Pipe Sizing ASHRAE

Embed Size (px)

Citation preview

  • 8/10/2019 Pipe Sizing ASHRAE

    1/2

    33.4

    Allowances for expected decreases in capacity are sometimes

    treated as a specific amount (percentage) . Dawson and Bowman

    (1933)

    added an

    allowance

    of 150Jo

    friction loss to new pipe

    (equivalent to an 8 decrease in capacity). Hennington, Durham,

    and Richardson 1981) increased the friction Joss by

    15

    to 20 for

    closed piping systems

    and 75

    to 90 for open systems. Carr ier

    (1960) indicates a factor

    of

    approximately

    1.75

    between friction

    factors for closed

    and

    open systems.

    Obrecht and Pourbaix (1 7) differentiated between the corrosive

    potential

    of

    different metals in potable water systems and concluded

    that iron is the most severely attacked, then galvanized steel, lead,

    copper, and finally copper alloys (i.e. brass). Hunter

    1941)

    and

    Feeman

    1941)

    showed the same trend. After four years

    of

    cold and

    hot water use, copper pipe ha d a capacity loss of

    25

    to 65 . Aged

    ferrous pipe has a capacity lo

    ss

    of

    40to

    80 . Smith 1983) recom

    mended increasing the design dischange by 1.55 for uncoated cast

    iron,

    1.08 for iron and steel, and 1.06 for cement or concrete.

    The Plastic Pipe Institute

    1971)

    found

    that

    corrosion is not a

    problem in plastic pipe, the capacity

    of

    plastic pipe used in Europe

    and the United States remaining essentially the same after 30 years

    in use.

    Extensive age-related flow

    data

    are available for use with the

    Hazen-Williams empirical equation. Difficulties arise in its ap

    plication, however, because the original Hazen-Williams rough

    ness coefficients are valid only for the specific pipe diameters,

    water velocities, and water viscosities used in the original ex

    periments. Th

    us,

    when the Cs are extended to different diameters,

    velocities, and/or water viscosities, errors

    of

    up to about 50 in

    pipe capacity can occur (Williams

    and Hazen 1933, Sanks 1978).

    Water Hammer

    When any moving fluid (not just water) is abrupt ly stopped as

    when a valve closes suddenly, large pressures can develop. While

    detailed analysis requires knowledge

    of

    the elastic properties of

    the pipe and the flow-time history, the limiting case of rigid pipe

    and instantaneous closure is simple to calculate. Under these

    condjtions,

    (9)

    where

    Ph = pressure ri

    se

    caused by water hammer, lbr/ft

    2

    e = fluid densi

    ty,

    lbn/ ft

    3

    c

    =

    velocity

    of

    sound in the fluid, ft / s

    V

    =

    fluid flow velocity, ft/s

    c for water is 4720 ft / s, although the elasticity

    of

    the pipe

    reduces the effective value.

    30

    20

    :::

    0

    10

    .-

    8

    -

    :::

    6

    u

    I)

    4

    0

    3

    J

    7

    I

    I li

    l/ 1

    I 11

    I

    Cl

    2

    (

    w

    I

    0.5

    0.5

    2 3 4 6 810 20 30 40 60 8 KlO

    1989 Fundamentals Handbook

    Example 3. What

    is

    the maximum pressure

    ri

    se if water flowing at

    10

    ft/s is stopped instantaneously?

    Solution

    Ph

    = 62.4 x 4720 x 10/ 32.2 =

    91468 lb

    / ft

    2

    = 635

    psi

    Other Considerations

    Not discussed in detail in this chapter,

    but of

    potentially great

    importance are a number

    of

    physical and chemical considerations:

    pipe

    and

    fitting design, materials,

    and

    joining methods must be

    appropriate for working pressures and temperatures encountered,

    as well as ~ i n g suitably resistant to chemical attack by the fluid.

    Other Piping Materials and Fluids

    For fluids not included in this chapter

    or

    for piping materials

    of

    different dimensions, manufacturer's literature frequently sup

    plies pressure drop charts. The Darcy-Weisbach equation and the

    Moody chart

    or

    the Colebrook equation can

    be

    used as an alter

    native to pressure drop charts

    or

    tables.

    HOI

    AND CHILLED WATER

    PIPE

    SIZING

    The Darcy-Weisbach equation with friction factors from the

    Moody chart or Colebrook equation (or, alternatively, the Hazen

    Williams equation)

    is

    fundamental to calculating pre

    ss

    ure drop

    in hot and chilled water piping; however, charts calculated from

    these equations (such as Figures I,

    2, and

    3) provide easy deter

    mination

    of

    pressure drops for specific fluids and pipe standards.

    In addition, tables

    of pressure drops can be found in Hydraulic

    Institute (1979)

    and

    Crane Co. (1976).

    Most tables and charts for water are calculated for properties

    at

    60 F. Using these for hot water introduces some error, although

    the answers are conservative;

    i

    cold water calculations overstate

    the pressure drop for hot water. Using 60 F water charts for 200 F

    water should

    not

    result in errors in

    J.p

    exceeding 20 .

    Range of Usage of Pressure Drop Charts

    General Design Range. The general ran ge

    of

    pipe frict ion

    Joss

    used for design

    of

    hydronic systems

    is

    between I

    and

    4 ft/

    100

    ft.

    A value

    of

    2.5 ft/100 ft represents the

    mean

    to which most systems

    are designed. Wider ranges may be used in specific designs, if cer

    tain precautions are taken.

    Piping Noise. Closed loop hydronic system pi ping is generally

    sized below certain arbi trary upper limits, such as a velocity lim it

    of 4 fps for 2-in. pipe and under, and a pressure drop limit of 4 ft

    I

    ....

    ....

    T J

    1/

    ' I Ill l I I r .....

    200

    3 4

    r oo m

    2000 300l 10000 40000

    100

    00

    FLOW

    RATE

    U S

    gal/min

    Fig. 1 Friction Loss for Water in Commercial Stee Pipe (Schedule 40)