Upload
vudien
View
227
Download
11
Embed Size (px)
Citation preview
S[)&@ O[f)@~&uO@[m~ C@~~u[~~
FINAL REPORT. VOl.UME IV
SOC SYSTEM ANAL VSIS R E (BOOK 2 OF 2)
0180-26495-4
DRl. T-1591 LINE ITEM 4 ORO MA-69i'T
(.~~ L""tt .~ q r .. \1 "'-...t w l.
111111111111111111111111111111111111111111111 NF02556
THE lI~t:I'E'NC COMPANY
HAMILTC)N STANDARD 0 DVISKX10f UNITED TECHNOLOGIES.
NASA-CR-167558 19820012330
https://ntrs.nasa.gov/search.jsp?R=19820012330 2018-06-24T20:55:59+00:00Z
0180-26495-4
SPACE OPERATIONS CENTER
SYSTEM ANALYSIS
Conducted for the NASA Johnson Space Center
Under Contra:ct NAS9-16151
FINAL REPORT
VOLUME IV
(Book 2 of 2)
SYSTEM ANALYSIS REPORT
D 180--26495-4
July ,1981 ,. /
1 , j' /
~~ /1' /sj-' ~. / / (", Ii ;f fl'. " Td~u 'Il'f1!l;((4Z;~ Approved by ''''\
BOEING AEROSPACE COMPANY
P.O. BOX 3999
Seattle, Washington 98124
Gordon R. Woodcock, SOC Study Manager
0180-26495-4
FOREWORD
The Space Operations Center System Analysis study (Contract NAS9-16151) was
initiated in June of 1980 and completed in May of 1981. This was the equivalent of
a NASA Phase A study. A separately funded Technology Assessment and
A.dvancement Plan study was conducted in parallel with the System A.nalysis Study.
These studies were managed by the Lyndon B. Johnson Space Center. The
Contracti.ng Officers Representative and Study Technical Manager is Sam Nassiff.
This study was conducted by The Boeing Aerospace Company, Large Space Systems
Group with the Hamilton Standard Division of United Technologies as subcontrac-
tor. The Boeing study manager is Gordon R. Woodcock. The Hamilton Standard
study manager is Harlan Brose.
This final report includes 8 documents:
D180-26495-1 Vol. I
D 180-26495-2 Vol. II
D180-26495-3 Vol. III
0180-26495-4 Vol. IV
D180-26495-5 Vol. V
D180-26495-6
0180-26495-7
0180-26495-8
Executive Summary
Requirements (NASA CR-160944)
SOC System Oefinition Report
SOC System Analysis Report (2 volumes)
Data Book {Limited Distribution}
(Reserved)
Space Operations Center Technology Identification
Support Study, Final Report
Final Briefing Book
For convenience to the reader, a complete listing of all of the known Space Opera-
tions Center documentation is included in the Reference section of each document.
This includes NASA, Boeing, and Rockwell documentation.
ii
D180-26~95-4
KEY TEAM MEMBERS
?ubject;
SOC Technical Manager
SOC T(~chnology Study Manager
System Design
Electrical Power
ECLSS/EVA
Communications & Tracking
Structures/Dynamic Control
Sta.b/Control
Propuls ion/Propellant Storage
Subsystem Interface
Programma tics
Software/Processing
Config. Design/Docking &
Berthing
Health Maintenance Facility
Crew Habitat
Operations
Space Construction Facility
Flight Support Facility
Crew Operations
Orbital Altitude
Opera tions Concepts/
Requirements
Transporta tion
JSC-Managernent Team
S. H. Nassiff
R. Kennedy
S. H. Nassiff
L. Murgia
D. Thompson
R. Dietz
R. Wren
J. Bigham
D. Kendrick
L. Monford
R. Kennedy
E. Dalke
J. Jones
D. Nachtwey
M. Dalton
B. M. Wolfer
L. Jenkins
H. Patterson
M. Dalton
F. Garcia
B. Wolfer
B. Wolfer
iii
Contractor Team
G. R. Woodcock
R. L. Olson
G. R. Woodcock
S. W. Silverman
K. H. Miller
H. Brose (Ham Std)
G. Rannenberg (Ham Std)
R. Cushman (Ham Std)
F. M. Kim
R. M. Gates
J. H. Mason
G. R. Woodcock
M. A. Stowe
G. R. Woodcock
G. R. Woodcock
L. E. Silva G. L. Hadley
J. J. Olson
K. H. Miller
K. H. Miller
K. H. MiUer
K. H. Miller
K. H. Miller
G. R. Woodcock
K. H. Miller
K. H. Miller
G. R. Woodcock
K. H. Miller
K. H. Miller
G. R. Woodcock
Subject
Technology
Cost
DI80-26495-4
KEY TEAM MEMBERS (Continued)
JSC-Management Team
R. Kennedy
W. H. Whittington
iv
Contractor Team
E. A. Gustan
R. L. Olson
G. R. Woodcock
T. Mancuso
D180-26495-4
TABLE OF CONTENTS
FORWARD
KEY TEAM MEMBERS
ACRONYMS AND ABBREVIATIONS
Section 1.0
1.1
1.2
1.3
1.4
Section 2.0
Section 3.0
Section 4.0
Section 5.0
Section 6.0
Secti()n 7.0
Section 8.0
Section 9.0
Section 10.0
Section 11.0
Section 12.0
Section 13.0
Section 14.0
Section 15.0
Section 16.0
Section 17.0
Section 18.0
BOOK 1 OF 2 --- -=-:~.:.....;:.....:::..;;.~--------,-,----"---INTRODUCTION AND BACKGROUND
Background
Program Objectives and Assumpti()ns
Study Purpose and Scope
Document Purpose
SUMMARY OF TRADES AND OPTIONS
MISSION ANALYSIS
CONSTRUCTION ANALYSIS
FLIGHT SUPPORT FACILITY ANALYSIS
SATELLITE SUPPORT FACILITY ANALYSIS
CREW CONSIDERATIONS
REFERENCES
BOOK 2 OF 2
ORBIT ALTITUDE SELECTION ANALYSIS
ELECTRICAL POWER SYSTEM ANALYSIS
ENVIRONMENT AL CONTROL/LIFE SUPPORT SYSTEM ANALYSIS
COMMUNICATIONS AND TRACKING SYSTEM ANALYSIS
STRUCTURAL DYNAMICS ANALYSIS
CONTROL DYNAMICS ANALYSIS
SOFTW ARE AND DATA PROCESSING ANALYSIS
PROPULSION AND PROPELLANTS ANALYSIS
SUBSYSTEM INTERRELATIONSHIPS ANALYSIS
SYSTEM DESIGN/OPERATIONS ANALYSIS
PROGRAMMA TICS AND DEVELOPMENT ANALYSIS
REFERENCES
v
AAP
AC
ADM
AM
APC
APSM
ACS
ARS
ASE
BIT
HITE
CAMS
C&D
C&W
CCA
CCC
eEl
CER
CF
CMG
CMD
CMDS
CO2 CPU
CRT
dB
DC
DCM
OOT&E
DOD, DoD
OT
DM
OMS
DSCS
D180-26495-4
LIST OF ACRONYMS AND ABBREVIA nONS
Air lock Adapter Plate
Alternating Current
Adaptive Delta Modulation
Air lock Module
Adaptive Predictive Coders
Automated Power Systems Management
Attitude Control System
Air Revitalization System
Airborn Support Equipment
Built in Test
Built in Test Equipment
Continuous Atmosphere Monitoring System
Controls and Displays
Caution and Warning
Communications Carrier Assembly
Contaminant Control Cartrige
Critical End Item
Cost Estimating Relationships
Construction Facility
Control Moment Gyro
Command
Commands
Carbon Dioxide
Computer Processor Units
Cathode Ray Tube
Decibles
Direct Current
Display and Control Module
Design, Development, Test, and Evaluation
Department of Defense
Docking Tunnel
Docking Module
Data Management System
Defense Satellite Communications System
vi
ECLSS
EDC
EEH
EIRP
EMI
EMU
EPS
EVA
EVC
EVVA
FM
FMEA
ftc
FSF
FSS
GN&C
GEO
GHZ
GPS
GSE
GSTDN
GFE
GTV
HLL
HLLV
HM
HMF
HPA
HUT
Hz ICD
IDB
IOC
IR
D 180-26495-4
LIST OF ACRONYMS AND ABBREVIA nONS (Cont.)
Environmental Control/Ufe Support System
Electrochemical Depolarized CO2 Concentrator
EMU Electrical Harness
Effective Isotropic Radiated Power
Electromagnetic Interference
Extravehicular Mobility Unit
Electrical Power System
Extravehicular Activity
EVA Communications System
E VA Visor Assembly
Flow Meter
Failure Mode and Effects Analysis
Foot candles
Flight Support Facility
Fluid Storage System
Guidance, Navigation and Control
Geosynchronous Earth Orbit
Gigahertz
Global Positioning System
Ground Support ~quipment
Ground Satellite Tracking and Data Network
Government Furnished Equipment
Ground Test Vehicle
High Level Language
Heavy Uft Launch Vehicle
Habitat Module
Health Maintenance Facility
Handling and Positioning Aide
Hard Upper Torso
Hertz (cycles per second)
Interface Control Document
Insert Dr ink Bag
Initial Operating Capability
Infrared
vii
IVA
J5C
KBPS
KM, Km
KSC
Ibm
LCD
LCVG
LED
LEO
LiOH
LM
LPC
LRU
LSS
LTA
LV
Ix
MBA
rnbps
MHz
MMU
MM-Wave
MOTV
MRWS
MSFN
N/A
NBS
NSA
N
NiCd
NiH2
Nm, nm
N/m2
D 180-26495-4
LIST OF ACRONYMS AND ABBREVIA nONS (Coot.)
Intravehicular Activity
Johnson Space Center
Kilo Bits Per Second
Kilometers
Kennedy Space Center
Pounds Mass
Liquid Crystal Display
Liquid Cooling and Ventilation Garment
Light Emitting Diode
Low Earth Orbit
Lithium Hydroxide
Logistics Module
Linear Predictive Coders
Lowest Replaceable Unit
Life Support System
Lower Torso Assembly
Launch Vehicle
Lumens
Multibeam Antenna
Megabits per second
Megahertz
Manned Maneuvering Unit
Millimeter wave
Manned Orbit Transfer Vehicle
Manned Remote Work Station
Manned Space Flight Network
Not Applicable
National Bureau of Standards
National Security Agency
Newton
Nickel Cadmium
Nickel Hydrogen
Nautical miles
Newtons per meter squared
viii
OBS
OCS
OMS
OTV
PCM
PCM
PEP
PIDA
P/L PLSS
PM
ppm
PRS
PSID RCS
REM
RF
RFI
RMS
RPM
SAF
SAWD
scfm
SCS
SCU
SEPS
SF
SM
SOC
SOP
SSA
SSP
SSTS
STAR
D 180-26495-4
LIST OF ACRONYMS AND ABBREVIATIONS (Coot.)
Operational Bioinstrumentation System
Onboard Checkout System
Orbital Maneuvering System
Orbital Transfer Vehicle
Pulse Code Modulation
Parametric Cost Model
Power Extension Package
Payload Installation and Deployment Apparatus
Payload
Portable Life Support System
Power Module
Parts per Million
Personnel Rescue System
Pounds per Square Inch Differential
Reaction Control System
Reoentgen Equivalent Man
Radio Frequency
Radio Frequency Interference
Remote Manipulator System
Revolutions Per Minute
Systems Assembly Facility
Solid Amine Water Desorbed
Standard Cubic Feet per Minute
Stability and Control System
Service and Cooling Umbilical
Solar Electric Propulsion System
Storage Facility
Service Module
Space Operations Center
Secondary Oxygen Pack
Space Suit Assembly
Space Station Prototype
Space Shuttle Transportation System
Shuttle Turnaround Analysis Report
ix
STDN
STE
TBD
TDRSS
TFU
TGA
TIMES
TLM
TM
TT
TV
UCD
VCD
VDC
WBS
WMS
DI80-26495-4
LIST OF ACRONYMS AND ABBREVIA nONS (eont.)
Spaceflight Tracking and Data Network
Standard Test Equipment
To Be Determined
Tracking and Data Relay Satellite System
Theoretical First Unit
Trace Gas Analyzer
Thermoelectric Integrated Membrane Evaporation System
Telemetry
Telemetry
Turn tab Ie /Tilttab Ie
Television
Urine Collection Device
Vapor Compression Distallation
Volts Direct Current
Work Breakdown Structure
Waste Management System
x
8.0 ORBIT All TITUDE SELECT1[ON ANALYSIS
8.1 ATMOSPHERE MODEL. 8-1
8.2 ORBIT DELAY TIME. . 8-1
8.3 PROPELLANT CONSUMPTION
8. 11 ORBIT ALTITUDE SELECTION 8-7
01S0-26495-4
S.o ORBIT ALTITUDE SELECTION ANALYSIS
B.1 ATMOSPHERE MODEL
Four atmosphere illodels were useLI in derivin\:j the orbit decay data, see Fiyure
Cl-I. The nominal model is the u.s. Standard Atmosphere, 1976. The other three II10deis were ~enerated vii!. tile quick-look density mOllel in At->t->e.ndix B of
NASA docUlilt:nt SP-S021, Models of Earth's Atmosphere (9U to 2~UU kill), for a
latitude of 00 This 1II0del calculates an exospheric temperature. i\ data
tab 1 e is then used to obta i n the lo!:) of the atmospheri c dens ity for the
desired altitude(s) for the calculated temperature. The NASA Neut ral dnll
Short Time Maximulll Models use val ues suggested for space shuttle studies. Hie
NASA Neutrdl Model is a high solar activity model, wittl a value of 23U for the
Inean lO,,] Cill solar flux and a geomagnetic index (Ap) of 20.3. The dSSUIlied
local lillie is U~UU hours. nil! Short Time IViaximUlIi IVlodel uses a h.l.7 crn solar flux of 23U, a geomagnetic index of 400, and a local time of 140U rlOurs.
These conditions would occur only for a tilile of 12 to 36 hours durill~ an
extreilleiy 1 ar~e Illagnet ic stonn. The IVli nillluHl l"Iodel uses fi gures of o~uu for
the IOCdl tillie, 7;).3 for the lU.7 CIII solar flux, and 10.9 for the ~eolllagnetic
index. The sol ar f1 ux and geomagnetic index fi gures are the 97.7 percent i Ie
fi~urt.:s for June 1%7 from tile IVldrshal"1 Space FI ight Center predictions.
The "NASA neutral" is considered to be the ~wrst long-term or continuous case
af)plicable to the 90-day resuf)ply cycle. The short-time maxilflufll \1ill be used
to estdbl ish thrust levels needed for control authority in all situations.
8.2 ORBIT DECAY TIME
Altitude Selection is based on maintainin\:j a minimum orbil: decdy tilfle of ~ll
days if no orbit maintenance occurs.
,--Tile velocity \JdS cdlculateu using V =; M x WUU Wflere M is the ~rdvitdtiollal rr
8-1
D 180-26495"-4
10'""12 12 ..
5xl0'"" - ....
21m 250 300 350 400 450 ALTITUDE IN KILOMETERS
Figure 8-1. Atmosphere Density Models
8-2
0180-26495-4
coefficiellL, eljuul LO 3~(5,6U1.2 krn3/secL, r is the rddius of the orbit, 1I1(~asured frolll the center of the Earth in kilometers, and the lOUO is a
cOllversion factor to yet the results in meters/sec.
COApV 2
Dray was calculated by f = 2 " where Co is the dray coefficient, A is the fronta 1 area in meters, pis the atmospheri c dens i ty in ky/m3 dno Vis the
velocity.
Mr COAp (8.64 x 107) The decilY rate \~as obtdined from the formula D = M ~~here CO' A, p dre as previously designated, M is the mass of the SOC in k~, dnd d.G4 x lU7 is the conversion factor to yet the results in kmjddY.
The decay tiliie was calculated from Q,o. =: Q~-l + (~ + ~) H Hhere l\ is the dl!Cay rilte at altitude x and H is the differencBA"Ot Bte t~JO altitudes. The SOC dldraneristies used in this set of calculations are Co = 3.0, A = 300m2, M = lUU,OUOky, and I = 23U sec. sp
Fi~ure 8-2 ShOHS the dltitude requirelnent as a function of atmosphere IIlodel.
The fi~ure is based on a lIledn CdA of 1800 square meters and a SOC mass of IUU
tonnes. Since the dctUd 1 SUC lIIass wi 11 pr'obab ly exceed th is fi yure, the curve
is slightly conservative.
F i yure 8-3 sho~~s atlflospheri c dray versus a 1t i tude for the four IIlode 1 sand
Figure 8-4 shows the orbit decay ranye. (Fiyure 8-2 was derived by numericcll
i nte'Jrat i on of Fi yure 8-4.)
8.3 PROPELLANT CONSUMPTION
Fi~ure 6-b shows the prOPellant consumption \~ith the decay altitude lilll"iL
superililposed. Propell ant consumption was based on the use of Illonopropell ant
IlytlruLine ilt a specific impulse of L3U sel.:.
The jJrope 11 ant usaye was equal to 86400f 9 Isp
8-3
where f is the dray force in
z : Hllil =: ;; 50 :::~. I--
>--< tj 10 o 5-I--
ill 0: o
D180-26495-4
., !
NOMINAL
I
1..1-L1.l 2013 2513 3013 3513 41313 450
ALTITUDE IN KILOMETERS
Figure 8-2. Orbit Decay Time lIS. Altitude
8-4
D 180-26495-4
1I:l0 ~-. 1 so : ,,~... ,
~ ,,~'-...'
f !
"I
" ,........... l
',"":::::--.... ; I , ..... '-.... .... J........; . I ' --..... : .',' "~'''''''''''''_i ' . ..... , ................ ; 1 .... , ; ............ : -...;-. I
, "'-" ~!-.. ... -.. '1- ... _--~ ".....,......:-_.;! - .. - . ......... --.. .... ...... ... ~: gj .S:: "i -..' --_ '~SHORT " --., ----. --.. ...... ~ U : ".... ... I : TIME .... ~-. ! .... .... i -.. .... ~ . MAXIMUM f.5 I ..... ' --...~ :I: .1 :~.....: --'''SNASA 5; ~: . ~ 1 .......... "' : .. : NEUTRAL ! .. os r. ' ! ... , ~ t~.. i! . ! ... .... ... ... ... ,. ~ NOMlHAL
, I : l' I .... ' .. 01 ~:: 1 , ' l' '. . '1' " .... '1 ... '" . .~ -. I, I .. ... ' .
~05 ELl.LLLLLL ,J,.LL,!. "J.LL:J .. LJ .. _LL .... LL -1. LL.L1J.::1;iMINlMUM 200 250 300 3S0400 450
ALTITUDE IN KILOMETERS
Figure 8-3. Atmospheric Drag vs. Altitude
"--r'" .. HlO ~ '. 50 .. ,,~.... ,
::.,~.
z ....
" ..... ~" ' ........ ,,:.-" .....,; .......................... ........ '...... ..... ............ '""to ..... ---..
...... ......-.. ..... .... ........ -...
' ........ ~ .... -....:. ... _--_. "-..... ...... . . ~ -''' ..... - -...... ':.: SH(Rf ........ . ............ ... ... __ = TIME
.... ..... -.. - _ . : MAXlMUN .......... : ' - -.......... -
....... -_.NASA ........ NEUTRAL
5 =--
t; . 1 m .. 05 -o
.... .... ........ ........ NOMlHAL
.... .... ........
...... '" .: 1 l..l I LI'j MINlMUN
.. 01 .--, i I .,105 LL!J J LJ ,1...1 l.L.LJ LLL.L.LL .. .1 l.lLL[
200 250 300 350 400 4S0 ALTITUDE IN KILOMETERS
Figure 8-4. Orbit Decay Rate vs. Altitude
8-5
D180-26495-4
IIOC39I
r"-' ".--" . -." .. -.-~
t; 10 . , =< 5 ...... - .. ...J r-' .J W n. 0 a:: n.
"- ... .... .... .... ' ...... NOMINAL ...
.5 ~ r- -~-
1 LLI .1 i
. i: 1 .. ..;. . "-.; ~.:.. ...... --, . .L .. I .. LL I .. L_L .. Li.Li.l_L--L. 1LL1._L1..1 . .1-.L .. LL.L:'l=l~ MINIMUM
200 250 300 350 400 450 ALTITUDE IN KILOMETERS
Figure 8-5. Propellant Usage vs. Altitude
8-6
D1()U-2b4~!:>-4
newtons, y is the dcceleration of grdvity, 9.81 m/secL , lsp is tile specific
impulse of the IIlotors, and 8G,400 is the conversion factor to yet the resuits in k.y/ddY.
A resu(Jply reL\uirement of LL k'::J/day has been defined based on tilis curve, with
2k'::J/day added for atmosphere makeup (from hydrazi ne decompos it i on) and a lU,o
lIlar~jin on the NASA neutl~al atmosphere point. The nominal resul-lply reL\uirelfient willi be somewhat less.
8.4 ORBIT ALTITUDE SELECTION
The selected orbit altitude is 37U km, as this is the altitude the shuttle Cdn
reach ~Jithout OMS kits. This provides the maximum payload bay lenyth
capabil ity. The mission II10dei analyses show tllisto be extremely ililP0rL.dllL.
During per"iods of hi'::Jh solar activity, the altitude will be raised to 4UO kill.
There are several operational options available to deal with the possibility
of needing full shuttle payload bay when the SOC is above J70 km.
The Y'esuPf.lly requireillent tldS been set at L2UU kg for' lUU days in sizin~ the
10!;jistics module. This requires only one ring of six 1.12 HI ,4411) tanks on tile "logistics Inodule.
&-7
9.0 ELECTRICAL POWER SYSTEM ANALYSIS
9.1 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . 9-1
9.2 ELECTRICAL LOADS DATA 9-1
D18U-l6495-4
9.0 ELECTRICAL POWER SYSTEM ANALYSIS
9.1 INTRODUCTION
Thl~ bu I k of the e I ectri Cd I power systeill ana lys is datd is inc 1 uded in the SUL
System Uefinition Report (Boeiny - 19) under WBS 1.2.2.1.7 so it is not
repeated herein. Section 9.2 gives the lower-level electrit:al 10dd tables.
Weiyht pendlty calculations are found in the Data Book (Boeing - ill.
9.2 ELECTRICAL LOADS DATA
Table 9-1 ::liVeS tile eleccrical "load sUllllllary. Tile life support e4uipment IOdds
~vere taken frolll Table B in WBS 1.2.1.1.13 in the SOC System Definition f{eport
(Boein,::)-19). The other subsystem electrical loads are detailed in Table l!::!-i.
9-1
SOC-1117
Table 9-1. Electrical Load Summary
REFERENCE CONfiGURATION INTERMITTENT LOAD
SUNLIGHT OCCULTED POWER
AC DC AC DC AC DC
LifE SUPPORT 19W 10,209W 6,565W 2,61 OW 3,85OW 3,75OW COMMUNICATIONSffELEMETRY 9,370W 9,270W DATA MANAGEMENT SYSTEM 1,OOOW 1,OOOW PROPULSION SYSTEM 200W 200\'\I t::J THERMAL CONTROL SYSTEM 2,00OW -2,00OW 00
CONTROL SYSTEM* 250W 250W 0 I N .. ICAL POWER 0\ ~
LOADS 12,50OW 4,500W \0 VI \J:) BATTERY RECHARGE 29,900W
I i ~ N
TOTALS 19,91gw 51,429W 19.365W 19,83OW 3,85OW 3,75OW
* 1 KW STARTUP - 6 HR {CAN BE SUPPORTED BY LOAD DIVERSITY)
[ .! ",,,,,,;,~ l;;;;~'" I I I I > 0 (.) 112 SOC CONFIG CONFIG 0 Z w w w 0 . .-,~-- 0 C) l- s: I- ~ I- w Z a: a: CC-n32 ::t: i= w C) ;- Z C) ..J S1 ..J 12 ...J 0 ::IE w :::; ::l ...J ::l ...J ::l DIST. ...J ::IE w 0 Z (.) Z
~ Z g FROM
10.0 EeLS AND EVA/IVA STUDIES
10.1 VENTILATION CONCEPTS STUDIES. . . . . . . . . . . . .. 10-1
10.1.1 Forced Convection Level Required to Simulate Free Convection 10-1
10.1.2 Use of Ventilation Direction to "Simulate" Gravity. 10-1
10.1.3 Flow Required for Cabin Heat Rejection . . . . . 10-2
10.1.4 Clean Air Supply Ducts vs. "Dirty" Air Return Ducts 10-3
10.1.5 Ventilation During SOC Buildup . . . . . . . . 10--5
10.1.6 Summary Description of the Selected Ventilation Concept. 10-6
10.2 EMERGENCY PERFORMANCE LEVEL DEFINITIONS. 10-7
10.3 CABIN PRESSURE ASSESSMENT . . . . . . . . . . . . . 10-10
. 10-11 10.3.1 Factors Influencing Selection of Cabin Pressure ....
10.3.2 The Effects of Selected Cabin Pressure on ECLS System
Com ponents II............... 10-16 10.3.3 Conclusions Regarding Selection of Cabin Pressure. . 10-18
10.4 REDUNDANCY PHILOSOPHY .... 10-22
10.5 MAINTENANCE CONCEPT DEFINITION 10-24
10.6 EVALUATION OF SELECTABLE CABIN TEMPERATURE AND CABIN
TEMPERA TURE BAND EXPANSION . . . .
10.7 ECLS SUBSYSTEM SELECTION RATIONALE ...
10.7.1
10.7.2
CO2 Removal Subsystem Concept Selection.
Wastewater Processing Concept Selection ..
10-33
. . . . 10-36
. . 10-36
10-50
D180-26495-4
10.0 EeLS AND EVA/IVA STUDIES
10.1 VENTILATION CONCEPTS STUDIES
10.1.1 Forced Convection Level Reguir!d To Simulate Free Convection
Manis physiology is equipped to reject body heat and moisture without wind across his body, providing he is in the earth's one gravity atmosphere. The effect of gravity is to induce a quantity of convective heat transfer and air mass transfer, driven by the change of density occurring near the surface of the body. This convective force is not present at zero gravity, making necessary an artificially induced convective ventilation in order to simu-late the free convection which is lost. This phenomenon has been evaluated and lived with in all previoUls spacecraft, and a fan induced average velocity of 25 feet/min has evolved as the accept-ed ventilation design value for spacecraft.
10.1.2 Use Of Ventilation Direction To "Simulate" Gravitl
Man's physiology and geometry are configured to reduce the likeli-hood of eye damage or choking from loose objects, such as some-th'ing dropped while eating or dropped from the hands. The eyes and mouth are "up", and things nOY'mally fall the other way, "down". In a zero-gravity environment this characteristic of getting things to fall dO~'1n may be partially simulated by util-iz~ing a ventilation system which has 'its cabin airflow descend from ceiling to floor. This concept has been selected for SOC.
However, it is not practical that the 25 feet/min ventilation vel~ocity of the previous paragraph be entirely made up by this dov~nward flow. Every air jet or anemostat is in effect the pri;mary nozzle of an ejector which induces many ,m,ultiples of secondary flow into its flow pattern. This in turn results in a circulation pattern where flow is concentrated in a downward, direction under the anemostat, proceeds down toward.the floor, and then circles back toward the anemostat and around again to rejoin the downward flow. The net flow is downward. but locally there is increased velocity in the down direction under the outlets, and in
10-1
0180-26495-4
an up direction between the outlets. For SOC, the primary flow of
the vent supply anemostats ;s sized by the flow required to pass
through the heat rejection heat exchangers in order to maintain
cabin temperature, as discussed in the next paragraph. If a
downward velocity of 25 ft/min were incorporated, the power con-
~umption of the ventilation system would be about 3 to 4 times the
selected baseline power requirement.
10.1.3 Flow Required for Cabin Heat Rejection
There are two choices in selecting the quantity of airflow which
is to be cooled in the heat rejection heat exchangers. One way is
to use 40F coolant fluid through the heat exchanger and calculate
the airflow required to transfer the heat load. The 40F value is
selected as the lowest feasible temperature to avoid freezing in
the coolant water to freon heat exchanger. In thi s case, there
would be condensation in the cooling heat exchangers, due to the
coolant being below the desired cabin air dew point. The moisture
thus removed would be collected at each heat exchanger and pumped
to the water processing system. The relative humidity of the air
leaving these heat exchangers would be excessive, since the air
would be essentially saturated. Also, when this method of select-
ing the airflow to be cooled in the heat rejection heat exchangers
is utilized, the resulting airflow is too low for use as the
primary anemostat flow to provide the required 25 ft/min local
velocity in the cabin. Additional cabin air circulating fans
would be necessary to raise the cabin air velocity to the required
level. The above method of selecting airflow for the heat rejec-
tion heat exchangers was not selected because of the complexity of
removing moisture at each heat exchanger, and the complexity of
additional circulating cabin air fans.
The other way in which cabin airflow through the heat rejection
heat exchangers can be sel ected was used in the SOC basel i ne
system of this report. In this case, the coolant fluid is con-
trolled to 55F entering the heat exchanger, rather than 40F as
described in the previous paragraph. This prevents condensation
of moisture present in the cabin air by keeping metal temperatures
10-2
D180-26495-4
over the dew point, and eliminates the problems of separating,
collecting, and pumping water, at each heat exchanger, as wel"' as
eliminating the possibility of fog generation at the cabin supply
anemostats. It also provides adequate primary flow in the cabin
supply anemostats to efficiently provide the desired cabin air
velocity.
Both of the above methods of selecting cabin air heat rejection
airflow were evaluated as part of the Space Station Prototype
(SSP) program, and the second method was selected. There is no
significant difference in requirements for SOC which would indi-
cate that the selected concept for SSP should not be the preferred
concept for SOC.
A schemat"ic of this ventilation concept, as selected for SOC, is
shown on Figure 10-1. Note on the figure that the principle of
IIdo~lnward" net airflow of Section 10.1.2 is accomplished by air
supply anemostats in the ceiling, supplemented by local adjustable
anemostats in accordance with the detailed floor plan (such floor
plan details will become evident later in the SOC development).
These supply anemostats are fed from a common plenum over the
ceiling, which in turn is fed by the sum of flow leaving the
temperature control heat exchangers plus the flow leaving the air
revitalization packs. The tE!rm "air revitalization pack" is used
here to describe the equipment group which includes the functions
of removal of humidity, CO 2 ' odor, and trace contaminants. De-
tails of this equipment group are summarized in WBS 1.2.1.1.13.2
in Boeing-19. The term "ventilation and temperature control" pack
is used to describe the equipment group which includes ventilating
airflow fans, particulate filtration, heat rejection heat exchan-
gers, and appropriate sound suppression baffling, as described in
WBS 1.2.1.1.13.1 in Boeing-19.
10.1.4 "Clean Air Supply Ducts vs. "Dirty" Air Return Ducts"
Another choice in design of the ventilation system is the way in
which odor and moisture sources are handled. A supply of "fresh"
air could be specially ducted to the toilet area, for example, or
10-3
0180-26495-4
a r'eturn duct carrying IIdirty" air from the odor source could be utilized. The only reason for considering the "fresh" duct option is that d shorter, reduced volume duct could possibly be selected for baseline, in spite of its potentially larger duct volume. Most
of the increased odor and moisture control duct volume will be in the overhead plenum on SOC, and it is presumed that SOC is a second generation spacecraft where such personal anemities as odor control should be! considered. No trade-off on quality of living is pos-sible, but the selected concept of controlling local odor and humidity sources appear to be common sense. In any case, the volume difference between these duct options is not a major matter, and furthermore an exact calculation of the difference in vol ume
between the two concepts is impossible.
10.1.5 Ventilation During SOC Buildup
It is not currently envisioned that thE! SOC will be permanently
inhabited until all baseline modules are in place. However, during the buildup sequence the crew may pressurize and enter the service module from the Shuttle. The service module will have its own power. Limited heat rejection will be provided by the battery and power conditioning equipment radiator. Humidity, and CO 2 control can be provided by using a snorkel line from the Shuttle air revita-
lization system. This capability (48 cfm) is a standard capability of the Shuttle for use with the Space lab. Some thermal control is also provided by this air f'low. Only one of the service module ventilation fans would be needed to provide minimum acceptable air mixing and air velocity for cooling.
After the first habitat module is in place the half SOC config-
uration will have an operational EClS system. No air flow mixing between the Shuttle and the habitat is required. The Shuttle must remain attached to provide adequate safety in case the habitat must be evacuated.
10-5
0180-26495-4
10.1.6 Summary Description Of The Selected Ventilation Concepts
The selected ventilation concept was shown schematically on Figure
10-1. Local anemostat detail s will not become apparent unti 1 an
actual design phase.
One major air recirculation path shown on Figure 10-1 consists of
return grills in the floor leading to an under floor plenum, with
two large vertical return ducts (approximately one square foot
each) connecting the under floor plenum with the ventilation and
temperature control packs in the overhead plenum. Each of these
ducts supplies one IIdouble ll vent pack in the overhead plenum.
These IIdouble ll packs each contain two independent temperature
control systems as are described in detail in WBS 1.2.1.1.13.1 in
Boeing-19. A half of one of these double ventilation and temper-
ature control packs is also utilized independently at each end of
the service module, as shown on Figure 10-1. In other words there
are four ventilation half packs in each habitat module (in two double units), and two other half packs in each service module,
making a total of six per half SOC or twelve per full SOC. This
a p pro a c h pro v ide sma x i mum co mm 0 n ali t y 0 f h a r d war e and imp r 0 v e s
reliability compared to the option where separate vent packs would
be sized for the habitat module and the service module.
Another air circulation path shown on Figure 10-1 consists of the
flow of dirty. odorous, or wet air taken from areas of contami-
nation, and ducting to two air revitalization packs arranged in
series in the overhead plenum. The suggested source areas shown on
Figure 10-1 include the shower, toilet, suit storage area, and the
remote end of the service module for contaminant control in the
service module. Roughly 5 percent of the total habitat module
supply airflow passes through the contaminant removal packs, so
that it takes 76 minutes for them to pass an airflow equal to that
of the entire cabin volume.
The total habitat module cabin supply airflow of 2440 CFM enters
the cabin through anemostats placed several feet apart at inter-
vals in the ceiling, and through adjustable anemostats placed as
10-6
D180-26495-4
dictated by the final design. The velocity of these cabin supply
airflow nozzles will generate an induced secondary airflow approx-
imately 4.5 times the primary flow. The resultant total flow is
adequate to provide an induced flow of 25 ft/min local velocity.
of '''hich the average up flow is 25 ft/rnin and the average down
flow is 32 ft/min, resulting in a net down flow down of 7 ft/rnin.
The induced flow performance of the primary airflow system select-
ed for SOC is based on studies and development activities per-
formed as part of the SSP program.
Figure 10-1 considers the baseline floor plan for the habitat
mod u 1 e con sis tin 9 0 f a sin g 1 e 1 0 n g i t u din a 1 floor. Ot her 0 p t i () n a 1
floor plans include "baloney slice" floors for at least a portion
of the module. As far as the ventilation concept of this report
is concerned, it is recommended that the basic concept resented be
used regardless of the floor plan selected. Obviously the imple-
mentation of the ventilation system is easiest with a single
longitudinal floor, and this is certainly one of the advantages of
such a floor plan. If other factors should predominate, and a
baloney slice floor plan is adopted, the ventilation duct system
becomes more complex and difficult to visualize. The basic flow
pattern from ceiling to floor should be preserved where feasible.
10.2 EMERGENCY PERFORMANCE LEVEL DEFINITIONS
A SOC requirement imposed by NASA in document NASA-6 directed a
fail operational/fail safe design criteria. This criteria, with
minor excE~ption has been retained. This minor exception is that
the "operational level" has been assumed a level which provide an
acceptable performance for a 90 day period. In order to meet this
safety requirement it is believed that no single failure of ECLS
equipment shall force abandonment of a habitat module. This
establ ishes the basic requirement for dual radiators, dual radi-
ator transport loops, and dual atmosphere supply and processing.
Each of these dual systems is not capable by itself to maintain
10-7
0180-26495-4
the excellent environment referred to as the lIoperationalll per-
formance level, since the result would be an unnecessarily large
vehicle penalty. Instead, it will take both of the dual systems
operating together to produce the lIoperationalll level. One of the
dual systems operating will produce a 1190 day acceptable ll envi-
ronment. By these steps of logic it is possible to design a
system which is fail operational (acceptable)/fail safe and which
imposes a minimum penalty to the vehicle. The performance level
capability of the EelS system is summarized on Table 10-1.
Referring to Table 10-1, note that the lIoperationalll performance,
which results without system failure and with the normal habitat
modul e crew compl ement of 4, is what coul d be descri bed as an
excellent environment. This performance can be maintained in
steady state for all mission activities of the 4 crew members.
More than 4 crew members in that habitat module will not cause a
noticeable reduction in the quality of the environment for rela-
tively short duration activities such as meals or meetings.
Neither will there be a noticeable reduction in environment qual-
ity for longer periods if the activity level is low, such as 8 men
sleeping. However, more than 4 crew members in the habitat module
continually, with full activity level, wash, shower, cooking, etc,
can cause the performance level to approach the 1190 day, acceptable ll
level. The table shows that this same 1190 day acceptable ll perfor-
mance level can be maintained with a 4 man complement after a worst
single non-maintainable failure in that module. This capability
enables the system to meet the fail operational criteria of not
having to abandon the habitat module with a worst single failure.
If the failure such as a major fire or major breach of the cabin
wall, has forced abandonment of a habitat module the entire crew
will be in the remaining habitat. In this situation the reduced
level of performance capability is still 1190 day acceptable ll As
shown on Table 10-1, 8 man capability is provided for at least 300
10-8
..... a I \0
TABLE 10-1
ECLS PERFORMANCE LEVEL REQUIREMENTS
Parameter
CO2 Partial Pressure
Temperature
** Dew i'~}int Temperature
ventilation
Wash Water
*** 02 Partial Pressure
Total Pressure
Trace Oontaminants
Units
mmHg
OF
OF
ft/min
1bj."roan day
psia
psia
Maximun number of crew per habitat without failure in each habitat
Maximum number of crew per habitat with worst single non-maintainable failure in that habitat
:190 "(perational" Acceptable"
3.8 max 7.6 max.
65-75 60-85
40-60 35-70
15-40 10-100
40 min 20 min
2.6 or 3.1 2.4-3.8
10.0 or 14.7 10.0-14.7
**** **** 24 hr. indo stld. 8 hr. indo stld.
4 8
NA* 4
;;300 Hour Emergency"
12 max
60-90
30-75
5-200
o
2.3-3.9
10.0-14.7
**** 8 hr. irrl. st'd. 12
8
*Acceptable level is adaquate to meet a "fail operational" reliability criteria.
**In no case shall relative humidities exceed the range of 25-75%.
***In no case shall the 02 partial pressure exceed 26.9% or be below 2.3 psia.
****hr. indo stld. = hour industrial standard
o -co o I
N 0'1 ~ ~
0180-26495-4
hours at the "300 hour emergency" level with a single worst non-maintainable failure after the crew has abandoned one habitat. It should be noted that a single habitat has a 12 man capability at the levels shown in the 300 hour emergency column without a time limit if no EelS equipment has failed.
The design point used to size any particular EClS subsystem ;s generally found in one of the columns and that subsystem will exceed the required performance of the other two columns. There al so are subsystems which exceed the fail operational (accept-able)/fail safe design criteria because of redundance dictated by the requirement that no single non-maintainable failure shall cause evacuation of a habitat.
The performance levels listed on Table 10-1 were arrived at by establishing the lowest performance level that could be tolerated for the respective continuous 90 day and 300 hour day time per-i 0 d s
The specific values are a result of years of study. Information from actual flight experience (Apollo, Skylab, Gemini, etc.) and space station study programs 1 ike the Space Station Prototype (SSP) have been used to define the values shown. These values also have been discussed and reviewed with NASA/JSC during the conduct of this SOC study.
10.3 CABIN PRESSURE ASSESSMENT
The baseline SOC cabin pressure for purposes of this study is 14.7 pSia. but there are many factors which would favor the selection of a lower cabin pressure, as discussed in the following Section 10.3.1. However, selection of a lower cabin pressure has adverse e f f e c ton the s i z e , wei g h t , and power con sum p t i on. 0 f c e r t a i n portions of the EelS, as discussed in Section 10.3.2. An overall conclusion regarding the factors affecting cabin pressure selec-tion is presented in Section 10.3.3.
10-10
0180-26495-4
10.3.1 Factors Influencing Selection Of Cabin Pressure
~)xia - One factor to be considered in selecting cabin pressure
is avoidance of hypoxia, or reduced brain function, caused by low
partial pressure of oxygen. Due to the fact that the majority of
the earth1s inhabitants live below StOOD feet, the maximum con-tinuous altitude at which body functions are measurably affected
is not clear. A partial pressure of oxygen in the cabin corres-
ponding to 4.000 feet or less would certainly be desirable, and is
considered a requirement by NASA ("Medical Science Position on
Space Cabin and Suit Atmospheres" Position paper by NASA JSC/SD,
May 1980). Although an altitude as high as 8,000 feet equivalent OXYgen level is considered to be an acceptable level for commer-
cial aircraft pressurization.
Flammabil i"!'y - Another major factor to be considered in selecting
cabin pressure is flammability of materials. The fire danger is
relalted to the percent oxygen PTesent in the cabin atmosphere.
The normal sea level oxygen concentration is 21 percent, and certainly a concentration this low in the SOC cabin would be
desirable from a flammability standpoint. Only one major material
used in Shuttle, a silicon fiberglass line insulation, has failed
tom e e t fl a mm a b i 1 i t Y t est sat 35 per c e n t O2 , and t his mat e ria 1 will be replaced in later Shuttle vehicles. The cabin pressure
control tolerances of the current Shuttle result in a maximum
normal oxygen concentration of 23.8 percent 2 " A caution and warning light is set on Shuttle to trip at the 25.9 percent level with a 26.9 percent O2 absolute maximum level has been selected for SOC. These same levels are probably going to be inherited by
SOC as the flammability requirement. The relation between flam-
mability and cabin pressure is shown on Figure 10-2.
Eliminating Pre-breathe The pre-breathe period required to
prevent "bends" with the presently ava-ilable 4.1 psi suit is
approximately 4 hours pre-breathe with a 14.7 psia cabin, and approximately 2 hours pre-breathe with an 11 psia cabin. This lost time in pre-breathe can be eliminated by increasing suit
10-11
OXYGEN PARTIAL PRESSURE (PSIA) N N N N w w W
N ~
mr-~--1r-r~------~-------r~------~~------~~------4~ . . . . . .
"'OU'J ::00 trln n U'J ):' U'Jn \:XI c:):' 1-4 ::0 to ":rj z trll-4 1-4
0
Z G) "t! ......
n c: :;0 ..... co
O~ ::0 trJ 0
ZZ trl en ..... I
..... U'JtJ en N
0 H ..... c: trl 0'\
I tJ(f) :;0 10
.s=-..... 0 N trl"tl I trl
C eVA 0
\0
S;:~ N 1-4
()'1
~ PRACTICA 2 TOXICITY ,
8trl "t! ..... .s=-
en N t"' H 1-4 trl L" S OU'J ):' z .pIT CONST zc: 8 U'JH _~ RUCTION
8
..... w
trJ ~ .... 10 o -C g, 1-4
..... ~ ":rj t"' '8 ",. trJ
Z 8
-SEA LEVEL CABIN SHUTTLE
..... I U'I
DI80-26495-4
pressure or decreasing cabin pressure. For SOC where several
EVA's a day will be routine, eliminating pre-breathe is extremely
desirable. The relationship between suit pressure to avoid pre-
breathe and cabin pressure is also shown on Figure 10-2.
~gen Toxicity - The partial pressure of oxygen in a breathable
atmosphere must be limited to avoid toxic effects. The crew is
exposed continuously to the oxygen level in the module, as opposed
to only eight hours per day exposure in the EVA suit. Because of
this, the continuous oxygen cabin limit which can be tolerated in
the cabin is lower than the short duration EVA oxygen limit.
The upper limit of oxygen partial pressure select~d for Apollo and
Skylab cabins was 5 psia, and in the case of Skylab this was for
continuous use. There was some medical evidence of undesirable
oxygen toxicity in these programs, as reported in the literature
("Extravehicular Cre\'Iman Work System Study Program", Final Report,
Vol I I, Con s t r u c t ion , J u "' y 1 98.0 , Con t r act N A S 9 - 1 5 290 R. C
Wilde, Hamilton Standard). There has also been evidence of tox-
icity revealed in tests run since then, but there does not seem to
be a real consensus on the degree of seriousness of these observed
eff,ects. An oxygen concentration as high as 4 psia O2
partial
pressure could probably be tolerated continuously in the SOC
cabin, but this is a moot point because SOC will utilize a two gas
atmosphen~ making this high a PP0 2 unnecessary, as shown on the
left-hand vertical scale of Figure 10-2.
Oxygen toxicity during EVA is a different matter. First because
EVA will occur for an individual crew member for a maximum of
about 25 percent of his total in orbit time, and second because
the atmosphere in the suit will in all likelihood be pure oxygen.
The rei s so m e e v ide n c e t hat 8 . psi a pur e 0 xy g en pre s sur e i nth e suit will result in unacceptable toxicity effects, as described
in the literature (NADC-74241-40, "Physiological Responses to
Intermittl:nt Oxygen and Exercise Exposures", E. Hendler, NADC,
Warminster, PA, 1974). For eight hours a day, a 4 psia level is
generally accepted. The maximum allowable suit level of pure
10-13
0180-26495-4
oxygen level for EVA therefore, probably lies between 4 and 8 psia
but it is not a black or white matter, and considerable difference in tolerance between individuals undoubtedly occurs. A limit of 6 psia is logical since 4 psia is acceptable and 8 psia is not, but it is a tentative limit, not clearly defined. This tentative 6 psia suit pressure limit for pure oxygen is identified on Figure 10 - 2.
Weight of Stored Cabin Pressurization Gas The leakage flow
through any hole or leak in the vehicle pressure wall is directly proportional to cabin pressure. SOC cabin leakage is expected to be about 5 pounds of air a day. Another 5.3 pounds of air per day is expected to be lost in use of airlocks on an EVA day assuming
pump down to 2 psia for a 14.7 psia cabin. This total air loss is made up by oxygen produced from wastewater by electrolysis, and by nitrogen obtained from the decomposition of 9.3 lb/EVA day of hydrazine. Capability for one complete repressurization utilizing stored high pressure gas wei'ghs approximately 750 lb, plus tank-age. The weight of the above varies as follows with cabin pres-
sure:
Design Cabin Pressure
14.7 psia 11 ps i a 9 psia
Resupply Hydrazi ne Required For Nitrogen Makeup Per 90 Days
775 580 474
Stored Repressurization Gas, Including Tankage
1321 989 809
Resupply Water, Including Tankage Required For Oxygen Makeup Per 90 Days
270 202 166
Vehicle Mechanical Strength - Thickness of the SOC vehicle skin is dictated by the need for protection from meteorites and space junk. Reducing the vehicle cabin pressure would therefore not reduce skin weight.
10-14
0180-26495-4
Suit Considerations The EVA suit is presently qualified for a
nominal operating pressure in space of 4.1 psia. There is reason
to believe, however. that this could be raised to 4.5 psia without
significant difficulty. Beyond this, significant suit development
would be required. Certainly a 6 psi suit would be less complex
and more flexible than an 8 psi suit, and certainly it would cost
less to develop in terms of time and money. Although this latter
factor is not considered par'ticularly s"jgnificant in the overall
evaluation, the incredsed safety and dexterity resulting from a 6
psi suit, rather than an 8 psi suit, could be particularly impor-
tant on SOC where construction tasks and other functions of the
vehicle place such emphasis on EVA capability.
A major consideration of an 8 psi suit used at 8 psi gage at sea
level for training and development testing would require the
standby use of a hyperbaric chamber for safety in the event of a
suit pressurization failure. Rapid decompression may rupture
lungs putting air into a pleural cavity. The lung may collapse
and allow air into the blood. Decompression is essential to
reduce bubble size to reduce danger of air embolisum. The highest
suit pressure which does not require such a chamber for sea level
safety is approximately 6 psi.
A 6 psi suit is identified on Figure 10-2 as a IImost practical"
upp,er limit for suit construction purposes, but this is a judge-
ment call and not amendable to exact evaluation.
Adaptabil'ity of "Shelf Hardware!! to Shuttle and SOC - There is an
intangible benefit in utilizing a sea level cabin pressure in that
its h 0 u 1 d red u c e cos t by m a kin g i tea s i e r to uti 1 i z e co mm e r cia 1
items already developed for earth use. This intangible benefit no
doubt was a major factor in influencing Shuttle to be designed for
a 14.7 psia cabin. Unfortunately, the real value of a 14.7 psia
cabin in adapting shelf hardware is of less consequence than was
hoped. Only air cooled electrical equipment items are effected by
cabin pressure, and these are as much effected by the zero-gravity
effect of space as they are by cabin pressure level. The lack of
10-15
0180-26495-4
free convection cooling in space means that new fans will have to
be added anyway to most items which were free convection cooled on
earth. Once these fans are added, it is probably not a signifi-
cant cost increment to select them for the appropriate cabin
pressure. Figure 10-2 shows an 8,000 foot cabin pressure alti-
tude, which is typical of airline practice, for reference, but it
should be pointed out again that this altitude at zero-gravity
poses entirely different equipment cooling problems.
Commonality With Shuttle Cabin Pressure - The rationale being used
to select the final value of Shuttle cabin pressure becomes an
important consideration in sel ecting SOC cabin pressure as well.
since commonality between the two would be extremely desirable, if
not essential. Shuttle cabin pressure selection is not yet firm,
and in the event the final selected value for Shuttle differs from
that considered in this report, this SOC cabin pressure assessment
will require review and possible revision.
10.3.2 The Effect of Selected Cabin Pressure on EClS System
Components
The value of cabin pressure selected for design has many ramifi-
cations, as discussed in the previous section. One of these is
the fact that a lower cabin pressure makes rejection of heat from
the cabin air to the radiator coolant fluid more costly in terms
of system size. complexity, and power consumption. This is be-
cause cabin air is the first stage coolant for rejecting most of
the heat load generated in the cabin. This heat transfer is a
function of air mass flow, not CFM, and therefore reduced air
density increases the power needed to circulate the airflow re-
quired for heat transfer. This study considers a sea level cabin
pressure as baseline. If this hardware were built and developed,
and the cabin pressure were then reduced, the baseline heat rejec-
tion capability of the baseline EClS would degrade as shown on
Figure 10-3. This higher temperature may be undesirable so changes
to the system may have to be made to accommodate lower cabin pres-
sures. These changes need be made only in the components involved
in the cabin air temperature control and ventilation functions,
since :he other EelS systems components are unaffected.
10-16
...:l oet: z 0 H E-t oet: p:: t1l 0.. 0
:E ::> :E H x oet: :E
c... 0
t1l p:: ::> E-< oet: p:: t1l 0.. :E t1l E-t
z H OJ oet: U
85
80 ~
75
70 10
0180-26495-4
.....
~ BASELINE DESIGN POINT, ~
11
. r----~
- 12 13 CABIN PRESSURE (PSIA)
FIGURE 10-3
CABIN PRESSURE AFFECT ON CABIN TEMPERATURE
10-17
...
14 15
0180-26495-4
The simplest change which can be made to the EClS system to com-pensate for reduced cabin pressure would be to increase fan air handling capacity in order to maintain the design value of mass airflow, and accept the power and noise suppression penalty which would occur as a result. Figure 10-4 shows how fan power would increase to hold airflows, and therefore heat transfer, constant. Unfortunately, this solution of increasing fan size to accommodate
a lower cabin design pressure would add significantly to the electric load demand of the EelS. Figure 10-4 shows for example that an increase in power is required per full SOC from 3.6 kw to 6.5 kw, or a delta increase of 2.9 kw. in dropping cabin pressure from sea level to 11 psia. Battery weight needed to provide this
2.9 kw of power on the dark side would weigh 910 pounds. This weight does not include the weight of hydrazine which must be
resupplied to keep an additional 2.9 kw of solar array in' orbit.
An alternate approach would be to redesign all air handling com-ponents of the EClS to maintain required airflow while holding the fan power increase to a minimum. This solution requires larger heat exchangers. filters, and distribution air ducting, as well as larger fans. The result of a family of such system designs is shown on Figure 10-5. Note on this Figure that the fan power delta ;s now only 1.9 KW in going from a sea level to 11 psia cabin. This is preferable to the 2.9 KW delta which results from changing only the fans, as shown on Figure 10-4. This lower power penalty is obtained by increasing the size of other air handling components in the system by 28 lb. and 1.7 ft 3
10.3.3 Conclusions Regarding Selection Of Cabin Pressure
It is beyond the scope of this study to recommend the design value of cabin pressure which should ultimately be selected for SOC, but a "suggested" value is presented in this Section. As the preced-
ing sections have pointed out, there are so many diverse factor to consider that the final selection is a difficult compromise. The following is a set of individual conclusions which may be reached concerning these factors:
10-18
u o Ul
a: r.J Po.
0:: r.J 5
2 :z /I( r... ...:I
~ 4
r.J Ul <
D180-26495-4
80~----~------~-----r CONSTANT CABIN
TEMPERATURE
~ 60~--------r-----l~~------~--------~------~ u :z .... a: r.J
~ Po.
:z ~
~ r.J U
40~--------+-----'---r--~~~r-------~--------~
BASELINE DESIGN POINT-
~ 20~--------r-------~------~--~~--~-------; Po.
O~---~-----r---'~--~---T--~-----r---~----r~~ 10 11 12 13 14 15
CABIN PRESSURE (PSIA)
FIGURE 10-4
CABIN PRESSURE AFFECT ON FAN POWER
10-19
~ ::.::
.ct: ~ ...:l IJJ 0
0:: IJJ ~ 0 tl.
M ~ r:...
.ct: ~ ...:l IJJ 0
IJJ ::E: ::> ...:l 0 :>
::E: tIl ..:I
< ~ ..:I IJJ 0
~ ::x:: C9 H IJJ ~
0180-26495-4
2 ~
'" ...... i'-.. 1 " ~ ............
'-0
, , 2 ~
I" to..... 1
~ ~
'" r-..... 0 '" ~
DESIGN CABIN PRESSURE (PSIA)
FIGURE 10-5
PENALTY ON REDUCED CABIN PRESSURE (FAMILY OF OPTIMIZED SYSTEMS)
10-20
D180-26495-4
1. Referring to Figure 10-2 it can be seen that the logical cabin
pressure for SOC 1 ies within the boundaries of a triangle
formed by the 26.9 percent oxygen Fire Limit on the left, the
tentative O2 Toxicity Limit and "Practical" Suit Limit on the
right, and the 8,000 foot equivalent oxygpn level at the
bottom of the triangle. Existing Shuttle pressures are shown
on the Figure for reference.
2. TherE! is a preponderance of medical/health logic to favor
selecting the SOC cabin toward the upper right portion of the
triangular boundaries, mainly because man obviously works
best near his ancestral sea level environment. The power,
weight, and volume penalties of operating toward the upper
right portion of the triangle, as opposed to operating toward
t h el 0 w e r 1 eft po r t ion, are not g rea t The s e pen a 1 tie s are
about one percent of the total resources of SOC.
3. A normal cabin pressure error band of .:t.2 psi is recommended for SOC, based on this value being used on the current Shut-
t 1 e.
4. The boundaries of the triangle call for tighter control on
normal oxygen partial pressure level than is exercised on the
existing Shuttle. A control of about .:t.11 psia oxygen par-tial pressure is recommended for SOC. This is the band used
by the STS-l for EVA support, shown on the Fi gure, and is
held by manual control. Automatic control on SOC should be
at least this accurate.
5. The Ibox 1 abel ed "suggested for SOC" on Fi gure 10-2 is just
that, a suggested compromise between the many diverse factors
involved. Based on information ava"ilable during this study,
it is a logical, but not firm, selection. Use of the trade-
off factors presented in Section 10.3 allows evaluation of the
effect of other cabin pressure over the full range being
considered.
10-21
0180-26495-4
10.4 REDUNDANCY PHILOSOPHY
The reliability of EClS equipment to perform its intended function is improved by installing redundant equipment. Previous manned space programs relied on this principle of installed redundancy to provide a reliability adequate to achieve their mission objec-tives. and these early space programs were of a mission length which made achieving reliability goals by this method feasible. The SOC has a 10 to 20 year expected useful life requirement. Because of this long life requirement providing adequate relia-bility by installed redundancy ;s not feasible. Hardware designed for inorbit maintenance is mandatory to achieve the long SOC mission. Maintenance, however, does not delete the requirement for needing installed redundancy, but the amount of installed redundance for SOC EelS hardware is dictated by different reasons than past manned space vehicles. The key reasons for installed redundancy on SOC are:
A fail operational/fail safe design requirement
No single EelS failure shall cause abandonment of a habitat module
No single EClS failure shall require a Shuttle flight before the next planned flight.
The fail operational/fail safe requirement dictates the need to withstand two non-maintainable worst failures and still remain in a safe operating mode. A non-maintainable worst failure does not mean to imply that the EelS system is not maintainable. All of the EClS system can be maintained. however. some of the equipment such as main distribution plumbing, major wiring distribution bundles and equipment support structure, all which have a reli-ability of nearly "one" and would be expected to last for the life
of the SOC, will be difficult to maintain and may require equip-ment and/or specialists to be supplied by the next Shuttle flight in order to conduct the maintenance. A non-maintainable failure also exists if the last spare has been used for equipment which is expected to be maintained. This first ground rule needs specified mission time periods to be meaningful. The fail operational time
10-22
0180-26495-4
period is defined as 90 days, which is the normal SOC resupply
period. The fail safe time period is defined to be 300 hours,
which would allow for an emergency rescue by Shuttle.
The requirement that no sing'le EClS failure shall cause abandon-
ment of a habitation module makes it clear that abandoning a
habitat due to a single worst non-maintainable failure is unac-
ceptable. The requirement that no single failure shall require a
Shuttle flight before the next planned flight is self-explanatory.
As a result of the above, all critical EelS functions must: be
redundant.
The implementation of this redundancy philosophy requires the
installation of dual heat transport and rejection loops, dual air
revitalization subsystems, and dual water processing modules in
each habitat SOC.
Theine are instances, however, where dual redundancy per habitat
was not followed. For example, there are four cabin ventilation
and thermal control packages installed in each habitat module.
The sizing of this equipment into a larger number of smaller
modules "'as determined by the desire for commonal ity with the
thermal control units used in the service module. The service
module units need to handle only about one half the heat load and
ventilation flow as compared to the habitat module requirements.
Only one O2
generation and one hydrazine decomposition subsystems
were installed in each service module, which in turn supports one
habitable module. Each, however, are double sized to be capable
of servicing the full SOC. Intercabin plumbing between modules
permits 'ither of these subsystems to maintain the pressure and
atmosphere composition control in both habitat modules and both
service modules. Fail safe operation following two non-repairable
failures is provided by a 300 hour stored gaseous supply.
Some of the equipment categorized under health and hygiene are not
considered as critical functions. The backup capabil ity provided
by inflight maintenance and alternate operation modes will provide
a reliab'ility level commensurate with the mission requirements.
Therefore, one washin~ machine, one shower and one dishwasher are
considered adequate.
10-23
0180-26495-4
A complete listing of SOC EClS system packages including the
location of the packages, and the number of packages installed in each location is provided in Table 10-2.
This redundancy philosophy which has evolved for SOC will provide a comfortable environment in each habitat for 4 man crew with short term capabi 1 ity for an 8 man crew when all of the EClS equipment is operational. After the first worst failure (before
maintenance is performed). the EClS equipment will provide an acceptable environment for a 4 man crew. Even with the fir s t
worst non-maintainable failure the EClS system will support an 8 man crew for a 300 hour emergency period at degraded levels if the other habitat must be evacuated. The capability of the system to satisfy various emergency levels is presented in Section 10.2.
10.5 MAINTENANCE CONCEPT DEFINITION
The EClS system, with its many pumps, fans, valves, instruments, controllers, etc., must be designed to be in-orbit maintainable in order to achieve the 10-20 year useful life required for the SOC.
The hardware in the EClS system will be designed for maximum life but all dynamic hardware, like that mentioned above, will have an unsatisfactory probability of failure and replacement will be required. In-orbit maintenance places specific design require-ments on the hardware. It al so must be assumed that mal ntenance must be performed by a SOC crew man who does not have the detailed training that a factory technician would have and further must be performed with the general purpose tools available in the SOC tool kit. The general requi rement for the EClS system to be in-orbit maintainable and the assumptions regarding crew training and tool availability dictate that the EelS system be designed so that:
Fault isolation to the lowest Replacement level(lRU) hardware item be generally automated (some interaction with the crew man to provide yes/no information to the fault isolation process is acceptable).
The lRU hardware item be adequately accessible.
0180-26495-4
'l'ABLE 10-2
ECLS EQUIPMENT PACKAGES AND LOCATION
Humber of 'ackaq,o. and t.ocauon Totat SOC EeLS
tCLS rUNCTXOrl ...... JOII. tt"Utl'1'Inl'l' HAe L ""8 :2 ,. 1 ,. I '" ... PaC'acz VontlJ. .. tlon 'ana 4 4 ~ ~ I.. 112"""'.-2 ..... C.b1n VontU.tlon and Thora.l Control Air Coo1!n9 fI t Eachaf'Hjl.re 4 4 Cold Pht /0 /0 26 26 40 .. -32,"""",.
~hl,l"ldlt leatton 2 2 4 COl JlellloOval
~ ~ 4 Catalytic o.ldiur 4 An Pllvttalhation
CO 2 I'teduction 2
Odor Control 2 2 4 Ataoeptutu fmnt tortn" 1 2
~d torl 2 ~ 4 froon Cool .. nt pu.p 'edr.a,,". 2 6 ""at Tranapo1"t and l'ta)Octlon 'reon To Water .... t tach.anq'u. 2 2 4
Waur Coolant Puap '.cu, 2 2 4 0, ee"...ratlOft 2 Hydrulna o.cOIOpoett1on"":z Supply
5 2
AUIIOaphorlc: Supply "ydraun. Slot(l9_ 5 boet9.ncy 0, Stor_;_ / / taor90ney "2 Stor~. 2 2 tv.poranon p",ntlc.tion Un~t. 2 1 4 NatoI' OuaUty P')()n1torlnq 1 2
Nolt.or .. roc tnq And Mflneq __ nt .... t ..... t.r Stor.9. 3 3 g PoUblo Watar 5tor89_ :3 t:a.tqoru:y "tlt..- 8tol:ID90 /EVA Wator 4 22 26
W.ate CoUoetlon And 8tor.,_ / 2 berg"nC'y W t. Collectlon 1 2 tkJt Water Supply I ~ Cold Waul' Supply 1 Showor - 1 Hand W.ah 1 2
Ho.l th ~no Ryq i 0". ClOtho. Washor/Dryer I ~ Tr h COtIpactor 1 rood Rotrlqerot.ol' 1 2 rood Fro.aer 1 aven 2 Dlshvaahor /
5u' U And aactpacke
T T ~ JIIoet..arqo SU,tiona r:W./IVA Support Au LoC'k Support 1 1 2
t.ltrqo"c:y [licap. $yateR :3 2 5 tCI..S Co"traJ Conll'ol/tlhphy : 2 Syll". Control Portable "'alnt"nanco Contro,\/Dhplay 2
10-25
0180-26495-4
LRU attachment fittings, plumbing connections, wire connec-
tors, etc. be generally standardized to minimize training and
tool requirements and captivated to avoid loss.
Drain and refill of systems be avoided for LRU replacement.
The definition of the LRU requires optimization studies. Pre-
vious EClS systems studies (i.e., the Space Station Prototype
program) indicated that the component level {pump, fan, valve,
instrument, controller, etc.} was the proper maintenance level.
The component level probably allows for the maximum use of common-
ality. Common components used in a variety of installations will
significantly reduce spares inventory requirements, logistics
requirements and crew training. The disadvantage is that common
components will be slightly oversized or undersized for some
installations.
With minor exception maintenance below the component level is not
practical because of excessive crew training, spares inventory and
special tool requirements. A higher level lRU than components may
have some merit. Benefits may be realized in reduced weight
abundance of installed equipment, on-board spares and resupplied
spares. Crew time and fault isolation instrumentation and soft-
ware will also be reduced. At this point a component level lRU ;s
being assumed. however. during the SOC Phase B effort when more
detailed subsystem schematics and hardware sizing information is
available, an optimization study should be conducted to determine
the appropriate lRU level and the degree to which hardware common-
ality is incorporated. Figures 10-6 and 10-7 show graphically how
an optimum lRU selection and a commonality decision might be made.
In addition to determining an optimum lRU and commonality levels,
as discussed above, certain goal s must be set in order to have a
comprehensive maintenance philosophy. The following goals, some
of which were stated earlier, have been established to minimize
the impact of I:laintenance on the SOC EClS system:
10-26
COMPONENT
0180-26495-4
SYSTEM PENALTY
-~, _______ INSTALLED
SIZE OF REPLACEMENT UNIT
FIGURE 10-6
EQUIPMENT
ON-BOARD SPARES
RESUPLY SPARES
SUBSYSTEM
LOWEST REPLACEABLE UNIT OPTIMIZATION
10-27
.. ~ l? H W ~
0180-26495-4
DIVERSITY OF SPARES
-C COMMONALITY
FIGURE 10-7
LOWEST REPLACEABLE UNIT COMMONALITY OPTIMIZATION
10-28
0180-26495-4
No maintenance task shall exceed 4 hours.
Unscheduled maintenance shall not exceed 8 man hours per month.
Scheduled maintenance shall not exceed 40 man hours per month.
Maintenance shall be accomplished with SOC tool kit TBD.
Maintenance skill level shall be within SOC technician cap-ability.
Spares commonality shall be selected to provide minimum penalty.
Equipment shall be designed to avoid fluid loss and air inclusion during maintenance.
For ease of maintenance, life support equipment will be located behind removable ceiling and floor panels. The equipment will be located so that repl aceabl e component and/or modul ar units are generally no more than a single layer deep with adequate perimeter access py'oviding up to five side access for maintenance. The replaceable modular units are packaged within a panel cavity so that plenum airflow is not disturbed during a maintenance pro-cedure.
Modular units should generally be configured as a group of com-ponents forming a logic group. On-board repair of components is not ordinarily considered feasible. However, consideration should be given to possible emergency repairs below the component level by using standard (common) parts.
Malfunctions shall be isolatable to the logic group level and, as a 90al, to the LRU level. Automatic detection of the' malfunction or degradation shall be provided for critical functions. Where the fault isolation cannot be narrowed to a specific LRU in the allowable down time, replacement shall be made to all suspect LRU's.
10-29
Sufficient spares shall performance within the ments. Cannibalization is possible to be done
0180-26495-4
be stored on-board to sustain the system resupply period, and reliability allot-of other systems can be considered if it within allowable maintenance time period.
The components in the SOC system which require replacement fall into several combinations of the following categories: low pres-
sure, high pressure, hazardous liquid, non-hazardous liquid, hazardous gas, and non-hazardous gas.
Gas-line components. In general, gas-line component problems are not as severe as liquid-line problems. Some gas lines do, how-ever. contain hazardous gases (such as hydrogen) or contaminated gases (such as commode outlet gas). Lines carrying hazardous gases have provisions for either purging or evacuating prior to component removal. Thereafter, maintenance considerations are the same as for any other gas-line and are described in the following paragraphs.
High-pressure gases. High-pressure lines are defined generally as those containing pressures which exceed 5 psig, while low-pressure
lines are defined generally as those containing pressures below 5 psig. Vacuum lines should be considered and maintained in the same manner as high-pressure lines.
The high-pressure gas-lines shall contain bypass lines and shutoff and depressurization valves which are properly located to allow for depressurization and maintenance without interrupting other critical system functions. Once depressurized, the 1 ines may be opened at the component fittings to allow component replacement.
Low-pressure gases. Components in the low-pressure lines will be connected to the duct through the use of flexible hoses, beaded tubes, and flanges or Marman-type couplings (or both). The Marman type flanges shall use of dovetailed grooves to captivate any seals which are used, and they should be coupled together with a quick release clamp. Where the system must remain operating, caps shall be provided to close off the open ports.
10-30
0180-26495-4
~id-line components. When considering the liquid subsystems and the requirement that the EelS must operate in a zero-g envi-
ronment, two important aspects of liquid-line component mainten-
anCE! became apparent: (a) prevention of liquid loss and, (b)
prevention of gas ingestion. Prevention of 1 iquid loss precludes
a recharge operation with the attendant need for replacement
1 iquid and minimizes spillage which could induce other component
failures, introduce possible contamination, and require varied,
complex, a~d time consuming cleanup operations. Prevention of gas ingestion eliminates the need for evacuation or bleeding and
reduces the performance requi rement of gas separat ion equi prnent.
One of the maintenance methods considered for liquid-line compon-
ents was the subsystem "drain and fill" approach. Although this
approach would permit the use of a greater number of "off-the-
shelf" or standard components, the design constraint resulting from
the possibility of gas entrapment could jeopardize the system
integration effort. This approach would also require many drain
ports and complex servicing equipment.
Requirements for draining, complex servicing equipment, and clean-
up problems are undesirable. Therefore, the subsystem shutdown
and drainage approach has been eliminated as a normal liquid-line
maintenance approach. The selected basic approach to maintenance
of the EelS liquid-line subsystems is that it can be accomplished
without requlrlng draining or complete subsystem deactivation.
Sevleral concepts are being developed which allow for replacement
of components and valves without system drainage and also allow
for bypassing failed line sections.
Non-maintainable Items
Failure of an item which is not normally maintainable is consid-
ered an exceptional event. Repair of these items may require disruption of normal activities since the repair effort may be of
long duration, requiring more than one crew member, and, in ex-
treme, the evacuation of thE! module may be required. The first
worst case failure of this equipment will cause a degraded perfor-
mance condition to exist which is acceptable for 90 day operation.
10-31
0180-26495-4
Items which cannot be maintained by the use of on-board spare
parts are requi red to have a rel iabil ity which approaches one. This equipment includes frames, main distribution fluid lines and
main distribution electrical harnesses.
Non-maintainable item should be protected so that maintenance of adjacent components does not pose the possibility of damage to the non-maintainable item. In the case of fluid lines and harnesses, these should be located behind panels and the harnesses should be routed in conduit. Where redundant fluid lines and harnesses are required, they should be routed in separate compartments and
should be located as far apart from one another as possible.
Non-maintainable items should be designed with conservative safety factors. possible.
Major structural members should contain redundancy where The non-maintainable items should be designed so that a
failure can be easily detected.
In order to minimize the number of random failures, low reliabil-ity and life limited items should be replaced before the expected failure occurs. The tradeoff is between crew convenience and
cost. The minimum cost approach is to let all equipment operate until it wears out. The maximum cost approach is to replace equipment at the minimum expected life. A third approach is to monitor equipment and predict equipment failure based on trend
analysis. If the predictions are fairly accurate, this third method would be close to the minimum cost, while providing flex-ibility for scheduling maintenance. The third approach should be considered whenever it can be accomplished without the addition of instrumentation. It should also be considered when the equipment is costly and there is a large spread between the minimum and maximum expected life.
10-32
0180-26495-4
10.6 EVALUATION OF SELECTABLE CABIN TEMPERATURE, AND CABIN TEMPERATURE BAND EXPANSION
There are several facets to a discussion of variations in cabin temperatul~e. First, there is the matter of control band varia-tion, that is to say the cabin temperature band over which the cabin temperature controls may be set by the crew. The set tem-perature is not related to the capacity of the EClS system to always provide this selected temperature. For example, the ther-mostat us.ed by the crew to select cabin temperature could be
settlable at any temperature between 65F and 80F. When in the full cold or full hot mode, any cabin temperature within this band would be maintained within the capacity of the EClS to do so. Cabin cooling capability, as discussed in this section, refers only to the full cold capability of the EClS to satisfy the oper-ating condition in question. The degree to which cooling capacity should be provided, to ensure that the lowest cabin temperature selectabll:? by the crew will be achieved, has weight, volume. and power impact on the EClS system. On the other hand, the ability to heat the cabin has no penalty since the vehicle is so well insulated, and since there is always a significant electrical
heat load to be dissipated. It is the cooling capacity required that sizes the thermal control packages, and the remainder of the heat rejection system as well.
This SOC study considers as its baseline a system capable of providing the following "full cold" cabin cooling capacity:
No. Temp. Hab. Mod. Control Crew Per Maximum Units Operating "Full Maximum
Cabin EClS Fa il ed Temp. Cold" Cabin Heat Crew Per Operating Per' Control Cabin Dew Load Hab. Mod. Mode Hab. Mod. Unit Temp. 'P'oi nt
Maximum 4 Operational 0 1 75 60
Maximum 4 90 Day 2 2 85 70 Degraded
Maximum 8 90 Day a 2 85 70 Degraded
Maximum 8 14 Day 2 4 90 75 Emergency
10-33
DI80-26495-4
In practice, the thermal system cannot be sized to simultaneously "just meet" all four of the above operating modes. In this case, the operational mode will be just met, and the cooling capacity requirement of the other three will be somewhat exceeded. The baseline system of this study, in the operational mode, will provide sufficient full cold cooling capacity at the maximum heat load case for a cabin temperature of 75F. The question arises;
what would be the effect on the EClS system if this cool ing ca-pacity requirement were increased to drop this maximum operational cabin temperature to 70F, and 65F respectively.
Preliminary designs of a family of different systems would exhibit the power, weight and volume penalties shown o~ Figure 10-8. Note that the penalties in gOing from 70F to 65F are much more severe than going from 75F to 70F. The reason for this is that there is an i nfi ni te penal ty in goi ng to a 55F cab; n because the ability to hold cabin relative humidity of 75% becomes impossible below a cabin temperature of 550'F. This is because the coolant water and therefore the dew point is 1 imited to 40F to prevent icing in the coolant water to freon heat exchanger.
The penalty study results shown in Figure 10-8 indicate that there is relatively little penalty to change the present 75F selected SOC baseline cabin temperature specification to require a full cold operational maximum temperature of 70F. This figure sho\,/s that the increased comfort which would result from a 70F cabin at high work rates would cost approximately 35 lb, 2.2 ft 3 and 400 watts. A further decrease in full cold cabin temperature capa-bility to 65F appears to have an unacceptable penalty.
This study does not recommend a reduction in max load cabin tem-perature capability from the baseline 75F value to .~OF, but the tradeoff study suggests that the increased penalty of this 5F
reduction is small enough to make such a change in the specifica-tion reasonable if it is desired for additional comfort for high work loads.
10-34
~ 2.0
1.5 ~ E-t 1.0 ...:I W Cl
0.5 Il:: w
0 ~ Il. -0.5
M 16 E-t Ii.
12
8
4
o -4
: 400 III ...:I
~ E-t ...:I W Cl
E-t :x: t? H
300
200
100
o
r\
"
1\ \
\ \
~ -100 65
"-
t\.
"
'" "-
D180-26495-4
'" r--..... ......... t-- t-- "- r-- ....
~ ..... ...... ... --~ -, NO'l'E: RADIATOR
NOT INCLUDE D
"-BASELINE DESIGN POINT-I
./
.......... r ........ ,/ V "-
70 75 DESIGN MAXIMUM OPERATIONAL
CABIN TEMPERATURE (OF)
FIGURE 10-8
80
SELECTABLE CABIN TEMPERATURE PENALTY
10-35
D180-26495-4
Most buildirig air conditioning systems include a thermostat setta-ble in the range of 65F to 80F, regardless of the capacity of the buildings system to satisfy this range under conditions of maximum load. It is suggested that the SOC cabin temperature
thermostat likewise have a thermostat settable range from 65F to
80F.
10.7 EClS SUBSYSTEM SELECTION RATIONALE
At the initiation of Boeing1s SOC Systems Analysis effort, an EClS reference baseline was defined by NASA in NASA-3 and NASA-6. The
EClS system defined in Boeing-19 differs from the NASA reference
basel ine in some areas. A rationale for the most significant
deviations is provided in this section. The differences discussed are:
CO 2 Removal Concept Selection Wastewater Processing Concept Selection
10.7.1 CO 2 Removal Subsystem Concept Selection
Hamilton Standard has been evaluating, by spacecraft CO 2 removal, concepts for more than
pendable and regenerable techniques have been cepts receiving considerable attention were:
lithium hydroxide Lithium peroxide Solid amines Molecular sieves Electrochemical Molten carbonate
analysis and test, 20 years. Both ex-
evaluated. The con-
With the exception of Skylab, all U.S. spacecraft to date have
used expendable lithium hydroxide. Skylab used a regenerable molecular sieve CO 2 removal and dump system. Spacecraft such as the pl anned SOC wi 11 requi re a regenerabl e CO 2 removal system which will supply pure CO 2 at atmospheric pressure for a CO 2 re-duction process in order to save the oxygen. Two concepts have evolved which meet these SOC requirements: solid amine and elec-
trochemical. Both of these concepts have been thoroughly tested
10-36
0180-26495-4
as prototype hardware under both NASA contracts and contractor R&D funds demonstrating their capability to perform the CO 2 removal and concentration functions. For the SOC study activity the Solid Amine Water (Atmospheric Pressure Steam) Desorbed (SAWD) has been selected by Hamilton Standard. The reasons for this selection are that SAWD as compared to the Electrochemical Depolarized CO 2 Concentrator (EOC) when integrated into the SOC life support system:
1. Has less system weight, volume and power penalty.
2. Is not dependent on an emergency liOH backup system.
3. Does not require over-sizing the electrolysis subsystem.
4. Is less dependent on other subsystems for operation (cas-cading failures).
5. Allows the EClS to be designed without introducing H2 into habitat module or requiring H2 lines passing through bulk-heads.
6. Is free from potential caustic carryover.
7. Is tolerant to the cabin humidity range without precondi-tioning the air.
8. Can be exposed to a depressurized cabin without requiring shut-off valves or other precautionary action.
9. Uses power on the light side of the orbit without a signi-ficant sizing penalty.
10. Is less expensive hardware.
In order to evaluate statement number 1, it is necessary to pro-vide a dE~sign specification for sizing the SOC CO 2 removal unit. It is believed that as a result of the SOC fail operational (90 day degraded)/fail safe (14 day further degraded) requirement the SAWD
CO 2 removal units must be s'ized for 8 men CO 2 output at 12 mmHg partial pressure. Four un'its sized to this criteria would be installed in the SOC, two per habitat, to meet safety require-ments. The EDC CO 2 removal unit can be sized for the same case as
10-37
0180-26495-4 the SAWD supported by four 4 man (+ EDC 02 and H2 ) electrolysis units operated on the sun side only. In this case. EDC would shut down on the dark side of the orbit. As another option, the EDC can be sized to run continuously with continuously running elec-trolysis units. In order to meet safety requirements. two EDC units and two electrolysis units would be required per habitabil-ity module in both of these cases.
Another approach using an EDC unit which would also meet the safety criteria is to incorporate a backup LiOH s