Upload
suvra-pattanayak
View
17
Download
1
Embed Size (px)
DESCRIPTION
power system oparation and control
Citation preview
11/13/2013
1
Fast Load Flowand
Contingency Analysis
Dr. Swapan Kr. GoswamiProfessor
Department of Electrical EngineeringJadavpur University
Applications of load flow As an independent tool
As a support tool
Speed requirements
Accuracy requirements
Fast and accurate : Fast decoupled load flow
Fast but approximate : DC load flow
Fast Decoupled Load Flow:Newton – Raphson method in polar co-ordinate
V
VLJ
NH
Q
P P-V & Q - are weakly coupled
V1X
V2 /
P+jQ
111
112
1
V
Pxjx
V
QV
V
jQPjxVV
V
jQPI
V
V0
0
L
H
Q
P
Assuming complete decoupling
V1
(Q/V1.X)(PX/V1)
V2
kmkmkmkmm
mkSpecifiedkk
kmkmkmkmm
mkSpecified
kk
BGVVQQ
BGVVPP
cossin
sincos
kmkmkm
kkkkkkkkkkkk
kmkmkmkmmkkmkm
jBGY
QVBLQVBH
BGVVLH
22 ;
;cossin
Normally,Vk, Vm 1.0 p.u.
R
xratio of lines are high
km are small
Thus, cos km 1, Gkm sin km << Bkm;
11/13/2013
2
kmkmkmkmm
mkk BGVVQ cossin
ko
kmm
kmko
kmm
km
kmm
kmkkm
km
YyYy
BBB
and
2
Thus,
kkkkkkk
kmmkkmkm
kmkm
ikokikk
VBLH
BVVLH
yY
yyY
The decoupled load flow equation is thus,
V
VVBVQ
VBVP
..
..
The elements of the matrices [B′ ] and [B″] are strictly elementsof [-B].Further simplification:(a)Taking the left hand V terms on to the left hand sides of the
equations and by setting all the right hand V terms to 1 p.u.(b) Omitting from [B′ ] the representation of those network
elements that predominantly affect MVAR flows i.e., shuntreactances and off-nominal in phase transformer taps.
(c) Omitting from [B″] the angle shifting effects of phase shifters.(d) Neglecting series resistances in calculating the elements of
[B′ ].
The final fast decoupled load flow equations
VBV
Q
BV
P
kmkmkk
kmkm
km kmkk
kmkm
bB
kmbB
xB
kmx
B
for,
1
for,1Where,
22kmkm
kmkm
kmkmkm
xr
xb
jbgy
The matrics B’ and B” are real, sparse and have the structuresof [H] and [L] respectively. Order of B’ and B” are (N – 1) and(N – M) respectively, where N is the number of bus bars and Mis the number of PV bus bars. B” is symmetric in value and so isB’ if phase shifters are ignored. The elements of the matricesare constant and need to be evaluated and triangulated onlyonce for a network.
The speed of iterations of the fast decoupled method is aboutfive times that of formal Newton – Raphson and about two thirdsthat of Gauss – Seidel method. Storage requirements are about60 percent of the formal Newton – Raphson method.
11/13/2013
3
KP = KQ = 1
Calculate [P/V]
Converged? KP=0
Solve for and update
KQ=1
KQ=0?
NO
YES
Out
put
Calculate [Q/V]
Converged ?
Solve forV andupdate V KQ=0
KP=1KP=0 ?
YES
NO
YES
NO
Y
NO
Flow Chart:
P-, Q- V equations to be converged simultaneously
Branch Outage Calculation:Equation to be solved in fast decoupled load flow are of the form
[R] = [Bo] [Eo]
For which a solution, [Eo] = [Bo]-1 [R] , can be obtained using thefactors of [Bo].For outage of element k-m
MbMBbBB boo
010100
0
1
0
1
0
0
1
k mk
m
b = line or transformer series admittance.
Using matrix inversion lema,
111
oo BMXCBB
to MBX
XMb
C
1
11
Where,
The solution vector [E1] to the outage problem is
oo
oo
EMXCE
RBMXCB
RBE11
111
quantityScalar11
;1
1
1
1
XMX
bb
XMb
CMB
Xt
o
M=
k
k
m
m
1
1
EE
ECE
EMXCEE
o
oo
oo
11/13/2013
4
The DC Power flow : Simplified further by dropping the Q-Vequation i.e., assuming V = 1 p.u.
BP
Useful for calculating MW flows through lines and transformers.
ik
kiik x
P
Extensively used in contingency analysis.
System Security:Involves practices designed to keep the system operating when componentsfail.
Mechanism: Maintaining proper spinning reserve Maintaining proper network flow margin.
Functions: System monitoring: Measuring critical power system quantities Estimation of system states.
Contingency analysis:To determine which contingencies cause limit violations and alsoseverity of such violation. Results of this study allow system to beoperated defensively.
Security constrained optimal power flow:Contingency analysis incorporated into power flow optimization
Why contingency analysis is needed:
250MW500MW
Unit 1 250 MW1200MW
700MW
Unit 2
Optimal dispatch
500MW
Unit 1 500MW
700MW
Unit 2
1200 MWPost contingency dispatch
200MW400MW
Unit 1 200 MW1200MW
800MW
Unit 2
Secure dispatch
400MW
Unit 1 400MW
800MW
Unit 2
1200 MW
Secure post contingency dispatch
Contingency Analysis Procedure:Start
Set system model to initialconditions
i = 1
Simulate outage of Generator i
Line flowor
Bus voltage limitviolated ?
last generatorconsidered
?
Display alarmmessage
i = i + 1
Yes
No
l = 1
Simulate outage of line l
line flowor
bus voltage limitviolated
?
Display alarmmessage
l = l + 1
last lineconsidered
?
No
No
end
Problem : Time Consuming
No
Yes
Yes
11/13/2013
5
Fast Solution: Two approaches1. Linear sensitivity factors : Uses simple multiplying
factors very fast andapproximate solutions.
2. Contingency ranking : Contingencies are rankedaccording to their severity, fullAC load flow performed for theselected cases.
Linear sensitivity factors:1. Generation shift factors.
2. Line outage distribution factors.
;i
lli P
fa
oii PP
fl = Change is flow through line lPi = Change is generation at bus i.
Pre-calculated set of a factors can be used to determine theChange in power flow on each line.
For outage of the generator at bus i,
ij
l
Generation shift factor of line ‘l’ due to a shift of generation atBus i,
DC Load flow equation:n m
lXl
i
minil
i
m
i
n
l
l
mn
ii
lli
XXx
dP
d
dP
d
x
xdP
d
dP
dfa
PX
BP
1
1
Generation Shift Factor:
i
mi
i
m
n
P
X 0
0
0
...............
.....X.......... ni
1
ilio
ll Paff ˆ
jljilio
ll PaPaff ˆ
If the generation outage is made up at bus j,
If all generations pick up in proportion to their rating
ikk
jji
ijijiljili
oll
P
PPaPaff
max
max
;ˆ
Post contingency flow through line l
11/13/2013
6
Line outage distribution factors:
oklk
oll
ok
llk
fdff
f
fd
.ˆ
k
l
i j
Outage of line k is simulatedas
Pi = + PijPj = - Pij
kp q
+Ppq
Ppq
- Ppql
r sPrs + drs - pq
Ppq
pqpqqqpprs
sqsprqrppq
pq
rspqrs
xXXXx
XXXXx
P
Pd
2
Contingency Selection:Severe contingencies are identified and ranked.Full AC load flow run for the selected cases.
ContingencySelection and
ranking
List
of p
ossi
ble
outa
ges
Shor
t lis
t of m
ost
seve
re c
ases
i = 1
Pick outage i from short list andremove the component from the power
flow model
Run AC power flow
Test for over load / voltage limitviolation
all cases done?
i = i + 1
end
Alar
m li
st
No
Yes
Contingency Ranking : According to Performance index (PI)Most severe contingency ranked first followed by lesssevere ones.
Active power contingency :n
element l
ll P
PWPI
2
Wl = weightage factor for element ‘l’Pl = power flow through element ‘l’_Pl = power rating of element ‘I’
11/13/2013
7
Reactive power / voltage contingencies:
2ll PxPI
xl = reactance of element l
This index can identity contingencies creating wide spreadvoltage problem. However, this index show little sensitivityto smaller local problems, where the voltage on one or a fewBuses has dropped only slightly.
Alternative approaches for the identification oflocal problems:
Local solution method:Voltage problems generally occur in the neighbourhoodof the dropped element. A modified Gauss – Seidelsolution algorithm is used by dividing the network into
layers. Voltage at buses near the outage are updated keepingthe voltage on the distant buses constant.
layer - 3
layer - 3layer - 2
layer - 1
outage line
layer =1end buses of the
outage line
Consider voltage at thebuses connected tolayer as constant
Determine voltage ofthe buses in the layer
bus voltages closeto the pre-contingencies
values?
Expand the layer byincluding the buses
directly connected tothe previous layer
Yesend
No
1P1Q method:One iteration of fast decoupled power flow.
B', B" matrices
model outage case
solve P - eqn.for , update
solve Q-v eqn. forv, update V
Calculate line flows and PI
Pick next outage case
Full o
utag
eca
se lis
t
PI lis
t(o
ne e
ntry
for
each
out
age
case
)
Questions ?
THANK YOU