The most advanced monitoring systems for medium voltage primary and secondary distribution lines. Fanox is a leader in protection & control and has a long experience as manufacturer of equipment for the market’s leading utilities and industry. We offer an extensive array of options within control, measurement and communication in electrical substations for secondary and primary distribution lines. Fanox’ long term commitment to produce high quality products offers our customers a total protection guarantee solution.
Citation preview
SIAProtection relay for secondary distribution
Self-powered Signalling with magnetic bistable indicators
High electromagnetic compatibility Events recorder and specific test menu
Protection relay for secondary distribution. SIA 4Protection functions and Standards 5How to select the SIA relay 6
SIA-C 8Main specifications 8Technical specifications 8Model list 11
SIA-E 12Main specifications 12Technical specifications 12Model list 15
SIA-D 16Main specifications 16Technical specifications 16Model list 19
Common elements and technical specifications 20Accessories 22
index
Fanox, getting one step ahead in stateof the art tendencies and the profoundchanges occurring in electrical energydistribution, constantly focusing onguaranteeing uninterrupted supply, hasdeveloped a complete line of self-normered, maintenance free protectionsto safely and efficiently meet secondarydistribution requirements.
Fanox is involved in all levels of electricaldistribution, both primary and secondary,and has an extensive experience indesigning and producing madecustomized equipment for manufacturersof primary substations with relation toprotection, control, measurement andcommunication, being an importantreference within this field.
4
Protection relays forsecondary distribution. SIA
The SIA relays family, composed of SIA-C, SIA-E and SIA-D, are designed to protect the secondary transformationand distribution centres of electrical grids. The protection features include protection against instantaneous andinverse time overcurrent (for the phases and the neutral) as well as an external trip support (temperature, pressure,etc.) depending on the model.
The protection functions can be enabled by using both the front panel and the communications link to the SIComprogramme. Combining the settings and IEC curves available allows for precise coordination with other equipment.
The combination of the available IEC curves and settings allows a precise combination with other equipments.
One of the outstanding features of the SIA-C and SIA-E is the use of the operating current itself for self-powering.This means that maintenance of the transformation and distribution centres is reduced. Neither batteries, chargers,nor any other external power elements are required.
Even more, one advantage over other equipment available on the market facilitates the start-up of installationsand the carrying out specific operations in adverse conditions. All models can be powered from an externalbattery, allowing us to guarantee complete operation of the equipment, including tripping due to any faults thatmay occur.
5
Protection functionsand Standards
Overcurrent protectionFunction 50Pinstantaneous phase overcurrent
Function 50Ninstantaneous neutral overcurrent
Function 51PInverse time phase overcurrent
Function 51NInverse time neutral overcurrent
Neutral directional protectionFunction 67NIt uses the residual voltage as the polarisation magnitudeand the residual current as the operating variable. Ifthe directional function 67N is not enabled, it behavesas a 50N Function. The operative time starts when thefollowing conditions are met simultaneously:
- residual voltage higher than setting
- residual current higher than setting
- the gap of the residual current voltage is such thatthe residual current is within the area of theintervention.
External tripFunction 49There is a direct trip input, normally associated with abimetallic contact that is fitted to the power transformer,which serves as a backup for the current functions. Inorder for it to be a real backup, this input is not relatedto the protection processors. This means that theprocessors do not read the input and trip the striker,but the input acts directly on the striker, remainingoperational for as long as the equipment is powered.This input is especial ly protected againstelectromagnetic noise.
Break disconnector protection using triplockingMany transformation centres have a disconnector asa break element. As line breakers have a limited openingcurrent, with short-circuit events at high currents theresponsibility for opening falls on the fuses, becauseotherwise, opening the line breaker would meandestroying it.
In order to deal with these situations, tripping either inphase or neutral is blocked when the measured currentexceeds a preset value.
IEC Curves 255-4/BS-142Standard curves are used for the protection function51 phase and neutral:
- Normally inverse
- Very inverse
- Extremely inverse
- Definite time
MeasurementsPhase and neutral currents are measured with anaccuracy of ±2% over the whole range.
StandardsEN 50263 (1999) Generic for equipment protection andmeasurement relays.
EN 61000-6-4 (2001) Generic for emissions in industrialenvironments
EN 61000-6-2 (2001) Generic for immunity in industrialenvironments.
EN 55011 and EN 55022 RF emissions, Group 1, ClassA limits.
IEC 61000-4-2 Electrostatic discharge immunity, level 3.
IEC 61000-4-3 Radiated RF immunity, level 3
IEC 61000-4-4 Electrical fast/burst immunity (EFT),level 4
IEC 61000-4-5 Surge immunity, level 3
IEC 61000-4-6 Conducted RF immunity, level 3
IEC 61000-4-8 and IEC 61000-4-9 Pulsed magneticfield immunity, level 5
IEC 61000-4-10 Damped oscillatory magnetic field,level 5
IEC 61000-4-11 Voltage dip and short interruptionimmunity
IEC 61000-4-12 and IEC 60255-22-1 Dampedoscillatory RF wave immunity, level 3
Fanox Quality Management System its certifiedaccording to standard ISO 9001:2008
6
Description SIA-C SIA-E SIA-D
Functions
50P
51P
50N
51N
67N (2 units) - -External trip
Protection of breaker by trip locking -
Supply
Self-powered through operating current -Auxiliar voltage 230 Vac -Auxiliar voltage 110-230 Vac / 90-300 Vdc - -Auxiliar voltage 24-48 Vdc - -Battery supply (KitCom)
Actuation
Striker or coil -Free of potencial contact
Current transformers
Standard CT /5 o /1 -Double core CT (CT-DB) - -
State and command
State and command of the circuit breaker - -Number of openings - -Acumulated amps - -
Control and signalling
Biestable magnetic indicators
4 configurable free of potential inputs - -
4 configurable free of potential outputs - -Events
Real time clock (RTC)
Communication
ModBus RTU protocol
RS232 port
RS485 port
(2)
-
Oscillography - -
How to select the SIA relay
(1) Use the TCM adapter to operate the coil(2) The trip is not battery supply operative in the SIA-D equipment
Available in all modelsSelected according to the model
7
50P 51P
50N 51N
49* Trip
Power
Tx Rx
52
tº Vaux* RTC* I/O* FRAM* RS485*
*optional
8
SIA-C
001
Technical specifications SIA-C
Functions diagram SIA-CBattery 9V
PC
SELF-POWERED OVERCURRENT PROTECTION RELAYFOR SECONDARY DISTRIBUTION
Main characteristics
- The SIA-C is a self-powered overcurrent protection relay using the operating current through three /5 or /1standard current transformers fitted on the lines. These transformers are also used to obtain currentmeasurements. The equipment can also occasionally supplied be temporarily supplied by an external battery.
- The events are recorded and a specific test menu is provided.
- High electromagnetic compatibility.
- The installation and subsequent maintenance of batteries is eliminated. The operating costs of the centre arereduced.
- Start-up of the relay from 0.2 times of the nominal current in one phase ensures capacity to trip at low energylevels.
- The line opening mechanism is activated either by means of a striker PRT, operated by the energy suppliedby the relay itself, or by a coil using the TCM trip adapter.
- There are bistable magnetic indicators which indicate the trip cause, maintaining their position even thoughthe relay loses the supply.
Connections diagram SIA-C
9
10
Technical specifications
Technical parameters SIA-C
External trip Charging time 10 s
Trip output24 V - 576 mJ (activation of the strike or thecoil with TCM adapter)
Frequency 50/60Hz
Current measure
Communication
Auxiliary supply
Battery supply With KITCOM adapter DB9
Self-power fromcurrent
One phase self-power level:I > 0.2 x In
Environment
Transformers
Mechanicalfeatures
Function 51N
Permission: yes/no
Operating range: 0,20 to 7 x In (step 0,01)
Curves: IEC 255-4/BS-142
Timing accuracy: 5% or 30 ms(greater of both)
Function 51P
Permission: yes/no
Operating range: 0,20 to 7 x In (step 0,01)
Curves: IEC 255-4/BS-142
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
Timing accuracy: 5% or 30 ms (greaterof both)
Function 50NFunction 50P
Permission: yes/no
Operating range: 0.20 to 30 x In (step 0.01)
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Dimensions and shut cutout SIA-C
Operating time:Inverse curve, very inverse curve,extremely inverse curve.Definite time: 0.02 to 300 s (step 0.01 s)
Permission: yes/no
Operating range: 0.20 to 30 x In (step 0.01)
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Operating time:Inverse curve, very inverse curve,extremely inverse curve.Definite time: 0.02 to 300 s (step 0.01 s)
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
True RMS
Sampling: 16 samples/cycle
Accuracy ±2% in the whole range
RS232 port: Modbus RTU
RS485 port: Modbus RTU
230 Vac ±20 %
Operating temperature: -10 to 60 ºC
Storage temperature: -20 to 70 ºC
Humidity: 95%
Power supply and measurement 3 CT /5 or /1
Metallic box
Panel mounting
1/3 Rack - 4 U
IP-52
cutout
11
Model list SIA-C
SIA
C 50P + 51P + 50N + 51N
15
1A5A
15AB
1 A5A
0,10 A0,20 A
56
50 Hz60 Hz
9 Vdc + Self-power9 Vdc + Self-power + 230 Vac9 Vdc + Self-power + 110 Vac9 Vdc + Self-power + 24 Vac
01
TY
PE
PH
AS
E M
EA
SU
RE
NE
UT
RA
L M
EA
SU
RE
NE
T F
RE
QU
EN
CY
PO
WE
R S
UP
PLY
EX
TR
A F
UN
CT
ION
S
CO
MM
UN
ICA
TIO
NS
INP
UT
S /
OU
TP
UT
S
PR
OC
ES
SO
R A
ND
ME
MO
RY
LA
NG
UA
GE
AD
AP
TAT
ION
English, Spanish and FrenchEnglish, Spanish, French and TurkishEnglish, Spanish, French and Polish
Without non-volatile RAM memoryWith non-volatile RAM memory
With non-volatile RAM memory and fast startup
Local ModBus (RS 232)Local ModBus (RS 232) y Scada (485)
With striker trip and without direct trip, (tª)With striker trip and without trip, (tª)
With potential-free trip and without direct trip, (tª)With potential-free trip and with direct trip, (tª)
Note: Common technical specifications and accessories, page 20.
0123
0123
Without inpust / outpustSignalingTrip bus
012
012
ABC
-A
First versíonSecond versíon
PC
12
SIA-ESELF-POWERED OVERCURRENT PROTECTION RELAYFOR SECONDARY DISTRIBUTION
002Main specifications
Technical specifications SIA-E
Functions diagram SIA-E
50P 51P
50N 51N
49* Trip
Power
Tx Rx
52
tº Vaux* RTC* I/O* FRAM* RS485*
*optional
Battery 9V
- The SIA-E is a self-powered overcurrent protection relay using the operating current through specific dual-core current transformers, one used for measuring and the other for powering.
- The events are recorded and a specific test menu is provided.
- High electromagnetic compatibility.
- Self power allows for the minimisation of costs for installation and maintenance of the centre as there is noneed for batteries or other external power supply items.
- SIA-E starts up from 5 A of primary single phase with the relay fully operative at this low energy level.
- Its reduced depth of 80 mm makes it easy to install.
- It includes the contact-breaker protection function by means of trip locking.
- The line opening mechanism is activated either by means of a striker PRT operated by the energy suppliedby the relay itself, or by a coil using the TCM trip adapter.
- There are bistable magnetic indicators which indicate the cause of the trip, maintaining their position eventhough the relay loses the supply.
Especificaciones técnicas
Connections diagram SIA-E
13
SIA-E
14
Technical specifications SIA-E
Technical parameters
Function 50P
Permission: yes/no
Function 50N
Permission: yes/no
Function 51P
Permission: yes/no
Operating range:SIAEA*: 3 to 105 A primary (step 0.1)SIAEB*: 5 to 175 A primary (step 0.1)
Curves: IEC 255-4/BS-142
Operating time:Inverse curve, very inverse curve, extremelyinverse curve.Definite time: 0.02 to 300 s (0.01 s)
Timing accuracy: 5% or 30 ms(greater of both)
Function 51N
Permission: yes/no
Operating range:SIAE*A: 0.3 to 10.5 A primary (step 0.1)SIAE*B: 0.3 to 10.5 A primary (step 0.1)
Curves: IEC 255-4/BS-142
Operating time:Inverse curve, very inverse curve, extremelyinverse curve.Definite time: 0.02 to 300 s (0.01 s)
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
Timing accuracy: 5% or 30 ms(greater of both)
Permission: yes/noBlocking level:SIAEA*: 105 to 300 A primary (step 0.1)SIAEB*: 175 to 500 A primary (step 0.1)
Charging time 10 s
10 V - 8 mJ (activation of the strike or withTCM adapter the coil)
With KITCOM adapter DB9
One phase self-power level:I > 5 A (primary)
100 A primary
Operating temperature: -10 to 60 ºC
Storage temperature: -20 to 70 ºC
Humidity: 95%
Power supply and measurement.Transformers with double core CT-DB
Metallic box
Panel mounting
1/2 Rack - 4 U
IP-52.
Dimensions and cutout pattern SIA-E
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Operating range:SIAEA*: 3 to 450 A primary (step 0.1)SIAEB*: 5 to 750 A primary (step 0.1)
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Operating range:SIAE*A: 0.3 to 45 A primary (step 0.1)SIAE*B: 0.3 to 45 A primary (step 0.1)
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
50/60 Hz
True RMS
Sampling: 16 samples/cycle
Accuracy ±2% in the whole range
RS232 port: Modbus RTU
RS485 port: Modbus RTU
230 Vac ±20 %
Trip blocking
Overtemperaturetrip input
Trip output
Frequency
Current measure
Communications
Auxiliary supply
Battery supply
Self-powerfrom current
Maximum permanentcurrent
Environment
Transformers
Mechanical features
cutout
Model list SIA-E
15
SIA
E
AB
ABC
56
01
01
01
01
012
ESF
0
TY
PE
PH
AS
E M
EA
SU
RE
NE
UT
RA
L M
EA
SU
RE
NE
T F
RE
QU
EN
CY
SU
PP
LY
TE
MP
ER
AT
UR
E
CO
MM
UN
ICA
TIO
NS
INP
UT
S /
OU
TP
UT
S
EV
EN
TS
LA
NG
UA
GE
RE
VIS
ION
50P + 51P + 50N + 51N + blocking
3 A - 450 A Blocking 300 A Ct 605 A - 750 A Blocking 600 A Ct 100
0.3 A - 45 A Ct 500 Sensitive neutral0.3 A - 45 A Ct 60 Solid neutral0.5 A - 75 A Ct 100 Solid neutral
50 Hz60 Hz
9 Vdc + Self-power9 Vdc + Self-power + 230Vac
Without direct trip, tºWith direct trip, tº
ModBus Local (RS 232)ModBus Local (RS 232) or ModBus Scada (485)
Without biestablesWith biestables
Without non-volatil RAM memoryWith non-volatil RAM memory
With non-volatil RAM and RTC clock
EnglishSpanishFrench
Note: Common technical specifications and accessories, page 20.
16
SIA-DOVERCURRENT PROTECTION RELAY FOR SECONDARY DISTRIBUTION
003Main specifications
Technical specifications
Functions diagram SIA-D
PC
Tx Rx
Battery 9V
52
tº
52
50N 51N
50P 51P
67N 67N
49
RTC* FRAM* RS485*
O
*optional
I
* *
Oscilo*
Vaux
110/220 Vac80/220Vac
- The SIA-D is an overcurrent protection relay with a switched auxiliary power supply (110-230 Vac / 90-300 Vdc).The current is measured by using /5 or /1 current transformers.
- The events are recorded and a specific test menu is provided.
- High electromagnetic compatibility.
- Its reduced depth of 75 mm makes it easy to install.
- It is ideal for transformation and distribution centres with auxiliary power supplies and/or rechargeable batteries.
- It is fitted with two 67 N neutral directional units.
- With circuit breaker control and monitoring (circuit breaker status, number of openings, accumulated amperes,etc.)
- It has freely 4 inputs and 4 free-potential outputs configuration.
- There are bistable magnetic indicators which indicate the cause of the trip, maintaining their position eventhough the relay loses the supply.
- Oscillography is available.
Especificaciones técnicas
Connections diagram SIA-D
17
SIA-D
Technical specifications SIA-D
Technical parameters
18
Function 51P
Permission: yes/no
Operating range: 0.20 to 7 x In (step 0.01)
Curves: IEC 255-4/BS-142
Timing accuracy: 5% or 30 ms(greater of both)
Function 50N
Function 51N
Function 50P
110 Vdc ±40 % - 0.5 VA
250 Vac - 830 Vdc - 5
Blocking level: 7 to 20 x In (step 0.01)
Alarm, maximum number of openings:1 to 2000
Alarm, maximum number of acumulated amps:
50/60Hz
Permission: yes/no
Operating range: 0.20 to 7 x In (step 0.01)
Curves: IEC 255-4/BS-142
Timing accuracy: 5% or 30 ms(greater of both)
Permission: yes/no
Operating range: 0.20 to 30 x In (step 0.01)
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Permission: yes/no
Operating range: 0.20 to 30 x In (step 0.01)
Operating time: 0.02 to 300 s (step 0.01)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
Operating time:Inverse curve, very inverse curve,extremely inverse curve.Definite time: 0.02 to 300 s (step 0.01 s)
Dial: 0.05 to 1.25
Curve, activation level 120%
Curve, deactivation level 100%
Definite time, activation level 100%
Definite time, deactivation level 95%
Instantaneous deactivation
Operating time:Inverse curve, very inverse curve,extremely inverse curve.Definite time: 0.02 to 300 s (step 0.01 s)
Function 67N(2 units)
Permission: yes/no
Operating range Io: 0.2 to 30 x In (step 0.01)
Operating range Vo: 0.4 to 20 V (step 0.1 V)
Operating time: 0.02 to 300 s (step 0.01 s)
Directionality: yes/no
Current, activation level 100%
Current, deactivation level 95%
Voltage, activation level 100%
Voltage, deactivation level 95%
Operating angle: 0 to 359º (step 1º)
Semicone angle: 0 to 180º (step 1º)
0 to 999.999 (kA2)
4 inputsconfigurables
4 outputsconfigurables
Trip blocking
Breakermonitoring
Frequency
True RMS
Sampling: 16 samples/cycle
Accuracy ±2% in the whole range
16 records per cycle
The beginning of the oscillography is configurable
2 registers: 3 cycle previous to the fault and 30 after fault
Current measure
Oscillography
Communications
Conmuted supply
Auxiliary supply
Battery supply
Environment
Transformers
Mechanical features
RS232 port: Modbus RTU
RS485 port: Modbus RTU
110-230 Vac / 90-300 Vdc, ±20 %
24-48 Vdc ±20 %
With KITCOM adapter DB9
Operating temperature: -10 to 60 ºC
Storage temperature: -20 to 70 ºC
Humidity: 95%
Measurement CT /5 or /1
Metallic box
Panel mounting
1/2 Rack - 4 U
IP-52
Model list SIA-D
19
Dimensions and cutout pattern SIA-D
SIA
D
125
cutout
TY
PE
PH
AS
E M
EA
SU
RE
NE
UT
RA
L M
EA
SU
RE
HA
RD
WA
RE
SE
TT
ING
S
PO
WE
R S
UP
PLY
EX
TR
A F
UN
CT
ION
S
CO
MM
UN
ICA
TIO
NS
INP
UT
S /
OU
PT
UT
S
EV
EN
TS A
ND
OS
CIL
LOG
RA
PH
Y
LA
NG
UA
GE
AD
AP
TAT
ION
In a same model, neutral measurement range can be selected using internal dipswitch
Note: Common technical specifications and accessories, page 20.
50P + 51P + 50N + 51N + Trip Locking + 52
1 A2 A5 A
0.1 A0.2 A1 A5 A
50 Hz + Breaker50 Hz + Circuit Breaker
60 Hz + Breaker60 Hz + Circuit Breaker
110-230 Vac / 90-300 Vdc24-48 Vdc
Without 67NWith 67N (2 units)
With 67NA
Local ModBus (RS 232)Local ModBus (RS 232) y Scada (485)
4 O + 4 I
Without non-volatile RAM memoryWith non-volatile RAM memory (events)
With non-volatile RAM memory (events + oscilo)
English, Spanish and FrenchEnglish, Spanish, French and TurkishEnglish, Spanish, French and Polish
First versionSecond version
AB15
5678
23
012
01
2
012
ABC
-A
20
HMIThe HMI consists of:
COMMON ELEMENTS (SIA-C, SIA-E y SIA-D)
- A 2x20 LCD screen with alphanumeric characters thatallow the equipment parameters to be set (adjusted)and monitored (measurements, statuses, events).
- A membrane keyboard with six keys that allow you tonavigate the menus and access information of interest.A seventh button - “RESET”, allows you to reset thebistable indicators and the events log. For securityreasons, an access code is needed to modify thesettings.
- LED indicators showing the type of power supply beingused at all times. The relay can use more than onepower source at one time.
- Bistable magnetic indicators that signal the cause oftripping. These indicators remain in position when theequipment loses power, reducing the time themaintenance service needs to identify the cause oftripping.
Test MenuThis allows you to use the HMI to verify correct operation of the LEDs, the bistable magnetic indicators and thetrip contact.
Activating the trip contact from the test menu allows you to verify correct operation of the opening mechanismsimply.
On SIA-D, it is possible to activate the 4 outputs.
EventsEvents are recorded and ordered chronologically (up to 500), allowing you to analyse what has happened withthe installation over time (start-ups, tripping power supplies, etc.). They are recorded chronologically to thenearest millisecond in real time, thanks to the Real Time Clock (RTC). Events can be recorded on a non-volatileRAM memory. This option can be selected according to the model.
21
elementsCommunicationsThe relays have an RS-232 serial port on the front of the equipment with a DB9 connector and an optional rearRS-485 port on connection terminals. The Modbus RTU protocol is implemented for both ports.
The SICom programme with Windows R 2000/XP uses a graphic user interface to allow you to access allequipment information, modify the settings and save events.
The programme can be used locally by using the front port or remotely by using the rear RS485 port.
There are 4 levels of access with user-definable codes.
Self-diagnosisDiagnostic algorithms to generate the corresponding events are executed on starting up the equipment and allthe time the relay is operating.
22
ACCESSORIES
Battery power supply KitComThe KitCom is an adapter that allows you to feed SIA relays from the front communications port, allowing alsoto communicate with the computer locally via RS232.
The power comes from two AA batteries of 1.5 Volts placed at the bottom of the device. The equipment has asmall Dc / Dc power supply raising the voltage to 12 volts required to operate the equipment. This operationincludes the energy necessary to trip. This is important in the commissioning processes of the transformationcentres, allowing full verification of the centre, without any auxiliary power supply.
The equipment has a microswitch that feeds the power supply with a LED (ON) when the voltage is 12 volts.
In addition to all the necessary to give the power supply, this device has two LED associated with the Rx andTx lines of communication, and they are used to verify that there is data traffic between the PC and the SIA relay.
Striker PRTThis is a single effect solenoid. The striker is springoperated.
The striker is activated by low-power polarised electricalsignal supplied by the relay in case of a fault.
The striker is reset to its starting position manually.
Travel: 8 mmSpring strength:
- Start of travel: 37 N- End of travel: 18 N
Response time: 4 msProtection rating: IP-40
Trip adaptor TCMThis item is connected to the relay trip output and suppliesthe energy needed to trip the coil.
It is loaded using the auxiliary 230 Vac voltage of thetransformation centre and retains power for up to 3 dayswithout external power supply.
e
23
140,4 40,3
40,3
80
CT-DB Dual-core Transformer- Current transformer for indoor service - no primary coil.
- With two secondary coils, one for protection and the other for self-powering (3 days in case of a fault).
- For use with the SIA-E protection relay.
Highest voltage/Insulation rating: 0.72 kV/3 kVInsulation class: Class B, 130 ºCShort-circuit thermal intensity/Dynamic: 20 kA - 1 s / 50 kAPlastic case with resin filling: self-extinguishing, halogen-free UL94-V0Standard: IEC 60044-1
PAE Asuaran - Edif. Artxanda, 2348950 Erandio (España)
tel.: (+34) 94 471 14 09//fax.: (+34) 94 471 05 92//
mail: [email protected]
www.fanox.com
Fanox reserves the right to modifytechnical specification of productscontained within this cataloguewithout previous notice
Fanox is involved in all levels of electrical distribution,both primary and secondary, and has a great deal ofexperience in designing and producing made to measureequipment for manufacturers of primary substationswith relation to protection control, measurement andcommunication, and is an important reference withinthis field.