42
S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Embed Size (px)

Citation preview

Page 1: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

S

Automation and Drives

INAMICS S120

Cabinet Modules – System Presentation

A&D LD IM TS, M. Finger

Page 2: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 2 © Siemens AG 2006 - We reserve the right to make

changes

Line Module

Motor Module

24-VTerminals

adaptor

DC link bracket

24-VPlug-in jumper

Motor Module

Rearranged DC link busbars

In small ones….

S120 Cabinet Modules – The idea

Simple plug-in, reliable connectionsSimple, secure DC link conductor bars

Page 3: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 3 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules – The idea

Motor Module

Motor Module

…as well as in large onesMotor Module

LineModule

Simple plug-in, reliable connectionsSimple, secure DC link conductor bars

Page 4: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 4 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules – The idea

The idea:

- Creating a new standard for industry which is based on the new generation- Quality ensured by type tests- Standardised HW interfaces- Minimizing variance- Customer specific group of options

Outcome:

- Type tested, MLFB standard units - High quality ensured by series production - Easy to maintain design - Footprint optimisation

Page 5: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 5 © Siemens AG 2006 - We reserve the right to make

changes

Connector-bridge for DC link

S120 Cabinet Modules, Operation: Standardized interfaces

Small cabinets – simple operation.

During development the chain of utilization was adhered to: Assembly Commissioning Service

Simple operation, simple assembly

Page 6: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 6 © Siemens AG 2006 - We reserve the right to make

changes

Plug-in jumper for auxiliary busbar

S120 Cabinet Modules, Operation: Standardized interfaces

Simple and quick wiring

Auxiliary busbar system

Page 7: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 7 © Siemens AG 2006 - We reserve the right to make

changes

Cabinet internal connections

Connections on the

customer side

X1 X2 X4 X5

X3

X10

The terminals -X1, -X2 and -X3 are for internal use only.

The terminal strip contains: With CU320 (K90) Without CU320 Terminal strip

- 8 digital inputs X -X4, -X5

- 8 bidirectional in/outputs ( DI/DO) X -X4, -X5

- Temperature sensor terminal ( KTY84) X -X5

- Auxiliary voltage output +24 V X X -X10

- Terminals for „STO“ and „SS1” X X -X4

S120 Cabinet Modules, Operation: Customer‘s terminal strip

Each Motor Module Chassis as well as modules with Control Units have a standardized interface within the terminal area according to the requirements of the system integration.

Page 8: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 8 © Siemens AG 2006 - We reserve the right to make

changes

Each option has a fixed position

S120 Cabinet Modules, Interfaces: Options

Options: Type tested and standardized

Page 9: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 9 © Siemens AG 2006 - We reserve the right to make

changes

What Cabinet Modules are available?

Line Connection Modules Line Infeed Modules

Basic Line Module Smart Line Module Active Line Module + Active Interface Module

Motor Modules - Chassis format Motor Modules - Booksize format Central Braking Modules Cabinets for the auxiliary power supply Motor-side filter/reactor cabinets

S120 Cabinet Modules – Overview

Page 10: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 10 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules Basics of Cabinet

Basic layout of Cabinet Modules

Cabinet system Rittal TS8, 2200 mm high

Degree of protection IP20 PE bars (nickel-plated) Coating RAL 7035 Bottom panel (divided into three) Air duct through the door Without side panels

Without DC busbars (mandatory – option) Without Control Unit CU320 Auxiliary busbar system (6 phase) underneath in cabinet Each Cabinet Module is supplied separately (individual order)

Customer‘s documents specific to the order

Page 11: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 11 © Siemens AG 2006 - We reserve the right to make

changes

Mo

tors

SINAMICS S120 Cabinet Modules

3 AC

main

s

System components SINAMICS S120 Chassis and Cabinet Modules

Line Modules:

ALM, SLM, BLM

Components on the line side

Current supply

DC link components

Control Units

Motor Modules

SINAMICS S120 Chassis and system components

Page 12: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 12 © Siemens AG 2006 - We reserve the right to make

changes

Overview - SINAMICS S120 Cabinet Modules

Typical plant/system configuration

Lin

e C

on

nec

tio

n

Mo

du

le

Lin

e In

feed

Au

xilia

ry P

ow

er

Su

pp

ly M

od

ule

Mo

tor

Mo

du

les

- C

has

sis

- B

oo

ksiz

e

Mo

tor

Mo

du

les

- C

has

sis

- B

oo

ksiz

e

Ou

tpu

t sw

itch

Cen

tral

Bra

kin

g

Mo

du

le

CU

320

/ Sim

oti

on

ce

ntr

ally

arr

ang

ed

Can be variably combined just as the plant/system demands it

Page 13: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 13 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Infeed: Basic Line Module (BLM)

Overview, Cabinet Module versions

Auxiliary Power

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Page 14: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 14 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Infeed: Basic Line Module (BLM)Order number Frame-

size Infeed power

rating DC link current rating Infeed current

rating

IN

Weight

Standard design

Dimensions

IP20 2)

W x D x H

kW A A kg mm

Supply voltage

380–480V

6SL3730-1TE34-2AA0 FB 200 420 365 166 400 x 600 x 2200

6SL3730-1TE35-3AA0 FB 250 530 460 166 400 x 600 x 2200

6SL3730-1TE38-2AA0 FB 400 820 710 166 400 x 600 x 2200

6SL3730-1TE41-2AA0 GB 560 1200 1010 320 400 x 600 x 2200

6SL3730-1TE41-2BA0 GB 560 1200 1010 440 600 x 600 x 2200

6SL3730-1TE41-2BC0 GB 560 1200 1010 480 600 x 600 x 2200

6SL3730-1TE41-5AA0 GB 710 1500 1265 320 400 x 600 x 2200

6SL3730-1TE41-5BA0 GB 710 1500 1265 440 600 x 600 x 2200

6SL3730-1TE41-5BC0 GB 710 1500 1265 480 600 x 600 x 2200

6SL3730-1TE41-8AA0 GD 900 1880 1630 320 400 x 600 x 2200

6SL3730-1TE41-8BA0 GD 900 1880 1630 440 600 x 600 x 2200

6SL3730-1TE41-8BC0 GD 900 1880 1630 480 600 x 600 x 2200

Supply voltage

660 – 690 V

6SL3730-1TH33-0AA0 FB 250 300 260 166 400 x 600 x 2200

6SL3730-1TH34-3AA0 FB 355 430 375 166 400 x 600 x 2200

6SL3730-1TH36-8AA0 FB 500 680 575 166 400 x 600 x 2200

6SL3730-1TH41-1AA0 GB 900 1100 925 320 400 x 600 x 2200

6SL3730-1TH41-1BA0 GB 900 1100 925 440 600 x 600 x 2200

6SL3730-1TH41-1BC0 GB 900 1100 925 480 600 x 600 x 2200

6SL3730-1TH41-4AA0 GB 1100 1400 1180 320 400 x 600 x 2200

6SL3730-1TH41-4BA0 GB 1100 1400 1180 440 600 x 600 x 2200

6SL3730-1TH41-4BC0 GB 1100 1400 1180 480 600 x 600 x 2200

6SL3730-1TH41-8AA0 GD 1500 1880 1580 320 400 x 600 x 2200

6SL3730-1TH41-8BA0 GD 1500 1880 1580 440 600 x 600 x 2200

6SL3730-1TH41-8BC0 GD 1500 1880 1580 480 600 x 600 x 2200

Intended for parallel connection

Page 15: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 15 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Infeed: Smart Line Module (SLM)

Overview, Cabinet Module versions

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Auxiliary Power

Page 16: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 16 © Siemens AG 2006 - We reserve the right to make

changes

Order No. Frame size

Rated power

Rated DC link current Line current

Weight,

standard version

Dimensions

IP20 2)

W x D x H

[kW] [A] [A] [kg] [mm]

Supply voltage 380–480V

6SL3730-6TE35-3AA0 GX 250 550 463 270 400 x 600 x 2200

6SL3730-6TE37-3AA0 GX 355 735 614 270 400 x 600 x 2200

6SL3730-6TE41-1AA0 HX 500 1050 883 490 600 x 600 x 2200

6SL3730-6TE41-1BA0 HX 500 1050 883 490 600 x 600 x 2200

6SL3730-6TE41-1BC0 HX 500 1050 883 490 600 x 600 x 2200

6SL3730-6TE41-3AA0 JX 630 1300 1093 775 800 x 600 x 2200

6SL3730-6TE41-3BA0 JX 630 1300 1093 775 800 x 600 x 2200

6SL3730-6TE41-3BC0 JX 630 1300 1093 775 800 x 600 x 2200

6SL3730-6TE41-7AA0 JX 800 1700 1430 775 800 x 600 x 2200

6SL3730-6TE41-7BA0 JX 800 1700 1430 775 800 x 600 x 2200

6SL3730-6TE41-7BC0 JX 800 1700 1430 775 800 x 600 x 2200

Supply voltage 660 – 690 V

6SL3730-6TG35-5AA0 GX 450 550 463 270 400 x 600 x 2200

6SL3730-6TG38-8AA0 HX 710 900 757 550 600 x 600 x 2200

6SL3730-6TG38-8BA0 HX 710 900 757 550 600 x 600 x 2200

6SL3730-6TG38-8BC0 HX 710 900 757 550 600 x 600 x 2200

6SL3730-6TG41-2AA0 JX 1000 1200 1009 795 800 x 600 x 2200

6SL3730-6TG41-2BA0 JX 1000 1200 1009 795 800 x 600 x 2200

6SL3730-6TG41-2BC0 JX 1000 1200 1009 795 800 x 600 x 2200

6SL3730-6TG41-7AA0 JX 1400 1700 1430 795 800 x 600 x 2200

6SL3730-6TG41-7BA0 JX 1400 1700 1430 795 800 x 600 x 2200

6SL3730-6TG41-7BC0 JX 1400 1700 1430 795 800 x 600 x 2200

Intended for parallel connection

S120 Cabinet Modules - Infeed: Smart Line Module (SLM)

Page 17: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 17 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Infeed: Active Infeed = Active Line Module + Active Interface Module

Overview, Cabinet Module versions

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Auxiliary Power

Page 18: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 18 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Infeed: Active Line Module + Active Interface Module (ALM)

Dimensions

IP20

Order No. Frame size

Rated infeed/regenerative feedback power

Rated DC link current Rated infeed/regenerative feedback current

IN

Weight,

standard version W x D x H

kW A A kg mm

Supply voltage 380 – 480 V

6SL3730-7TE32-1BA0 FX+FI 132 235 210 500 800 x 600 x 2200

6SL3730-7TE32-6BA0 FX+FI 160 291 260 500 800 x 600 x 2200

6SL3730-7TE33-8BA0 GX+GI 235 425 380 640 800 x 600 x 2200

6SL3730-7TE35-0BA0 GX+GI 300 549 490 640 800 x 600 x 2200

6SL3730-7TE36-1BA0 HX+HI 380 678 605 930 1000 x 600 x 2200

6SL3730-7TE38-4BA0 HX+HI 500 940 840 930 1000 x 600 x 2200

6SL3730-7TE41-0BA0 JX+JI 630 1103 985 1360 1400 x 600 x 2200

6SL3730-7TE41-0BC0 JX+JI 630 1103 985 1360 1400 x 600 x 2200

6SL3730-7TE41-4BA0 JX+JI 900 1574 1405 1360 1400 x 600 x 2200

6SL3730-7TE41-4BC0 JX+JI 900 1574 1405 1360 1400 x 600 x 2200

Supply voltage 660 – 690 V

6SL3730-7TH35-8BA0 HX+HI 560 644 575 930 1000 x 600 x 2200

6SL3730-7TH37-4BA0 JX+JI 800 823 735 1360 1400 x 600 x 2200

6SL3730-7TH37-4BC0 JX+JI 800 823 735 1360 1400 x 600 x 2200

6SL3730-7TH41-0BA0 JX+JI 1100 1148 1025 1360 1400 x 600 x 2200

6SL3730-7TH41-0BC0 JX+JI 1100 1148 1025 1360 1400 x 600 x 2200

6SL3730-7TH41-3BA0 JX+JI 1400 1422 1270 1360 1400 x 600 x 2200

6SL3730-7TH41-3BC0 JX+JI 1400 1422 1270 1360 1400 x 600 x 2200

Intended for parallel circuit configuration (with mirrored design)

Page 19: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 19 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Motor Module: Chassis format

Overview, Cabinet Module versions

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Auxiliary Power

Page 20: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 20 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules - Motor Module: Chassis format

Order No. Frame size

Rated power

Rated DC link current

Rated output current

IN

Base load current

IL

Power to

IH

Basic load current

IH

Weight Dimensions IP20

WxDxH

kW A A A kW A

Supply voltage

380 – 480 V

6SL3720-1TE32-1AA0 FX 110 252 210 205 90 178 145 400 x 600 x 2200

6SL3720-1TE32-6AA0 FX 132 312 260 250 110 233 145 400 x 600 x 2200

6SL3720-1TE33-1AA0 GX 160 372 310 302 132 277 286 400 x 600 x 2200

6SL3720-1TE33-8AA0 GX 200 456 380 370 160 340 286 400 x 600 x 2200

6SL3720-1TE35-0AA0 GX 250 588 490 477 200 438 286 400 x 600 x 2200

6SL3720-1TE36-1AA0 HX 315 726 605 590 250 460 490 600 x 600 x 2200

6SL3720-1TE37-5AA0 HX 400 894 745 725 315 570 490 600 x 600 x 2200

6SL3720-1TE38-4AA0 HX 450 1008 840 820 400 700 490 600 x 600 x 2200

6SL3720-1TE41-0AA0 JX 560 1182 985 960 450 860 700 800 x 600 x 2200

6SL3720-1TE41-2AA0 JX 720 1512 1260 1230 560 1127 700 800 x 600 x 2200

6SL3720-1TE41-4AA0 JX 800 1686 1405 1370 720 1257 700 800 x 600 x 2200

Supply voltage

660 – 690 V

6SL3720-1TH28-5AA0 FX 75 102 85 80 55 76 145 400 x 600 x 2200

6SL3720-1TH31-0AA0 FX 90 120 100 95 75 89 145 400 x 600 x 2200

6SL3720-1TH31-2AA0 FX 110 144 120 115 90 107 145 400 x 600 x 2200

6SL3720-1TH31-5AA0 FX 132 180 150 142 110 134 145 400 x 600 x 2200

6SL3720-1TH31-8AA0 GX 160 210 175 171 132 157 286 400 x 600 x 2200

6SL3720-1TH32-2AA0 GX 200 258 215 208 160 192 286 400 x 600 x 2200

6SL3720-1TH32-6AA0 GX 250 312 260 250 200 233 286 400 x 600 x 2200

6SL3720-1TH33-3AA0 GX 315 396 330 320 250 280 286 400 x 600 x 2200

6SL3720-1TH34-1AA0 HX 400 492 410 400 315 367 490 600 x 600 x 2200

6SL3720-1TH34-7AA0 HX 450 558 465 452 400 416 490 600 x 600 x 2200

6SL3720-1TH35-8AA0 HX 560 690 575 560 450 514 490 600 x 600 x 2200

6SL3720-1TH37-4AA0 JX 710 882 735 720 560 657 700 800 x 600 x 2200

6SL3720-1TH38-1AA0 JX 800 972 810 790 720 724 700 800 x 600 x 2200

6SL3720-1TH38-8AA0 JX 900 1092 910 880 800 814 700 800 x 600 x 2200

6SL3720-1TH41-0AA0 JX 1000 1230 1025 1000 900 917 700 800 x 600 x 2200

6SL3720-1TH41-3AA0 JX 1200 1524 1270 1230 1000 1136 700 800 x 600 x 2200

Page 21: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 21 © Siemens AG 2006 - We reserve the right to make

changes

Overview, Cabinet Module versions

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Auxiliary Power

S120 Cabinet Modules - Motor Module: Booksize Base Cabinet

Page 22: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 22 © Siemens AG 2006 - We reserve the right to make

changes

Single Motor Modules For output currents up to 200A

Double Motor Modules Space-saving version for 2 motors For output currents up to 18A

100 mm50 mm 150 mm 200 mm 300 mmModule width

Supply voltageRated output current (A) 3 5 9 18 30 45 60 85 132 200 3 5 9 18Maximum output current (A) 6 10 18 36 56 85 113 141 212 282 6 10 18 36Width (mm) 50 50 50 50 100 150 150 200 300 300 50 50 50 100Height (mm)Depth (mm)Degree of protectionCoolingAmbient temperature

Internal/external air cooling, Cold Plate cooling0-40°C without derating, up to 55°C with derating

Motor ModulesSingle Double

510-720V DC

380270IP20

S120 Cabinet Modules - Motor Module: Booksize format - versions

Page 23: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 23 © Siemens AG 2006 - We reserve the right to make

changes

Motor Module

Motor Module

24-V Terminal adaptor

DC link bracket

24-V Plug in jumper

24-VConductor bars

Motor Module

DC link adaptor

DC link conductor bars

DRIVE CLiQCable

S120 Cabinet Modules - Motor Module: Booksize format – Internal interfaces

high variability = high variancehigh variability = high variance

Page 24: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 24 © Siemens AG 2006 - We reserve the right to make

changes

Motor connector cable-With crimp contacts-With screws

Motor connector cable- pre-assembled

External built-on fan

Shield connection plate

Motor connector direct with cable lugs

Result:Many components have to be taken into account

Result:Many components have to be taken into account

S120 Cabinet Modules - Motor Module: Booksize format – Internal interfaces

Page 25: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 25 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules, Design concept

Page 26: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 26 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules, Design concept: Functional safety

Zone concept:

DC-link

Power section

Output components

Electronic and customer terminals

The components used in a cabinet are influenced by different ambient/environmentconditions.

Solution: Segregation into zones allows safe and reliable operation of all components.

The strict segregation between influencing areas was a core issue when developing the Cabinet Modules.

Page 27: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 27 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules, Design concept: Functionality and engineering

Design concept:

For example Booksize Base Cabinet

These cabinets can be freely configured with Booksize-kits.All of the components and possible options are arranged within these kits.

The consequence: Engineering and handling is simplified.

Identical design with a high degree of versatility.

Page 28: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 28 © Siemens AG 2006 - We reserve the right to make

changes

Additional Cabinet Modules

AUX_CI

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

S120 Cabinet Modules – Connection to the mains:Line Connection Module

Page 29: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 29 © Siemens AG 2006 - We reserve the right to make

changes

Order No.

Frame size

Rated current Dimensions

IP20 4) IN W x D x H

A mm

Supply voltage

380-480V

6SL3700-0LE32-5AA0 FL 250 400 x 600 x 2200

6SL3700-0LE34-0AA0 FL 380 400 x 600 x 2200

6SL3700-0LE36-3AA0 GL 600 600 x 600 x 2200

6SL3700-0LE38-0AA0 HL 770 600 x 600 x 2200

6SL3700-0LE41-0AA0 JL 1000 600 x 600 x 2200

6SL3700-0LE41-3AA0 JL 1250 600 x 600 x 2200

6SL3700-0LE41-6AA0 JL 1600 600 x 600 x 2200

6SL3700-0LE42-0AA0 KL 2000 1000 x 600 x 2200

6SL3700-0LE42-0BA0 KL 2000 1000 x 600 x 2200

6SL3700-0LE42-5BA0 KL 2500 1000 x 600 x 2200

6SL3700-0LE43-2BA0 LL 3200 1000 x 600 x 2200

Supply voltage

660-690V

6SL3700-0LG32-5AA0 FL 280 400 x 600 x 2200

6SL3700-0LG34-0AA0 FL 380 400 x 600 x 2200

6SL3700-0LG36-3AA0 GL 600 600 x 600 x 2200

6SL3700-0LG38-0AA0 HL 770 600 x 600 x 2200

6SL3700-0LG41-0AA0 JL 1000 600 x 600 x 2200

6SL3700-0LG41-3AA0 JL 1250 600 x 600 x 2200

6SL3700-0LG41-6AA0 JL 1600 600 x 600 x 2200

6SL3700-0LG42-0BA0 KL 2000 1000 x 600 x 2200

6SL3700-0LG42-5BA0 KL 2500 1000 x 600 x 2200

6SL3700-0LG43-2BA0 LL 3200 1000 x 600 x 2200

FS H/J FS K/L

S120 Cabinet Modules – Connection to the mains:Line Connection Module

Page 30: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 30 © Siemens AG 2006 - We reserve the right to make

changes

Additional Cabinet Modules

AUX_CI

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

S120 Cabinet Modules – Performance support: Central Braking Module

Page 31: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 31 © Siemens AG 2006 - We reserve the right to make

changes

Braking Module in the chassis format (not identical with the Braking Module that can be mounted in the chassis)

Braking power up to 1200 kW Independent control (open-loop) Braking resistor, external

(IP20 degree of protection)

S120 Cabinet Modules – Performance support: Central Braking Module

S120 Cabinet Modules, Central Braking Modules

380V to 480V 500V to 600V 660V to 690V

Contin-uous braking power

Peak power

Contin-uous braking power

Peak power

Contin-uous braking power

Peak power

200 kW 500 kW 225 kW 550 kW 250 kW 630 kW

320 kW 1000 kW 360 kW 1100 kW 400 kW 1200 kW

Page 32: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 32 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules – Power supply:Auxiliary Power Supply Module

Additional Cabinet Modules

AUX_CI

SITOP

BLMSLMALM

Braking ModuleLCM

M

CU320 / Simotion

CU

32

0

CU

32

0

MM Chassis

MM Booksize

Page 33: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 33 © Siemens AG 2006 - We reserve the right to make

changes

Auxiliary cabinet

Central fusing/protection of the AUX power supply voltage Generates the 2-ph. 230V AC control voltage

for circuit-breakers, contactors etc. Generates the 24V auxiliary supply

for the other Cabinet Modules Fused/protected power supply

for the unit fans Fused/protected power supply for additional loads

S120 Cabinet Modules – Power supply:Auxiliary Power Supply Module

Page 34: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 34 © Siemens AG 2006 - We reserve the right to make

changes

Line supply voltage2-ph. 380 V...690 V AC

Control voltage1/N/ 230 V AC

DC voltage2x 24 V DC

Transfer point---->

-Q 3 auxiliarybusbars

-Q 4terminal strip -

X 45

-F 21auxiliarybusbars

-F 22terminal strip -

X47Auxiliarybusbars

6SL3700-

0MX14-0AA0 63 A 50 A 6 A 8 A 20 A

0MX16-3AA0 80 A 63 A 10 A 10 A 40 A

0MX21-0AA0 100 A 80 A 10 A 10 A 80 A

0MX21-4AA0 100 A 80 A 20 A 20 A 80 A

Line supply voltage380-690 V

2-ph. 230 V AC

Auxiliary power rail

Customer terminals-X45

Customer terminals-X47

SITOPCustomer terminals-X46

S120 Cabinet Modules – Power supply:Auxiliary Power Supply Module

Page 35: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 35 © Siemens AG 2006 - We reserve the right to make

changes

Man

dat

ory

op

tio

nD

ocu

men

tati

on

General options

The options for the S120 Cabinet Modules are sub-divided into general options and module-specific options.

Options

Code Brief option description

L51 Holder for the arc detector

L55 Cabinet anti-condensation heating

M06 Base 100 mm high, RAL 7022 M07 Cable marshalling space 200 mm high, RAL 7035

M21 Degree of protection IP21

M23 Degree of protection IP23 M26 Side panel, mounted at the right

M27 Side panel, mounted at the left

M54 Degree of protection IP54 M59 Cabinet doors closed, air entry from below through an opening in the base plate (floor)

M60 Additional shock hazard protection M80 DC busbars (Id = 1170 A, 1x 60 x 10 mm)

M81 DC busbars (Id = 1500 A, 1x 80 x 10 mm)

M82 DC busbars (Id = 1840 A, 1x 100 x 10 mm) M83 DC busbars (Id = 2150 A, 2x 60 x 10 mm)

M84 DC busbars (Id = 2730 A, 2x 80 x 10 mm)

M85 DC busbars (Id = 3320 A, 2x 100 x 10 mm) M86 DC busbars (Id = 3720 A, 3x 80 x 10 mm)

M87 DC busbars (Id = 4480 A, 3x 100 x 10 mm)

M90 Crane transport hoisting lugs (top mounted) Y09 Special cabinet paint finish

Y11 Assembly of Cabinet Modules in the factory to create transport units

Y31 Labeling plate for plant identification (single-line, 40x80 mm) Y32 Labeling plate for plant identification (two-line, 40x180 mm)

Y33 Labeling plate for plant identification (four-line, 40 x 180 mm)

D02 Customer documentation (circuit diagram, terminal diagram, layout diagram) in DXF format

D14 Preliminary supply of the Equipment Manual (PDF format)

D58 Documentation in English / French

D60 Documentation in English / Spanish D80 Documentation in English / Italian

D99 No documentation T58 Rating plate data in English / French T60 Rating plate data in English / Spanish

T80 Rating plate data in English / Italian

Page 36: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 36 © Siemens AG 2006 - We reserve the right to make

changes

LCM

Motor Module_C

Module-specific options

Options

Code Brief option description

L13 Main contactor (for Line Connection Modules ¡Â800 A)

L23 Line reactor 2 % for Basic Line Modules

L25 Circuit-breaker, withdrawal type instead of fixed-mounted circuit-breaker (I >800 A)

L41 Current transformer in front of the main switch

L42 Line Connection Module for Active Infeed Modules

L43 Line Connection Module for Basic Line Modules

L45 Emergency Stop pushbutton in the cabinet door

L46 Grounding breaker in front of the circuit-breaker

L47 Grounding breaker after the circuit-breaker

L51 Holder for arc detector (being prepared)

L55 Anti-condensation heating for the cabinet

Code Brief option description

K08 Advanced Operator Panel AOP30, mounted in the cabinet doors

K46 Sensor Module Cabinet-Mounted SMC10

K48 Sensor Module Cabinet-Mounted SMC20

K50 Sensor Module Cabinet-Mounted SMC30

K75 Second auxiliary power busbar system

K80 Terminal module to control the "Safe Torque Off" function

K90 Control Unit CU320 with associated CompactFlash Card without performance expansion

K91 Control Unit CU320 with associated CompactFlash Card with performance expansion 1

L37 DC coupling incl. pre-charging of the associated DC link capacitors

L55 Cabinet anti-condensation heating

L61 Braking unit [braking chopper] 25 / 125 kW

L62 Braking unit [braking chopper] 50 / 250 kW

M70 EMC shield rail

Page 37: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 37 © Siemens AG 2006 - We reserve the right to make

changes

I 0

S120 Cabinet Modules, Special hardware options: Example: DC coupling

Advantage: Simple and more reliable operation (without maloperation).Advantage: Simple and more reliable operation (without maloperation).

The power unit software checks for the voltage gradient and the voltage magnitude of the DC link. No danger of „overrunning“ the preloading when irregularities occur.

Three-stage circuit breaker with two switch positions (0 – 1)0: OFF: Switch contacts are open1: Preloading: Preloading resistance is switched-in. Preloading is completed in the shortest time.

Operation: When the inverter‘s ON Signal is activated it will be automatically switched to the third position.

Page 38: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 38 © Siemens AG 2006 - We reserve the right to make

changes

S120 Cabinet Modules, Special options: Everything is possible

Variability is our strength !Variability is our strength !

Example:Booksize cabinets made to order

Application solution:The standard cannot meet every requirement.Should requirements exist which exceed our standard, then the requests for assembly can be carried out by using the regular cabinets as a basis and by using known assembly components.Our application specialists will get in touch with you.

Application solution:The standard cannot meet every requirement.Should requirements exist which exceed our standard, then the requests for assembly can be carried out by using the regular cabinets as a basis and by using known assembly components.Our application specialists will get in touch with you.

Page 39: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 39 © Siemens AG 2006 - We reserve the right to make

changes

Catalog D21.3CM, preliminary Flyer S120 Cabinet Modules SINAMICS Engineering Manual

Information material

Page 40: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 40 © Siemens AG 2006 - We reserve the right to make

changes

Highlights (1/2)

Extremely compact design (optimized footprint) Type tested units which match one another

Defined interfaces for power connections and auxiliary supply permit almost any plant/system configuration to be created

Extensive range of options allows tailored multi-motor drives to be created

Short delivery times through Modules that can be ordered by specifying an

Order No. [MLFB] High degree of standardization

Page 41: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 41 © Siemens AG 2006 - We reserve the right to make

changes

Highlights (2/2)

Increased operational safety and reliability in comparison to normal manufacturing by type tested Cabinet Modules

Order-specific hardware engineering is significantly reduced

Significantly lower logistical costs for order administration for the orderer and the factory

Every Cabinet Module has a number referred to the particular order. This means that an individual list of spare parts can be generated using SparesOnWeb

Page 42: S Automation and Drives INAMICS S120 Cabinet Modules – System Presentation A&D LD IM TS, M. Finger

Automation and Drives

SINAMICS S120 Cabinet Modules

S120 Cabinet Modules – System Presentation 04/2007, Page 42 © Siemens AG 2006 - We reserve the right to make

changes

SINAMICS S120 Cabinet Modules

1. Specify/purchase individual Cabinet Modules

2. OPTION:

Combine cabinet modules in transport sections.

Individual drawings for each cabinet – no interconnections

3. OPTION:

Engineering of line-up with interconnections etc.

Drawings for line-up

Individual drawings for each cabinet – no interconnections