Relay Coordination (1)

Embed Size (px)

Citation preview

  • 8/11/2019 Relay Coordination (1)

    1/41

    PRESENTATION ON

    RELAY CO-ORDINATION

    BY

    Manoj Pandey

  • 8/11/2019 Relay Coordination (1)

    2/41

    OBJECTIVE

    TO GIVE AN OVERVIEW OF SETTING ANDCO-ORDINATION OF PROTECTIVE

    RELAYS IN AN INDUSTRIAL POWERSYSTEM.

  • 8/11/2019 Relay Coordination (1)

    3/41

    RELAY CO-ORDINATION

    What is relay co-ordination ? Why it isrequired ?

    Properties of Protection Scheme. Basic terms related to relay co-ordination. Steps in Relay Co-ordination. Typical relay setting & co-ordination

    Example

  • 8/11/2019 Relay Coordination (1)

    4/41

    WHAT IS RELAY CO-ORDINATION

    PROTECTION CO-ORDINATIONREFERS TO CO-ORDINATION OFPROTECTIVEEQUIPMENT SUCHTHAT DEVICECLOSEST TO FAULTIS OPERATED FIRST.

  • 8/11/2019 Relay Coordination (1)

    5/41

    WHY RELAY CO-ORDINATION ISREQUIRED?

    IT IS REQUIRD TO ISOLATE ONLY THE FAULTYLINE WITHOUT AFFECTING OTHER LOAD

    CONNECTED TO BUS. FOR MINIMIZING THE DAMAGE.

  • 8/11/2019 Relay Coordination (1)

    6/41

    PROPERTIES OF PROTECTION SCHEME

    IT SHOULD SATISFY 3 S:

    (1) SENSITYVITY : It refers to minimum operation current.(2) SELECTIVITY : It refers to discrimination.(3) SPEED : It refers to time of operation of the relay.

  • 8/11/2019 Relay Coordination (1)

    7/41

  • 8/11/2019 Relay Coordination (1)

    8/41

  • 8/11/2019 Relay Coordination (1)

    9/41

    Co-ordination in small power distribution Between SFU & MCCB

    0

    0

    10

    1,000

    100,000

    1 10 100 1000 1000

    0

    CURRENT IN AMPS

    T I M E I N S E C

    SFU125MCCB125

  • 8/11/2019 Relay Coordination (1)

    10/41

  • 8/11/2019 Relay Coordination (1)

    11/41

    Co-ordination in small power distribution Between SFU & MCCB

    0.001

    0.1

    10

    1000

    100000

    1 10 100 1000 10000

    CURRENTIN AMPS

    T I M E I N

    S E C O N D

    SFU400

    MCCB400

  • 8/11/2019 Relay Coordination (1)

    12/41

    Co-ordination in small power distribution Between MCB & MCCB

    0.001

    0.1

    10

    1000

    100000

    1 10 100 1000 10000

    CURRENT IN AMPS

    T I M E

    I N S E C

    MCCB125

    MCB63

  • 8/11/2019 Relay Coordination (1)

    13/41

    Co-ordination in small power distribution Between SFU & MCCB

    0.01

    0.1

    1

    10

    100

    1000

    10000

    1 10 100 1000 10000

    MCCB630

    SFU400

  • 8/11/2019 Relay Coordination (1)

    14/41

    Terms related to Protection co-ordination

    Primary & back-up protection. Zones of protection. Selectivity. Pick-up. Plug Setting Multiplier (PSM). Time Setting multiplier (TSM). Primary Operating Current (POC).

    Relay Operation Time. Co-ordination Margin.

  • 8/11/2019 Relay Coordination (1)

    15/41

    Relay co-ordination Basic termsPrimary & Backup protection

    For fault at F1:R1 is PrimaryR2 is First Backup.

    R3 is Second Backup. For fault at F2:R4 is PrimaryR5 is First Backup.

  • 8/11/2019 Relay Coordination (1)

    16/41

    Relay co-ordination Basic terms Zones of protection

    Protection is arranged in zones,which would cover the powersystem completely leaving nopart unprotected. Zones ofprotection should overlap acrossthe circuit breaker being includedin both zones (Fig. A). Case A isnot always achieved,accommodation of CT being in

    some cases only on one side (Fig.B). For fault at F busbarprotection would operate and tripC but may continues to be fedthrough the feeder.

    Power system protection isusually engineered throughoverlapping zones. Theadvantage is positive discussionof faulty area / element. Thedisadvantage some times can bethat more breakers will be trippedthan the minimum necessary todisconnect the faulty element.

  • 8/11/2019 Relay Coordination (1)

    17/41

    Relay co-ordination Basic termsSelectivity

    Discrimination by time Discrimination by current Discrimination by time & current-Both.

  • 8/11/2019 Relay Coordination (1)

    18/41

    Relay co-ordination Basic termsPick-up

    Minimum value of input for which relay starttaking action:

    For ABB make SPAJ 140C ___(0.5 2.5)In Steps of 0.1

    It is related to sensitivity of the relay & donethrough plug setting on the relay.

  • 8/11/2019 Relay Coordination (1)

    19/41

    Relay co-ordination Basic terms Plug Setting Multiplier (PSM)

    Relay characteristics is not drawn on actual current basis. Relaycharacteristic curve is a curve of PSM Vs operation time.

  • 8/11/2019 Relay Coordination (1)

    20/41

    Relay co-ordination Basic terms Time Setting Multiplier (TSM)

    We Don t set desired relay operation time directly in seconds, butwe set them as Time Setting multiplier (TSM).

    TSM = Desired Operation timeOperation time at TSM=1

    Normal Range (0.05 1) in step of 0.01

  • 8/11/2019 Relay Coordination (1)

    21/41

    Relay co-ordination Basic termsRelay Operation time

    Relay Operation time depends ontype of curve selected.

    (50) DMT :- It has fixed current &Time settings.

    Range (0.5 40) In; step 0.1 In.Time delay (0.04 300 sec);

    step = 0.01 Sec.

    (51) IDMT :- Relay Equation:Operation time = TMS x

    (PSM) 1 As per IEC 60255

    Application

    NormalInv(NI)

    0.14 0.02 MCC/PCCINCOMER

    Very Inv(VI)

    13.5 1.0 PrimaryOf TR

    Extremeinv. (EI)

    80 2 Breaker /Fuse Co-ordination (Spl.In case of EF)

    Longtime Inv(LTI)

    120 1 NGR

  • 8/11/2019 Relay Coordination (1)

    22/41

    Relay co-ordination Basic termsCo-ordination Margin

    EMPIRICAL FORMULAS FOR CO-ORDINATION Fuse & Breaker

    td = 0.4t + 0.15, wheretd = discrimination time

    t = Fuse operation time0.15 = Relay operation time + safety margin0.4t = Relay ratio error

    Breaker & Breakertd = 0.25t + 0.25

    t = downstream relay operation time0.25 Down stream breaker tripping time + relay overshoot +

    Safety Margin.

  • 8/11/2019 Relay Coordination (1)

    23/41

    STEPS IN RELAY SETTING & CO-ORDINATION Assumptions:-(1) Complete single line diagram is available(2) Short circuit calculation at each relay point is done.

    THING TO REMEMBERRelay co-ordination for phase fault and earth fault is done separately.

    ROAD MAP FOR CO-ORDINATIONSTART FROM THE BOTTOM MOST RELAY AND GO UPWARD.USE EMPIRICAL FORMULA.

  • 8/11/2019 Relay Coordination (1)

    24/41

  • 8/11/2019 Relay Coordination (1)

    25/41

  • 8/11/2019 Relay Coordination (1)

    26/41

  • 8/11/2019 Relay Coordination (1)

    27/41

  • 8/11/2019 Relay Coordination (1)

    28/41

    OVER CURRENT RELAY SETTING: RELAY R1(51)Plug setting multiplier (PSM)

    Transformer Running load current I RL = 80% of transformer rating

    =0.8 X 2749.3 = 2199 Amp. Highest Rated Motor = 132 kW Running Load of 132 kW motor I FL = 235 Amp. Starting current of 132 kW motor I ST = 7.83 X I FL = 1840 Amp

    Considering Direct on line starting MethodPS = I RL - I FL + I ST = 2199 235 + 1840 = 1.27

    CTR 3000Set PS = 1.3

    Actual Primary Operating Current = PS x CTR = 1.3 x 3000 =3900 A

    Plug Setting Multiplier = I fault = 33805 = 8.66POC 3900

  • 8/11/2019 Relay Coordination (1)

    29/41

    OVER CURRENT RELAY SETTING: RELAY R1(51)Time setting multiplier (TSM)

    Choose NI Characteristic :Operating Time at PSM = 8.66 @ 1.0 TMS

    = (0.14) / ((8.66) 0.02 -1) = 3.17 secDesired Operating Time = 0.4 Sec (Assumed)Desired Time Dial (TMS) = 0.4 / 3.17 = 0.126

    Set TMS = 0.13Hence Actual operating Time = 0.13 x 3.17 = 0.41 sec.

    RECOMMENDED SETTINGS :

    PS = 1.3TMS = 0.13

  • 8/11/2019 Relay Coordination (1)

    30/41

    OVER CURRENT RELAY SETTING: RELAY R2(51)Plug Setting Multiplier (PSM)

    POC of downstream relay R1 = 3900 A @ 0.42 kV= 248.2 A @ 6.6 kV

    Hence Plug Setting (PS) = POC / CT PRIMARY= 248.2 / 200 = 1.24

    Set PS = 1.3 Actual Primary Operating Current = 1.3 x 200 = 260 A Fault Current = 33805 A @ 0.42 kV

    Reflected Fault Current = 2151.2 A @ 6.6 kV Plug Setting Multiplier (PSM) = 2151.2 / 260 = 8.27

  • 8/11/2019 Relay Coordination (1)

    31/41

  • 8/11/2019 Relay Coordination (1)

    32/41

    PROTECTION CO-ORDINATION EARTH FAULT RELAY

    Criteria for selecting ground fault pick up setting:Selection of plug settings for ground fault relays are not influenced

    by equipment rated current / motor starting current. For Solidly Grounded System :

    Higher pickup shall be selected to avoid excessive currentthrough the relay.

    By adopting higher plug setting, Sensitivity is not sacrificed asfault current is in kAmps. For High resistance Grounded System :

    Pick up shall be low enough to obtain desired sensitivity. This istrue as fault current is low. This current further reduces for arcing

    faults. To increase sensitivity, sometimes 5A CT connected to 1A relay.

  • 8/11/2019 Relay Coordination (1)

    33/41

    PROTECTION CO-ORDINATION EARTH FAULT RELAY

    Ground relay senses only zero sequence currents. Flow of zero sequence currents is very much influenced by

    Transformer vector group connections. Example : Fault on star side of delta Star Grounded.Transformer results in flow of zero sequence current on star

    side. Hence providing the backup Ground over current relay (say

    51N) on delta side of star delta transformer is meaningless. Detection of faults on the Under-grounded systems can only be

    done using voltage relays.

  • 8/11/2019 Relay Coordination (1)

    34/41

    EARTH FAULT RELAY SETTING: RELAY R1(51N)

    Set PS = 0.4 A Primary Operating Current = 0.4 x 3000 = 1200 A PSM = 33.8 / 1.2 = 28

    Choose Extremely inverse curve (EI) Operating time at PSM = 28, TSM = 1 Operating time = 80 = 0.20 Sec.

    20 2 1 Desired operating time = co-ordination margin + relay operation time. Co-ordination margin = (0.4t + 0.15) = 0.154 Desired time = down stream time + margin = 0.01 + 0.154 = 0.164 Time setting multiplier = Desired operation time = 164 = 0.85

    operation time at TSM=1 0.2

  • 8/11/2019 Relay Coordination (1)

    35/41

    EARTH FAULT RELAY SETTING: RELAY R2(50N)Note : Since primary of transformer is delta connected, line to ground fault

    current of 400 V will be reflected as line-line fault at 6.6 kV side.Hence set only 50N unit: Primary Protection for 6.6 kV Faults.(1) 6.6 kV system is resistance grounded and the fault current is limited to

    100 A.(2) Set PS = 0.1 A(3) Primary operating current = 0.1 x 200 = 20 A(4) Sensitivity = (20 x 100) / 100

    = 20% < 30 %(5) Hence set PS = 0.1 A(6) Time Delay = 0.0 sec

    Recommended Settings :PS = 0.1 A, Time Delay = 0.0 Sec

  • 8/11/2019 Relay Coordination (1)

    36/41

    RESTRICTED EARTH FAULT (64R) Normally set at lowest current tap available, say 10% To ensure relay does not operate during external faults, stabilizing resistor

    is added in series with the relay. Setting Procedure: The maximum voltage likely to appear across the relay during external

    faults is calculated, assuming worst condition i.e. CT on 1 side saturating. VR = I fault (R CT + 2R L)

    Where I

    fault= Secondary equivalent of fault current. = 33.8/3000 = 11.5 A

    R CT = The CT secondary winding resistance. =5 2R L = CT secondary lead resistance. = 2 x 5 = 10

    VR = 11.5 (15 ) = 173 V. Next calc. total relay circuit impedance R T; R T =V R / I R =173/11.5 = 15 .

    Obtain relay impedance R R from manufacturers catalogue. Stabilizing resistor R S = R T R R .

  • 8/11/2019 Relay Coordination (1)

    37/41

    PROTECTION CO-ORDINATION EARTH FAULT RELAY

    Relay 51S : Location : Stand by Earth fault relay of TR C.T.R. = 3000/1 Relay type = SPAJ 115C (SPACOM series ABB make) Earth fault IDMT unit (51N)

    Pick up = (0.05 0.4) x In, Step = 0.1 InTime Dial = 0.05-1.00, Step = 0.05

    Fault current passing = 33805 A (Earth fault current assumedthrough relay for same as phase fault current)MCC fault.

    Set PS at 0.4 A. Chosen characteristic is Normal Inverse (NI)

    Operating Time = 2.267 Sec. for PSM = 20.0 & Time Dial = 1.0

  • 8/11/2019 Relay Coordination (1)

    38/41

    PROTECTION CO-ORDINATION EARTH FAULT RELAY

    Desired operating time t1:Downstream relay 51N operating Time t = 0.164 Sec.Co-ordination interval td = (0.25t + 0.25) = 0.37 Sec.Desired Operating Time t1 = t + td = 0.164 + 0.37 = 0.534 Sec.

    Desired Time Dial TMS :TMS = Desired Operating Time t1 = 0.534 = 0.23

    Operating time @ TMS 1.0 2.267

    Set Time Dial at 0.25 [Time Dial = 0.05 1.00, Step = 0.05] Operating Time = 0.52 Sec.[2.267 x 0.23]

  • 8/11/2019 Relay Coordination (1)

    39/41

    Transformer Differential Protection

    DIFFERENTIAL PROTECTION.doc

    http://mumbaihome/trainingmodules/WIP%20Trg%20Module/Elect/Elect%20Module%20for%20review%20&%20comments/training%20material%20-%20elect-%20vadodara/Relay%20Co%20ordination/DIFFERENTIAL%20PROTECTION.dochttp://mumbaihome/trainingmodules/WIP%20Trg%20Module/Elect/Elect%20Module%20for%20review%20&%20comments/training%20material%20-%20elect-%20vadodara/Relay%20Co%20ordination/DIFFERENTIAL%20PROTECTION.doc
  • 8/11/2019 Relay Coordination (1)

    40/41

    Relays are installed not to prevent faults, but only to isolate the faultand minimize the damage. Most of the relays act after damage hasoccurred. Sophisticated relays and correct relay setting andcoordination are not a substitute for good maintenance practice.

    For successful clearing fault: (1) CT must not be saturated (2) CT & PT polaritymust be correct (3) Integrity of wiring between instrument transformers to relayshould be alright (4) Auxiliary supplies to the relay are available.

  • 8/11/2019 Relay Coordination (1)

    41/41

    Thank you