© 2003 American Standard Inc. All rights reserved. Service Alert RTAA/RTWA/RTUA Compressor Modules (MCSP) Order No: RTAA-SVA16A-EN Date: May 2003 This service alert contains preliminary information. An investigation is underway to verify the situation. If confirmed, we will issue a service bulletin with full details and any required corrective action. Regardless of the outcome, this service alert is cancelled 60 days from the issue date. Introduction The purpose of this alert is to advise customers of a problem associated with the Compressor (MCSP) module on RTAA/RTWA/RTUA 70-125 ton units. The action described in this alert is not being taken to address a safety concern. Discussion There were a number MCSP modules (X13650477-11 Rev. M) produced with reversed electrical components. The reversed components will be found in locations C35, C36, C39, C40, C43 and C44 in the current input circuits, C53 in the high pressure cutout input and C55 in the winding temp input. These capacitors will cause diagnostics such as High Pressure Cutout, Phase Loss and Phase Unbalance. These diagnostics will occur at power-up and will not clear or reset. To: Service Managers Parts Center Managers Field Service Representatives - FSR From: Jackie Sopko - Trane Pueblo

rtaa-sva16a

Embed Size (px)

DESCRIPTION

rtaa-sva16aFFF

Citation preview

Page 1: rtaa-sva16a

© 2003 American Standard Inc. All rights reserved.

ServiceAlert

RTAA/RTWA/RTUACompressor Modules (MCSP)

Order No: RTAA-SVA16A-EN Date: May 2003

This service alert contains preliminary information. An investigation is underway to verify the situation. If confirmed, we will issue a service bulletin with full details and any required corrective action. Regardless of the outcome, this service alert is cancelled 60 days from the issue date.

IntroductionThe purpose of this alert is to advise customers of a problem associated with the Compressor (MCSP) module on RTAA/RTWA/RTUA 70-125 ton units. The action described in this alert is not being taken to address a safety concern.

DiscussionThere were a number MCSP modules (X13650477-11 Rev. M) produced with reversed electrical components. The reversed components will be found in locations C35, C36, C39, C40, C43 and C44 in the current input circuits, C53 in the high pressure cutout input and C55 in the winding temp input.

These capacitors will cause diagnostics such as High Pressure Cutout, Phase Loss and Phase Unbalance. These diagnostics will occur at power-up and will not clear or reset.

To: Service Managers

Parts Center Managers

Field Service Representatives - FSR

From: Jackie Sopko - Trane Pueblo

Page 2: rtaa-sva16a

Trane has a policy of continuous product data and product improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this bulletin.

Literature Order Number RTAA-SVA16A-EN

File Number SL-RF-RLC-RTAA-SVA16A-EN-0503

Supersedes New

Stocking Location IElectronic Only

Trane

A business of American Standard Companieswww.trane.com

For more information contact your local district office or e-mail us at [email protected]

Products IncludedAll RTWA/RTUA and RTAA 70-125 ton units built between June 2002 (U02F*****) and December 2002 (U02M*****) may have the reversed electrical components installed in the compressor modules.

QuestionsContact the Product Technical Service department in Pueblo, Colorado with questions regarding this Service Alert. They can be reached at [email protected] or 888-244-5537.