37

power sysetm

Embed Size (px)

Citation preview

Page 1: power sysetm
Page 2: power sysetm
Page 3: power sysetm
Page 4: power sysetm
Page 5: power sysetm
Page 6: power sysetm

Per Unit CalculationsA key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually refer

impedances to the different sides of the transformers

This problem is avoided by a normalization of all variables.

This normalization is known as per unit analysis.

actual quantityquantity in per unit base value of quantity

Page 7: power sysetm

Per Unit Conversion Procedure, 11. Pick a 1 VA base for the entire system, SB

2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral.

3. Calculate the impedance base, ZB= (VB)2/SB

4. Calculate the current base, IB = VB/ZB 5. Convert actual values to per unit

Note, per unit conversion affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)

Page 8: power sysetm

Three Phase Per Unit

1. Pick a 3 VA base for the entire system, 2. Pick a voltage base for each different

voltage level, VB. Voltages are line to line. 3. Calculate the impedance base

Procedure is very similar to 1 except we use a 3 VA base, and use line to line voltage bases

3BS

2 2 2, , ,3 1 1

( 3 )3

B LL B LN B LNB

B B B

V V VZ

S S S

Exactly the same impedance bases as with single phase!

Page 9: power sysetm

Three Phase Per Unit, cont'd4. Calculate the current base, IB

5. Convert actual values to per unit

3 1 13 1B B

, , ,

3I I3 3 3B B B

B LL B LN B LN

S S SV V V

Exactly the same current bases as with single phase!

Page 10: power sysetm
Page 11: power sysetm
Page 12: power sysetm
Page 13: power sysetm
Page 14: power sysetm
Page 15: power sysetm
Page 16: power sysetm
Page 17: power sysetm
Page 18: power sysetm
Page 19: power sysetm
Page 20: power sysetm
Page 21: power sysetm
Page 22: power sysetm
Page 23: power sysetm

Load Representation

Page 24: power sysetm
Page 25: power sysetm
Page 26: power sysetm

Transmission Circuit Calculations

Page 27: power sysetm

Short Transmission lineIn the case of a short transmission line the capacitance and

conductance to earth may be neglected. Leaving only the series resistance and inductance to be taken

into consideration. The current entering the line at the sending-end termination

is equal to the current leaving at the receiving-end, and this same current flows through all the line sections.

The R and L parameters may therefore be regarded as ' lumped ' .

Page 28: power sysetm

The equivalent circuit diagram and the vector diagram for a short line are shown below in which:

Equivalent circuit for a short transmission line

Page 29: power sysetm

Vector diagram for a short transmission line .

Page 30: power sysetm

The currents IS and IR will be equal in magnitude but not in phase.

Since there is a phase-shift of voltage along the line. R is obtained from a knowledge of the line length ,the size of

conductor and the specifics resistance of the conductor material ,

while XL is calculated from the conductor spacing and radius using the formula derived in Chapter 3.

Page 31: power sysetm

Referring to the equivalent circuit :

Hence, if the receiving-end conditions are known the necessary sending-end voltage may be calculated .

(6.1 )S RI I a

( ) (6.1 )

S R L R

R R

V V R jX I bV Z I

Page 32: power sysetm

It will be noted that previous are phasor equations , a more approximate method involving scalar quantities is as follows: Referring to the vector diagram,

cos sinSX R R R R L RV V I R I X

cos sinSY R L R R RV I X I R

2

2 1 2

=[ ( cos sin )

+( cos sin ) ] S R R R R L R

R L R R R

V V I R I X

I X I R

Page 33: power sysetm

However (IR XL) and (IR R) are very much less than VR and the small voltage is in quadrate with the much larger VSX ,

The voltage regulation of the line is given by the rise in voltage when full loads is removed , or :

cos sinS SX R R R R L RV V V I R I X

( cos sin )% S R R L R

RR R

V V R Xage voltage regulation I

V V

Page 34: power sysetm

Example A three-phase line delivers 3 MW at 11 KV for a distance of 15 Km . Line loss is 10 % of power delivered , load power factor is 0.8 lagging . frequency is 50 Hz , 1.7 m equilateral spacing of conductors . Calculate the sending-end voltage and regulation .

Solution

11,000Receiving-end phase voltage = 6.3603 RV

3

3

Line current = phase current ( assuming a star connection ) 3,000 10 = 197 A

3 11 10 0.8

Page 35: power sysetm

Assuming that the conductors are manufactured from copper having a resistance of 0.0137 ohms per meter for a cross-sectional area of 1 mm2 , the conductor cross-section is 80 mm2 corresponding to a radius of 5 mm .

2

3

Total line loss =3 (in three conductors)10 = 3,000 10

100

I R

3

2

300 10 3 197

2.58 ohms

R

Page 36: power sysetm

71Inductance = (1 4 log ) 10 /2 c

dL H metre

r

37 3

length

1 1.7 10 = 314 (1 4 log ) 10 15 102 5

=5.75 ohms

L

c

X L

Page 37: power sysetm

cos sin = 6,350 + ( 197 2.58 0.8) + ( 197 5.75 0.6) = 6,350 + 1057 = 7,407 V per phase = 12,780 V line

S R R R R L RV V I R I X

( cos sin )Regulation = =

1,057 = 16.7 %6,350

S RR L RR

R R

V VR XI

V V