PV Power Systems

Embed Size (px)

Citation preview

  • 7/21/2019 PV Power Systems

    1/72

    Photovoltaic Power Systems -2

    Grid connected PV

    Professor Chem Nayar

    Curtin University of Technology

    Perth , Western Australia

  • 7/21/2019 PV Power Systems

    2/72

    Grid Connect PV Systems

    Simplest of systems

    No storage

    Maximise PV to Grid

  • 7/21/2019 PV Power Systems

    3/72

    Grid Connect PV Systems

    Net Metering single meter runs in both directions

    Can also be with two meters : one to measure energy sold

    and the other energy bought

  • 7/21/2019 PV Power Systems

    4/72

    Components of a Grid Connected System

  • 7/21/2019 PV Power Systems

    5/72

    SPECIFICATION (NOMINAL VALUE)

    MODEL : PV-MF130EA2

    MAXIMUM SYSTEM VOLTAGE 600 V

    MAXIMUM POWER (Pmax) 130 W

    OPEN CIRCUIT VOLTAGE (Voc) 24.2 V

    SHORT CIRCUIT CURRENT (Isc) 7.39 A

    MAXIMUM POWER VOLTAGE (Vmp) 19.2 VMAXIMUM POWER CURRENT (Imp) 6.79 A

    PV PANELS

  • 7/21/2019 PV Power Systems

    6/72

    Sine wave output Low harmonic distortion (lessthan 4%)

    Input voltage range 160 350 VDC

    Output voltage range 187 253 VAC

    Single phase, can operate in

    frequency range 50 Hz +/- 6% Power factor > 0.98

    High efficiency (more than 90%)

    Maximum power point tracking

    Mains and solar generator are galvanically

    isolated

    Disconnect from grid line within 1 cycle in

    case of abnormal condition

    Computer interface for local and remote

    monitoring and data retrieval

  • 7/21/2019 PV Power Systems

    7/72

    Connecting Solar Panels

    Series connection to increase voltageParallel connection for increasing current

    Terminology Module

    String

    Sub array

    Array

  • 7/21/2019 PV Power Systems

    8/72

    PV Array Diagram

  • 7/21/2019 PV Power Systems

    9/72

    Array of sub arrays

  • 7/21/2019 PV Power Systems

    10/72

  • 7/21/2019 PV Power Systems

    11/72

    Blocking Diodes to prevent reverse

    current flow

    PCU

  • 7/21/2019 PV Power Systems

    12/72

    Cable Sizing

    Size for volt drop Maximum of 5% recommended

    Size for current rating

    Note that energy can typically feed from boththe array and the power conditioner

    Current rating of the cable is the rating of the

    protective device, not the PV output Consider cable exposed temperature when

    sizing for current rating

  • 7/21/2019 PV Power Systems

    13/72

    Protection Requirements

    Module protection Bypass diodesString protection

    Blocking diodes

    Fuses

    Array protection

    Overcurrent protection disconnection

  • 7/21/2019 PV Power Systems

    14/72

    Australian Requirement

    Breaker trip current to be between 1.25 x Isc

    2 x Isc

    Isc is for the section feeding through thetrip device

    Cable is then sized to the breaker

    Note some PV manufacturers recommendmaximum fuse ratings for the modules

  • 7/21/2019 PV Power Systems

    15/72

    Components

    Over current protection Must be DC voltage rated

    DC arcs are hard to extinguish

    Disconnection Distinguish between isolators for breaking

    down the array and load break isolators for

    disconnection under load Plugs and sockets cant be separated under

    load

  • 7/21/2019 PV Power Systems

    16/72

    Components cont.

    Blocking diodes Are not considered a fuse

    Cannot be relied upon to block reverse current

    Make sure they meet the voltage rating requirementsof the system

    They can get hot, keep them cool

    Australian requirements include breaker the arrayinto Extra Low Voltage (ELV) sections and being

    able to isolate the inverter for removal

  • 7/21/2019 PV Power Systems

    17/72

    Australian considerations

    Australian requirements include breaking the array into ELV sections for safe

    install and maintenance

    being able to isolate the inverter for saferemoval

  • 7/21/2019 PV Power Systems

    18/72

    GRID CONNECTED INVERTER SYSTEM

    Converts DC current from solar panels to AC current and feed to the

    grid . The system uses 50 Hz voltage waveform from grid line as a

    reference signal and feed current to the grid line. Before connecting,the inverter will check property of grid line according to followingconditions :-

    Voltage level

    Frequency range

    Phase of signal

    If all conditions are within specified range and synchronized withinternal generating frequency, the inverter will be connected to thegrid

    In case there is some abnormal condition with the grid, invertershould disconnect itself for both safety to human life and safety to

    the system.

  • 7/21/2019 PV Power Systems

    19/72

    PV/Grid Energy System Inverter

    Configurations

    Large Single Inverter Type (Central

    Inverter)

    Multiple Small Inverter Type (StringInverter)

    DC Bus (Multi-string Inverter)

    AC Module

  • 7/21/2019 PV Power Systems

    20/72

    PV/Grid Energy System

    Inverter Configurations

  • 7/21/2019 PV Power Systems

    21/72

    Central Inverter Type

    Series and Parallelconnection on DC side

    All PV panels

    connected to single DC

    bus

    Single Central Inverter

    Affected by partial

    shading of panels

    Only one protection

    system required

  • 7/21/2019 PV Power Systems

    22/72

    Kalbarri PV System

    in Western Australia (1995)

    10kW 10kW

    35kVA

    (75kVA)

    250Vdc

    6.6kV

    100kVA

    415Vac

    10kW10kW 10kW10kW

    35kVA

    (75kVA)

    250Vdc35kVA

    (75kVA)

    250Vdc

    6.6kV

    100kVA

    415Vac

    6.6kV

    100kVA

    415Vac

    6.6kV

    100kVA

    415Vac

  • 7/21/2019 PV Power Systems

    23/72

    String Inverter TypeOne inverter per

    string

    Panels grouped

    into smaller

    inverter ratedpower of Inverter (

    0.7-5kW)

    Not so badlyaffected by shading

    Not badly affected

    by inverter failure

  • 7/21/2019 PV Power Systems

    24/72

    @ 3.3kW

    Grid-Connected PV Inverter (String Type)

  • 7/21/2019 PV Power Systems

    25/72

    String Inverter Battery Backup

    Controller Back up Line

    AC Grid Line

    DC 48 V

    AC Line

    DC from PV

    160 to 240 V

    AC Line

    DC 48 V

  • 7/21/2019 PV Power Systems

    26/72

    Grid-Connected PV System

    with Back up Inverter

    Kang Som-Mao, Ratchaburi

    PV

    CONTROLLER -

    BATTERY batteries for S-218C

    INVERTER APOLLO G304 And S-218C

    75 Wp x 42 modules

  • 7/21/2019 PV Power Systems

    27/72

    DC Linked or Multistring type

    Each panel orgroup have a DC-DC step up

    converterHigh voltage DC

    link feeds

    transformer-lessconverter

  • 7/21/2019 PV Power Systems

    28/72

    DC Linked

    #1String HFTboostL

    PVC

    1S

    3S

    4S

    2S

    1D

    3D

    2D

    4D

    DCC

    HFTboostL

    PVC

    1

    S3

    S

    4S

    2S

    1D

    3D

    2D

    4D

    DCC

    HFTboostL

    PVC

    1S

    3S

    4S

    2S

    1D

    3D

    2D

    4D

    DCC

    gridi

    gridLGridGround

    3S

    4S

    1S

    2S

    #2String

    #3String

  • 7/21/2019 PV Power Systems

    29/72

    AC Modules

    One Inverter perpanel

    High volume/ lowcost

    Plug-and-play

  • 7/21/2019 PV Power Systems

    30/72

    Inverter characteristics

    Efficiency

    Response times

    Harmonic output

    Fault current contribution

    Synchronisation

    Frequency control

    Power factor

    DC injection

    Requirement Standard Details

  • 7/21/2019 PV Power Systems

    31/72

    General AS/NZS 3100 Electrical Safety Requirement

    Compatibility with AS 60038 A.C. Voltage and frequency ratings

    electrical installation

    Power flow direction N/A Power flow between energy source and grid may

    be in either direction

    Power factor AS 4777.2 Range between 0.8 leading to 0.95 lagging

    between all outputs from 20% to 100%

    of rated volt-amperes

    Harmonic Currents AS 4777.2

    Harmonic current shall not exceed the limits in

    Table 1.

    EMC

    Radio

    Communications

    Act

    Voltage fluctuation

    AS/NZS

    61000.3.3 Rated less that or equal to 16A per a phase

    and flicker

    AS/NZS

    61000.3.5 Rated more than 16A per a phase

    Impulse protection IEC 60255-5 Withstand a standard lightning impulse of 0.5J, 5kV

    with 1.2/50 waveform

    Transient voltage AS 4777.2 Voltage-duration curve derived from

    limits measurements taken at a.c. terminal shall

    Not exceed the limits listed in Table 2.

    Direct current N/A Single-phase inverter: the dc output current of the

    injection inverter at the a.c. terminals shall not

    exceed 0.5% of its rated output or 5mAwhich ever is greater

    Three-phase inverter: the dc output current of the

    inverter at the a.c. terminals measured between

    any two phases or between any phase and neutral

    shall not exceed 0.5% of its rated output or 5m

    which ever is greater

    Data logging and AS/NZS 60950 Any electronic data logging or communications

    communication equipment incorporated in the inverter requires to

    devices comply with the appropriated requirements

  • 7/21/2019 PV Power Systems

    32/72

    DC-AC ELECTRICAL CONVERSION

    EFFICIENCY

    Efficiency is the most important parameter for grid-connected PV

    generation Depends on whether galvanic insulation transformer is used

    between the AC on the grid side and the DC generated on the PVside or not.

    Transformer can be either 50 Hz LF transformers, or HF

    transformers. The presence or absence of LF or HF transformers in the inverters

    influences not only the size, weight, ease of installation and materialcosts, but also the earthing and safety measures to be adopted in thePV system, and the control of DC injection feed into the grid.

    Inverters with an LF transformer can achieve DC-AC efficiency of92%,while those with an HF transformer typically achieve amaximum efficiency of 94%.

  • 7/21/2019 PV Power Systems

    33/72

    European EfficiencyNormalized efficiency, E, and is

    valid for irradiance levels in centralEurope. It is defined as a function of

    the efficiency at defined percentage

    values for nominal AC power. This is

    shown in the following equation:

    E = 0.035% + 0.0610% +0.1320% + 0.130% + 0.4850% +

    0.2100%

  • 7/21/2019 PV Power Systems

    34/72

    94.292.690.892.3E

    94.292.890.093.3100

    95.093.490.993.850

    94.693.192.593.130

    94.292.392.091.020

    91.588.990.485.810

    86.785.184.877.55

    Transformerless

    LF (new

    technology)

    LF (old

    technology)HF

    Efficiency by inverter type (%)

    AC power

    (% of nominal)

    Experimental inverter efficiencies for different string inverters; values used are

    representative of state-of-the-art technology

    Experimental inverter efficiencies

  • 7/21/2019 PV Power Systems

    35/72

    MAXIMUM POWER POINT TRACKING EFFICIENCY

    The DC power input to an inverter depends on which

    point in the current-voltage (I-V) curve of the PV arrayit is working at. Ideally, the inverter should operate atthe maximum power point (MPP) of the PV array. TheMPP is variable throughout the day, mainly as a

    function of environmental conditions such asirradiance and temperature, but inverters directlyconnected to PV arrays have an MPP trackingalgorithm to maximize energy transfer. The MPP

    tracking efficiency, MPPT, can be defined as the ratioof the energy obtained by the inverter from a PVarray, to the energy obtained with ideal MPP trackingover a defined period of time.

    MAXIMUM POWER POINT

  • 7/21/2019 PV Power Systems

    36/72

    where PDC isthe DC input

    power to the

    inverter and PMis the power at

    MPP

    MAXIMUM POWER POINT

    TRACKING EFFICIENCY

  • 7/21/2019 PV Power Systems

    37/72

    Inverters for grid-connected PV

    systems must generate energy at adefined quality

    The standards (example:

    international Standard IEC 61000-

    3-2 ) above require a THD of

    5% for the harmonic spectra of the

    current waveform. nominal.

    2

    1 1

    1

    2

    1

    2

    1

    100

    100

    100%

    =

    =

    =

    h s

    sh

    s

    ss

    s

    dis

    I

    Ix

    I

    IIx

    I

    IxTHD

    Total Harmonic Distortion

    Table 1 - Harmonic current limits [2]

    Harmonic order number Limit for each individual harmonic

    based on percentage of fundamental

    2-9 4%

    10-15 2%

    16-21 1.50%

    22-33 0.60%

    Even harmonics 25% of equivalent odd harmonics

    Total harmonic distortion (to the 50th harmonic) 5%

    AS 4777

  • 7/21/2019 PV Power Systems

    38/72

    Power Factor

    Traditionally poor due to displacement power factor

    harmonics

    Present technology is very good

    Maintain close to unity without great difficulty

    Can regulate power factor or reactive powerfor voltage control or power factor correction

    applications

  • 7/21/2019 PV Power Systems

    39/72

    Example :Current THD and power

    factor vs AC power

  • 7/21/2019 PV Power Systems

    40/72

    DC Injection

    Is possible if an output transformer is notpresent

    Control systems can be added to preventexcessive injection

    Is regulated by standards

    Limits of 5 mA (0.025% of the rms outputcurrent for a 5 kW system, based on the IEC61000-3-2) or 0.5% (UL1741) are beingadopted in the UK and US respectively

  • 7/21/2019 PV Power Systems

    41/72

    Synchronisation

    Performed automatically

    Typically uses zero crossing detection on

    the voltage waveform

    Can be instantaneous on the next zero

    crossing

    If phase locked loops are used it could takea up to few seconds

  • 7/21/2019 PV Power Systems

    42/72

    Frequency Control

    Locked to the grid

    May have a bias to drift in the event of grid

    failure

    Lock range may be limited

    Germany 49.8Hz - 50.2Hz

    Australia 48Hz - 52Hz India 47Hz - 53Hz

  • 7/21/2019 PV Power Systems

    43/72

    Prevention of Islanding

    An island occurs when the invertercontinues to supply power to a portion of

    the grid that has become isolated from the

    rest of the systemThe power may be unstable during the

    island period

  • 7/21/2019 PV Power Systems

    44/72

    Anti islanding methods

    Inverters are required to have measures toprotect against this occurring

    Passive methods

    Under/Over voltage Under/Over Frequency

    Active Methods

    Frequency drift

    Impedance measurement

    Power Shifting

  • 7/21/2019 PV Power Systems

    45/72

    Earth Leakage Current

    In the US, the National Electrical Code, NEC,

    requires all PV installations with system

    voltages above 50 V DC to be earthed.

    Ground fault protection ('GFP') devices areused to measure the earth leakage current, in

    order to disconnect from the ground (that is,

    unearth the installation), in the case of fault.

    Stray leakage currents may be an issue in the

    sensitivity of this protection.

  • 7/21/2019 PV Power Systems

    46/72

    Fault currents

    Battery-less systems can only deliverwhat the energy source can deliver

    for PV this can be very little to a maximum

    of 1.2 times rated current wind is extremely variable

    If a battery is present the fault current

    contribution is limited by the inverter.

    Typically in the range of 100% to 200%

  • 7/21/2019 PV Power Systems

    47/72

    AC Power Output

    The losses in a PV system are due to: Inverter losses

    Dust/dirt in the modules

    Mismatch in modules

    Differences in ambient conditions from

    Standard Test Conditions (STC) 1000w/m2,AM 1.5 and 250C.

    Pac =Pdc,STCx efficiency

  • 7/21/2019 PV Power Systems

    48/72

    Mismatch in Arrays

  • 7/21/2019 PV Power Systems

    49/72

    Mismatch in Arrays

  • 7/21/2019 PV Power Systems

    50/72

    Mismatch in Arrays

  • 7/21/2019 PV Power Systems

    51/72

    1. Select the size of the system to be installed2. Select main equipment to be installed, calculate

    for matching of spec. of

    2.1 PV panel2.2 Grid connected inverter3. Examine location for PV mounting. There should

    be no obstruction of sunlight for whole day or at

    least 9.00 a.m. to 4.00 p.m.4. Consider for tilt angle of panels according to

    latitude of that location5. Select PV mounting structures.

    System design

  • 7/21/2019 PV Power Systems

    52/72

    6. Check ampere capacity of each string of inverter, select sizeof blocking diode to be 30 % larger than string short circuitcurrent with diode max voltage more than 2 times of maxsystem voltage.

    8. Select proper wire size so voltage drop for DC side is lessthan 3%8.1 Select wire size between each string to the combiner box

    to enable less than 1% voltage drop8.2 Select wire size between the combiner box to control

    box / inverter to enable less than 2% voltage drop9. Select proper wire size so voltage drop for AC side is less

    than 3%10. Select size of disconnect switch both DC and AC side to

    proper rating

    System design

    Case Study : A PV grid connected system in

  • 7/21/2019 PV Power Systems

    53/72

    1. Select size of system to be around 3 kWp2. Select main equipments as

    2.1 PV panel - Mitsubishi model PV-MF130EA2- 130 Wp / panel- 2 strings with 12 panels in each string- Isc / string = 7.39 amp.- Total PV power = 130 x 24 = 3,120 Wp

    - V max = Voc = 24.2 x 12 = 290.4 Vdc- Oper. volt. at max. power = 19.2 x 12 = 230.4 Vdc- Max DC current = Isc x 2 = 7.39 A x 2 = 14.78 Amp

    2.2 Grid connected inverter - Leonics G-303M- 2.7 kW output- Max DC voltage = 350 Vdc- Nominal Operating PV voltage = 230 Vdc

    3. Location for PV mounting is on the roof deck with no obstruction ofsunlight for whole day

    4. Select hot dip galvanized steel for PV mounting with stainless steelnuts & bolts

    5. Tilt angle of panels is set to 14 deg. facing south as Bangkok locates atlatitude 13.73 deg. North

    Case Study : A PV grid connected system in

    Bangkok

  • 7/21/2019 PV Power Systems

    54/72

    6. Plan to install control box and inverter in training room , 3 rd floor.

    7. Selection of blocking diode7.1 Min. device rating (I) = Isc x 1.3

    = 7.39 x 1.3 = 9.61 A

    7.2 Min. device rating (V) = Voc x 2

    = 290.4 x 2 = 580.8 V

    Then select blocking diode to be 10 ampere 600 V. for each string.

    8. Measure cable length of the system

    8.1 Cable length between each string to the combiner box

    = 10 meters

    Select wire for each string to be 4 sq.mm. to get voltage drop < 1%

    Voltage drop in each string = 11,650 x 10 x 7.39 = 0.86 V

    Percentage of volt. Drop = 0.86 / 205 = 0.42 %

    Case Study : A PV grid connected system in Bangkok

    Case Study : A PV grid connected system in Bangkok

  • 7/21/2019 PV Power Systems

    55/72

    8.2 Cable length between combiner box to control box / inverter is 35 m.Select wire size to be 10 sq.mm. to get voltage drop < 2%

    Voltage drop = 3,903 x 35 x 7.39 x 2 = 2.02 V

    Percentage of volt. Drop = 2.02 / 205 = 0.99 %

    9. Cable length between Control Box / Inverter to load panel is 12 meters

    Select wire size to be 2.5 sq.mm. to get voltage drop < 3%

    Voltage drop = 15,695 x 12 x (2,700/238)

    = 2.14 V

    Percentage of volt. Drop = 2.14 / 238 = 0.90 %

    10. Max DC current = 7.39 x 2 = 14.78 A

    Max AC current = 2,700 / 232 = 11.64 A

    Select both DC and AC breaker to be 20 A

  • 7/21/2019 PV Power Systems

    56/72

  • 7/21/2019 PV Power Systems

    57/72

    Calculate annual energy output

    Use data source and get annual daily average energy

    available Adjust down for losses

    Inverter 7%

    Temperature 15%

    Cable 3% Dirt 2%

    Orientation 1%

    Total about 25%-30%

    Multiply by the size of the array to get the electrical kWhroutput OR

    Use a modelling package

  • 7/21/2019 PV Power Systems

    58/72

    Verify

    Does it fit in the areaDoes it meet budget

    Does it produce required kWhr

    Is the CO2 offset met

    Check it works

    Re-size if necessary

  • 7/21/2019 PV Power Systems

    59/72

    System Acceptance Test1. Sum total module ratings at STC (Standard Test Condition) : Watts STC

    2. Estimate inverter AC output to be 70% of Watts STC : Watts AC-estimated

    3. Measure real AC output and irradiation, then define

    Watts AC-corrected = Real AC output / irradiation x 1000

    4. Compare that Watts AC-corrected is more than Watts AC-estimated

    Result from the installation

    Generating power and irradiation is measured on Mar 26, 2004 at 11.25 p.m.

    Watts STC = 130 x 24 = 3,120 Wp

    Watts AC-estimated = 3,120 x 0.7 = 2,184 Watts

    Watts AC-corrected = 2,010 / 870 x 1000 = 2,310 Watts

    4. Watts AC-corrected (2,310) > Watts AC-estimated (2,184)

    *** PASS SYSTEM ACCEPTANCE TEST ***

  • 7/21/2019 PV Power Systems

    60/72

    Generating Power VS Time for 3.12 kWp

    Grid Connected inverter at Leo Electronics Co., Ltd. (Apr 1, 2004)

    0

    500

    1000

    1500

    2000

    2500

    7 8 9 10 11 12 13 14 15 16 17 18

    Time

    Generating

    Power

  • 7/21/2019 PV Power Systems

    61/72

    Date Gen. Power Date Gen. Power Date Gen. Power

    1/4/2004 14.30 24/3/2004 13.73 16/3/2004 12.85

    31/3/2004 12.79 23/3/2004 12.12 15/3/2004 10.88

    30/3/2004 12.13 22/3/2004 10.94 14/3/2004 12.53

    29/3/2004 12.33 21/3/2004 8.02 13/3/2004 12.02

    28/3/2004 13.49 20/3/2004 7.22 12/3/2004 11.67

    27/3/2004 13.51 19/3/2004 8.57 11/3/2004 13.21

    26/3/2004 13.14 18/3/2004 11.87 10/3/2004 11.34

    25/3/2004 13.01 17/3/2004 14.68 9/3/2004 10.15

    Max. Generating Power/day 14.68

    kWh/day

    Min. Generating Power/day 7.22 kWh/day

    Average Generating Power/day 11.94 kWh/day

    Power generating from Grid Connected System

  • 7/21/2019 PV Power Systems

    62/72

    Orientation terminology

  • 7/21/2019 PV Power Systems

    63/72

    Tracking Array

    The PV array may either be fixed, sun-tracking

    with one axis of rotation, or sun-tracking withtwo axes of rotation.

    Generally fixed arrays are used thoughsignificant increase in energy yield is possiblewith single axis tracking with an additional smallgain using duel axis tracking

    Trackers

    add cost but offset by PV savings require some maintenance

    Very good for water pumping applications

    Tracking Relative Energy

  • 7/21/2019 PV Power Systems

    64/72

    g gy

    Production

    0%

    20%

    40%

    60%

    80%

    100%

    120%

    140%

    160%

    Albany Geraldton Halls Creek

    Fixed north facing

    at latitude angle

    N-S Axis tracker -horizontal

    N-S Axis tracker -

    Fixed at latitude

    angleDual Axis

    34o57" 28o48" 18o14"

  • 7/21/2019 PV Power Systems

    65/72

    Energy from Power of the Sun

    0

    200

    400

    600

    800

    1000

    1200

    0:00

    2:00

    4:00

    6:00

    8:00

    10:00

    12:00

    14:00

    16:00

    18:00

    20:00

    22:00

    Time

    Powe

    rEnergy =Power x Time

    Area = 7500W.hr

    = Area under curve

  • 7/21/2019 PV Power Systems

    66/72

    Peak Sun Hours

    0

    200

    400

    600

    800

    1000

    1200

    0:00

    2:00

    4:00

    6:00

    8:00

    10:00

    12:00

    14:00

    16:00

    18:00

    20:00

    22:00

    Equivalent Time at 1 peak sun (1000W/m2)

    7.5 hours

    Area = 7500W.hr1000W/m2

    Solar Irradiance

  • 7/21/2019 PV Power Systems

    67/72

    0

    250

    500

    750

    1000

    0:00 6:00 12:00 18:00 0:00

    Time

    IrradianceS(W/sqm)

    18/05/98

    A typical sunny day in Perth

    0

    250

    500

    750

    1000

    0:00 6:00 12:00 18:00 0:00

    Time

    IrradianceS(W

    /sqm)

    15/05/98

    A Typical cloudy day in Perth

    Solar Irradiance

    Average Daily Solar Radiation Perth

  • 7/21/2019 PV Power Systems

    68/72

    Average Daily Solar Radiation, Perth

    Calculate annual energy output

  • 7/21/2019 PV Power Systems

    69/72

    Calculate annual energy output

    Use data source and get annual daily average energy

    available Adjust down for losses

    Inverter 7%

    Temperature 15%

    Cable 3% Dirt 2%

    Orientation 1%

    Total about 25%-30%

    Multiply by the size of the array to get the electrical kWhroutput OR

    Use a modelling package

    Verify

  • 7/21/2019 PV Power Systems

    70/72

    Verify

    Does it fit in the area

    Does it meet budget

    Does it produce required kWhr

    Is the CO2 offset met

    Check it works

    Re-size if necessary

    Suboptimal orientation the

  • 7/21/2019 PV Power Systems

    71/72

    impact

    Common in building integrated

    applications

    Roof may be wrong orientation

    Facade may be vertical

    Tilt angle may be dictated by aesthetics

  • 7/21/2019 PV Power Systems

    72/72