Refrigeration System Selection Guide ISSUE 2-0409

Refrigeration - hrponline.co.uk · 5 The chart shows a range of standard equipment selections designed to maintain an average room temperature of -18ºC based on the following design

Embed Size (px)

Citation preview

Refrigeration System Selection

GuideISSUE 2-0409

2

How to use

How to use the Selection ChartsThe selection charts on pages 4 to 15 of this brochure have been put together to make the specification and ordering of complete systems quick and easy.

To use this guide you need to know what temperature you wish to maintain, the Product Storage Conditions Chart on page 35 has more information.

Once you know the temperature, follow these simple step by step instructions and, when you have completed your specification, call your local HRP Service Centre for competitive pricing and fast delivery.

Selection CriteriaThe Systems listed in the Selection Charts are top quality brand products, and have been chosen to provide the installer with a ready-matched complete system to suit various applications:

• Frozen Food • Cool Storage • Food Preparation • Beer Cellars

Condensing Unit requirements can vary depending on location, space restrictions, compressor type and client preference.

Various Housed and Un-housed Units are included in the Selection Charts, from top brand manufacturers for whom HRP acts as a major Wholesaler.

The Penn Cold Room Controller suits all Cooler & Condensing Unit Systems in the Selection Charts, and is a reliable and recognised brand product.

The System Selection is completed with a Tube Pack consisting of:

• Copper Tube - 15m suction & liquid tube • Isoline Insulation - 15m (or equivalent)

HRP can also provide other manufacturers’ brand products, plus bespoke Dressed Units for particular applications - please refer to pages 28 to 30, or contact our Sale Support Controllers at your local HRP Service Centre.

HRP also supplies an extensive range of Capital Equipment from small panel evaporators to large industrial coolers, plus Semi-Hermetic and Scroll Condensing Units, Compressor/Receiver Units, Air-cooled and Water-cooled Condensers, etc., based on the latest range of commercially available refrigerants.

Quick & Easy Selection ChartsThe Chart allows the installer to make a quick and easy choice of the right product for the application, without the need for lengthy calculations or referral to tables and graphs.

The Chart represents a range of standard equipment selections designed to maintain an average room temperature as specified, based on the design criteria listed, relative to each Temperature Selection Chart.

The refrigerant pipework sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

The Systems detailed in this brochure are for guidance only and do not form part of a Contract. Please refer to the criteria on which the Selection Charts are based, which are listed at the right hand side of each temperature application page. All goods are supplied subject to HRP Terms & Conditions.

Step 1COLDROOM SIZE & COOLING kW

Step 2SELECT ONE

EVAPORATOR

Step 3SELECT ONE

CONDENSING UNIT

SELECT TEMPERATURE RANGE

Step 4ADD THE INSTALLATION PACK AND CONTROLLER

FOR THE ABOVE COMBINATION

a b

c

axbxc=x3

3

Temperature (Range) Index Page

-18ºC

(-15ºC to -25ºC)Frozen Food Holding Room Equipment Selections - R404A

Housed Units4 - 5

Un-housed Units

0ºC to +2ºC

(0ºC to +2ºC)Fresh Meat Holding Room Equipment Selections - R404A

Housed Units6 - 7

Un-housed Units

+2ºC to +4ºC

(+2ºC to +10ºC)Provisions Holding Room Equipment Selections - R404A

Housed Units8 - 9

Un-housed Units

+10ºC

(+8ºC to +12ºC)Food Preparation Room Equipment Selections

Housed Units10 - 11

Un-housed Units

+10ºC

(+8ºC to +12ºC)Beer Cellar (above ground) Equipment Selections - R134A Un-housed Units 12 - 13

+10ºC

(+8ºC to +12ºC)Beer Cellar (above ground) Equipment Selections - R407C

Qualitair Housed Units14 - 15

Marstair Housed Units

Technical Data Rivacold Evaporators Coolers 16

Technical Data Kobol Evaporators Coolers 17

Technical Data L’Unite Hermetique Condensing Unit Un-housed 18

Technical Data Copeland Scroll Condensing Unit Un-housed 19

Technical Data Profroid Housed Condensing Unit Housed 20

Technical Data Copeland Scroll EazyCool Condensing Unit Housed 21

Technical Data Qualitair Low Temp Cassette Systems 22

Technical Data Food Preparation Room EquipmentCopeland Un-housed

23RDF Dual Discharge Cooler

Technical Data Beer Cellar CoolerQualitair Systems

24Marstair Systems

Technical Data Penn Cold Room Controller 25

Copper Tube & Insulation Copper Tube/Insulation

26 - 27

Copper Fittings

Insulation Protective Paint

Adhesive

Brazing Rods

HRP Workshop

Installation Accessories, Tools & Equipment

Dressed Condensing Units

28 - 29Bespoke Engineered Equipment

Equipment Modifications

Additional Products available from HRP

Danfoss Friga-Bohn

30

Aspera L’UH

Copeland Profroid

Rivacold Kobol

Contactors Housings

Technical Centre 31

Training & CoursesMHI Installation & Product Training

32 - 33C&G 2078 2079

RefrigerantsRefrigerant

34Refrigerant Reclaim

Product Storage Conditions 35

Index

Step 1COLDROOM SIZE & COOLING kW

Step 2SELECT ONE EVAPORATOR

Step 3SELECT ONE CONDENSING UNIT

4

RC325-45ED

FH2480ZBR

OM 21

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

Frozen Food Holding Room Equipment Selections - R404A

Make a quick and easy selection of the right system for -18ºC applications.

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 1.8 kW 2 kW 2.13 kW 2.27 kW 2.6 kW 2.9 kW 3.36 kW 4.17 kW 4.7 kW 5.36 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RC325-33ED RC325-33ED RC325-45ED RC325-45ED RC325-45ED RC425-61ED RC425-61ED RCMR 2350406-ED RCMR 2350806-ED RCMR 2350806-ED

HRP Code 040151 040151 040154 040154 040154 040157 040157 040368 040371 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MC-23E MC-30E CC-27E CC-27E CC-33E CC-41E CC-41E CC-56E CC-56E CC-75E

HRP Code 080446 080470 081884 081884 081914 081949 081949 082015 082015 082058

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPL 08 WPL 11 WPL 11 WPL 11 WPL 16 WPL 16 WPL 16 WPL 22 - -

HRP Code - 1 phase 050136 050140 050140 050140 - - - - - -

HRP Code - 3 phase 050138 050142 050142 050142 050154 050154 050154 050156 - -

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model OM 15 OM 21 OM 21 OM 21 OM 21 OM 21 OM 26 OM 30 OM 38 OM 45

HRP Code - 1 phase 450485 450487 450487 450487 450487 450487 450489 - - -

HRP Code - 3 phase 450491 450493 450493 450493 450493 450493 450495 450497 450499 450501

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18)

L’Unite Model FH2480ZBR FH2480ZBR FH2480ZBR FH2511ZBR FH2511ZBR - - - - -

HRP Code - 1 phase 431714 431714 431714 431712 431712 - - - - -

HRP Code - 3 phase 431710 431710 431710 431729 431729 - - - - -

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model MC-D8-ZB15 MC-H8-ZB15 MC-H8-ZB15 MC-D8-ZB19 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26 MC-P8-ZB30 MC-M8-ZB38 MC-M8-ZB45

HRP Code - 1 phase 455262 455270 455270 455102 455106 455110 455114 - - -

HRP Code - 3 phase 455100 455188 455188 455104 455108 455112 455116 455194 455126 455128

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479932 479932 479932 479932 479932 479932 479932 479932 479933 479933

The Installation PackCopper tube pack including Isoline insulation - see p 28

5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 3/4” & 3/8” 3/4” & 3/8” 7/8” & 3/8” 7/8” & 1/2” 7/8” & 1/2”

148504 148504 148504 148504 148504 148506 148506 148508 148510 148510Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) POA POA POA POA POA POA POA - - -

- 3 Phase (Rivacold) 193443 193446 193446 193446 193449 193449 193449 193449 193451 193451

- 3 Phase (Kobol) 193443 193446 193446 193446 193449 193449 193450 193450 193453 193453

Power Supply *** 1ph & N 25 amps 25 amps 25 amps 25 amps 30 amps 30 amps 30 amps - - -

3ph & N 15 amps 15 amps 15 amps 15 amps 20 amps 20 amps 20 amps 20 amps 20 amps 25 amps

WPL 11

CC-33E

MC-M8-ZB38

(Supplied loose)

5

The chart shows a range of standard equipment selections designed to maintain an average room temperature of -18ºC based on the following design criteria:-

a) Ambient Temperature 32ºC.

b) Evaporator Temperature difference between air on and evaporating (delta T1) 5ºC to 7ºC.

c) Coldroom constructed from 75mm polyurethane insulation to walls, ceiling and floor, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 64kgs per m3 of Coldroom volume entering the room at no more than 6ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

*** The Power Supply shown equates to the total FLA of the Condensing Unit and Evaporator fans.

It assumes a defrost interlock such that defrost heaters and condensing units cannot operate at the same time.

POA: 1 phase control panels are available to special order for these applications.

The suitability of control panel application must be checked before the installation is undertaken.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

IDEAL STORAGE CONDITIONS FOR

PRE-FROZEN PRODUCTS

Please refer to the guide on

page 35

TEMPERATURE

-18ºC

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 1.8 kW 2 kW 2.13 kW 2.27 kW 2.6 kW 2.9 kW 3.36 kW 4.17 kW 4.7 kW 5.36 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RC325-33ED RC325-33ED RC325-45ED RC325-45ED RC325-45ED RC425-61ED RC425-61ED RCMR 2350406-ED RCMR 2350806-ED RCMR 2350806-ED

HRP Code 040151 040151 040154 040154 040154 040157 040157 040368 040371 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MC-23E MC-30E CC-27E CC-27E CC-33E CC-41E CC-41E CC-56E CC-56E CC-75E

HRP Code 080446 080470 081884 081884 081914 081949 081949 082015 082015 082058

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPL 08 WPL 11 WPL 11 WPL 11 WPL 16 WPL 16 WPL 16 WPL 22 - -

HRP Code - 1 phase 050136 050140 050140 050140 - - - - - -

HRP Code - 3 phase 050138 050142 050142 050142 050154 050154 050154 050156 - -

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model OM 15 OM 21 OM 21 OM 21 OM 21 OM 21 OM 26 OM 30 OM 38 OM 45

HRP Code - 1 phase 450485 450487 450487 450487 450487 450487 450489 - - -

HRP Code - 3 phase 450491 450493 450493 450493 450493 450493 450495 450497 450499 450501

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18)

L’Unite Model FH2480ZBR FH2480ZBR FH2480ZBR FH2511ZBR FH2511ZBR - - - - -

HRP Code - 1 phase 431714 431714 431714 431712 431712 - - - - -

HRP Code - 3 phase 431710 431710 431710 431729 431729 - - - - -

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model MC-D8-ZB15 MC-H8-ZB15 MC-H8-ZB15 MC-D8-ZB19 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26 MC-P8-ZB30 MC-M8-ZB38 MC-M8-ZB45

HRP Code - 1 phase 455262 455270 455270 455102 455106 455110 455114 - - -

HRP Code - 3 phase 455100 455188 455188 455104 455108 455112 455116 455194 455126 455128

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479932 479932 479932 479932 479932 479932 479932 479932 479933 479933

The Installation PackCopper tube pack including Isoline insulation - see p 28

5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 5/8” & 3/8” 3/4” & 3/8” 3/4” & 3/8” 7/8” & 3/8” 7/8” & 1/2” 7/8” & 1/2”

148504 148504 148504 148504 148504 148506 148506 148508 148510 148510Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) POA POA POA POA POA POA POA - - -

- 3 Phase (Rivacold) 193443 193446 193446 193446 193449 193449 193449 193449 193451 193451

- 3 Phase (Kobol) 193443 193446 193446 193446 193449 193449 193450 193450 193453 193453

Power Supply *** 1ph & N 25 amps 25 amps 25 amps 25 amps 30 amps 30 amps 30 amps - - -

3ph & N 15 amps 15 amps 15 amps 15 amps 20 amps 20 amps 20 amps 20 amps 20 amps 25 amps

Step 1COLDROOM SIZE & COOLING kW

Step 2SELECT ONE EVAPORATOR

Step 3SELECT ONE CONDENSING UNIT

6

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 1.85 kW 2.03 kW 2.22 kW 2.38 kW 2.78 kW 3.13 kW 3.72 kW 4.53 kW 5.23 kW 6.02 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RSI 2250ED RSI 2250ED RSI 2250ED RSI 3250ED RSI 3250ED RSI 3250ED RSI 4250ED RCMR 2350406-ED RCMR 2350406-ED RCMR 2350806-ED

HRP Code 040097 040097 040097 040100 040100 040100 040103 040368 040368 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MR-21E MR-21E MR-21E MR-21E MR-28E MR-28E MR-35E CR-52E CR-67E CR-67E

HRP Code 080233 080233 080233 080233 080276 080276 080306 081558 081582 081582

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPH 13 WPH 13 WPH 17 WPH 17 WPH 19 WPH 19 WPH 24 WPH 31 WPH 40 WPH 40

HRP Code - 1 phase 050108 050108 050112 050112 050116 050116 050120 050124 050128 050128

HRP Code - 3 phase 050110 050110 050114 050114 050118 050118 050122 050126 050130 050130

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model - - - - - - OM 15 OM 21 OM 21 OM 26

HRP Code - 1 phase - - - - - - 450485 450487 450487 450489

HRP Code - 3 phase - - - - - - 450491 450493 450493 145495

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page18)

L’Unite Model CAJ9510ZMHR CAJ9513ZMHR CAJ4517ZHR CAJ4517ZHR FH4522ZHR FH4522ZHR FH4524ZHR FH4531ZHR FH4531ZHR TFH4540ZHR

HRP Code - 1 phase 439304 439312 439320 439320 439339 439339 439347 439355 439355 -

HRP Code - 3 phase 439428 439436 439444 439444 439460 439460 439379 439487 439487 439495

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model - - - - - - MC-D8-ZB15 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26

HRP Code - 1 phase - - - - - - 455262 455102 455110 455115

HRP Code - 3 phase - - - - - - 455100 455104 455108 455116

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479931 479931 479931 479931 479932 479932 479932 479932 479932 479932

The Installation PackCopper tube pack including Isoline insulation - see p 28

5/8" x 1/4" 5/8" x 1/4" 5/8" x 1/4" 5/8" x 1/4" 3/4" x 3/8" 3/4" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 1.1/8" x 3/8"

148502 148502 148502 148502 148506 148506 148508 148508 148508 148512Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) 193434 193439 193439 193439 POA POA POA POA POA POA

- 3 Phase (Rivacold) 193443 193443 193443 193443 193443 193443 193446 193449 193449 193449

- 3 Phase (Kobol) 193443 193443 193443 193443 193443 193443 193446 193449 193450 193450

Power Supply *** 1ph & N 8.75 amps 11.75 amps 12.55 amps 12.55 amps 18.3 amps 18.3 amps 20.8 amps 29.16 amps 29.16 amps -

3ph & N 4.45 amps 5.35 amps 5.43 amps 5.43 amps 7.2 amps 7.2 amps 8.55 amps 10.2 amps 10.54 amps 11.6 amps

Fresh Meat Holding Room Equipment Selections - R404A

Make a quick and easy selection of the right system for 0ºC to +2ºC applications.

MC-D8-ZB15

FH4522ZHR

MR-28E

RSI 3250ED

OM 21

WPH 40

(Supplied loose)

7

The chart shows a range of standard equipment selections designed to maintain an average room temperature of 0ºC to +2ºC based on the following design criteria:-

a) Ambient Temperature 32ºC

b) Evaporator Temperature difference between air on and evaporating (delta T1) 5ºC to 7ºC.

c) Coldroom constructed from 75mm polyurethane insulation to walls, ceiling and floor, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 64kgs per m3 of Coldroom volume entering the room at no more than 6ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

*** The Power Supply shown equates to the total FLA of the Condensing Unit and Evaporator fans.

It assumes a defrost interlock such that defrost heaters and condensing units cannot operate at the same time.

POA: 1 phase control panels are available to special order for these applications.

The suitability of control panel application must be checked before the installation is undertaken.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

IDEAL STORAGE CONDITIONS FOR FRESH PROVISION

PRODUCTS

Please refer to the guide on

page 35

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 1.85 kW 2.03 kW 2.22 kW 2.38 kW 2.78 kW 3.13 kW 3.72 kW 4.53 kW 5.23 kW 6.02 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RSI 2250ED RSI 2250ED RSI 2250ED RSI 3250ED RSI 3250ED RSI 3250ED RSI 4250ED RCMR 2350406-ED RCMR 2350406-ED RCMR 2350806-ED

HRP Code 040097 040097 040097 040100 040100 040100 040103 040368 040368 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MR-21E MR-21E MR-21E MR-21E MR-28E MR-28E MR-35E CR-52E CR-67E CR-67E

HRP Code 080233 080233 080233 080233 080276 080276 080306 081558 081582 081582

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPH 13 WPH 13 WPH 17 WPH 17 WPH 19 WPH 19 WPH 24 WPH 31 WPH 40 WPH 40

HRP Code - 1 phase 050108 050108 050112 050112 050116 050116 050120 050124 050128 050128

HRP Code - 3 phase 050110 050110 050114 050114 050118 050118 050122 050126 050130 050130

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model - - - - - - OM 15 OM 21 OM 21 OM 26

HRP Code - 1 phase - - - - - - 450485 450487 450487 450489

HRP Code - 3 phase - - - - - - 450491 450493 450493 145495

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page18)

L’Unite Model CAJ9510ZMHR CAJ9513ZMHR CAJ4517ZHR CAJ4517ZHR FH4522ZHR FH4522ZHR FH4524ZHR FH4531ZHR FH4531ZHR TFH4540ZHR

HRP Code - 1 phase 439304 439312 439320 439320 439339 439339 439347 439355 439355 -

HRP Code - 3 phase 439428 439436 439444 439444 439460 439460 439379 439487 439487 439495

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model - - - - - - MC-D8-ZB15 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26

HRP Code - 1 phase - - - - - - 455262 455102 455110 455115

HRP Code - 3 phase - - - - - - 455100 455104 455108 455116

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479931 479931 479931 479931 479932 479932 479932 479932 479932 479932

The Installation PackCopper tube pack including Isoline insulation - see p 28

5/8" x 1/4" 5/8" x 1/4" 5/8" x 1/4" 5/8" x 1/4" 3/4" x 3/8" 3/4" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 1.1/8" x 3/8"

148502 148502 148502 148502 148506 148506 148508 148508 148508 148512Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) 193434 193439 193439 193439 POA POA POA POA POA POA

- 3 Phase (Rivacold) 193443 193443 193443 193443 193443 193443 193446 193449 193449 193449

- 3 Phase (Kobol) 193443 193443 193443 193443 193443 193443 193446 193449 193450 193450

Power Supply *** 1ph & N 8.75 amps 11.75 amps 12.55 amps 12.55 amps 18.3 amps 18.3 amps 20.8 amps 29.16 amps 29.16 amps -

3ph & N 4.45 amps 5.35 amps 5.43 amps 5.43 amps 7.2 amps 7.2 amps 8.55 amps 10.2 amps 10.54 amps 11.6 amps

TEMPERATURE

0ºC to +2ºC

Step 1COLDROOM SIZE & COOLING kW

Step 2SELECT ONE EVAPORATOR

Step 3SELECT ONE CONDENSING UNIT

8

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 2.02 kW 2.26 kW 2.44 kW 2.63 kW 3.06 kW 3.45 kW 4.54 kW 5.46 kW 6.29 kW 7.01 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RSI 3250ED RSI 3250ED RSI 3250ED RSI 4250ED RSI 4250ED RSI 4250EDRCMR 2350406-

EDRCMR 2350806-ED RCMR 2350806-ED RCMR 2350806-ED

HRP Code 040100 040100 040100 040103 040103 040103 040368 040371 040371 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MR-21E MR-21E MR-21E MR-28E MR-28E MR-35E CR-52E CR-67E CR-79E CR-79E

HRP Code 080233 080233 080233 080276 080276 080306 081558 081582 081612 081612

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPH 13 WPH 13 WPH 17 WPH 17 WPH 19 WPH 19 WPH 31 WPH 40 WPH 40 WPH 53

HRP Code - 1 phase 050108 050108 050112 050112 050116 050116 050124 050128 050128 -

HRP Code - 3 phase 050110 050110 050114 050114 050118 050118 050126 050130 050130 050146

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model - - - - - OM 15 OM 21 OM 21 OM 26 OM 30

HRP Code - 1 phase - - - - - 450485 450487 450487 450489 -

HRP Code - 3 phase - - - - - 450491 450493 450493 450495 450497

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18. Fitted options, pages 28 & 29)

L’Unite Model CAJ9513ZMHR CAJ9513ZMHR CAJ9513ZMHR CAJ4517ZHR FH4522ZHR FH4522ZHR FH4531ZHR FH4531ZHR TFH4540ZHR TAG4546ZHR

HRP Code - 1 phase 439312 439312 439312 439320 439339 439339 439355 439355 - -

HRP Code - 3 phase 439436 439436 439436 439444 439460 439460 439487 439487 439495 439509

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model - - - - - MC D8 ZB15 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26 MC-H8-ZB30

HRP Code - 1 phase - - - - - 455262 455102 455110 455115 -

HRP Code - 3 phase - - - - - 455100 455104 455108 455116 455122

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479931 479931 479931 479932 479932 479932 479932 479932 479932 479932

The Installation PackCopper tube pack including Isoline insulation - see p 28

1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 5/8" x 3/8" 5/8" x 3/8" 5/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8"

148500 148500 148500 148504 148504 148504 148508 148508 148508 148508Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) 193436 193436 193436 193439 POA POA POA POA POA POA

- 3 Phase (Rivacold) 193443 193443 193443 193443 193443 193443 193446 193446 193449 193449

- 3 Phase (Kobol) 193443 193443 193443 193443 193443 193443 193446 193447 193450 193450

Power Supply *** 1ph & N 12.05 amps 12.05 amps 12.05 amps 13.3 amps 18.7 amps 18.7 amps 29.16 amps 29.16 amps - -

3ph & N 5.65 amps 5.65 amps 5.65 amps 6.18 amps 7.6 amps 7.6 amps 10.2 amps 10.2 amps 11.26 amps 9.69 amps

OM 21

MR-28E

RSI 4250ED

Provisions Holding Room Equipment Selections - R404A

Make a quick and easy selection of the right system for +2ºC to +4ºC applications.

MC-D8-ZB15

FH4522ZHR

WPH 40

(Supplied loose)

9

The chart shows a range of standard equipment selections designed to maintain an average room temperature of +2ºC to +4ºC based on the following design criteria:-

a) Ambient Temperature 32ºC.

b) Evaporator Temperature difference between air on and evaporating (delta T1) 5ºC to 7ºC.

c) Coldroom constructed from 75mm polyurethane insulation to walls, ceiling and floor, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 64kgs per m3 of Coldroom volume entering the room at no more than 6ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

*** The Power Supply shown equates to the total FLA of the Condensing Unit and Evaporator fans.

It assumes a defrost interlock such that defrost heaters and condensing units cannot operate at the same time.

POA: 1 phase control panels are available to special order for these applications.

The suitability of control panel application must be checked before the installation is undertaken.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

Coldroom Internal Volume

Cubic Metre 20 m3 23 m3 26 m3 28 m3 36 m3 42 m3 57 m3 71 m3 83 m3 100 m3

Cubic Feet 700 ft3 800 ft3 900 ft3 1000 ft3 1250 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 3500 ft3

Cooling Capacity 2.02 kW 2.26 kW 2.44 kW 2.63 kW 3.06 kW 3.45 kW 4.54 kW 5.46 kW 6.29 kW 7.01 kW

Rivacold Evaporator - Includes Electric Defrost (Full specification, page 16)

Rivacold Model RSI 3250ED RSI 3250ED RSI 3250ED RSI 4250ED RSI 4250ED RSI 4250EDRCMR 2350406-

EDRCMR 2350806-ED RCMR 2350806-ED RCMR 2350806-ED

HRP Code 040100 040100 040100 040103 040103 040103 040368 040371 040371 040371

Kobol Evaporator - Includes Electric Defrost (Full specification, page 17)

Kobol Model MR-21E MR-21E MR-21E MR-28E MR-28E MR-35E CR-52E CR-67E CR-79E CR-79E

HRP Code 080233 080233 080233 080276 080276 080306 081558 081582 081612 081612

HOUSEDStandard Specification • Weather Proof Housing • Liquid Line Drier & Sight Glass • Crankcase Heater • HP/LP Switches

Profroid Quietis Housed Condensing Unit (Full specification, page 20)

Profroid Model WPH 13 WPH 13 WPH 17 WPH 17 WPH 19 WPH 19 WPH 31 WPH 40 WPH 40 WPH 53

HRP Code - 1 phase 050108 050108 050112 050112 050116 050116 050124 050128 050128 -

HRP Code - 3 phase 050110 050110 050114 050114 050118 050118 050126 050130 050130 050146

Copeland OM Housed Scroll Condensing Unit - EazyCool (Full specification, page 21)

Copeland Model - - - - - OM 15 OM 21 OM 21 OM 26 OM 30

HRP Code - 1 phase - - - - - 450485 450487 450487 450489 -

HRP Code - 3 phase - - - - - 450491 450493 450493 450495 450497

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18. Fitted options, pages 28 & 29)

L’Unite Model CAJ9513ZMHR CAJ9513ZMHR CAJ9513ZMHR CAJ4517ZHR FH4522ZHR FH4522ZHR FH4531ZHR FH4531ZHR TFH4540ZHR TAG4546ZHR

HRP Code - 1 phase 439312 439312 439312 439320 439339 439339 439355 439355 - -

HRP Code - 3 phase 439436 439436 439436 439444 439460 439460 439487 439487 439495 439509

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model - - - - - MC D8 ZB15 MC-H8-ZB19 MC-H8-ZB21 MC-H8-ZB26 MC-H8-ZB30

HRP Code - 1 phase - - - - - 455262 455102 455110 455115 -

HRP Code - 3 phase - - - - - 455100 455104 455108 455116 455122

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479931 479931 479931 479932 479932 479932 479932 479932 479932 479932

The Installation PackCopper tube pack including Isoline insulation - see p 28

1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 5/8" x 3/8" 5/8" x 3/8" 5/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8" 7/8" x 3/8"

148500 148500 148500 148504 148504 148504 148508 148508 148508 148508Expansion Valve - Danfoss TES 2 300475 300475 300475 300475 300475 300475 300475 300475 300475 300475

- Orifice 300023 300023 300035 300035 300035 300035 300035 300035 300037 300037

Penn Controller

- 1 Phase (All Models) 193436 193436 193436 193439 POA POA POA POA POA POA

- 3 Phase (Rivacold) 193443 193443 193443 193443 193443 193443 193446 193446 193449 193449

- 3 Phase (Kobol) 193443 193443 193443 193443 193443 193443 193446 193447 193450 193450

Power Supply *** 1ph & N 12.05 amps 12.05 amps 12.05 amps 13.3 amps 18.7 amps 18.7 amps 29.16 amps 29.16 amps - -

3ph & N 5.65 amps 5.65 amps 5.65 amps 6.18 amps 7.6 amps 7.6 amps 10.2 amps 10.2 amps 11.26 amps 9.69 amps

IDEAL STORAGE CONDITIONS FOR FRESH PROVISION

PRODUCTS

Please refer to the guide on

page 35

TEMPERATURE

+2ºC to +4ºC

Step 1COLDROOM SIZE & COOLING kW

Step 2aEVAPORATOR

10

AND

OR

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

Step 3bCONDENSING UNIT

Step 2bEVAPORATOR

Step 3aCONDENSING UNIT

Preparation Room Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3 145 m3 167 m3 197 m3 229 m3

Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3 5000 ft3 6000 ft3 7000 ft3 8000 ft3

Cooling Capacity 3.07 kW 3.94 kW 5.52 kW 7.09 kW 8.68 kW 12.57 kW 16.18 kW 19.49 kW 24.06 kW 29.17 kW

Qualitair Low Temperature Cassette - R407C (Full specification, page 22) Remote Thermostat included

Qualitair Model QLC 10 QLC 15 QLC 20 - - - - - - -

HRP Code 546909 546895 546925 - - - - - - -

HRP Code - Fascia 546917 546879 546879 - - - - - - -

HOUSED

Qualitair Housed Outdoor Unit - R407C (Full specification, page 22)

Qualitair Model ICUS 40 ICUS 55 ICUS 80 - - - - -

HRP Code - 1 phase 547128 547130 547132 - - - - -

HRP Code - 3 phase - - 547008 - - - - -

Rivacold Low Velocity Dual Discharge Evaporator - R404A (Full specification, page 23)

Rivacold Model RDF 3250 RDF 23503 RDF 23503 2 x RDF 23503 2 x RDF 23503 2 x RDF 33503 2 x RDF 43503 2 x RDF 43503 4 x RDF 33503

HRP Code - 040496 040499 040499 040499 040499 040502 040505 040505 040502

UN-HOUSED

Copeland Scroll Un-Housed Condensing Unit - R404A (Full specification, page 23)

Copeland Model MC D8 ZB15KE MC D8 ZB19KE MC K9 ZB21KE MC H8 ZB30KE MC M9 ZB45 KE MC S9 ZB56 KE MC V6 ZB75KE MC V6 ZB75KE MC V6 ZB11ME

HRP Code - 1 phase - 455262 455102 455224 - - - - - -

HRP Code - 3 phase - 455100 455104 455190 455122 455130 455209 455212 455212 455218

DON’T FORGET... Fitted Liquid Line Drier & Sight Glass - 479932 479932 479933 479933 479933 479936 479936 479936 479937

Expansion Valve - Danfoss TES 2 - 300475 300475 300475 2 x 300475 2 x 300475 2 x 300475 2 x 300475 2 x 300475 4 x 300475(Rivacold only) - Orifice - 300035 300035 300035 2 x 200035 2 x 200035 2 x 200037 2 x 200039 2 x 200039 4 x 200037

The Installation PackCopper tube pack including Isoline insulation - see p 28

- 3/4" x 3/8" 3/4" x 3/8" 7/8" x 1/2" 7/8" x 1/2" 7/8" x 1/2" 1.3/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 3/4"

- 148506 148506 148510 148510 148510 148518 148518 148518 148520Control Panels (Rivacold only)

- 1 Phase - POA POA POA - - - - - -

- 3 Phase - 193442 193445 193445 193449 193452 POA POA POA POA

Power Supply 1ph & N 14.1 amps 19.1 amps 19.1 amps - - - - - - -

(Qualitair) 3ph & N - - 7.4 amps - - - - - - -

Power Supply *** 1ph & N - 13.5 amps 13.3 amps 17.48 amps - - - - - -

(Rivacold) 3ph & N - 5.5 amps 7.0 amps 7.74 amps 14.93 amps 18.78 amps 24.13 amps 30.66 amps 30.66 amps 41.44 amps

Food Preparation Room Equipment Selections

Make a quick and easy selection of the right system for +10ºC applications.

RDF 3250

ICUS 40

QLC 10

MC-D8-ZB15

TEMPERATURE

-00ºC

11

Preparation Room Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3 145 m3 167 m3 197 m3 229 m3

Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3 5000 ft3 6000 ft3 7000 ft3 8000 ft3

Cooling Capacity 3.07 kW 3.94 kW 5.52 kW 7.09 kW 8.68 kW 12.57 kW 16.18 kW 19.49 kW 24.06 kW 29.17 kW

Qualitair Low Temperature Cassette - R407C (Full specification, page 22) Remote Thermostat included

Qualitair Model QLC 10 QLC 15 QLC 20 - - - - - - -

HRP Code 546909 546895 546925 - - - - - - -

HRP Code - Fascia 546917 546879 546879 - - - - - - -

HOUSED

Qualitair Housed Outdoor Unit - R407C (Full specification, page 22)

Qualitair Model ICUS 40 ICUS 55 ICUS 80 - - - - -

HRP Code - 1 phase 547128 547130 547132 - - - - -

HRP Code - 3 phase - - 547008 - - - - -

Rivacold Low Velocity Dual Discharge Evaporator - R404A (Full specification, page 23)

Rivacold Model RDF 3250 RDF 23503 RDF 23503 2 x RDF 23503 2 x RDF 23503 2 x RDF 33503 2 x RDF 43503 2 x RDF 43503 4 x RDF 33503

HRP Code - 040496 040499 040499 040499 040499 040502 040505 040505 040502

UN-HOUSED

Copeland Scroll Un-Housed Condensing Unit - R404A (Full specification, page 23)

Copeland Model MC D8 ZB15KE MC D8 ZB19KE MC K9 ZB21KE MC H8 ZB30KE MC M9 ZB45 KE MC S9 ZB56 KE MC V6 ZB75KE MC V6 ZB75KE MC V6 ZB11ME

HRP Code - 1 phase - 455262 455102 455224 - - - - - -

HRP Code - 3 phase - 455100 455104 455190 455122 455130 455209 455212 455212 455218

DON’T FORGET... Fitted Liquid Line Drier & Sight Glass - 479932 479932 479933 479933 479933 479936 479936 479936 479937

Expansion Valve - Danfoss TES 2 - 300475 300475 300475 2 x 300475 2 x 300475 2 x 300475 2 x 300475 2 x 300475 4 x 300475(Rivacold only) - Orifice - 300035 300035 300035 2 x 200035 2 x 200035 2 x 200037 2 x 200039 2 x 200039 4 x 200037

The Installation PackCopper tube pack including Isoline insulation - see p 28

- 3/4" x 3/8" 3/4" x 3/8" 7/8" x 1/2" 7/8" x 1/2" 7/8" x 1/2" 1.3/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 3/4"

- 148506 148506 148510 148510 148510 148518 148518 148518 148520Control Panels (Rivacold only)

- 1 Phase - POA POA POA - - - - - -

- 3 Phase - 193442 193445 193445 193449 193452 POA POA POA POA

Power Supply 1ph & N 14.1 amps 19.1 amps 19.1 amps - - - - - - -

(Qualitair) 3ph & N - - 7.4 amps - - - - - - -

Power Supply *** 1ph & N - 13.5 amps 13.3 amps 17.48 amps - - - - - -

(Rivacold) 3ph & N - 5.5 amps 7.0 amps 7.74 amps 14.93 amps 18.78 amps 24.13 amps 30.66 amps 30.66 amps 41.44 amps

The chart shows a range of standard equipment selections designed to maintain an average room temperature of +10ºC based on the following design criteria:-

a) Ambient Temperature 32ºC.

b) Evaporator Temperature difference between air on and evaporating (delta T1) 8ºC to 10ºC.

c) Room construction is 50mm Polyurethane insulated panels, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 25kgs per m3 of room volume entering the room at no more than 5ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

f) Occupancy is based on one person per 4m3 of floor area carrying out light work.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

*** The systems do not require an external electrical control panel.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

IDEAL WORKING CONDITIONS FOR

THE PREPARATION OF FRESH PRODUCTS

Please refer to the guide on

page 35

TEMPERATURE

+10ºC

Step 1COLDROOM SIZE & COOLING kW

Step 2SELECT ONE EVAPORATOR

Step 3SELECT ONE CONDENSING UNIT

12

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

Coldroom Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3 145 m3 167 m3 197 m3 229 m3

Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3 5000 ft3 6000 ft3 7000 ft3 8000 ft3

Cooling Capacity 2.75 kW 3.48 kW 4.26 kW 4.93 kW 5.47 kW 6.77 kW 7.99 kW 8.89 kW 10.03 kW 11.21 kW

Rivacold Evaporator (Full specification, page 16)

Rivacold Model RSI 3250 RSI 3250 RSI 4250 RSI 23503 RSI 23503 RCMR 2350404 RCMR 3350604 RCMR 3350604 RCMR 3350604 RCMR 3350604

HRP Code 040070 040070 040073 040076 040076 040308 040314 040314 040314 040314

Kobol Evaporator (Full specification, page 17)

Kobol Model MR-21 MR-28 MR-35 CR 44 CR 52 CR 67 CR 79 CR 79 CR 96 CR 119

HRP Code 080063 080101 080144 080691 080721 080764 080799 080799 080829 080831

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18. Fitted options, pages 28 & 29)

L’Unite Model FH4518YHR FH4518YHR FH4525YHR TAG4528YHR TAG4528YHR TAG4534YHR TAG4543YHR - - -

HRP Code - 1 phase 431567 431567 431583 - - - - - - -

HRP Code - 3 phase 431575 431575 431591 431621 431621 431605 431613 - - -

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model MC-D8-ZB15KE MC-D8-ZB19KE MC-H8-ZB21KE MC-H8-ZB26KE MC-H8-ZB30KE MC H8 ZB38KE MC-M8-ZB45KE MC-M8-ZB45KE MC-M9-ZB45KE MC-R7-ZB56KE

HRP Code - 1 phase 455262 455102 455110 455114 - - - - - -

HRP Code - 3 phase 455100 455104 455112 455116 455122 455166 455128 455128 455130 455208

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479932 479932 479933 479934 479934 479935 479935 479935 479936 479937

The Installation PackCopper tube pack including Isoline insulation - see p 28

3/4" x 3/8" 7/8" x 3/8" 7/8" x 1/2" 1.1/8" x 1/2" 1.18" x 1/2" 1.1/8" x 5/8" 1.1/8" x 5/8" 1.1/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 3/4"

148506 148508 148510 148514 148514 148516 148516 148516 148518 148520Expansion Valve - Danfoss TES 2 300451 300451 300451 300451 300451 300451 300451 300451 300451

- Orifice 300023 300023 300035 300035 300037 300037 300037 300039 300041

Penn Controller

- 1 Phase (All Models) POA POA POA POA - - - - - -

- 3 Phase (Rivacold) 193442 193445 193445 193448 193448 193452 193452 193452 193452 POA

- 3 Phase (Kobol) 193442 193445 193445 193448 193448 193452 193452 193452 193452 POA

Power Supply *** 1ph & N 14.85 amps 14.7 amps 19.55 amps 20.65 amps - - - - - -

3ph & N 6.85 amps 8.4 amps 10.35 amps 11.5 amps 12.95 amps 15.65 amps 16.19 amps 16.19 amps 17.24 amps 18.49 amps

MC-D8-ZB15KE

Beer Cellar (above ground) Equipment Selections - R134A

Make a quick and easy selection of the right system for +10ºC applications.

MR-21

RSI 3250

FH4522ZHR

(Supplied loose)

13

Coldroom Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3 145 m3 167 m3 197 m3 229 m3

Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3 5000 ft3 6000 ft3 7000 ft3 8000 ft3

Cooling Capacity 2.75 kW 3.48 kW 4.26 kW 4.93 kW 5.47 kW 6.77 kW 7.99 kW 8.89 kW 10.03 kW 11.21 kW

Rivacold Evaporator (Full specification, page 16)

Rivacold Model RSI 3250 RSI 3250 RSI 4250 RSI 23503 RSI 23503 RCMR 2350404 RCMR 3350604 RCMR 3350604 RCMR 3350604 RCMR 3350604

HRP Code 040070 040070 040073 040076 040076 040308 040314 040314 040314 040314

Kobol Evaporator (Full specification, page 17)

Kobol Model MR-21 MR-28 MR-35 CR 44 CR 52 CR 67 CR 79 CR 79 CR 96 CR 119

HRP Code 080063 080101 080144 080691 080721 080764 080799 080799 080829 080831

UN-HOUSED

L’Unite Hermetique Un-Housed Condensing Unit (Full specification, page 18. Fitted options, pages 28 & 29)

L’Unite Model FH4518YHR FH4518YHR FH4525YHR TAG4528YHR TAG4528YHR TAG4534YHR TAG4543YHR - - -

HRP Code - 1 phase 431567 431567 431583 - - - - - - -

HRP Code - 3 phase 431575 431575 431591 431621 431621 431605 431613 - - -

Copeland Scroll Un-Housed Condensing Unit (Full specification, page 19. Fitted options, pages 28 & 29)

Copeland Model MC-D8-ZB15KE MC-D8-ZB19KE MC-H8-ZB21KE MC-H8-ZB26KE MC-H8-ZB30KE MC H8 ZB38KE MC-M8-ZB45KE MC-M8-ZB45KE MC-M9-ZB45KE MC-R7-ZB56KE

HRP Code - 1 phase 455262 455102 455110 455114 - - - - - -

HRP Code - 3 phase 455100 455104 455112 455116 455122 455166 455128 455128 455130 455208

DON’T FORGET... for Un-Housed Units - Workshop fitted accessories:Fitted Liquid Line Drier & Sight Glass 479932 479932 479933 479934 479934 479935 479935 479935 479936 479937

The Installation PackCopper tube pack including Isoline insulation - see p 28

3/4" x 3/8" 7/8" x 3/8" 7/8" x 1/2" 1.1/8" x 1/2" 1.18" x 1/2" 1.1/8" x 5/8" 1.1/8" x 5/8" 1.1/8" x 5/8" 1.3/8" x 5/8" 1.3/8" x 3/4"

148506 148508 148510 148514 148514 148516 148516 148516 148518 148520Expansion Valve - Danfoss TES 2 300451 300451 300451 300451 300451 300451 300451 300451 300451

- Orifice 300023 300023 300035 300035 300037 300037 300037 300039 300041

Penn Controller

- 1 Phase (All Models) POA POA POA POA - - - - - -

- 3 Phase (Rivacold) 193442 193445 193445 193448 193448 193452 193452 193452 193452 POA

- 3 Phase (Kobol) 193442 193445 193445 193448 193448 193452 193452 193452 193452 POA

Power Supply *** 1ph & N 14.85 amps 14.7 amps 19.55 amps 20.65 amps - - - - - -

3ph & N 6.85 amps 8.4 amps 10.35 amps 11.5 amps 12.95 amps 15.65 amps 16.19 amps 16.19 amps 17.24 amps 18.49 amps

The chart shows a range of standard equipment selections designed to maintain an average room temperature of +10ºC based on the following design criteria:-

a) Ambient Temperature 32ºC.

b) Evaporator Temperature difference between air on and evaporating (delta T1) 8ºC to 10ºC.

c) Room construction is un-insulated brickwork, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 16 litres per m3 of room volume entering the room at no more than 8ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

*** The Power Supply shown equates to the total FLA of the Condensing Unit and Evaporator fans.

It assumes a defrost interlock such that defrost heaters and condensing units cannot operate at the same time.

POA: 1 phase control panels are available to special order for these applications.

The suitability of control panel application must be checked before the installation is undertaken.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

IDEAL STORAGE CONDITIONS FOR FRESH PRODUCTS

AND BEER

Please refer to the guide on

page 35

TEMPERATURE

+10ºC

Step 1COLDROOM SIZE & COOLING kW

Step 2aEVAPORATOR

Step 3aCONDENSING UNIT

Step 4ADD THE INSTALLATION PACK FOR THE ABOVE COMBINATION

14

Step 2bEVAPORATOR

Step 3bCONDENSING UNIT

AND

OR

CX30

ICC 25M

Beer Cellar Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3

For larger beer cellar applications - please refer to Page 13Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3

Cooling Capacity 2.75 kW 3.48 kW 4.26 kW 4.93 kW 5.47 kW 6.77 kW

Qualitair Evaporator (Full specification, page 24)

Qualitair Model ICC25M ICC35M ICC50M ICC50M ICC50M ICC70M

HRP Code 540110 540055 540150 540150 540150 540170

HOUSED

Qualitair Housed Condensing Unit (Full specification, page 24)

Qualitair Model ICUS30 ICUS40 ICUS55M ICUS55M ICUS80 ICUS80

HRP Code - 1 phase 540050 540055 540061 540061 540066 540066

HRP Code - 3 phase - - - - 547134 547134

Marstair (TEV) Evaporator (Full specification, page 24)

Marstair Model CX30 CX40 CX50 CX50 CX70 CX70

HRP Code 507720 507723 507726 507726 507729 507729

HOUSED

Marstair (TEV) Housed Condensing Unit (Full specification, page 24)

Marstair Model CKR30 CKC30 CKR50 CKR50 CKC80 CKC80

HRP Code - 1 phase 507713 507747 507715 507715 507770 507770

HRP Code - 3 phase - - - - 507772 507772

DON’T FORGET... Drier, Sight Glass and Expansion Valve are includedFitted Liquid Line Drier & Sight Glass Standard Standard Standard Standard Standard Standard

Expansion Valve Standard Standard Standard Standard Standard Standard

The Installation PackCopper tube pack including Isoline insulation - see p 28

1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 5/8" x 3/8" 5/8" x 3/8"

148500 148500 148500 148500 148504 148504Integral Controls included

- 1 Phase Standard Standard Standard Standard Standard Standard

- 3 Phase Standard Standard Standard Standard Standard Standard

Power Supply *** 1ph & N 5.8 amps 8.2 amps 10.6 amps 10.6 amps 16.1 amps 16.1 amps

3ph & N - - - - 6 amps 6 amps

Beer Cellar (above ground) Equipment Selections - R407C

Make a quick and easy selection of the right system for +10ºC applications.

CKC30

ICUS 40

15

The chart shows a range of standard equipment selections designed to maintain an average room temperature of +10ºC based on the following design criteria:-

a) Ambient Temperature 32ºC.

b) Evaporator Temperature difference between air on and evaporating (delta T1) 8ºC to 10ºC.

c) Room construction is un-insulated brickwork, with average door usage and no mechanical loading of produce.

d) The product loading has been based on a maximum of 16 litres per m3 of room volume entering the room at no more than 8ºC above room temperature.

e) The refrigerant line sizes are based on a maximum pipe run of 15 metres in a horizontal plane.

For Coldroom equipment selections outside the range set out in this table please contact your local HRP Service Centre.

All product storage conditions should be verified with the Coldroom user and the manufacturer of the product.

All equipment selections must be verified by the installer prior to installation.

The HRP SELECTOR DISC is available for other refrigeration applications not covered in this Selection Guide. Please contact your local HRP Service Centre.

IDEAL STORAGE CONDITIONS FOR SELECTED FRESH

PRODUCTS AND BEER

Please refer to the guide on

page 35

TEMPERATURE

+10ºC

Beer Cellar Internal Volume

Cubic Metre 28 m3 42 m3 57 m3 72 m3 83 m3 114 m3

For larger beer cellar applications - please refer to Page 13Cubic Feet 980 ft3 1500 ft3 2000 ft3 2500 ft3 3000 ft3 4000 ft3

Cooling Capacity 2.75 kW 3.48 kW 4.26 kW 4.93 kW 5.47 kW 6.77 kW

Qualitair Evaporator (Full specification, page 24)

Qualitair Model ICC25M ICC35M ICC50M ICC50M ICC50M ICC70M

HRP Code 540110 540055 540150 540150 540150 540170

HOUSED

Qualitair Housed Condensing Unit (Full specification, page 24)

Qualitair Model ICUS30 ICUS40 ICUS55M ICUS55M ICUS80 ICUS80

HRP Code - 1 phase 540050 540055 540061 540061 540066 540066

HRP Code - 3 phase - - - - 547134 547134

Marstair (TEV) Evaporator (Full specification, page 24)

Marstair Model CX30 CX40 CX50 CX50 CX70 CX70

HRP Code 507720 507723 507726 507726 507729 507729

HOUSED

Marstair (TEV) Housed Condensing Unit (Full specification, page 24)

Marstair Model CKR30 CKC30 CKR50 CKR50 CKC80 CKC80

HRP Code - 1 phase 507713 507747 507715 507715 507770 507770

HRP Code - 3 phase - - - - 507772 507772

DON’T FORGET... Drier, Sight Glass and Expansion Valve are includedFitted Liquid Line Drier & Sight Glass Standard Standard Standard Standard Standard Standard

Expansion Valve Standard Standard Standard Standard Standard Standard

The Installation PackCopper tube pack including Isoline insulation - see p 28

1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 1/2" x 3/8" 5/8" x 3/8" 5/8" x 3/8"

148500 148500 148500 148500 148504 148504Integral Controls included

- 1 Phase Standard Standard Standard Standard Standard Standard

- 3 Phase Standard Standard Standard Standard Standard Standard

Power Supply *** 1ph & N 5.8 amps 8.2 amps 10.6 amps 10.6 amps 16.1 amps 16.1 amps

3ph & N - - - - 6 amps 6 amps

16

Rivacold Model RCMR... 2350406 ED 2350806 ED 2350404 3350604

HRP Code - Electric Defrost 040368 040371 - -

HRP Code - Off-Cycle Defrost - - 040308 040314

Fin Spacing mm 6 6 4 4

Air Throw m 14 14 14 15

No. of Fans No. 2 x 350 2 x 350 2 x 350 3 x 350

Dimensions W x H x D mm 1304x475x450 1304x475x450 1304x475x450 1754x475x450

Net Weight kg 38.1 49.05 37.71 61.29

Connection Sizes Inlet 1/2" flare 5/8" flare 1/2" flare 7/8" sweat

Outlet 1.1/8" sweat 1.1/8" sweat 1.1/8" sweat 1.3/8" sweat

Condensation Drain Drain 1" Gas 1" Gas 1" Gas 1" Gas

Circuit Volume dm3 5.26 10.6 5.26 11.1

Motor Consumption A 1.16 1.16 1.16 1.74

230V-1ph-50hZ W 260 260 260 390

Electric Defrost A 11.2 11.2 - -

230V-1ph-50hZ W 2800 2800 - -

Rivacold Model RC... 325-33ED 325-45ED 425-61ED

HRP Code - Electric Defrost 040151 040154 040157

HRP Code - Off-Cycle Defrost 040133 040136 040139

Fin Spacing mm 5.3 5.3 5.3

Air Throw m 7.5 7 7

No. of Fans No. 3 x 250mm 3 x 250mm 4 x 250mm

Dimensions W x H x D mm 1314x350x330 1314x350x330 1684x350x330

Net Weight kg 27 30 40.2

Connection Sizes Inlet 1/2" flare 1/2" flare 1/2" flare

Outlet 7/8" sweat 7/8" sweat 1.1/8" sweat

Condensation Drain Drain 1" Gas 1" Gas 1" Gas

Circuit Volume dm3 3.17 4.77 6.7

Motor Consumption A 1.35 1.35 1.8

230V-1ph-50hZ W 195 195 260

Electric Defrost A 7.8 7.8 10.8

230V-1ph-50hZ W 1950 1950 1950

Rivacold Model RSI... 2250 ED 3250 ED 4250 ED 23503

HRP Code - Electric Defrost 040097 040100 040103 -

HRP Code - Off-Cycle Defrost - 040070 040073 040076

Fin Spacing mm 5.3 5.3 5.3 3.5

Air Throw m 7 8.5 9.5 10

No. of Fans No. 2 x 250 3 x 250 4 x 250 2 x 350

Dimensions W x H x D mm 935x241x461 1305x241x461 1675x241x461

Net Weight kg 18 22 28 36

Connection Sizes Inlet 1/2" flare 1/2" flare 1/2" flare 1/2" flare

Outlet 5/8" sweat 7/8" sweat 7/8" sweat 7/8" sweat

Condensation Drain Drain 1" Gas 1" Gas 1" Gas 1" Gas

Circuit Volume dm3 2.26 3.18 4.19 4.88

Motor Consumption A 0.9 1.35 1.8 1.3

230V-1ph-50hZ W 130 195 260 280

Electric Defrost A 3.6 5.2 7.2 -

230V-1ph-50hZ W 900 1300 1800 -

The RCMR series is suitable for all HCFC & HFC refrigerants for operation at room temperatures ranging from +10oC to -35oC.

The RCMR coil block is manufactured from rifled copper tube and has 4mm and 6mm fin spacing dependant on the model.

Casings are manufactured from white powder coated aluminium. Fan motors are all 230V 1ph 50/60Hz fitted with thermal protection.

All ED models are fitted with electric defrost heaters as standard.

RCMR Series

The RC series is suitable for all HCFC & HFC refrigerants for operation at room temperatures of +10oC to -30oC.

Fin spacing is 5.3mm on all models.

Casings are manufactured from white powder coated aluminium and assembled with stainless steel screws and washers.

Fan motors are suitable for 230V 1ph 50/60Hz and are fitted with thermal protection.

Defrost heaters are fitted as standard to all ED models.

RC Series

The RSI series of unit coolers is suitable for all HCFC & HFC refrigerants for operation at room temperatures of +12oC to -30oC.

250mm fan models have 5.3mm fin spacing for room temperatures of 0oC to -30oC whereas the 350mm fan model shown on this page has 3.5mm fin spacing for room temperatures of +12oC to -5oC. All casings are manufactured from white powder coated aluminium.

Fan motors are suitable for 230V 1ph 50/60Hz and fitted with thermal protection.

Electric defrost heaters are fitted as standard to all ED models.

RSI Series

RivacoldTechnical Data

17

Model CC... 27 E 33 E 41 E - 56 E 75 E -

CR... - - 52 E 67 E 79 E - -

CR... - 44 52 67 79 96 119

HRP Code - Electric Defrost 081884 081914 081949 - 082015 082058 -

HRP Code - Electric Defrost - - 081558 081582 081612 - -

HRP Code - Off-Cycle Defrost - 080691 080721 080764 080799 080829 080831

Fin Spacing - CC mm 7 7 7 - 7 7 -

Fin Spacing - CR mm - 4.5 4.5 4.5 4.5 4.5 4.5

Air Throw m 20 19 17 18 24 23 28

No. of Fans No. 1 x 350 2 x 315 2 x 315 3 x 315 2 x 350 2 x 350 2 x 350

Dimensions W x H x D mm 905x565x490 1145x440x450 1145x440x450 1595x410x450 1565x565x490 1565x565x490 2225x565x490

Net Weight kg 25.5 29.5 38 42 47 57 67

Connection Sizes Inlet 1/2" flare 1/2" flare 1/2" flare 1/2" flare 1/2" flare 5/8" flare 5/8" flare

Outlet 5/8" sweat 5/8" sweat 7/8" sweat 7/8" sweat 7/8" sweat 1.1/8" sweat 1.1/8" sweat

Condensation Drain Drain 3/4" Gas 3/4" Gas 3/4" Gas 1.1/4" Gas 1.1/4" Gas 1.1/4" Gas 1.1/4" Gas

Motor Consumption A 0.58 1.00 1.00 1.50 1.16 1.16 1.74

230V-1ph-50hZ W 145 220 220 330 290 290 435

Electric Defrost A 12.07 12.65 12.65 18.08 22.1 22.1 31.57

230V-1ph-50hZ W 3017 3162 3162 4521 5525 5525 7892

CC Series: 0.57 to 10.48 kW at -18oC room temperature at 7oCTD

CR Series: 1.2 to 16.87 kW at 0oC room temperature at 8oCTD

A wide range of ceiling mounted commercial unit coolers suitable for all HCFC & HFC refrigerants and operation at room temperatures ranging from +12oC to -25oC. The casing is manufactured from white enamelled galvanized steel and is easily removed for access to internal parts. All fans are 230V 1ph 50Hz external rotor axial flow with insulation class B, IP44 thermally protected.

All CR series models are available with and without electric defrost heaters whereas the CC series are all fitted with heaters as standard.

CC/CR Series

Kobol Model MC... 23 E 30 E MR... 21 E 28 E 35 E

HRP Code - Electric Defrost 080446 080470 080233 080276 080306

HRP Code - Off-Cycle Defrost - - 080063 080101 080144

Fin Spacing mm 7 7 4.2 4.2 4.2

Air Throw m 7.5 8.5 5.5 6.5 7.5

No. of Fans No. 4 x 250 5 x 250 3 x 250 4 x 250 5 x 250

Dimensions W x H x D mm 1435x195x480 1740x195x480 1130x195x480 1435x195x480 1740x195x480

Net Weight kg 24 30 19 24 30

Connection Sizes Inlet 1/2" flare 1/2" flare 1/2" flare 1/2" flare 1/2" flare

Outlet 5/8" sweat 5/8" sweat 5/8" sweat 5/8" sweat 5/8" sweat

Condensation Drain Drain 3/4" Gas 3/4" Gas 3/4" Gas 3/4" Gas 3/4" Gas

Motor Consumption A 1.4 1.75 1.05 1.4 1.75

230V-1ph-50hZ W 224 280 168 224 280

Electric Defrost A 7.8 9.6 2.95 3.85 4.75

230V-1ph-50hZ W 1931 2382 735 961 1186

MC Series: 504 to 2702 watts at -18oC room temperature at 7oCTD

MR Series: 811 to 3964 watts at 0oC room temperature at 8oCTD

A compact panel cooler suitable for all HCFC & HFC refrigerants for operation at room temperatures ranging from +12oC to -22oC. The MR series has 4.2mm fin spacing and is intended for room temperatures of +2oC to -10oC, whereas the MR series has 7mm fin spacing and is intended for room temperatures of -5oC to -22oC. The casing is manufactured from white enamelled galvanized steel and is easily removable to gain access to internal parts. All fans are 250mm 1ph axial flow with galvanized steel fan guards. All MR series are available with and without electric defrost heaters whereas the MC series are fitted with defrost heaters as standard.

MC/MR Series

KobolTechnical Data

18

Model CAJ CAJ CAJ FH/TFH FH/TFH FH/TFH TFH

9510 ZMHR 9513 ZMHR 4517 ZHR 4522 ZHR 4524 ZHR 4531 ZHR 4540 ZHR

HRP Code - 1 phase 439304 439312 439320 439339 439347 439355 -

HRP Code - 3 phase 439428 439436 439444 439460 439379 439487 439495

Liquid Receiver Volume kg 2.23 2.23 2.23 3.70 3.70 5.70 5.70

litre 2.35 2.35 2.35 3.90 3.90 6.00 6.00

Refrigerant Connections Suction (sw) 5/8" 5/8" 5/8" 5/8" 5/8" 7/8" 7/8"

(sweat) Liquid (sw) 3/8" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2"

Dimensions W x H x D mm 430x340x490 430x340x490 510x450x615 510x450x630 510x450x630 1002x469x618 1002x469x642

Weight kg 40 43 50 59 61 100 100

Condenser Fan No. 1 1 1 1 1 2 2

Air Flow m3/hr 980 980 2200 2250 2480 4800 4800

Sound Power @ 10m +/-2dBA 68 68 75 75 76 77 81

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (F) Max Run Amps 7.7 10.7 11.5 16.9 19 28 -

Locked Rotor Amps 29.7 30.7 34 48 51 70 -

420V-3ph-50hZ (T) Max Run Amps 3.4 4.3 4.38 5.8 6.72 9.04 10.1

Locked Rotor Amps 13.5 13.5 19 25 25 28.5 46

Unit Housing (Flat Pack)

HRP Code 291110 291110 291129 291129 291129 291145 291145

• Compressor charged with Ester oil

• Rotolock connections and sweat valves on the compressor and liquid receiver

• Pre-wired electrical box

• Compressor mounted on rubber grommets

• Holding charge of dry nitrogen

• Dual HP/LP switch on FH and TAG (Optional extra on CAJ)

• Crankcase heater on FH and TAG. (Optional extra on CAJ)

L’Unite Hermetique Condensing Unit Technical Data

Model FH/TFH FH/TFH TAG FH/TFH FH/TFH TAG TAG TAG

2480 ZBR 2511 ZBR 4546 ZHR 4518 YHR 4525 YHR 4528 YHR 4534 YHR 4543 YHR

HRP Code - 1 phase 431714 431712 - 431567 431583 - - -

HRP Code - 3 phase 431710 431729 439509 431575 431591 431621 431605 431613

Liquid Receiver Volume kg 3.70 3.70 5.70 2.23 3.70 5.70 5.70 5.70

litre 3.90 3.90 6.00 2.35 3.90 6.00 6.00 6.00

Refrigerant Connections Suction (sw) 5/8" 5/8" 7/8" 5/8" 5/8" 7/8" 7/8" 7/8"

(sweat) Liquid (sw) 3/8" 3/8" 5/8" 3/8" 3/8" 3/8" 3/8" 3/8"

Dimensions W x H x D mm 510x450x630 510x450x630 1080x565x650 510x450x630 510x450x630 600x560x670 1002x469x618 1002x469x642

Weight kg 61 62 115 58 62 89 107 116

Condenser Fan No. 1 1 2 1 1 1 2 2

Air Flow m3/hr 2500 2700 7000 2250 2250 3540 4800 4800

Sound Power @ 10m +/-2dBA 76 76 84 75 77 80 78 79

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (F) Max Run Amps 20.1 24.9 - 12.1 16.1 - - -

Locked Rotor Amps 70 83 - 48 57 - - -

420V-3ph-50hZ (T) Max Run Amps 4.33 5.43 8.53 4.58 6.03 4.98 5.65 6.8

Locked Rotor Amps 24 29 43 25 25 41.5 43 43

Unit Housing (Flat Pack)

HRP Code 291129 291129 291145 291129 291129 291137 291145 291145

19

Copeland Scroll CondensingUnit Technical Data

Model MC-D8-ZB MC-D8-ZB MC-H8-ZB MC-H8-ZB MC-H8-ZB MC-H8-ZB MC-H8-ZB

15KE 19KE 15KE 19KE 21KE 26KE 30KE

HRP Code - 1 phase 455262 455102 455270 455106 455110 455114 -

HRP Code - 3 phase 455100 455104 455188 455108 455112 455116 455122

Liquid Receiver Volume kg 3.5 3.5 7.1 7.1 7.1 7.1 7.1

litre 3.7 3.7 7.5 7.5 7.5 7.5 7.5

Refrigerant Connections Suction (sw) 3/4" 3/4" 3/4" 3/4" 7/8" 7/8" 7/8"

(sweat) Liquid (sw) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

Dimensions W x H x D mm 560x446x570 560x446x570 735x533x680 735x533x680 735x533x680 735x533x680 735x533x680

Weight kg 48.0 59 59 61 61 62 74

Condenser Fan No. 1 1 1 1 1 1 1

Air Flow m3/hr 1836 1836 3600 3600 3600 3600 3600

Sound Power @ 10m +/-2dBA 45.0 45.3 48.1 48.1 48.3 48.5 48.4

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (PFJ) Max Run Amps 13.5 13.3 14.2 14.2 17.75 19.35 -

Locked Rotor Amps 59 61 59 61 82 97 -

420V-3ph-50hZ (TFD) Max Run Amps 5.5 7.0 6.35 7.9 8.55 10.2 11.65

Locked Rotor Amps 26 32 26 32 40 46 49

Unit Housing (Flat Pack)

HRP Code 450913 450913 450213 450213 450213 450213 450213

• Compressor charged with Ester oil

• Rotolock connections and sweat valves on the compressor and liquid receiver

• Pre-wired electrical box

• Alco PS3 HP switch fitted to all models with compressors smaller than ZB38KE and ZF15KE, Alco dual HP/LP switch fitted to all other models

• Crankcase heater

• Oil sight glass and Schrader connection for oil fill/drain

• Compressor mounted on rubber grommets

Model MC-H8-ZB MC-M8-ZB MC-M8-ZB MC-M9-ZB MC-P8-ZB MC-R7-ZB

38KE 38KE 45KE 45KE 30KE 56KE

HRP Code - 1 phase - - - - - -

HRP Code - 3 phase 455166 455126 455128 455130 455194 455208

Liquid Receiver Volume kg 7.1 7.1 7.1 7.1 7.1 7.1

litre 7.5 7.5 7.5 7.5 7.5 7.5

Refrigerant Connections Suction (sw) 7/8" 7/8" 7/8" 7/8" 7/8" 1.3/8"

(sweat) Liquid (sw) 1/2" 1/2" 1/2" 1/2" 1/2" 5/8"

Dimensions W x H x D mm 735x533x680 735x708x108 735x708x708 735x708x708 950x633x640 1130x633x820

Weight kg 77 89 91 96 97 158

Condenser Fan No. 1 1 1 1 2 2

Air Flow m3/hr 3600 3312 3312 4464 3816 7092

Sound Power @ 10m +/-2dBA 48.6 48.1 48.5 49.5 47.7 54.5

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (PFJ) Max Run Amps - - - - - -

Locked Rotor Amps - - - - - -

420V-3ph-50hZ (TFD) Max Run Amps 14.15 14.15 14.45 15.50 10.84 16.75

Locked Rotor Amps 66 66 74 74 49 99

Unit Housing (Flat Pack)

HRP Code 450213 450316 450316 450316 450416 450513

20

Model WPH 13 WPH 17 WPH 19 WPH 24 WPH 31 WPH 40 WPH 53

HRP Code - 1 phase 050108 050112 050116 050120 050124 050128 -

HRP Code - 3 phase 050110 050114 050118 050122 050126 050130 050146

Liquid Receiver Volume kg 2.47 2.47 2.47 3.80 3.80 3.80 5.70

litre 2.60 2.60 2.60 4.00 4.00 4.00 6.00

Refrigerant Connections Suction (sw) 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" 7/8"

(sweat) Liquid (sw) 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 1/2"

Dimensions W x H x D mm 935x485x325 1120x620x325 1120x620x325 1120x620x325 1120x620x325 1120x620x325 1180x1200x420

Weight kg 60 90 90 90 90 90 140

Condenser Fan No. 1 1 1 1 1 1 2

Air Flow m3/hr 900 1800 1800 1800 2800 2500 3300

Sound Power @ 10m +/-2dBA 29 32 33 34 37 40 42

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (F) Max Run Amps 10.5 11.6 16.4 19.1 27.7 28.4 -

Locked Rotor Amps 30.7 34 35 51 70 92 -

420V-3ph-50hZ (T) Max Run Amps 4.30 4.90 5.80 6.20 9.50 10.60 14

Locked Rotor Amps 13.5 19 23 25 28.5 46 57

Model WPL 08 WPL 11 WPL 16 WPL 22

HRP Code - 1 phase 050136 050140 - -

HRP Code - 3 phase 050138 050142 050154 050156

Liquid Receiver Volume kg 2.47 2.47 5.70 5.70

litre 2.60 2.60 6.00 6.00

Refrigerant Connections Suction (sw) 5/8" 5/8" 7/8" 7/8"

(sweat) Liquid (sw) 3/8" 3/8" 3/8" 3/8"

Dimensions W x H x D mm 1120x620x325 1120x620x325 1180x1200x420 1180x1200x420

Weight kg 90 90 140 150

Condenser Fan No. 1 1 2 2

Air Flow m3/hr 1800 1800 3300 3300

Sound Power @ 10m +/-2dBA 34 35 36 38

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (C) Max Run Amps 20.2 25.0 - -

Locked Rotor Amps 70 83 - -

420V-3ph-50hZ (A) Max Run Amps 4.9 6.0 10.8 15.0

Locked Rotor Amps 24 29 46 65

• Compressor charged with Ester oil

• High and Low pressure safety switches

• Crankcase heater

• Suction and liquid shut off valves

• 8 pole low noise condenser fan(s)

• Condenser fan speed controller

• Liquid Receiver

• Liquid line drier and sight glass

• Pressure relief valve

• Galvanised sheet steel housing power painted (RAL7035)

• Accessible compressor compartment & top panels for easy maintenance

• Acoustic lining fitted to the compressor compartment

• Wall mounting kit (for single fan units only)

• Lockable Main Electrical Isolator

• Compressor contactor and circuit breakers

Profroid Housed CondensingUnit Technical Data

21

These low noise models are interchangeable with the standard models shown above for sites where noise levels are critical.

Low Noise Level Models OMQ 15 OMQ 21 OMQ 26 OMQ 30 OMQ 38 OMQ 45

HRP Code - 1 phase 450517 450519 450521 - - -

HRP Code - 3 phase 450523 450525 450527 450529 450531 450533

Liquid Receiver Volume kg 3.50 7.12 7.12 7.12 7.12 7.12

litre 3.70 7.50 7.50 7.50 7.50 7.50

Refrigerant Connections Suction (sw) 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"

(sweat) Liquid (sw) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

Dimensions W x H x D mm 1050x720x630 1050x720x630 1050x720x630 1050x720x630 1250x720x642 1250x720x642

Weight kg 74 84 85 98 99 118

Condenser Fan No. 1 1 1 1 1 1

Air Flow m3/hr 1908 3240 3240 2988 2988 3564

Sound Power @ 10m +/-1.5dBA 35 38 38 38 38 39

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (F) Max Run Amps 13.61 17.21 18.81 - - -

Locked Rotor Amps 58 82 97 - - -

420V-3ph-50hZ (T) Max Run Amps 7.11 8.01 9.66 11.11 13.61 13.91

Locked Rotor Amps 24 40 46 49.3 65.5 74

Standard Noise Level Models OM 15 OM 21 OM 26 OM 30 OM 38 OM 45

HRP Code - 1 phase 450485 450487 450489 - - -

HRP Code - 3 phase 450491 450493 450495 450497 450499 450501

Liquid Receiver Volume kg 3.50 7.12 7.12 7.12 7.12 7.12

litre 3.70 7.50 7.50 7.50 7.50 7.50

Refrigerant Connections Suction (sw) 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"

(sweat) Liquid (sw) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

Dimensions W x H x D mm 1050x720x630 1050x720x630 1050x720x630 1050x720x630 1250x720x642 1250x720x642

Weight kg 74 84 85 98 99 118

Condenser Fan No. 1 1 1 1 1 1

Air Flow m3/hr 2196 3744 3744 3708 3708 4068

Sound Power @ 10m +/-1.5dBA 46 49 49 49 49 50

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (F) Max Run Amps 13.5 17.8 19.4 - - -

Locked Rotor Amps 58 82 97 - - -

420V-3ph-50hZ (T) Max Run Amps 7.7 8.6 10.23 11.7 14.18 14.48

Locked Rotor Amps 24 40 46 49.3 65.5 74

• Compressor charged with Ester oil

• High and Low pressure safety switches

• Crankcase heater

• Suction and liquid shut off valves

• Oil service valve

• Oil sight glass

• Liquid Receiver

• Liquid line drier and sight glass

• Liquid line solenoid valve

• Pressure relief valve connection

• Weather resistant house manufactured from synthetic resin

• Accessible compressor compartment & top panels for easy maintenance

• Compressor contactor and circuit breakers

• Acoustic Jacket (Low Noise Level ‘Q’ Models only)

• Sickle blade condenser fan (Low Noise Level ‘Q’ Models only)

Copeland Scroll EazyCool Condensing Unit Technical Data

22

Model Cassette Unit QLC 10 QLC 15 QLC 20 QLC 10 QLC 15 QLC 20

Condensing Unit** ICUS 40 ICUS 55 ICUS 80 Condensing

Unit*** ICU 40 ICU 55 ICU 80

HRP Code - Cassette 546909 546895 546925 546909 546895 546925

HRP Code - Fascia 546917 546879 546879 546917 546879 546879

HRP Code - Condensing Unit 1 phase 547128 547130 547132 546981 546989 547004

HRP Code - Condensing Unit 3 phase - - 547008 - - 547028

Refrigerant Connections Suction 5/8" 5/8" 5/8" 5/8" 5/8" 5/8"

(Condensing Unit) Liquid 1/4" 1/4" 3/8" 1/4" 1/4" 3/8"

EvaporatorDimensions W x H x D mm 1165x299x535 1165x349x735 1165x349x735 1165x299x535 1165x349x735 1165x349x735

Air Volume Litres/sec 310 540 560 310 540 560

Noise Level dBA 53 59 59 53 59 59

Weight kg 52.5 75 75 52.5 75 75

Condensing UnitDimensions W x H x D mm 720x610x250 800x765x320 800x765x320 720x610x250 800x765x320 800x765x320

Weight kg 42 60 64 42 60 64

Sound Power @ 10m dBA 48 47 56 48 47 56

System Electrical Data (Cooling)Full Load Amps - 1 phase 7.6 11.6 17.2 7.6 11.6 17.2

- 3 phase - - 7.0 - - 7.0

System Electrical Data (Heating)Full Load Amps - 1 phase 14.1 19.1 19.1 14.1 19.1 19.1

- 3 phase - - 7.4 - - 7.4

**ICUS Condensing Units: Factory charged with OFN

Max pipe run 30 metres***ICUS Condensing Units:

Factory charged with R407C

Max pipe run 100 metres

• 4 way discharge cassette

• Designed for food preparation areas

• Controls down to 10°C

• Remote thermostat supplied

• Optional heater kit available

• Available without restrictor - suitable for Multi Compressor Pack Systems

• Up to 100m (equivalent length) pipe runs

• Outdoor units are charged with Oxygen Free Nitrogen as a holding charge which must be evacuated prior to charging with R407C on site during the commissioning process

Qualitair R407C

Low Temperature Cassette Systems Technical Data

23

The RDF series of unit coolers are suitable for all HCFC & HFC refrigerants for operation at room temperatures of +12oC to -30oC.

The range has two fin spacings: 3.5mm for room temperatures of +2oC to +10oC and 3.5mm fin spacing for room temperatures of +2oC to -30oC. All casings are manufactured from white powder coated aluminium.

Fan motors are suitable for 230V 1ph 50/60Hz and fitted with thermal protection. Coolers are delivered with fans wired for high speed operation (1360rpm) but are easily re-wired for low speed at 1050 rpm. The Food Preparation Room selections in this catalogue are all based on low speed fan operation.

Electric defrost heaters are fitted as standard to all ED models.

RDF Dual Discharge (Low Velocity)

Model MC-D8-ZB MC-D8-ZB MC-K9-ZB MC-H8-ZB MC-M9-ZB MC-S9-ZB MC-V6-ZB MC-V6-ZB

15KE 19KE 21KE 30KE 45KE 56 75KE 11ME

HRP Code - 1 phase 455262 455102 455224 - - - - -

HRP Code - 3 phase 455100 455104 455190 455122 4552130 455209 455212 455218

Liquid Receiver Volume kg 3.5 3.5 7.1 7.1 7.1 10.9 13.3 13.3

litre 3.7 3.7 7.5 7.5 7.5 11.5 14 14

Refrigerant Connections Suction (sw) 3/4" 3/4" 7/8" 7/8" 7/8" 1.3/8" 1.3/8" 1.5/8"

(sweat) Liquid (sw) 1/2" 1/2" 1/2" 1/2" 1/2" 5/8" 5/8" 3/4"

Dimensions W x H x D mm 560x446x570 560x446x570 950x454x640 735x533x680 735x533x680 1130x708x820 1330x835x820 1330x835x820

Weight kg 48.0 19.0 74 74 61 165 205 212

Condenser Fan No. 1 1 2 1 1 2 2 2

Air Flow m3/hr 1836 1836 3204 3600 3600 6984 10692 10692

Sound Power @ 10m +/-2dBA 45.0 45.3 47.1 48.4 48.3 54 57.4 57.4

Electrical Data - Condensing Unit Total

240V-1ph-50hZ (PFJ) Max Run Amps 13.5 13.3 17.5 - 17.75 - - -

Locked Rotor Amps 59 61 82 - 82 - - -

420V-3ph-50hZ (TFD) Max Run Amps 5.5 7.0 7.74 11.65 8.55 16.75 24.1 31.6

Locked Rotor Amps 26 32 40 49 40 99 127 198

Unit Housing (Flat Pack)

HRP Code 450913 450913 450290 450213 450213 450513 450516 450516

• Compressor charged with Ester oil

• Rotalock connections and sweat valves on the compressor and liquid receiver

• Pre-wired electrical box

• Alco PS3 HP switch fitted to all models with compressors smaller than ZB38KE and ZF15KE, Alco dual HP/LP switch fitted to all other models

• Crankcase heater

• Oil sight glass and Schrader connection for oil fill/drain

• Compressor mounted on rubber grommetsCopeland Scroll

Food Preparation Room Equipment Technical Data

Rivacold Model RDF... RDF 3250 RDF 23503 RDF 33503 RDF 43503

HRP Code - Electric Defrost 040529 040532 040535 040538

HRP Code - Off-Cycle Defrost 040496 040499 040502 040505

Fin Spacing mm 3.5 3.5 3.5 3.5

Air Throw m 8 9 11 12

No. of Fans No. 3 x 250 2 x 250 3 x 250 4 x 250

Dimensions W x H x D mm 1322x155x638 1366x241x756 1816x241x756 2266x241x756

Net Weight kg 28.5 36.1 50.4 60.6

Connection Sizes Inlet 1/2" flare 1/2" flare 1/2" flare 5/8" flare

Outlet 5/8" sweat 7/8" sweat 1.1/8" sweat 1.3/8" sweat

Condensation Drain Drain 1/2" Gas 1" Gas 1" Gas 1" Gas

Circuit Volume dm3 3.73 5.27 7.48 9.67

Motor Consumption A 1.35 1.64 2.46 3.28

230V-1ph-50hZ W 195 356 534 712

Electric Defrost A 10 11.2 16.38 21.44

230V-1ph-50hZ W 2500 2800 4096 5360

24

• 6 fins per inch brewery specification

• Moulded LMDPE plastic case

• Case incorporates an anti-bacterial additive

• Integral controls in Evaporator Unit

• Light-weight unit

• Controls temperature down to 10°C as standard

• De-ice thermostat option (allows control down to 8°C)

• Optional heater kit available

• Outdoor units are charged with Oxygen Free Nitrogen as a holding charge which must be evacuated prior to charging with R407C on site during the commissioning process

• CKC fitted with scroll compressor

• CKR fitted with rotary compressor

Marstair CellarKing R407C

• Robust stainless steel design

• 6 fins per inch brewery specification

• Integral controls in Evaporator Unit

• Controls temperature down to 8°C as standard (4oC when fitted with electronic controller)

• Wall or ceiling mounted indoor unit

• De-ice thermostat fitted

• Units available with factory fitted electric heater

• Up to 30m (equivalent length) pipe runs

• Outdoor units are charged with Oxygen Free Nitrogen as a holding charge which must be evacuated prior to charging with R407C on site during the commissioning process

Qualitair Invicta R407C

Beer Cellar Cooler Systems Technical Data

Model Evaporator ICC25M ICC35M ICC50M ICC50M ICC70M

Condensing Unit ICUS30 ICUS40 ICUS55M ICUS80 ICUS80

HRP Code - Evaporator 540110 540130 540151 540150 540170

HRP Code - Condensing Unit 1 phase 540050 540055 540061 540066 540066

HRP Code - Condensing Unit 3 phase - - - 547134 547134

Refrigerant Connections Suction 5/8" 5/8" 5/8" 5/8" 5/8"

(Condensing Unit) Liquid 3/8" 3/8" 3/8" 3/8" 3/8"

EvaporatorDimensions W x H x D mm 805x450x475 805x450x475 805x450x475 805x450x475 805x450x475

Weight kg 25 27 27 27 40

Condensing UnitDimensions W x H x D mm 720x610x250 720x610x250 800x765x320 800x765x320 800x765x320

Weight kg 42 42 60 64 64

Sound Power @ 10m dBA 48 48 47 53 53

System Electrical Data (Cooling)Full Load Amps - 1 phase 3.3 6.6 10.6 16.1 16.1

- 3 phase - - - 6 6

Optional System Electrical Data (Heating)- 1 phase 13.8 13.8 13.8 13.8 18.4

- 3 phase - - - - -

Model Evaporator CX30 CX40 CX50 CX70

Condensing Unit CKR30 CKC30 CKR50 CKC80

HRP Code - Evaporator 507720 507723 507726 507729

HRP Code - Condensing Unit 1 phase 507713 507747 507715 507770

HRP Code - Condensing Unit 3 phase - - - 507772

Refrigerant Connections Suction 5/8" 5/8" 5/8" 5/8"

(Condensing Unit) Liquid 3/8" 3/8" 3/8" 3/8"

EvaporatorDimensions W x H x D mm 845x467x320 845x467x320 845x467x320 845x467x320

Weight kg 18 20 20 23

Condensing UnitDimensions W x H x D mm 795x545x320 904x620x333 850x605x345 1004x720x333

Weight kg 39 48 48 66

Sound Power @ 10m dBA 47 53 47 54

System Electrical Data (Cooling)Full Load Amps - 1 phase 5.8 8.2 8.4 12.3

- 3 phase - - - 5.7

Optional System Electrical Data (Heating)- 1 phase 13.8 13.8 13.8 13.8

- 3 phase - - - -

25

Model CR... PS037-1 NS037-1 PS075-1 NS075-1 PS110-1 NS110-1 PS150-1 PT150-1 NS150-1

HRP Code - Electric Defrost - 193432 - 193434 - 193436 - - 193439

HRP Code - Off-Cycle Defrost 193431 - 193433 - 193435 - 193437 193438 -Panel Size 12 12 12 12 12 12 12 18 12

Description - 1 phase 1/2HP HT 1/2HP LT 1HP HT 1HP HT 1.1/2HP HT 1.1/2HP HT 2HP HT - 2HP LT

- 3 phase - 2HP HT

Electric Supply 240/1/50 240/1/50 240/1/50 240/1/50 240/1/50 240/1/50 240/1/50 415/3/50 240/1/50

Compressor HP 1/2 1/2 1 1 1.1/2 1.1/2 2 2 2

Amps (A) 5 5 8 8 10 10 12 3.5 12

Defrost Rating (A) - 8 - 12 - 12 - - 12

Cooler Fan Rating A 1.6 1.6 1.6 1.6 3.2 3.2 3.2 3.2 3.2

The range is designed to control both temperature & defrost functions of coldrooms.

The range incorporates the Penn MR series of digital controller, together with compressor circuit breaker and compressor contactor. Also incorporated is a control circuit breaker.

The panel components are all pre-wired to an internal terminal block for ease of site wiring. The panel casing has numerous electrical ‘knock outs’ which can be used for top, bottom or side electrical entry for the main electrical supply and system control cables.

The range incorporates control panels for off-cycle and electric defrost systems from 1/2hp up to 10hp all wired for Direct-on-Line compressor starting.

Penn Cold Room ControllersTechnical Data

• Power ratings from : 0.37 to 1.5kw in single phase 1.5 to 7.5kw in three phase

• Standard DIN rail mounted components

• Most internal wiring is incorporated onto the Printed Circuit Board

• Specially designed Penn MR controller incorporating system Pump-down control

• Accurate and interchangeable and extendable IP68 sensor

• IP65 Poly-carbonate cabinet

• Electric defrost loadings from 2kW up to 3.5kW (dependant on model)

• Integrated circuit breakers for compressor and controller

• Controller keyboard locking facility

• 3 Panel Sizes: 12 : 275mm W x 220mm H x 140mm D 18 : 380mm W x 220mm H x 140mm D 24 : 275mm W x 370mm H x 140mm D

• Declaration of Conformity: EN 50081-1 EN 50082-1 EN 60439-1

Model CR... NT150-1 NDT150-1 NFDT150-1 PT250-1 NT250-1 NDT250-1 PT400-1 NT400-1 NDT400-1

HRP Code - Electric Defrost 193440 193441 193454(1) - 193443 193444 - 193446 193447

HRP Code - Off-Cycle Defrost - - - 193442 - - 193445 - -

Panel Size 18 24 24 18 18 24 18 18 24

Description - 1 phase - - - - -

- 3 phase 2HP LT 2HP LT 2HP LT 3HP HT 3HP LT 3HP LT 5HP HT 5HP LT 5HP LT

Electric Supply 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50

Compressor HP 2 2 2 3 3 3 5 5 5

Amps (A) 3.5 3.5 3.5 5.7 5.7 5.7 8.5 8.5 8.5

Defrost Rating (A) 12 5 5 - 12 9 - 15 10

Cooler Fan Rating A 3.2 3.2 3.2 3.2 3.2 3.2 4.8 4.8 4.8

Model CR... NFDT400-1 PT550-1 NT550-1 NDT550-1 NT750-1 PT750-1 NDT750-1 NFDT750-1

HRP Code - Electric Defrost 193455(1) - 193449 193450 193451 - 193453 193456(1)

HRP Code - Off-Cycle Defrost - 193448 - - - 193452 - -

Panel Size 24 18 18 24 18 18 24 24

Description - 1 phase - - - - -

- 3 phase 5HP LT 7.1/2HP HT 7.1/2HP LT 7.1/2HP LT 10HP LT 10HP HT 10HP LT 10HP LT

Electric Supply 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50

Compressor HP 5 7.1/2 7.1/2 7.1/2 10 10 10 10

Amps (A) 8.5 11.5 11.5 11.5 15.5 15.5 15.5 15.5

Defrost Rating (A) 10 - 15 12 15 - 16 16

Cooler Fan Rating A 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

(1) Includes mains switch (isolation for the whole cabinet)

26

1/2” & 3/8”

Pack HRP Code 148500

Tube & Insulation Code 140198 140155 188509

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1/2”x21 3/8”x21 -

Insulation i.d. x wall - - 1/2”x1/2

• All Copper Tube to EN 12735-1

• All Insulation is 1/2” (13mm) wall thickness Class ‘O’ specification

• All Copper Tube sizes up to 3/4”OD are 15m soft copper coils

• All Copper Tube sizes from 7/8”o.d. and above are 3m half hard straight lengths

• Copper Tube Bundles are only supplied as complete sets under the parent HRP Code

Copper Tube & Insulation- 15 metre Packs

5/8” & 1/4”

Pack HRP Code 148502

Tube & Insulation Code 140236 140074 188510

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 5/8”x20 1/4”x22 -

Insulation i.d. x wall - - 5/8”x1/2

5/8” & 3/8”

Pack HRP Code 148504

Tube & Insulation Code 140236 140155 188510

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube swg 5/8”x20 3/8”x21 -

Insulation - - 5/8”x1/2

3/4” & 3/8”

Pack HRP Code 148506

Tube & Insulation Code 140279 140155 188511

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 3/4”x19 3/8”x21 -

Insulation i.d. x wall - - 3/4”x1/2

7/8” & 3/8”

Pack HRP Code 148508

Tube & Insulation Code 144592 140155 188510

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 7/8”x18 3/8”x21 -

Insulation i.d. x wall - - 7/8”x1/2

7/8” & 1/2”

Pack HRP Code 148510

Tube & Insulation Code 144592 140198 188417

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 7/8”x18 3/8”x21 -

Insulation i.d. x wall - - 7/8”x1/2

1.1/8” & 3/8”

Pack HRP Code 148512

Tube & Insulation Code 144614 140155 188425

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1.1/8”x18 3/8”x21 -

Insulation i.d. x wall - - 1.1/8”x1/2

1.1/8” & 1/2”

Pack HRP Code 148514

Tube & Insulation Code 144614 140198 188425

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1.1/8”x18 1/2”x21 -

Insulation i.d. x wall - - 1.1/8”x1/2

1.1/8” & 5/8”

Pack HRP Code 148516

Tube & Insulation Code 144614 140236 188425

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1.1/8”x18 5/8”x20 -

Insulation i.d. x wall - - 1.1/8”x1/2

1.3/8” & 5/8”

Pack HRP Code 148518

Tube & Insulation Code 144630 140236 188433

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1.3/8”x18 5/8”x20 -

Insulation i.d. x wall - - 1.3/8”x1/2

1.3/8” & 3/4”

Pack HRP Code 148520

Tube & Insulation Code 144630 140279 188433

Coil & Insulation Length m 1x15 1x15 1x15

Copper Tube o.d. x swg 1.3/8”x18 3/4”x19 -

Insulation i.d. x wall - - 1.3/8”x1/2

27

Copper Tube Coils - Individual Lengths

Diameter o.d. 1/4” 3/8” 1/2” 5/8” 3/4” 7/8”

swg 22 21 21 20 19 19

HRP Code - 15 metre coils 140074 140155 140198 140236 140279 140481

HRP Code - 30 metre coils 140082 140163 140201 140244 140287 -

Copper Tube - Straight Lengths Half Hard

Diameter o.d. 7/8” 1.1/8” 1.3/8”

swg 18 18 18

HRP Code - 3 metre straight 144592 144614 144630

HRP Code - 6 metre straight 144606 144622 144649

Copper Fittings - L/R Elbows F/F*

Diameter o.d. 5/8” 3/4” 7/8” 1.1/8” 1.3/8”

HRP Code 131768 131776 131784 131792 131806

Other diameter sizes also available

*Suitable for applications not exceeding 45 bar at an operating temperature of 55ºC (ambient condition 32ºC)

Isoline Insulation

Diameter copper tube o.d. 1/2” 5/8” 3/4” 7/8” 1.1/8” 1.3/8”

Box Qty 81 68 49 49 39 29

HRP Code - 2 metre length x 1/2” wall 188387 188395 188409 188417 188425 188433

HRP Code - 15 metre length x 1/2” wall 188509 188510 188511 188512 - -

Other diameter sizes also available

Insulation Protective Paint*

Size litre 1 1

Colour black grey

HRP Code 188937 188939

*Protects against sunlight, UV and Ozone

Adhesive*

Size - Adhesive litre 0.25 0.5 - -

Length - Tape m - - 10 30

Colour - - black black

HRP Code - Non-flammable adhesive 188907 188909

HRP Code - Class 0 self adhesive tape 188867 184902

*Non-flammable adhesive & tape

Brazing Rods*Solder Rod S2

1kgSilverbaze 38T Silver Solder

Copper to Copper Copper to Steel

HRP Code 166626 170887

*HRP offers a comprehensive range of brazing rods and silver solder products ideal for making copper to copper, copper to brass or copper to steel joints.

28

Fitted Controls & AccessoriesHRP Workshop ServicesHRP has provided engineering support to contractors for many years, from a well-equipped workshop at Rougham, staffed by skilled and experienced engineers.

Dressed condensing units This is a continuous requirement for dressed condensing units, workshop fitted with controls and accessories to client specifications. Many installers have come to appreciate the benefits of this service.

• All added components are fitted and tested under clean and controlled conditions

• Material and labour costs are lower compared to fitting on site

• Skilled labour can be deployed elsewhere on the site

• Time on site is minimised

The workshop has experience of all types of condensing unit: hermetic and semi-hermetic, scroll and reciprocating. As well as those listed in this brochure, units from other manufacturers can be similarly equipped ready for delivery to site.

Bespoke modifications A wide range of modifications to refrigeration and air conditioning equipment is undertaken in the HRP workshops.

This service is particularly valuable when end-user specifications require change to a large number of units. Workshop modification ensures a consistency of workmanship and speed of turnaround which would be difficult to achieve on site.

Installation Accessories, Tools & EquipmentHRP has over 12,000 product lines, providing refrigeration contractors and engineers with everything needed for installation, service, maintenance and refrigerant recovery.

The product groups listed below represent those useful in connection with the installation of coolers and condensers and other refrigeration products. Copper Tube and Insulation can be found on P26 - 27.

Condensing Unit MountingsWall Brackets Unistrut Channel & Brackets Big Foot Mounting Systems Mounting Blocks for Flat Roofs Plarock Roof Slabs

Installation SupportsNylon Treaded Rod Cable Tray Cable Fixing Components Quick Positioning Clips Wall Anchor Clips

Condensate PumpsTank Pumps Peristaltic Pumps (non-tank) Semi-Submersible Pumps Split Pumps with Remote Sensor

Vandal Security CagesCages for Condensing Units Ivory Coated Paint Finish Removable Sections for Maintenance

29

DRESSED OPTIONS workshop fitted, include:

Standard Options:

• LP Switch (Auto)

• HP Switch (Manual)

• HP/LP Switch (Man/Auto)

• HP/LP Switch (Auto/Auto)

• Condenser Fan Speed Control for low ambient operation (pressure actuated)

• Condenser Fan Switch pressure actuated

• Drier & Sight Glass liquid line

• Vibration Eliminator - suction to compressor

• Oil Separator

• Oil Separator with hand shut-off & Sight Glass

• Crankcase Heater

Other Options:

• Starter Panel

• Hot-gas/liquid injection capacity control

• Unloaded start (semi-hermetic)

• Capacity Control cylinder unloading (semi-hermetic)

Unit Housing - weatherproof housings

A range of Steel Flat Packed Housings are available, plus a range of GRP White Plastic Housings for smaller hermetic units.

The housings are listed in the Technical Specification pages 21 & 22.

Line Components & FittingsDriers, Sight Glasses, Expansion Valves, Capillaries, & Controls Brass Fittings, Access Valves, Solenoid Valves, Pressure Regulators, Penn, Ranco, Teddington & Alco Controls

Condensate Drain Piping & TubePVC White Straight lengths Fittings & Reducers Wall Clips and Worm Drive Clips Reinforced PVC Hose Clear Vinyl Tube & Connectors

Tools & AccessoriesFlaring Tools & Tube Benders Multi-Meters & Digital Thermometers Brazing Equipment, Alloy Rods, and Torches Hand Tools, Spanners, Screwdrivers, Goggles, Gloves, Cleaning & Safety Equipment

Vacuum Pumps & GaugesManifolds and Gauges Refrigerant Charging Scales Refrigerant Recovery Equipment Refrigerant Waste Transfer Cylinders Anti-syphon & Anti-blowback Valves

30

Additional products available from HRPHRP has a comprehensive range of products from many well know brand manufacturers.

The products listed in the Selection Charts of this brochure represent the popular brands, which are competitively priced, and have a reputation for quality and reliability.

In addition to these selected products, HRP supplies an extensive range of quality equipment:

DanfossCondensing Units - OPTYMA Scroll

Condensing Units - OPTYMA Recip.

Compressors

Expansion Valves

Refrigerant Controls

Friga-BohnPanel Coolers

Unit Coolers

Dual Discharge Coolers

Air Cooled Condensers

AsperaCondensing Units

Compressors

L’Unite HermetiqueCondensing Units - Silensys

Compressors - Refr. & Aircon

Spare Parts

CopelandSemi-Hermetic Condensing Units

Compressors - Scroll

Compressors - Semi-Hermetic

Compressors - Reed

Scroll Compressor Receiver Units

ProfroidCondensing Units - Quietis

Condensing Units - Quietor

Refrigeration Packs (supermarkets appl.)

RivacoldMonoblock Units for Cold Rooms < 11.6kW

Panel Coolers

Cubic Coolers

Dual Discharge Coolers

KobolDual Discharge Coolers

Cubic Coolers

Air-Cooled Condensers

Danfoss Switchgear & ContactorsMini Contactors

Auxiallry Contact Blocks

Thermal Overload Relays

Contactors - Mains 1ph & 3ph

Condensing Unit HousingsSteel Flat Packed - Copeland

Steel Flat Packed Housings

GRP Virgo Unit Housings

Compatible Housings - see page 18 & 19

31

Text...

Technical Centre

The route to excellenceImproving workforce skills is a always a worthwhile investment, particularly in building services, where new technologies, new regulation and increasing competition all make an impact on your business.

HRP Group has established its new Technical Centre to help you meet the challenges of the future. The Centre is staffed by experts in refrigeration and air conditioning, with the training skills, equipment and resources to equip your workforce for tomorrow’s business.

Who we are HRP is a leading national distributor and wholesaler of air conditioning and refrigeration equipment, with deep roots and a proud history in the industry.

The HRP Group Technical Centre has been founded in conjunction with leading air conditioning manufacturer Mitsubishi Heavy Industries. Together, we are committed to improving knowledge and skills to help build better businesses.

Comprehensive trainingA wide range of courses responds to the environmental and safety requirements placed on our industry. As well as basic introductions for beginners in refrigeration or air conditioning, there are essential courses on the legal and safety aspects of handling refrigerants.

The Centre is the only training facility in the country to cover the complete Mitsubishi Heavy Industries’ product range. Courses cover basic introductions, product application, design, installation, commissioning, servicing and trouble shooting of split, multi-split and VRF inverter based systems.

Courses are designed to suit design engineers, installers and service personnel. Bespoke courses to suit your needs can be arranged as required.

Purpose-built facilitiesThe HRP Group Technical Centre has been purpose built to provide theoretical and practical tuition with a range of training rooms and hands-on facilities. All course materials are supplied, with lunch and refreshments available.

For more details of courses and dates, call 01753 495700 or visit www.hrponline.co.uk

32

MHI Training Courses

MHI Module 1 – Introduction to MHI EquipmentDuration: 1 day Cost: Free Class Size: 15 maxBasic technical introduction to:• RAC Split System Heat Pumps (RAC mini splits)• PAC Split System Heat Pumps (Commercial Specification) including

Multi-Split systems• VRF Inverter Heat Pump Systems and how they are applied to building

design solutions• This course is suitable for those with minimal experience of air

conditioning or refrigeration

MHI Module 2 – RAC (Splits) PAC (Multi-Splits)Duration: 1 day Cost: Free Class Size: 12 maxApplication, Installation & Service for:• RAC Split System Heat Pumps (RAC mini splits)• PAC Split System Heat Pumps (Commercial Specification) including

Multi-Split systems• Correct installation practice, pipework, refrigerant charging,

condensate piping• Interrogation of diagnostic functions, troubleshooting, and rectification

Suitable for engineers with knowledge and experience in the principles of refrigeration, and the installation of split system heat pump systems.

MHI Module 3 – KX VRF Application & SelectionDuration: 1 day Cost: Free Class Size: 10 max• Application & Design of KX VRF Systems• Selection of indoor units, sensible and latent requirements• Allowances for pipework losses and adjustment for design conditions• Selection of outdoor units, allowance and significance of connectivity ratio• Application and operation of 2-pipe systems & 3-pipe heat recovery systems• VRF system design and layout using ’e-solution’ programme• Selection and grouping of controllers and central control systems

Suitable for contracts engineers and design engineers, with previous experience of VRF, who are involved in surveying buildings, producing design layouts, and project solutions for VRF applications in commercial buildings, through to quote preparation, pipework schematics and presentation to clients.

Delegates will receive a free copy of the advanced ’e-solution’ programme.

MHI Module 4 – KX VRF Installation, Operation & ServiceDuration: 1 day Cost: Free Class Size: 12 maxInstallation, Commissioning & Service of KX Systems:• Optimum location of indoor units and outdoor units• Selection of correct refrigeration pipework for R410A systems• Connection of refrigeration pipework, brazed joints, nitrogen purge,

pipework cleanliness• Design and installation of condensate drain piping and headers• Connection of mains power, isolators, controls (incl. BMS Interface)

and control wiring• Installation and connection of Distribution Controllers (PFD) for

3-pipe systems• Pressure testing, leak detection, system charging calculation and process

Suitable for engineers with previous experience of VRF installation, who require to advance their knowledge and skills, covering theoretical and practical hands-on training.

Modules 5 & 6 superseded by subsequent Modules

MHI Module 7 – SLA & SLB Control Systems & OperationDuration: 1/2 day Cost: Free Class Size: 10 maxExtension to Module 4 covering in-depth view of controls and operation of KX VRF Systems:• Controller types and their appropriate application• Address settings for single and multiple indoor unit connection

• SLA & SLB Touch-screen Controllers – monitoring and data output• Explanation of ‘fuzzy-logic’ control operation for maximum efficiency• System interrogation through controller display – check and

service functions• Analysis of system operational data

Delegates must have a working knowledge of VRF systems and must have attended Module 4 prior to attending this module.

MHI Module 8 – R410A Split System Installation Utilising Existing HCFC PipeworkDuration: 1/2 day Cost: Free Class Size: 15 maxThe Course informs on the conditions surrounding the installation of certain MHI split systems utilising existing interconnecting pipe-work:• Fundamental requirements and suitability of exiting system prior

to ‘change-out’• Analysis of existing pipework for condition, cleanliness, and pressure

limitation requirements• Recovery of HCFC refrigerant • Registration for Waste Transfer (DEFRA requirement) HRP reprocessing

services, and statutory requirements• Pipework processing, connection, pressure testing, leak testing

Suitable for engineers involved in system removal and upgrade to R410A. All delegates must have attended module 2 prior to attending this module.

MHI Module 9 – 1/2 Mente PC PAC & VRF Interrogation & AnalysisDuration: 1/2 day Cost: Free Class Size: 6The Mente-PC Programme is used by MHI engineers to perform detailed operational data interrogation and recording for PAC split systems and KX VRF Systems. This is an advanced and sophisticated programme capable of providing extensive information on all sections of the system and its various control components. The course is an in-depth view of the Mente-PC and covers the following:• Connecting and setting up the Mente-PC programme using

a compatible laptop PC• Methodology of access to the service, maintenance and operation• Selection of data modules relevant to the required interrogation field• Use of Mente-PC for control checking, wiring and commissioning• Fault diagnosis detailed information• System optimisation for efficient operation

Delegates must have attended Module 4 prior to enrolling for this module.

MHI Module 10 – KX & KXR Commissioning – Advanced LevelDuration: 1/2 day Cost: Free Class Size: 8This is an extension to Module 4 covering the complete commissioning procedures and operational analysis of KX & KXR 2-pipe & 3-pipe VRF Systems:• System control wiring and pipework requirements• Refrigerant charge calculation, checking and charging by weight• Commissioning of single and multiple VRF Systems• Detailed analysis of operational information available through

control connections

Delegates must have attended Module 4 prior to enrolling for this module.

The MHI Modules provide valuable training for people with different levels of knowledge and experience in the air conditioning industry. The courses are interactive, with the maximum possible participation and hands-on involvement of all delegates. The content of the various courses ranges from basic to very advanced.

Please note that the Modules above do not cover heat load calculations.

All courses commence at 09:30hrs. Full day courses are scheduled to finish around 16:00hrs.

33

Refrigeration Training Courses

Refrigeration Training Courses

Refrigerant Safe Handling C&G 2078 Although the City & Guilds 2078 qualification will be superseded in July 2011 by the City & Guilds 2079 qualification, the C&G 2078 is still the minimum requirement for Refrigerant Safe Handling. If Current certificates have lapsed the C&G 2078 can in the interim period be a temporary stepping stone to gain the C&G 2079.

Dependant on the candidates’ Skill Sets, two and five day courses are available, culminating in a Theory and Practical Assessment to C&G 2078.

F-Gas City & Guilds 2079The courses detailed below can be in continuation of the C&G 2078 stepping stone as detailed above, or as direct entry. We recommend the employment of the HRP Skill Scan to determine and tailor training to suit the individual’s needs.

For direct entry, it is recommended that attendees are competent, practicing Refrigeration / Air conditioning engineers.

With Pipework & Brazing being an integral part of the new F-Gas Assessment for both Cat 1 & 2. Candidates who have little or no experience of Oxy-Acetylene brazing would benefit by attending a relevant Pipework & Brazing course or Refresher prior to being assessed.

Details of Welding & Brazing Courses are available via The HRP Group Technical Centre.

WE RECOMMEND ALL CANDIDATES HAVE A ‘SKILL SCAN’ PRIOR TO CONFIRMING THE COURSE BOOKING.

1 Day RefresherThe object of the course is to allow the candidates to assess their present capabilities with regard to the requirements of the F-Gas qualification for both the theory and practical Element. The HRP Individuals ‘Skill Scan’ can help the candidate in deciding what training will be required to achieve the F-GAS 2079.

Note this course does not include any assessment to achieve the standards. Any further training and/or the Theory and Practical assessments would be booked on completion of the course.

2/3 Day CourseThis Course concentrates primarily on the Theory aspects of Refrigeration and assumes that an explanation and demonstration of the practical assessment is sufficient. Theory and Practical assessments would be booked during or on Completion of the course dependant on Location Circumstance and confidence of the Candidate.

Note: Day 3 is for assessments.

4/5 Day CourseThis Course concentrates on both the Theory and Practical aspects of Refrigeration in relation to the F-Gas assessment. Theory and Practical assessments would be booked during or on Completion of the course dependant on Location Circumstance and confidence of the Candidate.

Note: Day 5 is for assessments.

SummaryOn successful completion of the above courses and based on individual requirements the candidate will have acquired sufficient skills and knowledge to:

• Analyse system performance to determine efficiency• Demonstrate the ability to carry out an adequate leak test, using both

direct and indirect methods• Brazing and Jointing skills• Ability to identify refrigerant(s)• Charge and recover a zeotropic refrigerant• Pressure test and evacuate to BS-EN 378• Complete the required records to comply with F-Gas regulations• Dispose of all hazardous waste created in the correct legal manner

The assessment process for the above will include the two methods below:

• An online examination of 40 questions• A practical assessment of the candidates’ abilities to complete the

above tasks

It is intended that the above can be carried out at the majority of HRP outlets.

10 Day CourseAimed primarily at building service engineers, it would also suit engineers with a limited knowledge of the industry. This Course concentrates on both the Theory and Practical aspects of Refrigeration in relation to the F-Gas assessment. Each candidate’s progress is assessed daily to ensure that they achieve the outcomes as detailed above.

The City and Guilds 2078 can be used as a stepping stone as detailed above.

Theory and Practical assessments would be undertaken at appropriate times during the course dependant on progression and confidence of the Candidate. The course may be consecutive or non-consecutive weeks.

Additional Courses

Introduction to RefrigerationThis is a one day course covering the principles of the Vapour Compression Refrigeration Cycle, identifying the function of the essential components that form an operating refrigeration system.

This course is suitable for Building Service Engineers, Consultants, Facilities Management Personnel and Project Managers from the Construction and Services Industries to bring an understanding of the tasks and procedures required of good refrigeration practice in installation, service & maintenance.

Understanding Air ConditioningThis one day course explains the history and purpose of comfort cooling/air conditioning, dealing with the importance of Humidity and its controls. The course also deals with good Refrigeration practices as required for correct Installation, service and maintenance of optimum conditions.

The course is an Introduction to Air Conditioning and is suitable for Consultants, Facilities Management Personnel and Project Managers from the Construction and Services Industries.

Seminar - Current Industry LegislationF-Gas O.D.S and Hazardous WasteThis one day Seminar covers the History Facts and Conjecture surrounding Ozone Depletion, the current implementation of the F-Gas Regulations and the responsibilities of all of us in regards to the Environment and Hazardous Waste.

The Course is suitable for all including but not limited to, Contractors, Suppliers and End Users of Refrigeration and Air Conditioning Equipment.

National CoverageThe courses developed at the HRP Group Technical Centre are designed to be held in the training facilities located at most of the nationwide HRP Service Centres. Details available on request.

For more details of course booking, timings and dates, please call 01753 495700, or visit www.hrponline.co.uk

34

Refrigerants

In recent years, there have been many changes to the legislation governing the availability of refrigerants and more major changes will be implemented in the near future. The most significant is the banning of R22 (Virgin HCFC) from 1st January 2010.

New RefrigerantsHRP leads the way in the supply of refrigerants to the UK industry, in partnership with BOC Refrigerants. HRP provides a complete range of refrigerants in a variety of containers, from 1kg cans and dumpy cylinders, to 1000kg drums. Hydrocarbon, CO2 and Ammonia refrigerants are also available to special order.

HRP Service Centres are located throughout the UK and hold comprehensive stocks of refrigerant cylinders, plus engineers’ service tools and scales.

Refrigerant Waste Recovery Building owners, operators, landlords, auditors, leaseholders and tenants are now required by law to ensure any refrigeration plant or air conditioning systems, which contain refrigerant gas, must be properly de-gassed when the equipment is removed or scrapped.

Contractors and maintenance companies are now expected to provide an audit trail for the removal and reprocessing/destruction of these refrigerants in air conditioning split systems, heat pumps, vrf systems, roof-top units, chillers, etc. HRP has made this easy for all concerned.

Simplifying ProceduresHRP has provided a service for refrigerant ‘waste’ for the last 10 years, handling unwanted refrigerant and transferring it to its partner, BOC, for processing. HRP recognises refrigeration and air conditioning engineers do not like regulations, detest form filling, and have some fear, and possibly ignorance, of the legislation which now covers this subject. No one wants a visit from the ‘environment police’, or a hefty fine from the Environment Agency. No company director wants to be exposed for noncompliance.

To make things easy, HRP has produced a Consignment Form, in association with the Environment Agency, with much of the required information and coding already preprinted, allowing the contractor to follow several easy steps to comply with the Regulations.

HRP – Waste Refrigerant Processing HRP provides the following services from its 16 locations throughout the UK:

• Refrigerant Recovery Cylinders• Delivery and Collection service for registered companies• Consignment Forms for small and large cylinders, part completed, and simple to use• Forms include Waste Codes and UN Identification, plus Exemption References• Full responsibilities of the ‘Transfer Station’• Receiving cylinders containing waste refrigerant• Documentation for onward transfer and transport• Arrangements with BOC for analysis of waste refrigerants• Certificates for confirmation of re-processing or destruction

Engineers and Contractors ResponsibilitiesThe ‘waste producer’, i.e. the aircon or refrigeration contractor, must have the Minimum Qualification for engineers to remove refrigerant - City & Guilds 2078, or CITB equivalent. Training for these qualifications, and for F-Gas Inspection Training, are available at the new HRP Technical Centre and Training Facility, sponsored by Mitsubishi Heavy Industries Air Conditioning, which is located in Slough. HRP also supplies, recovery equipment, gauge sets, protective gloves & goggles, and many other tools and timesaving devices.

HRP – Peace of MindRegulations, forms, certificates, and inspectors, can be irritating and time consuming to deal with. HRP provides a comprehensive service to the industry, and has greatly simplified the documentation requirement for waste producers.

35

When designing a refrigeration system it is important to select refrigeration equipment that will maintain the correct storage conditions for the product to be stored. The list below includes many of the products that require controlled conditions to keep them fresh and the ideal storage temperature range is shown for each product. The relative humidity under which unwrapped products are stored can affect the length of storage time and the weight loss that is experienced during storage, therefore each application should be checked to assess the correct cold room temperature and relative humidity conditions if unwrapped product is being stored, before the installation is undertaken. Further advise on product storage conditions is available from HRP on request. The chart below is colour coded to guide you to the correct refrigeration equipment selection chart.

Product Storage Conditions

Product Ideal Storage Conditions

Air Temperature

Select Equipment

From...

Bakery Products

Active Yeast 0ºC to +2ºC

Bakery products with cream/custard +2ºC to +5ºC

Cooked Pastries +2ºC to +7ºC

Cooked Pies (Meat/Fish filled) +2ºC to +5ºC

Doughnuts & Cakes -25ºC to -20ºC

Dried Yeast +2ºC to +7ºC

Frozen Bread -25ºC to -20ºC

Unbaked Dough +2ºC to +5ºC

Uncooked Pastry +3ºC to +6ºC

Dairy

Butter +2ºC to +7ºC

Cream +2ºC to +5ºC

Dairy Based Desserts +3ºC to +6ºC

Fresh Eggs +1ºC to +2ºC

Frozen Butters & Fats -23ºC to -18ºC

Hard Cheeses +2ºC to +5ºC

Ice Cream -23ºC to -18ºC

Margarine/Fats +2ºC to +7ºC

Mayonnaise +2ºC to +3ºC

Milk +2ºC to +5ºC

Soft Cheese +2ºC to +5ºC

Yoghurt +2ºC to +5ºC

Fruit & Veg & Salads

Apples +3ºC to +5ºC

Apricots +3ºC to +5ºC

Asparagus +3ºC to +5ºC

Artichokes +3ºC to +5ºC

Aubergines +4ºC to +10ºC

Avocado +3ºC to +5ºC

Beetroot +3ºC to +5ºC

Brussel Sprouts +3ºC to +5ºC

Cabbage +3ºC to +5ºC

Carrots +3ºC to +5ºC

Cauliflower +3ºC to +5ºC

Celery +6ºC to +9ºC

Cherries +4ºC to +8ºC

Chicory +3ºC to +5ºC

Clementines +2ºC to +7ºC

Corn-on-the-Cob +2ºC to +3ºC

Courgettes +4ºC to +10ºC

Cucumbers +6ºC to +9ºC

Product Ideal Storage Conditions

Air Temperature

Select Equipment

From...

Frozen Fruits -23ºC to -18ºC

Grapes +3ºC to +5ºC

Grapefruit +9ºC to +12ºC

Green Beans +4ºC to +10ºC

Ginger +9ºC to +12ºC

Kiwi Fruit +1ºC to +2ºC

Leeks +3ºC to +5ºC

Lemons +10ºC to +12ºC

Lettuce (All Types) +3ºC to +5ºC

Mandarins +2ºC to +7ºC

Mangoes +9ºC to +12ºC

Marrow +4ºC to +10ºC

Melons +4ºC to +8ºC

Mushrooms 0ºC to +2ºC

Nectarines +3ºC to +5ºC

Nuts (All Types) 0ºC to +2ºC

Onions +3ºC to +5ºC

Oranges +2ºC to +7ºC

Parsnips +3ºC to +5ºC

Peaches +3ºC to +5ºC

Pears +3ºC to +5ºC

Peas in the Pod +3ºC to +5ºC

Peppers +4ºC to +10ºC

Pineapples +6ºC to +9ºC

Plums +3ºC to +5ºC

Potatoes (Eating) +6ºC to +9ºC

Potatoes (Seed) +4ºC to +10ºC

Pumpkin +9ºC to +12ºC

Raspberries +3ºC to +5ºC

Rhubarb +3ºC to +5ºC

Satsumas +2ºC to +7ºC

Strawberries +3ºC to +5ºC

Tangerines +2ºC to +7ºC

Tomatoes (Firm Ripe) +6ºC to +9ºC

Tomatoes (Green) +10ºC to +12ºC

Rice Salad +2ºC to +5ºC

Vegetable Salad +3ºC to +6ºC

Meat

Chilled Beef 0ºC to +2ºC

Cold Meat/Poultry (Pre-Packed) +3ºC to +5ºC

Cooked Meats +2ºC to +5ºC

Cooked/Uncooked Cured Sausage/Meats +2ºC to +7ºC

Product Ideal Storage Conditions

Air Temperature

Select Equipment

From...

Fresh Chicken 0ºC to +2ºC

Fresh Game 0ºC to +2ºC

Fresh Ham +3ºC to +5ºC

Fresh Offal (All Types) 0ºC to +2ºC

Fresh Pork 0ºC to +2ºC

Fresh Processed Meat (Sausage/Minced Meat) +3ºC to +5ºC

Frozen Beef -23ºC to -18ºC

Frozen Chicken -23ºC to -18ºC

Frozen Game -23ºC to -18ºC

Frozen Ham -23ºC to -18ºC

Frozen Lamb -23ºC to -18ºC

Frozen Pork -23ºC to -18ºC

Frozen Offal -23ºC to -18ºC

Meat Paste +2ºC to +5ºC

Other Frozen Poultry -23ºC to -18ºC

Salt Pork +6ºC to +9ºC

Smoked/Cured Meats +2ºC to +5ºC

Fish

Fish Paste +2ºC to +5ºC

Fresh Fish (Packed in Ice) 0ºC to +2ºC

Frozen Fish -25ºC to -20ºC

Smoked Fish +3ºC to +5ºC

Drinks

Frozen Concentrated Fruit Juice -23ºC to -18ºC

Squash +4ºC to +8ºC

Beer +8ºC to +12ºC

Other Products/Misc

Chocolate +4ºC to +10ºC

Confectionary +4ºC to +10ºC

Flowers (Cut) +2ºC to +7ºC

Frozen Chips -25ºC to -20ºC

Hops +4ºC to +10ºC

Plant Bulbs +4ºC to +10ºC

Plants (Growing) 0ºC to +2ºC

Sauces +3ºC to +5ºC

-18ºC0ºC to

+2ºC

+2ºC to

+4ºC+10ºC

Colour Code:

Better by degrees

Head Office

Rougham Industrial Estate Rougham, Bury St Edmunds

Suffolk IP30 9XATel: 01359 270888 Fax: 01359 271132

[email protected] www.hrponline.co.uk

3D Air Sales Ltd

159 Edinburgh Avenue Slough Trading Estate

Slough SL1 4UE Tel: 01753 495720 Fax: 01753 495721

[email protected] www.3dair.co.uk

HRP Group Technical Centre

159 Edinburgh Avenue Slough Trading Estate

Slough SL1 4UETel: 01753 495700 Fax: 01753 495701

[email protected] www.hrponline.co.uk/tc/

BedfordUnit B6

Manton Centre Manton Lane Bedfordshire

MK41 7PX

Tel: 01234 272702

[email protected]

FarehamUnit 2

Stephenson Road Segensworth, Fareham

Hampshire PO15 5RU

Tel: 01329 443515

[email protected]

NewcastleUnit K4, Hamar Close

Tyne Tunnel Trading Estate North Shields Tyne & Wear

NE29 7XB

Tel: 0191 258 3492

[email protected]

SouthamptonUnit 2, South Hampshire

Industrial Park Salisbury Road

Totton, Southampton Hampshire SO40 3SA

Tel: 02380 869966

[email protected]

BirminghamUnit 16 & 17, Fulford Drive Minworth Industrial Park

Minworth, Sutton Coldfield West Midlands B76 1DR

Tel: 0121 313 6720

[email protected]

Glasgow140 St. Andrew’s Road

Pollokshields Glasgow G41 1PP

Tel: 0141 420 1606

[email protected]

Norwich4/6 Murrayfield Road

Fifers Lane Norwich

Norfolk NR6 6NQ

Tel: 01603 409616

[email protected]

SwanleyTeardrop Centre

London Road Swanley

Kent BR8 8TJ

Tel: 01322 614811

[email protected]

BristolUnit 100

The Quadrant Ash Ridge Road Bradley Stoke

Bristol BS32 4QA

Tel: 01454 456430

[email protected]

LeedsUnit 1, Aintree Court

Hunslet Business Park National Road Leeds

West Yorkshire LS10 1TF

Tel: 0113 277 5000

[email protected]

SheffieldUnit 2, Brightside

443 Brightside Lane Sheffield

South Yorkshire S9 2RS

Tel: 0114 244 8222

[email protected]

WalthamstowUnit 12

Waltham Park Way Billett Road

Walthamstow London E17 5DU

Tel: 0208 531 9321

[email protected]

Bury St. EdmundsRougham Industrial Estate

Rougham Bury St Edmunds Suffolk IP30 9XA

Tel: 01359 270888

[email protected]

MertonUnit 2