PESL-00137-2007.pdf

  • Upload
    bansalr

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

  • 7/27/2019 PESL-00137-2007.pdf

    1/2

    Solution to Close-in Fault Problem in Directional Relaying

    A. K. Pradhan, P. Jena

    Abstract- Directional relays use voltage as the polarizing quantity.

    When three phase faults occur near to the relay bus the available

    voltage becomes nearly zero and this creates problem in estimation of

    the fault direction. The capacitor coupling voltage transformer

    (CCVT) subsidence transients add to this problem. The memory

    voltage used as the polarizing quantity at these situations is a

    compromise. This paper highlights these issues and proposes a simple

    solution using the power flow direction in addition to other

    information. Performance of the technique is evaluated through

    simulation in PSCAD.

    Key words- Fault, Digital Relay, Directional Relay, Phasor Estimation,Subsidence Transient

    I. INTRODUCTION

    IRECTIONAL relaying is widely applied in line protection to

    enhance the sensitivity and reliability of the protection schemes

    [1]-[4]. Current and voltage phasors or the derived sequence

    components are used to estimate the fault direction where voltage is

    used as polarizing quantity. When three phase faults occur near thesensors the available voltage to the relay becomes substantially low

    and it puts challenge in correct voltage phasor estimation. Due to

    subsidence transients with CCVT, at these situations the

    performance of directional relay is not reliable. As a measure, the

    low voltage polarizing quantity is substituted by any suitable

    memory signal such as prefault positive sequence voltage [1], [3].

    However this approach is also not reliable which is demonstrated in

    the following example.

    A 132 kV, 50 Hz three phase two-source system as shown in

    Fig. 1 is simulated using PSCAD. A directional relay is located at

    bus B and power flow direction at a situation is from bus A to bus

    C. Three phase faults are created at Fx and Fy sides of the relay

    and results are shown in table 1 (phasors computed through onecycle DFT with 1 kHz sampling rate). This indicates that the

    phase angle difference between positive sequence fault current and

    voltage is positive for Fx side faults and negative for Fy side faults.

    This rule is applied in such a directional relaying with the angle

    difference be restricted to rad.

    Next three phase fault is created in Fx side very close to the relay

    bus B. The voltage waveforms are shown in Fig. 2 where thesystem voltage collapses but corresponding CCVT outputs still

    show voltage. The results of different phasors are provided in table

    2 where it is observed that if the low voltage at relay bus is

    considered as the polarizing quantity the angle difference is

    negative for Fx case and positive for Fy case which contradicts to

    the earlier result in table 1. On the other hand if prefault positive

    sequence voltage becomes the polarizing voltage the results in last

    column are in accordance with the rule; providing accurate

    direction estimation.

    TABLE I RESULTS ON DIRECTIONAL RELAYING

    The power flow direction is then changed to bus C to A and simil

    faults are created in Fx and Fy sides. The phasor results a

    provided in table 3 where it is observed that with prefault volta

    as the polarizing quantity, for faults in Fx side the angle differen

    is negative and for Fy side it is positive which is aga

    contradictory. A solution to this problem is proposed in the ne

    section.

    D

    Fault current

    phasor

    Fault voltage

    phasor

    Fault

    position

    Mag

    (A)

    Angle

    (rad)

    Mag

    (A)

    Angle

    (rad)

    Angle

    Difference(rad)

    Fx 19.2 0.51 17.2 -1.88 2.39

    Fy 17.4 -2.61 30.3 -1.73 -0.88

    Fault current

    phasor

    (I1)

    Fault voltage

    phasor

    (V1)

    Prefault

    voltage phasor

    (VB)

    Fault

    position

    Mag

    (A)

    Ang

    (rad)

    Mag

    (A)

    Ang

    (rad)

    Mag

    (A)

    Ang

    (rad)

    I1- V1

    (rad)

    I1-

    (rad)

    Fx 28.6 0.30 3.6 2.88 62.8 -1.61 -2.58 1.91

    Fy 16.6 -2.95 4.6 2.87 62.8 -1.61 0.46 -1.34

    Fault current

    phasor

    Prefault voltage

    phasor

    Fault

    position

    Mag

    (A)

    Angle

    (rad)

    Mag

    (A)

    Angle

    (rad)

    Angle

    Difference(rad)

    Fx 17.6 2.11 63.5 -1.61 -2.56

    Fy 16.1 -0.39 63.5 -1.61 1.22

    Fig. 1. A two-source system

    A B

    Fx Fy

    ~

    Ipre

    ~C

    Fig. 2. (a) Line voltage during close-in fault at relay bus

    (b) CCVT output during close-in fault

    Time (sec)

    Voltae(V)

    0.24 0.26 0.28 0.3 0.32 0.34 0.36-100

    -50

    0

    50

    100

    Voltage(V)

    Time sec0.24 0.26 0.28 0.3 0.32 0.34 0.36

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5x 10

    5

    (a)

    (b)

    TABLE II RESULTS ON CLOSE-IN FAULT

    (POWER FLOW DIRECTION A TO C)

    TABLE III RESULTS ON CLOSE-IN FAULT (POWER FLOWS FROM C TO A

    The authors are with the Department of Electrical Engineering, Indian Institute ofTechnology Kharagpur, INDIA-721302

  • 7/27/2019 PESL-00137-2007.pdf

    2/2

    II. PROPOSED SCHEME

    It is observed that the decision of conventional directional relaying

    is not consistent for close-in faults when prefault voltage becomes

    the polarizing quantity. Numerous cases were simulated and it is

    found that for one direction of power flow such polarizing quantity

    provides correct decision but not for the reverse direction of power

    flow. This is due to fact that the fault current takes a different

    position when the power flow direction is changed. This is clearly

    evident from phasor diagrams in Fig. 3 and Fig.4. Positive

    sequence fault current (I1) and prefault voltage (VB) phasors for

    faults at Fx and Fy sides are available in Fig. 3. It is observed that

    the corresponding phase angle differences x and y are of

    positive and negative values respectively for power flow direction

    from bus A to C. On the other hand x and y for power flow

    direction from bus C to A (Fig.4) are negative and positive values

    respectively. Thus the phasor diagrams indicate that to obtain the

    correct fault direction the angle should be multiplied by -1 in

    the case of reverse power flow; from bus C to A. This provision is

    included in the proposed directional relaying scheme which is

    shown in Fig. 5.

    TABLE IV CLOSE-IN FAULT (POWER FLOWS FROM A TO C)

    TABLE V CLOSE-IN FAULT (POWER FLOWS FROM C TO A )

    To demonstrate the performance of the approach three phase close-

    in faults are simulated at Fx and Fy sides with power flow direction

    from A to C. The result for the case is provided in table 4 and it is

    found that it has correctly identified the direction. Similarly correct

    decisions are observed for power flow direction from C to A as

    presented in table 5.

    III. CONCLUSION

    This paper addressees issues related to close-in-fault in direction

    relaying when memory polarization (prefault voltage) is bein

    applied. It proposes a solution for such low voltage situatio

    using power flow direction as additional information which

    being verified through simulations.

    IV. REFERENCES

    [1] A. G. Phadke, S. H. Horowitz, Power Systems Relaying, Research StudPress, Taunton, 1992.

    [2] D. Birla, R. P. Mahwswari and H. O. Gupta, A new nonlinear directio

    overcurrent relay co-ordination technique, and banes and boons of near-efaults based approach,IEEE Trans. on Power Delivery, vol. 21, no. 3,

    1176-1182, 2006.

    [3] J. Roberts and A. Guzman, Directional element design and evaluatio

    www.selinc.com/techpprs/6009.pdf

    [4] A. K. Pradhan, A. Routray and G. S. Madhan, Fault direction estimation

    radial distribution system using phase change in sequence current, IE

    Trans. on Power Delivery, , vol. 22 , no. 4, pp. 2065 2071, 2007.

    Fault current

    phasor

    Prefault voltage

    phasor

    Power

    FlowDirection

    (PD)

    Angle

    Differenx PD

    Faultpositi

    on

    Mag(A)

    Ang(rad)

    Mag(A)

    Angl(rad)

    Ang(rad)

    Fx 17.1 -0.88 63.5 -1.61 0.73

    Fy 16.2 2.65 63.5 -1.61

    From

    A to C

    (+1)-2.02

    Fault currentphasor Prefault voltagephasor PowerFlowDirection

    (PD)

    AngleDifferenx PD

    Faultpositi

    on

    Mag

    (A)

    Ang

    (rad)

    Mag

    (A)

    Ang

    (rad)

    Ang

    (rad)

    Fx 17.6 2.18 63.5 -1.61 2.49

    Fy 16.1 -0.41 63.5 -1.61

    From

    C to A

    (-1)-1.20

    Fig. 5. Flow diagram for the algorithm

    Start

    Compute the positive

    sequence phasors of

    prefault voltage and

    current

    Compute the

    positive sequence

    phasors at fault

    Voltage and current samples acquisition

    Fault direction estimation

    Output

    Fault detection

    Estimation of

    power

    flow direction

    VC

    VA

    I1Fy

    Ipre

    1I

    (b) fault at Fy

    VC

    VA

    I1Fx

    Ipre

    1I

    (a) fault at Fx

    Fig. 4. Different positive sequence currents when power flows from bus C to A

    VBVB

    x

    y

    1 1pre FxI I I = + 1 1pre FyI I I

    =

    VA

    VC

    I1Fx

    Ipre

    1I

    (a) fault at Fx

    VA

    VC

    I1Fy

    Ipre

    y

    (b) fault at Fy

    Fig. 3. Phasor diagram showing different positive sequence currents, I1Fx and I1Fy -

    fault components only andI1' andI1'' fault currents (including load current) when

    power flows from bus A to C

    1I

    x

    VB VB

    1 1pre FxI I I =

    1 1pre FyI I I

    = +