Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/121898ETS/121898ETS/121898ETS/121898 C3030/42
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/01/2015
Material Description: Brown Clay, Occ Stone Host + 2% Cement Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
8.28.28.28.2 0.08 0.040.040.040.04
27.127.127.127.1 0.66 0.130.130.130.13
44.644.644.644.6 0.94 0.250.250.250.25
63.163.163.163.1 1.19 0.320.320.320.32
79.579.579.579.5 1.51 0.400.400.400.40
98.698.698.698.6 0.560.560.560.56
114.7114.7114.7114.7 0.770.770.770.77
130.4130.4130.4130.4 0.980.980.980.98
150.0150.0150.0150.0 1.221.221.221.22
166.5166.5166.5166.5 1.391.391.391.39
271.4271.4271.4271.4 0.000.000.000.00
0.00.00.00.0 1.11 0.690.690.690.69
Recovery % 27 50
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 153.0 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 101.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 28.928.928.928.9 %Moisture Content N/A % J A Hardcastle - Managing Director
20/01/2015
Location 2 Grid F3 Cemented Layer
Plate Diameter
Plate Correction Factor
Settlement
Ex-Site
153.0
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-121898 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/121901ETS/121901ETS/121901ETS/121901 C3030/45
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/01/2015
Material Description: Brown Clay, Occ Stone Host + 2% Cement Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
8.28.28.28.2 0.05 0.010.010.010.01
27.127.127.127.1 0.40 0.070.070.070.07
44.644.644.644.6 0.59 0.160.160.160.16
63.163.163.163.1 0.74 0.230.230.230.23
79.579.579.579.5 0.91 0.350.350.350.35
98.698.698.698.6 0.440.440.440.44
114.7114.7114.7114.7 0.560.560.560.56
130.4130.4130.4130.4 0.690.690.690.69
150.0150.0150.0150.0 0.830.830.830.83
166.5166.5166.5166.5 1.001.001.001.00
271.4271.4271.4271.4 1.281.281.281.28
0.00.00.00.0 0.55 0.620.620.620.62
Recovery % 39 52
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 198.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 131.7 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 45.445.445.445.4 %Moisture Content N/A % J A Hardcastle - Managing Director
21/01/2015
Location 2 - Piling Rig
Plate Diameter
Plate Correction Factor
Settlement
Ex-Site
198.6
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-121901 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123078ETS/123078ETS/123078ETS/123078 C3030/135
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 25/02/2015
Material Description: Brown Clay + Occ Stone + Cement Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.010.010.010.01
27.127.127.127.1 0.23 0.080.080.080.08
44.644.644.644.6 0.36 0.120.120.120.12
63.163.163.163.1 0.49 0.150.150.150.15
79.579.579.579.5 0.58 0.190.190.190.19
98.698.698.698.6 0.230.230.230.23
114.7114.7114.7114.7 0.280.280.280.28
130.4130.4130.4130.4 0.340.340.340.34
150.0150.0150.0150.0 0.410.410.410.41
291.1291.1291.1291.1 1.311.311.311.31
346.4346.4346.4346.4 0.000.000.000.00
0.00.00.00.0 0.41 0.210.210.210.21
Recovery % 29 84
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 283.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 187.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 84.184.184.184.1 %Moisture Content N/A % J A Hardcastle - Managing Director
06/02/2015
Crane Mat, Location Number 5
Plate Diameter
Plate Correction Factor
Settlement
Ex-Site
283.3
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123078 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123079ETS/123079ETS/123079ETS/123079 C3030/136
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 25/02/2015
Material Description: Type 1 Stone Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.020.020.020.02
27.127.127.127.1 0.35 0.140.140.140.14
44.644.644.644.6 0.61 0.220.220.220.22
63.163.163.163.1 0.83 0.320.320.320.32
79.579.579.579.5 1.12 0.480.480.480.48
98.698.698.698.6 0.680.680.680.68
114.7114.7114.7114.7 0.880.880.880.88
130.4130.4130.4130.4 1.091.091.091.09
150.0150.0150.0150.0 1.291.291.291.29
291.1291.1291.1291.1 0.000.000.000.00
346.4346.4346.4346.4 0.000.000.000.00
0.00.00.00.0 0.89 0.750.750.750.75
Recovery % 20 42
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 146.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 97.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 26.826.826.826.8 %Moisture Content N/A % J A Hardcastle - Managing Director
06/02/2015
Crane Mat, Location Number 6
Plate Diameter
Plate Correction Factor
Settlement
Ex-Site
146.4
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123079 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123420ETS/123420ETS/123420ETS/123420 C3030/240
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 02/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
19.919.919.919.9 0.46 0.210.210.210.21
37.637.637.637.6 0.77 0.370.370.370.37
54.054.054.054.0 1.01 0.470.470.470.47
72.772.772.772.7 1.21 0.580.580.580.58
89.089.089.089.0 1.35 0.670.670.670.67
104.5104.5104.5104.5 0.760.760.760.76
122.2122.2122.2122.2 0.870.870.870.87
138.3138.3138.3138.3 0.970.970.970.97
153.4153.4153.4153.4 1.061.061.061.06
186.2186.2186.2186.2 1.261.261.261.26
331.6331.6331.6331.6 0.000.000.000.00
0.00.00.00.0 0.75 0.000.000.000.00
Recovery % 45 100
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 184.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 122.5 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 40.140.140.140.1 %Moisture Content N/A % J A Hardcastle - Managing Director
23/02/2015
Top Layer, B5
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
184.8
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123420 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123731ETS/123731ETS/123731ETS/123731 C3030/268
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 02/03/2015
Material Description: Recycled Aggregate Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
19.919.919.919.9 0.32 0.100.100.100.10
37.637.637.637.6 0.45 0.160.160.160.16
54.054.054.054.0 0.60 0.220.220.220.22
72.772.772.772.7 0.74 0.310.310.310.31
89.089.089.089.0 0.85 0.360.360.360.36
104.5104.5104.5104.5 0.420.420.420.42
122.2122.2122.2122.2 0.480.480.480.48
138.3138.3138.3138.3 0.530.530.530.53
153.4153.4153.4153.4 0.600.600.600.60
186.2186.2186.2186.2 0.720.720.720.72
331.6331.6331.6331.6 1.191.191.191.19
0.00.00.00.0 0.50 0.460.460.460.46
Recovery % 42 61
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement >331.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 >220.2 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value >110.8>110.8>110.8>110.8 %Moisture Content N/A % J A Hardcastle - Managing Director
25/02/2015
B1, Base Layer
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123731 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123789AETS/123789AETS/123789AETS/123789A C3030/292A
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: Stone Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.37 0.290.290.290.29
34.134.134.134.1 0.82 0.510.510.510.51
55.555.555.555.5 1.29 0.670.670.670.67
76.976.976.976.9 1.67 0.850.850.850.85
99.599.599.599.5 2.11 0.930.930.930.93
117.2117.2117.2117.2 1.161.161.161.16
143.5143.5143.5143.5 1.991.991.991.99
162.8162.8162.8162.8 2.372.372.372.37
187.5187.5187.5187.5 2.782.782.782.78
251.3251.3251.3251.3 4.094.094.094.09
432.6432.6432.6432.6 0.000.000.000.00
0.00.00.00.0 1.61 1.641.641.641.64
Recovery % 24 60
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 120.0 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 98.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 27.627.627.627.6 %Moisture Content N/A % J A Hardcastle - Managing Director
27/02/2015
E3
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
120.0
0
100
200
300
400
0.00 2.00 4.00 6.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123789A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123789BETS/123789BETS/123789BETS/123789B C3030/292B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: Stone Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.44 0.120.120.120.12
34.134.134.134.1 0.85 0.210.210.210.21
55.555.555.555.5 1.15 0.310.310.310.31
76.976.976.976.9 1.44 0.430.430.430.43
99.599.599.599.5 1.68 0.570.570.570.57
117.2117.2117.2117.2 0.760.760.760.76
143.5143.5143.5143.5 1.031.031.031.03
162.8162.8162.8162.8 1.251.251.251.25
187.5187.5187.5187.5 1.581.581.581.58
251.3251.3251.3251.3 2.512.512.512.51
432.6432.6432.6432.6 0.000.000.000.00
0.00.00.00.0 0.99 0.670.670.670.67
Recovery % 41 73
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 162.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 134.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 46.946.946.946.9 %Moisture Content N/A % J A Hardcastle - Managing Director
27/02/2015
E4
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
162.8
0
100
200
300
400
0.00 1.00 2.00 3.00 4.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123789B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123968AETS/123968AETS/123968AETS/123968A C3030/313
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
14.714.714.714.7 0.18 0.080.080.080.08
48.148.148.148.1 0.67 0.300.300.300.30
79.379.379.379.3 1.05 0.480.480.480.48
112.2112.2112.2112.2 1.40 0.640.640.640.64
141.3141.3141.3141.3 1.74 0.830.830.830.83
175.3175.3175.3175.3 1.111.111.111.11
204.0204.0204.0204.0 1.381.381.381.38
231.9231.9231.9231.9 1.701.701.701.70
266.7266.7266.7266.7 2.012.012.012.01
423.5423.5423.5423.5 3.493.493.493.49
548.9548.9548.9548.9 0.000.000.000.00
0.00.00.00.0 1.04 1.531.531.531.53
Recovery % 40 56
450 mm
0.64
Bearing Pressure @ 1.25mm Settlement 190.2 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 97.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 27.127.127.127.1 %Moisture Content N/A % J A Hardcastle - Managing Director
04/03/2015
Crane Pad 1 - A
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
190.2
0
200
400
600
0.00 2.00 4.00 6.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123968A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123968BETS/123968BETS/123968BETS/123968B C3030/313B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
14.714.714.714.7 0.19 0.050.050.050.05
48.148.148.148.1 0.84 0.220.220.220.22
79.379.379.379.3 1.41 0.340.340.340.34
112.2112.2112.2112.2 1.91 0.490.490.490.49
141.3141.3141.3141.3 2.40 0.640.640.640.64
175.3175.3175.3175.3 0.950.950.950.95
204.0204.0204.0204.0 1.171.171.171.17
231.9231.9231.9231.9 1.451.451.451.45
266.7266.7266.7266.7 1.751.751.751.75
423.5423.5423.5423.5 2.722.722.722.72
548.9548.9548.9548.9 0.000.000.000.00
0.00.00.00.0 1.89 1.371.371.371.37
Recovery % 21 50
450 mm
0.64
Bearing Pressure @ 1.25mm Settlement 211.7 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 108.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 32.732.732.732.7 %Moisture Content N/A % J A Hardcastle - Managing Director
04/03/2015
Crane Pad 1 - B
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
211.7
0
200
400
600
0.00 2.00 4.00 6.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123968B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/123969BETS/123969BETS/123969BETS/123969B C3030/314B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
14.714.714.714.7 0.12 0.050.050.050.05
48.148.148.148.1 0.35 0.280.280.280.28
79.379.379.379.3 0.56 0.450.450.450.45
112.2112.2112.2112.2 0.94 0.640.640.640.64
141.3141.3141.3141.3 1.05 0.800.800.800.80
175.3175.3175.3175.3 1.121.121.121.12
204.0204.0204.0204.0 1.531.531.531.53
231.9231.9231.9231.9 1.951.951.951.95
266.7266.7266.7266.7 2.352.352.352.35
454.8454.8454.8454.8 4.714.714.714.71
548.9548.9548.9548.9 0.000.000.000.00
0.00.00.00.0 0.75 2.392.392.392.39
Recovery % 28 49
450 mm
0.64
Bearing Pressure @ 1.25mm Settlement 184.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 94.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 25.725.725.725.7 %Moisture Content N/A % J A Hardcastle - Managing Director
04/03/2015
Crane Pad 2 - B
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
184.3
0
200
400
600
0.00 2.00 4.00 6.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-123969B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124173AETS/124173AETS/124173AETS/124173A C3030/320
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.39 0.190.190.190.19
55.055.055.055.0 0.76 0.360.360.360.36
89.689.689.689.6 1.00 0.500.500.500.50
124.1124.1124.1124.1 1.22 0.630.630.630.63
160.5160.5160.5160.5 1.41 0.750.750.750.75
189.1189.1189.1189.1 0.890.890.890.89
231.5231.5231.5231.5 1.071.071.071.07
262.6262.6262.6262.6 1.221.221.221.22
302.5302.5302.5302.5 1.411.411.411.41
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.72 0.470.470.470.47
Recovery % 49 67
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 268.2 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 177.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 76.576.576.576.5 %Moisture Content N/A % J A Hardcastle - Managing Director
05/03/2015
C1, Substation
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
268.2
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124173A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124173BETS/124173BETS/124173BETS/124173B C3030/320B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 11/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.86 0.360.360.360.36
55.055.055.055.0 1.85 0.590.590.590.59
89.689.689.689.6 2.38 0.770.770.770.77
124.1124.1124.1124.1 2.80 0.920.920.920.92
160.5160.5160.5160.5 3.20 1.111.111.111.11
189.1189.1189.1189.1 1.451.451.451.45
231.5231.5231.5231.5 0.000.000.000.00
262.6262.6262.6262.6 0.000.000.000.00
302.5302.5302.5302.5 0.000.000.000.00
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 2.31 0.420.420.420.42
Recovery % 28 71
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 172.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 114.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 35.635.635.635.6 %Moisture Content N/A % J A Hardcastle - Managing Director
05/03/2015
B1, Substation
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
172.6
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124173B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477AETS/124477AETS/124477AETS/124477A C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.020.020.020.02
27.127.127.127.1 0.12 0.100.100.100.10
44.644.644.644.6 0.19 0.140.140.140.14
63.163.163.163.1 0.25 0.160.160.160.16
79.579.579.579.5 0.31 0.200.200.200.20
98.698.698.698.6 0.240.240.240.24
114.7114.7114.7114.7 0.290.290.290.29
185.3185.3185.3185.3 0.450.450.450.45
202.7202.7202.7202.7 0.500.500.500.50
220.6220.6220.6220.6 0.540.540.540.54
346.4346.4346.4346.4 0.860.860.860.86
0.00.00.00.0 0.16 0.270.270.270.27
Recovery % 49 68
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement >346.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 >230 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value >119.5>119.5>119.5>119.5 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
C1, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477BETS/124477BETS/124477BETS/124477B C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.010.010.010.01
27.127.127.127.1 0.33 0.090.090.090.09
44.644.644.644.6 0.62 0.150.150.150.15
63.163.163.163.1 0.84 0.220.220.220.22
79.579.579.579.5 1.03 0.340.340.340.34
98.698.698.698.6 0.490.490.490.49
114.7114.7114.7114.7 0.630.630.630.63
185.3185.3185.3185.3 1.281.281.281.28
202.7202.7202.7202.7 1.431.431.431.43
220.6220.6220.6220.6 0.000.000.000.00
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.85 0.810.810.810.81
Recovery % 18 44
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 181.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 120.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 39.039.039.039.0 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
D1, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
181.9
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477CETS/124477CETS/124477CETS/124477C C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.05 0.040.040.040.04
27.127.127.127.1 0.26 0.220.220.220.22
44.644.644.644.6 0.40 0.320.320.320.32
63.163.163.163.1 0.53 0.390.390.390.39
79.579.579.579.5 0.65 0.470.470.470.47
98.698.698.698.6 0.550.550.550.55
114.7114.7114.7114.7 0.630.630.630.63
185.3185.3185.3185.3 0.970.970.970.97
202.7202.7202.7202.7 1.051.051.051.05
255.9255.9255.9255.9 1.301.301.301.30
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.28 0.310.310.310.31
Recovery % 57 76
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 245.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 162.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 65.665.665.665.6 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
B1, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
245.6
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477C Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477DETS/124477DETS/124477DETS/124477D C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.02 0.020.020.020.02
27.127.127.127.1 0.14 0.090.090.090.09
44.644.644.644.6 0.27 0.140.140.140.14
63.163.163.163.1 0.41 0.190.190.190.19
79.579.579.579.5 0.53 0.260.260.260.26
98.698.698.698.6 0.370.370.370.37
114.7114.7114.7114.7 0.490.490.490.49
185.3185.3185.3185.3 0.990.990.990.99
202.7202.7202.7202.7 1.121.121.121.12
255.9255.9255.9255.9 1.501.501.501.50
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.34 0.680.680.680.68
Recovery % 36 55
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 221.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 146.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 54.954.954.954.9 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
B2, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
221.4
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477d Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477EETS/124477EETS/124477EETS/124477E C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.04 0.030.030.030.03
27.127.127.127.1 0.21 0.130.130.130.13
44.644.644.644.6 0.35 0.190.190.190.19
63.163.163.163.1 0.51 0.270.270.270.27
79.579.579.579.5 0.67 0.370.370.370.37
98.698.698.698.6 0.510.510.510.51
114.7114.7114.7114.7 0.670.670.670.67
185.3185.3185.3185.3 1.441.441.441.44
202.7202.7202.7202.7 0.000.000.000.00
255.9255.9255.9255.9 0.000.000.000.00
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.44 0.520.520.520.52
Recovery % 34 64
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 167.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 111.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 33.833.833.833.8 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
B3, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
167.5
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477E Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477FETS/124477FETS/124477FETS/124477F C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.010.010.010.01
27.127.127.127.1 0.16 0.060.060.060.06
44.644.644.644.6 0.27 0.080.080.080.08
63.163.163.163.1 0.37 0.110.110.110.11
79.579.579.579.5 0.48 0.160.160.160.16
98.698.698.698.6 0.230.230.230.23
114.7114.7114.7114.7 0.320.320.320.32
185.3185.3185.3185.3 0.760.760.760.76
202.7202.7202.7202.7 0.870.870.870.87
255.9255.9255.9255.9 1.311.311.311.31
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.39 0.710.710.710.71
Recovery % 19 46
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 248.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 164.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 67.067.067.067.0 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
A3, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
248.5
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477F Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124477GETS/124477GETS/124477GETS/124477G C3030/371
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 26/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.03 0.040.040.040.04
27.127.127.127.1 0.27 0.160.160.160.16
44.644.644.644.6 0.45 0.230.230.230.23
63.163.163.163.1 0.66 0.310.310.310.31
79.579.579.579.5 0.91 0.420.420.420.42
98.698.698.698.6 0.570.570.570.57
114.7114.7114.7114.7 0.720.720.720.72
185.3185.3185.3185.3 1.351.351.351.35
202.7202.7202.7202.7 0.000.000.000.00
255.9255.9255.9255.9 0.000.000.000.00
308.8308.8308.8308.8 0.000.000.000.00
0.00.00.00.0 0.66 0.760.760.760.76
Recovery % 27 44
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 172.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 114.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 35.735.735.735.7 %Moisture Content N/A % J A Hardcastle - Managing Director
11/03/2015
A2, Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
172.8
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124477G Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124617AETS/124617AETS/124617AETS/124617A C3030/372A
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
8.28.28.28.2 0.08 0.060.060.060.06
27.127.127.127.1 0.31 0.170.170.170.17
44.644.644.644.6 0.51 0.240.240.240.24
63.163.163.163.1 0.68 0.300.300.300.30
79.579.579.579.5 0.86 0.400.400.400.40
98.698.698.698.6 0.540.540.540.54
114.7114.7114.7114.7 0.690.690.690.69
130.4130.4130.4130.4 0.850.850.850.85
150.0150.0150.0150.0 1.021.021.021.02
166.5166.5166.5166.5 1.191.191.191.19
185.3185.3185.3185.3 1.371.371.371.37
0.00.00.00.0 0.63 0.780.780.780.78
Recovery % 27 43
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 172.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 114.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 35.735.735.735.7 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
1 - A1 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
172.8
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124617A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124617BETS/124617BETS/124617BETS/124617B C3030/372B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
8.28.28.28.2 0.12 0.020.020.020.02
27.127.127.127.1 0.24 0.100.100.100.10
44.644.644.644.6 0.38 0.170.170.170.17
63.163.163.163.1 0.51 0.270.270.270.27
79.579.579.579.5 0.65 0.360.360.360.36
98.698.698.698.6 0.470.470.470.47
114.7114.7114.7114.7 0.610.610.610.61
130.4130.4130.4130.4 0.790.790.790.79
150.0150.0150.0150.0 1.021.021.021.02
166.5166.5166.5166.5 1.161.161.161.16
185.3185.3185.3185.3 1.351.351.351.35
0.00.00.00.0 0.38 0.460.460.460.46
Recovery % 41 66
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 175.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 116.3 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 36.636.636.636.6 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
2 - J4 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
175.4
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124617B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124617CETS/124617CETS/124617CETS/124617C C3030/372C
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
8.28.28.28.2 0.08 0.050.050.050.05
27.127.127.127.1 0.33 0.210.210.210.21
44.644.644.644.6 0.49 0.300.300.300.30
63.163.163.163.1 0.62 0.370.370.370.37
79.579.579.579.5 0.75 0.440.440.440.44
98.698.698.698.6 0.540.540.540.54
114.7114.7114.7114.7 0.620.620.620.62
130.4130.4130.4130.4 0.690.690.690.69
150.0150.0150.0150.0 0.760.760.760.76
166.5166.5166.5166.5 0.820.820.820.82
291.1291.1291.1291.1 1.271.271.271.27
0.00.00.00.0 0.37 0.460.460.460.46
Recovery % 51 63
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 286.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 190.2 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 85.985.985.985.9 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
3 - J5 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
286.8
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124617C Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124618AETS/124618AETS/124618AETS/124618A C3030/373A
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.18 0.080.080.080.08
34.134.134.134.1 0.33 0.160.160.160.16
55.555.555.555.5 0.47 0.190.190.190.19
76.976.976.976.9 0.57 0.240.240.240.24
99.599.599.599.5 0.70 0.290.290.290.29
117.2117.2117.2117.2 0.370.370.370.37
143.5143.5143.5143.5 0.510.510.510.51
162.8162.8162.8162.8 0.600.600.600.60
187.5187.5187.5187.5 0.680.680.680.68
204.9204.9204.9204.9 0.770.770.770.77
341.5341.5341.5341.5 1.391.391.391.39
0.00.00.00.0 0.56 0.710.710.710.71
Recovery % 19 49
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 316.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 260.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 148.5148.5148.5148.5 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
1 - C5 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
316.6
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124618A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124618BETS/124618BETS/124618BETS/124618B C3030/373B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.12 0.150.150.150.15
34.134.134.134.1 0.29 0.260.260.260.26
55.555.555.555.5 0.36 0.300.300.300.30
76.976.976.976.9 0.44 0.350.350.350.35
99.599.599.599.5 0.53 0.400.400.400.40
117.2117.2117.2117.2 0.470.470.470.47
143.5143.5143.5143.5 0.550.550.550.55
162.8162.8162.8162.8 0.630.630.630.63
187.5187.5187.5187.5 0.690.690.690.69
204.9204.9204.9204.9 0.820.820.820.82
341.5341.5341.5341.5 1.381.381.381.38
0.00.00.00.0 0.30 0.480.480.480.48
Recovery % 44 65
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 310.0 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 255.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 143.2143.2143.2143.2 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
2 - C4 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
310.0
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124618B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124618CETS/124618CETS/124618CETS/124618C C3030/373C
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.05 0.050.050.050.05
34.134.134.134.1 0.08 0.080.080.080.08
55.555.555.555.5 0.12 0.110.110.110.11
76.976.976.976.9 0.16 0.140.140.140.14
99.599.599.599.5 0.20 0.200.200.200.20
117.2117.2117.2117.2 0.250.250.250.25
143.5143.5143.5143.5 0.290.290.290.29
162.8162.8162.8162.8 0.330.330.330.33
187.5187.5187.5187.5 0.400.400.400.40
204.9204.9204.9204.9 0.440.440.440.44
434.1434.1434.1434.1 0.890.890.890.89
0.00.00.00.0 0.05 0.480.480.480.48
Recovery % 77 46
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement >434.1 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 >357.7 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value >256.8>256.8>256.8>256.8 %Moisture Content N/A % J A Hardcastle - Managing Director
12/03/2015
3 - C3 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124618C Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619AETS/124619AETS/124619AETS/124619A C3030/374A
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.96 0.070.070.070.07
34.134.134.134.1 1.51 0.130.130.130.13
55.555.555.555.5 1.83 0.200.200.200.20
76.976.976.976.9 2.04 0.260.260.260.26
99.599.599.599.5 2.16 0.320.320.320.32
117.2117.2117.2117.2 0.420.420.420.42
143.5143.5143.5143.5 0.490.490.490.49
162.8162.8162.8162.8 0.600.600.600.60
187.5187.5187.5187.5 0.730.730.730.73
231.5231.5231.5231.5 0.950.950.950.95
318.4318.4318.4318.4 1.341.341.341.34
0.00.00.00.0 1.98 0.770.770.770.77
Recovery % 8 42
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 302.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 249.5 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 137.5137.5137.5137.5 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
1 - D3 Injection Bay
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
302.9
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619BETS/124619BETS/124619BETS/124619B C3030/374B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.56 0.180.180.180.18
34.134.134.134.1 0.91 0.300.300.300.30
55.555.555.555.5 1.23 0.370.370.370.37
76.976.976.976.9 1.54 0.460.460.460.46
99.599.599.599.5 1.70 0.540.540.540.54
117.2117.2117.2117.2 0.620.620.620.62
143.5143.5143.5143.5 0.730.730.730.73
162.8162.8162.8162.8 0.860.860.860.86
187.5187.5187.5187.5 0.980.980.980.98
231.5231.5231.5231.5 1.181.181.181.18
275.5275.5275.5275.5 1.431.431.431.43
0.00.00.00.0 1.28 0.590.590.590.59
Recovery % 24 59
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 242.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 199.7 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 93.593.593.593.5 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
2 - D4 Injection Bay
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
242.5
0
200
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619B Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619CETS/124619CETS/124619CETS/124619C C3030/374C
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.32 0.170.170.170.17
34.134.134.134.1 0.51 0.310.310.310.31
55.555.555.555.5 0.72 0.400.400.400.40
76.976.976.976.9 0.88 0.510.510.510.51
99.599.599.599.5 1.05 0.590.590.590.59
117.2117.2117.2117.2 0.680.680.680.68
143.5143.5143.5143.5 0.790.790.790.79
162.8162.8162.8162.8 0.930.930.930.93
187.5187.5187.5187.5 1.051.051.051.05
231.5231.5231.5231.5 1.251.251.251.25
275.5275.5275.5275.5 0.000.000.000.00
0.00.00.00.0 0.67 0.640.640.640.64
Recovery % 36 49
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 231.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 190.7 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 86.386.386.386.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
3 - D5 Injection Bay
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
231.5
0
200
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619C Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619DETS/124619DETS/124619DETS/124619D C3030/374D
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.59 0.130.130.130.13
34.134.134.134.1 0.92 0.230.230.230.23
55.555.555.555.5 1.04 0.280.280.280.28
76.976.976.976.9 1.22 0.340.340.340.34
99.599.599.599.5 1.40 0.390.390.390.39
117.2117.2117.2117.2 0.480.480.480.48
143.5143.5143.5143.5 0.610.610.610.61
162.8162.8162.8162.8 0.720.720.720.72
187.5187.5187.5187.5 0.820.820.820.82
231.5231.5231.5231.5 1.041.041.041.04
318.4318.4318.4318.4 1.451.451.451.45
0.00.00.00.0 1.15 0.750.750.750.75
Recovery % 18 48
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 273.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 225.3 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 115.3115.3115.3115.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
4 - D6 Injection Bay
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
273.5
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619D Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619EETS/124619EETS/124619EETS/124619E C3030/374E
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.46 0.350.350.350.35
34.134.134.134.1 0.96 0.500.500.500.50
55.555.555.555.5 1.39 0.620.620.620.62
76.976.976.976.9 1.75 0.730.730.730.73
99.599.599.599.5 2.06 0.840.840.840.84
117.2117.2117.2117.2 0.960.960.960.96
143.5143.5143.5143.5 1.061.061.061.06
162.8162.8162.8162.8 1.151.151.151.15
187.5187.5187.5187.5 1.231.231.231.23
204.9204.9204.9204.9 1.301.301.301.30
318.4318.4318.4318.4 0.000.000.000.00
0.00.00.00.0 0.95 0.620.620.620.62
Recovery % 54 53
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 192.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 158.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 62.662.662.662.6 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
5 - E6
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
192.3
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619E Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619FETS/124619FETS/124619FETS/124619F C3030/374F
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.55 0.320.320.320.32
34.134.134.134.1 1.12 0.440.440.440.44
55.555.555.555.5 1.62 0.570.570.570.57
76.976.976.976.9 2.03 0.640.640.640.64
99.599.599.599.5 2.38 0.780.780.780.78
117.2117.2117.2117.2 0.960.960.960.96
143.5143.5143.5143.5 1.101.101.101.10
162.8162.8162.8162.8 1.271.271.271.27
187.5187.5187.5187.5 0.000.000.000.00
204.9204.9204.9204.9 0.000.000.000.00
318.4318.4318.4318.4 0.000.000.000.00
0.00.00.00.0 1.87 0.000.000.000.00
Recovery % 22 100
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 160.2 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 132.0 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 45.645.645.645.6 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
6 - F2
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
160.2
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619F Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619GETS/124619GETS/124619GETS/124619G C3030/374G
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.60 0.320.320.320.32
34.134.134.134.1 0.61 0.430.430.430.43
55.555.555.555.5 1.36 0.560.560.560.56
76.976.976.976.9 1.69 0.670.670.670.67
99.599.599.599.5 1.97 0.800.800.800.80
117.2117.2117.2117.2 1.001.001.001.00
143.5143.5143.5143.5 1.231.231.231.23
162.8162.8162.8162.8 1.421.421.421.42
187.5187.5187.5187.5 0.000.000.000.00
204.9204.9204.9204.9 0.000.000.000.00
318.4318.4318.4318.4 0.000.000.000.00
0.00.00.00.0 1.35 0.510.510.510.51
Recovery % 31 64
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 145.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 120.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 38.838.838.838.8 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
7 - F3
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
145.8
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619G Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619HETS/124619HETS/124619HETS/124619H C3030/374H
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.21 0.220.220.220.22
34.134.134.134.1 0.50 0.370.370.370.37
55.555.555.555.5 0.82 0.520.520.520.52
76.976.976.976.9 1.13 0.650.650.650.65
99.599.599.599.5 1.47 0.740.740.740.74
117.2117.2117.2117.2 0.900.900.900.90
143.5143.5143.5143.5 1.171.171.171.17
162.8162.8162.8162.8 1.441.441.441.44
187.5187.5187.5187.5 1.681.681.681.68
204.9204.9204.9204.9 0.000.000.000.00
318.4318.4318.4318.4 0.000.000.000.00
0.00.00.00.0 1.00 0.650.650.650.65
Recovery % 32 61
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 149.1 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 122.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 40.340.340.340.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
8 - E2
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
149.1
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619H Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619IETS/124619IETS/124619IETS/124619I C3030/374I
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.17 0.080.080.080.08
34.134.134.134.1 0.32 0.150.150.150.15
55.555.555.555.5 0.48 0.200.200.200.20
76.976.976.976.9 0.59 0.220.220.220.22
99.599.599.599.5 0.69 0.270.270.270.27
117.2117.2117.2117.2 0.320.320.320.32
143.5143.5143.5143.5 0.390.390.390.39
162.8162.8162.8162.8 0.470.470.470.47
187.5187.5187.5187.5 0.540.540.540.54
204.9204.9204.9204.9 0.600.600.600.60
434.1434.1434.1434.1 1.261.261.261.26
0.00.00.00.0 0.47 0.680.680.680.68
Recovery % 31 46
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 430.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 354.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 253.3253.3253.3253.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
9 - D2
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
430.8
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619I Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619JETS/124619JETS/124619JETS/124619J C3030/374J
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.29 0.190.190.190.19
34.134.134.134.1 0.50 0.360.360.360.36
55.555.555.555.5 0.67 0.430.430.430.43
76.976.976.976.9 0.82 0.540.540.540.54
99.599.599.599.5 1.33 0.710.710.710.71
117.2117.2117.2117.2 0.830.830.830.83
143.5143.5143.5143.5 0.920.920.920.92
162.8162.8162.8162.8 1.091.091.091.09
187.5187.5187.5187.5 1.261.261.261.26
204.9204.9204.9204.9 1.371.371.371.37
275.5275.5275.5275.5 1.811.811.811.81
0.00.00.00.0 0.93 1.381.381.381.38
Recovery % 30 24
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 185.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 152.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 58.958.958.958.9 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
10 - E5 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
185.6
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619J Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619KETS/124619KETS/124619KETS/124619K C3030/374K
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.30 0.170.170.170.17
34.134.134.134.1 0.52 0.350.350.350.35
55.555.555.555.5 0.67 0.410.410.410.41
76.976.976.976.9 0.84 0.480.480.480.48
99.599.599.599.5 1.34 0.590.590.590.59
117.2117.2117.2117.2 0.750.750.750.75
143.5143.5143.5143.5 0.840.840.840.84
162.8162.8162.8162.8 1.021.021.021.02
187.5187.5187.5187.5 1.151.151.151.15
204.9204.9204.9204.9 1.301.301.301.30
275.5275.5275.5275.5 1.731.731.731.73
0.00.00.00.0 0.95 1.301.301.301.30
Recovery % 29 25
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 199.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 164.3 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 66.766.766.766.7 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
11 - F6 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
199.4
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619K Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619LETS/124619LETS/124619LETS/124619L C3030/374L
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.53 0.170.170.170.17
34.134.134.134.1 0.95 0.270.270.270.27
55.555.555.555.5 1.31 0.400.400.400.40
76.976.976.976.9 1.57 0.470.470.470.47
99.599.599.599.5 1.82 0.550.550.550.55
117.2117.2117.2117.2 0.670.670.670.67
143.5143.5143.5143.5 0.820.820.820.82
162.8162.8162.8162.8 1.001.001.001.00
187.5187.5187.5187.5 1.251.251.251.25
204.9204.9204.9204.9 1.381.381.381.38
231.5231.5231.5231.5 1.511.511.511.51
0.00.00.00.0 1.43 0.810.810.810.81
Recovery % 21 46
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 187.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 154.5 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 59.959.959.959.9 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
12 - G6 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
187.5
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619L Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619METS/124619METS/124619METS/124619M C3030/374M
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.48 0.240.240.240.24
34.134.134.134.1 0.90 0.350.350.350.35
55.555.555.555.5 1.28 0.460.460.460.46
76.976.976.976.9 1.61 0.560.560.560.56
99.599.599.599.5 1.91 0.680.680.680.68
117.2117.2117.2117.2 0.770.770.770.77
143.5143.5143.5143.5 0.880.880.880.88
162.8162.8162.8162.8 0.980.980.980.98
187.5187.5187.5187.5 1.111.111.111.11
204.9204.9204.9204.9 1.201.201.201.20
231.5231.5231.5231.5 1.271.271.271.27
0.00.00.00.0 1.26 0.780.780.780.78
Recovery % 34 38
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 223.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 184.0 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 81.281.281.281.2 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
13 - H6 Top Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
223.4
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619M Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619NETS/124619NETS/124619NETS/124619N C3030/374N
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.17 0.190.190.190.19
34.134.134.134.1 0.41 0.350.350.350.35
55.555.555.555.5 0.72 0.500.500.500.50
76.976.976.976.9 0.95 0.680.680.680.68
99.599.599.599.5 1.18 0.900.900.900.90
117.2117.2117.2117.2 1.081.081.081.08
143.5143.5143.5143.5 1.391.391.391.39
162.8162.8162.8162.8 1.661.661.661.66
187.5187.5187.5187.5 2.012.012.012.01
204.9204.9204.9204.9 2.332.332.332.33
318.4318.4318.4318.4 4.504.504.504.50
0.00.00.00.0 0.52 1.561.561.561.56
Recovery % 56 65
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 131.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 108.2 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 32.332.332.332.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
14 - H2
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
131.4
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00 6.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619N Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124619OETS/124619OETS/124619OETS/124619O C3030/374O
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.38 0.200.200.200.20
34.134.134.134.1 0.77 0.410.410.410.41
55.555.555.555.5 1.21 0.620.620.620.62
76.976.976.976.9 1.55 0.820.820.820.82
99.599.599.599.5 1.89 1.001.001.001.00
117.2117.2117.2117.2 1.191.191.191.19
143.5143.5143.5143.5 1.301.301.301.30
162.8162.8162.8162.8 1.481.481.481.48
187.5187.5187.5187.5 0.000.000.000.00
204.9204.9204.9204.9 0.000.000.000.00
318.4318.4318.4318.4 0.000.000.000.00
0.00.00.00.0 1.11 0.490.490.490.49
Recovery % 41 67
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 131.7 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 108.5 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 32.532.532.532.5 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
15 - E3
Plate Diameter
Plate Correction Factor
Settlement
Ex Site
131.7
0
100
200
300
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124619O Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628AETS/124628AETS/124628AETS/124628A C3030/375A
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.36 0.190.190.190.19
34.134.134.134.1 0.65 0.330.330.330.33
55.555.555.555.5 0.85 0.420.420.420.42
76.976.976.976.9 1.00 0.490.490.490.49
99.599.599.599.5 1.16 0.580.580.580.58
117.2117.2117.2117.2 0.650.650.650.65
162.8162.8162.8162.8 0.860.860.860.86
231.5231.5231.5231.5 1.191.191.191.19
297.5297.5297.5297.5 1.491.491.491.49
341.5341.5341.5341.5 1.701.701.701.70
434.1434.1434.1434.1 2.102.102.102.10
0.00.00.00.0 0.61 0.910.910.910.91
Recovery % 47 57
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 242.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 199.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 93.593.593.593.5 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
F4
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
242.3
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628A.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628BETS/124628BETS/124628BETS/124628B C3030/375B
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.41 0.130.130.130.13
34.134.134.134.1 0.98 0.220.220.220.22
55.555.555.555.5 1.57 0.300.300.300.30
76.976.976.976.9 2.10 0.370.370.370.37
99.599.599.599.5 2.67 0.460.460.460.46
117.2117.2117.2117.2 0.570.570.570.57
162.8162.8162.8162.8 1.041.041.041.04
231.5231.5231.5231.5 1.721.721.721.72
297.5297.5297.5297.5 2.452.452.452.45
341.5341.5341.5341.5 2.942.942.942.94
434.1434.1434.1434.1 3.363.363.363.36
0.00.00.00.0 1.34 0.780.780.780.78
Recovery % 50 77
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 183.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 151.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 57.957.957.957.9 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
F5
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
183.8
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628B.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628CETS/124628CETS/124628CETS/124628C C3030/375C
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.36 0.140.140.140.14
34.134.134.134.1 0.56 0.240.240.240.24
55.555.555.555.5 0.82 0.380.380.380.38
76.976.976.976.9 1.04 0.500.500.500.50
99.599.599.599.5 1.21 0.640.640.640.64
117.2117.2117.2117.2 0.760.760.760.76
162.8162.8162.8162.8 1.091.091.091.09
231.5231.5231.5231.5 1.561.561.561.56
297.5297.5297.5297.5 1.961.961.961.96
341.5341.5341.5341.5 2.222.222.222.22
434.1434.1434.1434.1 2.792.792.792.79
0.00.00.00.0 0.49 0.650.650.650.65
Recovery % 59 77
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 187.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 154.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 60.160.160.160.1 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
G2
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
187.9
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628C.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628DETS/124628DETS/124628DETS/124628D C3030/375D
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.35 0.200.200.200.20
34.134.134.134.1 0.54 0.350.350.350.35
55.555.555.555.5 0.77 0.600.600.600.60
76.976.976.976.9 0.96 0.770.770.770.77
99.599.599.599.5 1.23 0.980.980.980.98
117.2117.2117.2117.2 1.181.181.181.18
162.8162.8162.8162.8 1.641.641.641.64
231.5231.5231.5231.5 2.342.342.342.34
297.5297.5297.5297.5 3.033.033.033.03
341.5341.5341.5341.5 3.483.483.483.48
434.1434.1434.1434.1 4.194.194.194.19
0.00.00.00.0 0.00 1.371.371.371.37
Recovery % 100 67
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 125.6 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 103.5 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 29.929.929.929.9 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
G3
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
125.6
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628D.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628EETS/124628EETS/124628EETS/124628E C3030/375E
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.17 0.310.310.310.31
34.134.134.134.1 0.44 0.440.440.440.44
55.555.555.555.5 0.63 0.560.560.560.56
76.976.976.976.9 0.83 0.670.670.670.67
99.599.599.599.5 1.15 0.760.760.760.76
117.2117.2117.2117.2 0.900.900.900.90
162.8162.8162.8162.8 1.231.231.231.23
231.5231.5231.5231.5 1.601.601.601.60
297.5297.5297.5297.5 1.941.941.941.94
341.5341.5341.5341.5 2.162.162.162.16
434.1434.1434.1434.1 2.532.532.532.53
0.00.00.00.0 0.51 0.000.000.000.00
Recovery % 56 100
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 167.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 138.2 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 49.449.449.449.4 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
G4
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
167.8
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628E.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628FETS/124628FETS/124628FETS/124628F C3030/375F
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.18 0.310.310.310.31
34.134.134.134.1 0.46 0.570.570.570.57
55.555.555.555.5 0.74 0.690.690.690.69
76.976.976.976.9 1.00 0.750.750.750.75
99.599.599.599.5 1.20 0.800.800.800.80
117.2117.2117.2117.2 0.890.890.890.89
162.8162.8162.8162.8 1.191.191.191.19
231.5231.5231.5231.5 1.531.531.531.53
297.5297.5297.5297.5 1.821.821.821.82
341.5341.5341.5341.5 2.002.002.002.00
434.1434.1434.1434.1 0.000.000.000.00
0.00.00.00.0 0.67 0.590.590.590.59
Recovery % 44 70
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 173.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 142.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 52.352.352.352.3 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
G5
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
173.3
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628F.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628GETS/124628GETS/124628GETS/124628G C3030/375G
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.16 0.180.180.180.18
34.134.134.134.1 0.45 0.340.340.340.34
55.555.555.555.5 0.70 0.490.490.490.49
76.976.976.976.9 1.00 0.590.590.590.59
99.599.599.599.5 1.16 0.700.700.700.70
117.2117.2117.2117.2 0.840.840.840.84
162.8162.8162.8162.8 1.171.171.171.17
231.5231.5231.5231.5 2.332.332.332.33
297.5297.5297.5297.5 2.852.852.852.85
341.5341.5341.5341.5 3.183.183.183.18
434.1434.1434.1434.1 3.523.523.523.52
0.00.00.00.0 0.67 1.821.821.821.82
Recovery % 43 48
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 169.2 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 139.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 50.150.150.150.1 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
H3
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
169.2
0
200
400
600
0.00 1.00 2.00 3.00 4.00 5.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628G Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628HETS/124628HETS/124628HETS/124628H C3030/375H
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: Brown Clay Occ Stone Host + 2% Lime Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
15.415.415.415.4 0.11 0.190.190.190.19
34.134.134.134.1 0.34 0.280.280.280.28
55.555.555.555.5 0.57 0.330.330.330.33
76.976.976.976.9 0.69 0.360.360.360.36
99.599.599.599.5 0.84 0.420.420.420.42
117.2117.2117.2117.2 0.480.480.480.48
162.8162.8162.8162.8 0.590.590.590.59
231.5231.5231.5231.5 0.880.880.880.88
297.5297.5297.5297.5 1.261.261.261.26
341.5341.5341.5341.5 1.401.401.401.40
434.1434.1434.1434.1 1.701.701.701.70
0.00.00.00.0 0.29 0.650.650.650.65
Recovery % 66 62
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 294.2 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 242.3 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 130.8130.8130.8130.8 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
H4
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
294.2
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628H Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/124628IETS/124628IETS/124628IETS/124628I C3030/375I
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 16/03/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2 mm mm
15.415.415.415.4 0.28 0.190.190.190.19
34.134.134.134.1 0.47 0.290.290.290.29
55.555.555.555.5 0.69 0.370.370.370.37
76.976.976.976.9 0.90 0.430.430.430.43
99.599.599.599.5 1.01 0.490.490.490.49
117.2117.2117.2117.2 0.540.540.540.54
162.8162.8162.8162.8 0.720.720.720.72
231.5231.5231.5231.5 1.031.031.031.03
297.5297.5297.5297.5 1.381.381.381.38
341.5341.5341.5341.5 1.711.711.711.71
434.1434.1434.1434.1 2.402.402.402.40
0.00.00.00.0 0.66 1.381.381.381.38
Recovery % 34 42
762 mm
1.03
Bearing Pressure @ 1.25mm Settlement 272.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 224.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 114.8114.8114.8114.8 %Moisture Content N/A % J A Hardcastle - Managing Director
14/03/2015
H5
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
272.9
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Beari
ng P
ressure
(kN
/m2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-124628I.xlsx Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126800ETS/126800ETS/126800ETS/126800 C3030/400
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.51 0.200.200.200.20
55.055.055.055.0 0.68 0.350.350.350.35
89.689.689.689.6 0.86 0.490.490.490.49
124.1124.1124.1124.1 1.09 0.650.650.650.65
160.5160.5160.5160.5 1.30 0.790.790.790.79
189.1189.1189.1189.1 0.910.910.910.91
231.5231.5231.5231.5 1.041.041.041.04
262.6262.6262.6262.6 1.191.191.191.19
302.5302.5302.5302.5 1.331.331.331.33
444.4444.4444.4444.4 0.000.000.000.00
0.00.00.00.0 0.000.000.000.00
0.00.00.00.0 0.85 0.420.420.420.42
Recovery % 35 69
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 279.3 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 185.2 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 82.082.082.082.0 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid C2, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
279.3
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126800A Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126801ETS/126801ETS/126801ETS/126801 C3030/401
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.27 0.160.160.160.16
55.055.055.055.0 0.47 0.310.310.310.31
89.689.689.689.6 0.67 0.470.470.470.47
124.1124.1124.1124.1 0.85 0.600.600.600.60
160.5160.5160.5160.5 1.13 0.720.720.720.72
189.1189.1189.1189.1 0.850.850.850.85
231.5231.5231.5231.5 0.980.980.980.98
262.6262.6262.6262.6 1.121.121.121.12
302.5302.5302.5302.5 1.261.261.261.26
444.4444.4444.4444.4 0.000.000.000.00
0.00.00.00.0 0.000.000.000.00
0.00.00.00.0 0.45 0.460.460.460.46
Recovery % 60 64
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 299.5 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 198.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 92.692.692.692.6 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid C6, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
299.5
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126801 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126802ETS/126802ETS/126802ETS/126802 C3030/402
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.25 0.170.170.170.17
55.055.055.055.0 0.45 0.290.290.290.29
89.689.689.689.6 0.65 0.430.430.430.43
124.1124.1124.1124.1 0.85 0.590.590.590.59
160.5160.5160.5160.5 1.05 0.750.750.750.75
189.1189.1189.1189.1 0.930.930.930.93
231.5231.5231.5231.5 1.121.121.121.12
262.6262.6262.6262.6 1.261.261.261.26
302.5302.5302.5302.5 1.491.491.491.49
373.4373.4373.4373.4 1.941.941.941.94
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.54 0.530.530.530.53
Recovery % 48 72
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 261.0 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 173.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 73.073.073.073.0 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid J6, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
261.0
0
100
200
300
400
500
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126802 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126803ETS/126803ETS/126803ETS/126803 C3030/403
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.34 0.200.200.200.20
55.055.055.055.0 0.63 0.410.410.410.41
89.689.689.689.6 0.92 0.630.630.630.63
124.1124.1124.1124.1 1.19 0.810.810.810.81
160.5160.5160.5160.5 1.44 1.021.021.021.02
189.1189.1189.1189.1 1.251.251.251.25
231.5231.5231.5231.5 1.441.441.441.44
262.6262.6262.6262.6 1.671.671.671.67
302.5302.5302.5302.5 1.851.851.851.85
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.68 0.620.620.620.62
Recovery % 53 66
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 189.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 125.9 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 42.042.042.042.0 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid K5, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
189.9
0
100
200
300
400
500
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126803 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126804ETS/126804ETS/126804ETS/126804 C3030/404
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.29 0.130.130.130.13
55.055.055.055.0 0.58 0.230.230.230.23
89.689.689.689.6 0.79 0.440.440.440.44
124.1124.1124.1124.1 1.04 0.660.660.660.66
160.5160.5160.5160.5 1.28 0.880.880.880.88
189.1189.1189.1189.1 1.091.091.091.09
231.5231.5231.5231.5 1.271.271.271.27
262.6262.6262.6262.6 1.471.471.471.47
302.5302.5302.5302.5 0.000.000.000.00
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.57 0.600.600.600.60
Recovery % 55 59
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 226.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 150.4 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 57.257.257.257.2 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid J2, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
226.8
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126804 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126805ETS/126805ETS/126805ETS/126805 C3030/405
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.34 0.180.180.180.18
55.055.055.055.0 0.60 0.340.340.340.34
89.689.689.689.6 0.83 0.510.510.510.51
124.1124.1124.1124.1 1.07 0.720.720.720.72
160.5160.5160.5160.5 1.32 0.890.890.890.89
189.1189.1189.1189.1 1.071.071.071.07
231.5231.5231.5231.5 1.281.281.281.28
262.6262.6262.6262.6 1.541.541.541.54
302.5302.5302.5302.5 1.741.741.741.74
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.51 0.700.700.700.70
Recovery % 61 60
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 225.9 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 149.8 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 56.856.856.856.8 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid J3, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
225.9
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126805 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126806ETS/126806ETS/126806ETS/126806 C3030/406
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.31 0.050.050.050.05
55.055.055.055.0 0.44 0.070.070.070.07
89.689.689.689.6 0.55 0.080.080.080.08
124.1124.1124.1124.1 0.64 0.100.100.100.10
160.5160.5160.5160.5 0.71 0.120.120.120.12
189.1189.1189.1189.1 0.150.150.150.15
231.5231.5231.5231.5 0.180.180.180.18
262.6262.6262.6262.6 0.210.210.210.21
302.5302.5302.5302.5 0.240.240.240.24
444.4444.4444.4444.4 0.380.380.380.38
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 0.63 0.250.250.250.25
Recovery % 11 35
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement >444.4 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 295.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value >184>184>184>184 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid K4, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
0
200
400
600
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Press
ure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126806 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126807ETS/126807ETS/126807ETS/126807 C3030/407
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
24.924.924.924.9 0.70 0.290.290.290.29
55.055.055.055.0 1.36 0.570.570.570.57
89.689.689.689.6 1.94 0.730.730.730.73
124.1124.1124.1124.1 2.46 0.910.910.910.91
160.5160.5160.5160.5 2.90 1.171.171.171.17
189.1189.1189.1189.1 1.591.591.591.59
231.5231.5231.5231.5 2.312.312.312.31
262.6262.6262.6262.6 3.043.043.043.04
302.5302.5302.5302.5 3.693.693.693.69
373.4373.4373.4373.4 0.000.000.000.00
700.2700.2700.2700.2 0.000.000.000.00
0.00.00.00.0 1.91 1.361.361.361.36
Recovery % 34 63
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 166.1 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 110.1 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 33.333.333.333.3 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid K3, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
166.1
0
100
200
300
400
0.00 1.00 2.00 3.00 4.00 5.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126807 Page 1 of 1
Collins Earthworks Ltd
Unit 2B
Park Lane
Kirkby-In-Ashfield
Nottingham
NG17 9LE
Project PEPE, WarringtonProject PEPE, WarringtonProject PEPE, WarringtonProject PEPE, Warrington
Plate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR ValuePlate Loading Test to determine equivalent CBR Value REPORT NO:REPORT NO:REPORT NO:REPORT NO: ETS/126808ETS/126808ETS/126808ETS/126808 C3030/408
In house method based on BS1377: Part 9: 1990 & HA 25/95 (replaced by IAN 73/06) Report Date: 24/04/2015
Material Description: T1SB Date Tested:
Supplier/Source: Test Location:
Load
Bearing Pressure Seating Load Test Load
kN/m2
mm mm
5.05.05.05.0 0.04 0.050.050.050.05
24.924.924.924.9 0.09 0.080.080.080.08
39.339.339.339.3 0.13 0.110.110.110.11
55.055.055.055.0 0.17 0.150.150.150.15
72.172.172.172.1 0.21 0.180.180.180.18
89.689.689.689.6 0.220.220.220.22
107.3107.3107.3107.3 0.290.290.290.29
124.1124.1124.1124.1 0.350.350.350.35
142.8142.8142.8142.8 0.480.480.480.48
249.2249.2249.2249.2 1.271.271.271.27
302.5302.5302.5302.5 0.000.000.000.00
0.00.00.00.0 0.08 0.870.870.870.87
Recovery % 62 32
600 mm
0.83
Bearing Pressure @ 1.25mm Settlement 246.8 kN/m² Authorised Signatory
Modulus of Subgrade Reaction K762 163.6 kN/m²/mm
Equivalent CBR ValueEquivalent CBR ValueEquivalent CBR ValueEquivalent CBR Value 66.266.266.266.2 %Moisture Content N/A % J A Hardcastle - Managing Director
23/04/2015
Grid K6, H/S Layer
Plate Diameter
Plate Correction Factor
Settlement
Not Stated
246.8
0
100
200
300
400
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Bearing Pressure (kN/m
2)
Settlement (mm)
Load vs Settlement DataTEST LOAD
Expon. (Test Load)
R:\ETS Reports\Collins Earthworks\C3030 - Project PEPE, Warrington\Plates\ETS-126808 Page 1 of 1