El 087 KESHSh.a. Albanian Power Corporation ENVIRONMENTAL MANAGEMENT PLAN PROJECT FOR REHABILITATION, UPGRADING AND DEVELOPMENT OF BULK POWER TRANSMISSION SYSTEM (400 kV, 220 kV and 110 kV) The Albanian Power Corporation - KESH has recognized environmental protection as one of society's greatest concerns and has worked actively towards its solution. The issue of environmental protection has branched out in many ways to include mitigation measures, managing environmental situations such as oil leakage/spillage, noises, EMF, disposal of wastes etc. This project is proposed as an important action for upgrading and developing of the main transmission facilities in order to increase their capability for the exchange of electricity with neighbouring countries as well as for developing the sub-transmission facilities in the Albanian Power System for satisfying the growing internal demand. This project is to be considered as a very important one. The main goal of the project is to achieve significant improvement in the operational effectiveness of the power sector. The objectives of the project are to: (i) Improve the overall standard, reliability, quality, efficiency and safety of the bulk power transmission system, as well as the security of power supply by the replacement of the ageing existing facilities by new ones. (ii) Contribute to the optimal operation of the system, thus contributing to and facilitating the reduction of technical losses, as well as improving the voltage profilel; (iii) Support the development of the sub-transmission and distribution facilities; (iv) Improve and enhance the efficiency of electricity interchanges with neighbouring countries, creating an optimal environment for electricity exchanges in an integrated Balkan area market; 1 Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized

PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

  • Upload
    vonhi

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

El 087

KESHSh.a.AlbanianPower Corporation

ENVIRONMENTAL MANAGEMENT PLAN

PROJECT

FOR REHABILITATION, UPGRADING AND DEVELOPMENT OF BULKPOWER TRANSMISSION SYSTEM

(400 kV, 220 kV and 110 kV)

The Albanian Power Corporation - KESH has recognized environmental protection as oneof society's greatest concerns and has worked actively towards its solution. The issue ofenvironmental protection has branched out in many ways to include mitigationmeasures, managing environmental situations such as oil leakage/spillage, noises, EMF,disposal of wastes etc.This project is proposed as an important action for upgrading and developing of themain transmission facilities in order to increase their capability for the exchange ofelectricity with neighbouring countries as well as for developing the sub-transmissionfacilities in the Albanian Power System for satisfying the growing internal demand.This project is to be considered as a very important one.The main goal of the project is to achieve significant improvement in the operationaleffectiveness of the power sector. The objectives of the project are to:(i) Improve the overall standard, reliability, quality, efficiency and safety of the bulk

power transmission system, as well as the security of power supply by the replacementof the ageing existing facilities by new ones.(ii) Contribute to the optimal operation of the system, thus contributing to andfacilitating the reduction of technical losses, as well as improving the voltage profilel;(iii) Support the development of the sub-transmission and distribution facilities;(iv) Improve and enhance the efficiency of electricity interchanges with neighbouringcountries, creating an optimal environment for electricity exchanges in an integratedBalkan area market;

1

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Pub

lic D

iscl

osur

e A

utho

rized

Page 2: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

(v) Attract foreign investors for investing in generation facilities (e.g. IPPs, which requirea sound transmission system for their power delivery up to the final consumers).

Most of the equipment in the 220 kV substations are of old manufacture mostly about20 years old or even more (generally equipment from end 70's or beginning 80's). As aresult, most of the substations require substantial rehabilitation. The situation isworsened by the fact that spare parts are not available in the market. As for the abovefacilities, the control, monitoring and protection systems are also of old technology, notadequate and suffer from lack of spare parts, which are difficult to find in the market.Several of their components are out of function. Owing to recent international financinghowever, some modern SF6-gaz insulated switchgears were installed in a fewsubstations.Has been studied that a big amount of faults happened in transmission network arecaused by the old equipment as switchgears, disconnectors, voltage and currenttransformers, and the substations suffer of non effective measuring systems.Furthermore, during peak load periods, the main autotransformers are overloaded.

On the basis of these studies it was concluded that most of the system components of220kV and 400 kV substations require rehabilitation, reinforcement and development, asthey are generally old or very old. (Please see pictures of each substation)The proposed project includes rehabilitation and upgrading of 8 220kV and 400kVsubstations. They are:1) Vau Deja HPP Substation,

2) Fierza HPP Substation,

3) Fieri TPP Substation,

4) Tlrana 1 Substation,

5) Elbasan 1 Substation,

6) Elbasan 2 (400 kV) Substation and

7) Burreli Substation

8) Komani HPP Substation (only control monitoring paft).

In the main project scope is planned the supplying and installation of primaryequipment and upgrading of control monitoring system on Fierza, Komani, Vau Dejes,Fieri and Burreli substation. In sum, the rehabilitation and reinforcement plan consistsof:a) Replacement of 400 kV Line Bays 1 (unit)b) Replacement of 400 kV Transformer Bays I (unit)c) Replacement of 220 kV Line Bays 18 (units)d) Replacement of 220 kV Transformer Bays 10 (units)e) Replacement of 110 kV Line Bays 20 (units)

2

Page 3: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

f) Replacement of 110 kV Transformer Bays 16 (units)g) Replacement of 35 kV Line Bays and Transformer Bays 3 (installations)h) Replacement of 220 kV Bus Coupler Bays 5 (units)i) Replacement of 110 kV Bus Coupler Bays 5 (units)j) Replacement of 220 kV Busbar Measuring Bays 10 (units)k) Replacement of 110 kV Busbar Measuring Bays 10 (units)I) Replacement of the Protection, Control-Monitoring and Measurement Systems (in

substations Vau Deja, Fierza, Burreli, Fieri) 4 (units)m) Replacement of the Protection, Control-Monitoring and Measurement Systems (in

substation Komani) I (unit)

The project proposed has been designed to avoid any impacts to the environment.The new high voltage switching equipment shall be specified or designed to comply withthe relevant standards. This assure that the load assumption, design, constructionstandards and safety features are in accordance with industry norms and benefit fromthe experience. Other control, monitoring and protection equipment are indoor installedgenerally low voltage without any environmental impact.Being a rehabilitation project, the environmental problems that this project may havediffer from the environmental and pollution problems of a project with new constructionfacilities. As mentioned the main scope of project will be replacement of old equipmentwith the new one.

So this project characteristic is that it guarantees no new environmental impact will begenerated after construction. This because of:

1. Generally no extension of the quantities of the existed equipment,2. No extension of construction area of each substation,3. No changing of power frequency and voltage level of equipment and substations,4. New equipment will be designed and produced according most updated

technology for sure environmentally more suitable than existed.This project will be developed replacing and upgrading the same type of facilities, in thesame location, with same or lower sensitivity and in the same scale with existedconditions. According the Bank environmental classification, considering that no newenvironmental impact created after its implementation, perhaps this project can beconsidered as of Class C.Some of environmental impacts expected to have during construction period. For thisreason we have prepared this EMP and further KESH Environmental Management Unit(EMU) has organized some limited public consultations with representatives ofcommunity of each project region. The reports of these meetings are attached.The implementation of EMP is planned to reduce the negative impacts of the projectsduring construction and operation as well.This EMP is designed for each Substation and it includes:

3

Page 4: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

(a) a mitigation plan which identifies the major issue, how they will be mitigated, atwhat cost and who is responsible, (b) a monitoring plan with details of how, at whatcost and who is responsible.(a) The mitigation plan includes specific mitigation measures, identifies responsibilityand provides for mitigation cost to be included in the installation and construction costfor the project.(b) The monitoring plan has identified monitoring parameters such as dust, noise,wastewater, visual resources, soil handling, etc. especially during the constructionphase.Impacts of the rehabilitation work will be monitored by level of noise, vibration and dustduring the construction phase. These Environmental impacts during constructions phasewill be inspected against the WB and EU environmental standards.Most of construction and operation activities are not expected to create significant noiseproblems due to the low level of human habitation in the vicinity of the substations. Tominimize noise nuisance, construction activities that create significant levels of noise andvibration will be limited to daylight hours.Electro-magnetic field (EMF), Oil leakage/spillage are the main monitoring parameters atthe operation phase for substation components.During the operation phase to prohibit the exposure to electromagnetic fields theInternational Standards will be abided. Also will be prepared and implemented safetyand emergency procedures manual if a fire or explosions happen in substations. Duringoperations the plan will be implemented to reduce potential impacts in the event of anemergency to the environment.Oil leakage will be monitored visually and periodically by the Albanian TransmissionSystem Operator (ATSO). Electromagnetic fields will be measured against EU or WBstandards during a year.According to the EMP there are minor impacts due to very low of electro-magnetic field(EMF), spillage, waste water, etc.Several mitigation actions can be applied which include: (i) contractors will employappropriate techniques to protect the environment during construction, using prototypedesigns and well-tested guidelines provided by the WB. (ii) Electromagnetic Field is notconsidered a serious problem with low and medium voltage lines, however WB or EUaccepted standards will be used. (iii) The use of PCB in the oil for transformers or anyother equipment is prohibited and this will be specified in the bidding documents. Alsothere'll verify and conform that there are no impacts on protected areas.Limited air contamination will be caused by vehicles and dust during construction. Nospecific mitigation measures are required except to maintain vehicles in proper runningorder, to cover trucks carrying excavation material, and to water the road at a few siteto prevent dust.

4

Page 5: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

The intention of project is the use of construction techniques and best managementpractices to minimize potential impacts to the environment.

The rehabilitations of these substations will have beneficial impacts from rural and urbanelectric power supplying, permanent and temporary jobs for the population in thoseareas.

5

Page 6: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV Vau-Deja HPP Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

*Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reducefugitive dust emissions. l l

6

Page 7: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics * Temporary jobs Contractor

Operation * Noise * Not close then 500 m from sensitive areas. ATSO/EMU

Phase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones

. Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

7

Page 8: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 220/110 kV Vau-Deja HPP Substation

Monitoring Description Cost Responsibility

What ~~~~~~~~~~~~~~When is theWhat Where is the How is the arameter to parameter to be Why

Phase Parameter parameter to be be monitoredl/ monitored Is the parameter Intl Opre Isaf Oeaeis to be monitored? type of monitoring frequency of to be monitored? Install Operate Install Opte

monitored? equipment? measurement or (optional)

Constructi Noise! Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation bserve vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

they are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

8

Page 9: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMUphase Once per quarter human's health

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF VAU DEJA S/S

9

Page 10: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV FIERZA HPP Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

* Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reducefugitive dust emissions.

10

Page 11: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics * Temporary jobs Contractor

Operation * Noise *Not close then 500 m from sensitive areas. ATSO/EMUPhase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones

. Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU/spillage penodically.

* PCBs . It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

11

Page 12: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 220/110 kV FIERZA HPP Substation

Monitoring Description Cost Responsibility

What How is the parameter to When is the WhyParameter aWhere rs the be monitoredl pmontored Is the parameter

Phase is to be parameter to be type of monitoring monitored to be monitored? Install Operate Install Operate

monitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

they are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

12

Page 13: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMU

phase ~~~~~~~~~~~~~~every quarter human's health

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF FIERZA S/S

13

Page 14: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV BIURRELI Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.pennissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

* Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reducefugitive dust emissions.

14

Page 15: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics n Temporary jobs Contractor

Operation * Noise *Not close then 500 m from sensitive areas. ATSO/EMUPhase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones* Oil leakage * Transformers will be maintained and repaired 500 $ ATSO/EMU

/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

15

Page 16: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 220/110 kV BURRELI Substation

Monitoring Description Cost Responsibility

What How is the parameter to When is the WhyWhere is the H ie paraet parameter to be Why

Phase Parameter parameter to be be monitored" monitored Is the parameter Intl Opre Isal Oeaeis to be monitored? type of monitoring fqncyof to be monitored? Install Operate Install Operate

monitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

hey are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

16

Page 17: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMUphase Once per human's health

quarter

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF BURRELI S/S

17

Page 18: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV TIRANA 1 Substation

Cost Institutional responsibility} ~~~Phase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection . Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase *Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

* Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust . If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reduceI fugitive dust emissions.

18

Page 19: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics * Temporary jobs Contractor

Operation * Noise * Not close then 500 m from sensitive areas. ATSO/EMU

Phase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones. Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU

/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

19

Page 20: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 220/110 kV TIRANA 1 Substation

Monitoring Description Cost ResponsibilityWhen is the

What Where is the How is the parameter to Wheter the Why

Phase Parameter parameter to be be monitoredl frued o parametert Install Operate Install Operateis to be monitored? type of monitoring moqunitore ts the prmentoer?

monitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

hey are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

20

Page 21: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMUphase Once per human's health

quarter

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF TIRANA 1

21

Page 22: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV ELBASAN 1 Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

* Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reducefugitive dust emissions.

22

Page 23: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics * Temporary jobs Contractor

Operation * Noise . Not close then 500 m from sensitive areas. ATSO/EMU

Phase * Electrical Field * Structures will be constructed under ATSO/EMUInternational standards IEC ones

. Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU/spillage periodically.

* PCBs . It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics . Overall highly beneficial to both urban andrural areas supplying energy

23

Page 24: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 220/110 kV ELBASAN 1 Substation

Monitoring Description Cost Responsibility

What Wer i te How is the parameter to WhniteWyPhase ~Parameter paeraeter tohe be monitored/ prmoniertorbed is the parameter

Phase is to be motitore type of monitoring fmreun of to be monitored? Install Operate Install Operatemoioe?monitored? equipment? mesremuenty or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

they are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

24

Page 25: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMU

phase Once per quarter human's health

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMU

magnetic area meter human's health

field

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU

/spillage transformers visually by employees Every day human's health,flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU with

oil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSO

Activities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES AND

PUBLIC CONSULTATION REPORT OF ELBASAN I S/S

25

Page 26: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 400/220 kV ELBASAN 2 Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

* All active construction areas shall be watered atleast twice daily

* Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reducefugitive dust emissions.

26

Page 27: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling * All stockpiles have to be removed 500 $ Contractor

* Socioeconomics .Temporary jobs Contractor

Operation * Noise *Not close then 500 m from sensitive areas. ATSO/EMUPhase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC* Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU

/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

27

Page 28: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANB. MONITORING PLAN

Rehabilitation of 400/220 kV ELBASAN 2 Substation

Monitoring Description Cost Responsibility

What Where.is the How is the parameter to When is theWhat Where is the How istheparameterto parameter to be WhyPhase Parameter parameter to be be monitoredl monitored Is the parameter Install Operate Install Operate

is to be monitored? typ e of m on ito ring frequency of to be monitored? Insal Oete nsal Opremonitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

they are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

28

Page 29: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMU

phase ~~~~~~~~~~~~~~Once per quarter human's health

Electro- Near by substation Using a electrical field Once per To protect 6 000 $ ATSO/EMUmagnetic area meter quarterly human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF ELBASAN 2 S/S

29

Page 30: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV FIERI Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Instafl Operate

Design * Site selection . Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

. Noise/Vibration . Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase *Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

' The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

' Air emissions * All vehicles used during construction have to 1500 $ Contractorbe comply with applicable air quality standard & DFIPin EU Directive 2000/140EC of may 2000.

. All active construction areas shall be watered atleast twice daily

*Exposed stockpiles shall be enclosed, covered orwatered at least twice daily

* Dust * If dusty will be sprinkle water 1500 $ Contractor* When possible construction activities should be

scheduled during periods of low wind to reduceI fugitive dust emissions.

30

Page 31: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

* Soil Handling All stockpiles have to be removed 500 $ Contractor

. Socioeconomics *Temporaryjobs Contractor

Operation * Noise * Not close then 500 m from sensitive areas. ATSO/EMU

Phase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones

. Oil leakage . Transformers will be maintained and repaired 500 $ ATSO/EMU/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

* Socioeconomics * Overall highly beneficial to both urban andrural areas supplying energy

31

Page 32: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLAN

B. MONITORING PLANRehabilitation of 220/110 kV FIERI Substation

Monitoring Description Cost Responsibility

What Where is the How is the parameter to When is the WhyWhere is the e monitoredlparameter to be L h aaee

Phase Parameter parameter to be be monitored/ monitored IsInstall Operate Install Operateis to be monitored? type of monitoring frequency of to be monitored? Isal Oeae I tl prt

monitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

Air Nearby substation Observe vehicles, Every working To protect 1 200 $ Contractoremissions area construction areas if day during human's health & EMU

they are watered, constructionenclosing or wateringof stockpiles.

Dust Substation By observation Once a week To protect 500 $ Contractor(under windy/ dry human's health &EMUconditions)

Soil Substation area By observation Continually To protect 300 $ Contractorhandling human's health, &EMU

flora and fauna

32

Page 33: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMUphase Every quarter human's health

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Acronymus used:

ATSO: Albanian System Operator

DFIP: KESH Directory of Foreign Investments and Projects

EMU: KESH Environmental Management Unit

PICTURES ANDPUBLIC CONSULTATION REPORT OF FIERI S/S

33

Page 34: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLANA. MITIGATION PLAN

Rehabilitation of 220/ 110 kV KOMANI HPP Substation

Cost Institutional responsibilityPhase Issue Mitigating Measure

Install Operate Install Operate

Design * Site selection * Existed site with improved fence or wall. Contractor& DFIP

* PCBs * It is not prohibited under the Albanian low but Contractorthe Bidding documents specify International & DFIPstandards and it will be specified that PCB usewill be prohibited

* Noise/Vibration * Max.permissible noise level will be 70 dB and 1 000 $ ContractorConstruction will be specifided in the bidding documents. & DFIPPhase * Normal working hours (8 - 17.00) that will be

specified in the Biding documents.

* Visual resources * Color of equipment must have a low reflectivity 1 500 $ Contractorneutral gray finish to minimize visual salience & DFIP

* The chain link fences surrounding thesubstations will have a dulled, darkened finish toreduce their contrast with the surrounding

* Socioeconomics * Temporary jobs Contractor

Operation * Noise *Not close then 500 m from sensitive areas. ATSO/EMUPhase * Electrical Field * Structures will be constructed under ATSO/EMU

International standards IEC ones* Oil leakage * Transformers will be maintained and repaired 500 $ ATSO/EMU

/spillage periodically.

* PCBs * It is not prohibited under the Albanian low but ATSO/EMUthe Bidding documents specify Internationalstandards and it will be specified that PCB usewill be prohibited

34

Page 35: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

ENVIRONMENTAL MANAGEMENT PLAN

B. MONITORING PLAN

Rehabilitation of 220/110 kV KOMANI HPP Substation

Monitoring Description Cost Responsibility

What Where is the How is the parameter to When is the Why

Phase Parameter paeraeter tohe be monitoredl prmonirtorbed Is the parameterPhase is to be parameter to be type of monitoring monitored to be monitored? Install Operate Install Operate

monitored? equipment? measurement or (optional)

Constructi Noise/ Substation Using a noise meter Continually To protect 1000 $ 1000$ DIPH EMUon Phase Vibration human's health

Visual All the equipments Visually Continually To protect 1500$ EMURecources will have a low human's health,

reflectivity natural flora and faunagray finish tominimize visualsalience Visually

35

Page 36: PROJECT FOR REHABILITATION, UPGRADING AND …documents.worldbank.org/curated/en/... · environmental protection has ... The proposed project includes rehabilitation and upgrading

Operation Noise Substation area Using a noise meter Periodically To protect 1 000 $ DFIP ATSO/EMUphase Every quarter human's health

Electro- Near by substation Using a electrical field Once per year To protect 3 000 $ ATSO/EMUmagnetic area meter human's healthfield

Oil leakage Nearby Will be monitored Periodically To protect 500 $ ATSO/EMU/spillage transformers visually by employees Every day human's health,

flora and fauna

PCBs Test transformers Laboratory of Fieri Oil Every new supply To protect 3 500 $ EMU withoil Institute/ Nature human's health, support of

Science Faculty flora and fauna NatureScienceFaculty

All site In the site All related actives Every day To protect 1 500 $ ATSOActivities shall be human's health

Notes: 1. Acronymus used:

ATSO: Albanian System OperatorDFIP: KESH Directory of Foreign Investments and ProjectsEMU: KESH Environmental Management Unit

2. Because the scope of KOMANI HPP Substation includes only control monitoring and all of rehabilitation works arecarrying inside the Plant building, the mitigation and monitoring plan during construction phase is more simple then othersubstations where the rehabilitation works included all of primary equipment outdoor installed.