Section 3 REU615 standard configurations
3.1 Standard configurations
REU615 is available in two standard configurations. The standard signalconfiguration can be altered by means of the signal matrix or the graphicalapplication functionality of the Protection and Control IED Manager PCM600.Further, the application configuration functionality of PCM600 supports thecreation of multi-layer logic functions using various logical elements, includingtimers and flip-flops. By combining protection functions with logic functionblocks, the IED configuration can be adapted to user-specific applicationrequirements.
The IED is delivered from the factory with default connections described in thefunctional diagrams for binary inputs, binary outputs, function-to-functionconnections and alarm LEDs. The positive measuring direction of directionalprotection functions is towards the outgoing feeder.
Table 9: Standard configurations
Description Std.conf.Voltage and frequency based protection and measurement functions, synchrocheckand load shedding A
Automatic voltage regulator B
Table 10: Supported functions
Function IEC 61850 A B
Protection1)
Three-phase non-directional overcurrent protection, low stage PHLPTOC 1Three-phase non-directional overcurrent protection, high stage PHHPTOC 1Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1Residual overvoltage protection ROVPTOV 3 2) Three-phase undervoltage protection PHPTUV 3 3Three-phase overvoltage protection PHPTOV 3 3Positive-sequence undervoltage protection PSPTUV 2 Negative-sequence overvoltage protection NSPTOV 2 Frequency protection FRPFRQ 6 Three-phase thermal overload protection for power transformers, two timeconstants T2PTTR 1
Master trip TRPPTRC 2 2 3)
Arc protection ARCSARC (3) 4)
Multi-purpose protection 3)5) MAPGAPC 18 18Load shedding and restoration LSHDPFRQ 5 Control
Table continues on next page
1MRS757054 F Section 3REU615 standard configurations
REU615 29Application Manual
Function IEC 61850 A BCircuit-breaker control CBXCBR 1 3) 1
Disconnector control 3) DCXSWI 2 2
Earthing switch control 3) ESXSWI 1 1
Disconnector position indication 3) DCSXSWI 3 3
Earthing switch indication 3) ESSXSWI 2 2Tap changer position indication TPOSSLTC 1Tap changer control with voltage regulator OLATCC 1Synchronism and energizing check SECRSYN 1 Condition monitoringTrip circuit supervision TCSSCBR 2 3) 2Current circuit supervision CCRDIF 1Fuse failure supervision SEQRFUF 1
Runtime counter for machines and devices 3) MDSOPT 1 1MeasurementDisturbance recorder RDRE 1 1Load profile record LDPMSTA 1 1Three-phase current measurement CMMXU 1Sequence current measurement CSMSQI 1Three-phase voltage measurement VMMXU 2 1Residual voltage measurement RESVMMXU 1 Sequence voltage measurement VSMSQI 1 1Three-phase power and energy measurement PEMMXU 1RTD/mA measurement XRGGIO130 (1)Frequency measurement FMMXU 1
IEC 61850-9-2 LE (Voltage sharing) 6) SMVSENDER (1) (1)1, 2, ... = number of included instances() = optional
1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.2) Uo selectable by parameter, "Uo measured" as default3) Must be added with Application Configuration to be available in Signal Matrix and in IED4) Light only5) Multi-purpose protection is used, for example, for RTD/mA-based protection, or analog GOOSE.6) Only available with COM0031-0034
3.1.1 Addition of control functions for primary devices and theuse of binary inputs and outputsIf extra control functions intended for controllable primary devices are added to theconfiguration, additional binary inputs and/or outputs are needed to complementthe standard configuration.
If the number of inputs and/or outputs in a standard configuration is not sufficient,it is possible either to modify the chosen IED standard configuration in order torelease some binary inputs or binary outputs which have originally been configuredfor other purposes, or to integrate an external input/output module, for exampleRIO600, to the IED.
The external I/O module’s binary inputs and outputs can be used for the less time-critical binary signals of the application. The integration enables releasing someinitially reserved binary inputs and outputs of the IED’s standard configuration.
Section 3 1MRS757054 FREU615 standard configurations
30 REU615Application Manual
The suitability of the IED’s binary outputs which have been selected for primarydevice control should be carefully verified, for example make and carry andbreaking capacity. If the requirements for the primary device control circuit are notmet, using external auxiliary relays should be considered.
3.2 Connection diagrams
GUID-E8E4A6F1-57F5-4E53-AACF-FA95E7D92D83 V1 EN
Figure 11: Connection diagram for the A configuration (voltage protection withphase-to-phase voltage measurement)
1MRS757054 F Section 3REU615 standard configurations
REU615 31Application Manual
GUID-46B7ECD1-0F3F-4DCA-8144-8A485D02061A V1 EN
Figure 12: Connection diagram for the A configuration (voltage protection withphase-to-earth voltage measurement)
Section 3 1MRS757054 FREU615 standard configurations
32 REU615Application Manual
GUID-64ADD3D1-99D0-458B-8E28-5023277CFD6C V1 EN
Figure 13: Connection diagram for the B configuration (on-load tap changercontrol with phase-to-phase voltage measurement)
1MRS757054 F Section 3REU615 standard configurations
REU615 33Application Manual
GUID-AE8916E5-D21C-4C90-B38A-C93EDE80FF2E V1 EN
Figure 14: Connection diagram for the B configuration (on load tap changercontrol with phase-to-earth voltage measurement)
3.3 Standard configuration A
3.3.1 ApplicationsThe standard configuration is intended for voltage protection and synchronismcheck in the medium voltage networks. The configuration handles fault conditions
Section 3 1MRS757054 FREU615 standard configurations
34 REU615Application Manual