Upload
dacrys
View
214
Download
2
Tags:
Embed Size (px)
DESCRIPTION
a
Citation preview
Domestic Air Conditioner
SERVICE MANUAL
Models : H2SM-14HC03/R2
Features
Comfortable:wide-angle airflowHealth air purifying Quiet operation Engergy efficient Wide variety of functions
Serial Number: Versio n:00.00 Edition: 2005-3-25
H2SM-18HC03/R2
Content 1. Description of product model coding and series introduction 2. Specifications 3. Curves of performance 4. Description,net dimensions and functions of main component s
and accessories 5. Brief introduction to electrical control functions 6. Abnormity diagnose 7. Wiring diagram 8. Circuit diagram
9.Trouble shooting 10. Refrigerating cycle diagram 11. Noise level test chart and air veloc ity distribution 12. Installation manual
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Description of product modelcoding and series introduction
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
No.
1
2
3
Operating condition
Norminal cooling
Norminal heating
Norminal electricalheating
indoor air statusDBOC WBOC
20OC 15OC
DBOC WBOC
7OC 6OC
outdoor air status
--- --- --- ---
B.Standard Situation/Conditions
27OC 19OC 35OC 24OC
A. Description of coding rules of unit model
The type of power supplyDeveloping sequence
Function code H-heat pumpe-electric aided heating
numbers based on thousand unitThe structure code of indoor & outdoor unit
H-Abbreviation of Haier
3 4 5 6 7 81 9 10
C-cooling only
Examples:
H2SM-18HB03/R2,It represents wall-mounted multi-type split type room air conditioner.The cooling capacity is 18000BTU/h,and the power supply is 220-230V/50Hz,”B” means the improvement
2
The quantity of the indoor unit is two
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
C.Series brief introduction
1.comfortable:wide-angle airflow The vertical dual-flap and horizontal wide-angle louvers ensure the cool(warm air reaches every corner of the room.
2.Health air purifying and negative ion function An air purifying filter with deodorizing and disinfecting functions keeps the air clean and users healthy.The negative ion generator can produce the negative ion that make the air fresher and cleaner.
3.Quiet operation Fan With Random-pitched Blades. Random-pitched blades help reduce operating noise while maintaining a high airflow rate.
2.Engergy efficient The design of inner-grooved copper tube greatly increases the refrigerant contact area and the efficiency of cooling/heating functions.
5.Convenience Auto restart and washable panel: The grille can be removed easily and washed when necessary.Any series have the function then even if the power falls when the unit is operating unit will automatically return to the operating settings in use before the power failure when power is restored.
6.Wide variety of functions 24-Hour Timer: 24-hour timer allows users to select the exact time they would like the air conditioner to turn on and to turn off.Timers on previous models operation based on the number of hours of desired operation.
7.Night-set models When the air conditioner is operationg on the timer-off circuit.The preset room temperature gradually rises(going down in heating)before the unit stops as shown delow.Users can sleep comfortably without sudden change in temperature.
8.Program”dry” This function automatically reduces the level of humidity while maintaining the preset indoor temperature.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
CURVES OF PERFORMANCE
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Performance Curve Return Gas Temperature
35
Model 39A173A
Subcooling
8.3
Power Supply
220-230V / 50Hz / 1PH
Run Capacitor
25 μF / 370 VAC Ambient Temperature
35
Cond. Temperature
800970
114013101480165018201990216023302500
-8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
Cap
acit
y (K
cal/
Hr)
455055
60
550585620655690725760795830865900
-8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
Pow
er (W
atts
)
2.502.652.802.953.103.253.403.553.703.854.00
-8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
Cur
rent
(A
mps
)
20.023.527.030.534.037.541.044.548.051.555.0
-8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
Evaporating Temperature( )
Flow
(K
g/H
r)
C
C
C
C
OC
OC
OC
OC
50
55
60
OC
OC
OC
OC
45
5045
55
60
OC
OC
OC
OC
60O
C
55OC
50OC
OC45
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Performance Curve Return Gas Temperature 35
Model 44A233ASubcooling 8.3
Power Supply 220-230V / 50Hz / 1PH
Run Capacitor 40 uF / 370 VAC Ambient Temperature 35
Cond.Temperature
1500
190021002300250027002900310033003500
Capa
city
(Kca
l/Hr)
750790830870910950990
Pow
er(W
atts
)
3.33.53.73.94.14.34.54.74.95.15.3
Curre
nt(A
mps
)
38.041.244.447.6
57.2
70.0
Evaporating Temperature( )
Flow
(Kg/
Hr)
C
C
C
55 C
C60
C50
C45
55 C
C60
C50
C45
C45C50
55 CC60
C45C50
55 C
C
60
1700
0 1 2 3 4 5 6 7 8 9 10 11 12- 1
0 1 2 3 4 5 6 7 8 9 10 11 12- 1
0 1 2 3 4 5 6 7 8 9 10 11 12- 1
0 1 2 3 4 5 6 7 8 9 10 11 12- 1
50.854.0
60.463.666.8
107011101150
1030
C
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
DESCRIPTION, DIMENSION
& FUNCTION OF MAIN
COMPONENTS AND ACCESSORIES
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Description and function of main components and accessories
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
795
26
5
182
Net dimensions for outdoor unit
583815
869
68
0
319.5352
295
Net dimensions for indoor unit
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
BRIEF INTRODUCTION TO
ELECTRICAL CONTROL FUNCTION
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2314
one. Temperature Control Function In temperature control function, the operation frequency of outdoor unit is determined based on room temperature and the set temperature. In automatic fan speed mode, indoor fan is controlled based on the need of temperature control In heating mode, indoor fan is controlled based on the temperature of coil. 1-1-1.Specification of Indoor Ambient Temperature Sensor In case of short circuit or open circuit, indicator lamp alarms and indoor fan stops. When normal condition is resumed, fan will automatically restart and operate normally. Short Circuit: Temperature: over 126oC, Hexadecimal System: over F8H, Resistance: below 0.65K,Voltage: over 4.85V. Normal Temperature: Temperature: 25 oC, Hexadecimal System: 40H, Resistance: 23K, Voltage: 2.33V. Open Circuit: Temperature: below -31 oC, Hexadecimal System: below 08H, Resistance: below 620K Voltage: below 0.15V. B Parameter = 4200 R (25 oC) = 23K 1-1-2 Specification of Indoor Coil Temperature Sensor B Constant Number = 3700 R (25 oC) = 10K1-1-3 When heating operation starts and indoor fan stops or when within 30s of indoor fan starts after heating operation starts, the resistant of indoor ambient temperature sensor is ignored. (to avoid the impact of heat exchanger temperature over it.) When forced operation ends after start-up, temperature zone control begins. 1-3. Set Temperature Correction Set temperature is corrected according to unit model, operation mode, fan speed and whether it is in power operation. Fan speed correction is available only during low and mid heating operation. 1-4. Temperature Zone Control 1-4-1.ErrorTemperature zone error is calculated as per the following formula:In Heating Mode: E = (Remote Control Set Temperature + Correction Value) – Indoor Temperature In Cooling & Dehumidification Mode: E = Indoor Temperature - (Remote Control Set Temperature +
Correction Value) 1-4-2 Compressor Shutdown E is negative and |E|> T
Heating Cooling T TCHAHL 0.67 TCHACL 0.33
After change of T TCHAHH 0.67 TCHACH 1 T Change Condition When operation starts E 3.0 ,
Compressor shuts down after continuous testing for 120s, At the beginning of operation, with reference to the conditions given in above table, it operates based on the parameters after change of T until compressor shuts down for the first time. In the time period between compressor shutdown and restart, it operates based on T. (except in dehumidification mode) Compressor starts at the beginning of operation or upon switch of operation mode (except standby ends) or when E (error) > - T. When compressor is operating, remote control set temperature is changing towards the direction of compressor shutdown and when it is below – T, compressor will shut down. 2-4-3. Compressor Operation Compressor restarts when E (error) > - T+0.67 and when 3 mins standby is over.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2415
two. Indoor Fan Control
2-1. Heating 2-1-1. Warm Start Two. Cold Air Control in Heating Mode
Heat Exchange Temperature:
THHOT3
37.0
THHOT2
35.2
THHOT1
25.2 4mins
THHOTR
16
Stop SLO LO Set LO SLO Stop Conduct indoor fan control as per the above diagram and the heat exchange temperature. 1. Judge wind speed when heat exchange temperature is rising:
Fan is at super low level when heat exchange temperature is below 35.2 . Fan will stop upon initially energized into heating mode or after defrosting, or when heat exchange temperature is lower than 25.2 . Fan is at super low level when temperature is higher than 25.2 but lower than 35.2
. ;Fan is at low level when heat exchange temperature is between 35.2 and 37 ;Fan will operate as per setting when heat exchange temperature is above 37 .
2. Judge wind speed when heat exchange temperature is falling: Fan is at low level when heat exchange temperature is below 35.2 but above 25.2 ;Fan is at super low level and will maintain the mode when heat exchange temperature is lower than 25.2 Fan is at super low level upon initially energized into heating mode or after defrosting, or heat exchange temperature is lower than 25.2 but higher than 16 ; Fan will stop when heat exchange temperature falls below 16 .
3. Wind speed is at super low or low level when heat exchange temperature is rising. If heat exchange temperature fails to enter the next temperature zone after 4 mins while wind speed rises to the next stage, it is necessary to maintain the set wind speed for 4 mins before it is adjusted based on heat exchange temperature.
4. When heat exchange temperature is falling, wind speed will return to set speed if low wind level is maintained for over 4 mins.
2-1-2. 3 mins standby period when compressor shutdown. 1. When compressor shuts down temperature sensor is off , airflow is low for the initial 20s then reduced to super low (When in silent operation, it is SSLO); 2. Wind is maintained at super low level in the standby period in heating mode Compressor stops during mode switch. .3. Remote control shut down and stop indoor fan. 2-1-3. Compressor Restart When warm start, airflow is at remote control set level. When in automatic airflow mode, airflow is determined based on temperature. Refers to temperature zone control functions. 2-2 Cooling Airflow is different when airflow is set at high, mid and low level. When in automatic airflow mode, airflow is determined as per temperature. Refers to temperature control functions. 2-3. Dehumidification 2-3-1. Compressor is off and is in 3 mins standby.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2516
Fan will stop if compressor stops Fan is at super low level upon the end of 3 mins standby. Compressor is on after 3 mins standby. 2-3-2. Compressor is on. When airflow is set at high, mid or low level, fan will operate as per the setting. When in automatic airflow mode, airflow is determined as per temperature.
three. Timed Operation Time counting will start based on the difference of timer clock and current clock. In timed operation, display panel timer lamp is on. 3-0-1. Timer Off When timer off is set, panel timer lamp is on and unit will stop operation as per the timing. 3-0-2. Timer On If timer on is set, when unit is off, panel timer lamp will be on and unit will resume operation as per the timing and in set mode. Execution sequence is based on the setting. Four . Sleep Operation When remote control set sleep mode, timer lamp is on. 4 1. In cooling/dehumidification mode, set temperature will rise 1oC after 1 hour operation and another 1oC after the second hour. The unit will stop after another 6 hours. 4 2. In heating mode, set temperature will fall 2 oC after 1 hour and another 2 oC after the second hour and will rise 1oC after another 3 hours and the unit will stop after another 3 hours. 4 3 If airflow of indoor fan is high before setting sleep mode, then it will turn into mid level after sleep mode is set. If airflow of indoor fan is mid before setting, it will turn into low level after setting. If airflow of indoor fan is low before setting, then it will not change after setting. Five . Automatic Operation
4-1. Automatic Operation Mode: On entering this mode, main control unit will decide the corresponding operation mode as per room
temperature to maintain the set temperature Set temperature is 23 in heating mode and 26 in cooling mode. .
Upon initial startup, the unit will enter heating mode if room inlet air temperature is equal to or lower than 23 or it will enter cooling mode if temperature is higher than 23 .
When entering heating mode, the unit will operate as per heating program set temperature is 23Upon reaching temperature where compressor stops operation, compressor will stop and standby for 3 mins. In case it detects that inlet air temperature is higher than 27 15 mins after compressor stops, the unit will enter cooling mode. Otherwise, the unit will remain in heating mode.
When entering cooling mode, the unit will operate as per cooling program set temperature is 26 .Temperature difference compensation is automatically cancelled. Upon reaching temperature where compressor stops operation, compressor will stop and standby for 3 mins. In case it detects that inlet air temperature is equal to or lower than 23 15 mins after compressor stops, the unit will enter heating mode. Otherwise, the unit will remain in cooling mode.
If the unit changes into automatic mode from any other mode and if the operation mode is changed (detect before operation), the unit will stop for 3 mins and it will operate based on inlet air temperature after 3 mins.
Six . Trial OperationTrial operation will end after 30 mins, after which unit shuts down. In trial operation, the unit will quit trial operation mode upon reception of signal.
Compressor Stop Protection:
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2617
Eight . EEPROM Control When outdoor unit is supplied with power, if there is any inconsistency between EEPROM parameter and
checksum, EEPROM error.
When indoor unit receives EEPROM error signal from outdoor unit, it will display outdoor unit EEPROM error.
At this time, control and emergency operation are not acceptable.
It can only be cancelled through power off.
Nine . Error Detect Method 9-1. Indoor Temperature Sensor Error
In operation, an error occurs if the temperature is above 126 oC or below – 31oC.
Operation will resume automatically when temperature is outside the above range.
9-2. Heat Exchange Temperature Sensor Error
In operation, an error occurs if the temperature is above 196 oC or below – 53oC.
Operation will resume automatically when temperature is outside the above range.
In error condition, low load protection is cancelled.
9-4. Transmission Error
Based on the condition of communication between indoor and outdoor unit, in case outdoor unit fails to
receive signal within 20s after indoor unit sends out signal, transmission is abnormal. (except in the period of
first 2 mins when power is supplied.). It is confirmed as transmission error when outdoor unit receive the error
signal.
Transmission error is removed by stopping operation.
Ten . Special Function
10-1. Power-Off Compensation
a Entry Condition: Press sleep key 10 times in 7s and buzzer gives out 4 sounds and save the current status
into indoor unit EEPROM upon the entry.
b. On entering power-off compensation operation, indoor unit operates as per the following procedures:
Remote control emergency signal, and operates as per condition set by remote control and emergency setting
and save the current status into indoor unit EEPROM.
Main unit will operate as per condition set on panel board. And save the current status into indoor unit
EEPROM.
c. Exit Condition: Press sleep key 10 times in 7s and buzzer gives out 2 sounds
d. If timer and sleep features are set under power-off compensation condition, main unit memory is in a state
of shut-off if power is off and on again.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2718
Eleven . Error Presentation Mode 11.1 Three Indicator Error Code
Error Display
Error Conditions PS Timer Operation
Operation Heating Cooling
Indoor
Outdoor
Autom
atic
Reset
Cause
Indoor Senistor Error * * 1. Connector loose contact or ambient
temperature sensor error.
Indoor Heat Exchange Senistor Error
* * 1. Connector loose contact or coil sensor error.
Outdoor Senistor Error * * 1. Connector loose contact or sensor error
*1. There is large interference source around or wiring error. Transmission Error
* 2. Wiring error or control panel error.
* 1. Whether control panel is damaged. EEPROM Error
* 1. Whether control panel is damaged.
Indoor Fan Error *
Note On Blink Off * This function is available.
Twelve . Emergency Switch When shutdown, press emergency switch down for less than 5s, the unit will start emergency operation. When shutdown, press emergency switch down for more than 5s but less than 10s, the unit will start trial operation. When shutdown, press emergency switch down for more than 10s but less than 15s, it will demonstrate the previous error. When shutdown, press emergency switch down, the panel will display automatic operation. When shutdown, press emergency switch down for less than 15s, or remove hand from emergency switch, the unit will not accept remote control signal. Unit enters shutdown condition after 15s. Unit can receive remote control signal after 15s. Press emergency switch during operation, air-conditioner will shut down., During operation, if error occurs, press emergency switch to shut down the unit to clear error condition. During error presentation, press emergency switch and error presentation will end. During operation, if emergency switch is pressed continuously (press and hold) in normal or abnormal condition (such as tact switch short circuit) or in error presentation condition, the unit can also receive remote control signal. Error Record Presentation Mode: When press and hold switch for 10s it gives out 3 sounds, release switch to enter error record presentation mode. Press and hold switch for 15s, panel display is off and error record presentation mode is cancelled. Previous alarm information will be sent to display panel for status display. Error record presentation mode is cleared after 10s. (Error record presentation mode is only displayed for 10s.) During the presentation, no remote control signal except shutdown signal is accepted. There is no presentation when no error occurs, only buzzer utters sound.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2819
Outdoor PCB Function Manual 1. Single-unit cooling operation
1.1When the single unit’s indoor unit gives a cooling signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan operates 1
second before the compressor operates.
1.2When changed from heating to cooling, the compressor stands by for 3 minutes, the
outdoor fan operates to blow off remaining heat and stops 30 seconds later.
1.3When the outdoor ambient temperature T1 38 , the outdoor fan runs at the high
speed. There is a return difference of 2 for the change between high and medium
speed.
When the outdoor ambient temperature T1 26 , the outdoor fan runs at the low
speed. There is a return difference of 2 for the change between low and medium
speed.
When the outdoor ambient temperature T1 8 , the outdoor fan is in a cycle of 1
minute stop and 3 minute run. There is a return difference of 2 for the change
between low speed and run and stop.
1.4Once the fan operates in a mode, it must operate for more than 45 seconds.
There is a temperature cut-off protection: when the indoor coil temperature higher than
T_CPS (68 ) and maintains for 10 seconds, both the compressor and outdoor fan stop.
The compressor will not restart in 3 minutes until the coil temperature lower than T_CP
R(50 ). The indoor fan is controlled the same as the thermostat is OFF.
2. Double-unit cooling operation
2.1When the indoor unit gives out a double unit cooling signal, outdoor compressor A starts
cooling operation. During the operation, the outdoor fan runs 1 second before compressor
A operates, 20 seconds later, outdoor compressor B starts cooling operation.
2.2Once a compressor starts, the other compressor will not start in 20 seconds from the
start.
2.3 When changed from heating to cooling, the compressor stands by for 3 minutes. When
both compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates.
The status of the fan depends on the number of the compressors that operate.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
2920
2.4 When the outdoor ambient temperature T1 30 , the outdoor fan runs at the high
speed. There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1 23 , the outdoor fan runs at the low
speed. There is a return difference for the change between low and medium speed;
When the outdoor ambient temperature T1 5 , the outdoor fan is in a cycle of 1
minute stop and 3 minute run. There is a return difference of 2 for the change
between low speed and run and stop.
2.5Once the fan operates in a mode, it must operate for more than 45 seconds.
2.6 There is a temperature cut-off protection: when a indoor coil temperature higher than
T_CPS (68 ) and maintains for 10 seconds, the corresponding compressor stops. The
compressor will not restart in 3 minutes until the coil temperature lower than T_CP R(50 ).
The indoor fan is controlled the same as the thermostat is OFF.
2.7 In the case of double-unit cooling, one compressor stops and it changes to the
single-unit operation. The fan is controlled in the single-unit operation mode. It stops 30
after blowing off the remaining heat only if both compressors turn off at the same time.
3.Single unit heating operation:
3.1 When the single unit’s indoor unit gives a heating signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan and 4-way
valve operate 1 second before the outdoor fan operates.
3.2. When changed from cooling to heating, the compressor stands by for 3 minutes, the
outdoor fan stops.
3.3 When the outdoor ambient temperature T1 3 , the outdoor fan runs at the high
speed. There is a return difference of 2 for the change between high and medium
speed.
When the outdoor ambient temperature T1 13 , the outdoor fan runs at the low speed.
There is a return difference of 2 for the change between low and medium speed.
3.4. Once the fan operates in a mode, it must operate for more than 45 seconds.
3.5. There is a high temperature protection and a temperature cut-off protection.
High temperature protection: When the indoor coil temperature higher than T_OFS (56 ),
the outdoor fan stops; when the coil temperature falls to T_OFR (52 ), the outdoor fan
restarts. The outdoor fan stops for more than 45 seconds.
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
3021
High temperature cut-off protection: When the indoor coil temperature higher than T_CPS
(68 ) and maintains for 10 seconds, both the compressor and outdoor fan stop, and the
indoor fan operates as the thermostat is Off. The compressor will not restart in 3 minutes
until the coil temperature lower than T_CP R(50 ).
4. Double-unit heating operation
4.1 When the double-unit’s indoor unit gives out a heating signal, outdoor compressor A
starts heating operation. During the operation, outdoor compressor A and the 4-way valve
operate 1 second before the fan starts, 20 seconds later, outdoor compressor B starts
heating operation.
4.2Once an outdoor compressor starts, the other compressor will not start in 20 seconds
from the start.
4.3 When changed from cooling to heating, the compressor stands by for 3 minutes. When
both compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates.
The status of the fan depends on the number of the compressors that operate.
4.4 When the outdoor ambient temperature T1 10 , the outdoor fan runs at the high
speed. There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1 20 , the outdoor fan runs at the low
speed. There is a return difference for the change between low and medium speed.
4.5Once a fan operates in a mode, it must operate for more than 45 seconds.
5. Cooling and heating operations take place at the same time:
5.1 When one of the indoor units gives out a cooling signal and another unit gives out a
heating signal at the same time, the outdoor fan operates at the low speed.
5.2 When the indoor unit gives the value of coil temperature, the outdoor fan runs at the low
speed if the heating outdoor unit judges high load.
5.3When outdoor ambient temperature T1 28 , there is no heating operation.
5.4When outdoor ambient temperature T1 7 , there is no cooling operation.
5.5Once a compressor starts, the other compressor will not start in 20 seconds from the start.
6.Single-unit heating operation with heat load:
6.1 In the single-unit heating operation, the indoor unit gives out the value of the coil
temperature, and the outdoor unit judges whether to start in the high load protection operation
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
3122
based on the value of the coil temperature it has received. If the conditions for high load
protection are met, the outdoor fan stops immediately. It will restart 45 seconds later if the
signal for the outdoor heat load disappears. Otherwise, the outdoor fan will continue to stop
until the signal for the outdoor heat load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56 ), the
outdoor fan stops; when the coil temperature falls to T_OFR (52 ), the outdoor fan restarts.
The outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the coil temperature higher than T_CPS (68 ) and
maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor fan
operates as the thermostat is Off. The compressor will not restart in 3 minutes until the coil
temperature lower than T_CP R(50 ).
6.2 In the single-unit heating operation, the current in the compressor is larger than 4.0 A(for
Model 14)(4.8A for Model 18), and the outdoor fan stops. 45 seconds later, the current in the
compressor is less than 3.5A(for Model 14)(4.3A for Model 18), and the outdoor fan operates
in normal condition(the compressor does not detect current within 30 seconds after its start),
the current in the compressor is larger than 3.5A(for Model 14)(4.3A for Model 18) and less
than 4.0A(for Model 14)(4.8A for Model 18), and the outdoor fan does not restore.
7.Double-unit heating operation with heat load
7.1 In the double-unit heating operation, the indoor unit gives out the value of the coil
temperature, and the outdoor unit judges whether to start in the high load protection operation
based on the value of the temperature it has received. If the conditions for high load protection
are met, the outdoor fan stops immediately. It will restart 45 seconds later if the signal for the
outdoor heat load disappears. Otherwise, the outdoor fan will continue to stop until the signal
for the outdoor heat load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56 ),
the outdoor fan stops; when the coil temperature falls to T_OFR (52 ), the outdoor fan
restarts. The outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the coil temperature higher than T_CPS (68 )
and maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor
fan operates as the thermostat is Off. The compressor will not restart in 3 minutes until the
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
23
coil temperature lower than T_CP R(50 ).
7.2 When the outdoor single-unit gives out the heat load signal, the outdoor fan stops
immediately, 45 minutes later, the heat load signal disappears, and the outdoor fan
operates.
7.3 In heating operation, any of the current in the compressor is larger than or equal to 4.0
A (for Model 14, 4.8A for Model 18), and the outdoor fan stops. The current in the
compressor is less than or equal to 3.5A (for Model 14, 4.3A for Model 18), and the
outdoor fan restores (the compressor does not detect current within 30 seconds after its
start), the current in the compressor is larger than 3.5A (for Model 14, 4.3A for Model 18)
and less than 4.0A(for Model 14, 4.8A for Model 18), and the outdoor fan does not restore.
8. Current peak protection
8.1. The current in the compressor is larger than 6.8A(for Model 14, 8.2A for Model 18) for
more than 5 seconds, The compressor which has the highest current will stop(the
compressor does not detect current within 10 seconds after its start) and 3 minutes later it
will continue to operate.
8.2. The compressor will no longer operate if overcurrent protection occurs 4 times in a row
within 30 minutes, and the output transformer signal fails. In the double-unit operation, if
one of the compressors stops due to the current too high, the other system is a single
system.
9. Single-unit defrosting operation (outdoor judgement)
Defrosting control
9.1. Conditions for starting in the defrosting operation
The heating compressor starts and operate continuously for 10 minutes. After the
compressor has been operating for 45 minutes in total, detecting the defrosting sensor TE
(detecting the frosting of the outdoor heat exchanger) and the outdoor ambient
temperature sensor TA for straight 2 minutes, provided the following conditions are met, it
will start for the defrosting operation: TE C TA
Where,
C: TA 0
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
3324
C=0.8
TA 0
C=0.6
=6
In the place where it tends to frost, it is preferred to choose H. In the place where it does not
intend to frost, it is preferred to choose L. It is set M at delivery.
During the defrosting operation, the temperature control starts -15 C TA -2
9.2. Interval of defrosting
When the result of the calculation from C TA falls in the range of -15 C TA ,
the interval between two defrosting operations is 45 minutes.
When the result of the calculation from C TA falls in the range of C TA <-15 , the
interval between two defrosting operations is 55 minutes.
9.3. Defrosting operation
At the beginning of defrosting, the compressor is halted for the first one minute, but the
outdoor fan operates, 50 seconds later, the 4-way valve is OFF.
9.4. Once starting to defrost, the compressor must be guaranteed at least 2 minutes of
operation before canceling defrosting. As for the conditions to cancel defrosting, it will restore
to the heating operation from the defrosting operation as long as any of the following
conditions is met.
(1) . The outdoor heat exchanger temperature is above 7 degrees for consecutive 80
seconds.
(2) . The outdoor heat exchanger temperature is above 5 degrees for consecutive 12
seconds.
(3) . The defrosting operation has lasted 9 minutes.
9.5 After the conditions for cancellation of defrosting are met, the following operations will
follow:
The compressor stops, the outdoor fan starts, 50 seconds later, the 4-way valve is engaged,
and 60 seconds later, the compressor operates.
10. Double-unit defrosting operation
After receiving the signal to stop the indoor unit during the defrosting period, the unit must not
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
3425
be turned off until the outdoor defrosting lasts more than 2 minutes.
When the double units are activated for defrosting, the activation of compressor B is 20
minutes later than that of compressor A.
Conditions for ending defrosting: It will restore to the heating operation from the defrosting
operation as long as any of the following conditions is met.
(1) . The temperatures on both outdoor heat exchangers are above 7 degrees for consecutive
80 seconds.
(2) . The temperatures on both outdoor heat exchangers are above 5 degrees for consecutive
12 seconds.
(3) . The defrosting operation has lasted 9 minutes.
The starting conditions and control process for the double-unit are same as that for single-unit
defrosting, the only difference is that the activation of compressor B lags that of compressor A.
11. Alarming operation
1. When the whole unit is in normal operation, the alarm light is always on, but does not
flash.
2. When the outdoor temperature sensor short-circuited or disconnected, the outdoor fan
always operates at the medium speed and will restore automatically after the sensor
comes to normal.
3. When the temperature sensor short-circuited or disconnected or the current transformer
fails, the alarm light flashes in the following manner; when the current transformer fails,
the signal is sent to the indoor unit that operates abnormally, and the corresponding
indoor unit indicates trouble:
Additional codes for overcurrent
LED light flashes once outdoor Eeprom in trouble
LED light flashes twice outdoor ambient temperature sensor in trouble
LED light flashes 3 times communication with indoor unit A in trouble
LED light flashes 5 times outdoor unit A’s coil in trouble
LED light flashes 6 times outdoor unit A’s CT current too high
LED light flashes 7 times communication with indoor unit B in trouble
LED light flashes 9 times outdoor unit B’s coil in trouble
LED light flashes 10 times outdoor unit B’s CT current too high
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
3526
H2SM-14/18C03/R2
2 8
Codes and Description Code indication
indoor Description
Outdoor led1 blinks times
Power timer operate Operate heating cooling
★ ■ ■ Room temperature sensor failure --
★ □ □ Heat-exchange sensor failure --
★ □ ★ Indoor EEPROM error ---
■ □ ★ Indoor fan motor malfunction --
Indoor
Malfunction
■ ■ ★ Communication Error (between indoor and outdoor unit) 3 or 7
outdoor EEPROM error 1
★ □ ■ Outdoor Senistor Error 2
outdoor unit A’s coil sensor failure 5
Outdoor
Malfunction
outdoor unit B’s coil sensor failure 9
explanation □on★flash■off
Trouble Shooting ★ ■ ■: Room temperature sensor failure CN8 ★ □ □: Heat-exchange sensor failure CN8
YES
NO
YES
whether terminal CN8 on
indoor PCB contact wellt?
Pull out the terminals on the indoor mainboard and
reinsert them
Pull the sensor out of the mainboard
1) Measure the value of resistance Between its two
jumpers
2) Measure the temperature at the room temperature
sensing head.
Check the value of the
sensor to see whether the
sensor is damaged or not?
NO Sensor is broken,replace it with new sensor
The indoor PCB is broken, replace with new indoor PCB
H2SM-14/18C03/R2
2 9
★ □ ★: Indoor EEPROM error: Replace the PCB of indoor unit ■ □ ★:Indoor fan motor malfunction
Yes
Yes
YES
NO
whether terminal CN7
and CN11 on indoor PCB
well inserted or not?
Pull out and reinsert the terminals
Electrify the machine again and turn it on in the cooling
operation, Measure voltage between the positions 1 ( red
wire) and 5( black wire) of Terminal CN1 on the indoor PCB
NO the indoor pcb is damaged and need replace . the voltage is about
90-200vac
check whether motor
can run when
turn on the unit
the indoor motor is damaged and need
replace
NO
When motor is running Measure
whether there is voltage
pulse(0-5VDC) between the
positions 2 (middle wire) and
3( black wire) of Terminal CN7
on the indoor PCB
the indoor motor is damaged and need
replace
the indoor pcb is damaged and need replace
NO
H2SM-14/18C03/R2
3 0
LED1 of outdoor pcb flashes once: outdoor EEPROM error: Replace the PCB of outdoor unit, ★ □ ■ LED1of outdoor pcb flashes twice: Outdoor ambient Sensor failure CN1,
YES
NO
YES
whether terminal CN1 on
outdoor PCB contact well?
Pull out the terminals on the outdoor mainboard and
reinsert them
Pull the sensor out of the mainboard
3) Measure the value of resistance Between its two
jumpers
4) Measure the temperature of Outdoor ambient
Check the value of the
sensor to see whether the
sensor is damaged or not?
NO Sensor is broken,replace it with new sensor
The outdoor PCB is broken, replace a new one
H2SM-14/18C03/R2
3 1
■ ■ ★ :Communication fault between indoor and outdoor system
Yes NO Yes NO YES NO YES NO NO YES NO YES NO NO YES
Check whether the linking cable
between the indoor and outdoor
is not well connected
Reconnect the linking cable;
If unit A have error , please turn
on A and B both,check whether B
is fine
please reverse the outdoor
connecting wires A(C) and B (C)
between unit A and B,
if A is error and B is fine, indoor
unit A PCB is damaged
if A is fine and B has error,the
outdoor unit main PCB is damaged
please check whether the
connecting of L or N is reversed of
the two units
reconnect the L and N wires
Check whether the LED1
on the outdoor pcb is on the outdoor PCB is damaged
check whether the voltage of
CN7 in outdoor pcb is about
198-253VAC
check whether fuse of outdoor
pcb is broken reaplace the fuse with
T3.15A 250V
check whether the voltage of
CN4
in outdoor pcb is about 12VAC
check whether the wire from
terminal block to out pcb is well
connected
Reconnect the linking
wire
the transformer is bad
the outdoor PCB is damaged
H2SM-14/18C03/R2
3 2
LED1 of outdoor pcb flashes 5 or 9 times outdoor unit A or B’s coi sensor failure CN2
YES
NO
YES
whether terminal CN2 on
outdoor PCB contact well?
Pull out the terminals on the outdoor mainboard and
reinsert them
Pull the sensor out of the mainboard
5) Measure the value of resistance Between its two
jumpers
6) Measure the temperature of outdoor unit A or B’s coi
Check the value of the
sensor to see whether the
sensor is damaged or not?
NO Sensor is broken,replace it with new sensor
The outdoor PCB is broken, replace a new one
H2SM-14/18C03/R2
3 7
1 2 3 4 5 6 7 8
A
B
C
D
87654321
D
C
B
A
R1710k
C12102
C13104
C16102
12345CN13
13 2
XT1
8M
R1510k
R2410K
R184.7k
R41 1K
R5210K
+5
C5 102
R30
10K
R28 1K
R27 10K
+5
R29 10K
Q22SC2412
Q12SC24121
2CN9
12 ZJ1
123
CN7
+5
C43103
+5VR50 51K
R14 1K
+5
IC10
TLP3526
123
CN1 C392UF 450V +5V
R57220
R42
345
678 1
2
IC2
24C02
+5
E6 4.7UF/50V
E7 4.7UF/50V
1234
CN8
R44 1K
R45 1K
R35 3.3K 1%
R3420K 1%
+5
C2 104
R46
1KC15102
C10102
C9102
Q4
2SC2412
SDASCL
123456789 10 11 12 13 14 15 16
IC42003
CD
BA
+12
C4
104
+5
C6
103/
50V
E5100u/16v
C18104/50V
+5
R65
10k
C36
103/50v
.
RL1JQ1A-12V
+12
R20 10K
+5
R10 10K
1234
CN6
R36 1K
R37 10K +5V
R8 10K
+5VR7 10K
C14104
BUZ1
BEEP-PKM13EPY-4002
Q52SC2412
R11
10K
R49100
R9 4.7K
R11M
R31
10K
+12V
C41102
R2 10K
R3 1K
C1102
+5V
02 IRQ
07
08 PTF4/TBCH0
PTF3/TBCH3
48
49
PTH1/KBD3
PTH1/KBD4
03 RST
21 VSS GND
GNDAVSS/VRE45
60 PTC0
PTF710
13 PTE0/TXD
56 VSSA GND
14 PTE1/RXD
PTE2/TACH015
25 PTG2/KBD2
PTE3/TACH11617 PTE4/SS18
19
20
PTE5/MISO
PTE6/MOSI
PTE7/SPSCK
PTC401
26PA0
27 PA128 PA229 PA330 PA431 PA532 PA633
PA738 PTB4
R3210K
50 PTD4
34PTB0/ATD0
35 PTB1/ATD1
394041424346
PTB5/ATD5PTD6/ATD6PTB7/ATD7PTD0PTD1PTD2
47PTD3
VDDAREF 44
0605PTF1/TACH3
PTF2/TBCH2
57 CGMXFC
5455
VDDAVREFH
59
58
OSC1
OSC2
51PTD5PTD6/TACLK 52
53626364
PTD7PTC2/MCLKPTC3PTC5
PTF0/TACH2 04
22
3637PTB3/ATD3
PTB2/ATD2
VDD
09 NC
61
2324
PTC1
PTG1/KBD1PTG0/KBD0
1CON1(red)
C19
104 MC68HC908AB32
+12v
R13 10K R12
10K
R2610K
5v
1112
PTF5PTF6
C7
104/
50V
C3103
C29104/50v
R53 1K
SW1
220V
-N
R594.7K
1CON2(white)
220V-L
220V-N
R66 27
C25102/50VC27102/50VC26102/50V
C47104/50V
E13100u/25v
R69 10KR68 10KR67 10K
R70 560R71 560R72 560
53
52
51
R88 560
C38102/50V
61
R1610k
+5
R21 10K
SW2
R73
10K
D6 1N4007
1
CON5
R81
330K 1/4W
R82
330 1/4W
C22
102R85 2.2K 1/4W
R87
10K 1/4W
+5
R8610K 1/4W
R80
2.2k 1/4WIC12
TLP421
+5R83
2.2K
1
N
C49103/50V
R84 6.8K 2WLED1
GREEN
+5
Q92SC2412
IC14TLP371
+51
2 4
56
1
23
4
D81N4007
Q3
2SC2412
R4 4.7KR38 10K+5VR39 4.7K
Q10
2SC2412
D7
RLS4148
R64 10K
R40 10K+5V
R8922K
R91
4.7K
5vSW3
R9210K
R93
10K
Q11
2SC2412
D1-D4
IN4007
FUSE3.15A
T1
D5
1N4007
E82200UF/25V
Z1
561K
C40
104/275V CN4
B2P3-VH-A
IC9
7805CN3
0-171825-3
CN2
RTB-1.5-2P
C35104
+12+5
C17104
R51
3.3K
Q82SB1197
R54680
R433.3K
1234567
CN5
SJ20-07WX
R47 560 1/4W
R5 10K
C24
0.01u/275V120 1W
L1
125uH
+5
R58 10K
R25
10K
R610K
R97
10K
R95
10K
R96
10K
R98
10K
R33
10K
5v
+5V
+5V
E4100u/16v
C28104/50V
+5
E15
470UF/16V
C42104/50V
+12
E9
100u/25v
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
50
40
Warning and cautions:
1.1 The multi-mounted split unit adopts double separated cooling systems (A and B) that are not connected together. If
the refrigerant leaks, the leaking system of them must be determined. So we can solute the abnormality. And refill the
system that lacks refrigerant. I t will influence the effect if the A and B systems are wrongly estimated.
1.2 The maximum length of single connecting pipe is 7m. And the units can't run normally if the pipe is over required
length.
1.3 Fill refrigerant in accordance with the diagram below if the connec ting pipe is over 5m.
Length 5m 7m ----
Outdoor unitHeat exchanger
B indoor unitHeat exchanger
A indoor unitHeat exchanger
A Compressor
A 4-way valve B 4-way valve
B Compressor
Capillary tubeCapillary tube
Capillary tube
Capillary tube
3- way valve
Cooling
Heating
3- way valve
2- way valve
2- way valve
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
42
NOISE LEVEL TEST CHART
& AIR VELOCITY DISTRIBUTION
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
4843
Domestic Air Conditioner Model: H2SM-14HC03/R2 H2SM-18HC03/R2
Indoor unit B
Outdoor unit
NL
YEL/GRN
BRN
BLU{
PO
WER
YEL/GRNRED
WHT
BLK
WHTBLK
YEL/GRN
RED
13
2
12
3(C
)
YEL/GRNRED
WHT
BLK
WHT
BLK
YEL/GRN
RED
13
2
12
3(C
)
Indoor unit A
51