Kestrel Aluminium Systems Limited
Product Manual Section 6Low Rise Curtain Walling
Manual Version 23.0.1
© Kestrel Aluminium Systems Low Rise Curtain Walling
Section 6 Contents
Due to our policy of continued improvement Kestrel
Aluminium Systems reserve the right to alter details and
specifications without prior notice.
06.01.00
Sheet 1 01.11.14
Section 6.01 – Product specification 6.01.01 sheet 1 Low Rise Curtain Walling – Product Specification
6.01.02 sheet 1 Low Rise Curtain Walling – Product Specification
6.01.03 sheet 1 Low Rise Curtain Walling – Product Specification (Thermal)
Section 6.02 – Design guidance 6.02.01 sheet 1 Design guidance
6.02.01 sheet 2 Design guidance
6.02.02 sheet 1 Design guidance – Single span mullion application
6.02.03 sheet 1 Design guidance – Multi span mullion application
6.02.04 sheet 1 Design guidance – Deflection and elastic bending stress formulae
6.02.05 sheet 1 Section properties
6.02.05 sheet 2 Section properties
Section 6.03 – Section identification 6.03.01 sheet 1 Section identification – Open boxes and plates
6.03.02 sheet 1 Section identification – Transoms
6.03.03 sheet 1 Section identification – 50mm section and insert
6.03.04 sheet 1 Section identification – Inserts and shear blocks, 75mm, 100mm and 125mm
6.03.05 sheet 1 Section identification – External caps, perimeter infills and SG adapter
6.03.06 sheet 1 Section identification – Glazing accessories and zone seal block
6.03.07 sheet 1 Section identification – Fixing bracket
6.03.08 sheet 1 Section identification – Serrated plates
6.03.08 sheet 1 Section identification – Fixings
Section 6.04 – Glazing options 6.04.01 sheet 1 Glazing options – 6-6.4mm, 8.8mm and 10-10.8mm (Single Glazed)
6.04.02 sheet 1 Glazing options – 24mm and 28mm (Double Glazed)
Section 6.05 – Typical arrangements 6.05.01 sheet 1 Typical arrangements – 6-6.4mm glass SG
6.05.02 sheet 1 Typical arrangements – 8.8mm glass SG
6.05.03 sheet 1 Typical arrangements – 10-10.8mm glass SG
6.05.04 sheet 1 Typical arrangements – 24mm glass DG
6.05.05 sheet 1 Typical arrangements – 28mm glass DG
Section 6.06 – Detail Drawings 6.06.01 sheet 1 Detail drawings – AFT door into curtain wall
6.06.01 sheet 2 Detail drawings – Thermally broken AFT door into curtain wall
6.06.02 sheet 1 Detail drawings – Auto sliding door into curtain wall
6.06.03 sheet 1 Detail drawings – Auto swing door into curtain wall
6.06.04 sheet 1 Detail drawings – 60mm casement window into curtain wall
6.06.05 sheet 1 Detail drawings – Parallel window into curtain wall
6.06.06 sheet 1 Detail drawings – Trickle vent into curtain wall (Glaze in type)
6.06.07 sheet 1 Detail drawings – Head and cill – Direct fix
6.06.07 sheet 2 Detail drawings – Head and cill – Spigot fix
6.06.08 sheet 1 Detail drawings – Typical jamb detail
© Kestrel Aluminium Systems Low Rise Curtain Walling
Section 6 Contents
Due to our policy of continued improvement Kestrel
Aluminium Systems reserve the right to alter details and
specifications without prior notice.
06.01.00
Sheet 2 01.11.14
6.06.08 sheet 2 Detail drawings – Typical jamb detail with fixing bracket shown
6.06.09 sheet 1 Detail drawings – Typical external corner
6.06.09 sheet 2 Detail drawings – Typical external corner with KAS811/805
6.06.10 sheet 1 Detail drawings – Typical internal corner
6.06.11 sheet 1 Detail drawings – Typical intermediate tie back
6.06.12 sheet 1 Detail drawings – Typical intermediate tie back – single span
6.06.12 sheet 2 Detail drawings – Typical intermediate tie back – double span
Section 6.07 – New items 6.07.01 sheet 1 Section properties – KAS825
6.07.02 sheet 1 Section properties – KAS826
6.07.03 sheet 1 Cap sections KAS854 (Bull nose) and KAS855 (Aero) and end plates
6.07.03 sheet 2 Cap sections KAS854and KAS855 isometric details
6.07.04 sheet 1 Thermal performance of KAS825/KAS854
6.07.05 sheet 1 Thermal performance of KAS826/KAS855
Section 6.08 – New items – Mullion drained sections 6.08.01 sheet 1 Section properties – KAS831 and KAS832
6.08.02 sheet 1 Cap sections KAS833 and KAS834
6.08.03 sheet 1 Thermal performance of KAS831/851 and KAS832/834
6.08.04 sheet 1 Thermal performance of KAS832/833
Section 6.09 – New items – Mullion drained sections – Typical details 6.09.01 sheet 1 Typical details - KAS831/851 mullion
6.09.02 sheet 1 Typical details - KAS832/833 transom
6.09.03 sheet 1 Typical details - KAS832/834 transom
6.09.04 sheet 1 Typical details – Eaves detail with mitre mullion joint
6.09.05 sheet 1 Typical details – Eaves detail with separate roof element
6.09.05 sheet 2 Typical details – Eaves detail – Roof only
6.09.06 sheet 1 Typical details – Cill detail – Mullion drained profiles
6.09.06 sheet 2 Typical details – Alternative cill detail – Mullion drained profiles
6.09.07 sheet 1 Typical details – Base fixing onto cill – Mullion drained profiles
6.09.07 sheet 2 Typical details – Base fixing onto cill – Mullion drained profiles
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.01.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Product Specification
Low Rise Curtain Wall
The Kestrel Low Rise Curtain Wall system is an ecomomic and aesthetically pleasing solution to facade cladding. The system is suitable for use on all buildings where good thermal and weather performance is required.
The range of profiles is based around 75mm, 100mm and 125mm mullion and transom designs accompanied by purpose designed ancillary items required of a high performance curtain wall system. Section performance requirements must be calculated from site conditions and all loading requirements. Please contact our technical office for advice and support regarding application.
The system is desgined for pressure equalised zone drainage and this is achieved with drained and ventilated glazing rebates. The glass or panel/window infills are retained with rigid PVC pressure plates which have co-extruded weather seals. Inner seals are available in lineal form and vulcanised pre-formed corner pieces.
Materials:Aluminium profiles are extruded from alloy 6060/6063 T6 complying with the recommendations of BS EN 755:1-9
Finishes:Mill finishEtched and anodised to BS 3987: 1991 (01.06.2007) - Silver AA25 or colours on request.Polyester Powder coat paint to BS EN 12206-1:2004. See separate list for standard colour range available.
Construction:Aluminium profiles are square cut mechanically jointed and secured using stainless steel screws driven into extruded screw splines. All joints should be sealed against water penetration.
Glass, Glazing and Infil Panels:The system can accomodate 24mm and 28mm thick IGU's or composite panels and 6mm, 6.4mm, 8.8mm, 10mm and 10.8mm single glazing variations by using aluminium rebate adapters and alternative internal gasket types.
PVC co-extruded pressure plate and internal EPDM glazing gaskets are extruded to BS 2782 and BS 476 part 7 and BS 4255 part 1 respectively
Installation:Kestrel Aluminium Systems Limited recommends that fabricators and installers are able to demonstrate competence and experience in carrying out such work. Records should be kept regarding training and other relevant experience. Installers should be CWCT trained and certified.
Installation standard = CWCT - Standard and Guide to Good Practice for Curtain Walling.
Please see page 6.01.02 for comprehensive performance data
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.01.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Product Specification
Low Rise Curtain Wall
Performance: Weather
The system has been independantly tested by a UKAS certified body in accordance with the CWCT Test Method for Curtain Walling:
CWCT Section 4 Air Permeability 600paCWCT Section 5 Watertightness, Static 600paCWCT Section 8 Wind Resistance, Servicability 1500paCWCT Section 9 Wind Resistance, Safety 2250pa
Copies of the test reports are available for inspection on request
Performance: Thermal
Profiles have been independantly modelled and assessed in accordance with BS EN ISO 10077-2:
The analyses assume steady state heat flow and therefore any thermal mass effect of any potential adjacent construction or building component has not been considered. The sealed unit edge spacer used in the thermal models was of the type shown in BS prEN13947, with a 0.5 mm wall thickness aluminium hollow profile and 0.5 mm thick seals between the edge profile and the glass panes.
The models are based on the standard Kestrel Aluminium Systems low-rise curtain walldetails (issue 1).
The following values were used in the analyses:
Internal air temperature 20°CExternal air temperature 0°CExternal surface resistance 0.04 m2K/WInternal surface resistances 0.13 & 0.20 m2K/W
Airspace thermal resistances from BS (CEN) EN ISO 10211-1 (automatically generated by LBNL THERM)
U-value of central areas of sealed units (4-16-4) 1.7 W/m2K (Pilkington published value)
Thermal Conductivities (* = manufacturer's value):
Aluminium 160 W/mKGlass 1.00 W/mKEPDM rubber 0.25 W/mKNitrile rubber 0.16 * W/mKPVC 0.16 * W/mKSealed unit edge seal 0.19 W/mKSilica gel desiccant 0.13 W/mK
Continued on page 6.01.03
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.01.0301.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Product Specification
Low Rise Curtain Wall
Performance: Thermal
Model Name (Panel)Utotal1
W/m2K
Qtotal1(Panel)W/mK m
thkPanel U
PanelW/m2K W/mK
infillQ Uf*
W/m2K W/m2K(IGU)
Utotal1
W/mK(IGU)
Qtotal1IGUU
W/m2K W/mKIGUQ g
W/mK
KAS801 75mm
Mullions
1.5351 0.6601 0.024 1.1686 0.4441 4.32 2.3922 1.0286 1.7 0.6460 0.083
KAS804 75mm 1.5349 0.6600 0.024 1.1686 0.4441 4.32 2.3916 1.0284 1.7 0.6460 0.083
KAS811 100mm 1.5405 0.6624 0.024 1.1686 0.4441 4.37 2.4372 1.0480 1.7 0.6460 0.092
KAS814 100mm 1.5403 0.6623 0.024 1.1686 0.4441 4.37 2.4367 1.0478 1.7 0.6460 0.092
KAS821 125mm 1.5517 0.6672 0.024 1.1686 0.4441 4.46 2.4720 1.0630 1.7 0.6460 0.097
KAS824 125mm 1.5514 0.6671 0.024 1.1686 0.4441 4.46 2.4714 1.0627 1.7 0.6460 0.097
Panelthk
0.024
m
0.024
0.024
KAS824 125mm
KAS821 125mm
KAS814 100mm
0.66771.5528
KAS801 75mm
KAS804 75mm
KAS811 100mm
Model Name
1.5264 0.6564
0.6629
-
1.5417
Qtotal1
W/mK(Panel)
W/m2K
Utotal1(Panel)
TransomsQtotal1
0.44411.1686 4.47 2.4713
W/mK
0.4441
0.4441
1.1686
1.1686
U
W/m2KPanel
Qinfill
2.39174.25
4.38 2.4369
W/m2K
Uf*
W/m2K
Utotal1(IGU)
0.64601.0627 1.7 0.097
Q
W/mK
0.6460
0.6460
IGU
1.71.0284
1.0479 1.7
W/m2KW/mK(IGU)
UIGU
0.085
0.092
W/mK
g
NB: * the frame thermal transmittance (U-value) quoted is derived from the BS EN ISO 10077-2 procedure and does not include the effect of the spacer bar in the sealed unit. The spacer bar effect is accounted for by yg (linear thermal transmittance)
- -- -- -----
- - - - - - - - - - -
- - - - - - - -- - -
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.02.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Design guidance
Low Rise Curtain Wall
System Design.
As curtain walling is installed from a set of pre-fabricated components partly in the factory and finally on site, far greater care and use of trained site personnel is required over and above that for installing windows. To this end we have listed the following general guidance notes.
Further reading:
Centre for Window and Cladding Technology;
Standard and Guide to Good Practice for Curtain Walling.
British Standard publications;
BS EN 13830: 2003BS 8200: 1985
BS 8118: Part 1: 1991.BS 8118: Part 2: 1991.BS 6399: Part 2: 1997.
Fabricators and installers MUST maintain accurate records of accredited training, and proof of experience regarding the fabrication and installation of curtain walling.
Basic design considerations.
Building tolerances and movement.
The elevation containing curtain walling must be assessed and discussed at design stage as the structural opening and fixing areas will not always be plum, square and true dimensionally. Thus when designing a curtain walling screen agreement must be reached on tolerances within the building. Either by agreed dimensions or a full survey of the structural opening and fixing grounds prior to manufacture (allow sufficient time for fabrication after a site survey).
The fixing points and openings may be subject to movement (designed in by the structural engineer, or due to general building settlement) these tolerances must also be taken into account during the design of a curtain walling screen. Agreement with the project architect and engineer must take place to ascertain the maximum and minimum dimensions for tolerances and movement at ALL fixing points and curtain wall perimeters during the initial design stage.
All movement MUST be isolated between floors and at no time should a mullion member be fixed rigidly at all fixing points on the primary structure.
Continued on 6.02.01 sheet 2
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.02.0101.10.08Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Design guidance
Low Rise Curtain Wall
Loading.
Curtain wall sections are designed to carry self weight, glass weight, wind pressures and other imposed loads. A curtain wall mullion must NEVER be used as a primary structural member within the building, or have loads designed for the primary structure transferred to the curtain wall grid.
Hung Condition.
A hung curtain walling is based upon the top section of the lower mullion being fixed via fixing brackets back to a suitable structural fixing point. This fixing carries all dead loads, wind loads and all other associated loading back to the structure. The bottom of the hung mullion is located in position by either a sleeve welded to a base plate or in multi-storey situations by a sleeve within the top of the hung mullion. This detail allows for vertical movement and in no circumstances should the mullion section be fixed to the sleeve.
Prop Condition.
A propped curtain walling is based upon the bottom of the mullion carrying all the loads either direct to structure at cill or in multi-storey situations by a bracket back to suitable fixing points. The top of the bottom mullion is located in position by a sleeve. The head of the lower mullion has no mechanical fixings to mullion or sleeve. The head of the mullion carries no dead loads it only transfers wind/imposed loads to fixing detail. This detail allows for vertical movement and in no circumstances should the mullion section be fixed to the sleeve.
Section performance requirements must be calculated from site conditions and all loading requirements. Please contact our technical office for advice and support regarding application.
Fixing points.
Fixing points for curtain walling must be sufficient to carry the weight of the screen plus and other imposed loads. Do not fix to cold rolled sections i.e. sheeting rails / purlins etc. fixing to concrete floor slabs and hot rolled sections are recommended. Agree with the project architect and engineer the method of fixing (hung or propped) and cost effective fixing options at head, cill and intermediate levels as necessary at design stage. These faces should be a set close to the rear of the curtain wall main box sections. It is advised that a nominal distance of 25-30mm is allowed between structural fixing and the back of the mullion to minimise the cantilever effect thus saving on the size of bracket required.Important note: If at any time you have any queries regarding the Kestrel Low Rise Curtain Wall system please contact the Technical Department.
Prior to any installation on site it is advised that the structural fixing points and all fixing details have been issued to and approved by either the contract Architect or contract structural engineer.It is also advised that full working drawings are prepared and approved by the contract Architect prior to commencement of the installation on site.Prior to the installation of the curtain wall grid it is advised that a check of the structural opening is carried out.
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.02.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Design guidance
Mul
lion
Leng
th .
Com
bine
d M
ullio
n Le
ngthMul
lion
Sing
le S
pan
Mul
lion
Leng
th
Mul
lion
Sing
le S
pan
LL-WL
DL & WL
Mov
emen
t Joi
nt4m
m
.
Spandrel
GlazedPart ElevationPart Elevation
Unglazed
Spandrel Spandrel
Spandrel
.Tr
anso
m C
entr
es
Vision Vision Vision
Spandrel
Vision Vision
Spandrel
Vision
Can be used for multi storey applications of upto 20 Metres
Consult a structural engineer if there is any doubt regardingDesigns must accomodate thermal and structural movement .
Keep Any Cantilever to a Minimum
Single Span Mullion Applications
Customers Detail
WL-DL
Do not exceed the capabilities of the system.
Recommendations
Coping Design to
the application.
The span capabilities of the mullion profiles .Transportation to site and ease of handling.Site access.
Restrictions
Advantages
Positive and Negative Wind Load Imposed
Spandrel
to the Curtain Wall and Structural Fixings
Loading and/or Thermal Movement
upon the Glazed Curtain Wall and Transfered
LL - Live LoadVariable Movement of the Structure through
.
.
MullionCentres
Spandrel Spandrel
Structure, Curtain Wall and Structural Fixings
DL - Dead Load
WL - Wind Load
Abbreviations
Weight of the Curtain wall imposed upon the
Vertical Section Thro.
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.02.0301.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Design guidance
.
Mul
lion
Leng
thSpan
Inbe
twee
n Fi
Poi
nts
Span
Inbe
twee
n Fi
Poi
nts
Vertical Section Thro.DL-WL
WL-LL
.
Spandrel
GlazedPart ElevationPart Elevation
Unglazed
Spandrel Spandrel
Spandrel
.Tr
anso
m C
entr
es
Vision Vision Vision
Spandrel
Vision Vision
Spandrel
Vision
capability with the same mullion would be exceeded.the span capability of mullions where a single spanIn some instances can be used to slightly increase
Consult a structural engineer if thier is any doubt regardingDesigns must accomodate thermal and structural movement .
Keep Cantilever to a minimum
Multi Span Mullion Applications
Customers Detail
WL-LL
Do not exceed the capabilities of the system.
The span capabilities of the mullion profiles .
Recommendations
Transportation to site and ease of handling
Coping Design to
the application.
Site access.
The available length of the mullion profiles.Restrictions
Advantages
Positive and Negative Wind Load Imposed
Spandrel
to the Curtain Wall and Structural Fixings
Loading and/or Thermal Movement
upon the Glazed Curtain Wall and Transfered
LL - Live LoadVariable Movement of the Structure through
.
.
.MullionCentres
Spandrel Spandrel
Structure, Curtain Wall and Structural Fixings
DL - Dead Load
WL - Wind Load
Abbreviations
Weight of the Curtain wall imposed upon the
Spans between fixings must be of equal length
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.02.0401.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
Design guidance
Equation [8] ST = (0.15 x Q1) / Z
Q1 x ((3 x L2^) - 0.090)
Simply supported by 2 point loads each at 150mm from ends (transom dead load)
{Equation [7] F =
Q1 = each separate point load
Equation [4] ST = (Q x L) / (8 x Z)
) / (185 x E x I)
Continuous (double span of 2 equal spans) beam (mullion wind load)
x (3 - N
Q = load on 1 span
Equation [3] F = (Q x L3
L = mullion span (1 span only)
Equation [6] ST = Q x L{ 2
160 x E x I){ / }
24 x (L - (B/2)) x Z / 2 }) { }
) x (1 - (N
N = B/L (if B > L then N = 1 & L = B)
Simply supported trapezoidal load (transom wind load)
Equation [2] ST = (Q x L) / (8 x Z)
3
Simply supported rectangular load (mullion wind load)
= I/y where y is the largest distance from neutral axis to edge of section
I = second moment of area sectionE = Youngs modulus of material
Deflection & elastic bending stress formulae
Equation [5]
B = load area heightL = transom span
(5 x Q x L{ 4
Equation [1] F = (5 x Q x L
L = mullion span
ST = elastic bending stress
Z = elastic modulus of section
Wp = wind pressureF = deflection
Q = load
generally:
} 384 x E x I x (L - (B/2)) /5))2 / } 2 {
) / (384 x E x I)
Low Rise Curtain Walling
Section Properties
KESTRELALUMINIUM SYSTEMS
6.02.0501.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
x
KAS824y
x
x
y
KAS823y
KAS822y
x
x
y
x
x
y
KAS814
KAS821y
y
KAS813y
x
x
y
y
x
x
x
y
306.07125mm 37.35 44.85
31.33260.55125mm
137.26
39.48
125mm
125mm
22.77
6.84
71.84
188.17100mm
100mm
26.71
15.15
21.08
5.15
0.13
37.80
5.14
KAS812y
KAS811y
x
x
x
y
x
x
y
KAS804y
KAS803y
y
x
x
y
x
x
y
y
Profile
KAS801
KAS802
y
x
x
y
x
165.57
19.69100mm
100mm
4.35
24.15
29.53
103.67
7.83
75mm
75mm
75mm
8.56
17.51
2.39
0.12
18.46
5.13
30.74
0.12
94.39
Ixx(cm4)
75mm
Type
16.96
Zxx(cm3)
16.77
Zyy(cm3)
Iyy(cm4)
5.44
0.13
3.04
12.30
5.74
0.13
3.05
15.12
6.33
0.13
3.06
17.94
Low Rise Curtain Walling
Section Properties
KESTRELALUMINIUM SYSTEMS
6.02.0501.10.08Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale n/a
KAS857
KAS858
KAS853
KAS852
Profile
KAS805
KAS851
y
x
y
x
48.6850mm 10.16 21.32
Type Ixx(cm4)
Zxx(cm3)
Iyy(cm4)
Zyy(cm3)
KAS806
x
y
x
y
8.53
50mm 12.09 4.94 5.78 2.63
KAS859
KAS856
KAS866 BLACKPVC
EXTRUSION
BLACKCo-Extruded
PVC EXTRUSION
KAS861 (M)
KAS862 (T)
KAS861 use on mullions - fixing holes pre-punched
KAS862 use on transoms - fixing/drain holes pre-punched
Low Rise Curtain Walling
Section identification - Open boxes and plates
KESTRELALUMINIUM SYSTEMS
6.03.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
50
125
50
No10
125mm PlateKAS822
KAS811100mm Mullion
100mm Plate
No10
KAS812
34.25
125mm MullionKAS821
No12
100
7550
No10
No10
No12
34.25
No10
KAS802
KAS80175mm Mullion
75mm Plate
No12
34.25
No10
Low Rise Curtain Walling
Section identification - Transoms
KESTRELALUMINIUM SYSTEMS
6.03.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
7550
No10
No12
75mm TransomKAS804
34.25
No10
125
No10
50
No10
KAS824125mm Transom
No12
34.25
100mm TransomKAS814
34.25100
50
No10 No10
No12
Low Rise Curtain Walling
Section identification - 50mm section and insert
KESTRELALUMINIUM SYSTEMS
6.03.0301.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
50
50
No10
34.25
50mm TransomKAS805
KAS80650mm insert
43.9
44
Low Rise Curtain Walling
Section identification - inserts and shear blocks 75mm, 100mm, 125mm
KESTRELALUMINIUM SYSTEMS
6.03.0401.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
2033.7
125mm Mullion/Transom Insert
100mm Mullion/Transom Insert
118.5
33.7
KAS823
KAS813
Cut and Drilled
KAS872D125mm Shear Block
Ø 6
20∅3.5
20KAS871D100mm Shear BlockCut and Drilled
75mm Mullion/Transom Insert
93.5
68.5
33.7
KAS803
Ø 6 20
Ø 6
∅3.5
20
Cut and Drilled
KAS870D75mm Shear Block
∅3.5
20
Low Rise Curtain Walling
Section identification - External caps, perimeter infills, SG adapter
KESTRELALUMINIUM SYSTEMS
6.03.0501.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
37.5
20
Aluminium Perimeter InfilKAS856
21
20
Single Glaze AdaptorKAS859
17.550
Cover PlateMullion Clip On KAS851
1414.5
50Transom Clip OnCover Plate
KAS852
50.7
Sloped TransomClip OnCover Plate
KAS853
KAS866Black PVC Perimeter Infil
19.5
33.25
19.9
(Use where VISIBLE)
Low Rise Curtain Walling
Section identification - Glazing accessories and zone seal block
KESTRELALUMINIUM SYSTEMS
6.03.0601.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
16.25
KAS862Co- Extruded Pressure PlatePre Punched Fixing Holes and Drainage Slots
49.5
Pre Punched Fixing HolesCo- Extruded Pressure Plate
49.5
KAS861
16.2
5
5
and 28mm Units
and 24mm Units
KAS869for Double GlassSetting Block
10.75
KAS864
10 Suits 8.8mm Glass
12.75
suits 6/6.4mm GlassEPDM Inner GasketKAS863
10
8.75
KAS865suits 10/10.8mm GlassEPDM Inner Gasket
10
12
5
30
Setting Blockfor Single Glass
KAS868
KAS867Black PolyetyleneZone Sealing Blocks
KAS863C
KAS865C
Vulcanised gasket corners are 300mm x 300mm
(Use on mullions)
(Use on transoms)
Low Rise Curtain Walling
Section identification - Fixing bracket
KESTRELALUMINIUM SYSTEMS
6.03.0701.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1 & 1.4
8
30 40
100
Also Available in Bar Length Ref. KAS858 - 5.0M Long
1012
100
100
30
30
Use with KAS875C and12
40
KAS 876C Serrated Plates
Slots to suit M12 Bolts
Slots to suit M10 Bolts
KAS 876B Serrated PlatesUse with KAS875B and
Use with KAS875A andKAS 876A Serrated Plates
10
40
KAS877C
8
KAS877B
122 Slot Ctrs.
52
175
11.5 3034
to
Slot
Ctr
.
82
Slots to suit M8 Bolts40
14KAS877A
Low Rise Curtain Walling
Section identification - Serrated plates
KESTRELALUMINIUM SYSTEMS
6.03.0801.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
∅6
80
∅6
80
∅6
80
Also Available in Bar Length Ref. KAS857 - 5.0M Long
Tie Back Bracket
∅816
Use with KAS877A
Hole to suit M8 BoltKAS876A
Tie Back BracketTie Back Bracket
∅1016
Use with KAS877B
Hole to suit M10 BoltKAS876B
∅1216
Use with KAS877C
Hole to suit M12 BoltKAS876C
∅8
32
Tie Back BracketUse with KAS877A
16
Hole to suit M8 BoltKAS875A
32
3232
∅12∅10
Tie Back BracketUse with KAS877B
16
Hole to suit M10 BoltKAS875B
Tie Back BracketUse with KAS877C
16
KAS875CHole to suit M12 Bolt
32 32
Low Rise Curtain Walling
Section identification - Fixings
KESTRELALUMINIUM SYSTEMS
6.03.0901.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
KAS889.M12
KAS889.M10
KAS889.M08Cat. 1 Mullion Bracket FixingM8 x 100 Hexagon Bolt, Nut and Washers
M10 x 100 Hexagon Bolt, Nut and WashersCat 2. Mulliion Bracket Fixing
Cat 3. Mullion Bracket FixingM12 x 100 Hexagon Bolt, Nut and Washers
M12
M10
M12
M10
KAS889.M06
KAS885Magnetic Hexagon Socket Driverto suit KAS883 Fixing Screws
KAS882Pozi Pan Head Fixing Screwfor Mullion to Transom Fixing
M6 x 100 Hexagon Bolt, Nut and Washers Straight thro.Shear Block Fixing
M6
M8
Hexagon Head Fixing Screwfor 80mm Serrated Plates
KAS884
Transom to Shear BlockCsk Head Fixing ScrewKAS881
M6
M8
bypass transom positionswhere KAS803, 813 and 823
Pozi Csk. Head Fixing Screwfor Mullion to Transom Fixing
KAS886
Screw for Pressure CapsHexagon Washered FixingKAS883
Low Rise Curtain Walling
Glazing options - Single glazed variations
KESTRELALUMINIUM SYSTEMS
6.04.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
Vertical Pressure Plate
Clip Fit Adaptor Profile
KAS865 EPDM Gasket
Vertical Pressure Plate
KAS851KAS861
10/10.8mm Single Glass
KA
S859
KAS861KAS851
Clip Fit Adaptor Profile
KAS864 EPDM Gasket
Vertical Pressure Plate
Clip Fit Adaptor Profile
KAS863 EPDM Gasket
8.8mm Single Glass
6/6.4mm Single Glass
KA
S859
KAS851KAS861
KA
S859
Low Rise Curtain Walling
Glazing options - Double glazed variations
KESTRELALUMINIUM SYSTEMS
6.04.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
Vertical Clip on Cap
Vertical Pressure Plate
KAS865 EPDM Gasket
28mm Double Glass
KAS861KAS851
Vertical Clip on Cap
KAS863 EPDM Gasket
Vertical Pressure Plate
24mm Double Glass
KAS861KAS851
Low Rise Curtain Walling
Typical arrangements - 6/6.4mm glass
KESTRELALUMINIUM SYSTEMS
6.05.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
75
KAS883 Hexagon Head Screw
Vertical Clip on Cap
Vertical Pressure Plate
Clip Fit Adaptor Profile
KAS863 EPDM Gasket
KAS851KAS861
KA
S859
52
KA
S802
KA
S801
KA
S822
KA
S812
50
KAS824125 100
KAS814
KA
S821
KA
S811
100
125
50
KAS859
75KAS804
52KAS853
Low Rise Curtain Walling
Typical arrangements - 8.8mm glass
KESTRELALUMINIUM SYSTEMS
6.05.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
75
KAS883 Hexagon Head Screw
Vertical Pressure Plate
Vertical Clip on Cap
KAS864 EPDM Gasket
Clip Fit Adaptor Profile
KAS851KAS861
KA
S859
52
KA
S802
KA
S801
KA
S812
KA
S822
50
KAS824125
KAS814100
KA
S821
KA
S811
100
125
50
KAS859
75KAS804
52KAS853
Low Rise Curtain Walling
Typical arrangements - 10/10.8mm glass
KESTRELALUMINIUM SYSTEMS
6.05.0301.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
75
KAS883 Hexagon Head Screw
Vertical Pressure Plate
Vertical Clip on Cap
Clip Fit Adaptor Profile
KAS865 EPDM Gasket
52
KAS851KAS861
KA
S859
KA
S802
KA
S801
KAS804
KA
S822
KA
S812
75
50
KAS824125
KAS814100
KA
S821
KA
S811
100
125
50
KAS859
52KAS853
Low Rise Curtain Walling
Typical arrangements - 24mm IGU's
KESTRELALUMINIUM SYSTEMS
6.05.0401.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
KAS851KAS861
Vertical Pressure Plate
KAS883 Hexagon Head Screw
Vertical Clip on Cap
KAS863 EPDM Gasket
5275
KA
S802
KA
S812
KA
S801
100
KA
S811
50
75
50
KA
S822
KAS814KAS824125 100
KAS80452
KA
S821
125
KAS853
Low Rise Curtain Walling
Typical arrangements - 28mm IGU's
KESTRELALUMINIUM SYSTEMS
6.05.0501.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
75
Vertical Pressure Plate
Vertical Clip on Cap
KAS865 EPDM Gasket
KAS883 Hexagon Head Screw
KAS851KAS861
52
KA
S802
KA
S801
KAS80475
50
KAS824125 100
KAS814
125
100
KA
S821
KA
S822
KA
S812
KA
S811
50
52KAS853
Low Rise Curtain Walling
Detail Drawings - AFT door into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
Doo
r Stil
e H
eigh
t100
52
KAS861KAS851
100
KA
S26
KA
S811
KA
S856
KA
S27
KA
S812
Outside
M10
22 Out
side
Typical Elevation - Scale 1:50
50
Transom Closer Bracket
100
No10
KAS814
52
No10
KAS856
50
A6.06.01
6.06.01A
6.06.01B
6.06.01B
6.06.01C
6.06.01C
KAS13
KAS12
KAS853
KAS25
KAS24
50
Low Rise Curtain Walling
Detail Drawings - Thermally broken AFT door into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0101.11.14Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
52
KAS861
KAS851
100
KA
S81
1K
AS
856
KA
S8
12
Outside
Typical Elevation - Scale 1:50
100
No10
KAS814
52
No10
KAS856
50
A6.06.01
6.06.01A
6.06.01B
6.06.01B
6.06.01C
KAS853
50
KAS722
KAS480A
KAS753
KAS752
KAS480A
KAS751
KAS631
Anti-finger trapprofile.
Anti-finger trap single action, open out,stile shown (KAS753) with double actionstile (KAS752) shown dashed.
KAS282
KAS467
KAS768
109
70
KAS756
KAS757
KAS762
KAS631
KAS219
100
57
28
4
85
Low Rise Curtain Walling
Detail Drawings - Auto sliding door into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0201.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
KAS85
KAS13
52
KA
S856
KAS851KAS861
100
KA
S812
KA
S811
KA
S22
KAS84
Typical Elevation - Scale 1:50
KAS87
Meeting Stile in
KAS28 KAS2910
0
130m
m P
anel
Hei
ght
KAS80
200
KAS811
KAS812
50
KA
S852
KAS856
Insu
late
d In
fil P
anel
50
6.06.02A
6.06.02A
6.06.02B
6.06.02B
6.06.02C
6.06.02D
6.06.02C
6.06.02D
Low Rise Curtain Walling
Detail Drawings - Auto swing door into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0301.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
100
200
KAS24
KAS77
KAS93
50
KAS814
KAS80
No10
50
KAS856
No10
Typical Auto Unit
KAS 77 used to allow easier fitting of operating arm
Door opens IN
6.06.03A
A6.06.03
152
100 24
116
Low Rise Curtain Walling
Detail Drawings - 60mm casement window into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0401.11.14Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
KA
S81
1
KA
S81
2
KAS814
Outside
KAS851
KAS861
Ou
tsid
e
KAS805
Typical Elevation - Scale 1:50
KAS853
KAS853
50 98
152
28100
5050
6.06.04A
6.06.04B
C6.06.04
6.06.04A
6.06.04B
6.06.04C
NB: Window profile KAS628 has a 28mm glaze in edge
50
98
KAS635
2050
27
KAS668
KAS662
KAS628
KAS635
KAS668
KAS662
KAS628
KAS635
2050 27
KAS668
KAS662
KAS628
Low Rise Curtain Walling
Detail Drawings - Parallel window into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0501.11.14Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
KA
S81
1
KA
S81
2
KAS814
Outside
KAS851
KAS861
Ou
tsid
e
KAS805
Typical Elevation - Scale 1:50
KAS853
KAS853
50 97
152
28100
5050
6.06.05A
6.06.05B
C6.06.05
6.06.05A
6.06.05B
6.06.05C
NB: Window profile KAS628 has a 28mm glaze in edge
50
97KAS628
KAS628
KAS628
KAS691
KAS693
KAS694
KAS691
KAS693
KAS694
5125
20
KAS693
KAS691
KAS694
Low Rise Curtain Walling
Detail Drawings - Trickle vent into curtain wall
KESTRELALUMINIUM SYSTEMS
6.06.0601.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
50
KAS805 KAS853
2450
10250 24
Glaze-in Trickle Vent
Typical arrangement shown.
Glass height deductions will vary by manufacturer - always check!
* 24mm glaze-in edge shown
28mm may also be available, check with manufacturer.
Fixed light
KAS806
Gla
ss d
educ
tion
will
var
y!
*
Low Rise Curtain Walling
Detail Drawings - Head and cill - Direct fix
KESTRELALUMINIUM SYSTEMS
6.06.0701.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
Vertical Sections
KAS853
M8
Plan Sections
M8
M8
KA
S801
Out
side
KAS802
KAS852
KAS866
50
127
5010
10
127
50
KAS802
KAS851
Anchor bolt fixing intosuitable structural grounds
KAS866
KAS801
24
Low Rise Curtain Walling
Detail Drawings - Head and cill - Spigot fix
KESTRELALUMINIUM SYSTEMS
6.06.0701.10.08Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
Plan Sections
M8
Purpose Made Base Plate with Shear Block Insert
M6 M6
M8
Vertical Sections
Isolator
Purpose Made Cill Member
Vapour Barrier
Insulate this AreaM8
KA
S801
KAS804
Out
side
KAS804
KAS852
KAS853The nose of the mullion to be cut back at the bottom 20mm to allow the cill to run through.
5050
Anchor bolt fixing intosuitable structural grounds
All internal finishes by others
10
127
Low Rise Curtain Walling
Detail Drawings - Typical jamb detail
KESTRELALUMINIUM SYSTEMS
6.06.0801.11.14Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1 & 1.2
10/1
0.8
35
28
KAS861
KA
S8
51
KA
S8
66
KAS861
KA
S85
1
KA
S8
66
KAS861
24K
AS
85
1
into a Revealed Structural Opening it is Advised toAllow a Minimum Overall Width Tolerance of 20mm
Polyethylene Backer Rod (Sealant Saver)
When Stacking Curtain Wall Modules Horizontally
10
Architectural Grade Silicone SealantTremco FA600 Low Modulas
KAS861
KAS851
KA
S86
6
52
Vertical Pressure Plate
Vertical Clip on Cap
KAS883 Hexagon Head Screw
KA
S80
2
6/6.
48.
8
KA
S8
66
KAS861
KA
S8
59
KA
S8
51
KA
S86
6
KAS861
KA
S8
59
KA
S8
51
KA
S86
6 KA
S8
59
75K
AS
801
KAS863 EPDM Gasket
50
Low Rise Curtain Walling
Detail Drawings - Typical jamb detail with fixing bracket shown
KESTRELALUMINIUM SYSTEMS
6.06.0801.10.08Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
Fixing to Structure
Jamb
M10 x 40 Hexagon Head Bolt Modified with a Slot
Modified Serrated Fixing Bracket Factory Fixed to theMullion (use the offcut for the opposite hand bracket)
for Tightening Purposes, Including Nut and Washers
24mm thick Double Glass Sealed Units
Mullion
The Structure Should be Checked for Verticality and10mm Minimum
Width Variations Before Tolerances are Finalised
Outside
30
KAS861
KAS866
KA
S851
KAS861
Intermediate
Once the Mullions are Aligned and Levelled the
the Vertical Movement of the Mullion.
Fixing Bolt Should be Tightened to Ensure that
are not De-formed to the Extent that they Restrictthe Serrations are Engaged but the Bracket Legs
Mullion
and Accomodate Vertical Live Load and ThermalThis Tie Back is Intended to Resist Wind Load
Movements.
KA
S851
Outside50
50
175
82
KAS858 (bracket)
KAS857 (serrated plate)
Nom
inal
20m
m
Low Rise Curtain Walling
Detail Drawings - Typical external corner
KESTRELALUMINIUM SYSTEMS
6.06.0901.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
76 x 76 x 6.4 Angle Brackets with
Nuts and Bolts to Secure the Spreader Plates and Hexagon
Secure Corner Mullions Together
External Corner
Insulated Corner Cladding Panel
the Mullion Profilesor Plate Together before Fixing toMitre the Corner Transom and Weld
Purpose Made Pressed Aluminium
KA
S851
KAS851
KAS861
KA
S812
KAS811
KA
S811
KA
S861
KAS812
156
28
152
50
100
177
Low Rise Curtain Walling
KESTRELALUMINIUM SYSTEMS
6.06.0901.06.09Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
KAS851KAS861
KA
S812
KA
S811
No10
KAS805 KA
S851
KA
S861
Purpose Made Pressed AluminiumInsulated Corner Cladding Panel
External Corner
Scale 1.2
127
106
96
100
KAS812
KA
S861
KAS811
28
KA
S851
152
This Frame is separatewith the KAS 812 Plateto the interfacing jamb
This
fram
e to
be
cons
truc
ted
to in
clud
eth
e K
AS8
11 a
nd K
AS8
05 m
ullio
n pr
ofile
co
mbi
natio
n at
the
corn
er ju
nctio
n
15
12mm Ø clear hole to allow head of 4.8 x 50 self
tapping screw to pass
19
25
19
Backmarks required for 5mm Ø clear holes to
allow 4.8 (No.10) pan headself tapping screw to pass
4.0mm Ø pilot hole into KAS805
for height stacked frames andThis construction is not suitable
other application should beKestrel recommend that any
checked by a structural engineer
Detail Drawings - Typical external corner KAS811 & KAS805
Low Rise Curtain Walling
Detail Drawings - Typical internal corner
KESTRELALUMINIUM SYSTEMS
6.06.1001.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
87
175
Purpose Made Pressed AluminiumInsulated Corner Cladding Panel
200
59KAS851
KAS861
100
KA
S851
KA
S861
KAS811
KAS812
Internal Corner
KA
S812
KA
S811
50
28
Low Rise Curtain Walling
Detail Drawings - Typical intermediate tie back
KESTRELALUMINIUM SYSTEMS
6.06.1101.10.08Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2Outside
KAS861KAS851
KAS876
KAS875
M12
KAS877
increasing when used with Cast inLateral +/-8mm with Anchor Bolts
Insert Channels+/- 8mm
M12O
utsi
de
HALFEN 28/15
Adjustment Possibilities with this
Hexagon Head Fixing ScrewsApplied to Dead Fix Aligned and Levelled Framework
Hexagon Bolts and Nuts with WashersBolt Diameter to Suit Application Requirements
+/- 12mm
KAS889
KAS884
Bracket Arrangement are:-
+/- 12mm
min 8mm max 34mm
KAS876
KAS875
M12
28
M12
M6
Mullion/Transom Nom. 52mm
24
24
Low Rise Curtain Walling
Detail Drawings - Typical intermediate tie back - Single span
KESTRELALUMINIUM SYSTEMS
6.06.1201.11.14Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
Ou
tsid
e
Outside
KAS861
KAS851
to Avoid Water Penetration (Hatched Area Also)
(Length to Suit Structural Requirements)
Cap Must Be Sealed with Tremco SB660 butyl in order
At the Joint Positions the Rebate Face of the Mullion
the Mullion Nose, and the Face Width of the Pressure
The Designed Joint Size between Mullions Should
also be used for the Pressure Cap and Cover Cap
Outer Cover Cap should be Offset as Illustrated
The Jointing Position of the Pressure Cap and the
The Joint Sleeve is Illustrated by the Broken Lines
or Structural Movement the Edge Cover to the Underside
To Increase the Joint Size Allowing for Greater Thermal
of the Transom Above a Joint Can be Reduced by 5mm
Using the Standard Deductions to Calculate Glass or
Panel Sizes, a 15mm All-round Edge Cover is Achieved
Using this Criteria the Maximum Permissible Joint Size
KAS875
KAS876
M12
KAS877
to give 9mm Joint Size
between two mullions is 4mm.
100
KAS876
KAS813
M12
KAS875
M12
M12
4
100
4
KAS877
min 8mm max 34mm
4
M6
24
24
Low Rise Curtain Walling
Detail Drawings - Typical intermediate tie back - Double span
KESTRELALUMINIUM SYSTEMS
6.06.1201.10.08Sheet 2
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.2
min 8mm max 34mm O
utsi
de
KAS851
OutsideKAS861
KAS875
KAS877
increasing when used with Cast in
+/- 8mmInsert Channels
Once the Mullions are Aligned and Levelled the
the Vertical Movement of the Mullion.
the Serrations are Engaged but the Bracket Legsare not De-formed to the Extent that they Restrict
Fixing Bolt Should be Tightened to Ensure that
This Tie Back is Intended to Resist Wind Loadand Accomodate Vertical Live Load and Thermal
Lateral +/-8mm with Anchor Bolts
Movements.
Hexagon Bolts and Nuts with WashersBolt Diameter to Suit Application Requirements
Structural/Thermal Movement Possibilitieswith this Bracket Arrangement are:-
Adjustment Possibilities with this
HALFEN 28/15
KAS889
+/- 12mm
Bracket Arrangement are:-
+/- 12mm
KAS875
25
28
KAS875KAS877
Mullion/Transom Nom. 52mm
24
24
Section Properties KAS825
KESTRELALUMINIUM SYSTEMS
6.07.0101.01.10Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
Low Rise Curtain Walling
50
150
Section Properties: KAS825
Ixx = 606.9242 cm4Iyy = 62.5899 cm4
Zxx = 58.9261 cm3Zyy = 25.0360 cm3
KAS823 (Sleeve profile)
Ixx = 137.26 cm4Iyy = 22.77 cm4
34.2
5
175
34.2
5
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.07.02Scale 1.1
Sheet 1 01.01.10
50
© Kestrel Aluminium Systems
Section Properties KAS826Low Rise Curtain Walling
Section Properties: KAS826
Ixx = 836.9752 cm4Iyy = 70.8850 cm4
Zxx = 73.2958 cm3Zyy = 28.3540 cm3
KAS823 (Sleeve profile)
Ixx = 137.26 cm4Iyy = 22.77 cm4
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.07.03Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Cap sections KAS854 & KAS855Low Rise Curtain Walling
KAS861
KAS852 transom cap
50
2814
.542
.5
KAS883
KAS854
KAS854 Bull nose cap
8528
KAS852 transom cap
14.5
KAS855 Aero cap
KAS883
KAS855
KAS861
50
Typical mullion
Typical mullion
KAS890.854 end plate
KAS890.855 end plate
Use No.8 fixings in cap screw ports
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.07.03Sheet 2 01.01.10
© Kestrel Aluminium Systems
Cap sections KAS854 & KAS855Low Rise Curtain Walling
KAS854 Bull nose cap
KAS855 Aero cap
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.07.04Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Thermal performance - KAS825/854Low Rise Curtain Walling
Section Properties (Thermal) : KAS825/KAS854
Uf = 3.61 W/m2KΨg = 0.0570 W/m @ 1.1 IGU centre pane U value
28mm glazing thickness (panel = 1.0309 W/m2K)
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.07.05Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Thermal performance - KAS826/855Low Rise Curtain Walling
Section Properties (Thermal) : KAS826/KAS855
Uf = 3.68 W/m2KΨg = 0.0583 W/m @ 1.1 IGU centre pane U value
28mm glazing thickness (panel = 1.0309 W/m2K)
KAS826 part omitted for clarity
Section Properties KAS831 & KAS832
KESTRELALUMINIUM SYSTEMS
6.08.0101.01.10Sheet 1
Kestrel Aluminium Systems©
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.
Scale 1.1
Low Rise Curtain Walling
50
100
34.2
5
Section Properties: KAS831
Ixx = 190.9430 cm4Iyy = 39.0283 cm4
Zxx = 27.3027 cm3Zyy = 15.6113 cm3
KAS803 (Sleeve profile)
Ixx = 29.5274 cm4Zxx = 8.5636 cm3
Section Properties: KAS832
Ixx = 10.9382 cm4Iyy = 7.4502 cm4
Zxx = 3.4362 cm3Zyy = 2.9801 cm3
50
34.2
516
16
2.5mm corner radii
Section KAS831 is a mullion drained profile - KAS832 purlin to be used horizontally on sloped applications
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.08.02Scale 1.1
Sheet 1 01.02.10
© Kestrel Aluminium Systems
Cap sections KAS833 & KAS834Low Rise Curtain Walling
KAS834 Roof cap >45°
45°30°
KAS833 Roof cap <45°
No12 x 22mm philips csk
Silicone sealhere if required
here if requiredSilicone seal
KAS862
KAS883
KAS832 Purlin
KAS832 Purlin
28
28
57
61
10.5
17
KAS192
KAS860
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.08.03Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Thermal performance - KAS831/851, KAS832/834Low Rise Curtain Walling
Section Properties (Thermal) : KAS831/KAS851
Uf = 3.99 W/m2KΨg = 0.0540 W/m @ 1.1 IGU centre pane U value
28mm glazing thickness (panel = 1.0309 W/m2K)
Section Properties (Thermal) : KAS832/KAS834
Uf = 3.34 W/m2KΨg = 0.0377 W/m @ 1.1 IGU centre pane U value
28mm glazing thickness (panel = 1.0309 W/m2K)
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.08.04Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Thermal performance - KAS832/833Low Rise Curtain Walling
Section Properties (Thermal) : KAS832/KAS833
Uf = 6.14 W/m2KΨg = 0.0329 W/m @ 1.1 IGU centre pane U value
28mm glazing thickness (panel = 1.0309 W/m2K)
Application of U-values for sloped glazing situations;
AD L1A, L1B, L2A, L2B
Tables indicating limiting U-values
Note 2:
The U-values for roof windows and rooflights in this table are based on the U-value having been assessed with the roof window or rooflight in the vertical position. If a particular unit has been assessed in a plane other than the vertical, the standards given in this Approved Document should be modified by making an adjustment that is dependant on the slope of the unit following the guidance given in BR 443.
Inclination of roof U-value adjustment (W/m2K) Twin skin or double glazed Triple skin or triple glazed
70° or more (vertical) <70° and >60° <60° and >40° <40° and >20° <20° (horizontal)
0.00+ 0.20+ 0.30+ 0.40+ 0.50 + 0.30
+ 0.20+ 0.20+ 0.10 0.00
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.01Scale 1.1
Sheet 1 01.11.14
© Kestrel Aluminium Systems
Typical details - KAS831/851 mullionLow Rise Curtain Walling
Typical Mullion Section15
10
1628
100
50
KAS803
KAS861
KAS883
KAS851
No. 8 x 9.5mm pan hd S/S screw
KAS832
KAS852'W
et Z
on
e'
Important notes - sealing the mullion and transom 'wet zone'
50mm wide x 1.2mm PB Ali tape bonded to u/side of mullion drainage zone and eaves type mitre jointsonto water channels
Bed mullions ends on SB660 butyl seal - and ensure fully watertight (See 6.09.06 sheet 1 and 2 and 6.09.07 sheet 1)
Use FA600 to fully seal underside of transom KAS832 into KAS831 mullion side cut out
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.02Scale 1.1
Sheet 1 01.02.10
© Kestrel Aluminium Systems
Typical details - KAS832/833 transomLow Rise Curtain Walling
here if requiredSilicone seal
KAS192
KAS832 Purlin
KAS831 mullion
KAS851 cap
50
100
30°
KAS860
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.03Scale 1.1
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Typical details - KAS832/834 transomLow Rise Curtain Walling
100
50
Silicone sealhere if required
KAS862
KAS883
KAS851 cap
KAS831 mullion
45°
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.04Scale 1.2
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Typical eaves details - mitre mullion jointLow Rise Curtain Walling
46
M10
bracket (3mm)Pressed up cap Panel
KAS803 corner joint insert
Weld and use bespoke angle plates to reinforce
68.5
6
100
Suitable structural support required at eaves level with correctly detailed fixing brackets and fixings.
KAS832 Purlin
KAS851 cap
KAS831 mullion
52
30°
20
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.05Scale 1.2
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Typical eaves details - separate roof elementLow Rise Curtain Walling
KAS832 Purlin
KAS831 mullion
to allow pressing to runSloping mullion notched
Standard Transom drained profiles
KAS339a
End stop
Pressed up eaves trim
Mullion nose stops here
(insulated)
Compriband seal
M6
bracket (3mm)Pressed up gutter
Panel continuously
M10
M10
Suitable structural support required at eaves level with correctly detailed fixing brackets and fixings.
30°
20
152
20
Rain water goods by others
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.05Scale 1.2
Sheet 2 01.01.10
© Kestrel Aluminium Systems
Typical eaves details - roof onlyLow Rise Curtain Walling
KAS859
Suitable structural support required at eaves level with correctly detailed fixing brackets and fixings.
30°
52
9915
6
No 10
No 10
41
No 10
16
No 10
KAS831 mullion
KAS851Typical external roof/canopy - single glazed
KAS890.831 end plate in 3mm aluminium plate
KAS890.831 end plate
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.06Scale 1.2
Sheet 1 01.01.10
© Kestrel Aluminium Systems
Typical cill detail - Mullion drained profilesLow Rise Curtain Walling
5
KAS 68 cill
KAS 832
KAS 866
30
10
15
Packing shims as necessary
1/2" cill board by others - notch around mullion required
concealedBase fixing M
8
KAS 832
KAS 831
1/2" cill board by others - notch around mullion required
DPC
1005250
16
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.06Scale 1.2
Sheet 2 01.01.10
© Kestrel Aluminium Systems
Alternative cill detail - Mullion drained profilesLow Rise Curtain Walling
DPC
5
KAS 68 cill
1/2" cill board by others - No notch around mullion required
15
10
Packing shims as necessary
3" x 2" x 1/8" aluminium channelM
8
KAS 832
7415KAS 832
KAS 866concealedBase fixing
KAS 831
3010052
1/2" cill board by others - No notch around mullion required
16
50
76.2 7.8
52
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.07Scale 1.2
Sheet 1 01.11.14
© Kestrel Aluminium Systems
Base fixing onto cill - Mullion drained profilesLow Rise Curtain Walling
KAS 832
KAS 68 cill
50 100
50*
KAS 68 cill
SB660 butyl seals
M6
M8
If hung fixing condition, run Compriband 600 (10/3-7) as continuous rununder mullion and Ali tape PB also
M6
KAS 68 cill
14.5
M6M6
Ø8
KAS803
4150*
36.5
50 x 30 Ali-tape PB (1.2mm)
Compriband 600 (10/3-7)
M8
10
63.5
ø10*
* Preparation of drilled holes for main fixings
50mm centres for main fixings can increaseif required for ease of fixing and as required by fixing type/specification.
Preparation for sealing the under side of mullion 'wet zone'
PB Ali tape bonded to u/side of mullion drainage zone
Bed mullion on SB660 butyl seal - and ensure fully watertight
Expanding seal to underside of transom KAS832
See note above regarding fixing centres
30
See note above regarding fixing centres
*
Due to our policy of continued improvement Kestrel Aluminium Systems reserve the right to alter details and specifications without prior notice.ALUMINIUM SYSTEMS
KESTREL 6.09.07Scale 1.2
Sheet 2 01.01.10
© Kestrel Aluminium Systems
Base fixing onto cill - Mullion drained profilesLow Rise Curtain Walling
Preparation for cill transom
Use 5mmØ bit
85
50.5
KAS80330
16.5
Mullion base
KAS889.M06M6 x 100 Hexagon Bolt, Nut and Washers
R2.5
9.5
See sheets:
6.09.06 sheet 16.09.06 sheet 2
6.09.07 sheet 1