Panel Bus I/O Modules Product Data Copyright © 2019 Honeywell GmbH ● All Rights Reserved EN0Z-0979GE51 R1219 GENERAL The CentraLine Panel Bus I/O Modules communicate via the Panel Bus. The pluggable CentraLine Panel Bus I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connec- tions: Simply unplug the "old" and insert the "new" module. WARNING Risk of electric shock or equipment damage! Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install the control system. More than one disconnect switch may be required to de-energize the system. Do not reconnect the power supply until you have completed the installation. Unused terminals must be closed (by completely screwing in the terminal screws), thus preventing the accidental touching of "live" parts. The mixed CentraLine Panel Bus I/O modules offer a mix of 34 inputs and outputs in a compact housing. Software updates, configuration, and commissioning are all done automatically by the controller for all Panel Bus I/O Modules. The Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Panel Bus I/O Modules may be used with any CPU supporting Panel Bus communication (e.g., the LION, EAGLE, etc.). FEATURES Plug-and-play functionality for easy maintenance. Pluggable Panel Bus I/O modules can be exchanged without rewiring. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase. Fast wiring with state-of-the-art push-in terminals (screw- type terminals also available) and bridge connectors. Wide range of sensors supported (NTC20kΩ, NTC10kΩ, PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed Panel Bus I/O modules CLIOP830A and CLIOP831A feature inputs suitable for signals from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only! Binary input LEDs of the pluggable CentraLine Panel Bus I/O Modules can be configured for status display (off / yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules CLIOP830A and CLIOP831A feature only non-configurable binary input LEDs! Configurable safety position for outputs, in case of loss of communication with the controller. Max. wiring flexibility due to optional accessories like auxiliary terminals and cross-connectors. Can be mounted in small installation housings Flexible mix of Panel Bus I/O modules covering all your application requirements.

Panel Bus I/O Modules Product Data - CentraLine · 2020. 8. 11. · PANEL BUS I/O MODULES – PRODUCT DATA 3 EN0Z-0979GE51 R1219 Table 2. Overview of auxiliary parts and spare parts

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

  • Panel Bus I/O Modules Product Data

    Copyright © 2019 Honeywell GmbH ● All Rights Reserved EN0Z-0979GE51 R1219

    GENERAL The CentraLine Panel Bus I/O Modules communicate via the Panel Bus. The pluggable CentraLine Panel Bus I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connec-tions: Simply unplug the "old" and insert the "new" module.

    WARNING

    Risk of electric shock or equipment damage! ► Do not touch any live parts in the cabinet. ► Disconnect the power supply before you start to install

    the control system. More than one disconnect switch may be required to de-energize the system.

    ► Do not reconnect the power supply until you have completed the installation.

    ► Unused terminals must be closed (by completely screwing in the terminal screws), thus preventing the accidental touching of "live" parts.

    The mixed CentraLine Panel Bus I/O modules offer a mix of 34 inputs and outputs in a compact housing. Software updates, configuration, and commissioning are all done automatically by the controller for all Panel Bus I/O Modules. The Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Panel Bus I/O Modules may be used with any CPU supporting Panel Bus communication (e.g., the LION, EAGLE, etc.).

    FEATURES Plug-and-play functionality for easy maintenance. Pluggable Panel Bus I/O modules can be exchanged

    without rewiring. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase.

    Fast wiring with state-of-the-art push-in terminals (screw-type terminals also available) and bridge connectors.

    Wide range of sensors supported (NTC20kΩ, NTC10kΩ, PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed Panel Bus I/O modules CLIOP830A and CLIOP831A feature inputs suitable for signals from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only!

    Binary input LEDs of the pluggable CentraLine Panel Bus I/O Modules can be configured for status display (off / yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules CLIOP830A and CLIOP831A feature only non-configurable binary input LEDs!

    Configurable safety position for outputs, in case of loss of communication with the controller.

    Max. wiring flexibility due to optional accessories like auxiliary terminals and cross-connectors.

    Can be mounted in small installation housings Flexible mix of Panel Bus I/O modules covering all your

    application requirements.

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 2

    OVERVIEW

    CLIOP821A CLIOP822A

    CLIOPR822A

    CLIOP823A CLIOP824A

    CLIOPR824A CLIOPR825A

    1 2 3 4 5 6 7 8 9 10 11 12B1 B2 B3 B4 B5 B6

    B12126

    B11115

    B10104

    B993

    B882

    B771

    DI

    Binary Inputs

    G1 G241 42

    GND Analog Outputs

    AI2 AI3 AI414 15 16

    AI1

    17 18 19 2013

    Analog InputsAO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO42125 26 27 28

    22 23 24

    DO

    24V Relays

    NO1 NO2 NO3 NO4 NO5 NO6

    CO1 CO2 CO3 CO4 CO5 CO63529 30 31 32 33 34

    36 37 38 39 40

    1 2 3 4 5 6Install. Instr.MU1B-0473GE51

    !

    AI5 AI6 AI7 AI8

    CentraLine

    CLIOP830A

    XS821-22XSU821-22CONTROLLER

    XS823XSU823

    XS824-25XSU824-25

    PANELBUS MODULES

    pluggableANALOG OUTPUT

    pluggableANALOG INPUT

    pluggableBINARY INPUT

    pluggableFLOATINGOUTPUT

    MIXED I/Os(with integrated socket)

    pluggableRELAY OUTPUT

    Panel Bus

    1 2 3 4 5 6 7 8 9 10 11 12B1 B2 B3 B4 B5 B6

    B12126

    B11115

    B10104

    B993

    B882

    B771

    DI

    Binary Inputs

    G1 G241 42

    GND Analog Outputs

    AI2 AI3 AI414 15 16

    AI1

    17 18 19 2013

    Analog InputsAO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO42125 26 27 28

    22 23 24

    DO

    24V Relays

    NO1 NO2 NO3 NO4 NO5 NO6

    CO1 CO2 CO3 CO4 CO5 CO63529 30 31 32 33 34

    36 37 38 39 40

    1 2 3 4 5 6Install. Instr.MU1B-0473GE51

    !

    AI5 AI6 AI7 AI8CentraLine

    CLIOP830ACLIOP831A

    CLIOP831A

    Fig. 1. Overview of CentraLine Panel Bus I/O Modules

    Table 1. Overview of CentraLine Panel Bus I/O Modules

    order number description Pluggable Panel Bus I/O Modules CLIOP821A Pluggable Panel Bus Analog Input Module (with 8 analog inputs) CLIOP822A Pluggable Panel Bus Analog Output Module (with 8 analog outputs) CLIOPR822A Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides) CLIOP823A Pluggable Panel Bus Binary Input Module (with 12 binary inputs) CLIOP824A Pluggable Panel Bus Relay Output Module (with 6 relay outputs) CLIOPR824A Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides) CLIOPR825A Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)

    Mixed Panel Bus I/O Modules with integrated socket CLIOP830A Mixed Panel Bus I/O Module (with 8 AIs, 8 AOs, 12 BIs, and 6 ROs); housing fits to LION Controller housing CLIOP831A Mixed Panel Bus I/O Module (with 8 AIs, 8 AOs, 12 BIs, and 6 ROs); housing fits to EAGLE Controller housing

    Terminal Sockets (not needed for the mixed I/O modules CLIOP830A and CLIOP831A) XS821-22 Push-in terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label) XSU821-22 Screw-type terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label) XS823 Push-in terminal socket for pluggable BI modules (incl. bridge connector, swivel label) XSU823 Screw-type terminal socket for pluggable BI modules (incl. bridge connector, swivel label)

    XS824-25 Push-in terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)

    XSU824-25 Screw-type terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 3

    Table 2. Overview of auxiliary parts and spare parts order number description

    XS814

    Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.

    XS830A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9

    Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of two groups of nine internally-connected push-in terminals. For CLIOP830 and CLIOP831, only.

    XS831A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8

    Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block consists of two groups of four pairs of push-in terminals (each with a 499Ω resistor to GND) for supporting up to eight current inputs. For CLIOP830A and CLIOP831A, only.

    XS815

    20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package. For pluggable I/O modules, only.

    XS816

    10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.

    XAL10

    10 Swivel Labels (for attaching the application-specific label printed with CARE / COACH AX / COACH NX). One Swivel Label is included in the Terminal Socket package.

    XAL11

    10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each mixed I/O module package. For mixed I/O modules, only. NOTE: Phased out.

    NOTE: The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit,

    24 VAC +20%, and 40 VDC. In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents are not exceeded. See also sub-section "Features" in section "Relay Output Modules" (pg. 15), "Floating Output Module" (pg. 18), and "Mixed I/O Modules" (pg. 20).

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 4

    Table 3. Pluggable Panel Bus I/O Module specifications

    Module Analog Inputs Analog Outputs Binary Inputs Relay Outputs Floating Outputs

    CLIOP821A CLIOP822A, CLIOPR822A

    CLIOP823A CLIOP824A, CLIOPR824A CLIOPR825A

    no. of I/Os

    8 analog inputs 8 analog outputs 12 binary inputs re-quiring a gold con-tact or open collector

    6 relay outputs 3 floating outputs

    charac-teristic

    Linear Graph, 0...10 VDC with pull-up, 0(2)…10 VDC without pull-up NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…150 °C) PT1000-2 (0…400 °C) Johnson A99 (-40…+120 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…150 °C) BALCO500 (-30…120 °C) Also configurable as: binary inputs Linear graph (0…10 V with

    pull-up) Features: 16-bit resolution configurable offset per input auxiliary voltage: 10 VDC,

    Imax = 5 mA

    0…11 VDC / 1 mA, 8-bit resolution (default) Also configurable as: floating outputs or binary outputs (0 V / 10 V) Features: 8-bit resolution Safety position

    (remain, 0%, 50%, 100%) red LED per output light intensity follows

    output level in auto Version with manual override (R): 1 potentiometer per

    output auto feedback signal

    (mode + value) blinking in manual

    override position

    static binary input, (default: dry contact)Also configurable as: totalizers (20 Hz) Features: 1 LED per input Color mode can

    be set per input to OFF/yellow or green/red using CARE / COACH AX / COACH NX ON: < 1.6 kΩ to

    GND or < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND

    relay outputs (default) Features: Changeover relays Voltage:

    19…250 VAC, 1…29 VDC, P>50 mW max. total current:

    12 A current per relay:

    N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) Safety position

    (remain, 0%, 100%) yellow LED per output Version with manual override (R): 1 switch per output auto feedback signal

    (mode + value) blinking in manual

    override position

    floating outputs Features: 2 relays per

    floating output Voltage:

    19…250 VAC, 1…29 VDC, P>50 mW max. total current:

    12 A current per relay:

    N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) 1 potentiometer per

    floating output 2 LEDs per output:

    green: relay 1 closed, red: relay 2 closed blinking in manual

    override position auto feedback

    signal (mode + value)

    Manual Overrides as per EN ISO 16484-2:2004 The manual override switches and potentiometers of the output modules (…R822A, …R824 A, and CLIOPR825A) support direct operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units." Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the given override position to the controller (which will then also store this information in its alarm memory). NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their

    manual override switches and/or potentiometers.

    Table 4. Mixed CentraLine Panel Bus I/O module specifications (CLIOP830A and CLIOP831A)

    Analog Inputs Analog Outputs Binary Inputs Relay Outputs Number: 8 Configurable types: NTC20kΩ (-30…+110 °C)

    (default) Linear Graph 0...10 VDC with pull-up 0(2)…10 VDC without pull-up Also configurable as: binary inputs (static, dry

    contact, only) Features: 10-bit resolution configurable offset per input

    Number: 8 Configurable types: 0…11 VDC / 1 mA (default) Also configurable as: binary outputs (0 V / 10 V) Features: 10-bit resolution (default) Safety position (remain, 0%,

    50%, 100%)

    Number: 12 (requiring a gold contact or open collector) Configurable types: Static binary inputs (default:

    static, dry contact) ON: < 1.6 kΩ to GND or

    < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND

    Also configurable as: totalizers (15 Hz) Features: 1 yellow LED per input

    Number: 6 Configurable types: Relay outputs (default) Features: Voltage: 24 VAC/DC,

    P>50 mW max. total current: 3 A

    (AC/DC) current per relay: 500 mA normally-open contacts: P >

    50 mW, voltage: 24 V (AC/DC) 1 yellow LED per output

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 5

    GENERAL FEATURES

    PRESS PRES

    S PRESS PRES

    S

    1 2 3 Honeywell

    AUTO0

    !

    A A A100

    S1 S2210 F E DCB

    9876

    543

    A

    71 COM a

    72 COM b

    73 24V~

    74 24V 0~

    21

    22

    23

    14 4424 5434 64 25

    13

    12

    11 31

    32

    33

    41

    42

    43

    51

    52

    53

    61

    62

    61

    62

    6363

    1 2 3 4 5 6 7 8 Honeywell

    AUTO0

    !

    A A A A A A A A100

    S1 S2210 F EDCB

    9876

    543

    A

    21

    9

    GND GND

    AI/AOVAUX

    10 11 12 13 14 15 16 17 18 25 26

    22 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 Honeywell

    --1--0--AUTO

    !

    S1 S2210 F E DCB

    9876

    543

    A

    21

    22

    23

    14 4424 5434 64 25

    13

    12

    11 31

    32

    33

    41

    42

    43

    51

    52

    53

    61

    62

    61

    62

    6363

    1 2 3 4 5 6 7 8 Honeywell

    !

    21

    9

    GND GND

    AI/AOVAUX

    10 11 12 13 14 15 16 17 18 25 26

    22 1 2 3 4 5 6 7 8

    GND

    BI

    13 14 15 16 17 18 19 20 21 22 23 24 25 26

    1 2 3 4 5 6 7 8 9 10 11 12

    1 2 3 4 5 6 7 8 9 10 11 12 Honeywell

    !

    S1 S2210 F EDCB

    9876

    543

    A

    71 COM a

    72 COM b

    73 24V~

    74 24V 0~

    PRESS PRES

    S

    1:ABCDFERTAQWESDERT12:ABCDFERTAQWESDERT23:ABCDFERTAQWESDERT34:ABCDFERTAQWESDERT45:ABCDFERTAQWESDERT56:ABCDFERTAQWESDERT67:ABCDFERTAQWESDERT78:ABCDFERTAQWESDERT8

    3 42

    6 7

    571 COM a

    72 COM b

    73 24V~

    74 24V 0~

    1

    Fig. 2. CentraLine Panel Bus I/O Modules on DIN rails

    Legend 1 Controller (e.g., LION, EAGLE, HAWK, etc.) 2 Cable (power, Panel Bus) connection from controller to

    Panel Bus I/O Modules 3 Swivel label holder 4 Cable connection between Panel Bus I/O Modules on

    separate DIN rails 5 Bridge connectors between Panel Bus I/O Modules on

    same DIN rail 6 Stopper (from 3rd-party supplier) 7 Auxiliary terminal packages LEDs Each CentraLine Panel Bus I/O Module is equipped with: one green power LED one yellow service LED Overvoltage Protection The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit, 24 VAC +20%, and 40 VDC. In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents are not exceeded. See also sub-section "Features" in section "Relay Output Modules" (pg. 15), "Floating Output Module" (pg. 18), and "Mixed I/O Modules" (pg. 20). Service LED Each Panel Bus I/O Module is equipped with a yellow service LED (status: yellow/OFF) for easy diagnosis of failures. Microprocessor Each Panel Bus I/O Module is equipped with its own microprocessor. Addressing Addressing is performed using the HEX switch.

    System Constraints

    Table 5. System constraints Max. no. of I/O modules (any combination) per controller

    depends upon controller type

    Max. no. of I/O modules per row 10 Max. current (F1) 4 A Max. current (F2) 12 A Max. current (F3) 12 A Max. current (F4) (mixed I/O modules, only) 3 A

    Max. row length 3 m Max. distance between rows 40 m Min. cross-section of GND (terminal 9) (protected by F2) 1.5 mm

    2

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 6

    Analog Input Module

    1

    2 3

    Fig. 3. CLIOP821A Panel Bus AI Module (shown with

    terminal socket) Legend 1 Hex switch S2 2 Service LED 3 Power LED The pluggable CentraLine Panel Bus Analog Input Module, with 8 analog inputs, is installed with the XS821-22 or XSU821-22 Terminal Socket.

    24.9 kOHM

    RTD

    10 VDC

    AI

    GND

    Fig. 4. Analog input low impedance (input circuit for

    PT1000, Johnson A99 PTC, Balco500, PT3000, NI1000TK5000, slow binary input)

    199.9 kOHMVi

    AI

    GND

    Fig. 5. Analog input high impedance (input circuit for

    voltage input for active sensors)

    199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)

    Vi

    AI

    GND

    24.9 kOHM

    10 VDC

    Fig. 6. Analog input impedance setpoint (input circuit for

    NTC10kΩ, NTC20kΩ, wall module setpoint)

    71 7572 7673 7774

    21

    9

    VAUX

    GND GND GND GND GND GND GND GND GND GND

    VAUX

    22

    10

    1

    11

    AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8

    2

    12

    3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8

    18 25 26

    78

    COMA

    COMA

    COMB

    COMB

    24V~

    24V~

    24V~0

    24V~0

    Fig. 7. CentraLine Panel Bus Analog Input Module

    (schematic) Features 0…10 VDC, 2…10 VDC without pull-up 0…10 VDC with pull-up (linear graph, e.g. used for wall

    module connection) 0/4…20 mA, needs 499 Ω resistor in parallel NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…+150 °C) PT1000-2 (0…+400 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…+150 °C) BALCO500 (-30…+120 °C) Binary input 16-bit resolution Configurable offset per input Auxiliary voltage: 10 VDC, IMAX = 5 mA Sensor failure detection See also section "Sensor Characteristics" on pg. 24.

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 7

    OPT. AUX. TERMINAL MODULE XS814

    A1 A2 A3 A4 A5 A6 A7 B1 B

    CLIOP821A ANALOG INPUT MODULE

    74

    21

    9 925GND GNDGND GNDGNDGNDGNDGND GND GND GND GND

    22

    10 1026

    1

    11

    AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8

    2

    12

    3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8

    18

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    VAUX VAUX

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    ACTIVE SENSOR1: 24V POWER2: 0...10 VDC SIGNAL3: GND (24V 0)

    ~

    ~

    AUX. VOLTAGE + POT.1: SIGNAL2: GND3: 10 VDC AUX.

    2 23 31 1

    F1

    F2

    CLIOP...

    (24 VAC)EXTERNALGROUND

    REQUIRED TOPOWER

    EXTERNALDEVICES

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF2F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    Fig. 8. CLIOP821A Panel Bus AI Module, wiring example 1: Active sensor and potentiometer

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 8

    DRY CONTACT1: SIGNAL2: GND

    CLIOP821A ANALOG INPUT MODULE

    CLIOP... CLIOP...

    74

    21

    9 925GND GNDGND GNDGNDGNDGNDGND GND GND GNDGND

    22

    10 1026

    1

    11

    AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8

    2

    12

    3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8

    18

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    VAUX VAUX

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    2 22 1 11

    DRYCONTACT TEMP. SENSOR(NTC20k or Pt1000)

    0(4)...20 mA1: IN2: OUT

    7824V~0777675

    24V~

    COMB

    COMA

    EXTERNAL 499 OHMRESISTOR WITHTWIN WIRE-END

    FERRULESREQUIRED.

    EXTERNALDC POWER

    SUPPLY

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF2F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    Fig. 9. CLIOP821A Panel Bus AI Module, wiring example 2: Passive sensor and 0 (4) … 20 mA signal

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 9

    Analog Output Modules

    4 53

    2

    1

    Fig. 10. CLIOPR822A Panel Bus AO Module (shown with

    terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CentraLine Panel Bus Analog Output Modules, with 8 analog outputs, are available in the following models: CLIOP822A Panel Bus Analog Output Module (without

    manual overrides) CLIOPR822A Panel Bus Analog Output Module (with

    manual overrides) They are installed with the XS821-22 or XSU821-22 Terminal Socket.

    71 7572 7673 7774

    21

    9GND GND GND GND GND GND GND GND GND GND

    22

    10

    1

    11

    AO1NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8

    2

    12

    3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8

    18 25 26

    78

    COMA

    COMA

    COMB

    COMB

    24V~

    24V~

    24V~0

    24V~0

    Fig. 11. CentraLine Panel Bus Analog Output Modules

    (schematic) Features 0…11 VDC, +/-1 mA Floating actuator (requires MCD3) Binary output (0 V / 10 V) red LED per output (brightness according to signal level) Optional versions with manual override potentiometers

    (Auto, 0…100%; LED flashes in override mode) Feedback on manual override signal 8-bit resolution Configurable safety position for outputs in case of

    communication problems (remain, 0%, 50%, 100%)

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 10

    CLIOP822A ANALOG OUTPUT MODULE

    CLIOP...

    OPT. AUX. TERMINAL MODULE XS814

    74

    925GND GND

    1026

    A1 A2 A3 A4 A5 A6 A7 B1

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    2 31

    F1

    F2

    21NC NC

    22 1AO1AO2AO3AO4AO5AO6AO7AO8

    2 3 4 5 6 7 8

    M

    9GND GND GNDGNDGNDGND GND GND GNDGND

    10 11 12 13 14 15 16 17 18

    24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL

    ~

    ~~

    B

    XS814

    A1 A

    (24 VAC)EXT. GROUND

    REQUIREDTO POWER

    EXT. DEVICES

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF2F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    Fig. 12. CLIOP822A Panel Bus AO Module, wiring example 1: Actuator

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 11

    CLIOP822A ANALOG OUTPUT MODULE

    CLIOP...

    OPT. AUX. TERMINAL MODULE XS814

    74

    925GND GND

    1026

    A1 A2 A3 A4 A5 A6 A7 B1

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    2

    2

    3

    3L N

    1

    1

    F1

    F2

    21NC NC

    22 1AO1AO2AO3AO4AO5AO6AO7AO8

    2 3 4 5 6 7 8

    M

    M

    2 1

    M

    9GND GND GNDGNDGNDGND GND GND GND GND

    10 11 12 13 14 15 16 17 18

    11 12 13 14 15 16 17 18

    1 2 3 4 5 6 7 8

    MCD 3

    K1 K2 K3

    24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL

    ~

    ~~

    B

    XS814

    A1 A

    (24 VAC)

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF2F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    EXT. GROUNDREQUIREDTO POWER

    EXT. DEVICES

    Fig. 13. CLIOP822A Panel Bus AO Module, wiring example 2: Relay Module MCD 3

    The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 17 of MCD3 controls changeover contact K3. Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 12

    CLIOP822A ANALOG OUTPUT MODULE

    CLIOP...

    OPT. AUX. TERMINAL MODULE XS814

    74

    925GND GND

    1026

    A1 A2 A3 A4 A5 A6 A7 B1

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    2 31

    F1

    F2

    21NC NC

    22 1AO1AO2AO3AO4AO5AO6AO7AO8

    2 3 4 5 6 7 8

    M

    9GND GND GNDGNDGNDGND GND GND GNDGND

    10 11 12 13 14 15 16 17 18

    24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL

    ~

    ~~

    B

    XS814

    A1

    (24 VAC)

    11 12 13 14 15 16 17 18

    1 2 3 4 5 6 7 8

    MCE 3

    K1 K2 K3

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF2F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    EXT. GROUNDREQUIREDTO POWER

    EXT. DEVICES

    Fig. 14. CLIOP822A Panel Bus AO Module, wiring example 3: Relay Module MCE 3

    The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 16 of MCE3 controls the N.O. contact K3. Input terminal 17 of MCE3 controls the changeover contact K2. Input terminal 18 of MCE3 controls the changeover contact K1.

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 13

    Binary Input Module

    3 42

    1

    Fig. 15. CLIOP823A Panel Bus BI Module (shown with

    XS823 terminal socket) Legend 1 Hex switch S2 2 Status LEDs 3 Service LED 4 Power LED The pluggable CentraLine Panel Bus Binary Input Module, with 12 binary inputs, is installed with the XS823 or XSU823 Terminal Socket. Configuration as Fast Totalizer Using CARE / COACH AX / COACH NX, the binary inputs can be configured as fast totalizers for operation in con-junction with devices equipped with an open collector output.

    Table 6. Binary inputs used as fast totalizers Frequency max. 20 Hz

    Pulse ON min. 25 ms

    Pulse OFF min. 25 ms

    Bounce max. 5 ms

    FASTTOTALIZER

    DRY CONTACT4 ... 40 VDC = OPEN0 ... 2 VDC = CLOSED

    150 kOHM

    10 kOHM

    18 VDC (NOT STABILIZED)+V

    BI

    GND

    Fig. 16. Configuration of a binary input as a fast totalizer

    71 7572 7673 7774

    GND GND GND GND GND GND GND GND GND GND GND GND

    1BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12

    2 3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8 9 10 11 12

    18 19 20 21 22 23 24 25 26

    78

    COMA

    COMA

    COMB

    COMB

    24V~

    24V~

    24V~0

    24V~0

    Fig. 17. CentraLine Panel Bus Binary Input Modules

    (schematic) Features Static binary input (dry contact) Totalizer for up to 20 Hz LEDs per binary input supporting alarm display mode

    (red/green) or status mode (off/yellow). Color mode of each LED can be set to OFF/yellow or

    green/red in CARE / COACH AX / COACH NX.

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 14

    DRY CONTACT1: SIGNAL2: GND

    TOTALIZER1: SIGNAL2: GND

    CLIOP823A BINARY INPUT MODULE

    CLIOP...

    74

    25GNDGND GNDGND GND GND GND GND GNDGND GND GND

    26

    1BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9BI10 BI11BI12

    2 3

    13

    4

    14

    5

    15

    6

    16

    7

    17

    8 9 10 11 12

    18 19 20 21 22 23 24

    747824V~0 24V~0 24V~073 737772 727671 7175

    24V~

    24V~

    24V~

    COMB

    COMB

    COMB

    COMA

    COMA

    COMA

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    21

    DRYCONTACT

    F1

    21

    TOTALIZERMIN. 25 ms

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm 2

    DASHED LINES

    THIN LINESF1

    LEGEND:

    THICK LINES

    MAX. 4 A

    Fig. 18. CLIOP823A Panel Bus BI Module, wiring example: Dry contact and totalizer

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 15

    Relay Output Modules

    1

    4 53

    2

    Fig. 19. CLIOPR824A Panel Bus Relay Output Module

    (shown with terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CentraLine Panel Bus Relay Output Modules, with 6 relay outputs, are available in the following versions: CLIOP824A Panel Bus Relay Output Module (without

    manual overrides) CLIOPR824A Panel Bus Relay Output Module (with

    manual overrides) They are installed with the XS824-25 or XSU824-25 Terminal Socket.

    REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)

    NO

    NC

    COM

    111213

    NO

    NC

    COM

    212223

    313233

    NO

    NC

    COM

    414243

    NO

    NC

    COM

    515253

    NO

    NC

    COM

    616263

    NO

    NC

    COM

    25

    71 7572 7673 7774 78

    COMA

    COMA

    COMB

    COMB

    24V~

    24V~

    24V~0

    24V~0

    RELAY BLOCK 1 RELAY BLOCK 2

    Fig. 20. CentraLine Panel Bus Relay Output Modules

    (schematic) Features - Cross-Connecter - 1 yellow LED per output - Optional versions with manual override switches (Auto, 0,

    1; LED flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of

    communications problems (remain, OFF, ON) - Permissible Load per Relay Output Module (Total)

    Max. load (fuse F3): 19…250 VAC: 12 A 1…29 VDC: 12 A resistive, 3 A inductive

    - Permissible Load per Normally-Open Contact: Max. load:

    19…250 VAC: 4 A resistive or inductive 1…29 VDC: 4 A resistive, 1 A inductive

    Min. load: P > 50 mW - Permissible Load per Normally-Closed Contact:

    Max. load: 19…250 VAC: 2 A resistive, 1 A inductive 1…29 VDC: 2 A resistive, 1 A inductive

    Min. load: P > 50 mW

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 16

    OPTIONAL AUX. TERMINAL PACKAGE XS814

    POWER SUPPLY230 VAC

    NL

    B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7

    CLIOP...

    74 24V~0737271

    24V~

    COMB

    COMA

    7824V~0777675

    24V~

    COMB

    COMA

    74 24V~0737271

    24V~

    COMB

    COMA

    CLIOP824A RELAY OUTPUT MODULE

    NO

    NC

    COM

    111213

    NO

    NC

    COM

    212223

    313233

    NO

    NC

    COM

    414243

    NO

    NC

    COM

    515253

    NO

    NC

    COM

    616263

    NO

    NC

    COM

    25

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    FIELD DEVICE1: 230 V (N)2: 230 V (L)

    FIELD DEVICE1: 230 V (N)2: 230 V (L)

    1 2

    M230 V

    1 2

    M230 V

    F1

    F3

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm - or less, as per F32

    DASHED LINES

    THIN LINESF3F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    CROSS CONNECTOR XS815 (FACTORY-MOUNTED)

    Fig. 21. CLIOP824A Panel Bus RO Module, wiring example 1: Both relay blocks with line voltage

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 17

    POWER SUPPLY230 VAC

    CROSS CONNECTOR XS815 (FACTORY-MOUNTED)

    NL

    CLIOP...

    74 24V~0737271

    24V~

    COMB

    COMA

    7824V~0777675

    24V~

    COMB

    COMA

    74 24V~0737271

    24V~

    COMB

    COMA

    CLIOP824A RELAY OUTPUT MODULE

    NO

    NC

    COM

    111213

    NO

    NC

    COM

    212223

    313233

    NO

    NC

    COM

    414243

    NO

    NC

    COM

    515253

    NO

    NC

    COM

    616263

    NO

    NC

    COM

    25

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    FIELD DEVICE1: 230 V (N)2: 230 V (L)

    FIELD DEVICE1: 230 V (N)2: 230 V (L)

    1 2

    M230 V

    1 2

    M230 V

    F1

    FIELD DEVICE1: 230 V (N)2: 230 V (L)

    1 2

    M230 V

    OPTIONAL AUX. TERMINAL PACKAGE XS814

    B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7

    F3

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm - or less, as per F32

    DASHED LINES

    THIN LINESF3F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    Fig. 22. CLIOP824A Panel Bus RO Module, wiring example 2: Relay blocks with low and line voltage

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 18

    Floating Output Module

    4 53

    2

    1

    Fig. 23. CLIOPR825A Panel Bus Floating Output Module

    (shown with terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CLIOPR825A Panel Bus Floating Output Module, with manual overrides and 3 floating outputs, is installed with the XS824-25 or XSU824-25 Terminal Socket.

    REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)

    NO

    NC

    COM

    111213

    NO

    NC

    COM

    212223

    313233

    NO

    NC

    COM

    414243

    NO

    NC

    COM

    515253

    NO

    NC

    COM

    616263

    NO

    NC

    COM

    25

    71 7572 7673 7774 78

    COMA

    COMA

    COMB

    COMB

    24V~

    24V~

    24V~0

    24V~0

    ACTUATOR 1 ACTUATOR 2 ACTUATOR 3

    Fig. 24. CentraLine Panel Bus Floating Output Module

    (schematic) Features - Cross-Connecter - 1 red LED (opening) and 1 green LED (closing) per

    floating output - Manual override potentiometers (Auto, 0%...100%; LED

    flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of

    communication problems (remain, 0%, 50%, 100%) - Permissible Load per Floating Output Module (Total)

    Max. load (fuse F3): 19…250 VAC: 12 A 1…29 VDC: 12 A resistive, 3 A inductive

    - Permissible Load per Normally-Open Contact: Max. load:

    19…250 VAC: 4 A resistive or inductive 1…29 VDC: 4 A resistive, 1 A inductive

    Min. load: P > 50 mW - Permissible Load per Normally-Closed Contact:

    Max. load: 19…250 VAC: 2 A resistive, 1 A inductive 1…29 VDC: 2 A resistive, 1 A inductive

    Min. load: P > 50 mW

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 19

    FLOATING ACTUAOR WITH 230VAC(REQUIRES TWO RELAYS)1: 2: 3: N

    NO

    NC

    COM

    111213

    NO

    NC

    COM

    212223

    313233

    NO

    NC

    COM

    414243

    NO

    NC

    COM

    515253

    NO

    NC

    COM

    616263

    NO

    NC

    COM

    CON CON CON CON CON CON14 24 34 44 54 64

    CLIOP...

    74 24V~0737271

    24V~

    COMB

    COMA

    7824V~0777675

    24V~

    COMB

    COMA

    74 24V~0737271

    24V~

    COMB

    COMA

    CLIOPR825A FLOATING OUTPUT MODULEF1

    25

    SHIELDINTERNALLYCONNECTEDTO DIN RAIL

    POWER SUPPLY230 VAC

    NL 23 1

    M

    F3

    OPTIONAL AUX. TERMINAL PACKAGE XS814

    B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7

    CROSS CONNECTOR XS815 (FACTORY-MOUNTED)

    SELECTED INTERNAL CONNECTIONS

    MIN. 0.75 mm 2

    MIN. 1.5 mm - or less, as per F32

    DASHED LINES

    THIN LINESF3F1

    LEGEND:

    THICK LINES

    MAX. 12 AMAX. 4 A

    Fig. 25. CLIOPR825A Panel Bus FO Module, wiring example: Floating actuator

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 20

    Mixed I/O Modules CLIOP830A CLIOP831A

    Fig. 26. Mixed Panel Bus Modules

    The CLIOP830A and CLIOP831A mixed Panel Bus I/O modules feature 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs. The CLIOP830A is equipped with push-in terminals, while the CLIOP831A features screw-type terminals. Both feature an integrated terminal socket and electronic module. The CLIOP830A can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top and/or bottom. The CLIOP831A can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top, only.

    AI5

    AI1 AI2 AI3 AI4 41G1 G2

    42

    1713 14 15 16

    18 19 20AI6 AI7 AI8 AO5

    2521 22 23 24

    26 27 28 3529 30 31 32 33 34

    36 37 38 39 40

    AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6

    AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6

    1 2 3 4 5 6

    25 26 27 28 35 36 37 38 39 40

    1 21 22 23 24 29 30 31 32 33 342 3 4 5 6 13 14 15 16 41 42

    7 8 9 10 11 12 17 18 19 20

    Analog Inputs Analog OutputsGND

    DO!

    CLIOP830A12 BI / 8 AI / 8 AO / 6 RO

    24V, 15VA, T500706AX0001-XFU830A

    Made in Germany0532

    8

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93

    24V Relays

    2 1 0 F E D C B

    9 8

    7

    6 5 4 3

    A

    40 External

    24V for relay 1...5

    24V

    J1 J2 J3 J4 J5

    71 75767778

    COM aCOM b24V~24V~0

    COM aCOM b

    24V~24V~0

    727374 S2

    A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8

    B7

    B1 B2 B3 B4 B5 B6

    B8 B9 B10 B11 B12

    DI

    Binary Inputs

    Install. Instr.EN1B-0375GE51

    71 2 3 4 5 6

    8 9 10 11 12

    1 2 3 4 5 6 7 8 9 10 11 12

    1 2

    4

    Fig. 27. CLIOP830A mixed Panel Bus I/O module, shown with 4 optional aux. terminal blocks (top view)

    1 2 3 4 5 6 7 8 9 10 11 12B1 B2 B3 B4 B5 B6

    B12126

    B11115

    B1010

    4

    B993

    B88

    2

    B77

    1

    BI

    Binary Inputs

    G1 G241 42

    GND Analog Outputs

    AI2 AI3 AI4

    14 15 16

    AI1

    AI5 AI6 AI7 AI817 18 19 2013

    Analog Inputs

    AO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO421

    25 26 27 28

    22 23 24

    BO

    24V Relays

    NO1 NO2 NO3 NO4 NO5 NO6

    IN1 IN2 IN3 IN4 IN5 IN63529 30 31 32 33 34

    36 37 38 39 40

    1 2 3 4 5 6 !

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B91

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B92

    A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B84

    40 External

    24V FOR RELAY 1...5

    24V

    J1 J2 J3 J4 J5

    71 COM aCOM b24V~24V~0

    727374

    75767778

    COM aCOM b

    24V~24V~0

    Fig. 28. CLIOP831A mixed Panel Bus I/O module, shown

    with 4 optional aux. terminal blocks (top view)

    Features - 1 yellow LED per output - Configurable safety position for outputs in case of com-

    munications problems (remain in last position, OFF, ON)

    Table 7. Permissible loads of Mixed Panel Bus I/O Modules

    max. load min. load

    per module (total for all relay contacts)

    19…29 VAC, 1…29 VDC 3 A resistive or inductive, cos φ ≥ 0.6, no capacitive load, protected by fuse F4

    per nor-mally open contact

    19…29 VAC, 1…29 VDC 0.5 A resistive or inductive, cos φ ≥ 0.6, no capacitive load

    >50 mW, 0.05 A res./ind.,cos φ ≥ 0.6

    199.9 kOHMVi

    AI

    GND

    Fig. 29. Analog input high impedance (input circuit for

    voltage input for active sensors)

    199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)

    Vi

    AI

    GND

    24.9 kOHM

    10 VDC

    Fig. 30. Analog input impedance setpoint (input circuit

    for NTC10kΩ, NTC20kΩ, wall module setpoint)

    FASTTOTALIZER

    DRY CONTACT16 ... 22 VDC = OPEN 0 ... 2 VDC = CLOSED

    150 kOHM

    10 kOHM

    18 VDC (NOT STABILIZED)+V

    BI

    GND

    Fig. 31. Configuration of a binary input as a fast totalizer

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 21

    CLIOP830A Mixed I/O Module

    2 21

    DRYCONTACT1: GND2: SIGNAL

    DRYCONTACT1: GND2: SIGNAL

    21 1

    ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 0...10 VDC

    ~~

    23 31

    0...10 VDC 0...10 VDCM

    1 2

    M

    1 2

    XS830 OPT. AUX. TERM. MODULE XS830

    F1

    F4

    1 2

    74 24V~0737271

    24V~

    COMB

    COMA

    7824V~0777675

    24V~

    COMB

    COMA

    41 42

    B10 B11 B12 AI5

    AI1

    AI6

    AI2

    AI7

    AI3

    AI8

    AI4

    AO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO4

    IN1

    NO1

    IN2

    NO2

    IN3

    NO3

    IN4

    NO4

    IN5

    NO5

    IN6

    NO6

    B7 B8 B97 8 9 10 11 12 17

    13

    18

    14

    19

    15

    20

    16

    25

    21

    26

    22

    27

    23

    28

    24

    35

    29

    36

    30

    37

    31

    38

    32

    39

    33

    40

    34B1 B2 B3 B4 B5 B61 2 3 4 5 6

    G1 G2

    A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6

    TOTALIZER1: GND2: SIGNAL

    NTC20kOHMSENSOR1: GND2: SIGNAL

    24V

    1: GND (24V 0)2: 24V POWER3: 0...10 VDC

    ~ DRIVE with0...10V SIGNAL

    ~~

    DCA1: 24V 02: 24V

    ~~

    MIN. 0.75 mm 2MIN. 1.5 mm - or less, as per F2, F42

    THIN LINESF4

    F1 F2LEGEND:

    THICK LINES

    MAX. 3 AMAX. 4 A MAX. 12 A

    F2

    (GND 24 VAC)

    BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS

    (24 VAC)(GND)

    Fig. 32. CLIOP830A mixed Panel Bus I/O Module, wiring example: Actuators

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 22

    ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 4...20 mA

    ~~

    CLIOP831A Mixed I/O Module

    74 24V~0737271

    24V~

    COMB

    COMA

    7824V~0777675

    24V~

    COMB

    COMA

    A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6

    A4 A8B4 B8G1 G2A1 A5B1 B5A2 A6B2 B6A3 A7B3 B7

    OPT. AUX. TERM. MODULE XS830 OPT. AUX. TERM. MODULE XS830

    OPT. AUX. TERM. MODULE XS831

    F2

    F1

    4...20 mA

    1 2 3

    MIN. 0.75 mm 2MIN. 1.5 mm - or less, as per F22

    THIN LINES

    F1 F2LEGEND:

    THICK LINES

    MAX. 4 A MAX. 12 A

    BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS

    41 42

    B10 B11 B12 AI5

    AI1

    AI6

    AI2

    AI7

    AI3

    AI8

    AI4

    AO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO4

    IN1

    NO1

    IN2

    NO2

    IN3

    NO3

    IN4

    NO4

    IN5

    NO5

    IN6

    NO6

    B7 B8 B97 8 9 10 11 12 17

    13

    18

    14

    19

    15

    20

    16

    25

    21

    26

    22

    27

    23

    28

    24

    35

    29

    36

    30

    37

    31

    38

    32

    39

    33

    40

    34B1 B2 B3 B4 B5 B61 2 3 4 5 6

    G1 G2

    Fig. 33. CLIOP831A mixed Panel Bus I/O Module, wiring example: Current inputs

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 23

    Approvals, Certifications, and Standards Approvals and Certifications

    CE-approved Conforms to EN 60730-1 and EN 60730-2-9 Investigated according to United States Standard

    UL916 (USL-listed) as well as according to Canadian National Standard(s) C22.2 (CNL-listed)

    Classification according to EN60730-1 Environmental conditions: For use in home (residential,

    commercial, and light-industrial) environments

    Pollution degree: Class 2 Protection against shock: Class II Software class: Class A Overvoltage category: II Classification according to EN60529 (Degree of Protection Provided by Enclosures) Classification: IP20 Ambient Environmental Limits Operating temperature: 0 … +50 °C at 5…93% r.H. Storage temperature: -20 … +70 °C at 5…93% r.H. Humidity: 5 … 93% r.h. non-condensing Current Requirement and Heat Dissipation The Panel Bus I/O Modules are equipped with highly-efficient switching power supplies which provide for relatively uniform power consumption over a wide range of supply voltages (see Table 8). The specific heat dissipation inside the modules amounts to less than 2 W for all models.

    Table 8. Current requirements of CentraLine Panel Bus I/O Modules

    devices powered supply voltage

    24 VAC 24 VDCCLIOP821A 130 mA 80 mA CLIOP822A, CLIOPR822A 150 mA 90 mA CLIOP823A, CLIOL823A 180 mA 130 mACLIOP824A, CLIOPR824A, CLIOPR825A 140 mA 80 mA

    CLIOP830A, CLIOP831A 200 mA 95 mA

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 24

    Mechanical Housing dimensions (H x W x D) The pluggable CentraLine I/O Modules (mounted on Terminal Sockets) all have the dimensions: 110 X 90 X 93 mm (see also Fig. 34 on page 25). The CLIOP830A mixed Panel Bus I/O module has the dimensions: 216 X 110 X 93 mm (see also Fig. 35 on page 25). The CLIOP831A mixed Panel Bus I/O module has the dimensions: 216 X 110 X 61 mm (see also Fig. 36 on page 26). Housing Material Plastic, flame-retardant Mounting Methods DIN-rail mounting (e.g. in control cabinet). Calculated Lifetime of Weakest Components MTBF 13.7 years (under typical operating conditions) Sensor Characteristics The following sensor characteristics do not include failures due to: ● sensor failures; ● wiring resistance or wiring failures; ● misreadings due to a meter connected to measure

    resistance or voltage at the input. For more-detailed values, see section "Appendix 3: Sensor Characteristics" of the CentraLine I/O Modules – Installation & Commissioning Instructions (EN1Z-0973GE51).

    Table 9. BALCO 500 Temp. [°C] Resistance [] Terminal voltage [V]

    -20.0 415 0.164 0.0 453 0.179

    20.0 493 0.194 40.0 535 0.210 60.0 579 0.227 80.0 625 0.245

    100.0 673 0.263 120.0 724 0.283

    Table 10. NTC 20 kOhm

    Temp. [°C] Resistance [k Terminal voltage [V] -20.0 221.0 8.08

    0.0 70.2 6.76 20.0 25.3 4.75 40.0 10.2 2.81 60.0 4.52 1.51 80.0 2.17 0.792

    100.0 1.11 0.425 120.0 0.61 0.238

    Table 11. Pt 1000 Temp. [°C] Resistance [ Terminal voltage [V]

    -20.0 922 0.357 0.0 1000 0.386

    20.0 1078 0.415 40.0 1155 0.443 60.0 1232 0.471 80.0 1309 0.499

    100.0 1385 0.527 120.0 1461 0.554

    Table 12. Ni1000TK5000

    Temp. [°C] Resistance [Ω] Terminal voltage [V] -20.0 913.5 0.354

    0.0 1000.0 0.386 20.0 1090.7 0.420 40.0 1185.7 0.455 60.0 1285.4 0.491 80.0 1390.1 0.529

    100.0 1500.0 0.568 120.0 1615.4 0.609

    Table 13. NTC 10 kOhm

    Temp. [°C] Resistance [k Terminal voltage [V] -20.0 97.073 7.241

    0.0 32.650 5.299

    20.0 12.490 3.207

    40.0 5.327 1.724

    60.0 2.488 0.898

    80.0 1.258 0.478

    100.0 0.680 0.265

    Table 14. Pt 3000 Temp. [°C] Resistance [k Terminal voltage [V]

    -20.0 3.090 1.104 0.0 3.266 1.160

    20.0 3.440 1.214 40.0 3.613 1.267 60.0 3.784 1.319 80.0 3.954 1.370

    100.0 4.122 1.420 120.0 4.289 1.469

  • PANEL BUS I/O MODULES – PRODUCT DATA

    EN0Z-0979GE51 R1219 25

    Dimensions

    LOCK

    89.5 94.1

    51.5

    45

    83 67.

    5

    14

    110

    XS814 Aux. Terminal Package (optional)

    2830.6

    SWIVEL LABEL HOLDER

    38

    SCREW-TYPETERMINALS

    Fig. 34. CentraLine Panel Bus I/O Modules (example shows Manual Overrides), incl. Terminal Socket, outside

    dimensions (in mm)

    92.5

    51.545

    69

    100

    CLE

    ARAN

    CE

    15

    110

    28

    SWIVEL LABEL HOLDER

    B7

    B1 B2 B3 B4 B5 B6

    71 2 3 4 5 6

    8 9 10 11 12B8 B9 B10 B11 B12 AI5

    AI1 AI2 AI3 AI4 41G1 G2

    42

    1713 14 15 16

    18 19 20AI6 AI7 AI8 AO5

    2521 22 23 24

    26 27 28 3529 30 31 32 33 34

    36 37 38 39 40

    AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6

    AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6

    1 12 23 34 45 56 67

    25 26 27 28 35 36 37 38 39 40

    1 21 22 23 24 29 30 31 32 33 342

    8 9

    3

    10

    4

    11

    5

    12

    6 13 14 15 16 41 42

    7 8 9 10 11 12 17 18 19 20

    DI

    Binary Inputs Analog Inputs Analog Outputs 24V RelaysGND

    S2

    DO!

    Install. Instr.EN1B-0375GE51

    CLIOP830A12 BI / 8 AI / 8 AO / 6 RO

    24V, 15VA, T500706AX0001-XFU830A

    Made in Germany0532

    8

    2 1 0 F E D C B

    9 87

    6 5 4 3

    A

    40 External

    24V for relay 1...5

    24V

    J1 J2 J3 J4 J5

    71 75767778

    COM aCOM b24V~24V~0

    COM aCOM b

    24V~24V~0

    727374

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9A

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9B

    A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9C

    216

    A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8D

    D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)

    Fig. 35. CLIOP830A mixed Panel Bus I/O module (shown with 4 auxiliary terminal packages), dimensions (in mm)

  • PANEL BUS I/O MODULES – PRODUCT DATA

    Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative: CentraLine Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 845 Fax +49 (0) 7031 637 740 [email protected] www.centraline.com

    Subject to change without notice EN0Z-0979GE51 R1219

    216 54.444

    61.1

    110

    1 2 3 4 5 6 7 8 9 10 11 12B1 B2 B3 B4 B5 B6

    B12126

    B11115

    B10104

    B993

    B882

    B771

    BI

    Binary Inputs

    G1 G241 42

    GND Analog Outputs

    AI2 AI3 AI414 15 16

    AI1

    AI5 AI6 AI7 AI817 18 19 2013

    Analog Inputs

    AO5

    AO1

    AO6

    AO2

    AO7

    AO3

    AO8

    AO42125 26 27 28

    22 23 24

    BO

    24V Relays

    NO1 NO2 NO3 NO4 NO5 NO6

    IN1 IN2 IN3 IN4 IN5 IN63529 30 31 32 33 34

    36 37 38 39 40

    1 2 3 4 5 6 !

    40 External

    24V FOR RELAY 1...5

    24V

    J1 J2 J3 J4 J5

    71 COM aCOM b24V~24V~0

    727374

    75767778

    COM aCOM b

    24V~24V~0

    Fig. 36. CLIOP831A mixed Panel Bus I/O module, dimensions (in mm)