PB04_Counter Area Input DataProject Name: BANYU_URIP_PROJECT_REV11/13/2014Prepared by: wen03:52PMHourly Analysis Program v4.50Page2of2
1. General Details:Air System NamePB04_Counter AreaEquipment TypeSplit AHUAir System TypeSingle Zone CAVNumber of zones1
2. System Components:Ventilation Air Data:Airflow ControlConstant Ventilation AirflowVentilation Sizing MethodSum of Space OA AirflowsUnocc. Damper PositionClosedDamper Leak Rate0%Outdoor Air CO2 Level400ppm
Central Cooling Data:Supply Air Temperature14.4CCoil Bypass Factor0.100Cooling SourceAir-Cooled DXScheduleJFMAMJJASONDCapacity ControlCycled or Staged Capacity - Fan On
Supply Fan Data:Fan TypeForward CurvedConfigurationDraw-thruFan Performance300PaOverall Efficiency70%
Duct System Data:Supply Duct Data:Duct Heat Gain0%Duct Leakage0%
Return Duct or Plenum Data:Return Air ViaDucted Return
3. Zone Components:Space Assignments:
Zone 1: Zone 1 PB04_Counter Areax1
Thermostats and Zone Data:ZoneAllCooling T-stat: Occ.23.0CCooling T-stat: Unocc.29.0CHeating T-stat: Occ.21.1CHeating T-stat: Unocc.15.6CT-stat Throttling Range1.70KDiversity Factor100%Direct Exhaust Airflow0.0L/sDirect Exhaust Fan kW0.0kW
Thermostat SchedulePB-04Unoccupied Cooling isAvailable
Supply Terminals Data:ZoneAllTerminal TypeDiffuserMinimum Airflow6.00ACH
Zone Heating Units:ZoneAllZone Heating Unit TypeNone
Zone Unit Heat SourceElectric ResistanceZone Heating Unit ScheduleJFMAMJJASOND
4. Sizing Data (Computer-Generated):System Sizing Data:Cooling Supply Temperature14.4CSupply Fan Airflow717.6L/sVentilation Airflow35.6L/s
Hydronic Sizing Specifications:Chilled Water Delta-T5.6KHot Water Delta-T11.1K
Safety Factors:Cooling Sensible10%Cooling Latent10%Heating0%
Zone Sizing Data:Zone Airflow Sizing MethodSum of space airflow ratesSpace Airflow Sizing MethodIndividual peak space loads
ZoneSupply AirflowZone Htg UnitReheat Coil- (L/s)(kW)(kW)(L/s)1717.6--
5. Equipment DataCentral Cooling Unit - Air-Cooled DXEstimated Maximum Load9.9kWDesign OAT35.0CEquipment SizingAuto-SizedCapacity Oversizing Factor0%ARI Performance Rating2.96EERConventional Cutoff OAT12.8CLow Temperature OperationNot used