Upload
bansalr
View
214
Download
0
Embed Size (px)
Citation preview
7/27/2019 PESL-00137-2007.pdf
1/2
Solution to Close-in Fault Problem in Directional Relaying
A. K. Pradhan, P. Jena
Abstract- Directional relays use voltage as the polarizing quantity.
When three phase faults occur near to the relay bus the available
voltage becomes nearly zero and this creates problem in estimation of
the fault direction. The capacitor coupling voltage transformer
(CCVT) subsidence transients add to this problem. The memory
voltage used as the polarizing quantity at these situations is a
compromise. This paper highlights these issues and proposes a simple
solution using the power flow direction in addition to other
information. Performance of the technique is evaluated through
simulation in PSCAD.
Key words- Fault, Digital Relay, Directional Relay, Phasor Estimation,Subsidence Transient
I. INTRODUCTION
IRECTIONAL relaying is widely applied in line protection to
enhance the sensitivity and reliability of the protection schemes
[1]-[4]. Current and voltage phasors or the derived sequence
components are used to estimate the fault direction where voltage is
used as polarizing quantity. When three phase faults occur near thesensors the available voltage to the relay becomes substantially low
and it puts challenge in correct voltage phasor estimation. Due to
subsidence transients with CCVT, at these situations the
performance of directional relay is not reliable. As a measure, the
low voltage polarizing quantity is substituted by any suitable
memory signal such as prefault positive sequence voltage [1], [3].
However this approach is also not reliable which is demonstrated in
the following example.
A 132 kV, 50 Hz three phase two-source system as shown in
Fig. 1 is simulated using PSCAD. A directional relay is located at
bus B and power flow direction at a situation is from bus A to bus
C. Three phase faults are created at Fx and Fy sides of the relay
and results are shown in table 1 (phasors computed through onecycle DFT with 1 kHz sampling rate). This indicates that the
phase angle difference between positive sequence fault current and
voltage is positive for Fx side faults and negative for Fy side faults.
This rule is applied in such a directional relaying with the angle
difference be restricted to rad.
Next three phase fault is created in Fx side very close to the relay
bus B. The voltage waveforms are shown in Fig. 2 where thesystem voltage collapses but corresponding CCVT outputs still
show voltage. The results of different phasors are provided in table
2 where it is observed that if the low voltage at relay bus is
considered as the polarizing quantity the angle difference is
negative for Fx case and positive for Fy case which contradicts to
the earlier result in table 1. On the other hand if prefault positive
sequence voltage becomes the polarizing voltage the results in last
column are in accordance with the rule; providing accurate
direction estimation.
TABLE I RESULTS ON DIRECTIONAL RELAYING
The power flow direction is then changed to bus C to A and simil
faults are created in Fx and Fy sides. The phasor results a
provided in table 3 where it is observed that with prefault volta
as the polarizing quantity, for faults in Fx side the angle differen
is negative and for Fy side it is positive which is aga
contradictory. A solution to this problem is proposed in the ne
section.
D
Fault current
phasor
Fault voltage
phasor
Fault
position
Mag
(A)
Angle
(rad)
Mag
(A)
Angle
(rad)
Angle
Difference(rad)
Fx 19.2 0.51 17.2 -1.88 2.39
Fy 17.4 -2.61 30.3 -1.73 -0.88
Fault current
phasor
(I1)
Fault voltage
phasor
(V1)
Prefault
voltage phasor
(VB)
Fault
position
Mag
(A)
Ang
(rad)
Mag
(A)
Ang
(rad)
Mag
(A)
Ang
(rad)
I1- V1
(rad)
I1-
(rad)
Fx 28.6 0.30 3.6 2.88 62.8 -1.61 -2.58 1.91
Fy 16.6 -2.95 4.6 2.87 62.8 -1.61 0.46 -1.34
Fault current
phasor
Prefault voltage
phasor
Fault
position
Mag
(A)
Angle
(rad)
Mag
(A)
Angle
(rad)
Angle
Difference(rad)
Fx 17.6 2.11 63.5 -1.61 -2.56
Fy 16.1 -0.39 63.5 -1.61 1.22
Fig. 1. A two-source system
A B
Fx Fy
~
Ipre
~C
Fig. 2. (a) Line voltage during close-in fault at relay bus
(b) CCVT output during close-in fault
Time (sec)
Voltae(V)
0.24 0.26 0.28 0.3 0.32 0.34 0.36-100
-50
0
50
100
Voltage(V)
Time sec0.24 0.26 0.28 0.3 0.32 0.34 0.36
-1.5
-1
-0.5
0
0.5
1
1.5x 10
5
(a)
(b)
TABLE II RESULTS ON CLOSE-IN FAULT
(POWER FLOW DIRECTION A TO C)
TABLE III RESULTS ON CLOSE-IN FAULT (POWER FLOWS FROM C TO A
The authors are with the Department of Electrical Engineering, Indian Institute ofTechnology Kharagpur, INDIA-721302
7/27/2019 PESL-00137-2007.pdf
2/2
II. PROPOSED SCHEME
It is observed that the decision of conventional directional relaying
is not consistent for close-in faults when prefault voltage becomes
the polarizing quantity. Numerous cases were simulated and it is
found that for one direction of power flow such polarizing quantity
provides correct decision but not for the reverse direction of power
flow. This is due to fact that the fault current takes a different
position when the power flow direction is changed. This is clearly
evident from phasor diagrams in Fig. 3 and Fig.4. Positive
sequence fault current (I1) and prefault voltage (VB) phasors for
faults at Fx and Fy sides are available in Fig. 3. It is observed that
the corresponding phase angle differences x and y are of
positive and negative values respectively for power flow direction
from bus A to C. On the other hand x and y for power flow
direction from bus C to A (Fig.4) are negative and positive values
respectively. Thus the phasor diagrams indicate that to obtain the
correct fault direction the angle should be multiplied by -1 in
the case of reverse power flow; from bus C to A. This provision is
included in the proposed directional relaying scheme which is
shown in Fig. 5.
TABLE IV CLOSE-IN FAULT (POWER FLOWS FROM A TO C)
TABLE V CLOSE-IN FAULT (POWER FLOWS FROM C TO A )
To demonstrate the performance of the approach three phase close-
in faults are simulated at Fx and Fy sides with power flow direction
from A to C. The result for the case is provided in table 4 and it is
found that it has correctly identified the direction. Similarly correct
decisions are observed for power flow direction from C to A as
presented in table 5.
III. CONCLUSION
This paper addressees issues related to close-in-fault in direction
relaying when memory polarization (prefault voltage) is bein
applied. It proposes a solution for such low voltage situatio
using power flow direction as additional information which
being verified through simulations.
IV. REFERENCES
[1] A. G. Phadke, S. H. Horowitz, Power Systems Relaying, Research StudPress, Taunton, 1992.
[2] D. Birla, R. P. Mahwswari and H. O. Gupta, A new nonlinear directio
overcurrent relay co-ordination technique, and banes and boons of near-efaults based approach,IEEE Trans. on Power Delivery, vol. 21, no. 3,
1176-1182, 2006.
[3] J. Roberts and A. Guzman, Directional element design and evaluatio
www.selinc.com/techpprs/6009.pdf
[4] A. K. Pradhan, A. Routray and G. S. Madhan, Fault direction estimation
radial distribution system using phase change in sequence current, IE
Trans. on Power Delivery, , vol. 22 , no. 4, pp. 2065 2071, 2007.
Fault current
phasor
Prefault voltage
phasor
Power
FlowDirection
(PD)
Angle
Differenx PD
Faultpositi
on
Mag(A)
Ang(rad)
Mag(A)
Angl(rad)
Ang(rad)
Fx 17.1 -0.88 63.5 -1.61 0.73
Fy 16.2 2.65 63.5 -1.61
From
A to C
(+1)-2.02
Fault currentphasor Prefault voltagephasor PowerFlowDirection
(PD)
AngleDifferenx PD
Faultpositi
on
Mag
(A)
Ang
(rad)
Mag
(A)
Ang
(rad)
Ang
(rad)
Fx 17.6 2.18 63.5 -1.61 2.49
Fy 16.1 -0.41 63.5 -1.61
From
C to A
(-1)-1.20
Fig. 5. Flow diagram for the algorithm
Start
Compute the positive
sequence phasors of
prefault voltage and
current
Compute the
positive sequence
phasors at fault
Voltage and current samples acquisition
Fault direction estimation
Output
Fault detection
Estimation of
power
flow direction
VC
VA
I1Fy
Ipre
1I
(b) fault at Fy
VC
VA
I1Fx
Ipre
1I
(a) fault at Fx
Fig. 4. Different positive sequence currents when power flows from bus C to A
VBVB
x
y
1 1pre FxI I I = + 1 1pre FyI I I
=
VA
VC
I1Fx
Ipre
1I
(a) fault at Fx
VA
VC
I1Fy
Ipre
y
(b) fault at Fy
Fig. 3. Phasor diagram showing different positive sequence currents, I1Fx and I1Fy -
fault components only andI1' andI1'' fault currents (including load current) when
power flows from bus A to C
1I
x
VB VB
1 1pre FxI I I =
1 1pre FyI I I
= +