76
Second Revision No. 1-NFPA 79-2017 [ Global Comment ] *************GLOBAL INSTRUCTION - COMP: See Mark's note for clarity*************** Remove all parenthetical terms of (plug/socket) and any variation of (plug and socket outlets)etc. in Sections 3.3.96, 5.3.3.2(1), 5.3.5.1(2), 6.4.2(5), 11.2.1.8, 13.1.2.1, 13.4.5, 13.4.5.1, 13.4.5.2, 13.4.5.3, 13.4.5.4, 13.4.5.5, 13.4.5.6, 13.4.5.7, 13.4.6, 15.1.1(4), and A.11.2.1.7 The parenthetical terms to remove are (plug/socket), (plug/socket combination), (plugs)- (socket outlets), (socket-outlets) and (plug and socket outlets) in the body of the document. Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle." Additionally, the Committee removes the definition of the term “socket” and the associated note from Chapter 3, and the annex information in A.3.3.9 and A.3.3.82. Remove completly A.3.3.9, A.3.3.82 Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle." Submitter Information Verification Submitter Full Name: Mark Cloutier Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jan 10 12:46:45 EST 2017 Committee Statement Committee Statement: The Committee removes the parenthetical terms (plug/socket), (plug/socket combination), (plugs)-(socket outlets), (socket-outlets) and (plug and socket outlets) from the body of the document. Additionally the Committee removes the definition of the term “socket” and the associate note from Chapter 3, the annex information in A.3.3.9 and A.3.3.82 and the symbols and descriptions related to “plug and socket” in Figure D.1q. Also Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle." These actions are consistent with the actions taken in the 2015 cycle and during the First Draft to remove the parenthetical terms from the body of the document and provide correlation information in Annex J. See the actions taken in SR 1. Response Message: Public Comment No. 39-NFPA 79-2016 [Section No. A.3.3.9] Public Comment No. 49-NFPA 79-2016 [Section No. 6.4.2] Public Comment No. 52-NFPA 79-2016 [Section No. 13.4.5] Public Comment No. 54-NFPA 79-2016 [Section No. A.11.2.1.7] Public Comment No. 59-NFPA 79-2016 [Section No. 13.4.6] Public Comment No. 58-NFPA 79-2016 [Section No. 13.1.2.1] Public Comment No. 53-NFPA 79-2016 [Section No. A.3.3.82]

Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Second Revision No. 1-NFPA 79-2017 [ Global Comment ]

*************GLOBAL INSTRUCTION - COMP: See Mark's note for clarity***************

Remove all parenthetical terms of (plug/socket) and any variation of (plug and socket outlets)etc. in Sections 3.3.96, 5.3.3.2(1), 5.3.5.1(2), 6.4.2(5), 11.2.1.8, 13.1.2.1, 13.4.5, 13.4.5.1, 13.4.5.2, 13.4.5.3, 13.4.5.4, 13.4.5.5, 13.4.5.6, 13.4.5.7, 13.4.6, 15.1.1(4), and A.11.2.1.7

The parenthetical terms to remove are (plug/socket), (plug/socket combination), (plugs)-(socket outlets), (socket-outlets) and (plug and socket outlets) in the body of the document. Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle." Additionally, the Committee removes the definition of the term “socket” and the associated note from Chapter 3, and the annex information in A.3.3.9 and A.3.3.82.

Remove completly A.3.3.9, A.3.3.82

Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle."

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 10 12:46:45 EST 2017

Committee Statement

Committee Statement:

The Committee removes the parenthetical terms (plug/socket), (plug/socket combination), (plugs)-(socket outlets), (socket-outlets) and (plug and socket outlets) from the body of the document. Additionally the Committee removes the definition of the term “socket” and the associate note from Chapter 3, the annex information in A.3.3.9 and A.3.3.82 and the symbols and descriptions related to “plug and socket” in Figure D.1q. Also Delete 3.3.9 "Attachment Plug (Plug Cap) (Plug)" and 3.3.82 "Receptacle." These actions are consistent with the actions taken in the 2015 cycle and during the First Draft to remove the parenthetical terms from the body of the document and provide correlation information in Annex J. See the actions taken in SR 1.

Response Message:

Public Comment No. 39-NFPA 79-2016 [Section No. A.3.3.9] Public Comment No. 49-NFPA 79-2016 [Section No. 6.4.2] Public Comment No. 52-NFPA 79-2016 [Section No. 13.4.5] Public Comment No. 54-NFPA 79-2016 [Section No. A.11.2.1.7] Public Comment No. 59-NFPA 79-2016 [Section No. 13.4.6] Public Comment No. 58-NFPA 79-2016 [Section No. 13.1.2.1] Public Comment No. 53-NFPA 79-2016 [Section No. A.3.3.82]

Page 2: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Public Comment No. 45-NFPA 79-2016 [Section No. 3.3.96] Public Comment No. 47-NFPA 79-2016 [Section No. 5.3.5.1] Public Comment No. 48-NFPA 79-2016 [Section No. 3.3.96] Public Comment No. 50-NFPA 79-2016 [Section No. 11.2.1.8] Public Comment No. 60-NFPA 79-2016 [Section No. 15.1.1]

Second Revision No. 59-NFPA 79-2017 [ Global Comment ]

The term 'plainly' should be removed before 'visible' throughout the standard.

Submitter Information Verification

Submitter Full Name: Sonia Barbosa

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Mar 17 11:31:55 EDT 2017

Committee Statement

Committee Statement:

When there is a visibility requirement within a section it must be judged based on the particular application. Using either 'plainly' before 'visible' or 'clearly' before 'visible' does not help with enforcing or interpreting a visibility requirement. Whether something is 'visible' can only be judged on the specific application.

Response Message:

Second Revision No. 54-NFPA 79-2017 [ Detail ]

********INSTRUCTION********

This detail is on SR-53 Section 5.3.1.4 to revise Exception No. 1

Exception No.1: An interlock forwithin the control enclosure shall not be required where devices other than the handles of circuit breakers or switches are guarded by a dead-front cover and the use of a key or tool is necessaryrequired for opening the supply circuit disconnecting means enclosure to access exposed live parts. A safety sign shall be provided in accordance with Section 16.2.

Submitter Information Verification

Page 3: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 15:11:22 EST 2017

Committee Statement

Committee Statement:

The revised text clarifies the required construction of the equipment to use this exception. This detail is on SR-53 Section 5.3.1.4 to revise Exception No.1.

Response Message:

Public Comment No. 31-NFPA 79-2016 [Section No. 5.3.1.4] Public Comment No. 19-NFPA 79-2016 [Section No. 5.3.1.4]

Second Revision No. 55-NFPA 79-2017 [ Detail ]

*************INSTRUCTION**********

This detail is to revise the text in Section 5.3.3.1 (3) on SR-53

5.3.3.1

(3) Be provided with a permanent means permitting it to be locked in the off (open) position only (e.g., by padlocks), independent of the door or cover position. that also prevents When so locked, remote as well as local closing into the ( on ) position shall be prevented.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 15:18:58 EST 2017

Committee Statement

Committee Statement:

The Committee restores "when so locked" to more clearly indicate that the preventing of closing only occurs when locked. This is a ballotable detail on Section 5.3.3.1 (3) for SR-53.

Response Message:

Page 4: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Public Comment No. 62-NFPA 79-2016 [Section No. 5.3.3.1]

Second Revision No. 56-NFPA 79-2017 [ Detail ]

***************INSTRUCTION****************

This detail is to revise Section 5.3.5.1 (4) for SR-53

(4) Circuits supplying equipment that arerequiredneed to remain energized for satisfactory operation [e.g., temperature-controlled measuring devices, product (work in progress) heaters, program storage devices, inputs, non-motion outputs, and displays and safety interlocks.]

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 15:22:22 EST 2017

Committee Statement

Committee Statement:

The TC agreed to add "and safety interlocks" to item "(4)" which are another example of circuits that may need to remain energized to ensure proper operation of a machine. This ballotable detail is to revise Section 5.3.5.1 (4) for SR-53.

Response Message:

Public Comment No. 63-NFPA 79-2016 [Section No. 5.3.5.1]

Second Revision No. 9-NFPA 79-2017 [ Section No. 1.1.1 ]

1.1.1

The provisions of this standard shall apply to the electrical/electronic equipment, apparatus, or systems of industrial machines operatingsupplied from a nominal voltage of 1000 volts or less, and commencing at the point of connection of the supply circuit conductors to the electrical equipment of the machine.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

Page 5: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

City:

State:

Zip:

Submittal Date: Mon Jan 16 17:23:12 EST 2017

Committee Statement

Committee Statement:

The Technical Committee replaced "operating" with "supplied" which clarifies the voltage requirement is in regards to the supply voltage not the operating voltage.

Response Message:

Public Comment No. 73-NFPA 79-2016 [Section No. 1.1.1]

Second Revision No. 57-NFPA 79-2017 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.

NFPA 70®, National Electrical Code®, 2017 edition.

NFPA 70E®, Standard for Electrical Safety in the Workplace®, 20152018 edition.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 25 13:11:13 EST 2017

Committee Statement

Committee Statement: Update to the next edition of NFPA 70 E (2018) that will be issued before NFPA 79 is issued.

Response Message:

Second Revision No. 14-NFPA 79-2017 [ Section No. 3.3.11 ]

3.3.10* Basic Protection (Protection From Direct Contact).

Protection against electric shock under fault-free conditions.

Submitter Information Verification

Page 6: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 10:08:56 EST 2017

Committee Statement

Committee Statement:

The TC removes the parenthetical term "Protection From Direct Contact" because this is explained in the Annex note. The TC gave further consideration to the ballot comments during voting in FR 20. NFPA 70E primarily addresses work practices where NFPA 79 primarily applies to the design and installation of equipment of industrial machinery. There are no similar or equivalent terms in 70E that address this.

Response Message:

Public Comment No. 41-NFPA 79-2016 [Section No. 3.3.11] Public Comment No. 7-NFPA 79-2016 [Section No. 3.3.11]

Second Revision No. 15-NFPA 79-2017 [ Section No. 3.3.46 ]

3.3.45* Fault Protection (Protection From Indirect Contact).

Protection against electric shock under single-fault conditions.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 10:17:08 EST 2017

Committee Statement

Committee Statement:

The TC removes the parenthetical term "Protection from Indirect contact" because this is explained Annex J. The TC gave consideration to the ballot comments during the voting on FR 20. NFPA 70E primarily addresses work practices where NFPA 79 primarily applies to the design and installation

Page 7: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

of equipment of industrial machinery. There are no similar or equivalent terms in 70 E that address this.

Response Message:

Public Comment No. 8-NFPA 79-2016 [Section No. 3.3.46] Public Comment No. 42-NFPA 79-2016 [Section No. 3.3.46]

Second Revision No. 39-NFPA 79-2017 [ New Section after 3.3.69 ]

3.3.69 Machine Supply Circuit.

The conductors between the premises wiring and the machine disconnecting means or terminals.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 09:43:03 EST 2017

Committee Statement

Committee Statement:

Add a new definition “Machine Supply Circuit”. The definition is being added as a companion comment to comment number 31 and is intended to assist with clarifying what is the supply circuit to the machine. There is a need to differentiate between the requirements for the source(s) of supply for the machine and the downstream disconnects and enclosures. This is not new material based on ballot comments during voting.

Response Message:

Public Comment No. 33-NFPA 79-2016 [New Section after 3.3.69]

Second Revision No. 4-NFPA 79-2017 [ Section No. 3.3.110 ]

3.3.108 Visible, Plainly.

Able to be seen without the movement or unmounting of surrounding equipment.

Submitter Information Verification

Page 8: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 16 16:01:11 EST 2017

Committee Statement

Committee Statement:

The definition was removed as it did not add clarity or usability to the document as not all possible situations that could occur were considered. When there is a visibility requirement within a section it must be judged based on the particular application. Using either “plainly” before “visible” or “clearly” before “visible” does not help with enforcing or interpreting a visibility requirement. Whether something is “visible” can only be judged on the specific application.

Response Message:

Public Comment No. 32-NFPA 79-2016 [Section No. 3.3.110] Public Comment No. 13-NFPA 79-2016 [Section No. 3.3.106]

Second Revision No. 10-NFPA 79-2017 [ New Section after 4.2 ]

4.3 Installation and Use of Listed or Labeled Equipment.

Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 16 17:53:06 EST 2017

Committee Statement

Committee Statement:

The TC adds this requirement to clarify that listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing and labeling. NFPA 79 should not rely on 1.5 to refer users to NEC 110.3(B). This is re-located to Chapter 4 in the new location as a new section after 4.2 as 4.3 as it is more appropriate under the general requirements as opposed to administration in Chapter 1.

Page 9: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Response Message:

Public Comment No. 87-NFPA 79-2016 [New Section after 1.6]

Second Revision No. 49-NFPA 79-2017 [ Section No. 4.3.2.8 ]

4.4.2.8 Circuits Supplied From Power Conversion Equipment.

Electrical conductors and equipment supplied by power conversion equipment as part of adjustable speed drive systems and servo drive systems shall be listed flexible motor supply cable marked type RHH, RHW, RHW-2, XHH, XHHW, or XHHW-2 or selected based on the electrical power characteristics involved and the equipment manufacturer’s instructions.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:57:08 EST 2017

Committee Statement

Committee Statement:

Listed flexible motor supply cable marked type RHH, RHW,RHW-2, XHH, XHHW or XHHW-2 will provide protection against damage which may occur in applications of variable frequency drives subjected to nonlinear power distortions. Use of these cables provides an alternate solution to following the equipment manufacturer’s instructions The reference to “electrical power characteristics involved” is deleted as it is vague and unenforceable (unclear to users of the standard). Deletion of this text addresses Public Comment No. 14, CC Note # 9.

Response Message:

Public Comment No. 14-NFPA 79-2016 [Section No. 4.3.2.8] Public Comment No. 2-NFPA 79-2016 [Section No. 4.3.2.8]

Second Revision No. 13-NFPA 79-2017 [ Section No. 4.4.2 ]

4.5.2* Electromagnetic Compatibility (EMC).

Transient suppression, isolation, or other appropriate means shall be provided where the equipment of an industrial machine generates electrical noise or transients, which can affect the operation of equipment that is on or part of the industrial machine.

Page 10: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 09:12:45 EST 2017

Committee Statement

Committee Statement:

The committee statement for FR 14 indicates that: The effects on other equipment within the surrounding area must be considered but the machine is not required to have noise suppression for other such equipment. The TC has clarified the text and considered the negative comments as directed by the CC.

Response Message:

Public Comment No. 15-NFPA 79-2016 [Section No. 4.4.2] Public Comment No. 61-NFPA 79-2016 [Section No. 4.4.2] Public Comment No. 51-NFPA 79-2016 [Section No. 4.4.2]

Second Revision No. 50-NFPA 79-2017 [ Section No. 4.8 ]

4.9 Available Fault Current.

The available fault current at the point of supply to each industrial control panel of a machinemachine supply circuit disconnecting means shall not be greater than the short-circuit current rating marked on the machine industrial control panel nameplate.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 13:44:09 EST 2017

Committee Statement

Page 11: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Committee Statement:

The revised text addressed the concerns of the negative comment during voting as directed by the CC and is consistent with changes made to address the machine supply circuit. Available fault current is the most consistent term for the amount of current available during a short circuit. .

Response Message:

Public Comment No. 16-NFPA 79-2016 [Section No. 4.8]

Second Revision No. 40-NFPA 79-2017 [ Chapter 5 [Title Only] ]

Supply Circuit Terminations and Disconnecting Means

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 10:01:44 EST 2017

Committee Statement

Committee Statement:

This revised title indicates that the means for disconnecting power to a machine’s supply circuit conductor terminations and/or other permitted circuit conductors associated with machine equipment are located in this chapter. This simplification will better assist readers of the document which chapter of the standard to refer to for disconnecting means. The TC reconsidered the ballot comments as directed by the CC during revision of the title.

Response Message:

Public Comment No. 12-NFPA 79-2016 [Chapter 5 [Title Only]] Public Comment No. 17-NFPA 79-2016 [New Section after 5.1.1]

Second Revision No. 53-NFPA 79-2017 [ Sections 5.1, 5.2, 5.3, 5.4, 5.5 ]

5.1 IncomingMachine Supply Circuit Conductor Terminations. 5.1.1*

Where practicable, the electrical equipment of a machine shall be connected to a single power supply circuit. Where it is necessary to use another supply circuit for certain parts of

Page 12: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

the equipment (e.g., electronic circuits, electromagnetic clutches), that supply circuit shall, as far as is practicable, be derived from devices (e.g., transformers, converters) forming part of the electrical equipment of the machine.

5.1.2

The incoming supply circuit conductors shall be terminated at the supply circuit disconnecting means, where practicable. Connections to terminal blocks ahead of the disconnecting means shall be permitted for excepted circuits according to 5.3.5 or where the incoming supply circuit conductors are other than those identified for the supply circuit disconnecting means. Terminals for more than one conductor shall be so identified.

5.1.3*

Where a grounded conductor is used, it shall be clearly indicated in the technical documentation of the machine, such as in the installation diagram and in the circuit diagram. A separate insulated terminal shall be provided for the grounded conductor.

5.1.4

All terminals for each incoming supply circuit shall be legibly marked and correspond with markings on the technical documentation.

5.1.5

The wire bending space provided between the terminals of the supply circuit disconnecting means (or terminals described in 5.1.2) and the wall of the enclosure shall not be less than required by Section 430.10(B) of NFPA 70. Space shall be determined by the maximum wire size of incomingthe supply circuit conductors or not smaller than the conductors required by Section 670.4(A) of NFPA 70. When the wire bending space is based on more than one conductor per phase, the intended conductor size and number shall be so identified on interconnection diagrams as in 17.5.7.

5.1.6

Each set of incoming supply circuit conductors on the line side of the disconnecting means shall be separated from all other internal conductors, including conductors of other supply circuits by either of the following:

(1) Mounting the supply circuit disconnect as near as practicable to the top of the enclosure with dedicated wire bending space as in 5.1.5

(2) Mounting the supply circuit disconnect other than at the top of the enclosure and by separating the supply circuit conductors from other internal conductors by the use of a barrier

5.1.7

All live parts on the line side of the supply circuit disconnecting means shall be protected from unintentional direct contact by use of insulation or obstacle(s) when the disconnecting means is in the open (off) position and the enclosure door is open.

5.2* Machine Supply Circuit Grounding Terminal.

A grounding terminal shall be provided for each incoming supply circuit.

5.3 Machine Supply Circuit Disconnecting (Isolating) Means. 5.3.1 General.

The following general requirements in 5.3.1.1 through 5.3.1.5apply to 5.3.2 through 5.3.5.

5.3.1.1

A supply circuit disconnecting means shall be provided for the following:

Page 13: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(1) Each supply circuit connecting to a machine

(2) Each supply circuit connecting to a feeder system using collector wires, collector bars, slip-ring assemblies, or flexible cable systems (reeled, festooned) to a machine or a number of machines

(3) Each on-board power source (e.g., generators, uninterruptible power supplies)

Exception: Communication, remote control, and signaling circuits of less than 50 volts shall not be required to be provided with a supply circuit disconnecting means.

5.3.1.1.1*

Each supply circuit disconnecting means required by 5.3.1.1 shall be legibly marked to indicate the equipment it disconnects.

5.3.1.1.2

A mainsupply circuit disconnecting means shall be marked as main if multiple“Machine Supply Circuit Disconnect” if additional disconnecting means are supplied from the mainsupply circuit disconnecting means.

5.3.1.1.3

Where a machine is supplied by more than one supply circuit, a marking shall be installed at each supply circuit disconnect location denoting the location of all other supply circuit disconnects.

5.3.1.2

The supply circuit disconnecting means shall disconnect (isolate) the electrical equipment of the machine, including all control circuits, from the supply circuit when required (e.g., for work on the machine, including the electrical equipment). Circuits that are not required to be disconnected by the supply circuit disconnecting means shall comply with 5.3.5.

5.3.1.3

Each supply circuit disconnecting means other than attachment plugs and receptacles shall be mounted within the control enclosure or immediately adjacent thereto.

Exception No. 1: Externally mounted supply circuit disconnecting means, whether interlocked or not interlocked with the control enclosure, supplying machines totaling 2 hp or less shall be permitted to be mounted up to 6 m (20 ft) away from the control enclosure, provided the control enclosure is marked to indicate the location of the supply circuit disconnecting means and the supply circuit disconnecting means complies with all the following:

(1) Is in sight of the control enclosure it supplies

(2) Is readily accessible

(3) Is marked in accordance with 5.3.1.1.1

Exception No. 2: A supply circuit disconnecting means mounted in a separate enclosure and interlocked in accordance with 6.2.3.1 with the control enclosure(s) it supplies shall be permitted to be mounted up to 6 m (20 ft) away from the control enclosure, provided the control enclosure is marked to indicate the location of the supply circuit disconnecting means and the supply circuit disconnecting means complies with all the following:

(1) Is in sight of the control enclosure it supplies

(2) Is readily accessible

Page 14: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(3) Is marked in accordance with 5.3.1.1.1

Detail SR-54 5.3.1.4

Each supply circuit disconnecting means mounted within or adjacent to the control enclosure shall be interlocked with the control enclosure in accordance with 6.2.3.1.

Exception No. 1: An interlock withinfor the control enclosure shall not be required where devices other than the handles of circuit breakers or switches are guarded by a dead-front cover and the use of a key or tool is requirednecessary for opening the supply circuit disconnecting means enclosure to access exposed live parts. A safety sign shall be provided in accordance with Section 16.2. Exception No. 2: Where a supply circuit disconnecting means supplying machines totaling 2 hp or less is not located within or adjacent to the control enclosure it supplies, the control enclosure shall comply with 6.2.3.1 or 6.2.3.2. Where a supply disconnecting means is an attachment plug and receptacle, the control enclosure it supplies shall comply with 6.2.3.2. Where compliance with 6.2.3.2 is required, a safety sign shall be provided in accordance with Section 16.2. 5.3.1.5

Where two or more supply circuit disconnecting means are provided within the control enclosure for multiple supply circuits, they shall be grouped in one location where practicable. Protective interlocks for their correct operation shall be provided where a hazardous condition or damage to the machine or to the work in progress can occur.

5.3.2 Type.

The supply circuit disconnecting device shall be one of the following types:

(1) A listed motor circuit switch (switch disconnector) rated in horsepower

(2) A listed molded case circuit breaker

(3) A listed molded case switch

(4) An instantaneous trip circuit breaker that is part of a listed combination motor controller limited to single motor applications

(5) A listed self-protected combination controller limited to single motor applications

(6) An attachment plug and receptacle (plug/socket combination) for cord connection

5.3.3 Requirements.

Detail SR-55 5.3.3.1*

Where the supply circuit disconnecting device is one of the types in 5.3.2(1) through 5.3.2(5), the device shall fulfill all of the following requirements:

(1) Isolate the electrical equipment from the supply circuit and have one off (open) and one on (closed) position only. Circuit breakers, instantaneous trip circuit breakers, molded-case switches, and self-protected combination motor controllers are permitted to have a reset (tripped) position between off (open) and on (closed).

(2) Have an external operating means (e.g., handle) that complies with 5.3.4.

Page 15: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Exception: Power-operated switchgear need not be operable from outside the enclosure where there are other means to open it.

(3) Be provided with a permanent means permitting it to be locked in the off (open) position only (e.g., by padlocks), independent of the door or cover position, that also prevents. When so locked, remote as well as local closing into the (on)on position shall be prevented.

(4) Simultaneously disconnect all ungrounded conductors of the power supply circuit.

(5) Be operable by qualified persons independent of the door or cover position without the use of accessory tools or devices.

(6) Be rated for the application as follows:

(a) With an ampere rating at least 115 percent of the sum of the full-load currents required for all equipment that is in operation at the same time under normal conditions of use

(b) Where rated in horsepower, with a horsepower rating at least equal to that which is defined by Table 430.251(B) of NFPA 70 for a locked rotor current equal to the largest sum resulting from the locked rotor currents of any combination of motors that can be started simultaneously and the full-load currents of the remaining motor and non-motor loads that can be operated at that time

(c) With a voltage rating at least equal to the nominal supply circuit voltage

(7) Be of a type that plainly indicates whether it is in the off (open) or on (closed) position.

Global SR-1 5.3.3.2*

When the supply circuit disconnecting device is an attachment plug and receptacle (plug/socket combination), it shall fulfill all of the following requirements:

(1) Have a load-break rating or be interlocked with a switching device that is load-break rated and complies with 5.3.3.1(6)

(2) Be listed as a switch-rated plug and receptacle (plug/socket combination) rated greater than 20 amperes or 2 hp

(3) Be of such a type and be so installed as to prevent unintended contact with live parts at any time, even during insertion or removal of the connectors

(4) Have a first-make, last-break electrical grounding contact

(5) Have a retaining means to prevent unintended or accidental disconnection where rated at more than 20 amperes

(6) Be located within sight from the operator station and be readily accessible

5.3.3.3

Page 16: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

In addition to the requirements in 5.3.3.2, an additional switching device on the machine shall be provided for routine power switching operations of the machine on and off.

5.3.4 Operating Handle. 5.3.4.1

The center of the grip of the operating handle of the supply circuit disconnecting means, when in its highest position, shall be not more than 2.0 m (6 ft 7 in.) above the servicing level. A permanent operating platform, readily accessible by means of a permanent stair or ladder, shall be considered the servicing level for the purpose of this requirement.

5.3.4.2

An operating handle of the supply circuit disconnecting means required by 5.3.3.1 shall meet the following criteria:

(1) Be readily accessible with doors in the open or closed position

(2) Maintain the environmental rating of the enclosure to the degree necessary for the application when installed through the control enclosure

(3) Not be restricted by the enclosure door when the door is in the open position

5.3.5 Excepted Circuits.

Detail SR-56 5.3.5.1

The following circuits shall not be required to be disconnected by the mainmachine supply circuit disconnecting means:

(1) Lighting circuits for lighting needed during maintenance or repair

(2) Attachment plugs and receptacles (plug and socket outlets) for the exclusive connection of repair or maintenance tools and equipment (e.g., hand drills, test equipment)

(3) Undervoltage protection circuits that are only used for automatic tripping in the event of supply circuit failure

(4) Circuits supplying equipment that are requiredneed to remain energized for satisfactory operation [e.g., temperature-controlled measuring devices, product (work in progress) heaters, program storage devices, inputs, non-motion outputs, and displays, and safety interlocks]

5.3.5.2

The supplyExcepted circuits for excepted circuits shall be provided with all of the following:

(1) A disconnecting means, isolating transformer, and overcurrent protection mounted in an enclosure adjacent to the main control enclosure or within the control enclosure, adjacent to the main supply circuit disconnecting means

(2) Line side (of the supply circuit disconnect) supply circuit conductors, when internal to the control enclosure, that are separate from and do not share a raceway with other conductors and that are encased in rigid or flexible conduit if longer than 460 mm (18 in.)

5.3.5.3

The control interlocking circuits shall be capable of being disconnected at the control panel from which they are sourced.

Page 17: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

5.3.5.4

Where the excepted circuits are not disconnected by the supply circuit disconnecting means, all of the following requirements shall be met:

(1) Permanent safety sign(s) shall be placed adjacent to the supply circuit disconnecting operating handle(s), indicating that it does not de-energize all exposed live parts when it is in the open (off) (isolated) position as in 16.2.4.

(2) A statement containing the information from 16.2.4 shall be included in the machine documentation.

(3) A permanent safety sign shall be placed on a nonremovable part inside the control enclosure in proximity to each excepted circuit, or shall be identified by color as defined in 13.2.4.

5.4 Means for Removal of Power for Prevention of Unexpected Start-Up. 5.4.1

Means for removal of power shall be provided when prevention of unexpected start-up is required (e.g., during maintenance where the unexpected start-up of a machine or part of the machine results in a hazardous situation). Such means shall be as follows:

(1) Appropriate for the intended use, and

(2) Conveniently located, and

(3) Readily identifiable as to their function and purpose, and

(4) Provided with permanent means for locking in the off position only

5.4.2

Removal of power shall be accomplished by the use of one of the following:

(1) The machine supply circuit disconnecting means

(2) Additional devices conforming to 5.3.2 or 5.5.4

(3) Other means (e.g., a contactor switched off by a control circuit) that meet the requirements of 5.4.3 and 5.4.4

5.4.3*

Where other means of removal of power are used, a single failure of any of its components shall not result in an inadvertent or unexpected start-up.

5.4.4

Other means of removal of power shall be employed only for situations that include the following:

(1) Routine exchange of work pieces, fixtures, and tools requiring no significant dismantling of the machine

(2) Work on the electrical equipment where all of the following conditions exist:

(a) There is no hazard arising from electric shock and burn.

(b) The switching off means cannot be negated by the work.

(c) The work is of a minor nature (e.g., replacement of plug-in devices without disturbing existing wiring).

Page 18: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(d) There is no hazard arising from the unexpected energizing or de-energizing of circuits.

5.5 Devices for Disconnecting (Isolating) Electrical Equipment. 5.5.1

Devices shall be provided for disconnecting (isolating) electrical equipment to enable work to be performed when it is de-energized and isolated.

5.5.2

The machine supply circuit disconnecting devicemeans(see Section 5.3) shall be permitted to fulfill this requirement where there is no need for disconnecting individual portions of the electrical circuit.

5.5.3

Where it is expected that it will be necessary to work on separately operable parts of a machine, a disconnecting means shall be permitted for the electrical equipment of each such part of the machine requiring separate disconnection.

5.5.4

The following devices shall be permitted to fulfill the isolating function of 5.5.3:

(1) Devices described in 5.3.2

(2) A manual motor controller marked “suitable as motor disconnect” and in compliance with UL 508, Standard for Industrial Control Equipment, where located on the load side of the last short-circuit protective device (in the branch)

(3) System isolation equipment that incorporates control lockout stations and is listed for disconnection purposes where located on the load side of the main supply circuit disconnecting means and overcurrent protection

5.5.5

Each operating means of the isolation devices in 5.5.4 shall be as follows:

(1) Readily accessible and complies with 5.3.4

Exception: Switches and circuit breakers installed adjacent to motors, appliances, or other equipment that they supply shall be permitted to be accessible by portable means.

(2) Within sight of the part of the machine requiring disconnection

(3) Readily identifiable as an isolating means and marked to identify the equipment that is disconnected

(4) For other than attachment plugs, provided with permanent means for locking in the off position only

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

Page 19: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

City:

State:

Zip:

Submittal Date: Wed Jan 18 14:55:40 EST 2017

Committee Statement

Committee Statement:

The concept to replace the term “incoming” with “machine” clarifies the machine’s supply circuit is the one that originates from the premises wiring. Adding the word “machine” before the words “supply circuit” clarifies to the users of the document which requirements apply to circuits supplying the machine and which requirements apply to other permitted circuits originating from the machine (load side of the machine supply circuit disconnecting means). Other changes were made as necessary so the requirements read correctly and align with the new definition of a "Machine Supply Circuit." In "show markup" The parenthetical term "plug/socket", and the term "plainly" were also deleted to be consistent with their deletion in other sections. Section 5.3.3.1 (6) (a), (b), and (c) were incorrectly renumbered and underlined and must be restored. Section 5.4.4 (2) (a), (b), (c) and (d) were incorrectly renumbered and underlined and must be restored. Revise Exception No. 1 to Section 5.3.1.4 as a separate ballotable detail SR-54 Revise text to Section 5.3.3.1 (3) as a separate ballotable detail SR-55 Revise Section 5.3.5.1 (4) as a separate ballotable detail SR-56

Response Message:

Public Comment No. 30-NFPA 79-2016 [Section No. 5.3.1.1.2] Public Comment No. 56-NFPA 79-2016 [Section No. 5.5.4] Public Comment No. 46-NFPA 79-2016 [Section No. 5.3.3.2] Public Comment No. 44-NFPA 79-2016 [Section No. 5.3.2] Public Comment No. 18-NFPA 79-2016 [Section No. 5.3.1 [Excluding any Sub-Sections]]

Second Revision No. 17-NFPA 79-2017 [ Section No. 7.2.10.1 ]

7.2.10.1*

Each motor controller and its associated wiring shall be protected as an individual branch circuit by a short-circuit protective device (SCPD) as specified by the controller manufacturer. The maximum rating of the designated SCPD shall be as shown in Table 7.2.10.1. Exception No. 1: Table 7.2.10.1 shall not apply to Design B energy efficient motor circuits. The provisions of NFPA 70 shall be observed for Design B energy efficient motor circuits.

Page 20: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Exception No. 2: Where the controller is an adjustable speed drive that is listed and marked “Suitable for Output Conductor Protection,” the maximum rating of the designated SCPD shall be permitted to be determined by replacing the full-load current in Table 7.2.10.1 with the drive’s rated input current. The SCPD shall not exceed the rating marked on the adjustable speed drive or in the manufacturer’s instructions.

Table 7.2.10.1 Maximum Rating or Setting of Fuse and Circuit Breakers: Motor, Motor Branch Circuit, and Motor Controller

Full-Load Current (%)

Fuse Class with Non–Time Delay AC-2 AC-3 AC-4 R 300 300 300

CF or J 300 300 300

CC 300 300 300

T 300 300 300

Type of Application2 a

Fuse Class with Time Delay1b AC-2 AC-3 AC-4

RK-53c 150 175 175

RK-1 150 175 175

CF or J 150 175 225

CC 150 300 300

Instantaneous trip circuit breaker4d 800 800 800

Inverse trip circuit breaker5e 150 250 250

Note: Where the values determined by this table do not correspond to the standard sizes or ratings, the next higher standard size, rating, or possible setting shall be permitted. 2a Types of starting duty are as follows:

(a)(1) AC-2: All light-starting duty motors, including slip-ring motors; starting, switching off

(b)(2) AC-3: All medium starting duty motors including squirrel-cage motors; starting, switching off while running, occasional inching, jogging, or plugging but not to exceed 5 operations per minute or 10 operations per 10 minutes and all wye-delta and two-step autotransformer starting motors

(c)(3) AC-4: All heavy starting duty motors including squirrel-cage motors; starting, plugging, inching, jogging 1b Where the rating of a time-delay fuse (other than CC type) specified by the table is not sufficient for the starting of the motor, it shall be permitted to be increased but shall in no case be permitted to exceed 225 percent. The rating of a time-delay Class CC fuse and non–time-delay Class CC, J, CF, or T fuse shall be permitted to be increased but shall in no case exceed 400 percent of the full-load current. 2 Types of starting duty are as follows: (a) AC-2: All light-starting duty motors, including slip-ring motors; starting, switching off (b) AC-3: All medium starting duty motors including squirrel-cage motors; starting, switching off while running, occasional inching, jogging, or plugging but not to exceed 5 operations per minute or 10 operations per 10 minutes and all wye-delta and two-step autotransformer starting motors (c) AC-4: All heavy starting duty motors including squirrel-cage motors; starting, plugging, inching, jogging

3cUnless a motor controller is listed for use with RK-5 fuses, Class RK-5 fuses shall be used only with NEMA-rated motor controllers.

Page 21: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

4dInstantaneous trip circuit breakers shall be permitted to be used only if they comply with all of the following:

(a)(1) They are adjustable.

(b)(2) Part of the combination controller has motor-running protection, short-circuit protection, and ground-fault protection in each conductor.

(c)(3) The combination is especially identified for use.

(d)(4) It is installed per any instructions included in its listing or labeling.

(e)(5) They are limited to single motor applications; circuit breakers with adjustable trip settings are to be set at the controller manufacturer's recommendation, but not greater than 1300 percent of the motor full-load current. 5eWhere the rating of an inverse time circuit breaker specified in this table is not sufficient for the starting current of the motor, it shall be permitted to be increased but in no case exceed 400 percent for full-load currents of 100 amperes or less or 300 percent for full-load currents greater than 100 amperes.

7.2.10.1.1

A listed self-protected combination controller shall be permitted in lieu of the devices specified in Table 7.2.10.1 for branch circuit and overload protection of a single motor circuit.

7.2.10.1.2

Where a listed self-protected combination controller has an adjustable, instantaneous trip setting, the setting shall not exceed 1300 percent of full-load motor current for other than Design B energy efficient motors and not more than 1700 percent of full-load motor current for Design B energy efficient motors.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 11:09:47 EST 2017

Committee Statement

Committee Statement:

The text has been revised to clarify that the exception is permitted to be used but not required. The TC has considered the comments as directed by the CC and determined that no additional revisions are required.

Response Message:

Public Comment No. 21-NFPA 79-2016 [Section No. 7.2.10.1]

Page 22: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Second Revision No. 20-NFPA 79-2017 [ Section No. 7.2.10.2 ]

7.2.10.2

Several motors, each not exceeding 1 hp in rating, shall be permitted on a nominal 120-volt branch circuit protected at not over 20 amperes or a 600-volt 1000-volt nominal or less branch circuit, protected at not over 15 amperes, where all of the following conditions are met:

(1) The full-load rating of each motor does not exceed 6 amperes.

(2) The rating of the branch-circuit short-circuit and ground-fault protective device marked on any of the controllers is not exceeded. The short-circuit and ground-fault protection is provided by a single inverse time circuit breaker or single set of fuses.

(3) Individual overload protection conforms to Section 7.3.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 11:23:53 EST 2017

Committee Statement

Committee Statement:

This comment is an output of the 1000V NFPA79 Task Group. The revised change aligns with 430.53(A) in the 2017 NEC.

Response Message:

Public Comment No. 74-NFPA 79-2016 [Section No. 7.2.10.2]

Second Revision No. 16-NFPA 79-2017 [ Section No. 7.2.10.4 ]

7.2.10.4

Two or more motors, or one or more motor(s) and other load(s), and their control equipment shall be permitted to be connected to a single branch circuit where short-circuit and ground-fault protection is provided by a single inverse time circuit breaker or a single set of fuses, provided the following conditions under 7.2.10.4(1) and either 7.2.10.4(2) or 7.2.10.4(3) are met:

(1) Each motor controller and overload device is either listed for group installation with specified maximum branch-circuit protection or selected such that the ampere rating of the motor branch short-circuit and ground-fault protective device does not exceed that permitted by 7.2.10.1 for that individual motor controller or overload device and corresponding motor load.

Page 23: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(2) The rating or setting of the branch short-circuit and ground-fault protection device does not exceed the values in Table 7.2.10.4 for the smallest conductor in the circuit.

Exception: Where a controller is an adjustable speed drive that is listed and marked “Suitable for Output Conductor Protection,” the conductors from the drive to the motor shall not applybe required to be used when determining the smallest conductor in the circuit. The conductors from the drive to the motor shall have an ampacity in accordance with Sections 12.5 and 12.6.

(3) The rating or setting of the branch short-circuit and ground-fault protection does not exceed the value specified in 7.2.10.1 for the highest rated motor connected to the branch circuit plus an amount equal to the sum of the full-load current ratings of all other motors and the ratings of other loads connected to the circuit. Where this calculation results in a rating less than the ampacity of the branch circuit conductors, it shall be permitted to increase the maximum rating of the fuses or circuit breaker to a value not exceeding that permitted by Sections 12.5 and 12.6. Overcurrent protection for loads other than motor loads shall be in accordance with 7.2.3, 7.2.4, and 7.2.11. Where 16 AWG or 18 AWG conductors are used for branch circuit conductors or tap conductors under 7.2.10.5, the rating and type of the branch short-circuit and ground-fault protection shall be in accordance with 12.6.1.

Table 7.2.10.4 Relationship Between Conductor Size and Maximum Rating or Setting of Short-Circuit Protective Device for Power Circuits Group Installations

Conductor Size .

(AWG)

Maximum Rating .

Fuse or Inverse Time* .

Circuit Breaker .

(amperes) 18 See footnote.

16 See footnote.

14 60

12 80

10 100

8 150

6 200

4 250

3 300

2 350

1 400

0 500

2/0 600

3/0 700

4/0 800

*Maximum ratings and type of branch short-circuit and ground-fault protective devices for 16 AWG and 18 AWG shall be determined in accordance with 12.6.1.

Submitter Information Verification

Page 24: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 10:59:52 EST 2017

Committee Statement

Committee Statement:

The Technical Committee has revised the text in exception No. 2 for clarity for application of a single branch circuit supplying two or more motors, or one or more motor(s) and other load(s), and their control equipment .

Response Message:

Public Comment No. 22-NFPA 79-2016 [Section No. 7.2.10.4]

Second Revision No. 18-NFPA 79-2017 [ Section No. 7.2.10.5 ]

7.2.10.5

For group installations described in 7.2.10.4(3), the conductors of any tap supplying a single motor shall not be required to have an individual branch-circuit short-circuit and ground-fault protective device, provided they comply with one of the following:

(1) No conductor to the motor shall have an ampacity less than that of the branch-circuit conductors.

(2) No conductor to the motor shall have an ampacity less than one-third that of the branch-circuit conductors, with a minimum in accordance with Sections 12.5 and 12.6, the conductors to the motor overload device being not more than 7.5 m (25 ft) long and being suitably protected from physical damage in accordance with Chapter 13.

(3) Conductors from the point of the tap from the branch-circuit short-circuit and ground-fault protective device to a listed manual motor controller additionally marked “Suitable for Tap Conductor Protection in Group Installations” or to a branch circuit protective device shall be permitted to have an ampacity not less than 1/10 the rating or setting of the branch-circuit short-circuit and ground-fault protective device. The conductors from the controller to the motor shall have an ampacity in accordance with Sections 12.5 and 12.6. The conductors from the branch-circuit short-circuit and ground-fault protective devicepoint of the tap to the controller shall (1) be enclosed either by an enclosed controller or by a raceway and be not more than 3 m (10 ft) long or (2) have an ampacity not less than that of the branch-circuit conductors.

Submitter Information Verification

Page 25: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 11:15:46 EST 2017

Committee Statement

Committee Statement: The TC has revised the text to correlate with 430.53(D)(3) of NFPA 70 2017.

Response Message:

Public Comment No. 64-NFPA 79-2016 [Section No. 7.2.10.5]

Second Revision No. 41-NFPA 79-2017 [ Section No. 7.5.3 ]

7.5.3 Restarting.

Upon restoration of the voltage or upon switching on the incomingmachine supply circuit, automatic or unintentional restarting of the machine shall be prevented when such a restart causes a hazardous condition.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:04:36 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Page 26: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Second Revision No. 58-NFPA 79-2017 [ Section No. 7.8.1 ]

7.8.1 Surge ProtectionProtective Devices (SPDs).

SPDs shall be permitted to be provided for industrial machinery with safety interlock circuits to protect against the effects of overvoltages due to lightning or switching surges.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 25 13:24:41 EST 2017

Committee Statement

Committee Statement:

The technical committee revised the existing requirement in 7.8.1 to require an appropriate SPD for protection of industrial machinery with safety interlock circuits to correlate with NFPA 70 670.6. The manufacturer of the industrial machinery can determine what specific type of SPD is to be used to provide the needed protection based on the installation and equipment design.

Response Message:

Second Revision No. 21-NFPA 79-2017 [ Section No. 7.9 ]

7.9 Power Factor Correction Capacitor Overcurrent Protection.

Where capacitors are installed for motor power factor correction on circuits of 6001000 volts, nominal, and under, overcurrent protection for the conductors shall be provided. Each capacitor cell or capacitor bank shall be protected against rupture of the individual cells. Protection included as a part of the capacitor assembly shall be permitted.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 11:25:32 EST 2017

Committee Statement

Page 27: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Committee Statement:

The proposed change increases the voltage to 1000V to include all equipment covered by the revised scope change.

Response Message:

Public Comment No. 75-NFPA 79-2016 [Section No. 7.9]

Second Revision No. 38-NFPA 79-2017 [ Section No. 8.1.2 ]

8.1.2 Connections.

Except at either the source or first disconnecting means of a grounded separately derived system, grounded conductors shall not be connected to the equipment grounding conductor.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 18:11:29 EST 2017

Committee Statement

Committee Statement:

The first use of the term grounded is unnecessary since an ungrounded separately derived system does not contain a grounded conductor. This change improves clarity. The TC reviewed the CC comments as directed by the CC.

Response Message:

Public Comment No. 84-NFPA 79-2016 [Section No. 8.1.2] Public Comment No. 23-NFPA 79-2016 [Section No. 8.1.2]

Second Revision No. 23-NFPA 79-2017 [ Section No. 8.2.1.1 ]

8.2.1.1 Effective Ground FaultGround-Fault Current Path.

All parts of theThe effective ground faultground-fault current path shall be capable of withstanding the highest thermal and mechanical stress that can be caused by fault currents in that part of the circuitsafely carrying the maximum ground-fault current likely to be imposed on it from any point where a ground fault could occur from the point of connection of the supply circuit conductors to the electrical equipment of the machine.

Submitter Information Verification

Page 28: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 12:41:43 EST 2017

Committee Statement

Committee Statement:

The language accepted in the FR could be misunderstood. The proposed language is consistent with the same requirement in 250.4 of NFPA 70.

Response Message:

Public Comment No. 83-NFPA 79-2016 [Section No. 8.2.1.1]

Second Revision No. 24-NFPA 79-2017 [ Section No. 8.2.1.2.2 ]

8.2.1.2.2

Where electrical devices are mounted on metal mounting panels that are located within nonmetallic enclosures, the metal mounting panels shall be effectively grounded. Where electrical devices are mounted on metal mounting panels that are located within nonmetallic enclosures, the metal mounting panels shall be connected to an equipment grounding conductor or bonding jumper.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 14:26:42 EST 2017

Committee Statement

Committee Statement:

This is an editorial change to address an inadvertent addition of a duplicate sentence during the transition to TerraView.

Response Message:

Public Comment No. 80-NFPA 79-2016 [Section No. 8.2.1.2.2]

Page 29: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Second Revision No. 25-NFPA 79-2017 [ Section No. 8.2.1.3.1 ]

8.2.1.3.1

For each machine supply circuit, an equipment grounding conductor terminal shall be provided in the vicinity of the associated phase conductor terminals and shall be connected to the equipment grounding conductor.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 14:28:50 EST 2017

Committee Statement

Committee Statement:

“Shall be” is added to improve readability of the text. And "machine" is added Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Public Comment No. 81-NFPA 79-2016 [Section No. 8.2.1.3.1]

Second Revision No. 26-NFPA 79-2017 [ Section No. 8.2.1.3.4 ]

8.2.1.3.4

Where an auxiliary grounding electrode is specified, theby the industrial machinery manufacturer or provider, a terminal shall accommodate this additional grounding electrode conductor.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 14:34:46 EST 2017

Page 30: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Committee Statement

Committee Statement:

For other than custom built industrial machinery, the industrial machinery manufacturer has no way of knowing if the installer or user will specify something. This will clarify that the additional terminal requirement is only necessary to be provided by the industrial machinery manufacturer if they specify an auxiliary grounding electrode.

Response Message:

Public Comment No. 82-NFPA 79-2016 [Section No. 8.2.1.3.4]

Second Revision No. 27-NFPA 79-2017 [ Section No. 8.2.3.2 ]

8.2.3.2

Removing a device shallEquipment grounding conductors and bonding jumpers shall be installed in a manner such that removal of a wiring device, such as a receptacle or switch, does not interrupt the continuity of the equipment grounding conductor or bonding jumperconductor.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 14:53:04 EST 2017

Committee Statement

Committee Statement:

Pressure connectors and terminal bars are devices and removing them would interrupt the continuity of the equipment grounding conductor. The intent of the requirement is to ensure that devices that are likely to be replaced, can be removed and replaced without losing the effective ground fault path. The sentence is restructured to improve readability.

Response Message:

Public Comment No. 78-NFPA 79-2016 [Section No. 8.2.3.2]

Second Revision No. 28-NFPA 79-2017 [ Section No. 8.2.3.4 ]

8.2.3.4

Raceways, wireways, and cable trays shall not be used as equipment grounding or bonding conductors.Equipment containing energized conductors shall be provided with a separate wire-type equipment grounding conductor or bonding jumper.

Page 31: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 14:59:35 EST 2017

Committee Statement

Committee Statement:

The structure of the language is revised to avoid leaving other types of equipment, such as an auxiliary gutters, from the list and instead provides the intended requirement in positive text.

Response Message:

Public Comment No. 79-NFPA 79-2016 [Section No. 8.2.3.4]

Second Revision No. 30-NFPA 79-2017 [ Section No. 9.1.1.4 ]

9.1.1.4

The source of supply for all control circuits shall be taken from the load side of the supply disconnecting means.

Exception: The power supply circuit to controlControl circuits meeting the requirements of excepted circuits in 5.3.5.1(4)shall be permitted to be taken from the line side of the supply disconnecting means or other power source.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 15:50:49 EST 2017

Committee Statement

Committee Statement: The TC removes the phrase "The power supply circuit to" from the exception for clarity.

Response Message:

Page 32: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Public Comment No. 25-NFPA 79-2016 [Section No. 9.1.1.4]

Second Revision No. 31-NFPA 79-2017 [ Section No. 9.2.5.4 ]

9.2.5.4 Stop by De-Energization.

Except for cycle stop commands (stop by energization), stop functions shall be initiated by de-energization, not energization of a device or as a command to a programmable logic controller (PLC).

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 16:09:19 EST 2017

Committee Statement

Committee Statement:

The new requirement has been deleted because it is unclear as to the extent of stop commands it covers and in its reference to the use of Safety PLC's for issuing of stop commands. Stopping by de-energization is presently mentioned in Annex H.2 as one component for minimizing the probability of control function failure.

Response Message:

Public Comment No. 65-NFPA 79-2016 [Section No. 9.2.5.4]

Second Revision No. 42-NFPA 79-2017 [ Section No. 9.2.5.5.2.2 ]

9.2.5.4.2.2

Emergency switching off shall be accomplished by disconnecting the incomingmachine supply circuit of the machine effecting a Category 0 stop. Where the machine cannot tolerate the Category 0 stop, it shall be necessary to provide other protection (e.g., against direct contact), so that emergency switching off is not necessary.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

Page 33: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

State:

Zip:

Submittal Date: Wed Jan 18 12:13:32 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Second Revision No. 32-NFPA 79-2017 [ Section No. 11.2.1.10 ]

11.2.1.10

Busbars shall be securely fastened in place and the. The minimum spacing between uninsulated parts of busbars, busbar terminals, and other bare metal parts for busbars in feeder circuits shall not be less than specified in Table 430.97(D) of NFPA 70.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 16:29:00 EST 2017

Committee Statement

Committee Statement:

The requirement has been revised to indicate the increased spacing is only required for busbars located in feeder circuits.

Response Message:

Public Comment No. 66-NFPA 79-2016 [Section No. 11.2.1.10]

Second Revision No. 33-NFPA 79-2017 [ Section No. 11.4.8.1 ]

11.4.8.1

Page 34: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

When this is not practicable, itIt shall be permissible to place a pocket that is suitable for the environment outside the door of the control enclosure or compartment in a well-identified location.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 16:54:23 EST 2017

Committee Statement

Committee Statement:

The TC removes "When it is practicable" to allow the print pocket to be located elsewhere. Someone should not need to open an enclosure, possibly exposing themselves to hazards.

Response Message:

Public Comment No. 89-NFPA 79-2016 [Section No. 11.4.8.1]

Second Revision No. 34-NFPA 79-2017 [ Section No. 11.5 [Excluding any Sub-Sections] ]

Access and working space for control cabinets and compartments operating at 6001000 volts, nominal, or less to ground and likely to require examination, adjustment, servicing, or maintenance while energized shall comply with the provisions of Chapter 11. Sufficient access and working space shall be provided and maintained around all control cabinets and compartments to permit ready and safe operation and maintenance of such control cabinets and compartments. Working space for cabinets and compartments that contain supply conductors to industrial machinery that are covered by Article 670 of NFPA 70 shall be in accordance with the NEC.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 17:06:43 EST 2017

Page 35: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Committee Statement

Committee Statement:

The TC changed the requirement to increase the voltage to 1000V to include all equipment covered by the revised scope change and aligns with the 2017 edition of NFPA 70.

Response Message:

Public Comment No. 76-NFPA 79-2016 [Section No. 11.5 [Excluding any Sub-Sections]]

Second Revision No. 35-NFPA 79-2017 [ Section No. 11.5.1.1 ]

11.5.1.1

The depth of the working space in the direction of access to live parts shall not be less than indicated in Table 11.5.1.1. Distances shall be measured from the control cabinet or compartment front or opening.

Table 11.5.1.1 Working Space Depth

Minimum Clear Distance

Nominal Voltage to Ground Condition 1 Condition 2 Condition 3

0–150 914900 mm (3 ft) 914900 mm (3 ft) 914900 mm (3 ft)

151–600 914900 mm (3 ft) 1.071.0 m (31⁄2 ft) 1.221.2 m (4 ft)

601–1000 900 mm (3 ft) 1.2 m (4 ft) 1.5 m (5 ft)

Note: Where the conditions are as follows:

Condition 1 — Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by insulating materials. Insulated wire or insulated busbars operating at not over 300 volts to ground shall not be considered live parts.

Condition 2 — Exposed live parts on one side and a grounded surface on the other side. Concrete, brick, or tile walls shall be considered as grounded.

Condition 3 — Exposed live parts on both sides of the working space (not guarded as provided in Condition 1) with the operator between.

Exception No. 1: Working space shall not be required in back or sides of control cabinets or compartments, where there are no renewable or adjustable parts on the back or sides and where all connections are accessible from locations other than the back or sides. Where rear access is required to work on de-energized parts on the back of enclosed control cabinet and compartment, a minimum working space of 762 mm (2 1⁄2 ft) horizontally shall be provided. Exception No. 2: By special permission, working space clearance depth of 762 mm (21⁄2 ft) or less shall be permitted where all uninsulated parts are at a voltage no greater than 50 volts rms ac or 60 volts dc. Exception No. 3: Condition 2 working clearance depth shall be permitted between control cabinets or compartments located across the aisle from each other or across from non-machinery-associated switchgear, panelboards, or motor control centers where conditions of maintenance and supervision ensure that written procedures have been adopted to prohibit the affected equipment doors on both sides of the aisle from being open at the same time and qualified persons who are authorized will service the installation.

Page 36: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 37: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Exception No. 4: Condition 1 working clearance depth shall be permitted between control cabinets or compartments located across the aisle from each other, or across from a grounded surface, where all associated control cabinet or compartment devices and equipment operating at greater than 50 volts rms ac or 60 volts dc are separately enclosed, guarded, or constructed so that openings to live parts of the devices and equipment will not permit the entry of a 12.5 mm (0.5 in.) diameter rod. Exception No. 5: By special permission, the minimum working space clearance depth of 762 mm (21⁄2 ft) shall be permitted where all of the following conditions are met:

(1) The control cabinet or compartment is operating at not over 150 volts line-to-line or line-to-ground.

(2) The conditions of maintenance and supervision ensure that only qualified persons will service the installation.

(3) The control cabinet and compartment require a tool to open.

(4) Where only diagnostic troubleshooting and testing on live parts are involved.

(5) The door(s) of the control cabinet and compartment open at least 90 degrees or are removable.

Supplemental Information

File Name Description Approved 11.5.1.1_screen_shot_table.jpg 11.5.1.1 table updated

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 17:12:59 EST 2017

Committee Statement

Committee Statement:

This comment is an output of the 1000V NFPA 79 Task Group. The proposed change increases the voltage to 1000V to include all equipment covered by the revised scope change and aligns with the 2017 NEC changes to Table 110.26(A)(1). One issue the task group identified to be addressed is if the working distances apply to the incoming source voltage or to any working voltage present in the panel including DC voltages.

Response Message:

Public Comment No. 77-NFPA 79-2016 [Section No. 11.5.1.1]

Page 38: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Second Revision No. 19-NFPA 79-2017 [ Section No. 12.5.5 ]

12.5.5

Conductors supplying a single motor or multiple motors shall be permitted to be sized based on 125 percent of the highest rated motor at demand factors based on the loading or application of the motors.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 11:20:08 EST 2017

Committee Statement

Committee Statement:

The TC has considered the negative comments expressed during voting as directed by the CC and deleted the requirement as it can result in smaller unprotected conductors.

Response Message:

Public Comment No. 67-NFPA 79-2016 [Section No. 12.5.5] Public Comment No. 27-NFPA 79-2016 [New Section after 12.5.4]

Second Revision No. 48-NFPA 79-2017 [ Section No. 13.2.2.1 ]

13.2.2.1*

The color GREEN with or without one or more YELLOW stripes shall be used to identify the equipment grounding conductor where insulated or covered. This color identification shall be strictly reserved for the equipment grounding conductor. GREEN shall be the predominant color when used in combination with one or more YELLOW stripes.

Exception No. 1: Conductors with green insulation or insulation that is green with one or more yellow stripes shall be permitted to be used for other than equipment grounding purposes where all of the following conditions are met:

(1) The conductor is part of a multiconductor cable.

(2) The multiconductor cable containing the conductor contains only circuits supplied from a source limited to less than 50 volts.

(3) The multiconductor cable containing the conductor contains only circuits supplied from a source limited to no more than a power-limited Class 2 energy level.

Page 39: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(4) The conductor is reidentified at all accessible locations, or the multiconductor cable is part of a listed assembly.

Exception No. 2: It shall be permitted to use conductors of any color, provided the insulation or cover is appropriately identified at all points of access. Exception No. 3: For grounded control circuits, use of a GREEN insulated conductor with or without one or more YELLOW stripes or a bare conductor from the transformer terminal to a grounding terminal on the control panel shall be permitted.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:47:15 EST 2017

Committee Statement

Committee Statement:

This action reinstates and revises Exception 1 that was removed in the First Revision Meeting. The revision addresses the concerns that low-energy equipment supplied from an ungrounded source should not place a restriction on the use of the green conductor in a multiconductor cable. The changes correlate with the language in Section 250.119 of NFPA 70 as directed by the CC. The changes provide necessary restrictions on use of green conductors to address the substantiation for removing the exception in FR 39.

Response Message:

Public Comment No. 28-NFPA 79-2016 [Section No. 13.2.2.1] Public Comment No. 90-NFPA 79-2016 [New Section after 13.2.2.1] Public Comment No. 68-NFPA 79-2016 [Section No. 13.2.2.1]

Second Revision No. 5-NFPA 79-2017 [ Section No. 14.8 ]

14.8 Direction Arrow.

Where reverse rotation produces an unsafe condition or causes damage to connected equipment, a direction arrow shall be installed. The arrow shall be adjacent to the motor and plainly visible.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

Page 40: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

State:

Zip:

Submittal Date: Mon Jan 16 16:33:01 EST 2017

Committee Statement

Committee Statement:

Using the term “plainly” before “visible” does not help with enforcing or interpreting a visibility requirement nor does it add any clarity to the requirement. Whether something is “visible” can only be judged based on the specific application.

Response Message:

Public Comment No. 34-NFPA 79-2016 [Section No. 14.8]

Second Revision No. 36-NFPA 79-2017 [ New Section after 14.9 ]

14.10 Motor Controllers.

Motor controllers shall be provided in accordance with Article 430, Part VII, of NFPA 70.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 17 17:38:39 EST 2017

Committee Statement

Committee Statement:

Presently, specific guidance on selecting motor controllers is missing in NFPA 79. Motor overload protection is specified to be provided using Article 430 of NFPA 70, Part III in NFPA 79 7.3.1. Transformer protection is required to be provided using NEC Article 450, Part IV in NFPA 79 7.2.7. Motor controllers should have a similar more specific reference other than NFPA 79 1.5 which sends you back to NFPA 70.

Response Message:

Public Comment No. 55-NFPA 79-2016 [New Section after 14.9]

Second Revision No. 11-NFPA 79-2017 [ Sections 16.2.2, 16.2.3 ]

Page 41: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

16.2.2

Safety signs shall be plainly visible on the enclosure door or cover.

16.2.3*

Electrical equipment for industrial machines, such as industrial control panels and the enclosures of disconnecting devices, shall be marked with a safety sign in accordance with ANSI Z535.4, Product Safety Signs and Labels, to warn qualified persons of potential electric shock and arc flash hazards.

16.2.3.1

The marking shall be located so as to be plainly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

16.2.3.2

It shall be permitted to omit safety signs where the size of the enclosure precludes placement of the label on the enclosure (e.g., operator–machine interfaces, control stations, position sensors).

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 16 18:28:39 EST 2017

Committee Statement

Committee Statement:

Using the term “plainly” before “visible” does not help with enforcing or interpreting a visibility requirement nor does it add any clarity to the requirement. Whether something is “visible” can only be judged based on the specific application.

Response Message:

Public Comment No. 36-NFPA 79-2016 [Section No. 16.2.3.1] Public Comment No. 35-NFPA 79-2016 [Section No. 16.2.2]

Second Revision No. 12-NFPA 79-2017 [ Section No. 16.4.1 ]

16.4.1

Control equipment shall be legibly and durably marked in a way that is plainly visible after the equipment is installed. A nameplate giving the following information shall be attached to the outside of the enclosure, or on the machine immediately adjacent to the enclosure:

(1) Name or trademark of supplier

(2) Model, serial number, or other designation

Page 42: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

(3) *Rated voltage, number of phases and frequency (if ac), and full-load current for each supply

(4) Ampere rating of the largest motor or load

(5) Maximum ampere rating of the short-circuit and ground-fault protective device, where provided

(6) Short-circuit current rating of the industrial control panel

(7) Electrical diagram number(s) or the number of the index to the electrical drawings

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 16 18:35:27 EST 2017

Committee Statement

Committee Statement:

Using the term “plainly” before “visible” does not help with enforcing or interpreting a visibility requirement nor does it add any clarity to the requirement. Whether something is “visible” can only be judged based on the specific application.

Response Message:

Public Comment No. 37-NFPA 79-2016 [Section No. 16.4.1]

Second Revision No. 37-NFPA 79-2017 [ Section No. 16.4.2 ]

16.4.2

The full-load current shown on the nameplate shall not be less than the full-load currents for all motors and other equipment that can be in operation at the same time under normal conditions of use, design load, and duty cycle. Where unusual loads or duty cycles require oversized conductors, the required capacity shall be included in the full-load current specified on the nameplate.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

Page 43: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

State:

Zip:

Submittal Date: Tue Jan 17 18:04:38 EST 2017

Committee Statement

Committee Statement:

The proposed text addresses the concerns expressed in PI 113 without always requiring measurement of input current.

Response Message:

Public Comment No. 72-NFPA 79-2016 [Section No. 16.4.2]

Second Revision No. 43-NFPA 79-2017 [ Section No. 16.4.3 ]

16.4.3

Where more than one incomingmachine supply circuit is to be provided, the nameplate shall state the information in 16.4.1 for each circuit.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:14:51 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Second Revision No. 7-NFPA 79-2017 [ Section No. 16.4.4 ]

16.4.4

Where only a single motor or motor controller is used, the motor nameplate shall be permitted to serve as the electrical equipment nameplate where it is plainly visible.

Page 44: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 16 17:05:40 EST 2017

Committee Statement

Committee Statement:

Using the term “plainly” before “visible” does not help with enforcing or interpreting a visibility requirement nor does it add any clarity to the requirement. Whether something is “visible” can only be judged based on the specific application.

Response Message:

Public Comment No. 38-NFPA 79-2016 [Section No. 16.4.4]

Second Revision No. 29-NFPA 79-2017 [ Sections 18, 18 ]

Chapter 18 Testing and Verification 18.1* General.

The verification of the continuity of the equipment grounding circuiteffective ground-fault current path shall be conducted and documented. When the electrical equipment is modified, the requirements in Section 18.7 shall apply. Applicable tests shall be performed where deemed necessary in accordance with the references in the following list:

(1) Verification that the electrical equipment is in compliance with the technical documentation (see Chapter 17)

(2) Insulation resistance test (see Section 18.3)

(3) Voltage test (see Section 18.4)

(4) Protection against residual voltages test (see Section 18.5)

(5) Functional test (see Section 18.6)

18.2* Continuity of the Equipment Grounding CircuitEffective Ground-Fault Current Path.

One of the following methods shall be used to verify the continuity of the equipment grounding circuiteffective ground-fault current path:

(1) UseUsing an impedance measuring device, take into account any impedance in the measuring circuit. The measured impedance shall be 0.1 ohm or less.

(2) Apply a current of at least 10 amperes, 50 Hz or 60 Hz, derived from aan SELV source. The tests are to be made between the equipment grounding terminal and relevant points that are part of the equipment grounding

Page 45: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

circuiteffective ground-fault current path; the measured voltage between the equipment grounding terminal and the points of test is not to exceed the values given in Table 18.2.

Table 18.2 Verification of Continuity of the Equipment Grounding CircuitEffective Ground-Fault Current Path

Minimum Equipment Grounding Conductor Cross-Sectional Area of the Branch Under Test

.

(AWG)

Maximum Measured

.

Voltage Drop* .

(V)

18 3.3

16 2.6

14 1.9

12 1.7

10 1.4

>8 1.0

*Values are given for a test current of 10 amperes.

18.3 Insulation Resistance Tests.

The insulation resistance measured at 500 volts dc between the power circuit conductors and the equipment grounding circuiteffective ground-fault current path shall not be less than 1 megohm. The test shall be permitted to be made on individual sections of the machine.

18.4* Voltage Tests.

The machine shall withstand without breakdown a test voltage gradually applied from 0 volts to 1500 volts ac or 2121 volts dc and held at the maximum value for a period of at least 1 second between the conductors of all primary circuits and the equipment grounding circuiteffective ground-fault current path. The test voltage shall be supplied from an isolated power supply with a minimum rating of 500 volt amperes. Components that are not rated to withstand the test voltage shall be disconnected during testing.

18.5 Protection Against Residual Voltages.

Residual voltage tests shall be performed to ensure compliance with Section 6.5.

18.6 Functional Tests.

The functions of electrical equipment, particularly those related to safety and safeguarding, shall be tested.

18.7 Retesting.

Where a portion of the machine and its associated equipment is changed or modified, that portion shall be reverified and retested as appropriate.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Page 46: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submittal Date: Tue Jan 17 15:20:20 EST 2017

Committee Statement

Committee Statement:

The changes in terms made in Chapter 8 during the first revision meeting with FR 29, placed the terminology in Chapter 18 in conflict. These changes make the document consistent.

Response Message:

Public Comment No. 85-NFPA 79-2016 [Sections 18, 18]

Second Revision No. 44-NFPA 79-2017 [ Section No. 19.4 ]

19.4 Contactor.

Where a contactor is installed ahead of the incoming supply conductors to the servo drive, the contactor current rating shall not be less than 115 percent of the maximum servo drive nameplate rating or shall be sized in accordance with the manufacturer's specifications.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:16:03 EST 2017

Committee Statement

Committee Statement: The TC removed the term "incoming" to be consistent with other sections.

Response Message:

Second Revision No. 45-NFPA 79-2017 [ Section No. A.5.1.1 ]

A.5.1.1

For large complex machinery comprising a number of widely spaced machines working together in a coordinated manner, more than one incomingmachine supply circuit might be needed, depending upon the site supply circuit arrangements (see 5.3.1).

Submitter Information Verification

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 47: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:22:31 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Second Revision No. 46-NFPA 79-2017 [ Section No. A.11.5 ]

A.11.5

Figure A.11.5 identifies the requirements for determining the working spaces for electrical equipment associated with industrial machinery.

Figure A.11.5 Clarification of Working Space Requirements at the Termination Location of IncomingMachine Supply Circuit Conductors.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 48: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

The left side of Figure A.11.5 depicts a situation where the incomingmachine supply circuit disconnecting means, required by 5.3.1.1, is located in the industrial machine control panel or compartment.

The right side of Figure A.11.5 depicts a situation where the incomingmachine supply circuit disconnecting means, required by 5.3.1.1, is externally mounted to the industrial machine control cabinet or the compartment it supplies.

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:23:44 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Page 49: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Response Message:

Second Revision No. 47-NFPA 79-2017 [ Section No. B.1 ]

B.1

It is recommended that the information in Figure B.1 be provided by the intended user of the equipment. It facilitates an agreement between the user and supplier on basic conditions and additional user requirements to ensure proper design, application, and utilization of the electrical equipment of the machine (see Section 4.1).

Figure B.1 Inquiry Form for the Electrical Equipment of Machines.

Page 50: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

DELETED

Page 51: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 52: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 53: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Information Verification

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 12:29:32 EST 2017

Committee Statement

Committee Statement:

Revising the text so it reads “machine supply circuit” clarifies the machine’s supply circuit originates from the premises wiring. This clarification will assist readers of the document with determining which requirements apply to the circuit supplying the machine and which requirements apply to circuits originating from the machine (load side of the machine supply circuit disconnecting means).

Response Message:

Second Revision No. 51-NFPA 79-2017 [ Section No. D.1 ]

D.1

Figure D.1(a) through Figure D.1(q) are not intended to be (design) guidelines. They are included only to illustrate documentation methods.

Figure D.1(a) Cover Sheet and Sheet Index.

Page 54: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(b) System Layout and Installation Diagram.

DELETED

Page 55: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(c) Block (System) Diagram.

Figure D.1(d) Interconnection Diagram.

Page 56: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(e) Elementary Schematic.

Figure D.1(f) PLC Input Diagram.

Page 57: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 58: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(g) PLC Output Diagram.

Page 59: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 60: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(h) Sample Enclosure Layout — Interior.

Page 61: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(i) Sample Enclosure Layout — Exterior.

Figure D.1(j) Sequence of Operations — Graphical.

Page 62: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(k) Sequence of Operations — Descriptive Graphical.

Page 63: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(l) Sample Servo Diagram.

Page 64: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(m) Sample PLC Network — Station Layout.

Page 65: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 66: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(n) Sample Operator Station.

Page 67: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to
Page 68: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(o) Sample Parts List.

Figure D.1(p) ISO (A2) Drawing Standard Framework.

Page 69: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Figure D.1(q) Selections from ANSI Y32.2/IEEE 315 Symbol Table.

Page 70: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

DELETED

Page 71: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Information Verification

Page 72: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 14:02:52 EST 2017

Committee Statement

Committee Statement:

Delete the term "duct" and replace with "wireway" in D.1 b. The committee agreed to do this as indicated in the Committee Statement to FR 50 for the 2015 edition. The terms described do not always match the term they follow as many times they are not directly interchangeable. Annex J was added in the 2015 edition to help users understand the differences between terms used in other standards. Disregard the strikeouts.

Response Message:

Public Comment No. 57-NFPA 79-2016 [Section No. D.1] Public Comment No. 43-NFPA 79-2016 [Section No. D.1]

Second Revision No. 52-NFPA 79-2017 [ Section No. K.1 ]

K.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections of this standard and are not part of the requirements of this document unless also listed in Chapter 2 for other reasons.

K.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 70®, National Electrical Code®, 2017 edition.

NFPA 70E®, Standard for Electrical Safety in the Workplace®, 20152018 edition.

NFPA 77, Recommended Practice on Static Electricity, 2014 edition.

K.1.2 Other Publications. K.1.2.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI B11.0, Safety of Machinery — General Requirements and Risk Assessment, 20102015.

ANSI B11-TR4, Selection of Programmable Electronic Systems (PES/PLC) for Machine Tools, 2004.

ANSI B11-TR6, Safety Control Systems for Machine Tools, 2010.

ANSI Z535.4, Product Safety Signs and Labels, 2011.

K.1.2.2 CENELEC Publications.

Page 73: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

CENELEC, European Committee for Electrotechnical Standardization, CENELEC Management Centre, Avenue Marnix 17, 4th floor, B - 1000 Brussels.

BS EN 60204-1, Safety of machinery — Electrical equipment of machines — Part 1: General requirements, corrigendum, 20102017.

BS EN 61010-1, Safety requirements for electrical equipment for measurement, control, and laboratory use — Part 1: General requirements,2010, corrigendum, 20112017.

K.1.2.3 IEC Publications.

International Electrotechnical Commission, 3, rue de Varembé, P.O. Box 131, CH-1211 Geneva 20, Switzerland.

IEC 60034-1 Ed. 12.0, Rotating electrical machines — Part 1: Rating and performance, 2010.

IEC 60072-1 Ed. 6.0, Dimensions and output series for rotating electrical machines — Part 1: Frame numbers 56 to 400 and flange numbers 55 to 1080, 1991.

IEC 60204-1 Ed. 5.16.0, Safety of machinery — Electrical equipment of machines — Part 1: General requirements, 20092016.

IEC 60332-1-1 Ed. 1.1, Tests on electric and optical fibre cables under fire conditions — Part 1-1: Test for vertical flame propagation for a single insulated wire or cable apparatus, 2015.

IEC 60364-4-41 Ed. 5.0, Electrical installations of buildings — Part 4-41: Protection for safety — Protection against electric shock, 2005.

IEC 60364-5-53 Ed. 3.2, Electrical Installations of buildings — Part 5-53: Selection and erection of electrical equipment — Isolation, switching and control, 2015.

IEC 60417 DB [Database], Graphical symbols for use on equipment — Part 1: Overview and application, 2002.

IEC 60529 Ed. 2.2, Degrees of protection provided by enclosures (IP Code), 2013, corrigendum 2, 2015.

IEC 60621-3 Ed. 1.0, Electrical installations for outdoor sites under heavy conditions (including open-cast mines and quarries) — Part 3: General requirements for equipment and ancillaries, 1979 (withdrawn).

IEC 60742 Ed. 1.0, Isolating transformers and safety isolating transformers, 1983 (superseded by IEC 61558-1).

IEC 60870-5-1 Ed. 1.0, Telecontrol equipment and systems — Part 5: Transmission protocols — Section One: Transmission frame formats, 1990.

IEC 60947-4-1 Ed. 3.1, Low-voltage switchgear and controlgear — Part 4-1: Contactors and motor-starters — Electromechanical contactors and motor-starters, 2012.

IEC 60947-5-1 Ed. 3.1, Low-voltage switchgear and controlgear — Part 5-1: Control circuit devices and switching elements — Electromechanical control circuit devices, 2009.

IEC 60947-7-1 Ed. 3.0, Low-voltage switchgear and controlgear — Part 7-1: Ancillary equipment — Section 1: Terminal blocks for copper conductors, 2009.

IEC 61010-1 Ed. 3.0, Safety requirements for electrical equipment for measurement, control, and laboratory use — Part 1: General requirements, 2010.

IEC 61310-1 Ed. 2.0, Safety of machinery — Indication, marking and actuation — Part 1: Requirements for visual, auditory and tactile signals, 2007.

Page 74: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

IEC 61310-3 Ed. 2.0, Safety of machinery — Indication, marking and actuation — Part 3: Requirements for the location and operation of actuators, 2007.

IEC 61508 Ed. 2.0, [Series] Functional safety of electrical/electronic/programmable electronic safety-related systems, 2010.

IEC 61558-1 Ed. 2.1, Safety of power transformers, power supply units and similar — Part 1: General requirements and tests, 2011.

IEC 61800-5-2 Ed. 1.0, Adjustable speed electrical power drive systems — Part 5-2: Safety requirements — Functional, 2007.

IEC 62061 Ed. 1.2, Safety of machinery — Functional safety of electrical, electronic and programmable control systems, 2015, corrigendum 1, 2015.

NOTE: The IEC publishes consolidated editions of its publications with all the amendments and corrigenda included with the base document. For example:

Edition 1.0 is a base document without any amendments.

Edition 1.1 is the base 1.0 edition consolidated with one amendment.

Edition 1.2 is the base 1.0 edition consolidated with two amendments.

Edition 2.0 is the second edition of a base document. This may include new information combined as well as amendments from edition 1.x.

Edition 2.1 is the second edition of a document consolidated with amendment 1 to that edition.

K.1.2.4 IEEE Publications.

IEEE, 3 Park Avenue, 17th Floor, New York, NY 10016-5997.

IEEE 100 CD, The Authoritative Dictionary of IEEE Standard Terms, 2013.

ANSI Y32.2/IEEE 315, IEEE Graphic Symbols for Electrical and Electronics Diagrams (Including Reference Designation Letters), 1993.

IEEE 841, Petroleum and Chemical Industry — Premium-Efficiency, Severe-Duty, Totally Enclosed Fan-Cooled (TEFC) Squirrel Cage Induction Motors — Up to and Including 370 kW (500 hp), 2009.

K.1.2.5 ISO Publications.

International Organization for Standardization, ISO Central Secretariat, BIBC II, 8, Chemin de Blandonnet, CP 401, 1214 Vernier, Geneva, Switzerland.

ISO 7000, Graphical symbols for use on equipment — Registered symbols, 2014.

ISO 12100, Safety of machinery — General principles for design — Risk assessment and risk reduction, 2010.

ISO 13849-1, Safety of machinery — Safety-related parts of control systems — Part 1: General principles for design, 2006, corrigendum 1, 2009.

ISO 13849-2, Safety of machinery — Safety-related parts of control systems — Part 2: Validation, 2012.

ISO 13850, Safety of machinery — Emergency stop function — Principles for design, 2015.

K.1.2.6 NEMA Publications.

National Electrical Manufacturers Association, 1300 North 17th Street, Suite 900, Arlington, VA 22209.

Page 75: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

NEMA MG-1, Motors and Generators, 2014.

NEMA 250, Enclosures for Electrical Equipment (1000 Volts Maximum), 2014.

K.1.2.7 SEMI Publications.

Semiconductor Equipment and Materials International, 3081 Zanker Road, San Jose, CA 95134.

SEMI S2, Environmental, Health, and Safety Guideline for Semiconductor Manufacturing Equipment, 2010.

SEMI S9, Safety Guideline for Electrical Design Verification Tests for Semiconductor Manufacturing Equipment, 2001 (withdrawn 2007).

SEMI S22, Safety Guideline for the Electrical Design of Semiconductor Manufacturing Equipment, 2010.

K.1.2.8 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 50, Standard for Enclosures for Electrical Equipment, 2007, revised 2015.

UL 62, Standard for Flexible Cord and Fixture Wire, 2010, revised 2014.

UL 248-14, Standard for Low-Voltage Fuses — Part 14: Supplemental Fuses, 2000, revised 2015.

UL 489, Standard for Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures, 2009, revised 2014.

UL 498, Standard for Attachment Plugs and Receptacles, 2012, revised 2014.

UL 508, Standard for Industrial Control Equipment, 1999, revised 2013.

UL 508A, Standard for Industrial Control Panels, 2001, revised 2014.

UL 651, Standard for Schedule 40 and 80, EB and A Rigid PVC Conduit and Fittings, 2011, revised 2014.

UL 758, Appliance Wiring Material, 2014, revised 2014.

UL 1004-1, Standard for Rotating Electrical Machines, 2012, revised 2015.

UL 1077, Standard for Supplementary Protectors for Use in Electrical Equipment, 2005, revised 2015.

UL 1682, Plugs, Receptacles, and Cable Connectors of the Pin and Sleeve Type, 2013, revised 2013.

UL 60950-1, Information Technology Equipment — Part I: General Requirements, 2007, revised 2014.

UL 2237 Outline, Outline of Investigation for Multi-Point Interconnection Power Cable Assemblies for Industrial Machinery, 2015.

UL 2238, Cable Assemblies and Fittings for Industrial Control and Signal Distribution, 2011.

IEC/UL 6101061010A-1, Electrical Equipment for Measurement, Control and Laboratory Use — Part 1: General Requirements, 2014.

UL 61010-1, UL Standard for Safety Electrical Equipment For Measurement, Control, and Laboratory Use — Part 1: General Requirements, 2004, revised 2015.

Submitter Information Verification

Page 76: Second Revision No. 1-NFPA 79-2017 [ Global …...This detail is to revise the text in Section 5.3.3.1 (3) on SR-53 5.3.3.1 (3) Be provided with a permanent means permitting it to

Submitter Full Name: Mark Cloutier

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 18 14:11:19 EST 2017

Committee Statement

Committee Statement:

The TC updated edition dates and corrected the title of ANSI B11.0 which addressed the CC comments.

Response Message:

Public Comment No. 29-NFPA 79-2016 [Section No. K.1]