Title: Create a Submittal Module : KOHLER Power Systems Course : KOHLER QuickPack Kohler Learning For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit: Version: Prelim Last Modified: 7/27/2007 11:54:00 AM Work Instruction Page 1 / 6 Work Instruction Create a Submittal Purpose Use this procedure to create a submittal. Trigger Perform this procedure when you need to create a submittal. Prerequisites You are logged in to QuickPack and are open to the home page. You have a quote ready for submittal. Transaction Code Helpful Hints None

~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Embed Size (px)

Citation preview

Page 1: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 1 / 6

Work Instruction

Create a Submittal

Purpose

Use this procedure to create a submittal.

Trigger

Perform this procedure when you need to create a submittal.

Prerequisites

• You are logged in to QuickPack and are open to the home page. • You have a quote ready for submittal.

Transaction Code

Helpful Hints

None

Page 2: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 2 / 6

Procedure

QuickPack Home Page

1. Click the tab.

Page 3: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 3 / 6

Commerce Management

2. Click the link of the job for which you are submitting. Example:

Page 4: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 4 / 6

Document

3. Click the tab.

4. Click to preview the submittal.

Depending on the complexity of the job being submitted, this process may take a few minutes.

Page 5: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 5 / 6

Submittal Package

The system displays the submittal. From this screen you may save or print your submittal.

Result

You have completed this transaction. You have created a submittal.

Comments

None

Page 6: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Title: Create a Submittal Module : KOHLER Power Systems

Course : KOHLER QuickPack Kohler Learning

For Kohler Internal Training Purposes Only File name: ~QUICKPACK_CREATE A SUBMITTAL Unit:

Version: Prelim Last Modified: 7/27/2007 11:54:00 AM

Work InstructionPage 6 / 6

This page is intentionally left blank.

Page 7: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Submittal Package To: Kohler Co.

Michelle

444 Highland Drive

Kohler, 53044

P: 920-565-3381 F: 920-459-1416

[email protected]

Date: Job Name:

Proposal:

QuickPack Submittal Sample

Sample Submittal

Contact Name - Kohler Co.,

We are pleased to offer the following proposal for your consideration.

Thank you, Karen, Kohler Co.

Page 1

Page 8: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

TABLE OF CONTENTS Section Literature PageQuote 1Model 30REOZJB Spec Sheets 7Model MODELK1 Spec Sheets 22Dimensional Drawings 29

ADV6623 30adv6708 33

Wiring Schematic Diagrams 34ADV6619 35ADV6789 36ADV7016 38GM19432 40GM25000 42GM39349 44gm46273 46gm46297 48

Warranty 49tp5374 50tp5373 51

Prototype Test Certifications 52g1856.pdf 53

Misc 54ADV5795 55ADV5849 56244578 62ADV5971 63233967 64

Pre-Startup Checklist 66PreStartUpCheckList 67

Page 2

Page 9: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Job Name: QuickPack Submittal SampleProposal: Sample Submittal

"DID YOU KNOW" Kohler Co. HAS RENTAL GENERATORS To: Kohler Co.

Michelle Manthey

444 Highland Drive

Kohler, 53044

P: 920-565-3381

F: 920-459-1416

[email protected]

From:

Kohler Co.

Karen

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

[email protected]

Contact Name - Kohler Co.,

We are pleased to offer the following offer for your consideration.Thank you, Karen, Kohler Co.

Page 1

Page 10: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Job Name: QuickPack Submittal SampleProposal: Sample Submittal

GENERATOR SET

Model: 30REOZJBThis generator set equipped with a alternatoroperating at volts is rated for kW/ kVA.Output amperage:

Standard Features: Alternator Features:

• Kohler Co. provides one-source responsibility forthe generating system and accessories.

• The generator set and its components areprototype-tested, factory-built, and production-tested.

• The 60 Hz generator set offers a UL 2200 listing.• The generator set accepts rated load in one step.• The generator set complies with ISO 8528-5, Class

G2, requirements for transient performance in allgenerator set configurations. Select the Decision-Maker™ 550 controller for improved voltageregulation and ISO 8528-5, Class G3, compliance.

• A one-year limited warranty covers all systems andcomponents. Two-, five-, and ten-year extendedwarranties are also available.

• Kohler's unique Fast-Response™ II excitation system deliversexcellent voltage response and short circuit capability using apermanent magnet (PM)-excited alternator.

• The brushless, rotating-field alternator has broad rangereconnectability.

Other Features:

• Controllers are available for all applications. Seecontroller features inside.

• The low coolant level shutdown preventsoverheating (standard on radiator models only).

• Integral vibration isolation eliminates the need forunder-unit vibration spring isolators.

Configuration Qty Description 1 Voltage,60Hz,277/480V,Wye,3Ph,4W,0.8PF 1 Nameplate Rating, Standby 130 Degree 1 30REOZJB,12V,60Hz,Tier II 1 Alternator, 4P5 1 Covers, 4P J-Box (No LCB) 1 Cooling, Unit Mounted Radiator 1 Controller, 16 Light,Dec3+,12V 1 Control & Harness, JD3029 1 Air Intake, Standard Duty 1 Skid, 34" 1 Battery,1/12V,650CCA,Wet 1 Battery Charger,Float w/Alarms,12V-10A 1 Warranty, 1 Year Standby

Page 2

Page 11: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Job Name: QuickPack Submittal SampleProposal: Sample Submittal

Model: MODELK1

3 Pole, 4 Wire, Solid Neutral pole, 150 Amps amp,Kohler automatic transfer switch, ModelMODELK1, rated 480, 60Hz volts, complete withall standard equipment and housed in aNEMA Type 1 enclosure.

MPAC® 1500 Controller

Standard Features• Microprocessor-based controller• Environmentally sealed user interface• LCD display, 4 lines x 20 characters, backlit• Dynamic function keypad with tactile feedback pushbuttons allows complete programming

and viewing capability at the door• LED indicators: Source available, transfer switch position, service required (fault), and “not

in auto"• Broadrange voltage sensing (208--600 VAC) on all phases• Phase-to-phase sensing and monitoring with 0.5% accuracy on both sources• Frequency sensing with 0.5% accuracy on both sources• Anti-single phasing protection• Phase rotation sensing for three-phase systems• Real-time clock with battery backup and automatic adjust for daylight saving time and leap

year• Time-stamped event log• Fail-safe transfer for loaded test and exercise functions• DIP switches: password disable and maintenance• Modbus® RTU and Modbus® TCP/IP protocols• (Modbus® register map available)• RJ45 connector for 10/100 ethernet connection• USB port with read/write compatibility• Isolated RS-485 ports• One-year limited warranty

Page 3

Page 12: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Job Name: QuickPack Submittal SampleProposal: Sample Submittal

Qty Description1 KBP-DMTA-0150S

1 Warranty, 1 Year Standard 1 CSA Certification, Bypass

Page 4

Page 13: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Job Name: QuickPack Submittal SampleProposal: Sample Submittal

MISCELLANEOUS

OFFER ACCEPTANCE

I hereby authorize Kohler Co. to use this form as a bona fide purchase order of the equipment shown on Proposal Number: Sample Submittal, which clearly establishes definite price, and specifications of material ordered. The person signing is doing so according to the terms and conditions. Proposed by: Accepted by: Company:

Kohler Co. Company: _______________________________

Print Name:

Karen Print Name: _______________________________

Title:

Gordon Title: _______________________________

Signature:

_______________________________ Signature: _______________________________

Date Date: _______________________________

Page 5

Page 14: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Spec Sheets

Page 6

Page 15: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

30REOZJB

Fuel

Standard Features• Kohler Co. provides one-source responsibility for the

generating system and accessories.• The generator set and its components are prototype-

tested, factory-built, and production-tested.• The 60 Hz generator set offers a UL 2200 listing.• The generator set accepts rated load in one step.• The generator set complies with ISO 8528-5, Class G2,

requirements for transient performance in all generatorset configurations. Select the Decision-Maker™ 550controller for improved voltage regulation and ISO8528-5, Class G3, compliance.

• A one-year limited warranty covers all systems andcomponents. Two-, five-, and ten-year extendedwarranties are also available.

• Alternator Features:o Kohler's unique Fast-Response™ II excitation

system delivers excellent voltage response and shortcircuit capability using a permanent magnet (PM)-excited alternator.

o The brushless, rotating-field alternator has broadrange reconnectability.

• Other Features:o Controllers are available for all applications. See

controller features inside.o The low coolant level shutdown prevents overheating

(standard on radiator models only).o Integral vibration isolation eliminates the need for

under-unit vibration spring isolators.

Generator Set RatingsStandby130C

Standby RatingsAlternator Voltage Ph Hz kW/kVA Amps

4P5 277/480 3 60 34/43 51RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source. Thestandby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS5514, AS2789, and DIN 6271. PrimePower Ratings: Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity isavailable for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings,consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the right to change the design or specificationswithout notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 1.3% per 100 m (328 ft.) elevation above 2000 m (6560 ft.). Temperature: Derate 1.0%per 10°C (18°F) temperature above 40°C (104°F).

Page 7

Page 16: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Model: 30REOZJB, continued

Alternator Specifications

Specifications Alternator

Alternator manufacturer KohlerType Brushless,Permanent-MagnetLeads, quantity 12, ReconnectableVoltage regulator Solid State, Volts/HzInsulation NEMA MG1Insulation: Material Class HInsulation: Temperature Rise 130°C, StandbyBearing: quantity, type 1, SealedCoupling Flexible DiscAmortisseur windings FullVoltage regulation, no-load to full-load Permanentmagnet (PM) alternator

±2% Average

550 controller (with 0.5% drift due to temperaturevariation)

3-Phase Sensing, ±0.25%

One-Step Load Acceptance 100% of RatingUnbalanced load capability 100% of Rated Standby Current

• The brushless, rotating-field alternator has broad range reconnectability.• NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.• Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.• Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.• Self-ventilated and dripproof construction.• Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.• Superior voltage waveform from a two-thirds pitch stator and skewed rotor.• Fast-Response™ II brushless alternator with brushless exciter for excellent load response.

Page 8

Page 17: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Model: 30REOZJB, continued

Engine

Engine Specifications

Engine Manufacturer John DeereEngine Model 3029TF270Engine: type 4-Cycle, TurbochargedCylinder arrangement 3 InlineDisplacement, L (cu. in.) 2.9 (177)Bore and stroke, mm (in.) 106 x 110 (4.17 x 4.33)Compression ratio 17.2:1Piston speed, m/min. (ft./min.) 396 (1299)Main bearings: quantity, type 4, Replaceable InsertRated rpm 1800Max. power at rated rpm, kWm (BHP) 48 (64)Cylinder head material Cast IronCrankshaft material Forged SteelValve (exhaust) material Intake Chromium-Silicon SteelValve (exhaust) material Exhaust Stainless SteelGovernor: type, make/model Mechanical, Stanadyne/DB2Frequency regulation, no-load to-full load 3-5%Frequency regulation, steady state ±0.33% (mech.governor)Frequency regulation, steady state ±0.25% (elect.isoch.gov.)Frequency FixedAir cleaner type, all models Dry

Exhaust

Exhaust System

Exhaust Manifold Type DryExhaust flow at rated kW, EPA certified, m³/min.(cfm)

9.1 (320)

Exhaust flow at rated kW, non-emissions certified,m³/min. (cfm)

8.4 (295)

Exhaust temperature at rated kW, dry exhaust, non-emissions certified, °C ( °F)

474 (885)

Exhaust temperature at rated kW, dry exhaust, EPAcertified, °C ( °F)

498 (928)

Maximum allowable back pressure, kPa (in. Hg) 7.5 (2.2)Exh. outlet size at eng. hookup, mm (in.) 63.5 (2.5)

Engine Electrical

Engine Electrical System

Battery charging alternator 12 VoltBattery charging alternator: Ground (negative/positive) Negative Volts (DC) 12 Ampere rating 55Starter motor rated voltage (DC) 12Battery, recommended cold cranking amps (CCA): Qty., CCA rating each One, 640Battery voltage (DC) 12

Page 9

Page 18: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Model: 30REOZJB, continued

Fuel

Fuel System

Fuel supply line, min. ID, mm (in.) 11.0 (0.44)Fuel return line, min. ID, mm (in.) 6.0 (0.25)Max. lift, fuel pump: type, m (ft.) Engine-Driven, 1.8 (6.0)Max. fuel flow, Lph (gph) 112 (29.6)Fuel prime pump ManualFuel Filter Secondary 8 Microns @ 98% EfficiencyFuel Filter Water Separator YesRecommended fuel #2 Diesel

Lubrication

Lubrication System

Type Full PressureOil pan capacity, L (qt.) 7.6 (8.0)Oil pan capacity with filter, L (qt.) 8.5 (9.0)Oil filter: quantity, type 1, CartridgeOil cooler Water-Cooled

Cooling

Radiator System

Ambient temperature, °C (°F) 50 (122)Engine jacket water capacity, L (gal.) 5.7 (1.5)Radiator system capacity, including engine, L (gal.) 13.6 (4.6)Engine jacket water flow, Lpm (gpm) 110 (29)Heat rejected to cooling water at rated kW, kW, dryexhaust, certified, Kw Btu/min.

26.9 (1530)

Water pump type CentrifugalFan diameter, including blades, mm (in.) 483 (19)Fan, kWm (HP) 2.1 (2.8)Max. restriction of cooling air, intake and dischargeside of radiator, kPA (in. H20)

0.125 (0.5)

Remote Radiator System

Exhaust manifold type Dry*Connection sizes: Water inlet, mm (in.) 48 (1.88)Connection sizes: Water outlet, ID hose, mm (in.) 38 (1.50)Static head allowable above engine, kPa (ft. H2O) 63 (21)Contact your local distributor for cooling systemoptions and specifications based on your specificapplication.

Contact your local distributor for cooling system options and specificationsbased on your specific application.

Page 10

Page 19: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Model: 30REOZJB, continued

Operation Requirements

Air Requirements

Radiator-cooled cooling air, m³/min. (scfm) * 91 (3200)Cooling air required for generator set whenequipped with city water cooling or remote radiator,based on 14 °C (25°F) rise, m³/min. rise andambient temp. of 29°C (85°F) m³/min. (cfm)

54 (1900)

Combustion air, m³/min. (cfm) 3.5 (123)Heat rejected to ambient air: Engine, kW (Btu/min.) 8.8 (500)Heat rejected to ambient air: Alternator, kW (Btu/min.)

5.6 (320)

*Air density = 1.20 kg/m³ (0.075 lbm/ft³)

Dimensions and Weights

Overall Size, L x W x H, mm (in.): Wide Skid 2000 x 1040 x 1274 (78.74 x 40.94 x 50.15)Overall Size, L x W x H, mm (in.): Narrow Skid 2000 x 864 x 1274 (78.74 x 34.02 x 50.15)Weight (radiator model), wet, kg (lb.): 708 (1560)

NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributorfor more detailed information.

Page 11

Page 20: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Industrial Generator Set Accessories

Generator Set Controller

Decision-Maker�3+ Controller

General Description and Function

The generator set controller provides system control,monitoring, and diagnostics for optimum performance.

The generator set controller provides both analog ACmeters and engine gauges and 16-light annunciation ofshutdowns, warnings, and status events.

Standard Features

� Supports Modbus� RTU (Remote Terminal Unit)communication protocol via RS-485 networks.

� Supports CANbus J1939 communication protocol forECM engines

� Contains microcomputer-based logic with a ROM(read-only memory)-based control algorithm.

� Features upgradeable software for new systemfunctionality.

� Provides overspeed protection, cooldown mode, and aselectable crank mode.

� Provides audio and visual alarms.

� Features analog meters and engine gauges.

� Meets the National Fire Protection Associationrequirements of NFPA 99 and NFPA 110 with additionalaccessories. NFPA 110, Level 1 requirements typicallyapply to health care facilities; NFPA 110, Level 2requirements apply to less-critical applications.

� Uses conformal coated circuit boards for environmentaldurability.

Modbus� is a registered trademark of Schneider Electric.

G6-30 9/05j

Page 21: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

G6-30 9/05j

Decision-Maker™ 3+, 16-Light Controller

Controller Features

General Specifications

� Power source with circuit protection: 12- or 24-volt DC

� Power draw: 220 milliamps in system ready mode(or 200 milliamps without panel lamps)

� Humidity range: 5% to 95% noncondensing

� Operating temperature range:--40°C to +70°C (--40°F to +158°F)

� Storage temperature range:--40°C to +85°C (--40°F to +185°F)

� Standards:

� NFPA 99

� NFPA 110

� UL 508

� Dimensions—W x H x D,461 x 247 x 297 mm (18.15 x 9.71 x 11.68 in.)

Hardware Features

� AC interlock to prevent starter reengagement with enginerunning

� Battery (DC) circuits are fuse protected

� Controller mounts locally or remotely up to a distance of 12 m(40 ft. ) and viewed from one of four positions

� LEDs for visual annunciation

� Gauges and meters for system data

Communication Features

� Supports Modbus� RTU (Remote Terminal Unit) via RS-485(Comm. module GM32644-KA1 or GM32644-KP1 required)

� Supports Modbus� TCP (Transmission Control Protocol) viaEthernet (Converter GM41143-KP1 required)

� Supports CANbus J1939 communication protocol

Modbus� is a registered trademark of Schneider Electric.

NFPA Requirements

� In order to meet NFPA 110, Level 1 requirements thegenerator set controller must monitor and display specificengine/generator safety indications and shutdowns

� Engine functions:

� Overcrank shutdown

� High engine temperature shutdown

� High engine temperature warning *

� Low water (engine) temperature warning *

� Low oil pressure warning *

� Low oil pressure shutdown

� Overspeed shutdown

� Low fuel (level or pressure) warning *

� Low coolant level (auxiliary fault) shutdown

� High battery voltage warning *

� Low battery voltage warning *

� Air damper indicator

� General functions:

� Battery charger warning *

� Master switch not-in-auto

� Lamp test

� Audible alarm silence

* Requires optional input sensors on some generator set models

Page 22: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

G6-30 9/05j

Standard Features

� Sixteen LED indicating lights for status, warnings, andshutdowns

� Status indicators:

� Air damper (red) (if equipped)*

� Master switch not-in-auto (red)

� System ready (green)

� Warning indicators:

� Auxiliary (multiple function)(red)

� Battery charger (red)*

� Fuel, low—level or pressure (red)*

� Pressure, low oil (yellow)*

� Temperature, low water (engine) (red)*

� Temperature, high engine (yellow)*

� Voltage, high battery (yellow)*

� Voltage, low battery (red)*

� Shutdown indicators:

� Auxiliary (multiple function)(red)

� Emergency stop (red)*

� Low fuel (utilizes auxiliary indicator)(red); 125RZG modelonly

� Level, low coolant (utilizes auxiliary indicator) (availablewith radiator-mounted generator set models only)

� Overcrank (red)

� Overspeed (red)

� Temperature, high engine (red)

� Pressure, low oil (red)

� Underfrequency (utilizes auxiliary indicator)(red)

� Panel illumination lamps (2)

� Analog gauges, 51 mm (2 in.):

� Pressure gauge, oil

� Temperature gauge, engine cooling system

� Voltmeter, DC battery

� Analog meters, 89 mm (3.5 in.):

� AC ammeter, 2% of full-scale accuracy

� AC voltmeter, 2% of full-scale accuracy

� Frequency meter, 0.5% of full-scale accuracy

� Running time meter

� Switches and standard features:

� Horn, alarm (with silencing switch)

� Mode, prime power via jumper selection

� Potentiometer, generator output voltage-adjusting(front panel mounted, ±5% of nominal voltage)(350--2000 kW models have adjustment on voltageregulator in junction box)

� Shutdown, overvoltage protection

� Switch, latch-type emergency stop (standard on most200--2000 kW generator set models)

� Switch, lamp test

� Switch, meter range selector

� Switch, run, off/reset, auto (engine start) generator setmaster

� Timer, engine cooldown, (5-minute fixed)

� Eight DIP switches for control and communication:

� Cooldown disable

� Crank mode select for continuous or cyclic cranking.The cranking provides up to 30 seconds of continuouscranking or 75 seconds of cyclic cranking (crank15 seconds, rest 15 seconds, crank 15 seconds, etc.).The crank disconnect speed is 750 rpm (25 Hz).

� Engine communication setting (2)

� Modbus� addresses (bit 0, bit 1, bit 2)

� Overspeed protection selection of 60 Hz for 50 Hz modelsor 70 Hz for 60 Hz models

� Terminal strips:

� Terminal strip connections for 2-wire remote start

� Terminal strip connections for 2-wire (series connection)remote emergency stop

� Terminal strip connections for remote annunciator

� Terminal strip connections for remote dry contact kit

� Terminal strip connections for prime power feature(prevents battery drain when not in use and no batterycharger connected)

� LEDs on circuit board for troubleshooting diagnosis

� Crank fault

� Emergency stop

� Overvoltage fault

� Run operation

* Requires optional kit or user-provided device to enable function and lamp indication.

Page 23: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

© 1995, 1996, 1997, 1999, 2000, 2002, 2003, 2005 by Kohler Co. All rights reserved.

DISTRIBUTED BY:

G6-30 9/05j

Selected Decision-Maker�3+ Accessories

� Common Failure Relay remotely signals auxiliaryfault, emergency stop, high engine temperature, lowoil pressure, overcrank, and overspeed via one single-pole, double-throw relay with 10 amp at 120 VAC,10 amp at 28 VDC contacts.

� Controller Cable, 12 m (40 ft.), enables remotemounting of the controller.

� Controller Connection Kit provides a cableconnecting the controller to a terminal strip in thejunction box. Specify the controller connection kitfor junction box remote device connections.

� Dry Contact Kits interface between the controllersignals and customer-supplied accessories providingcontact closure to activate warning devices such aslamps or horns. Kits are available in either one or tensingle-pole, double-throw relays with 3 amp at 250 VACcontacts. A kit with twenty single-pole, double- throwrelays with 3 amp at 250 VAC contacts is available on450--2000 kW models.

� FASTCHECK� hand-held diagnostic fault detectoractivates controller circuits without operating engine/generator. Helps service or maintenance personnelquickly identify faults in controller and engine circuits.

� 10 Amp Float/Equalize Battery Charger with AlarmFeature warns controller of battery charger fault, highbattery voltage, and low battery voltage.

� 6 Amp Float/Equalize Battery Charger has automatic3-stage charging with indicator LEDs. Durable pottedassembly for full waterproofing and shockproofing.UL 1236 listed.

� Controller-Mounted Emergency Stop Switch shutsdown generator set immediately in emergency situations.Use the generator set master switch for normal shutdowns.Standard on most 200--2000 kW generator set models(see respective generator set specification sheet for details).

� Remote Emergency Stop Panel immediately shuts thegenerator set down from a remote station.

� Prealarms warn of low water (engine) temperature,approaching low oil pressure, and approaching high enginetemperature. Kits for gas-fueled models include a low fuelpressure switch.

� Remote Audiovisual Panel warns the operator of faultshutdowns and prealarm conditions. Common fault lampand horn with silence switch.

� Remote Serial Annunciator Panel enables the operatorto monitor the status of the generator from a remotelocation. May be required for NFPA 99 and NFPA 110installations. Uses Modbus� RTU (Remote Terminal Unit),an industry standard open communication protocol.

� Communication Module GM32644-KA1 or GM32644-KP1

is required when using the remote serial annunciator (RSA)

and/or Modbus�/Ethernet communications.

� Remote Annunciator Panel enables the operator tomonitor the status of the generator from a remote location.May be required for NFPA 99 and NFPA 110 installations.

� Run Relay provides a three-pole, double-throw relay with10 amp at 250 VAC contacts for indicating that the generatorset is running or shut down.

� Modbus�/Ethernet Converter GM41143-KP2 for network

communications.

Modbus� is a registered trademark of Schneider Electric.

Kohler Power SystemsAsia Pacific Headquarters7 Jurong Pier RoadSingapore 619159Phone (65) 6264-6422, Fax (65) 6264-6455

Availability is subject to change without notice. Kohler Co. reserves theright to change the designor specificationswithout noticeandwithout anyobligation or liability whatsoever. Contact your local Kohler� generatorset distributor for availability.

KOHLER CO., Kohler, Wisconsin 53044 USAPhone 920-565-3381, Fax 920-459-1646For the nearest sales and service outlet in theUS and Canada, phone 1-800-544-2444KohlerPowerSystems.com

Page 24: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Industrial Geneator Set Accessories

Float/EqualizeBattery Charger

Standard Features• Kohler automatic battery chargers feature two

charging modes to keep lead-acid and nickel-cadmium batteries fully charged withoutovercharging. The battery charger automatic float-to-equalize operation maintains battery voltage with nomanual intervention.

• Temperature compensation feature preventsovercharging or undercharging battery at high/lowambient temperatures.

• Current-limiting circuitry prevents battery charger fromoverload at low battery voltage and during a shortcircuit. The ten amp DC current limit allows the batterycharger to remain connected to the battery duringengine cranking.

• Battery charger complies with NFPA 110 coderequirements when equipped with optional alarmcircuit board. Alarm board features low batteryvoltage, high battery voltage, and battery chargermalfunction alarm contacts.

Specifications

Installed Battery NFPA 110 Alarm Outputs Output Number of Cells

Voltage Amps Lead Acid Ni-Cd

PAD-292863 Yes 12 10 6 9

Input Voltage 120/240 VAC

Input Frequency 50/60 Hz

Line Regulation Across Input Voltage Range ±1%

Dimensions (L x W x D) 271 x 143 x 422 mm (10.67 x 5.63 x 16.63 in.)

Weight 11.8 kg (26 lb.)

Page 16

Page 25: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Float/Equalize Battery Charger, continued

Automatic Float to Equalize When the battery loses its charge, the battery chargeroperates in the High Rate Constant Current Mode until thebattery voltage rises to the preset equalize level.At thepreset equalize level, the battery charger switches to theconstant voltage Equalize Mode until the current requiredto maintain this voltage drops to 50% of the batterycharger's high rate current.The battery charger thenswitches to the lower constant voltage Float Mode whenthe battery nears full charge. The battery chargercontinues to operate in this mode until AC input powerdisconnects or the current required to maintain the batteryat the float voltage setting exceeds 6 amps.

Temperature Compensation The battery charger compensates for battery temperatureusing a negative temperature coefficient. The batterycharger provides temperature compensation of -2mv/°Cper cell over the ambient temperature range of -40°C upto 60°C. The temperature compensation automaticallyadjusts the float and equalize voltage settings to preventthe battery from overcharging at high ambienttemperatures and undercharging at low ambienttemperatures.

Page 17

Page 26: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Float/Equalize Battery Charger, continued

Standard Features

• Ammeter and voltmeter indicate battery charging rate with 5% full-scale accuracy. POWER ON lamp indicates batterycharger is operating.

• AC input and DC output fuses prevent battery charger damage from abnormal overload and short-circuit conditions.

• Operational temperature range is from 40°C (--40°F) to 60°C (140°F). Battery charger float equalize voltageautomatically adjust throughout the temperature range.

• Reverse polarity protection circuitry prevents battery charger from energizing if improperly connected.

• Internal terminal blocks for AC input and DC output/ sensing lead connections.

• DC voltage regulation of ±1% from no load to full load and AC input line voltage variations of ±10%.

• UL listed/CSA certified.

• Wall-mount, slotted enclosure with knockouts for customer conduit installation. Reconnection blocks allowoperation at 120 or 240 volts AC, single phase, 50 or 60 hertz.

• Battery charger circuitry protected from AC line and DC load voltage spikes and transients.

• Terminal block for remote battery sensing leads.

• Automatic float-to-equalize operation with individual potentiometer adjustments. Charge up to 12 lead-acid or 18nickel-cadmium battery cells.

• No adjustments are necessary for lead-acid or nickel-cadmium batteries.

• Oversized transformer and SCR heatsink allow constant current charging at 10 amps up to the equalize voltagesetting for fastest battery charging. Note: The battery charger will discharge the engine starting battery(ies) when the battery charger is connected to thebattery(ies) and is not connected to an AC power supply. To prevent engine starting battery(ies) discharge, install batterycharger relay kit GM39659.

Page 18

Page 27: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Float/Equalize Battery Charger, continued

Page 19

Page 28: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Industrial Generator Set Accessories

Voltage Regulators

Fast Response™ II PMG with Average Voltage SensingVoltage Regulator (20-300 kW Generator Set Models)

The solid-state voltage regulator has ±2% no-load to full-loadregulation using average voltage sensing. The voltage regulator features single- or three-phase sensingoptions and is available for 12- or 24-volt engine electricalsystems. Available with optional ±1% no-load to full-load regulationusing average single-phase voltage sensing.

Voltage Regulators The following information provides general features,specifications, and functions of available voltageregulators. This information generally applies to a single generator setand multiple generator sets with paralleling applications.Refer to the respective generator set specification sheetand see your authorized distributor for informationregarding specific voltage regulator applications andavailability.

Page 20

Page 29: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Voltage Regulators, continued

Specification Fast Response II

Generator Set Availability 20-300 kW 20-300 kWModels

Type Analog/Discrete

Status and ShutdownIndicators

Operating Temperature -40°C to 70°C (-40°F to 158°F)

Storage Temperature -40°C to 85°C (-40°F to 185°F)

Humidity NA

Circuit Protection 15 Amp Fuse

Sensing, Nominal 190-277 Volts, (L-L) 50-60 Hz

Sensing Mode Average, Single- or Three-Phase

Input Requirements 8-32 VDC

Continuous Output 100 mA at 2 VDC

Maximum Output 100 mA at 2 VDC

Transition Frequency 50-70 Hz

Exciter Field Resistance NA

No-Load to Full-LoadVoltage Regulation

±2% * Linear Loads

Thermal Drift <1.0% 40 C (104 F) Change(-40 C to 70 C range) [-40 F to158 F]

Response Time Less Than 7µS

Voltage Adjustment (ofsystem voltage)

150-300 (low volt connection)

300-600 (high voltconnection)

Voltage Adjustment Potentiometer

Remote VoltageAdjustment

Remote-MountedPotentiometer Optional

Paralleling Capability Optional Reactive Droop KitRequired

VAR/PF Control Input -

* A ±1% (linear loads) voltage regulator with single-phase voltage sensing

is available on selected models.

DVR® is a registered trademark of Marathon Electric Mfg. Corp.

NA - Data not available at time of print.

Fast Response™ II PMG Voltage Regulator • The voltage regulator monitors output voltage magnitude and

frequency to supply current to the stationary LED board.• The stability potentiometer adjusts the voltage regulator to

reduce light flicker.• The volt/Hz adjustment potentiometer determines the engine

speed (Hz) at which the generator output voltage begins todrop.

Adjustment Potentiometers• Stability• 50 Hz Volt/Hz Adjustment• 60 Hz Volt/Hz Adjustment Jumpers• 50 or 60 Hz Selection Jumper for Volts/Hz Standard Average Voltage Sensing Model• 12- or 24-Volt Engine Electrical System, ±2%

Single-Phase Voltage Sensing Average Voltage Sensing Models Available• 12- or 24-Volt Engine Electrical System, ±2%

Three-Phase Voltage Sensing• 12- or 24-Volt Engine Electrical System, ±1%

Single-Phase Voltage Sensing (some models)

Accessories Refer to the respective generator set spec sheet and yourauthorized distributor for specific accessories. Fast Response™ II PMG Voltage Regulator

• Reactive Droop Compensator Kit• Voltage Adjustment Potentiometer Kit• Voltage Regulator Relocation Kit

Page 21

Page 30: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Model KBP-DMTA-0150S

Transfer Switch Standard Features• UL 1008 listed at 480 VAC, file # E108981• CSA certification available• Bypass/isolation switches for uninterrupted power to the load

during switch maintenance and testing• Standard-transition or programmed-transition modes of

operation• Ratings from 150 to 3000 amps• Ratings of bypass switch and automatic transfer switch identical• Available in 2, 3, or 4 pole configurations• Available to 600 VAC, 60 or 50 Hz• Suitable for emergency and standby applications on all classes

of load, 100% tungsten rated through 400 amps• NEMA type 1 enclosure• Exceeds UL 1008 requirements for temperature rise after

overload and endurance tests in unventilated enclosure• Auxiliary position contacts: two closed on normal switch position,

two closed on emergency switch position (rated 15 A @ 240VAC)

• Standard-transition transfer time less than 100 milliseconds (6cycles @ 60 Hz)

MPAC® 1500 Controller

Standard Features• Microprocessor-based controller• Environmentally sealed user interface• LCD display, 4 lines x 20 characters, backlit• Dynamic function keypad with tactile feedback pushbuttons

allows complete programming and viewing capability at the door• LED indicators: Source available, transfer switch position,

service required (fault), and “not in auto"• Broadrange voltage sensing (208--600 VAC) on all phases• Phase-to-phase sensing and monitoring with 0.5% accuracy on

both sources• Frequency sensing with 0.5% accuracy on both sources• Anti-single phasing protection• Phase rotation sensing for three-phase systems• Real-time clock with battery backup and automatic adjust for

daylight saving time and leap year• Time-stamped event log• Fail-safe transfer for loaded test and exercise functions• DIP switches: password disable and maintenance• Modbus® RTU and Modbus® TCP/IP protocols• (Modbus® register map available)• RJ45 connector for 10/100 ethernet connection• USB port with read/write compatibility• Isolated RS-485 ports• One-year limited warranty

Programmable Features• Programming and monitoring methods:

o

Monitoring and password-protected programming at the doorusing the keypad and display

o

Program and monitor using a PC with Monitor III integratedgenerator set and ATS monitoring software

o

Transfer files through the USB port

• System voltage and frequency• Voltage unbalance• Over/undervoltage and over/underfrequency for all phases of the

normal and emergency sources• Time delays• Load/no load/auto-load test and load/no-load exercise functions• Programmable inputs and outputs• Load control outputs (load stepping)• Selectable operating modes: utility-generator, generator-

generator, or utility-utility• Load bank control for exercise or test• Pre/post-transfer, 9 individual time delays for selected loads• ABC/BAC/none phase rotation selection with error detection• Resettable historical data• In-phase monitor• Password protection, 3 security levels

Page 22

Page 31: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

User Interface LED Indicators• Contactor position: source N and source E• Source available: source N and source E• Service required (fault indication)• Not in automatic mode

LCD Display• System status• Line-to-line voltage• Line-to-neutral voltage• Active time delays• Source frequency• Preferred source selection• System settings• Common alarms• Load current, each phase (requires optional current

transformers)• Inputs and outputs• Faults• Time/date• Address• Event history• Maintenance records• Exerciser schedule• Exerciser mode• Time remaining on active exercise

Dynamic Function Tactile Keypad Operations• Scroll up/down/forward/back• Increase/decrease/save settings• End time delay• Start/end test• Reset fault• Lamp test

Main Logic Board Inputs and Outputs• Two (2) programmable inputs• Two (2) programmable outputs, isolated form C (SPDT) contacts

rated 1 amp @ 30 VDC, 500 mA @120 VAC

DIP Switches• Maintenance mode• Password disable

Event History• View up to 99 time and date-stamped events on the display or

on a personal computer equipped with optional Monitor IIIsoftware. Download up to 2000 events with Monitor III softwareor download complete event history file to a PC or a memorydevice connected to the USB port.

Communications• USB port with read/write capability• Isolated RS-485 ports• RJ-45 connector for 10/100 ethernet connection• Modbus® RTU and Modbus® TCP/IP protocols (Modbus®

register map available)• USB Port. Upload or download files from a PC or a memory

device through the USB port.

o Application software

o Event history files

o Language files

o Parameter settings

o Usage reports

o Feature configuration

Programmable Features• System voltage, 208 600 VAC *• System frequency, 50/60 Hz *• Single/three-phase operation *• Standard/programmed-transition operation *• Preferred source selection• Phase rotation: ABC/BAC/none• Voltage and frequency pickup and dropout settings• Voltage unbalance, enable/disable• In-phase monitor: enable/disable and phase angle• Transfer commit/no commit• Source/source mode: utility/gen, gen/gen, utility/utility• Passwords, system and test• Time, date, automatic daylight saving time enable/disable• Time delays (see table)• Exerciser: calendar mode, loaded/unloaded up to 21 events• Test: load/no-load/auto load (1 60 minutes)• Automatic override on generator failure (loaded test and

exercise)• External test: loaded/unloaded• Peak shave delay enable/disable• Current monitoring (requires optional current transformers)• Pre/post-transfer, 9 individual time delays for selected loads• ABC/BAC/none phase rotation selection with error detection• Resettable historical data

Page 23

Page 32: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

Programmable Inputs • External time delay input• External battery fault• External common fault• Inhibit transfer• Load shed to force transfer to OFF (programmed-transition

models only)• Peak shave/area protection input• External test• Three-source system disable• Bypass disable

Programmable Outputs• Chicago alarm control• Common alarm events• Contactor position• Exercise active• Failure to acquire standby source• Failure to transfer• Generator engine start, source N and E• I/O module faults• Load bank control• Load control active (pre/post transfer delay, up to 9 outputs)• Load control active• Loss of phase fault, source N and E• External battery fault• Non-emergency transfer• Not in automatic mode• Over/underfrequency faults, source N and E (generator)• Over/undervoltage faults, source N and E• Peak shave/area protection active• Phase rotation error, source N and E• Preferred source supplying load• Software-controlled relay outputs (4 maximum)• Source available, preferred and standby• Standby source supplying load• Synchronizing output• Test active• Transfer switch auxiliary contact fault• Transfer switch auxiliary contact open• Voltage unbalance

Voltage and Frequency SensingParameter Default Adjustment Range

Undervoltage dropout 90% of pickup 75% 98%

Undervoltage pickup 90% of nominal 85% 100%

Overvoltage dropout * 115% of nominal* 106% 135%

Overvoltage pickup 95% of dropout 95% -100%

Unbalance enable Disable Enable/Disable

Unbalance dropout 20% 5%-20%

Unbalance pickup 10% 3%-18%

Voltage dropout time 0.5 sec. 0.1-9.9 sec.

Underfrequency dropout 99% of pickup 95%-99%

Underfrequency pickup 90% of nominal 80%-95%

Overfrequency dropout 101% of pickup 101%-115%

Overfrequency pickup 110% of nominal 105%-120%

Frequency dropout time 3 sec. 0.1-15 sec.

* 690 volts, maximum. Default = 110% for 600 volt applications.

Adjustable Time DelaysParameter Default Adjustment Range

Emergency source engine

start

3 sec. 0-6 sec.

Normal source engine start

(gen/gen mode)

0 sec.

Emergency source engine

cooldown

5 sec.

Normal source engine

cooldown (gen/gen mode)

2 sec.

Failure to acquire standby

source

1 min.

Preferred to standby 1 sec.

Standby to preferred 15 min. 0-60 min. †

Pretransfer to preferred signal 0 sec.

Post-transfer to preferred

signal

0 sec.

Pretransfer to standby signal 0 sec.

Failure to synchronize 1 min.

Off (preferred to standby,

programmed-transition only)

1 sec.

Off (standby to preferred,

programmed-transition only)

1 sec.

Auto load test duration 30 min. 1-60 min. ‡

†Adjustable in 1 second increments. Engine start can be extended to 60

minutes with an External Battery Supply Module Kit.

‡1 minute increments.

Page 24

Page 33: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

Environmental Specifications OperatingTemperature

-20°C to 70°C (-4°F to 158°F)

Storage Temperature -40°C to 85°C (-40°F to 185°F)Humidity 5% to 95% noncondensing

Input and Output Connection Specifications Component Wire Size RangeMain board I/Oterminals

#12-24 AWG

I/O module terminals #14-24 AWG

Auxiliary Position Indicating Contacts

(rated 10 Amps @ 32 VDC/250 VAC)

Switch Rating (Amps) Number of ContactsIndicating

Transition

0150 2, 3

0150 7, 7

UL-Listed Solderless Screw-Type Terminals forExternal Power Connections

Normal, Emergency, and Load Terminals

Switch Rating,amps

Max Number ofCables per Pole

Range of WireSizes

150, 2-, 3-pole 1 #4 AWG to 600MCM

150, 2-, 3-pole 2 1/0 AWG to 250MCM

150, 4-pole 2 #1 AWG to 600MCM

Use 75&#176;C minimum Cu/Al wire for power connections.

Codes and Standards • Underwriters Laboratories UL 508, Standard for Industrial

Control Equipment• Underwriters Laboratories UL 1008, Standard for Automatic

Transfer Switches for Use in Emergency Standby Systems, file# E108981

• CSA C22.2 No. 178 certification at 600 VAC available, file #LR58301

• NFPA 70, National Electrical Code• NFPA 99, Essential Electrical Systems for Health Care Facilities• NFPA 110, Emergency and Standby Power Systems• IEEE Standard 446, IEEE Recommended Practice for

Emergency and Standby Power Systems for Commercial andIndustrial Applications

• NEMA Standard IC10-1993 (formerly ICS2-447), AC AutomaticTransfer Switches

• EN61000-4-4 Fast Transient Immunity Severity Level 4• IEC 60947-6-1, Low Voltage Switchgear and Control Gear;

Multifunction Equipment; Automatic Transfer SwitchingEquipment

• EN61000-4-5 Surge Immunity Class 4 (voltage sensing andprogrammable inputs only)

• IEC Specifications for EMI/EMC Immunity:

o CISPR 11, Radiated Emissions

o IEC 1000-4-2, Electrostatic Discharge

o IEC 1000-4-3, Radiated Electromagnetic Fields

o IEC 1000-4-4, Electrical Fast Transients (Bursts)

o IEC 1000-4-5, Surge Voltage

o IEC 1000-4-6, Conducted RF Disturbances

o IEC 1000-4-8, Magnetic Fields

o IEC 1000-4-11, Voltage Dips and Interruptions• IEEE 472 (ANSI C37.90A) Ring Wave Test

Weight, kg (lb.) Number of Poles Amps

158 (350) 3 150

Page 25

Page 34: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

Withstand/Closing Ratings (WCR)

Transition Model

Maximum current in RMS symmetrical amperes when coordinated with customer-supplied fuses or circuit breakers.

Withstand and Closing Current Ratings in RMS Symmetrical Amperes*

Any Circuit Breaker Current Limiting Fuses

SwitchRating, amps

Cycles @ 60Hz

MaximumAmps @ 480

VAC

MaximumAmps @ 600

VAC

Current-LimitingFuses

MaximumAmps

Current-Limiting

Fuses Volts,Max

Current-LimitingFuses

MaximumFuse Size,

amps

Current-Limiting

Fuses Type

150 3 35,000 22,000 200,000 480 450 JAll values are available symmetrical RMS amperes and tested in accordance with the withstand/closing requirements of UL 1008. Application requirementsmay permit highter withstand ratings for certain size switches. Contact Kohler Co. for assistance.

Ratings with Specific Manufacturer's Circuit Breaker The following chart lists power switching device withstand and closing ratings (WCR) in RMS symmetrical amperes forcircuit breakers from specific manufacturers. Circuit breakers are supplied by the customer.

Molded-Case Circuit Breaker

Switch Rating,amps

Voltage,Max.

Withstand/ClosingRating (WCR), RMSSymmetrical Amps

Manufacturer Type Max. Size,amps

150 480 42,000 General Electric TEL, THED, THLC1, 150

150 480 42,000 General Electric TFL, THLC2 225

150 480 42,000 General Electric SFL, SFLA, SFP 250

150 480 42,000 General Electric SGL4, SGP4, TB4,THLC4, TLB4

400

150 480 42,000 General Electric SGLA, SGL6, SGP6 TB6 600

150 480 42,000 ITE CFD6, HFD6 250

150 480 42,000 ITE CJD6, HHJD6, HHJXD6,HJD6, SCJD6, SHJD6

400

150 480 42,000 ITE CLD6, HHLD6, HHLXD6,HLD6, SHLD6

600

150 480 42,000 Square D KC, KI 250

150 480 42,000 Square D LC, LI 400

150 480 42,000 Cutler-Hammer HJD, JDC 250

150 480 42,000 Cutler-Hammer HKD, KDC, LCL, Tri-PacLA

400

150 480 42,000 Cutler-Hammer HLD 600

150 480 42,000 Cutler-Hammer Tri-Pac NB 800

150 480 42,000 ABB S3 150

150 480 42,000 Merlin Gerin CF250 250

150 480 42,000 Merlin Gerin CJ400 400

Page 26

Page 35: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

Page 27

Page 36: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

KBP-DMTA-0150S, continued

Accessories

Accessories are available either factory-installed or as loose kits, unless otherwise noted.

Accessory Modules The mounting kit holds up to five optional modules. Themaximum total current draw is 300 mA. If an ExternalBattery Module is installed, there is no current restriction. Module Current Draw Specification, mA

Alarm Module 75

Standard I/O Module 75

High Power I/O Module 100Standard Input/Output Module Inputs

AvailableInputs

2

Input Definition Contact closure

Current 5 mA Max

ConnectionType

Terminal Strip

Wire Size #14-24 AWG

Max Distance 700 feet

Outputs

OutputsAvailable

6

Contact Type Form C (SPDT)

ContactVoltage Rating

2 A @ 30 VDC

500 mA @ 125 VAC

ConnectionType

Terminal Strip

Wire Size #14-24 AWG

CSA Certification

Load Shed Kit• Forced transfer from Emergency to OFF for

programmed-transition models• External hardware is required for the forced

transfer to OFF function• Factory-installed

Warranty

• Warranty-1-year

Page 28

Page 37: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Dimensional Drawings

Page 29

Page 38: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 39: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 40: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 41: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 42: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Wiring Schematics

Page 34

Page 43: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 44: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 45: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 46: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 47: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 48: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 49: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 50: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 51: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 52: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 53: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 54: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 55: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 56: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 57: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Warranty

Page 49

Page 58: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

*Some restrictionsmay apply. Contact yourKohler distributor/dealer for full details.

�Startup must occur within 24 months of original shipment by Kohler Co.

Your Kohler product has been manufactured and inspected with care by experienced craftsmen. If you are the original consumer,Kohler Co. warrants, for the period indicated below, each product to be free from defects in materials and workmanship. Repair,replacement,orappropriateadjustmentatKohler Co.’soptionwill be furnished if theproduct,uponKohler Co.’s inspection, is found tobeproperly installed, maintained, and operated in accordance with Kohler Co.’s instruction manuals. A Kohler distributor, dealer, orauthorized representative must perform startup. This warranty does not apply to malfunctions caused by damage, unreasonable use,misuse, repair or service by unauthorized persons, or normal wear and tear.

TP-5374 12/99c

Warranty Coverage*

One (1) year or 2000 hours (whichever occurs first) from date of initial startup�One (1) year or 2000 hours (whichever occurs first) from date of initial startup�

Kohler Product

Generator Set & AccessoriesPrime Power Generator Set 20 kW or Larger

Stationary Standby and Prime Power One-Year orTwo Thousand (2000)-Hour Limited Warranty

A Startup Notification form must be on file at Kohler Co. A Startup Notification form must be completed by Seller and received atKohler Co. within 60 days after the date of initial startup. Standby systems not registered within 60 days of startupwill automatically beregistered by Kohler Co. using the Kohler Co. ship date as the startup date.

To obtain warranty service, call 1-800-544-2444 for your nearest authorized Kohler service representative or write Kohler Co.,Generator Service Department, Kohler, WI 53044 USA.

KOHLERCO.SHALLNOTBELIABLEFORSPECIAL, INCIDENTAL,ORCONSEQUENTIALDAMAGESOFANYKIND including,butnot limited to, incidental consequential laborcosts, installationcharges, telephonecharges,or transportationcharges inconnectionwiththe replacement or repair of defective parts.

This is our exclusive written warranty. We make no other express warranty nor is anyone authorized to make any on our behalf.

ANY IMPLIEDORSTATUTORYWARRANTY, INCLUDINGANYWARRANTYOFMERCHANTABILITYORFITNESSOFPURPOSE,is expressly limited to the duration of this warranty. Some states do not allow limitations on how long an implied warranty lasts, or theexclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.

The following will not be covered by the warranty:

1. Normal engine wear, routine tuneups, tuneup parts,adjustments, and periodic service.

2. Damage caused by accidents, improper installation orhandling, faulty repairs not performed by an authorizedservice representative, or improper storage.

3. Damage caused by operation with improper fuel or atspeeds, loads, conditions, modifications, or installationcontrary to published specifications or recommendations.

4. Damage caused by negligent maintenance such as:

a. Failure to provide the specified type and sufficientquantity of lubricating oil.

b. Failure to keep the air intake and cooling fin areasclean.

c. Failure to service the air cleaner.

d. Failure to provide sufficient coolant and/or cooling air.

e. Failure to perform scheduled maintenance asprescribed in supplied manuals.

f. Failure to regularly exercise the generator set underload (stationary applications only).

5. Original installation charges and startup costs.

6. Starting batteries and the following related expenses:

a. Labor charges related to battery service.

b. Travel expense related to battery service.

7. Engine coolant heaters, heater controls, and circulatingpumps after the first year.

8. Rental of equipment during performance of warrantyrepairs.

9. Parts purchased from sources other than Kohler Co.Replacement of a failed Kohler part with a non-Kohler partvoids warranty on that part.

10. Radiators replaced rather than repaired.

11. Fuel injection pumps not repaired locally by an authorizedservicing dealer.

12. Non-Kohler-authorized repair shop labor without priorapproval from Kohler Co. Warranty Department.

13. Engine fluids such as fuel, oil, or coolant/antifreeze.

14. Shop supplies such as adhesives, cleaning solvents, andrags.

15. Expenses incurred investigating performance complaintsunless the problem is caused by defective Kohlermaterials or workmanship.

16. Maintenance items such as fuses, lamps, filters, sparkplugs, loose or leaking clamps, and adjustments.

KOHLER CO. Kohler, Wisconsin 53044Phone 920-565-3381, Fax 920-459-1646For the nearest sales/service outlet in theUS and Canada, phone 1-800-544-2444KohlerPowerSystems.com

Page 59: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Your Kohler product has been manufactured and inspected with care by experienced craftsmen. If you are the original consumer,Kohler Co. warrants, for the period indicated below, each product to be free from defects in materials and workmanship. Repair,replacement, or appropriate adjustment at Kohler Co.’s option will be furnished if the product, uponKohler Co.’s inspection, is found tobe properly installed, maintained, and operated in accordance with Kohler Co.’s instruction manuals. A Kohler distributor, dealer, orauthorized representativemust perform startup. This warranty does not apply to malfunctions caused by damage, unreasonable use,misuse, repair or service by unauthorized persons, or normal wear and tear.

TP-5373 12/99d

Transfer Switch and Bypass Isolation Transfer SwitchOne-Year Limited Warranty

A Startup Notification form must be on file at Kohler Co. A Startup Notification form must be completed by Seller and received atKohler Co. within 60 days after the date of initial startup. Standby systems not registered within 60 days of startupwill automatically beregistered by Kohler Co. using the Kohler Co. ship date as the startup date.

To obtain warranty service, call 1-800-544-2444 for your nearest authorized Kohler service representative, or write Kohler Co.,Generator Service Department, Kohler, WI 53044 USA.

KOHLERCO.SHALLNOTBELIABLEFORSPECIAL, INCIDENTAL,ORCONSEQUENTIALDAMAGESOFANYKIND including,butnot limited to, incidental consequential laborcosts, installationcharges, telephonecharges,or transportationcharges inconnectionwiththe replacement or repair of defective parts.

This is our exclusive written warranty. We make no other express warranty nor is anyone authorized to make any on our behalf.

ANY IMPLIEDORSTATUTORYWARRANTY, INCLUDINGANYWARRANTYOFMERCHANTABILITYORFITNESSOFPURPOSE,is expressly limited to the duration of this warranty. Some states do not allow limitations on how long an implied warranty lasts, or theexclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.

Transfer Switch and Bypass Isolation Switch One (1) year from date of startup

Kohler Product Warranty Coverage*

The following will not be covered by the warranty:

1. Normal wear, periodic service, and routine adjustments.

2. Damage caused by accidents, improper installation orhandling, faulty repairs not performed by an authorizedservice representative, or improper storage.

3. Damage caused by operation above or below ratedcapacity, voltage, or frequency; modifications; orinstallation contrary to published specifications, codes,recommendations, and accepted industry practices.

4. Original installation charges and startup costs.

5. Damage caused by negligent maintenance such as:

a. Failure to provide a clean, dry environment.b. Failure to perform recommended exercising.c. Failure to perform scheduled maintenance as

prescribed in supplied manuals.d. Useof other than factory-suppliedor -approved repair

parts and/or procedures.

6. Rental of equipment during performance of warrantyrepairs.

7. Non-Kohler-authorized repair shop labor without priorapproval from the Kohler Co. Warranty Department.

8. Expenses incurred investigating performancecomplaintsunless the problem is caused by defective Kohlermaterials or workmanship.

9. Maintenance items such as fuses, lamps, andadjustments.

*Some restrictions may apply. Contact your Kohler distributor/dealer for full details.

KOHLER CO. Kohler, Wisconsin 53044Phone 920-565-3381, Fax 920-459-1646For the nearest sales/service outlet in theUS and Canada, phone 1-800-544-2444KohlerPowerSystems.com

Page 60: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Prototype Test Certifications

Page 52

Page 61: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

G18-56 12/05a

Kohler Standby/Prime Generator Set Test Program

Testing is an integral part of quality assurance. In keepingwith ouruncompromising commitment to quality, safety,and reliability, every Kohler Standby/Prime power generator set undergoes an extensive series of prototype andproduction testing.

Prototype Testing

Prototype testing includes the potentially destructivetests necessary to verify design, proper function ofprotective devices and safety features, and reliabilityexpectations. Kohler’s prototype testing includes thefollowing:

� Alternator temperature rise test per NEMAMG1-32.6. Standby and prime ratings of thealternator are established during this test.

� Maximum power test to assure that the primemover and alternator have sufficient capacity tooperate within specifications.

� Alternator overload test per NEMA MG1-32.8.

� Steady-state load test to ensure voltage regulationmeets or exceeds ANSI C84.1, NEMAMG1-32.17requirementsand toverifycompliancewithsteady-state speed control specifications.

� Transient test to verify speed controls meets orexceeds specifications.

� Transient load tests per NEMA MG1-32.18, andISO 8528 to verify specifications of transientvoltage regulation, voltage dip, voltage overshoot,recovery voltage, and recovery time.

� Motor starting tests per NEMA MG1-32.18.5 toevaluate capabilities of generator, exciter, andregulator system.

� Three-phase symmetrical short-circuit test perNEMA MG1-32.13 to demonstrate short circuitperformance, mechanical integrity, ability tosustain short-circuit current.

� Harmonic analysis, voltage waveform deviationper NEMA MG1-32.10 to confirm that thegenerator set is producing clean voltage withinacceptable limits.

� Generator set cooling and air flow tests to verifymaximum operating ambient temperature.

� Reliability tests to demonstrate product durability,followed by root cause analysis of discoveredfailures and defects. Corrective action is taken toimprove thedesign,workmanship, or components.

� Acoustical noise intensity and sound attenuationeffects tests.

Production Testing

In production, Kohler Standby/Prime generator setsare built to the stringent standards established by theprototype program. Every Kohler Generator set isfully tested prior to leaving the factory. Productiontesting includes the following:

� Stator and exciterwinding high-potential test onallgenerators. Surge transient tests on stators forgenerators 180 kW or larger. Continuity andbalance tests on all rotors.

� One-step, full-load pickup tests to verify that theperformance of each generator set, regulator, andgovernor meets published specifications.

� Regulation and stability of voltage and frequencyare testedandverifiedatno load, 1/4 load, 1/2 load,3/4 load, and full-rated load.

� Voltage, amperage, frequency and power outputratings verified by full-load test.

� The proper operation of controller logic circuitry,prealarm warnings, and shutdown functions istested and verified.

� Any defect or variation from specificationdiscoveredduring testing is correctedand retestedprior to approval for shipment to the customer.

Torsional analysis data, to verify torsional effects are not detrimental and that the generator set will providedependable service as specified, is available upon request.

Kohler offers other testing at the customer’s request at an additional charge. These optional tests include powerfactor testing, customized load testing for specific application, witness testing, and a broad range ofMIL-STD-705c testing. A certified test report is also available at an additional charge.

KOHLER CO. Kohler, Wisconsin 53044Phone 920-565-3381, Fax 920-459-1646For the nearest sales/service outlet in theUS and Canada, phone 1-800-544-2444KohlerPowerSystemscom

Page 62: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Miscellaneous

Page 54

Page 63: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 64: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 65: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 66: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 67: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 68: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 69: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 70: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 71: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 72: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 73: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal
Page 74: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

444 Highland Drive

Kohler, Wisconsin 53044

P: 920-565-3381 F: 920-453-6362

Prestartup Checklist

Page 66

Page 75: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

Generator Set/Transfer Switch Installation Checklist

This document has generic content and some items may not apply to some applications. Check only the items that apply to the specificapplication. Read and understand all of the safety precautions found in the Operation and Installation Manuals. Make the followinginstallation checks before performing the Startup Checklist.

Note: Use this form as a general guide, along with any applicable codes or standards. Comply with all applicable codes and standards.Improper installation voids the warranty.

Equipment Room or Weather Housing

Yes

DoesNotApply

� � 1. Is the equipment installed in a fire-resistant room(made of non-combustible material) or in an outdoorweather housing?

� � 2. Is there adequate clearance between the engine andfloor for service maintenance?

� � 3. Is there emergency lighting available at theequipment room or weather housing?

� � 4. Is there adequate heating for the equipment room oroutdoor weather housing?

� � 5. Is the equipment room clean with all materials notrelated to the emergency power supply systemremoved?

� � 6. Is the equipment room protected with a fireprotection system?

Engine and Mounting

� � 7. Is the mounting surface(s) properly constructed andleveled?

� � 8. Is the mounting surface made from non-combustiblematerial?

� � 9. Was the generator-to-engine alignment performedafter attaching the skid to the mounting base?Generator sets with two-bearing generators requirealignment.

Lubrication

� � 10. Is the engine crankcase filled with the specified oil?

Cooling and Ventilation

� � 11. Is the cooling system filled with the manufacturer’sspecified coolant/antifreeze and purged of air?

� � 12. Is there adequate inlet and outlet air flow (electriclouvers adjusted and ventilation fan motor(s)connected to the corresponding voltage)?

� � 13. Is the radiator duct properly sized and connected tothe air vent or louver?

� � 14. Are flexible sections installed in the cooling waterlines?

Fuel

� � 15. Is there an adequate/dedicated fuel supply?

� � 16. Are the fuel filters installed?

� � 17. Are the fuel tanks and piping installed in accordancewith applicable codes and standards?

� � 18. Is there adequate fuel transfer tank pump liftcapacity and is the pump motor connected to thecorresponding voltage?

� � 19. Is the fuel transfer tank pump connected to theemergency power source?

� � 20. Are flexible fuel lines installed between the enginefuel inlet and fuel piping?

� � 21. Is the specified gas pressure available at the fuelregulator inlet?

� � 22. Does the gas solenoid valve function?

� � 23. Are the manually operated fuel and cooling watervalves installed allowing manual operation or bypassof the solenoid valves?

Exhaust

� � 24. Is the exhaust line sized per guidelines and does ithave flexible connector(s)? Is the flexibleconnector(s) straight?

Yes

DoesNotApply

� � 25. Is there an exhaust line condensate trap with a draininstalled?

� � 26. Is the specified silencer installed and are the hangerand mounting hardware tightened?

� � 27. Is a heat-isolating thimble(s) installed at pointswhere exhaust lines pass through combustiblewall(s) or partition(s)?

� � 28. Is the exhaust line free of excessive bends andrestrictions? Is the backpressure withinspecifications?

� � 29. Is the exhaust line installed with a downward pitchtoward the outside of the building?

� � 30. Is the exhaust line protected from entry by rain,snow, and animals?

� � 31. Does the exhaust system outlet location prevententry of exhaust gases into buildings or structures?

� � 32. Are individuals protected from exposure to hightemperature exhaust parts and are hot parts safetydecals present?

AC Electrical System

� � 33. Does the nameplate voltage/frequency of thegenerator set and transfer switch matchnormal/utility source ratings?

� � 34. Do the generator set load conductors have adequateampacity and are they correctly connected to thecircuit breakers and/or the emergency side of thetransfer switch?

� � 35. Are the load conductors, engine starting cables,battery charger cables, and remote annunciatorleads installed in separate conduits?

� � 36. Is the battery charger AC circuit connected to thecorresponding voltage?

Transfer Switch, Remote Control System, Accessories

� � 37. Is the transfer switch mechanism free of binding?Note: Disconnect all AC sources and operate thetransfer switch manually.

� � 38. Are the transfer switch AC conductors correctlyconnected? Verify lead designations using theappropriate wiring diagrams.

� � 39. Is all other wiring connected, as required?

Batteries and DC Electrical System

� � 40. Does the battery(ies) have the specified CCA ratingand voltage?

� � 41. Is the battery(ies) filled with electrolyte andconnected to the battery charger?

� � 42. Are the engine starting cables connected to thebattery(ies)?

� � 43. Do the engine starting cables have adequate lengthand gauge?

� � 44. Is the battery(ies) installed with adequate airventilation?

� � 45. Are the ends of all spark plug wires properly seatedonto the coil/distributor and the spark plug?

Special Requirements

� � 46. Is the earthquake protection adequate for theequipment and support systems?

� � 47. Is the equipment protected from lightning damage?

Page 76: ~QuickPack Create a Submittal - Kohler Power Groupkohlerpower.bigmachines.com/.../Help_PDF_Files/CreateASubmittal.pdf · Perform this procedure when you need to create a submittal

* Some models with an Engine Electronic Control Module (ECM) may limit or prohibit adjusting the engine speed or testing shutdowns.Refer to appropriate documentation available from the manufacturer.

Generator Set/Transfer Switch Startup Checklist

This document has generic content and some itemsmaynot apply to some applications. Check only the items that apply to the specific application.Read and understand all of the safety precautions found in the Operation and Installation Manuals. Complete the Installation Checklist beforeperforming the initial startup checks. Refer to Service Bulletin 616 for Warranty Startup Procedure Requirements regarding generator set modelswith ECM-controlled engines.

Yes

DoesNotApply

� � 1. Verify that the engine is filled with oil and the coolingsystem is filled with coolant/antifreeze.

� � 2. Prime the fuel system.

� � 3. Open all water and fuel valves. Temporarily remove theradiator cap to eliminate air in the cooling system.Replace radiator cap in step 21.

� � 4. Place the generator set master switch in theOFF/RESET position. Observe Not-in-Auto lamp andalarm, if equipped, on the controller.

� � 5. Press the lamp test, if equipped on controller. Do all thealarm lamps on the panel illuminate?

� � 6. Open the main line circuit breakers, open the safeguardbreaker, and/or remove fuses connected to thegenerator set output leads.

� � 7. Turn down the speed control (electronic governor) orspeed screw (mechanical governor).*

� � 8. Verify the presence of lube oil in the turbocharger, ifequipped. See the engine and/or generator setoperation manual.

� � 9. Place the generator set master switch in the RUNposition. Allow the engine to start and run for severalseconds.

� � 10. Verify that the day tank, if equipped, is energized.

� � 11. Place the generator set master switch in theOFF/RESET position. Check for oil, coolant, andexhaust leaks.

� � 12. Turn on the water/oil heaters and fuel lift pumps.

� � 13. Check the battery charger ammeter for battery chargingindication.

� � 14. Place the generator set master switch in the RUNposition. Verify whether there is sufficient oil pressure.Check for oil, coolant, and exhaust leaks.

� � 15. Close the safeguard circuit breaker. Adjust the enginespeed to 50/60 Hz if equipped with an electronicgovernor or to 52.8/63 Hz if equipped with a mechanicalgovernor.*

� � 16. If the speed is unstable, adjust according to theappropriate engine and/or governor manual.*

� � 17. Adjust the AC output voltage to match the load voltageusing the voltage adjusting control. See the generatorset/controller operation manual.

� � 18. Allow the engine to reach normal operating coolanttemperature.

� � 19. Check the operating temperature on city water-cooledmodels and adjust the thermostatic valve as necessary.

� � 20. Manually overspeed the engine to cause an engineshutdown (68-70 Hz on 60 Hz models and 58-60 Hz on50 Hz models). Place the generator set master switchin the OFF/RESET position.*

� � 21. Check the coolant level, add coolant as necessary, andreplace the radiator cap. Verify that all hose clamps aretight and secure.

� � 22. Place the generator set master switch in the RUNposition.

� � 23. Verify the engine low oil pressure and high coolanttemperature shutdowns.*

� � 24. Check the overcrank shutdown.*

� � 25. Place the generator set master switch in theOFF/RESET position.

� � 26. Open the normal source circuit breaker or remove fusesto the transfer switch.

� � 27. Disconnect the power switching device and logiccontroller wire harness at the inline disconnect plug atthe transfer switch.

� � 28. Manually transfer the load to the emergency source.

Yes

DoesNotApply

� � 29. Close the normal source circuit breaker or replace fusesto the transfer switch.

� � 30. Check the normal source voltage, frequency, andphase sequence on three-phase models. The normalsource must match the load.

� � 31. Open the normal source circuit breaker or remove fusesto the transfer switch.

� � 32. Manually transfer the load to the normal source.

� � 33. Close the generator set main line circuit breakers, closethe safeguard breaker, and/or replace the fusesconnected to the transfer switch.

� � 34. Place the generator set master switch in the RUNposition.

� � 35. Check the generator set voltage, frequency, and phasesequence on three-phase models. The generator setmust match normal source and load.

� � 36. Place the generator set master switch in theOFF/RESET position.

� � 37. Open the generator set main line circuit breakers, openthe safeguard breaker, and/or remove the fusesconnected to the transfer switch.

� � 38. Reconnect the power switching device and logiccontroller wire harness at the inline disconnect plug atthe transfer switch.

� � 39. Close the normal source circuit breaker or replace fusesto the transfer switch. Place the generator set masterswitch to the AUTO position.

� � 40. Close the generator set main line circuit breakers, closethe safeguard breaker, and/or replace the fusesconnected to the transfer switch.

� � 41. Place the transfer switch in the TEST position (load testor open normal source circuit breaker). NOTE: Obtainpermission from the building authority beforeproceeding. This procedure tests transfer switchoperation and connects building load to generator setpower.

� � 42. Readjust frequency to 50 or 60 Hz with total buildingloads.*

� � 43. Verify that the current phase is balanced for threephase systems.

� � 44. Release the transfer switch test switch or close thenormal circuit breaker. The transfer switch shouldretransfer to the normal source after appropriate timedelay(s).

� � 45. Allow the generator set to run and shut downautomatically after the appropriate cool down timedelay(s).

� � 46. Set the plant exerciser to the customer’s requiredexercise period, if equipped.

� � 47. Verify that all options on the transfer switch are adjustedand functional for the customer’s requirements.

� � 48. If possible, run the building loads on the generator setfor several hours or perform the load bank test ifrequired.

� � 49. Verify that all the wire connections from the generatorset to the transfer switch and optional accessories aretight and secure.

� � 50. Verify that the customer has the appropriateengine/generator set and transfer switch literature.Instruct the customer in the operation and maintenanceof the power system.

� � 51. Fill out the startup notification at this time and send thewhite copy to the Generator Warranty Dept. Include thewarranty form if applicable.