SebaKMT · Dr.-Herbert-Iann-Str. 6 · 96148 Baunach/Germany · Tel. +49(0) 95 44 - 6 80 Fax +49(0) 95 44 - 22 73 · [email protected] · www.sebakmt.com ISO 9001:2008 Technical data subject to change without notice. LFT_OWTS M 60_eng_2011_04 sebaKMT is a registered trademark of the sebaKMT group OWTS M 60 Partial discharge Test and Fault Location System Benefits PD Measurement by means of DAC similar to nominal net frequency Online processing for complex PD-Diagnosis Portable test system, compact design and low weight Integrated tan δ - measurement Description The oscillating wave test system OWTS is used to identify, evaluate and locate partial discharge (PD) faults in a cable insulation and accessories in all types of medium voltage cables. The system consists of a notebook as a WLAN control unit and a HV unit. The HV unit contains a HV source and a resonance inductor with an integrated electronic switch to generate the AC test voltage. The HV divider and an em- bedded controller for the digital data acquisition and PD signal processing is integrated. The storage, analysis and evaluation of the PD signals takes place in the notebook and can be done either on site or in the office. The PD fault location is based on the time domain reflection method. For the PD diagnosis the test object is charged to the pre- selected peak value by a HV source within a couple of seconds and afterwards shorted with an electronic switch via a resonance coil. Thus a sinusoidal oscillating AC voltage with low damping is created (DAC). The frequency is fixed in a range from 50 Hz to several 100 Hz, depending on the capacitance of the test object. Since the frequency of the test voltage is close to nominal ser- vice conditions, all measured PD activities can be effectively evaluated. The oscillating voltage energizes the test object only for a few 100 ms and therefore cause no long-term influences. The PD extinction voltage and the tan δ-value can be easily determined due to the decaying amplitude of the test voltage. Critical PD levels responsible for the future status of the cable insulation are an important criteria in the evaluation. The analysis and evaluation of the typical PD parameter as well as the PD fault location supports the Asset Management for reliable decision criteria for maintenance- or replacement activities. Features PD diagnosis by means of damped AC voltage (DAC) PD level measurement according to IEC 60270 Automatic adjustment of the bandwidth of the measurement circuit for optimised signal detection Automatic calibration mode with joint location feature PC with WIN XP and WLAN for system control Statistical PD fault acquisition, online processing Menu-driven unit to operate the test sequence Portable design, low weight, easy set-up on-site Scope of delivery HV unit Notebook with WLAN connection to the HV unit Safety-Box with HV ON/OFF; Emergency push button and key switch Accessory bag Operating manual 5 m HV test lead; power supply- and grounding cable OWTS Explorer package, 2 Dongle CD-ROM Calibrator Additional capacitor Technical Data Max. DAC output- voltage 60 kVpeak / 42 kVrms DAC frequency range 50 Hz … 800 Hz Capacitance range 0.025 μF … 4 μF HV charging current 7 mA PD measuring range 1 pC … 100 nC PD level detection acc. to IEC 60270 Bandwidth for PD- localisation 150 kHz … 45 MHz Dissipation factor tan δ 0.1 % … 10 % Power supply 110 … 240 V-AC, 50 … 60 Hz Operating temperature -10 °C … +40 °C Weight app. 80 kg Components Unit 1 Ø: 650 mm, H: 970 mm Unit 2 Notebook app. 2 kg

SEBA KMT OWTS M 60

Embed Size (px)

Citation preview

Page 1: SEBA KMT OWTS M 60

SebaKMT · Dr.-Herbert-Iann-Str. 6 · 96148 Baunach/Germany · Tel. +49(0) 95 44 - 6 80 Fax +49(0) 95 44 - 22 73 · [email protected] · www.sebakmt.com ISO 9001:2008 Technical data subject to change without notice.

LFT_OWTS M 60_eng_2011_04

seb

aKM

T is

a r

egis

tere

d tr

adem

ark

of th

e se

baK

MT

grou

p

OWTS M 60Partial discharge Test and Fault Location System

Benefi ts PD Measurement by means of DAC similar to nominal net frequency

Online processing for complex PD-Diagnosis

Portable test system, compact design and low weight

Integrated tan δ - measurement

Description

The oscillating wave test system OWTS is used to identify, evaluate and locate partial discharge (PD) faults in a cable insulation and accessories in all types of medium voltage cables.

The system consists of a notebook as a WLAN control unit and a HV unit. The HV unit contains a HV source and a resonance inductor with an integrated electronic switch to generate the AC test voltage. The HV divider and an em-bedded controller for the digital data acquisition and PD signal processing is integrated. The storage, analysis and evaluation of the PD signals takes place in the notebook and can be done either on site or in the offi ce. The PD fault location is based on the time domain refl ection method.

For the PD diagnosis the test object is charged to the pre-selected peak value by a HV source within a couple of seconds and afterwards shorted with an electronic switch via a resonance coil. Thus a sinusoidal oscillating AC voltage with low damping is created (DAC). The frequency is fi xed in a range from 50 Hz to several 100 Hz, depending on the capacitance of the test object.

Since the frequency of the test voltage is close to nominal ser-vice conditions, all measured PD activities can be effectively evaluated.

The oscillating voltage energizes the test object only for a few 100 ms and therefore cause no long-term infl uences.

The PD extinction voltage and the tan δ-value can be easily determined due to the decaying amplitude of the test voltage. Critical PD levels responsible for the future status of the cable insulation are an important criteria in the evaluation.

The analysis and evaluation of the typical PD parameter as well as the PD fault location supports the Asset Management for reliable decision criteria for maintenance- or replacement activities.

Features

PD diagnosis by means of damped AC voltage (DAC) PD level measurement according to IEC 60270 Automatic adjustment of the bandwidth of the

measurement circuit for optimised signal detection Automatic calibration mode with joint location feature PC with WIN XP and WLAN for system control Statistical PD fault acquisition, online processing Menu-driven unit to operate the test sequence Portable design, low weight, easy set-up on-site

Scope of delivery

HV unit Notebook with WLAN connection to the HV unit Safety-Box with HV ON/OFF; Emergency push button

and key switch Accessory bag Operating manual 5 m HV test lead; power supply- and grounding cable OWTS Explorer package, 2 Dongle CD-ROM Calibrator Additional capacitor

Technical Data Max. DAC output-voltage

60 kVpeak / 42 kVrms

DAC frequency range 50 Hz … 800 HzCapacitance range 0.025 µF … 4 µFHV charging current 7 mAPD measuring range 1 pC … 100 nCPD level detection acc. to IEC 60270Bandwidth for PD-localisation

150 kHz … 45 MHz

Dissipation factor tan δ 0.1 % … 10 %Power supply 110 … 240 V-AC, 50 … 60 HzOperating temperature -10 °C … +40 °CWeight app. 80 kgComponentsUnit 1 Ø: 650 mm, H: 970 mmUnit 2 Notebook app. 2 kg