gauge Framing - Expansion Joint At Floor Line

SLOPE BOTTOM SURFACE 1/5 MIN.

OUTWARD TO DRAIN

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT FINISH

SEE NOTE 3

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

DRYVIT ADHESIVE

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

SUBSTRATE

OS 0.0.13

BY OTHERS DRYVIT OUTSULATION SYSTEM

Page 16: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

OS 0.0.14

version.

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

1. standards. This detail is for general information and guidance only2.

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

DRYVIT OUTSULATION SYSTEMBY OTHERS

Termination at Parapet-Cap Flashing®Outsulation System

The architecture, engineering and design of the project using the

DRYVIT FINISH

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

PARAPET COPING ASSEMBLY,

BY OTHERS

DRYVIT COMPATIBLE SEALANT WITH

BOND BREAKER, BY OTHERS

WRAP DRYVIT REINFORCING MESH

AND BASE COAT OVER TOP OF FRAMING

(SEE NOTE 2)

FRAMING

ROOF

ASSEMBLY

SUBSTRATE

64 MM (2 1/2") MIN.

NOTE: Dryvit products is the responsibility of the project's design

08/0612DAW

detail and for the architecture, design, engineering or workmanship of

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

AS AN OPTION, DRYVIT AQUAFLASH®

SYSTEM OR DRYVIT FLASHING TAPE

SURFACE CONDITIONER™ AND DRYVIT

FLASHING TAPE™ MAY BE USED TO

PROVIDE ADDITIONAL PROTECTION AT THE

TOP OF A PARAPET WALL.

®

DATE:REV:APPROVED BY:

DRYVIT ADHESIVE

Page 17: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT REINFORCING

MESH EMBEDDED IN

DRYVIT BASE COAT

203 MM (8") MIN.

NOTE:Dryvit products is the responsibility of the project's design

RS 08/0714

AS AN OPTION, DRYVIT AQUAFLASH®

SYSTEM OR DRYVIT FLASHING TAPE

SURFACE CONDITIONER™ AND DRYVIT

FLASHING TAPE™ MAY BE USED TO

PROVIDE ADDITIONAL PROTECTION AT THE

TOP OF A PARAPET WALL.

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

any project. The project design professional determines, in its sole

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

detail and for the architecture, design, engineering or workmanship of

2.1.

®Outsulation System Termination at Parapet - Solid Substrate

The architecture, engineering and design of the project using the

DRYVIT OUTSULATION SYSTEMBY OTHERS

DRYVIT FINISH

PARAPET COPING ASSEMBLY,

BY OTHERS WRAP DRYVIT DETAIL

MESH 51 MM (2") MIN.

AT UNDERSIDE OF EPS

(SEE NOTE 2)

WRAP DRYVIT REINFORCING MESH

AND BASE COAT OVER TOP OF

FRAMING (SEE NOTE 2)

DRYVIT COMPATIBLE

SEALANT, BY OTHERS

DRYVIT COMPATIBLE

SEALANT WITH BOND

BREAKER, BY OTHERS

SOLID SUBSTRATE

ROOF FLASHING AND COUNTER

FLASHING BY OTHERS

ROOF ASSEMBLY

EPS INSULATION

DRYVIT ADHESIVE

64 MM (2 1/2") MIN.

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

OS 0.0.15

without notice. Contact Dryvit to insure you have the most recent

®

APPROVED BY: REV: DATE:

Page 18: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

EDGE/REGLET DETAIL SHOWN

IN ENLARGED SECTION VIEW

ROOFING SYSTEM

NOTE: Dryvit products is the responsibility of the project's design

05/067RS

without notice. Contact Dryvit to insure you have the most recent

REV:APPROVED BY: DATE:

version.

2. FLASHINGS SHALL BE CONFIGURED AND

INSTALLED IN A WATER TIGHT FASHION

PRIOR TO OUTSULATION INSTALLATION

APPLY AQUAFLASH® SYSTEM OR FLASHING

TAPE™ AT WALL/SLEEVE TRANSITION.

1.

any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

ROOF FLASHING AND COUNTER

FLASHING, BY OTHERS

DRYVIT COMPATIBLE SEALANT

W/CLOSED CELL BACKER ROD,

BY OTHERS

Outsulation® System Parapet/Wall Termination

The architecture, engineering and design of the project using the

DRYVIT FINISH

OUTSULATION SYSTEM

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

FLASHING SLEEVE SHOWN

IN EXPLODED VIEW

METAL COPING FLASHING

AT PARAPET WALL

DRYVIT OUTSULATION SYSTEM

ALUMINUM REGLET

OS 0.0.16

Page 19: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

APPROVED BY: REV: DATE:

OS 0.0.17

The architecture, engineering and design of the project using the

Soffit With Fascia Extended Drip

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

does not violate Dryvit's warranty. This detail is subject to change

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

detail and for the architecture, design, engineering or workmanship of

without notice. Contact Dryvit to insure you have the most recent

NOTE:Dryvit products is the responsibility of the project's design

08/0612DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS. ®

version.

1.and Dryvit specifically disclaims any liability for the use of this

25 MM (1") MAX.

®Outsulation System

DRYVIT ADHESIVE

DRYVIT REINFORCING

MESH EMBEDDED IN

DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

FRAMING

SUBSTRATE

BY OTHERS DRYVIT OUTSULATION SYSTEM

Page 20: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

version.

any project. The project design professional determines, in its sole

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

1.

DRYVIT DETAIL

MESH® EMBEDDED

IN DRYVIT BASE COAT

OVERLAP 64 MM (2 1/2") MIN.

Soffit Router Cut Drip®Outsulation System

The architecture, engineering and design of the project using the

19 MM (3/4") MIN.

DRYVIT REINFORCING

MESH EMBEDDED IN

DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

DRYVIT ADHESIVE

SUBSTRATE

FRAMING

OS 0.0.18

DRYVIT OUTSULATION SYSTEMBY OTHERS

NOTE:Dryvit products is the responsibility of the project's design

08/0612DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

®

APPROVED BY: DATE:REV:

Page 21: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

NOTE:Dryvit products is the responsibility of the project's design

DATE:APPROVED BY: REV:

DAW 08/0612

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

®

version.

1.

detail and for the architecture, design, engineering or workmanship of

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

professional. All systems must comply with local building codes and

Outsulation System®Soffit With Expansion Joint

The architecture, engineering and design of the project using the

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

19 MM (3/4") MIN.

DRYVIT FINISH

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

SUBSTRATE

DRYVIT ADHESIVE

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

BY OTHERS DRYVIT OUTSULATION SYSTEM

OS 0.0.19

Page 22: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

version.

3. REFER TO DRYVIT PUBLICATION DS 173, FOR

APPLICATION ON EXTERIOR SOFFITS.

1. SOFFITS WITHOUT EPS INSULATION REQUIRE

EXPANSION JOINTS EVERY 6.096 M (20 FT).

2.

Soffit - Uninsulated

The architecture, engineering and design of the project using the

Outsulation®System

DRYVIT FINISH

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT ADHESIVE

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

SUBSTRATE

OS 0.0.20

BY OTHERS DRYVIT OUTSULATION SYSTEM

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

detail and for the architecture, design, engineering or workmanship of

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS. ®

DATE:REV:APPROVED BY:

25 MM (1") MAX.

SUBSTRATE

DRYVIT COMPATIBLE SEALANT

WITH BOND BREAKER, BY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN BASE COAT

NOTE:Dryvit products is the responsibility of the project's design

08/0612DAW

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

any project. The project design professional determines, in its sole

Page 23: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

®

DATE:REV:APPROVED BY:

203 MM (8") MIN.

SEE NOTES 2 AND 3

NOTE:

08/0612DAW

version.

3. DO NOT LAP REINFORCING MESH WITHIN

203 MM (8") OF A CORNER.

any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

2. DOUBLE WRAP OUTSIDE CORNERS WITH

REINFORCING MESH OR USE CORNER MESH.1.

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Outside CornersROutsulation SystemDryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

203 MM (8") MIN.

SEE NOTES 2 AND 3

SUBSTRATE

DRYVIT FINISH

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE

EPS INSULATION

OS 0.0.21

DRYVIT OUTSULATION SYSTEMBY OTHERS

Page 24: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT BASE COAT

NOTE:professional. All systems must comply with local building codes and

08/0612DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

without notice. Contact Dryvit to insure you have the most recent

APPROVED BY:

®

REV: DATE:

version.

1.

any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

203 MM (8") MIN.

Outsulation System® Outside Corner - High Impact

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT FINISH

PANZER® 15 OR 20

REINFORCING MESH

DRYVIT STANDARD OR STANDARD

PLUS REINFORCING MESH OVERLAP

MIN. 203 MM (8") AT CORNER

DRYVIT CORNER MESH

DRYVIT ADHESIVE

EPS INSULATION

DRYVIT BASE COAT

SUBSTRATE

OS 0.0.22

DRYVIT OUTSULATION SYSTEM

BY OTHERS

Page 25: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

OPTIONAL SECONDARY

SEAL, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

WRAP DRYVIT DETAIL

MESH® 51 MM (2") MIN.

AT UNDERSIDE OF EPS

(SEE NOTE 2)

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

19 MM (3/4") MIN.

NOTE:professional. All systems must comply with local building codes and

detail and for the architecture, design, engineering or workmanship of

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

08/0613DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

®

DATE:APPROVED BY: REV:

AS AN OPTION, THE REINFORCED

BASE COAT EDGE WRAP MAY BE

EXTENDED ONTO THE CONCRETE

EDGE AND/OR FRAMING.

1. 2.

Structural Expansion Joint

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

®Outsulation System

EPS INSULATION

DRYVIT ADHESIVE

FRAMING

SUBSTRATE

DRYVIT

OUTSULATION

SYSTEM

DRYVIT FINISH

BY OTHERS

SOLID SUBSTRATE

OS 0.0.23

Page 26: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative

1.and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

®Outsulation System Outsulation Expansion Joint - Dissimilar Substrates

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

DRYVIT COMPATIBLE SEALANT WITH

CLOSED-CELL BACKER ROD, BY OTHERS

19 MM (3/4") MIN.

DRYVIT FINISH

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

SUBSTRATE

BY OTHERS

FRAMINGSOLID SUBSTRATE

OS 0.0.24

DRYVIT ADHESIVE

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COATWRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

EPS INSULATION

DRYVIT

OUTSULATION

SYSTEM

NOTE:professional. All systems must comply with local building codes and

08/0612DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

®

APPROVED BY: REV: DATE:

Page 27: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

DRYVIT ADHESIVE

NOTE: professional. All systems must comply with local building codes and

08/0614RS

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

APPROVED BY:

®

REV: DATE:

2. AS AN OPTION, THE REINFORCED BASE

COAT EDGE WRAP MAY BE EXTENDED ONTO

THE FRAMING.

1.

any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

Outsulation System®Structural Expansion Joint - Inside Corner

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

FRAMING

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

(SEE NOTE 2)

19 MM (3/4") MIN.

OPTIONAL SECONDARY

SEAL, BY OTHERS

DRYVIT-COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

DRYVIT ADHESIVE

SUBSTRATE

OS 0.0.25

DRYVIT OUTSULATION SYSTEM BY OTHERS

Page 28: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

REV:APPROVED BY: DATE:

1. 2. AS AN OPTION, THE REINFORCED BASE

COAT EDGE WRAP MAY BE EXTENDED

ONTO THE FRAMING.

NOTE: professional. All systems must comply with local building codes and

08/0613RS

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

detail and for the architecture, design, engineering or workmanship of

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

®

The architecture, engineering and design of the project using the

Structural Expansion Joint - Outside Corner

Dryvit products is the responsibility of the project's design

Outsulation System®

DRYVIT OUTSULATION SYSTEMBY OTHERS

DRYVIT REINFORCING MESH

EMBEDDED IN BASE COAT

EPS INSULATION

DRYVIT FINISH

DRYVIT ADHESIVE

OPTIONAL SECONDARY

SEAL, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

(SEE NOTE 2)

19 MM (3/4") MIN.

DRYVIT COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

SUBSTRATE

OS 0.0.26

Page 29: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

AS AN OPTION, THE REINFORCED BASE

COAT EDGE WRAP MAY BE EXTENDED ONTO

THE FRAMING. any project. The project design professional determines, in its sole

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

1. 2.and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

PenetrationsOutsulation SystemThe architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

®

DRYVIT FINISH

DRYVIT ADHESIVE

DRYVIT DEMANDIT OR COLOR PRIME

ON SURFACES TO RECEIVE SEALANT

SUBSTRATE

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT UNDERSIDE OF EPS

(SEE NOTE 2)

OPTIONAL SECONDARY SEAL,

BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACES TO RECEIVE SEALANT

DRYVIT-COMPATIBLE SEALANT WITH

CLOSED CELL BACKER ROD, BY OTHERS

19 MM (3/4") MIN.

OS 0.0.27

DRYVIT OUTSULATION SYSTEMBY OTHERS

OPTIONAL SECONDARY SEAL

19 MM (3/4") MIN.

NOTE: professional. All systems must comply with local building codes and

08/0612DAW

DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

®

DATE:REV:APPROVED BY:

Page 30: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail

and Dryvit specifically disclaims any liability for the use of this

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

Outsulation System®Sign Attachment

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

12.7 MM (12") MIN.

DRYVIT REINFORCING

MESH EMBEDDED IN

DRYVIT BASE COAT

DRYVIT FINISH

SIGN FIXTURE

FRAMING

PIPE SLEEVE SET IN SEALANT

SCREW OR BOLT ATTACHMENT

TO BUILDING FRAMING OR

STRUCTURAL SUBSTRATE

BEARING WASHER

professional. All systems must comply with local building codes andPERIMETER OF PIPE SLEEVE IS CAULKED TO

PREVENT WATER ENTRY INTO WALL.

NOTE:

1.

05/0612DAW

version.

APPROVED BY:

®

DATE:REV:

DRYVIT-COMPATIBLE

SEALANT AND BOND

BREAKER TAPE, BY OTHERS

EPS INSULATION

BLOCKING OR STRUCTURAL

SUBSTRATE AS REQUIRED

DRYVIT ADHESIVE

SUBSTRATE

OS 0.0.28

DRYVIT

OUTSULATION

SYSTEMBY OTHERS

BY OTHERS

Page 31: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

OS 0.0.29

1.4 KG/M² (2.5 LBS/YD²) OR 1.8 KG/M²

(3.4 LBS/YD²) GALVANIZED EXPANDED

METAL LATH (BY OTHERS)

ATTACH METAL LATH TO STRUCTURAL

FRAMING USING APPROPRIATE

FASTENERS (BY OTHERS)

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE (KEYED INTO LATH)

SUBSTRATE

EPS INSULATION

BY OTHERS DRYVIT OUTSULATION SYSTEM

DRYVIT FINISH

METAL OR

WOOD STUDS

DRYVIT ADHESIVE (KEYED INTO LATH)

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

1.4 KG/M² (2.5 LBS/YD²) OR 1.8 KG/M²

(3.4 LBS/YD²) GALVANIZED EXPANDED

METAL LATH (BY OTHERS)

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

The architecture, engineering and design of the project using the

Outsulation Applied Over Metal Lath

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

version.

DATE:REV:APPROVED BY:

12DAW 08/06

DRYVIT FINISH

Outsulation System

NOTE:

®

BRICK, MASONRY

OR CONCRETE

CONSTRUCTION

EPS INSULATION

®

ATTACH METAL LATH TO SUBSTRATE

USING APPROPRIATE FASTENERS OR

ANCHORS (BY OTHERS)

Page 32: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

12

2. SLOPE BOTTOM EDGE OF REVEAL FOR

POSITIVE DRAINAGE.

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD

MESH™ OR STANDARD PLUS MESH™.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

professional. All systems must comply with local building codes and

DAW

version.

®

DATE:REV:APPROVED BY:

08/06

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

Aesthetic RevealsOutsulation System

NOTE:

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

®

DRYVIT DETAIL MESH®

EMBEDDED IN DRYVIT BASE COAT

19 MM (3/4") MIN.

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT OUTSULATION SYSTEMBY OTHERS

DRYVIT FINISH

FRAMING MEMBER

DRYVIT ADHESIVE

SUBSTRATE

OVERLAP 64 MM (2 1/2")

OS 0.0.30

Page 33: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

BY OTHERS

1. MAXIMUM THICKNESS OF EPS BUILT OUT

SHAPES SHALL NOT EXCEED 305 MM (12

INCHES) AT ANY POINT MEASURED FROM THE

SUBSTRATE

version.

PERCENTAGE OF WALL AREA COVERED BY

EPS FOAM SHAPES IN EXCESS OF 102 MM (4

IN.) IN THICKNESS SHALL NOT EXCEED 15%

®

REV: DATE:APPROVED BY:

05/0612DAW

2.discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

DRYVIT FINISH

DRYVIT ADHESIVE

OVERLAP 64 MM (2 1/2")

Outsulation SystemNOTE:

® Projecting Graphics

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

DRYVIT REINFORCING MESH

LAPPED 64 MM (2 1/2") MIN.

SUBSTRATE

DRYVIT

OUTSULATION

SYSTEM

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

EPS INSULATION

DRYVIT ADHESIVE

SUBSTRATE

OS 0.0.31

Page 34: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

SUBSTRATE

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

Recessed Graphics

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT REINFORCING MESH

LAPPED 64 MM (2 1/2") MIN.

Outsulation SystemNOTES:

®

DRYVIT ADHESIVEEPS INSULATION

BY OTHERS

DRYVIT

OUTSULATION

SYSTEM

OVERLAP 64 MM (2 1/2") MIN.

19 MM (3/4") MIN.

DRYVIT FINISH

DRYVIT FINISH

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

DRYVIT ADHESIVE

SUBSTRATE

OS 0.0.32

standards. This detail is for general information and guidance only1. SLOPE BOTTOM EDGE OF HORIZONTAL

RECESSES FOR POSITIVE DRAINAGE

detail and for the architecture, design, engineering or workmanship of

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of this

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

version.

DATE:REV:APPROVED BY:

11DAW 05/06

®

Page 35: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

FLASHING NO. 1, BY OTHERS,

EXTEND UP BEHIND FLASHING

NO. 2 76 MM (3") MIN.

REFER TO OS 0.0.34 FOR DECK

CUTAWAY DETAIL.

THESE DETAILS DO NOT APPLY TO

CANTILEVERED DECKS. CANTILEVERED DECKS

REQUIRE JOB SPECIFIC FLASHING DETAILS.

professional. All systems must comply with local building codes and

version.

DATE:APPROVED BY: REV:

05/066DAW

®

2. WHEN FLASHING NUMBER 1 IS IN PLACE, EPS

WILL NEED TO BE PRE WRAPPED WITH BASE

COAT AND MESH.

of any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative

and Dryvit specifically disclaims any liability for the use of

this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only

WRAP DRYVIT DETAIL MESH® 51 MM

(2") MIN. AT BACKSIDE OF EPS BOARD

SUBSTRATE

Outsulation® SystemNOTE:

1. 3.The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

Termination at Deck - Section

64 MM (2-1/2") MIN.

DRYVIT COMPATIBLE SEALANT

WITH BOND BREAKER, BY OTHERS

25 MM (1") MIN.

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

FLASHING NO. 3, BY OTHERS, EXTEND UP

BEHIND EPS INSULATION 76 MM (3")

WOOD SUPPORT STRIP

WOOD DECK FRAMING

FLASHING NO. 2, BY OTHERS, EXTEND UP

BEHIND FLASHING NO. 3 76 MM (3") MIN.

51 MM (2") MIN.

WOOD DECK BOARDS

DRYVIT FINISH

OS 0.0.33

DRYVIT ADHESIVE

EPS INSULATION

Page 36: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

DECK BOARD

professional. All systems must comply with local building codes and

THESE DETAILS DO NOT APPLY TO

CANTILEVERED DECKS. CANTILEVERED

DECKS REQUIRE JOB SPECIFIC FLASHING

DETAILS.

version.

DATE:REV:APPROVED BY:

05/066DAW

®

51 MM

(2") MIN.

DRYVIT COMPATIBLE

SEALANT WITH BOND

BREAKER, BY OTHERS

OS 0.0.34

REFER TO OS 0.0.33 FOR DECK SECTION DETAIL.2.of any project. The project design professional determines, in its sole

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

and Dryvit specifically disclaims any liability for the use of

this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only

Outsulation® SystemNOTES:

1.The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

Termination at Deck - Cut Away

END JOIST

FLASHING NO. 2,

BY OTHERS

FLASHING NO. 1,

BY OTHERS 51 MM (2") MIN.

FLASHING NO. 3, BY

OTHERS TURNED DOWN

OVER END JOIST

Page 37: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

METAL FLASHINGS ARE 254 MM (10") X 51 MM

(2") LONGER THAN THE EXPOSED PORTION OF

THE ROOFING SHINGLE AND ARE BENT IN HALF

TO ALLOW FOR TWO 127 MM (5") LEGS.

ALTHOUGH NOT SHOWN, METAL FLASHINGS ARE

STEP FLASHED (INTERWOVEN) WITH ROOFING

SHINGLES.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

EXTEND DIVERTER FLASHING

(KICKOUT) A MINIMUM OF 25 MM

(1") BEYOND FACE OF SYSTEM.

3. EXTEND ROOFING UNDERLAYMENT

127 MM (5") UP VERTICAL WALL

BEHIND METAL FLASHING.

DAW 05/063

APPROVED BY: REV: DATE:

2. ROOF DIVERTER TO BE MADE FROM

CORROSION RESISTANT MATERIAL MIN.

24 GAGE WITH WATER TIGHT SEAMS.

®

ROOF DIVERTER FLASHING,

BY OTHERS (SEE NOTE 2)

ROOF STEP FLASHING,

BY OTHERS

ROOFING UNDERLAYMENT,

BY OTHERS (SEE NOTE 3)

Termination at Sloped Roof

GUTTER SYSTEM SLOPED

AWAY FROM WALL

(6")

Outsulation® SystemNOTE:

4.1.

(12")305 MM

152 MM

152 MM(6")

110

ROOF DIVERTER

(NOTE 2)

100

DRYVIT FINISH

ROOFING SHINGLES

51 MM (2") MIN.

EPS INSULATION

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

SUBSTRATE

FRAMING

OS 0.0.35

Page 38: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

standards. This detail is for general information and guidance only

05/06

DATE:

1DAW

APPROVED BY: REV:

®

is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

version.

does not violate Dryvit's warranty. This detail is subject to change

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

and Dryvit specifically disclaims any liability for the use of this

DRYVIT COMPATIBLE

SEALANT, BY OTHERS

Outsulation SystemDryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the

®Termination at Roof Stop Flashing

ROOF SHINGLES

GLUED TO FLASHING

51 MM (2") MIN.

102 MM (4") MIN.

SHINGLES

ROOF STOP FLASHING,

BY OTHERS

ROOF/WALL FLASHING,

BY OTHERS

FASCIA BOARD

OS 0.0.36

Page 39: OUTSULATION - Dryvittest.dryvit.com/fileshare/doc/us/detail/ds107.pdfreinforced with panzer® mesh prior to standard mesh™ or standard plus mesh™. location of high impact zones

WATER-RESISTIVE BARRIER

EXTENDED BEHIND FLASHING,

BY OTHERS

professional. All systems must comply with local building codes and

RS 0 05/08

version.

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED TO

ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE

IMPACT HAVE THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD™ OR

STANDARD PLUS™ MESH. LOCATION OF HIGH

IMPACT ZONES SHOULD BE INDICATED ON

CONTRACT DRAWINGS.

APPROVED BY: REV: DATE:

1.

discretion, whether this detail or a functionally equivalent alternative

DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED LIEU OF DRYVIT

AQUAFLASH SYSTEM.is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only2.

NOTE:

Horizontal Joint At Stone Veneer

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

STONE VENEER SYSTEM, BY OTHERS

APPROVED SUBSTRATE

EPS INSULATION BOARD NOTCHED TO

ACCOMMODATE FLASHING

DRYVIT ADHESIVE

DRYVIT DEMANDIT® OR COLOR PRIME™

ON SURFACE(S) TO RECEIVE SEALANT

CONTINUOUS FLASHING, BY OTHERS

SEALANT WITH BOND

BREAKER, BY OTHERS

DRYVIT COMPATIBLE SEALANT WITH CLOSED

CELL BACKER ROD, BY OTHERS

19 MM (3/4") MIN.

DRYVIT FINISH

DRYVIT REINFORCING MESH

EMBEDDED IN BASE COAT

WRAP DRYVIT DETAIL MESH®

51 MM (2") MIN. AT BACKSIDE OF EPS

DRYVIT AQUAFLASH®

SYSTEM (SEE NOTE 2)

DRYVIT OUTSULATION SYSTEMBY OTHERS

OS 0.0.37

Outsulation® System