Up to Up to Up to Up to VersionVersionVersionVersion: P631/P632/P633/P634-309-40x-630-725 IssueIssueIssueIssue: a ReleaseReleaseReleaseRelease: 04 / 2012
MiCOM MiCOM MiCOM MiCOM P631/P632/P633/P634P631/P632/P633/P634P631/P632/P633/P634P631/P632/P633/P634 Transformer Differential ProtectionTransformer Differential ProtectionTransformer Differential ProtectionTransformer Differential Protection
Version Version Version Version HistoryHistoryHistoryHistory This document does not replace the Technical Manual
Contents
1.1.1.1. Device versions P63xDevice versions P63xDevice versions P63xDevice versions P63x----301301301301----40x40x40x40x----601 ff601 ff601 ff601 ff 3333
2.2.2.2. Device versions P63xDevice versions P63xDevice versions P63xDevice versions P63x----304304304304----40x40x40x40x----610 ff610 ff610 ff610 ff 10101010
3.3.3.3. Device versions P63xDevice versions P63xDevice versions P63xDevice versions P63x----308308308308----40404040xxxx----620 ff620 ff620 ff620 ff 16161616
4.4.4.4. Device versions P63xDevice versions P63xDevice versions P63xDevice versions P63x----308308308308----40x40x40x40x----630 ff630 ff630 ff630 ff 25252525
INSTIN, ооо инстин , http://inctin.com/ [email protected]
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/PMiCOM P631/P632/PMiCOM P631/P632/PMiCOM P631/P632/P633/P634633/P634633/P634633/P634 3
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
1. Device versions P63x-301-40x-601 ff
Version Changes
P631-301-401/402-601
P632-301-401/402-601
P633-301-401/402/403-601
P634-301-401/402-601
Release: 15.01.2001
Initial product release
Hardware No changes
Diagram No changes
Software
DVICE Cyrillic characters supported Analog (I/O) module Y supported
P631-301-40x-601-701
P632-301-40x-601-701
P633-301-40x-601-701
P634-301-40x-601-701
Release: 03.04.2001 COMM1 Communication interfaces supported with protocols
selectable by switch-over
P634-301-401/402-601-702
Release: 17.05.2001
This version has no release!
Hardware No changes
Diagram No changes
Software
DVICE Improved calibration algorithm.
P631-301-40x-601-703
P632-301-40x-601-703
P633-301-40x-601-703
P634-301-40x-601-703
Release: 02.08.2001
Hardware No changes
Diagram No changes
Software
DVICE Device types with ring-terminal connection supported.
P631-301-40x-601-704
P632-301-40x-601-704
P633-301-40x-601-704
P634-301-40x-601-704
Release: 17.12.2001
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 4
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
P631-302-401/402-602
P632-302-401/402-602
P633-302-401/402/403-602
P634-302-401/402-602
Release: 25.01.2002
Hardware Optional output board with 4 static make contacts is now available.
Optional communication board with 2 communication interfaces is now available.
Two options (with or without angle brackets) are offered for flush panel mounting. The dimensional drawings and required panel cutouts are shown in the Supporting Documents packed with the devices as are the location and terminal connection diagrams.
Diagram No changes
Software
PC Selection of spontaneous signals is now available (003 189) P C S e l e c t . s p o n t a n . s i g . )
Additional Timeout setting is available for coordination with new COMM2.
COMM1 Additional interface protocol: ”COURIER“.
Selection of spontaneous signals is now available for the interface protocols according to IEC 60870-5-103, IEC 60870-5-101 and ILS-C: (003 179) C O M M 1 S e l e c t . s p o n t a n . s i g .
Testing of spontaneous signals for the interface protocols according to IEC 60870-5-103, IEC 60870-5-101 and ILS-C (menu “Operation and control”).
COMM2 "Logical" Communication Interface 2 is now available.
MEASI Display of the PT100-measured temperature as per-unit value.
MAIN Separate setting for the secondary nominal current of the primary transformers for measurement of phase currents and transformer starpoint or residual currents: (010 142) M A I N I Y , n o m d e v i c e , e n d a (010 143) M A I N I Y , n o m d e v i c e , e n d b (010 144) M A I N I Y , n o m d e v i c e , e n d c
Assignment of the "logical" communication interfaces COMM1 and COMM2 to the physical communication channels of module A (003 169 M A I N C h a n n . a s s i g n . C O M M 1 / 2 ).
Grouping of the signals of measuring-circuit monitoring to form a multiple signal (036 155 M A I N M e a s . c i r c . I f a u l t y ).
DIFF New Signals: (041 221) D I F F I d > > t r i g g e r e d (041 222) D I F F I d > > > t r i g g e r e d
THRM1 to THRM2
Modified texts for some of the settings.
Per-unit measured values have been added.
The signals T H R M x : N o t r e a d y have been added.
MCM_1 to MCM_4
Measuring-circuit monitoring functions now available.
V/f Overfluxing protection function is now available.
LOGIC The number of binary input signals LOGIC: Input n EXT is increased from 16 to 40.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 5
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
DVICE Bug fixing: The device was blocked after power-up if either V<> or f<> was enabled, due to erroneous hardware self-identification.
P631-302-40x-602-705
P632-302-40x-602-705
P633-302-40x-602-705
P634-302-40x-602-705
Release: 19.04.2002
Hardware No changes
Diagram No changes
Software
LOC Bug fixing: Some cyrillic characters were displayed in a wrong way. This bug affected only the regional language character set of variant -805.
P631-302-40x-602-706
P632-302-40x-602-706
P633-302-40x-602-706
P634-302-40x-602-706
Release: 06.06.2002
Hardware No changes
Diagram No changes
Software
DVICE Bug fixing: A device ID for the entry of an order extension number was missing.
P631-302-401/402-603
P632-302-401/402-603
P633-302-401/402/403-603
P634-302-401/402-603
Release: 27.11.2002 DIFF Amplitude matching factor restrictions are relaxed.
Zero sequence current filtering for odd vector group IDs is improved.
Setting ranges of the tripping characteristic and of the unrestrained differential element are extended.
The hysteresis of the tripping characteristic can now be disabled.
Definite-time trip delay is available.
REF_1 REF_2 REF_3
Amplitude matching factor restrictions are relaxed.
Two new operating modes are available. One of them provides high impedance measuring principle.
Setting range of the unrestrained differential element is extended.
New tripping signals are provided for the application of low impedance REF on autotransformers.
IDMT1 IDMT2 IDMT3
Accuracy of tripping time is improved. Particularly the characteristic ‚IEC extremely inverse‘ is now within the claimed tolerance range.
f<> New measured fault data: In the event of under-frequency the minimum frequency is acquired and in the event of over-frequency the maximum frequency is acquired.
V/f Setting range of (081.213) V / f > > is extended.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 6
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
DTOC The instantaneous operation of the function has been set to higher priority to obtain shorter tripping times.
P631-302-40x-603-707
P632-302-40x-603-707
P633-302-40x-603-707
P634-302-40x-603-707
Release: 25.03.2003
Hardware No changes
Diagram No changes
Software
DIFF Bug fixing: The saturation discriminator did not operate correctly.
P631-302-40x-603-708
P632-302-40x-603-708
P633-302-40x-603-708
P634-302-40x-603-708
Release: 16.05.2003
Hardware No changes
Diagram No changes
Software
LOC Bug fixing: The LCD with Cyrillic characters was not correctly addressed.
P631-302-40x-603-709
P632-302-40x-603-709
P633-302-40x-603-709
P634-302-40x-603-709
-805
Release: 26.11.2003
Hardware No changes
Diagram No changes
Software
LOC French menu text modification.
P631-302-40x-603-709
P632-302-40x-603-709
P633-302-40x-603-709
P634-302-40x-603-709
-802
Release: 10.02.2004
Hardware No changes
Diagram No changes
Software
P631-302-40x-603-721
P632-302-40x-603-721
P633-302-40x-603-721
P634-302-40x-603-721
Release: 23.09.2009
COMM1 Bug fixing in the DNP protocol: Status signals were no more reported twice. For Px3x devices there are two kinds of DNP3 Binary Inputs. The first group is reported spontaneously from the protection or control application software, and from this report the value and timestamp are sent to the communication unit. The second group has no spontaneous report, only a static value which is polled cyclically and updated on the communication unit only if changed (for example the physical states of the LED's, binary opto-coupler inputs and relay outputs). In the previous protocol implementation some events were sent twice to the communication unit, by both methods mentioned above, but with different time stamps.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 7
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
This version is project-specific and only available on request!
There is no software version –604 available for the devices P631, P632, P633!
Hardware The Ethernet communication module is now available.
Diagram The new connection diagrams include the Ethernet communication module interfaces:
� P634.403 (for 84TE case, pin terminal connection) � P634.404 (for 84TE case, ring terminal connection)
Software
P634-303-403/404-604
Release: 09.10.2003
UCA2 Initial implementation of the UCA2 communication protocol.
P631-303-403/404-605
P632-303-403/404-605
P633-303-404/405/406-605
P634-303-403/404-605
Release: 30.04.2004
Hardware The new hardware variants now offer, per ordering option, additional operate thresholds for the binary signal inputs:
>18 V (standard variant) (no order ext. No.)
>90 V (60...70% of VA,nom = 125...150 V) (Order ext. No. 461)
>155 V (60...70% of VA,nom = 220..0.250 V) (Order ext. No. 462)
Installation of the standard variant is generally recommended if the application does not specifically require such binary signal inputs with higher operate thresholds.
The Ethernet communication module interface is now also available for the P631, P632 and P633.
Diagram The new connection diagrams include the Ethernet communication module interfaces:
� P631 -403 (for 40TE case, pin terminal connection) � P631 -404 (for 40TE case, ring terminal connection)
� P632 -403 (for 40TE case, pin terminal connection) � P632 -404 (for 84TE case, ring terminal connection)
� P633 -404 (for 40TE case, pin terminal connection) � P633 -405 (for 84TE case, pin terminal connection) � P633 -406 (for 84TE case, ring terminal connection)
Software
UCA2 Implementation of the UCA2 communication protocol in the P631, P632 and P633.
Extension to all 4 devices of the expanded spontaneous signaling range initially implemented in the P634-604. In addition, GOOSE messages and fault transmission are now supported.
SFMON If the same fault is detected after a warm restart has been triggered by the self-monitoring system (with no resetting of the alarm buffer since first entry), then the protective functions remained blocked (please also refer to chapters 3.13 [Self monitoring] and 10 [Troubleshooting] of the manual). This reaction has been changed in that way, that blocking now takes place only if the repeated occurrence of the fault takes place within a settable retention time (021 018 S F M O N M o n . s i g . r e t e n t i o n ). Thus it is possible, to tolerate sporadic faults without the necessity to reset the alarm buffer in between. For this improvement, the meaning of the time tag of the entry of the fault in the warning buffer had to be changed. Now, the date and time of the latest fault occurrence is memorised.
DIFF The saturation discriminator was further improved.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 8
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
P631-304-403/404-606
P632-304-403/404-606
P633-304-404/405/406-606
P634-304-403/404-606
Release: 20.05.2005
Hardware The new hardware variants now offer, per ordering option, additional operating thresholds for the binary signal inputs:
>18 V (standard variant) (no order ext. No.)
>90 V (60...70% of VA,nom = 125...150 V) (Order ext. No. 461)
>155 V (60...70% of VA,nom = 220..0.250 V) (Order ext. No. 462)
>73 V (67% of VA,nom = 110 V) (new) (Order ext. No. 463)
>146 V (67% of VA,nom = 220 V) (new) (Order ext. No. 464)
Installation of the standard variant is generally recommended if the application does not specifically require such binary signal inputs with higher operating thresholds.
A DSP coprocessor is now available as ordering option. This coprocessor provides enhanced features and overall better performance of the supplementary functions of the device. It is a prerequisit for using the new CT supervision function (CTS).
Diagram No changes
Software Note: Software version –606 is compatible to all previous hardware versions.
COMM1 Bug fixing in the IEC 60870-5-101 protocol:
o Support of the 7-byte time tag length has been corrected C O M M 1 T i m e t a g l e n g t h = ‚7 Byte’ (003 198).
o Transmission of negative cyclic measured values has been corrected.
o Acknowledgment of the general scan command has been corrected.
o Signals in the general scan are now transmitted correctly without a time tag.
o Command rejections issued internally by the protection device (between the processor module and communication module) are no longer signaled by the communication interface.
o Commands are now transmitted correctly, even when the ASDU address length is 2 byte C O M M 1 A d d r e s s l e n g t h A S D U = ‚2 Byte’ (003 193).
Bug fixing in the Courier protocol: Upon activation of Courier protocol a warm restart of the device was initiated.
MAIN Priority control of clock synchronisation is now settable.
Positive and negative sequence currents are now continuously calculated and displayed as per unit and primary metering values.
The functionality of virtual windings has been extended. Beside Addition of 2 windings it is now also possible to sum up currents of 3 windings and to subtract currents of 2 windings.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 9
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
SFMON In the course of platform harmonisation the configuration table of the user defined alarm condition has been accomplished by the instantaneous and timed outputs 30…32(t) of the programmable LOGIC:
098 053 SFMON Output 30 ~ 042 090 LOGIC Output 30
098 054 SFMON Output 30 (t) ~ 042 091 LOGIC Output 30 (t)
098 055 SFMON Output 31 ~ 042 092 LOGIC Output 31
098 056 SFMON Output 31 (t) ~ 042 093 LOGIC Output 31 (t)
098 057 SFMON Output 32 ~ 042 094 LOGIC Output 32
098 058 SFMON Output 32 (t) ~ 042 095 LOGIC Output 32 (t)
These signals can be used to create alarm signals under complex application conditions. This signaling has no influence on the device operation (i.e. no warm restart or blocking of the device takes place).
FT_RC The recording duration for binary tracks is now limited to 1 minute in order to prevent recording of endless events.
OL_RC, FT_RC
Overload and fault recording now use the same list of binary signals that might be entered into those records.
DIFF Setting ranges of the tripping characteristic slopes m1 and m2 have been extended down to 0.10 (previous limit: 0.15).
Saturation discriminator starting condition has been modified in that way that secondary injection tests of differential protection with conventional test sets (which do not provide correct transient signals) is possible again.
Along with the new CTS function, an additional threshold Idiff>(CTS) is provided to de-sensitise differential protection in case of a failure in the CT secondary circuit. For more details about this feature please refer to CTS description.
Bug fixing: In few cases the inrush stabilisation did not operate properly. Also sometimes the inrush signaling was not immediately reset in case of correct differential trips.
REF_1 REF_2 REF_3
Along with the new CTS function it is user settable, whether the REF protection for the faulty end is blocked or not. For more details about this feature please refer to CTS functional description.
CTS First implementation of a current transformer secondary wiring supervision function which operates fast enough to prevent differential protection from tripping under load in case of a CT failure. This function can only be used if the new processor board with DSP coprocessor is fitted!
MCM_1 MCM_2 MCM_3 MCM_4
The existing measuring circuit monitoring functions which are based on the phase currents per end got enhanced to use them for broken conductor protection applications.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 10
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
2. Device versions P63x-304-40x-610 ff
Version Changes
Hardware No changes
Diagram No changes
Software Note: Software version –606 is compatible to all previous hardware versions.
IEC Implementation of the new substation communication protocol per IEC 61850 standard.
P631-304-403/404-610
P632-304-403/404-610
P633-304-404/405/406-610
P634-304-403/404-610
Release: 03.2006
GSSE In conjunction with the IEC 61850 communication protocol a communication procedure has been implemented that is compatible with previous UCA2 GOOSE for the exchange of binary information within an Ethernet network section.
GOOSE For the exchange of binary information in an Ethernet network section the IEC 61850 communication procedure (IEC-GOOSE) has been implemented.
UCA2 The substation communication protocol per UCA2 standard is not supported with this firmware version.
MAIN Phase reversal logic is now available. This feature allows that the phase reversal switch in motor/generator applications can be located inside the protection zone of the transformer differential relay.
The vector group numbers of the power transformer are now settable per parameter subset. This feature can be used in protection of phase angle regulating transformers.
Bug fixing: The trip signals of the 3 measuring systems (e.g. 041.002 D I F F T r i p s i g n a l 1 ) were falsely instantaneously raised, regardless of the set trip delay time. (Note: 041.075 D I F F T r i p s i g n a l was correctly timed.)
Hardware No changes
Diagram No changes
Software Note: This version is not released for applications with IEC 61850 systems! Version -610-714 may be used as an alternative.
P631-305-40x-610-710
P632-305-40x-610-710
P633-305-40x-610-710
P634-305-40x-610-710
Release: 23.06.2006
DIFF Bug fixing: In versions -606 to -610 inrush signaling from all three measuring systems was suppressed when harmonic blocking in measuring system 1 was triggered. This was not accompanied by tripping. Nevertheless there was the possibility of an overreaction (tripping) when an inrush condition was not recognized by one measuring system with the operating mode set to "Not phase-selective" and in an other measuring system the second harmonic component reached a value of approximately between 70% and 130% of the fundamental.
FT_DA Bug fixing: The fault data for F T _ D A F a u l t c u r r . I Y , b p . u . (026 088) were mistakenly calculated on the basis of current IY,a.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 11
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
This version has no release!
P631-305-40x-610-711
P632-305-40x-610-711
P633-305-40x-610-711
P634-305-40x-610-711
Release: ---
Hardware No changes
Diagram No changes
Software Note: This version is not released for applications with IEC 61850 systems! Version -610-714 may be used as an alternative.
P631-305-40x-610-712
P632-305-40x-610-712
P633-305-40x-610-712
P634-305-40x-610-712
Release: 09.10.2006
IEC Bug fixing: The cause for a break in the client-server communications link after approximately 49 days for about 20 minutes has been removed. GOOSE and GSSE were not affected by this break in the client-server communications link.
Bug fixing: If communication was interrupted during control access via the Ethernet interface using the operating program MiCOM S1, renewed control access was only possible after a warm restart of the protection and control unit.
COMM1 The upgraded communications software 3.18 is now implemented. Various small bugs have been fixed in communication protocols per IEC 60870-5-101 and MODBUS.
Hardware No changes
Diagram No changes
Software Note: This version is not released for applications with IEC 61850 systems! Version -610-714 may be used as an alternative.
P631-305-40x-610-713
P632-305-40x-610-713
P633-305-40x-610-713
P634-305-40x-610-713
Release: 12.12.2006
MAIN Bug fixing: The sequence of M A I N : G e n e r a l s t a r t i n g (036 000) and D I F F : T r i p s i g n a l (041 075) have been changed such that starting always comes first.
Hardware No changes
Diagram No changes
Software
P631-305-40x-610-714
P632-305-40x-610-714
P633-305-40x-610-714
P634-305-40x-610-714
Release: 07.02.2007
IEC Bug fixing: The cause for a break in the client-server communications link after approximately 49 days for about 20 minutes has been removed. GOOSE and GSSE were not affected by this break in the client-server communications link.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 12
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware As an ordering option for the 40TE and 84TE model versions there is now a variant available with a detachable HMI. The detachable HMI is always supplied with a case width of 40TE.
The detachable HMI provides the following new features:
� Six freely configurable LEDs (H18 to H23) are situated next to six freely configurable function keys.
� All of the freely configurable LEDs (H4 to H16 and H18 to H23) are provided as multi-color type LEDs.
Note:
When the local control panel is ordered together with a detachable HMI for version -306, it is delivered with function keys and multi-coloured LED indicators fitted. Otherwise the earlier local control panel is delivered without having function keys and multi-coloured LED indicators fitted.
With version -307 and irrelevant of the ordering option, the local control panel is delivered with function keys and multi-coloured LED indicators fitted.
P631-306-405/406-611
P632-306-405/406-611
P633-306-407/408/409-611
P634-306-405/406-611
Release: 15.03.2007
P631-307-405/406-611
P632-307-405/406-611
P633-307-407/408/409-611
P634-307-405/406-611
Release: 05.11.2007
Diagram The updated connection diagrams now include the interfaces to connect the detachable HMI.
� P631 -405 (for 40TE case, pin-terminal connection) � P631 -406 (for 84TE case, ring-terminal connection)
� P632 -405 (for 40TE case, pin-terminal connection) � P632 -406 (for 84TE case, ring-terminal connection)
� P633 -407 (for 40TE case, pin-terminal connection) � P633 -408 (for 84TE case, pin-terminal connection) � P633 -409 (for 84TE case, ring-terminal connection)
� P634 -405 (for 40TE case, pin-terminal connection) � P634 -406 (for 84TE case, ring-terminal connection)
Software
LOC Because of the ordering option "detachable HMI" this additional Device Identification parameter is now available: L O C : L o c a l H M I exists (221 099).
LOC MAIN
Respective binary signal inputs (if previously unavailable) are assigned to all default reset functions. These binary input functions are now available in the configuration list for the two newly implemented group resetting functions as well as the extended functional assignment for the CLEAR key ('C'):
M A I N F c t . a s s i g n . r e s e t 1 (005 248) M A I N F c t . a s s i g n . r e s e t 2 (005 249) LOC A s s i g n m e n t r e s e t k e y (005 251)
Two menu jump lists may now be configured. These menu jump lists make it possible to select individual menu points (i.e. set values, counters, triggering functions, event logs) in a freely definable sequence.
L O C F c t . m e n u j m p l i s t 1 (030 238) L O C F c t . m e n u j m p l i s t 2 (030 239)
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 13
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
IEC Implementation of active monitoring of the communications data links to logged-on clients with the parameter I E C T C P k e e p - a l i v e t i m e r ( 1 0 4 0 6 2 ) . This active monitoring now replaces previous passive monitoring using parameter I E C I n a c t i v i t y t i m e r ( 1 0 4 0 5 0 ) .
Implementation of an automatic switchover to daylight saving time, activated by parameter I E C S w i t c h . d a y l . s a v . t i m e (104 219). Switchover times for the automatic switch to daylight saving time are governed by the following settings:
I E C D a y l . s a v . t i m e s t a r t (104 220) I E C D a y l . s a v . t i m e s t . d (104 221) I E C D a y l . s a v . t i m e s t . m (104 222) I E C D a y l . s a v . t . s t . 0 : 0 0 + (104 223) I E C D a y l . s a v . t i m e e n d (104 225) I E C D a y l . s a v . t i m e e n d d (104 226) I E C D a y l . s a v . t i m e e n d m (104 227) I E C D a y l . s a v . t . e n d 0 : 0 0 + (104 228)
A second SNTP server may now be applied for time synchronization. Should no answer be transmitted by the first SNTP server the next request is automatically transferred to the second SNTP server (backup function).
I E C S N T P s e r v e r 1 I P ( 1 0 4 2 0 2 ) I E C S N T P s e r v e r 2 I P ( 1 0 4 2 1 0 )
Instead of setting a router address and target network, so as to establish a communication link to a client situated exterior to the local network, now only the setting of the gateway address is required via I E C : G a t e w a y a d d r e s s (104 011).
Now 'unbuffered reports' are available for all logical nodes.
LED The new detachable HMI provides the following extended display functionalities:
� The operating mode for the LED indicators has been extended by the operating mode LED flashing.
� Two differing signals may now be assigned to the freely configurable LED indicators (H 4 to H 16 and H 18 to H 23) to emit either red or green light. If both assigned signals are active the resulting LED color will be 'amber' (yellow).
Configuration, operating mode and physical state of the permanently configured LED indicators H1 and H17 are now displayed via configuration parameters and physical state signals.
F_KEY The new detachable HMI provides 6 freely configurable function keys operated either as a key or switch with or without password protection.
CBF_1 ... CBF_4
Implementation of the new circuit breaker failure protection function including a current reset criterion. Depending on the number of ends on the protected object there are up to 4 function groups available.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 14
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
P631-30x-40x-611-715
P632-30x-40x-611-715
P633-30x-40x-611-715
P634-30x-40x-611-715
Release: 12.06.2007
IEC The ICD files have been modified. urcbMX has been added to the logical nodes PhsPDIF1, Rf1PDIF1, Rf2PDIF1 and Rf3PDIF2.
Implementation of the communication protocol IEC 61850 in these versions is KEMA certified.
LOC Bug fixing: Reset functions configured to the CLEAR key ('C') are now carried out correctly. A system restart could previously occur when the detachable HMI was disconnected.
FT_DA Bug fixing: The fault data for differential current and restraining current issued by the ground differential protection functions REF_2 and REF_3 are now also calculated correctly when the operating mode is set to "Low imped. / IP,max" (previously they had twice the value).
REF_1 ...REF_3
When the differential protection is triggered these functions are now blocked as long as at least one of the following conditions is met: D I F F M e a s . s ys t e m 1 t r i g g . (041 124) D I F F M e a s . s ys t e m 2 t r i g g . (041 125) D I F F M e a s . s ys t e m 3 t r i g g . (041 126)
CBF_1 ... CBF_4
Timer stages 't1 3p' and 't2' of functions CBF_2…CBF_4 are now processed regardless of the setting at CBF_1.
Hardware No changes
Diagram No changes
Software
P631-30x-40x-611-716
P632-30x-40x-611-716
P633-30x-40x-611-716
P634-30x-40x-611-716
Release: 31.08.2007
IEC The data model of the measured operating values for differential current and restraining current in the functions DIFF and REF_n is now implemented according to the data attributes for the standard WYE, ACT and ACD classes.
Note: With this implementation, the "phase" measured values from the DIFF protection functions correspond to the measured values of the three measuring systems: "phSA" = Measuring system 1 "phSB" = Measuring system 2 "phSC" = Measuring system 3
Accordingly the measured values from the REF_n protection functions are modeled as "neut".
ICD and PICS-MICS-ADL files have been upgraded accordingly.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 15
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
P631-30x-40x-611-717
P632-30x-40x-611-717
P633-30x-40x-611-717
P634-30x-40x-611-717
Release: 18.09.2008
DVICE Calibration process modified.
Hardware No changes
Diagram No changes
Software
P631-30x-40x-611-719
P632-30x-40x-611-719
P633-30x-40x-611-719
P634-30x-40x-611-719
Release: 30.01.2009
MAIN Bug fixing: In offline operation mode, measured operating values for phase C were not calculated correctly with the 60 Hz nominal frequency.
The measured operating values for the positive sequence currents are now calculated independently of the DTOC/IDMT protection functions.
Hardware No changes
Diagram No changes
Software
IEC Bug fixing: The incorrect scaling factor for Inom = 5A in the Comtrade files wascorrected.
P631-30x-40x-611-722
P632-30x-40x-611-722
P633-30x-40x-611-722
P634-30x-40x-611-722
Release: 27.05.2010 FT_RC The neutral current IN is scaled acc. to the nominal current of the
phase CT inputs (Inom) instead of the nominal current of the neutral CT input (IN,nom).
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 16
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
3. Device versions P63x-308-40x-620 ff
Version Changes
Hardware The binary I/O module X(4H) with four high-break contacts is now available.
With the P632/P633, the binary I/O module X(6I, 6O) for the control of up to three switchgear units is available as an additional option.
Diagram The updated connection diagrams now include the new binary I/O module X(4H) and the binary I/O module X(6I, 6O).
� P631 -407 (for 40TE case, pin-terminal connection) � P631 -408 (for 40TE case, ring-terminal connection)
� P632 -407 (for 40TE case, pin-terminal connection) � P632 -408 (for 84TE case, ring-terminal connection)
� P633 -410 (for 40TE case, pin-terminal connection) � P633 -411 (for 84TE case, pin-terminal connection) � P633 -412 (for 84TE case, ring-terminal connection)
� P634 -407 (for 84TE case, pin-terminal connection) � P634 -408 (for 84TE case, ring-terminal connection)
Software
P631-308-407/408-620
P632-308-407/408-620
P633-308-410/411/412-620
P634-308-407/408-620
Release: 06.06.2008
DVICE Calibration process modified.
With P632 and P633 up to 3 switchgear units may now be controlled but this requires that the device be fitted with module X (6I,6O) (see "Hardware" above).
The previous parameter D V I C E : O r d e r N o . (000 001) has been renamed to D V I C E : A F S O r d e r N o . (001 000).
LOC The previous parameters L O C A s s i g n m e n t r e s e t k e y (005 251) and L O C A s s i g n m e n t r e a d k e y (080 110) have been renamed to L O C F c t . r e s e t k e y (005 251) and L O C F c t . r e a d k e y (080 110) without any changes in their functionality.
Now the selection offered for the parameter L O C L a n g u a g e (003 020) no longer is between, e.g. German and English but between Regional language and Reference language. (This will not cause any changes in functionality as the Reference language is US English and the Regional language will depend on the language order option -8xx.)
COMM1 The menu point C O M M 1 - 1 0 3 p r o t . v a r i a n t (003 178) is now available when the communications protocol IEC 60870-5-103 is set.
GOOSE P632, P633 only: Several GOOSE signals have been added as part of the new control functionality. For a detailed listing see sections "Settings / Configuration Parameters" and "Information and Control Functions / Logic State Signals".
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 17
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
MAIN The following menu points are now available for each parameter subset (e.g. for PS1):
M A I N V n o m p r i m . e n d a P S 1 (019.017) M A I N V n o m p r i m . e n d b P S 1 (019.018) M A I N V n o m p r i m . e n d c P S 1 (019.019) M A I N V n o m p r i m . e n d d P S 1 (019.037)
The following parameter has been renamed: M A I N D e v i c e o n - l i n e (003.030) (previously: M A I N P r o t e c t i o n e n a b l e d )
The following parameters are now available for status signals from external devices (CBx = CB1 to CB4):
M A I N S i g . a s g . C B x o p e n (e.g. CB1 021.017) M A I N S i g . a s g . C B x c l o s e d (e.g. CB1 021.020)
Note: These signal assignment parameters are visible for 4 circuit breakers with P631, P632, P633 and P634. However, they can only be used with the P632 and P633 and only in accordance with the number of CBs supported.
In order to configure function keys with control functions the P632 and P633 have the following parameters available which may be assigned to four of the six function keys:
M A I N D e v i c e s e l e c t i o n k e y (006 001) M A I N D e v i c e O P E N k e y (006 002) M A I N D e v i c e C L O S E k e y (006 003) M A I N L o c a l / R e m o t e k e y (006 004)
The P632 and P633 now feature the acquisition of debounced binary signals for control functions, and the parameter M A I N T i m e t a g (221 098)
As part of the control functionality the P632 and P633 now feature additional parameters.
M A I N T yp e o f b a y (220 001) M A I N C u s t o m i ze d b a y t yp e (221 062)
MEASI The result of the temperature measurement may now be also read out as the maximum value since the last reset operation (temperature Tmax).
INP The setting I N P F i l t e r (010 220) is now available for conformity with standard IEC 60255-22-7, class A.
FT_DA Bug fixing: The wrong internal timing where the parameter F T _ D A R u n t i m e t o m e a s . (004 199) could take on the value 'Overflow' has been corrected.
THRM1, THRM2
Bug fixing: With the following menu points the step size for temperature values has be reduced from 0.01 to 0.001.
T H R M 1 O b j e c t t e m p . p . u . 1 (004 205) T H R M 2 O b j e c t t e m p . p . u . 2 (004 208) T H R M 1 C o o l a n t t e m p . p . u . 1 (004 206) T H R M 2 C o o l a n t t e m p . p . u . 2 (004 209)
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 18
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
CBF_x The parameter C B F _ 1 F u n c t i o n g r o u p C B F (056 007) h as been renamed to C B F _ 1 F u n c t i o n g r o u p C B F _ 1 (056 007) without any changes in the functionality.
The following parameters may now not only be set to an explicit time value but also to 'Blocked'.
C B F _ 2 D e l a y / f a u l t b e h . C B (022 227) C B F _ 3 D e l a y / f a u l t b e h . C B (022 240) C B F _ 4 D e l a y / f a u l t b e h . C B (022 254)
The startup criterion has been modified. After a CBF startup the state of the general trip signal or the external trigger signal are now no longer considered. The CBF will then only reset if the current criterion is met (current values to fall below I< with all three phases) or the CB state is open.
DEV01 to DEV03 (P632, P633 only)
New function groups "External Devices xx" (xx = 01, 02, 03) as part of the implementation of control functions.
ILOCK (P632, P633 only)
New function group "Interlocking Logic" as part of the implementation of control functions.
CMD_1 (P632, P633 only)
New function group "Single Pole Commands" as part of the implementation of control functions.
SIG_1 (P632, P633 only)
New function group "Single Pole Signals" as part of the implementation of control functions.
Hardware No changes
Diagram No changes
Software
DVICE Calibration process modified.
P631-308-40x-620-718
P632-308-40x-620-718
P633-308-40x-620-718
P634-308-40x-620-718
Release: 18.09.2008 IEC Bug fixing pertaining to the COMTRADE fault files which a client
receives via the IEC 61850 interface: The correct number of binary channels is now entered in the COMTRADE configuration file (*.cfg). In previous versions when, because of the function configuration, n*16 binary information was stored then the number of binary channels was given as n*16+1. Therefore the data stored in the *.cfg and the *.dat files did not match.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 19
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
IEC Bug fixing: The automatically generated data file names are now correct with fault numbers exceeding 999. Data file names are issued according to this format:
yyyymmdd_HHMMSS_xxx_rNNNN.eee With yyyy = year mm = month dd = day HH = hour MM = minute SS = second xxx = millisecond r = permanent single character NNNN = fault number eee = file extension
In previous versions the dot (.) was overwritten for fault numbers exceeding 999.
Stating of 'Control Modes' in the ICD file has been corrected. The device IEC data model is not affected by this.
LOC Bug fixing: Using the function where the set password can be made visible on the LC-display by pressing all four arrow keys simultaneously during the start up of the device is now also possible with the new local control panel (with function keys).
PSS Bug fixing: The time tags for the P S S P S x a c t i v e spontaneous signals (according to the communications protocol per IEC-60870-5-10x) and the entry in the operating data memory did not match.
MAIN Bug fixing: In off-line operation mode, measured operating values for phase C were not calculated correctly with the 60 Hz nominal frequency.
V<> Bug fixing: After a warm restart the following setting was not active: V<> tTransient PSx = Blocked (e.g. PS1: 076 029). Because of this, the following signals were issued when undervoltage conditions were present:
V < > : t V < e l a p s . T r a n s i e n t (042 023) V < > : t V < < e l a p s e d t r a n s . (042 025)
CBF_1 to CBF_4
The release condition for the function has been dissociated from the drop-out of the internal trip signal. Therefore the sequence will now only be stopped when a loss of load/undercurrent condition has occurred or when the CB signals that its contacts are open.
Bug fixing: The time tags for the C B F _ n R e a d y spontaneous signals (according to the communications protocol per IEC-60870-5-10x) and the entry in the operating data memory did not match.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 20
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
P631-308-407/408-621
P632-308-407/408-621
P633-308-410/411/412-621
P634-308-407/408-621
Release: 24.03.2009
DVICE The device’s capability to detect its hardware state has been enhanced so that future Ethernet communication and binary modules can be fitted without having to update the software.
The following addresses are now visible:
D V I C E S W v e r s i o n D H M I (002 131) D V I C E S W v e r s i o n D H M I D M (002 131)
IEC The processing times for the control and monitoring of switchgear units between the Ethernet communication module and the main CPU have been reduced.
Bug fixing: The standardized model according to WYE class (e.g. 'phsA' instead of 'adphsA') is now applied with the data model for measured values for current summation ('virtual end').
The data object LN_CFG has been extended in logical nodes Dt1NgsPTOC1, Dt2NgsPTOC1, Dt3NgsPTOC1.
Further logical nodes have been added:
LN PloGGIO4 to the P631 LN PloGGIO4, IdcGGIO1, RtdGGIO1 to the P633 and P634
The AlmGGIO logical node has been extended by the following signals:
Alm5: T H R M 1 C T A e r r o r (039 127) Alm6: T H R M 2 C T A e r r o r (039 187) Alm7: M E A S I P T 1 0 0 o p e n c i r c u i t (040 190) Alm8: M E A S I Over load 20mA input (040 191) Alm9: M E A S I Open c irc. 20mA inp. (040 192) Alm10: C T S O p e r a t e d ( u p d a t i n g ) (036 099)
The 'Bl.f.' data objects are now available in all nodes: PTOC, PTOV, PTUV, PTTR, PTOF, PTUF, RBRF, PVPH. Because of this, the 'Blocking EXT' condition has been removed from the 'MODE'.
The parameter I E C : D e a d b a n d V L L (104 232) has been renamed to I E C : D e a d b a n d V .
Since the corresponding measured values are not provided by the P63x, the following addresses have been deleted:
I E C D e a d b a n d V P G ( 104 233) I E C D e a d b a n d P (104 235) I E C D e a d b a n d Z (104 237) I E C D e a d b a n d A S C (104 239) I E C U p d a t e c yc l e e n e r g y (104 060)
COMM1 Bug fixing with the use of the MODBUS communication protocol: Faults can now be read out.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 21
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
MAIN The P633 and P634 now allow disconnection of individual ends by assigning functions to binary signal inputs.
Bug fixing: The measured operating values for the positive sequence currents are now calculated independently of the DTOC/IDMT protection functions.
Display of the following settings has been limited in accordance with the device function.
Visible only in the P632/P633 are:
M A I N S i g . a s g . C B 1 o p e n (021 017) M A I N S i g . a s g . C B 1 c l o s e d (021 020) M A I N S i g . a s g . C B 2 c l o s e d (021 060) M A I N S i g . a s g . C B 2 o p e n (021 061)
M A I N D e v i c e s e l e c t i o n k e y (006 001) M A I N D e v i c e O P E N k e y (006 002) M A I N D e v i c e C L O S E k e y (006 003) M A I N L o c a l / R e m o t e k e y (006 004)
Visible only in the P633 are:
M A I N S i g . a s g . C B 3 c l o s e d (021 062) M A I N S i g . a s g . C B 3 o p e n (021 063)
DIFF The starting condition for the saturation discriminator has been enhanced by the addition of a further minimum condition for the restraining quantity with basic filtering. Without this minimum condition, the saturation discriminator could be incorrectly triggered during the test of a characteristic using virtual test signals in the absence of a preload current.
REF_1 to REF_3
Blocking of the REF functions while the DIFF protection (functional enhancement by -611-715) has been triggered can now be enabled or disabled using setting parameters. Furthermore the REF_n: Blocking EXT binary signal input functions are now available to allow for a more flexible application of the functions. Since operational readiness is no longer solely depending on the device setting, its state is also signaled: REF_n: Ready (= enabled AND NOT blocked).
REF_1 The function has been enhanced so that further ends can be included into the protection zone, e.g. to provide ground differential protection for autotransformers (‘Autotransformer Wrap-around Differential’).
CBF_1 to CBF_4
As an option, the undercurrent criterion can now also be used with the residual current.
The external function startup may now occur either when only the undercurrent criterion is applied or also with the CB contact position criterion.
DEV02 to DEV03
Bug fixing: The menu text in the reference language (English) has been corrected for the following signals:
D E V 0 2 : S w i t c h . d e v i c e o p e n (218 002) corrected to: D E V 0 2 : O p e n c m d . r e c e i v e d
D E V 0 2 : S w i t c h . d e v i c e c l o s e d (218 003) corrected to: D E V 0 2 : C l o s e c m d . r e c e i v e d
etc. valid for all devices except DEV01.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 22
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
DIFF It could happen that triggering of the saturation discriminator by an external fault was not reset fast enough when an additional fault had occurred within the same protection zone. Such condition are now considered by an additional reset condition based on harmonic analysis of differential currents has been added to the saturation discriminator function.
P631-308-40x-621-720
P632-308-40x-621-720
P633-308-40x-621-720
P634-308-40x-621-720
Release: 31.08.2009
CBF_1 to CBF_4
Current flow monitoring has been improved to prevent chattering signalling during decaying DC current (with long time constants and values above I< threshold). The associated signal CBF_x: Current flow y (y=A, B, C) would sometimes jitter during an open command.
CBF start up and state signaling has been improved by optimizing the protection function tasks sequencing.
Hardware New Schneider-Electric design for the local control panel (HMI).
Diagram No changes
Software
P631-308-407/408-622
P632-308-407/408-622
P633-308-410/411/412-622
P634-308-407/408-622
Release: 09.02.2011
PC The following menu point has been removed: P C N a m e o f m a n u f a c t u r e r (003 183) Note: Compatibility even with older versions of the operating program continues to be guaranteed.
COMM1 The data point C O M M 1 - 1 0 3 p r o t . v a r i a n t (003 178) may now be used to select between the 103 protocol variants Private and Compatible. The protocol variant Compatible corresponds to the VDEW implementation. Note: As before this setting is hidden unless an IEC 60870-5 protocol is enabled.
The data point C O M M 1 M O D B U S p r o t . v a r i a n t (003 214) may now be used to select between the MODBUS protocol variants Private and Compatible. The protocol variant Compatible corresponds to the MODBUS implementation in the MiCOM Px20 and Px40 protection devices. The protocol variant Private corresponds to the first implementation of the MODBUS protocol. Note: As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1, COMM2
The menu points C O M M 1 N a m e o f m a n u f a c t u r e r (003 161) and C O M M 2 N a m e o f m a n u f a c t u r e r (103 161) can no longer be set by using a selection list but, for reasons of compatibility, they may now be defined as free text. The default is ‚SE’ but, in individual cases, it may become necessary to enter texts differing from the default. Notes: These parameters can only be set using the operating program and it is not possible to set them locally using the integrated local control panel (HMI). The maximum text length is 8 characters and designations exceeding this will be truncated. The parameter C O M M 1 : N a m e o f m a n u f a c t u r e r is hidden unless an IEC 60870-5 protocol is enabled.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 23
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
IEC Bug fixing: The implementation of the IEC 61850 signals RBRFn and the IEC 61850 modeling of IN in the Logical Nodes MMXU and MSQ has been modified so that it matches other MiCOM Px3x protection devices.
LED, MAIN, SFMON, CBF_4
The English designation texts of the following data points have been changed, but their functionality remains unchanged. The old designation is shown on the left and the new designation on the right hand side.
LED: Fct.assig. H12 rot ⇒ LED: Fct.assig. H12 red
SFMON: Unsuff. no. of ends ⇒ SFMON: Unsuff. No. of ends
MAIN: Disconnect End A EXT ⇒ MAIN: Disconnect End a EXT similar for MAIN: Disconnect End x MAIN: End x disconnected (old: x=A,B,C,D; new: x=a,b,c,d)
P634 only:
CBF_4: CB pos. implausibel ⇒ CBF_4: CB pos. implausible
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 24
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware No changes
Diagram No changes
Software
P631-308-407/408 -622-724
P632-308-407/408 -622-724
P633-308-410/411/412 -622-724
P634-308-407/408 -622-724
Release: 01.02.2012
IEC Upon receiving a "Cancel" command while a switchgear device is selected, a positive acknowledgement response ("Ack OK") is sent. Previously, a "Negative ack" was sent.
Bug fixing: If single-pole signals of function group SIG_1 were active during device startup, this could lead to an aborted initialization of the Ethernet communication module.
Bug fixing: If clients did connect to the device immediately after completion of Ethernet communication module startup, this could lead to the temporary erroneous reporting of default values for the external device status (DEVxx) and of the single-pole signals (SIG_1).
Bug fixing: During the process of connection with clients that use the "IntegrityPeriod" option, sporadically the MMS communication of the Ethernet communication module would crash without an internal monitoring response to re-establish the functionality. (GOOSE messaging and other communication tasks were not affected.)
Bug fixing: Reports of events could get lost, if too many state changes occurred in a short period of time, especially during secondary injection testing.
Bug fixing: If during device startup one of the configured inputs of function group SIG_1 is active, the initialisation of the Ethernet communication module may have failed.
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is enhanced with respect to simultaneous state changes of multiple GOOSE messages.
COMM1 Bug fixing: A change of the setting (003.161) C O M M 1 : N a m e o f m a n u f a c t u r e r became active only after a device reboot.
PC, COMM2
Bug fixing: If clients did connect to the device immediately after startup of the Ethernet communication module, the initialization of the second internal communication interface could remain incomplete. As a consequence, access by the operating program via the COMM2 interface or by tunneling was not possible in this case.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 25
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
4. Device versions P63x-308-40x-630 ff
Version Changes
Hardware New Schneider-Electric design for the local control panel (HMI).
Diagram No changes
Software
P631-308-407/408-630
P632-308-407/408-630
P633-308-410/411/412-630
P634-308-407/408-630
Release: 09.02.2011
DVICE The new data point (008 233) D V I C E S W v e r s . C h i n . D H M I D M is a purely internal version number (for the order option "Chinese display").
Bug fixing: Display problems with the Fault Panel are resolved.
IEC, GOOSE
Phase 2 of the IEC 61850 communications protocol has been implemented. See section "Communication Interface IEC 61850 (Function Group IEC)" for a detailed description of the numerous function enhancements carried out.
IEC Bug fixing: The implementation of the IEC 61850 signals RBRFn and the IEC 61850 modeling of IN in the Logical Nodes MMXU and MSQ has been modified so that it matches other MiCOM Px3x protection devices.
PC The following menu point has been removed: P C N a m e o f m a n u f a c t u r e r (003 183) Note: Compatibility even with older versions of the operating program continues to be guaranteed.
COMM1 The data point C O M M 1 - 1 0 3 p r o t . v a r i a n t (003 178) may now be used to select between the 103 protocol variants Private and Compatible. The protocol variant Compatible corresponds to the VDEW implementation. Note: As before this setting is hidden unless an IEC 60870-5 protocol is enabled.
The data point C O M M 1 M O D B U S p r o t . v a r i a n t (003 214) may now be used to select between the MODBUS protocol variants Private and Compatible. The protocol variant Compatible corresponds to the MODBUS implementation in the MiCOM Px20 and Px40 protection devices. The protocol variant Private corresponds to the first implementation of the MODBUS protocol. Note: As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1 (P632 and P633 only)
Communications protocol IEC 60870-5-103: When checking during test operations it is now possible to trigger signals (SIG) and contact positions (DEV) from the control part (previously only possible from the protection part).
These new addresses were added:
C O M M 1 S e l . p o s . d e v . t e s t (221 105) – Not assigned – DEV01 to DEV03
C O M M 1 T e s t p o s i t i o n d e v . (221 106) – don't execute – execute open – execute close – execute intermed.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 26
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
COMM1, COMM2
The menu points C O M M 1 N a m e o f m a n u f a c t u r e r (003 161) and C O M M 2 N a m e o f m a n u f a c t u r e r (103 161) can no longer be set by using a selection list but, for reasons of compatibility, they may now be defined as free text. The default is ‚SE’ but, in individual cases, it may become necessary to enter texts differing from the default. Notes: These parameters can only be set using the operating program and it is not possible to set them locally using the integrated local control panel (HMI). The maximum text length is 8 characters and designations exceeding this will be truncated. The parameter C O M M 1 : N a m e o f m a n u f a c t u r e r is hidden unless an IEC 60870-5 protocol is enabled.
MAIN New logic state signal for clock synchronization. The parameter M A I N T i m e s yn c h r o n i ze d (009 109) shows whether an external clock synchronization had been carried out. This signal is reset after 10 minutes.
Bug fixing: Settings for daylight saving time were reset after a warm restart.
V/f The setting range for V / f t a t V / f = 1 . 0 5 P S x has been extended: Previously: 1.0 s to 1000.0 s in steps of 0.1 s, Now: 1.0 s to 6000.0 s in steps of 0.1 s.
Similarly, the setting range for V / f R e s e t t i m e P S x has been extended: Previously: 0 s to 10000 s in steps of 1 s, Now: 0 s to 60000 s in steps of 1 s.
DEV01 to DEV03
Device identifiers can now be edited.
In the "Designat. ext. dev." parameters the 'Device Name User' setting should be selected. Then the text for the device's name, entered by the user at each of the "DEV-Name User" parameters, will be used as the device’s designation. The maximum number of 4 characters was not changed from the previous permanent default setting
D E V x x : D E V - N a m e U s e r (218 101, 218 102, 218 103)
IEC Bug fixing: The implementation of the IEC 61850 signals RBRFn and the IEC 61850 modeling of IN in the Logical Nodes MMXU and MSQ has been modified so that it matches other MiCOM Px3x protection devices.
LED, MAIN, SFMON, CTS, CBF_4
The designation text of the following data point has been changed, but the functionality remains unchanged. The left side shows the old designation and the right side shows the new designation.
LED: Fct.assig. H12 rot ⇒ LED: Fct.assig. H12 red
SFMON: Unsuff. no. of ends ⇒ SFMON: Unsuff. No. of ends
CTS: Reset latching EXT ⇒ CTS: Reset latch. EXT
MAIN: Disconnect End A EXT ⇒ MAIN: Disconnect End a EXT similar for MAIN: Disconnect End x MAIN: End x disconnected (old: x=A,B,C,D; new: x=a,b,c,d)
P634 only:
CBF_4: CB pos. implausibel ⇒ CBF_4: CB pos. implausible
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 27
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
Hardware The P63x is now fitted with an improved power supply module.
With hardware index -308 a new communication module (“REB” = “Redundant Ethernet Board”) is now available as an ordering option.
A detailed description of the module and the appropriate network connections is available as a separate document (“Redundant Ethernet Board, Application Guide”).
Diagram The new diagrams now include the new “REB” module.
� P631 -409 (for 40TE case, pin-terminal connection) � P631 -410 (for 40TE case, ring-terminal connection)
� P632 -409 (for 40TE case, pin-terminal connection) � P632 -410 (for 84TE case, ring-terminal connection)
� P633 -413 (for 40TE case, pin-terminal connection) � P633 -414 (for 84TE case, pin-terminal connection) � P633 -415 (for 84TE case, ring-terminal connection)
� P634 -409 (for 84TE case, pin-terminal connection) � P634 -410 (for 84TE case, ring-terminal connection)
Software
P631-309-409/410-630-725
P632-309-409/410-630-725
P633-309-413/414/415-630 -725
P634-309-409/410-630-725
Release: 01.02.2012
IEC Upon receiving a "Cancel" command while a switchgear device is selected, a positive acknowledgement response ("Ack OK") is sent. Previously, a "Negative ack" was sent.
The Originator Category information is now extensively supported for control commands.
Bug fixing: If single-pole signals of function group SIG_1 were active during device startup, this could lead to an aborted initialization of the Ethernet communication module.
Bug fixing: If clients did connect to the device immediately after completion of Ethernet communication module startup, this could lead to the temporary erroneous reporting of default values for the external device status (DEVxx) and of the single-pole signals (SIG_1).
Bug fixing: During the process of connection with clients that use the "IntegrityPeriod" option, sporadically the MMS communication of the Ethernet communication module would crash without an internal monitoring response to re-establish the functionality. (GOOSE messaging and other communication tasks were not affected.)
Bug fixing: Events that occured after a communication link had been interrupted and before this interruption had been detected by the server, were not sent as "Buffered reports" after the connection was re-established.
Bug fixing: Reports of events could get lost, if too many state changes occurred in a short period of time, especially during secondary injection testing.
Notice: It is not possible to read the IEC configuration back from the device, if the dataset size(s) exceed(s) the GOOSE size limit significantly.
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 28
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Version Changes
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is enhanced with respect to simultaneous state changes of multiple GOOSE messages.
COMM1 Bug fixing: A change of the setting (003.161) C O M M 1 : N a m e o f m a n u f a c t u r e r became active only after a device reboot.
PC, COMM2
Bug fixing: If clients did connect to the device immediately after startup of the Ethernet communication module, the initialization of the second internal communication interface could remain incomplete. As a consequence, access by the operating program via the COMM2 interface or by tunneling was not possible in this case.
SFMON The device module check has been enhanced to accept the new redundant Ethernet module only with the new power supply module („PSU2“). If a wrong PSU is fitted, one of the following monitoring signals is recorded: 40TE case: S F M O N : W r o n g m o d u l e s l o t 9 (097.008). 84TE case: S F M O N : W r o n g m o d u l e s l o t 2 0 (097.019).
[[[[Multifunction IED's] ] ] ] MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634MiCOM P631/P632/P633/P634 29
P631/P632/P633/P634-309-40x-630-725 Schneider Electric Energy Transformer Differential Protection
Schneider Electric As standards, specifications and designs change from time to time, please ask for contribution
35, rue Joseph Monier – CS30323 of the information given in this publication. F - 92500 Rueil-Malmaison cedex (France)
Tel: +33 (0)1 41 29 85 00
Fax: +33 (0)1 41 29 71 00
RCS Nanterre 954 503w
Capital social 896 313 776 € Design: Schneider Electric
ww.schneider-electric.com Photos: Schneider Electric
EnergyAutomation-MiCOM P631/P632/P633/P634– History-EN 04 / 2012
2011 Schneider Electric. All rights resereved