RFI Response #1 Central Christian Church Phase 2 Balcony Addition & Lobby Remodel Release Date 02.23.16 Bid Due Date: 03.03.16 1) Fixture type L3 – please provide specs and the number of LED drivers required for a certain linear footage. A: Fixture Type L3 should be removed from the Lighting Fixture Schedule. The aisle light is to be provided by the seating vendor as an integral part of the seating system. The electrical contractor will provide electrical connections to the aisle light with connection locations to be provided by the seating vendor. 2) Is there a responsibility matrix, is GC to provide the low voltage system (Telecom, AV, fire alarm)? A: Audio Visual and Telecom is not in the GC scope of work. Fire Alarm is integrated with Siemens Building Technologies, please contact Steve Ciulla, Account Executive at 702-855-5300 x 5342, or [email protected] 3) The door schedule on sheet A700 states that the doors shall be refurbished salvaged doors. Are there enough salvaged doors with the correct swings for the project and who is to refurbish the doors the owner since they are doing the staining and painting or the contractor? Please clarify what refurbish means – i.e. Just finish or changing swings? A: There are 14 pairs of exit type doors used for this project. 12 pairs are to be demo'd, these can be used in the new construction, 3 new pairs will be needed. The door hardware should be the same or equal to the hardware in use on site. Hardware subcontractor should verify the hardware set used. There are 3 single exit doors and 5 on the demo so there is no need for new doors. 2 doors are not required to be exits. The Owner has classroom doors that can be used for these. Note; the 200 A-E and 205 A-D should have a closure, the schedule is marked incorrect. Meaning of refurbished is only that if the doors are removed during demolition and are in good condition with no visible defects from relocation they can be used in that condition. If they are damaged during demolition and can be repaired, that contractor is required to place them in a good condition.

RFI Response #1 - construction22.com PLANS/A6352 Central Christian Churc… · provide Matrix on bid documents of these items. 11) The Unit Price form in the bid form starts with

  • Upload
    buidan

  • View
    215

  • Download
    1

Embed Size (px)

Citation preview

RFI Response #1 Central Christian Church

Phase 2 Balcony Addition & Lobby Remodel Release Date 02.23.16

Bid Due Date: 03.03.16

1) Fixture type L3 – please provide specs and the number of LED drivers required for a certain linear footage. A: Fixture Type L3 should be removed from the Lighting Fixture Schedule. The aisle light is to be provided by the seating vendor as an integral part of the seating system. The electrical contractor will provide electrical connections to the aisle light with connection locations to be provided by the seating vendor.

2) Is there a responsibility matrix, is GC to provide the low voltage system (Telecom, AV, fire alarm)?

A: Audio Visual and Telecom is not in the GC scope of work. Fire Alarm is integrated with Siemens Building Technologies, please contact Steve Ciulla, Account Executive at 702-855-5300 x 5342, or [email protected]

3) The door schedule on sheet A700 states that the doors shall be refurbished salvaged doors. Are there enough salvaged doors with the correct swings for the project and who is to refurbish the doors the owner since they are doing the staining and painting or the contractor? Please clarify what refurbish means – i.e. Just finish or changing swings?

A: There are 14 pairs of exit type doors used for this project. 12 pairs are to be demo'd, these can be used in the new construction, 3 new pairs will be needed. The door hardware should be the same or equal to the hardware in use on site. Hardware subcontractor should verify the hardware set used. There are 3 single exit doors and 5 on the demo so there is no need for new doors. 2 doors are not required to be exits. The Owner has classroom doors that can be used for these. Note; the 200 A-E and 205 A-D should have a closure, the schedule is marked incorrect. Meaning of refurbished is only that if the doors are removed during demolition and are in good condition with no visible defects from relocation they can be used in that condition. If they are damaged during demolition and can be repaired, that contractor is required to place them in a good condition.

4) Sheet A700 does not offer detail on the base or head of the interior partitions, rated walls, non-rated walls, acoustical walls, chase walls and 2 hour walls. Fire Caulking is shown at the top of Type 2A walls and we are unclear if the intention is for rating or acoustical purposes. Sheet A101.1 shows openings that would compromise any rating. A: The drawings are incorrect the sealant should be acoustical only on non rated walls. After further review I believe there will not be a required two hour wall so A101.1 will be a 2A not 4A. 5) Wall type legend on A700 shows fire caulking at top of Type 2A walls (as if the walls are fire rated). We believe these are non-rated walls and the caulking is for acoustical purposes only. Please clarify. NOTE: On page A101.1 the walls are shown with openings that will compromise the rating if the intent is for these walls to be fire rated. A: A101.1 will be corrected with first review by city.

6) The carpet tiles and VCT is OFOI – will the Vinyl Base be by the Owner also?

A: Vinyl Base is OFOI.

7) The finish schedule states the ACT-1 is Owner Furnished – who is doing the install of

this material?

A: Contractor to provide and install grid and ACT provided by owner.

8) Will the metal stud framing as shown on structural drawings S607 need to have

engineered shop drawings?

A: Shop drawings for the stud framing on S607 are not needed. The stud framing details provided on S606 & S607, with combination of the notes and plans in the structural drawings should be sufficient.

9) Will the Owner be submitting the plans for the building permit as well as paying all associated fees?

A: Yes, the owner will be paying for the permit and associated fees.

10) Please clarify Unit Price 4 in the bid form - It states Miscellaneous and Structural Steel $ per unit. This cannot be priced as stated as there are many types of structural steel as well as misc. items and they are all different prices? Not clear what you are looking for.

A: Sort out the Miscellaneous and Structural Steel. Giive individual pricing on the type or classification of the material, plus the cost of erection. (i.e. Description, quantity, price per ea./TN/SFS/LF etc.) Use additional sheets to list or GC can provide Matrix on bid documents of these items.

11) The Unit Price form in the bid form starts with Unit Price 3. Are there Unit prices 1 & 2? A: Referring to “Unit Prices” in spec book, Address Letters A-D (3-5). Additionally, address Unit pricing through the RFP to bidders. This is a more complete Bid Form Document is required to be filled out completely.

12) On sheet D121 Demo note 4 calls out that all exposed fireproofing be treated with

Silicate Hardener – Please specify which product would be required for this work? A: The intent of this matter, is that the owner does not want the existing fireproofing flaking off after construction is complete. If the existing fireproofing is already dense enough to not and the new paint added to the exposed construction, then this note is not required.

13) All demo items listed as remove and salvage to owner – will all this material be taken

to a storage area on the church property or will we be required to transport it offsite to a remote storage location? A: Note on D121 is incorrect. Do not salvage existing ACT nor grid. Seating storage provided by owner under owner’s roof, seating to be removed and stored at owner’s direction under owner’s roof.

14) Are there any particular doors that we are to use for access to the work area?

A: Please plan to use the Door Entry 3 for access for workers. There may be times that other doors can be made available by coordinating with owner. Please address this issue if required in the Bidding GC presentation.

15) RFP Page 2 Item 12….What are the CCC Lender Requirements and the NRS Project disbursement company rules and regulations? A: Lender requires a standardized Pay Application from the GC, to be broken out by standardized 16 CSI Divisions. Selected GC for project will go over this detail with Central Christian Church Construction Team once selected. Project disbursement company (TBD), typical rules & regulations apply for working with a Nevada Company.

16) Is there an asbestos survey already completed on this project?

A: Please see attached Asbestos Report from CCC Phase 1 Construction.

17) Which party will be responsible for the furnish and installations of the following items? Please identify as one of the following- OFOI (Owner Furnish Owner Install),OFCI (Owner Furnished Contractor Install), CFOI (Contractor Furnish Owner Install), or CFCI (Contractor Furnish Contractor Install) 1. EC-1 -OFOI 2. EC-2 -OFOI 3. CT-1 - CFCI 4. CT-2 - CFCI 5. CPT-1 -OFOI 6. VB-1 - OFOI 7. ACT-1 -Contractor install grid, owner furnished tile. 8. P-1 - OFOI 9. P-2 - OFOI 10. P-3 - OFOI 11. P-4 - OFOI 12. P-5 - OFOI

18) Sheet G000 “Code Analysis” indicates building is Type 1B construction. Sheet A100 & A701 states construction type to be 1A. Please clarify building type. A: Type 1B

19) Sheet A121.1 states Fireproofing to be minimum 40lb density. When referencing A701, the materials mentioned Z106hy is a medium density cementitious SFRM with a 22lb density. Please clarify which product you want sprayed.

A: A701 is correct, the medium density fireproofing is acceptable.

20) Building section D1 on sheet A200 illustrates that the existing roof is less than 20’ AFF. Is the existing structural frame & roof assemble already fireproofed? If not, please clarify what grid lines you wanted fireproofed on sheet S104

A: Fireproofing will need to be added to bays between C & E.

21) Bidders have identified the existing glazing systems are Interplane high performance glass, they are no longer in business. A close match may be available from Viracon. Are the building record glazing specifications available for the bidders to aid in figuring their glazing cost.

A: Viracon is an acceptable substitution.

RFIResponse#2CentralChristianChurch

Phase2BalconyAddition&LobbyRemodelReleaseDate02.25.16

BidDueDate:03.03.16

1) ConfirmexistingtopchordatD&Eistoremaininplace.IfsoareshopdrawingsavailablefortheChord?

A:Yes,thetopchordonD&Etoremaininplace.Contractortoprovideall

measuresnecessarytoprotectexitingroofandtopchordduringtheinstallation

ofthenewroofbeamsandtruss.Wedon’thaveshopdrawingsfortheexisting

chord. 2) IwouldliketoconfirmSheetS605Detail8andifthatiswhatisintended.

A:Yes,thedetailisaccurate.

3) Duetothelengthofsomeofthebeamsontheprojecttherewillhavetobeaconnectionoftwosmallerbeams,nosuchdetailhasbeenprovided.Ifoneisgoingtobeprovided,whichbeamsarewetoapplythisdetailtoandatwhatlocations?A:Beamsmaybefullpenweldedatcontractorrequest.Contractortoprovideinformationregardingmaximumlength.

4) DrawingE0.1–IcannotfindthelocationofexistingMSA,whereisthetieinpointfortheexistingconduitfromMSAtoDSB?

A:MainServiceSwitchboard‘MSA’islocatedintheCentralPlantBuilding.WearelookingtointerceptandaddajunctionboxandsplicefortheexistingfeedertoDistributionSwitchboard‘DSB’andextendthefeedertothenewlocationontheSecondFloor.TheinterceptpointshouldbeincloseproximitytothecurrentlocationofDistributionSwitchboard‘DSB’asshownonSheetED2.0A.

5) OnPageMP0.1theyspecoutsteelpipewithweldedorscrewedfittingsforthemechanicalpiping.IssteelpipewithgroovedVictaulicfittingsaccepted?

A:Yes,steelpipewithgroovedVictaulicfittingswillbeaccepted.

6) WilltheAluminumstorefrontdoorsatthenewEntries3and4andthesecondfloorpairofdoorsrequirepanichardware?

A:Allexitdoorsrequirepanichardware.

7) AmItofigureusingHandicapOperatorsonOne(1)dooreach(exteriorandvestibule)attheEntries3and4Justliketherestofthebuilding?

A:Yes.

RFIResponse#2(A)CentralChristianChurch

Phase2BalconyAddition&LobbyRemodelReleaseDate02.25.16

BidDueDate:03.03.16

1) ConfirmexistingtopchordatD&Eistoremaininplace.IfsoareshopdrawingsavailablefortheChord?

A:Yes,thetopchordonD&Etoremaininplace.Contractortoprovideall

measuresnecessarytoprotectexitingroofandtopchordduringtheinstallation

ofthenewroofbeamsandtruss.Wedon’thaveshopdrawingsfortheexisting

chord. 2) IwouldliketoconfirmSheetS605Detail8andifthatiswhatisintended.

A:Yes,thedetailisaccurate.

3) Duetothelengthofsomeofthebeamsontheprojecttherewillhavetobeaconnectionoftwosmallerbeams,nosuchdetailhasbeenprovided.Ifoneisgoingtobeprovided,whichbeamsarewetoapplythisdetailtoandatwhatlocations?A:Beamsmaybefullpenweldedatcontractorrequest.Contractortoprovideinformationregardingmaximumlength.

4) DrawingE0.1–IcannotfindthelocationofexistingMSA,whereisthetieinpointfortheexistingconduitfromMSAtoDSB?

A:MainServiceSwitchboard‘MSA’islocatedintheCentralPlantBuilding.WearelookingtointerceptandaddajunctionboxandsplicefortheexistingfeedertoDistributionSwitchboard‘DSB’andextendthefeedertothenewlocationontheSecondFloor.TheinterceptpointshouldbeincloseproximitytothecurrentlocationofDistributionSwitchboard‘DSB’asshownonSheetED2.0A.

5) OnPageMP0.1theyspecoutsteelpipewithweldedorscrewedfittingsforthemechanicalpiping.IssteelpipewithgroovedVictaulicfittingsaccepted?

A:Yes,steelpipewithgroovedVictaulicfittingswillbeaccepted.

6) WilltheAluminumstorefrontdoorsatthenewEntries3and4andthesecondfloorpairofdoorsrequirepanichardware?

A:Allexitdoorsrequirepanichardware.

7) AmItofigureusingHandicapOperatorsonOne(1)dooreach(exteriorandvestibule)attheEntries3and4Justliketherestofthebuilding?

A:(ArchitecturalResponse)–Yes.

(ElectricalResponse)-Thecontractorshallfurnishandinstallelectricalconnectiontoautooperatorstobeinstalledonthenewentrydoors.Verifythecorrectdoorswiththearchitecturaldrawingspriortorough-in.Route¾”C–2#12,1#12gnd,fromeachpairofdoorswithanautooperatorandroutetoaspare20A,1PcircuitbreakerinPanel‘DBSA’.Pleaseroutetocircuits24and26.Provideallcontrolconduitandconductorsfromtheautooperatortothecontrolelement(electriceyeorpushplate)asperapprovedequipmentshopdrawings.

Prepared for:

Wallin Construction, LLC 7330 Eastgate Road, Suite 110

Henderson, Nevada 89011

LIMITED ASBESTOS SURVEY REPORT

CENTRAL CHRISTIAN CHURCH AUDITORIUM

1001 NEW BEGINNINGS DRIVE HENDERSON, NEVADA 89011

Prepared by:

Dominion Environmental Consultants NV, Inc. 150 North Durango Drive, Suite190

Las Vegas, Nevada 89145 (702) 368-2700

Dominion Project Number: NV1421.04

Inspection Date: October 1, 2014

TABLE OF CONTENTS

LIMITATIONS ...................................................................................................................................... SECTION 1 EXECUTIVE SUMMARY .................................................................................................................... SECTION 2 SITE MAP ............................................................................................................................................... SECTION 3 PLM BULK SAMPLE SUMMARY ..................................................................................................... SECTION 4 PLM BULK SAMPLE LOCATION MAP .......................................................................................... SECTION 5 PLM LABORATORY ANALYSIS REPORT ..................................................................................... SECTION 6 EPA NESHAP NOTIFICATION INFORMATION SHEET ............................................................. SECTION 7 GENERAL NOTES/EXCLUSIONS ..................................................................................................... SECTION 8 INSPECTOR CERTIFICATIONS ....................................................................................................... SECTION 9 LABORATORY CERTIFICATIONS ................................................................................................ SECTION 10

SECTION 1

LIMITATIONS

LIMITATIONS The conclusions and results contained herein are based solely on the information presented in this report and are for the sole use of the Client exclusively and are subject to the terms and conditions of “The Contract”. No other person or entity may rely on this report without the prior written consent of Dominion Environmental Consultants NV, Inc. The sampling, testing, and observations described in the report represent conditions only at the specified times and locations. Additional materials or information which were hidden, undiscovered, inaccessible, or are not a part of the finding presented herein, would result in the modification of the conclusions and recommendations made herein. Any response action guidelines are based solely on the findings contained herein. The response action guidelines are presented as a courtesy and are not to be considered a complete or detailed set of specifications. Dominion performed these services using the degree of care and skill ordinarily exercised under similar conditions by reputable members of the profession practicing in the same or similar circumstances. Please note, with regard to laboratory analysis of suspect bulk asbestos-containing materials: The Environmental Protection Agency (EPA) Method 600/R-93-116, Polarized Light Microscopy (PLM) is used for the testing of bulk building materials for asbestos by performing a visual estimation. This method is the most widely used method for estimating asbestos in bulk building materials and works well for most sample types. However, it might require a more detailed method such as point counting for accurate estimation of asbestos in samples with low asbestos concentration. This method is also not applicable for samples containing large amounts of fine fibers below the resolution of the PLM (<0.3 microns). Typically, the asbestos fibers present in non-friable organically bound (NOB) materials are often less than 0.1 microns in diameter and therefore may cause the PLM method to yield low estimates or even false negative results. Dominion suggests that Transmission Electron Microscopy (TEM) Chatfield Semi-Quantitative EPA Method 600/R-93-116 be used to confirm all negative results of NOB materials. This method is particularly useful to reduce the possibility of false negatives in NOBs and to provide additional quantitative data for samples which contain low levels of asbestos. The TEM method is available at additional cost and is done only at the client’s request. Dominion’s scope of service for this report did not include the inspection for, or identification of fungi, lead paint, or any other hazardous or controlled substances not specifically identified herein. Dominion is not responsible for the accuracy of information provided by others, or for conditions or consequences arising from relevant facts that were withheld, concealed, undiscovered, or not fully disclosed. Dominion is not a law firm and therefore, makes no representations regarding any potential liability of any person or entity for site conditions. Further, Dominion is not qualified to present medical advice. If any present or future health issues are in question, it is recommended that the findings in this report be presented to a qualified medical professional for evaluation.

SECTION 2

EXECUTIVE SUMMARY

EXECUTIVE SUMMARY INTRODUCTION This report presents the results of a limited AHERA-style asbestos inspection conducted for Wallin Construction, LLC. The limited asbestos inspection was conducted at the Central Christian Church Auditorium, located at 1001 New Beginnings Drive, in Henderson, Nevada. Dominion was authorized by Mr. Justin Wallin, with Wallin Construction LLC, to perform the limited asbestos inspection via verbal authorization on October 1, 2014. BACKGROUND INFORMATION Dominion was informed that during renovations at the church, Clark County Air Quality had arrived on site and requested that asbestos sampling be performed. ASBESTOS SAMPLING The limited asbestos inspection of the auditorium was conducted on October 1, 2014, by Mr. Christopher Webster, an EPA-accredited AHERA asbestos building inspector and Nevada OSHA-licensed asbestos inspector. Mr. Wallin outlined the areas and the materials being disturbed during the renovation activities, instructed Dominion to collect bulk samples of the building materials, and instructed Dominion to have those samples analyzed for the presence of asbestos fibers by a qualified laboratory. A total of 42 bulk samples were collected from the suspect building materials within the outlined areas of the auditorium. The suspect bulk samples were submitted to EMLab P&K, LLC (EMLab) for analysis using Polarized Light Microscopy (PLM) methods. EMLab used the methods prescribed in Method 40 CFR, Part 763, in the Code of Federal Register in analyzing bulk samples. EMLab is certified by the National Institute of Standards and Technology (NIST) as adhering to and in compliance with the National Voluntary Laboratory Accreditation Program (NVLAP) and holds the certification number 500031-0. The suspect asbestos bulk samples were collected and submitted to the laboratory using established chain of custody procedures. Bulk samples were collected utilizing safety and health practices as required by the Occupational Safety and Health Administration (OSHA). Following are the suspect building materials that were sampled during the limited asbestos inspection:

• Black Textured Drywall System o Black Paint o White Texture o Cream Tape o White Joint Compound o White Drywall

• Orange Peel Textured Drywall System o Black Paint o White Texture o Cream Tape o White Joint Compound o White Drywall with Brown Paper

• Dark Brown 4” Cove Base and Associated Material o Dark Brown Baseboard o Cream Mastic

• Gray Fireproofing • White 2’x4’ Acoustic Ceiling Tile • Stage Floor Top Layer (Black) • Gray Stage Concrete Slab

• Outer Layer HVAC Wrap - Pink • Inner Layer HVAC Wrap - Pink • Silver Tape - HVAC - Yellow • Silver Ducting Wrap - HVAC - Yellow • Gray Carpet and Associated Material

o Gray Carpet o Yellow Mastic

• Black Felt (Between Slab & Wood) • Yellow Wood Stage Mastic

The building materials sampled were reported by laboratory PLM analysis to be “none detected” for asbestos. RECOMMENDATIONS Based on the previously referenced laboratory analytical data, there are no asbestos recommendations at this time. If any un-sampled suspect building materials are discovered during the renovation project, those building materials should be properly sampled by a certified inspector prior to their disturbance. All documentation is provided to Wallin Construction, LLC., and should be retained in a permanent record. Should you have any questions regarding the procedures that were followed on this project, please contact me at any time. Thank you for the opportunity to provide these environmental consulting services. Christopher Webster Benjamin Bojda Project Manager Director of Nevada Operations NEVADA Asbestos Inspector NEVADA Asbestos Inspector/Project Monitor NV License Number: IM-1529 NV License Number: IPM-1380 Expires: April 14, 2015 Expires: September 16, 2015 AHERA Asbestos Building Inspector AHERA Asbestos Building Inspector AHERA Certificate Number: F 9962 AHERA Certificate Number: G 1655 Expires: April 4, 2015 Expires: September 4, 2015

SECTION 3

SITE MAP

Site MapCentral Christian Church1001 New Beginnings DriveHenderson, Nevada 89011

N

Project No. NV1421.04

DOMINION ENVIRONMENTAL CONSULTANTS NV, INC.150 North Durango, Suite 190, Las Vegas, Nevada 89145

Office: (702) 368-2700 Fax: (702) 368-2707

Not to Scale

Stage

Hallway 1 Hallway 2

Auditorium

SECTION 4

PLM BULK SAMPLE SUMMARY

DOMINION ENVIRONMENTAL CONSULTANTS NV, INC.PLM Bulk Sample Summary

Sample Number Material Description Sample Location Friable Asbestos Content

Black Paint No None Detected

White Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Black Paint No None Detected

White Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Black Paint No None Detected

White Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Black Paint No None Detected

White Orange Peel Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Black Paint No None Detected

White Orange Peel Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Auditorium Debris

Auditorium Debris

NV1421.04-PLM-05

NV1421.04-PLM-04

Auditorium Debris

Auditorium Debris

Auditorium DebrisNV1421.04-PLM-03

NV1421.04-PLM-02

NV1421.04-PLM-01

Client: Wallin Construction, LLC

Site: Central Chritian Church Auditorium - 1001 New Beginnings Drive, Henderson, Nevada Sample Date: October 1, 2014

Dominion Project Number: NV1421.04

Page 1

DOMINION ENVIRONMENTAL CONSULTANTS NV, INC.PLM Bulk Sample Summary

Sample Number Material Description Sample Location Friable Asbestos Content

Client: Wallin Construction, LLC

Site: Central Chritian Church Auditorium - 1001 New Beginnings Drive, Henderson, Nevada Sample Date: October 1, 2014

Dominion Project Number: NV1421.04

Black Paint No None Detected

White Orange Peel Texture Yes None Detected

Cream Tape No None Detected

White Joint Compound Yes None Detected

White Drywall No None Detected

Dark Brown 4" Cove Base No None Detected

Cream Mastic No None Detected

Dark Brown 4" Cove Base No None Detected

Cream Mastic No None Detected

Dark Brown 4" Cove Base No None Detected

Cream Mastic No None Detected

NV1421.04-PLM-10 Gray Fireproofing Auditorium - SE Corner Yes None Detected

NV1421.04-PLM-11 Gray Fireproofing Auditorium - SE Corner Yes None Detected

NV1421.04-PLM-12 Gray Fireproofing Auditorium - SE Corner Yes None Detected

NV1421.04-PLM-13 White 2'x4' Acoustic Ceiling Tile Auditorium Debris Yes None Detected

NV1421.04-PLM-14 White 2'x4' Acoustic Ceiling Tile Auditorium Debris Yes None Detected

NV1421.04-PLM-15 White 2'x4' Acoustic Ceiling Tile Auditorium Debris Yes None Detected

NV1421.04-PLM-16 Black Stage Floor Top Layer Stage - West No None Detected

NV1421.04-PLM-17 Black Stage Floor Top Layer Stage - West No None Detected

NV1421.04-PLM-18 Black Stage Floor Top Layer Stage - West No None Detected

NV1421.04-PLM-19 Gray Stage Concrete Slab Stage - West No None Detected

NV1421.04-PLM-20 Gray Stage Concrete Slab Stage - West No None Detected

NV1421.04-PLM-21 Gray Stage Concrete Slab Stage - West No None Detected

NV1421.04-PLM-22 Outer Layer HVAC Wrap - Pink Auditorium Debris No None Detected

NV1421.04-PLM-23 Outer Layer HVAC Wrap - Pink Auditorium Debris No None Detected

NV1421.04-PLM-24 Outer Layer HVAC Wrap - Pink Auditorium Debris No None Detected

Auditorium Debris

Auditorium Debris

Auditorium Debris

NV1421.04-PLM-09

NV1421.04-PLM-08

NV1421.04-PLM-07

Auditorium DebrisNV1421.04-PLM-06

Page 2

DOMINION ENVIRONMENTAL CONSULTANTS NV, INC.PLM Bulk Sample Summary

Sample Number Material Description Sample Location Friable Asbestos Content

Client: Wallin Construction, LLC

Site: Central Chritian Church Auditorium - 1001 New Beginnings Drive, Henderson, Nevada Sample Date: October 1, 2014

Dominion Project Number: NV1421.04

NV1421.04-PLM-25 Inner Layer HVAC Wrap - Pink Auditorium Debris No None Detected

NV1421.04-PLM-26 Inner Layer HVAC Wrap - Pink Auditorium Debris No None Detected

NV1421.04-PLM-27 Inner Layer HVAC Wrap - Pink Auditorium Debris No None Detected

NV1421.04-PLM-28 Silver Tape - HVAC Yellow Auditorium Debris No None Detected

NV1421.04-PLM-29 Silver Tape - HVAC Yellow Auditorium Debris No None Detected

NV1421.04-PLM-30 Silver Tape - HVAC Yellow Auditorium Debris No None Detected

NV1421.04-PLM-31 Silver Ducting Wrap - HVAC Yellow Auditorium Debris No None Detected

NV1421.04-PLM-32 Silver Ducting Wrap - HVAC Yellow Auditorium Debris No None Detected

NV1421.04-PLM-33 Silver Ducting Wrap - HVAC Yellow Auditorium Debris No None Detected

Gray Carpet No None Detected

Yellow Mastic No None Detected

Gray Carpet No None Detected

Yellow Mastic No None Detected

Gray Carpet No None Detected

Yellow Mastic No None Detected

NV1421.04-PLM-37 Black Felt Stage - West No None Detected

NV1421.04-PLM-38 Black Felt Stage - West No None Detected

NV1421.04-PLM-39 Black Felt Stage - West No None Detected

NV1421.04-PLM-40 Yellow Wood Stage Mastic Stage - West No None Detected

NV1421.04-PLM-41 Yellow Wood Stage Mastic Stage - West No None Detected

NV1421.04-PLM-42 Yellow Wood Stage Mastic Stage - West No None Detected

Auditorium - NE Corner

Auditorium - NE Corner

Auditorium - NE Corner

NV1421.04-PLM-36

NV1421.04-PLM-35

NV1421.04-PLM-34

Page 3

SECTION 5 ♦

PLM BULK SAMPLE LOCATION MAP

PLM Bulk Sample Location MapCentral Christian Church1001 New Beginnings DriveHenderson, Nevada 89011

N

Project No. NV1421.04

DOMINION ENVIRONMENTAL CONSULTANTS NV, INC.150 North Durango, Suite 190, Las Vegas, Nevada 89145

Office: (702) 368-2700 Fax: (702) 368-2707

Not to Scale

Stage

Hallway 1 Hallway 2

Auditorium

PLM Bulk Sample Location

10

11

12

3635

3421

18

37 38

40 41

19

2016

17

39 42

25, 26, 27

28, 29, 30

31, 32, 33

22, 23, 24

1, 2, 3

4, 5, 6

13, 14, 15

7, 8, 9

SECTION 6 ♦

PLM LABORATORY ANALYSIS REPORT

Approved by:

Approved SignatoryRenee Luna

Report for:

Mr. Christopher WebsterDominion Environmental Consultants, Inc.150 N. Durango Drive, Suite 190Las Vegas, NV 89145

Regarding: Project: NV1421.04; Central ChurchEML ID: 1271143

All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.

EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.

Dates of Analysis:Asbestos PLM: 10-02-2014

Service SOPs: Asbestos PLM (EPA Methods 600/R-93/116 & 600/M4-82-020, SOP EM-AS-S-1267)

EMLab ID: 1271143, Page 1 of 13Aerotech Laboratories, Inc

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Total Samples Submitted: 42Total Samples Analysed: 42

Total Samples with Layer Asbestos Content > 1%: 0

Location: 1, PLM-01 Black Textured Drywall System (Paint, Texture, Tape, Joint Compound & Drywall) Lab ID-Version‡: 5786534-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

Location: 2, PLM-02 Black Textured Drywall System (Paint, Texture, Tape, Joint Compound & Drywall) Lab ID-Version‡: 5786535-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

Location: 3, PLM-03 Black Textured Drywall System (Paint, Texture, Tape, Joint Compound & Drywall) Lab ID-Version‡: 5786536-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

EMLab ID: 1271143, Page 2 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 4, PLM-04 Orange Peel Textured Drywall System, Paint, Texture, Tape, Joint Compound, & Drywall Lab ID-Version‡: 5786537-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

EMLab ID: 1271143, Page 3 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 5, PLM-05 Orange Peel Textured Drywall System, Paint, Texture, Tape, Joint Compound, & Drywall Lab ID-Version‡: 5786538-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

Location: 6, PLM-06 Orange Peel Textured Drywall System, Paint, Texture, Tape, Joint Compound, & Drywall Lab ID-Version‡: 5786539-1

Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND

White Joint Compound NDCream Tape ND

White Texture NDBlack Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor

Location: 7, PLM-07 Dark Brown 4" Cove Base & Mastic Lab ID-Version‡: 5786540-1

Sample Layers Asbestos ContentCream Mastic ND

Dark Brown Baseboard NDSample Composite Homogeneity: Moderate

Location: 8, PLM-08 Dark Brown 4" Cove Base & Mastic Lab ID-Version‡: 5786541-1

Sample Layers Asbestos ContentCream Mastic ND

Dark Brown Baseboard NDSample Composite Homogeneity: Moderate

EMLab ID: 1271143, Page 4 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 9, PLM-09 Dark Brown 4" Cove Base & Mastic Lab ID-Version‡: 5786542-1

Sample Layers Asbestos ContentCream Mastic ND

Dark Brown Baseboard NDSample Composite Homogeneity: Moderate

Location: 10, PLM-10 Gray Fire Proofing Lab ID-Version‡: 5786543-1

Sample Layers Asbestos ContentGray Fireproofing ND

Composite Non-Asbestos Content: 25% CelluloseSample Composite Homogeneity: Good

Location: 11, PLM-11 Gray Fire Proofing Lab ID-Version‡: 5786544-1

Sample Layers Asbestos ContentGray Fireproofing ND

Composite Non-Asbestos Content: 25% CelluloseSample Composite Homogeneity: Good

Location: 12, PLM-12 Gray Fire Proofing Lab ID-Version‡: 5786545-1

Sample Layers Asbestos ContentGray Fireproofing ND

Composite Non-Asbestos Content: 25% CelluloseSample Composite Homogeneity: Good

EMLab ID: 1271143, Page 5 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 13, PLM-13 White 2'x4' Acoustic Ceiling Tile Lab ID-Version‡: 5786546-1

Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 40% Cellulose30% Glass Fibers

Sample Composite Homogeneity: Good

Location: 14, PLM-14 White 2'x4' Acoustic Ceiling Tile Lab ID-Version‡: 5786547-1

Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 40% Cellulose30% Glass Fibers

Sample Composite Homogeneity: Good

Location: 15, PLM-15 White 2'x4' Acoustic Ceiling Tile Lab ID-Version‡: 5786548-1

Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 40% Cellulose30% Glass Fibers

Sample Composite Homogeneity: Good

Location: 16, PLM-16 Stage Floor Top Layer Lab ID-Version‡: 5786549-1

Sample Layers Asbestos ContentBlack Flooring ND

Sample Composite Homogeneity: Good

EMLab ID: 1271143, Page 6 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 17, PLM-17 Stage Floor Top Layer Lab ID-Version‡: 5786550-1

Sample Layers Asbestos ContentBlack Flooring ND

Sample Composite Homogeneity: Good

Location: 18, PLM-18 Stage Floor Top Layer Lab ID-Version‡: 5786551-1

Sample Layers Asbestos ContentBlack Flooring ND

Sample Composite Homogeneity: Good

Location: 19, PLM-19 Stage Concrete Slab Lab ID-Version‡: 5786552-1

Sample Layers Asbestos ContentGray Concrete ND

Sample Composite Homogeneity: Good

Location: 20, PLM-20 Stage Concrete Slab Lab ID-Version‡: 5786553-1

Sample Layers Asbestos ContentGray Concrete ND

Sample Composite Homogeneity: Good

EMLab ID: 1271143, Page 7 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 21, PLM-21 Stage Concrete Slab Lab ID-Version‡: 5786554-1

Sample Layers Asbestos ContentGray Concrete ND

Sample Composite Homogeneity: Good

Location: 22, PLM-22 Outer Layer HVAC Wrap Pink Lab ID-Version‡: 5786555-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 3% Glass FibersSample Composite Homogeneity: Good

Location: 23, PLM-23 Outer Layer HVAC Wrap Pink Lab ID-Version‡: 5786556-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 3% Glass FibersSample Composite Homogeneity: Good

Location: 24, PLM-24 Outer Layer HVAC Wrap Pink Lab ID-Version‡: 5786557-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 3% Glass FibersSample Composite Homogeneity: Good

EMLab ID: 1271143, Page 8 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 25, PLM-25 Inner Layer HVAC Wrap Pink Lab ID-Version‡: 5786558-1

Sample Layers Asbestos ContentSemi-Transparent Wrap ND

Composite Non-Asbestos Content: 5% Glass FibersSample Composite Homogeneity: Good

Location: 26, PLM-26 Inner Layer HVAC Wrap Pink Lab ID-Version‡: 5786559-1

Sample Layers Asbestos ContentSemi-Transparent Wrap ND

Composite Non-Asbestos Content: 5% Glass FibersSample Composite Homogeneity: Good

Location: 27, PLM-27 Inner Layer HVAC Wrap Pink Lab ID-Version‡: 5786560-1

Sample Layers Asbestos ContentSemi-Transparent Wrap ND

Composite Non-Asbestos Content: 5% Glass FibersSample Composite Homogeneity: Good

Location: 28, PLM-28 HVAC (Yellow) Silver Tape Lab ID-Version‡: 5786561-1

Sample Layers Asbestos ContentSilver Tape NDComposite Non-Asbestos Content: 30% Cellulose

5% Glass FibersSample Composite Homogeneity: Good

EMLab ID: 1271143, Page 9 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 29, PLM-29 HVAC (Yellow) Silver Tape Lab ID-Version‡: 5786562-1

Sample Layers Asbestos ContentSilver Tape NDComposite Non-Asbestos Content: 30% Cellulose

5% Glass FibersSample Composite Homogeneity: Good

Location: 30, PLM-30 HVAC (Yellow) Silver Tape Lab ID-Version‡: 5786563-1

Sample Layers Asbestos ContentSilver Tape NDComposite Non-Asbestos Content: 30% Cellulose

5% Glass FibersSample Composite Homogeneity: Good

Location: 31, PLM-31 HVAC (Yellow) Ducting Wrap Lab ID-Version‡: 5786564-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 30% Cellulose15% Glass Fibers

Sample Composite Homogeneity: Good

Location: 32, PLM-32 HVAC (Yellow) Ducting Wrap Lab ID-Version‡: 5786565-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 30% Cellulose15% Glass Fibers

Sample Composite Homogeneity: Good

EMLab ID: 1271143, Page 10 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 33, PLM-33 HVAC (Yellow) Ducting Wrap Lab ID-Version‡: 5786566-1

Sample Layers Asbestos ContentSilver Wrap ND

Composite Non-Asbestos Content: 30% Cellulose15% Glass Fibers

Sample Composite Homogeneity: Good

Location: 34, PLM-34 Gray Carpet & Yellow Mastic Lab ID-Version‡: 5786567-1

Sample Layers Asbestos ContentYellow Mastic NDGray Carpet ND

Composite Non-Asbestos Content: 45% Synthetic Fibers< 1% Cellulose

Sample Composite Homogeneity: Moderate

Location: 35, PLM-35 Gray Carpet & Yellow Mastic Lab ID-Version‡: 5786568-1

Sample Layers Asbestos ContentYellow Mastic NDGray Carpet ND

Composite Non-Asbestos Content: 45% Synthetic Fibers< 1% Cellulose

Sample Composite Homogeneity: Moderate

Location: 36, PLM-36 Gray Carpet & Yellow Mastic Lab ID-Version‡: 5786569-1

Sample Layers Asbestos ContentYellow Mastic NDGray Carpet ND

Composite Non-Asbestos Content: 45% Synthetic Fibers< 1% Cellulose

Sample Composite Homogeneity: Moderate

EMLab ID: 1271143, Page 11 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 37, PLM-37 Black Felt - Between Slab and Wood Lab ID-Version‡: 5786570-1

Sample Layers Asbestos ContentBlack Felt NDComposite Non-Asbestos Content: 60% CelluloseSample Composite Homogeneity: Good

Location: 38, PLM-38 Black Felt - Between Slab and Wood Lab ID-Version‡: 5786571-1

Sample Layers Asbestos ContentBlack Felt NDComposite Non-Asbestos Content: 60% CelluloseSample Composite Homogeneity: Good

Location: 39, PLM-39 Black Felt - Between Slab and Wood Lab ID-Version‡: 5786572-1

Sample Layers Asbestos ContentBlack Felt NDComposite Non-Asbestos Content: 60% CelluloseSample Composite Homogeneity: Good

Location: 40, PLM-40 Yellow Wood Stage Mastic Lab ID-Version‡: 5786573-1

Sample Layers Asbestos ContentYellow Mastic ND

Composite Non-Asbestos Content: 2% CelluloseSample Composite Homogeneity: Good

EMLab ID: 1271143, Page 12 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

EMLab P&K1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: Dominion Environmental Consultants, Inc.C/O: Mr. Christopher WebsterRe: NV1421.04; Central Church

Date of Sampling: 10-01-2014Date of Receipt: 10-02-2014Date of Report: 10-02-2014

ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 41, PLM-41 Yellow Wood Stage Mastic Lab ID-Version‡: 5786574-1

Sample Layers Asbestos ContentYellow Mastic ND

Composite Non-Asbestos Content: 2% CelluloseSample Composite Homogeneity: Good

Location: 42, PLM-42 Yellow Wood Stage Mastic Lab ID-Version‡: 5786575-1

Sample Layers Asbestos ContentYellow Mastic ND

Composite Non-Asbestos Content: 2% CelluloseSample Composite Homogeneity: Good

EMLab ID: 1271143, Page 13 of 13Aerotech Laboratories, Inc

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

SECTION 7 ♦

EPA NESHAP NOTIFICATION INFORMATION SHEET

EPA NESHAP NOTIFICATION INFORMATION SHEET

Central Christian Church 1001 New Beginnings Drive Henderson, Nevada 89011

Property Owner Central Christian Church

Inspection Date October 1, 2014 Laboratory EMLab P & K, LLC. Number of Samples 42 PLM Date Analyzed October 2, 2014 Inspector Certification Name Christopher Webster

Training Provider The Asbestos Institute AHERA Certificate Number F 9962 Expiration Date April 4, 2015

The building materials sampled were reported by laboratory PLM analysis to be “none detected” for asbestos.

SECTION 8

GENERAL NOTES/EXCLUSIONS

GENERAL NOTES/EXCLUSIONS • Mr. Justin Wallin, with Wallin Construction LLC, outlined the areas and the materials currently disturbed

or scheduled to be disturbed during the renovation activities, instructed Dominion to only collect bulk samples of the outlined materials, and to have those samples analyzed for the presence of asbestos fibers by a qualified laboratory.

• This was a limited inspection and those areas not specifically identified in this report were not inspected;

nor any area outside the specific area described herein. • If any un-sampled suspect building materials are discovered during the renovation activities, those

materials should be properly sampled by a certified inspector and analyzed by a qualified laboratory prior to their disturbance.

SECTION 9

INSPECTOR CERTIFICATIONS

SECTION 10

LABORATORY CERTIFICATIONS