SERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE . THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY. HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON. Air Conditioner Edition:2006/1/10 MODEL: HSU- MODEL: HSU-07HV03/R2 HSU-09HV03/R2 HSU-12HV03/R2 HSU-18HV03/R2 HSU-22HV03/R2

SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Embed Size (px)

Citation preview

Page 1: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

SERVICE MANUAL

Air Conditioners

CAUTION

READ THIS MANUAL CAREFULLY TO

DIAGNOSE TROUBLE CORRECTLY

BEFORE OFFERING SERVICE .

THIS MANUAL IS USED BY

QUALIFIED APPLIANCE

TECHNICIANS ONLY. HAIER

DOES NOT ASSUME ANY

RESPONSIBILITY FOR PROPERTY

DAMAGE OR PERSONAL INJURY

FOR IMPROPER SERVICE

PROCEDURES DONE BY ONE

UNQUALIFIED PERSON.

Air Conditioner Edition:2006/1/10

MODEL: HSU-MODEL: HSU-07HV03/R2 HSU-09HV03/R2 HSU-12HV03/R2 HSU-18HV03/R2 HSU-22HV03/R2

zhanglizhi
zhanglizhi
REVISION 0
Page 2: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

health air purifying

quiet operation

super energy efficient

Main Specification

Cooling Capacity 2300W

Rated Power/Current(cooling) 680W/3.0A

EER: 3.38

Heating Capacity 2500W

Rated Power/Current(heating): 690W/3.1A

COP: 3.62

Air Volume(Indoor): 400m3/h

Power: 1PH 220-230V~ 50 Hz

MODEL: HSU-07HV03/R2

Page 3: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

health air purifying

quiet operation

super energy efficient

Main Specification

Cooling Capacity 3000W

Rated Power/Current(cooling) 860W/3.5A

EER: 3.49

Heating Capacity 3000W

Rated Power/Current(heating): 830W/3.5A

COP: 3.61

Air Volume(Indoor): 420m3/h

Power: 1PH 220-230V~ 50 Hz

MODEL: HSU-09HV03/R2

Page 4: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

health air purifying

quiet operation

super energy efficient

Main Specification

Cooling Capacity 4000W

Rated Power/Current(cooling) 1200W/5.0A

EER: 3.33

Heating Capacity 4200W

Rated Power/Current(heating): 1160W/5.8A

COP: 3.62

Air Volume(Indoor): 450m3/h

Power: 1PH 220-230V~ 50 Hz

MODEL: HSU-12HV03/R2

Page 5: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

health air purifying

quiet operation

super energy efficient

Main Specification

Cooling Capacity 5000W

Rated Power/Current(cooling) 1555W/6.9A

EER: 3.22

Heating Capacity 5500W

Rated Power/Current(heating): 1525W/6.8A

COP: 3.61

Air Volume(Indoor): 750m3/h

Power: 1PH 220-230V~ 50 Hz

MODEL: HSU-18HV03/R2

Page 6: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

health air purifying

quiet operation

super energy efficient

Main Specification

Cooling Capacity 6000W

Rated Power/Current(cooling) 1990W/8.9A

EER: 3.02

Heating Capacity 6500W

Rated Power/Current(heating): 2020W/9.0A

COP: 3.22

Air Volume(Indoor): 750m3/h

Power: 1PH 220-230V~ 50 Hz

MODEL: HSU-22HV03/R2

Page 7: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10

Safety Information

General Information

This Service Manual describes the operation,disassembly,troubleshooting,and repair of Haier Room Air

Conditioners,etc. It is intended for use by authorized servicers who troubleshoot and repair these units.

NOTE:It is assumed that users of this manual are familiar with the use of tools and equipment used to

troubleshoot and repair electrical,mechanical,and refrigeration systems;and understand the terminology

used to describe and discuss them.

Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure

to comply with safety information may result in severe personal injury or death.

Related Publications

This is a base service manual,covering a range of similar models.It is intended to be used in

conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.

General Precautions and Warnings

WARNING

To avoid risk of personal injury or death due to electrical shock,disconnect electrical power to unit

before attempting to service the unit.

WARNING

To avoid risk of personal injury or death due to electrical shock,DO NOT,under any circumstances,alter

the grounding plug .Air conditioner must be grounded at all times.Do not remove warning tag from power

cord.If a two-prong (non-grounding) wall receptacle is encountered,contact a qualified electrician and

have the receptacle replaced with a properly grounder wall receptacle in accordance with the National

Electrical Code.

WARNING

To avoid risk of personal injury or death due to electrical shock,grounding wires and wires colored like

grounding wires are NOT to be used as current carrying conductors.The standard accepted color coding

for ground wires is green or green with a yellow stripe.Electrical components such as the compressor

and fan motor are grounded through an individual wire attached to the electrical component and to

another part of the air conditioner.Grounding wires should not to be removed from individual components

while servicing,unless the component is to be removed and replaced.It is extremely important to replace

all removed grounding wires before completing service.

WARNING

To avoid risk of heat exposure,which may cause death or severe illness,air conditioner must be

monitored when malfunctions or shuts down.

Page 8: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

CONTENTS

1. SPECIFICATION....................................1

2. OPERATION........................................7

3. ELECTRICAL CONTROLL..............................33

4. TROUBLE SHOOTING................................60

5.INSTALLA TION.....................................62

6. CIRCUIT AND WIRING DIAGRAM.......................71

Air Conditioner Edition:2006/1/10

zhanglizhi
jykthwkf
Page 9: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner

SPECIFICATION

1

Edition:2006/1/10

zhanglizhi
zhanglizhi
zhanglizhi
zhanglizhi
Page 10: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Model HSU-07HV03/R2 Brand Mark HAIER

Cooling Capacity 2300W Frequency Range 50Hz

Rated Power/Current 680W/3.0A Power 1PH 220-230V~ 50 Hz

Max Power/Current 1050W/4.0A Cooling

EER 3.38 Model×Sectional Area

--------

Heating Capacity 2500W

Power Cord

Refer. No. --------

Rated Power/Current 690W/3.1ACompressor

manufacturer/Type

Max Power/Current 1300W/5.3A

Heating

COP 3.62

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R410A 650g

Operating temp. range -7OC-43OCAdditional Charge for

exhausting air. 0 g

H 1200 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1000 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L 950 r/min

Capilary

Refer No. ----

H 850 r/min Indoor ---- mm H ---- r/min

Height of rising

radiator slice Outdoor ---- mm

H ---- r/min Net 8.6kg

Outdoor

Velocity Indoor Weight

Gross 10.6kg

Net 28kg

Indoor 400 m3/hOutdoor Weight

Gross 30kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 778*197*250mm

Capacitor of Fan Motor: 2.5μF indoor Packaging Dimension(L×W×H) 865*272*330mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 780*245*540 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 908*342*619mm

Moisture Removal 1.2×10-3m3/h liquid /Gas pipe Diametre 6.35/9.52 mm

Model: YR-H65 standard Lenth 5mRemote

Controller Refer. No. 0010401540

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose ---- MPa

Appearance ----- Max. pressure at warm side 4.15 MPa

Climate Type T1 Max.pressure at cool side 4.15MPa

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-23 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32℃/ 223 Dry/Wet ball(indoor):27 / --Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor):24℃/18℃

Air Conditioner Edition:2006/1/10

2

zhanglizhi
zhanglizhi
zhanglizhi
RECHI/39A173AD&94K
zhanglizhi
----(poe)
zhanglizhi
1.4*550+1.4*1350
Page 11: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Model HSU-09HV03/R2 Brand Mark HAIER

Cooling Capacity 3000W Frequency Range 50Hz

Rated Power/Current 860W/3.5A Power 1PH 220-230V~ 50 Hz

Max Power/Current 1150W/5.0A Cooling

EER 3.49 Model×Sectional Area

--------

Heating Capacity 3000W

Power Cord

Refer. No. --------

Rated Power/Current 830W/3.5ACompressor

manufacturer/Type

Max Power/Current 1500W/6.3A

Heating

COP 3.61

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R410A 950g

Operating temp. range -7OC-43OCAdditional Charge for

exhausting air. 0 g

H 1250 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1050 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L 950 r/min

Capilary

Refer No. ----

H 850 r/min Indoor ---- mm , ---- r/min

Height of rising

radiator slice Outdoor ---- mm

L ---- r/min Net: 8.6kg

Outdoor

Velocity Indoor Weight

Gross 10.6kg

Net 31kg

Indoor 420 m3/hOutdoor Weight

Gross 32kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 778*197*250mm

Capacitor of Fan Motor: 2.5μF indoor Packaging Dimension(L×W×H) 865*272*330 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 780*245*540mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 908*342*619 mm

Moisture Removal 1.2×10-3m3/h liquid /Gas pipe Diametre 6.35/9.52 mm

Model: YR-H65 standard Lenth 5mRemote

Controller Refer. No. 0010401540

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose ---- MPa

Appearance ----- Max. pressure at warm side 4.15 MPa

Climate Type T1 Max.pressure at cool side 4.15MPa

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-23 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32℃/ 223 Dry/Wet ball(indoor):27 / --Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor):24℃/18℃

Air Conditioner Edition:2006/1/10

3

zhanglizhi
zhanglizhi
zhanglizhi
RECHI/44A233AJ-JEK
zhanglizhi
---(poe)
zhanglizhi
1.4*750+1.4*800
Page 12: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Model HSU-12HV03/R2 Brand Mark HAIER

Cooling Capacity 4000W Frequency Range 50Hz

Rated Power/Current 1200W/5.0A Power 1PH 220-230V~ 50 Hz

Max Power/Current 1500W/6.0A Cooling

EER 3.33 Model×Sectional Area

--------

Heating Capacity 4200W

Power Cord

Refer. No. --------

Rated Power/Current 1160W/5.8A Compressor

manufacturer/Type

Max Power/Current 1500W/6.3A

Heating

COP 3.62

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R410A 950g

Operating temp. range -7OC-43OCAdditional Charge for

exhausting air. 0 g

H 1350 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1200 r/min Lenth×Internal/External

Diametre

-----Indoor

Velocity

L 1150 r/min

Capilary

Refer No. -----

H 850 r/min Indoor ---- mm M ---- r/min

Height of rising

radiator slice Outdoor ------ mm

L ---- r/min Net 8.8kg

Outdoor

Velocity Indoor Weight

Gross 10.6kg

Net 31kg

Indoor 450 m3/hOutdoor Weight

Gross 32kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 795*182*265 mm

Capacitor of Fan Motor: 2.5¦ÌF indoor Packaging Dimension(L×W×H) 865*272*330 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 780*245*540mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 908*342*619 mm

Moisture Removal 1.6×10-3m3/h liquid /Gas pipe Diametre 6.35/9.52 mm

Model: YR-H65 standard Lenth 5mRemote

Controller Refer. No. 0010401540

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose ---- MPa

Appearance ----- Max. pressure at warm side 4.15 MPa

Climate Type T1 Max.pressure at cool side 4.15MPa

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-23 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32℃/ 223 Dry/Wet ball(indoor):27 / --Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor):24℃/18℃

Air Conditioner Edition:2006/1/10

4

zhanglizhi
zhanglizhi
zhanglizhi
MEIZHI/PA150X2C-4EN
zhanglizhi
500(poe)
Page 13: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Model HSU-18HV03/R2 Brand Mark HAIER

Cooling Capacity 5000W Frequency Range 50Hz

Rated Power/Current 1555W/6.9A Power 1PH 220-230V~ 50 Hz

Max Power/Current 2000W/9.2A Cooling

EER 3.22 Model×Sectional Area

--------

Heating Capacity 5500W

Power Cord

Refer. No. --------

Rated Power/Current 1525W/6.8A Compressor

manufacturer/Type

Max Power/Current 2000W/9.2A

Heating

COP 3.61

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R410A 1230g

Operating temp. range -7OC-43OCAdditional Charge for

exhausting air. 0 g

H 1350 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1250 r/min Lenth×Internal/External

Diametre

-----Indoor

Velocity

L 1100 r/min

Capilary

Refer No. -----

H 880 r/min Indoor 1.30 mm M ---- r/min

Height of rising

radiator slice Outdoor 1.55 mm

L ---- r/min Net 12kg

Outdoor

Velocity Indoor Weight

Gross 15kg

Net 39kg

Indoor 750 m3/hOutdoor Weight

Gross 44kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 850×305×230 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 960x310x370 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 820×290×650 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 890×340×710 mm

Moisture Removal 2.0×10-3m3/h liquid /Gas pipe Diametre 6.35/12.7 mm

Model: YR-H10 standard Lenth 5mRemote

Controller Refer. No. 0010401627

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose ---- MPa

Appearance ----- Max. pressure at warm side 4.15 MPa

Climate Type T1 Max.pressure at cool side 4.15MPa

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-23 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32℃/ 223 Dry/Wet ball(indoor):27 / --Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor):24℃/18℃

Air Conditioner Edition:2006/1/10

5

zhanglizhi
zhanglizhi
zhanglizhi
HITACHI/ASH201
zhanglizhi
500(poe)
Page 14: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Model HSU-22HV03/R2 Brand Mark HAIER

Cooling Capacity 6000W Frequency Range 50Hz

Rated Power/Current 1990W/8.9A Power 1PH 220-230V~ 50 Hz

Max Power/Current 2650W/14.0A Cooling

EER 3.02 Model×Sectional Area

--------

Heating Capacity 6500W

Power Cord

Refer. No. --------

Rated Power/Current 2020W/9.0A Compressor

manufacturer/Type

Max Power/Current 2650W/14.0/

Heating

COP 3.22

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R410A 1530g

Operating temp. range -7OC-43OCAdditional Charge for

exhausting air. 0g

H 1350 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1250 r/min Lenth×Internal/External

Diametre

-----Indoor

Velocity

L 1150 r/min

Capilary

Refer No. -----

H 880 r/min Indoor 1.30 mm M ---- r/min

Height of rising

radiator slice Outdoor 1.55 mm

L ---- r/min Net 12kg

Outdoor

Velocity Indoor Weight

Gross 15kg

Net 45kg

Indoor 750 m3/hOutdoor Weight

Gross 53kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 865×228×304 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 923x294x347 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 810×288×680 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 915×325×699 mm

Moisture Removal 2.5×10-3m3/h liquid /Gas pipe Diametre 6.35/12.7 mm

Model: YR-H10 standard Lenth 5mRemote

Controller Refer. No. 0010401627

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose ----

Appearance ----- Max. pressure at warm side 4.15 MPa

Climate Type T1 Max.pressure at cool side 4.15MPa

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-23 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32℃/ 223 Dry/Wet ball(indoor):27 / --Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor):24℃/18℃

Air Conditioner Edition:2006/1/10

6

zhanglizhi
zhanglizhi
zhanglizhi
HITACHI/PA240X2CS-4KT1
zhanglizhi
500(poe)
Page 15: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner

OPERATION

7

Edition:2006/1/10

Page 16: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Before disposing an old air conditioner thatgoes out of use, please make sure it's inop-erative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.

It must be noticed that air conditioner system contains refrigerants, which require speciali-zed waste disposal. The valuable materials contained in an air conditioner can be recycled.Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damagedprior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.

CautionsDisposal of the old air conditioner

All the packaging materials employed in thepackage of your new air conditioner may bedisposed without any danger to theenvironment.

The cardboard box may be broken or cut intosmaller pieces and given to a waste paperdisposal service. The wrapping bag made ofpolyethylene and the polyethylene foam padscontain no fluorochloric hydrocarbon.

All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.

Consult your local authorities for the nameand address of the waste materials collecting centers and waste paper disposal services nearest to your house.

Disposal of the packaging of yournew air conditioner

Before starting the air conditioner, read theinformation given in the User's Guide caref-ully. The User's Guide contains very impor-tant observations relating to the assembly, operation and maintenance of the air conditioner.

The manufacturer does not accept respon-sibility for any damages that may arise due to non-observation of the followinginstruction.

Damaged air conditioners are not to beput into operation. In case of doubt, consultyour supplier.

Use of the air conditioner is to be carriedout in strict compliance with the relativeinstructions set forth in the User's Guide.

Installation shall be done by professionalpeople, don't install unit by yourself.

For the purpose of the safety,the air con-ditioner must be properly grounded in acco-rdance with specifications.

Always remember to unplug the airconditioner before openning inlet grill. Neverunplug your air conditioner by pulling onthe power cord. Always grip plug firmly andpull straight out from the outlet.

All electrical repairs must be carried outby qualified electricians. Inadequate repairsmay result in a major source of danger forthe user of the air conditioner.

Safety Instructions and Warnings

Do not damage any parts of the airconditioner that carry refrigerant by piercingor performating the air conditioner's tubeswith sharp or pointed items, crushing ortwisting any tubes, or scraping the coatingsoff the surfaces. If the refrigerant spurtsout and gets into eyes, it may result inserious eye injuries.

Air Conditioner Edition:2006/1/10

zhanglizhi
8
Page 17: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Do not obstruct or cover the ventilationgrille of the air conditoner.Do not put fingersor any other things into the inlet/outlet and swing louver.

Do not allow children to play with the air conditioner.In no case should children beallowed to sit on the outdoor unit.

The refrigerating circuit is leak-proof.

1.Applicable ambient temperature range:

Cooling

IndoorMaximum:D.B/W.B 32oC/23oC

24oC/18oC-7oC/-8oC

43oC/26oC18oC

27oC15oC

18oC/14oC

Maximum:D.B/W.BMinimum:D.B

Maximum:D.BMinimum:D.B

Minimum:D.B/W.B

Maximum:D.B/W.BMinimum:D.B/W.B

Outdoor

Indoor

OutdoorHeating

Specifications

The machine is adaptive in following situation

10 .The power plug and connecting cable must have acquired the local attestation.

2. If the power supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.

3. If the fuse of indoor unit on PC board is broken,please change it with the type of T. 3.15A/ 250V.

4. The wiring method should be in line with the local wiring standard.

5. After installation, the power plug should be easily reached.

6. The waste battery should be disposed properly.

7. The appliance is not intended for use by young children or infirm persons without supervision.

8. Young children should be supervised to ensure that they do not play with the applience.9.Please employ the proper power plug, which fit into the power supply cord.

Cautions

9

Air Conditioner Edition:2006/1/10

Page 18: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Cautions

STRICTENFORCEMENT

Safety Instruction

Installation

WARNING

Please read the following Safety Instructions carefully prior to use.

The instructions are classified into two levels, WARNING and CAUTION according to the seriousness of possible risks and damages as follows. Compliance to the instructions are strictly required for safety use.

Please call Sales/Service Shop for the Installation.Do not attempt to install the air conditioner by yourself because improper works may cause electric shock, fire, water leakage.

lnstallation in a inadequate place may cause accidents. Do not install in the following place.

Connect the earthcable.

earthing

Do not install in the place where there is any possibility of inflammable gas leakage around the unit.

Do not get the unit exposed to vapor or oil steam.

Check proper installation of the drainage securely

PROHIBITION PROHIBITION

10

CAUTION

Air Conditioner Edition:2006/1/10

Page 19: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

CautionsWARNING

When abnormality such as burnt-small found, immediately stop the operation button andcontact sales shop.

OFF

Use an exclusive power source with acircuit breaker

ENFORCEMENT

Connect power supply cordto the outlet completely

Use the proper voltage

Do not use power supply cordin a bundle.

Take care not to damagethe power supply cord.

Do not use power supply cord extended or connected in halfway

STRICTENFORCEMENT

STRICT

STRICTENFORCEMENT PROHIBITION

PROHIBITION PROHIBITION

PROHIBITION

Do not start or stop theoperation by disconnectingthe power supply cord and so on.

Do not channel the air flow directlyat people, especially at infants orthe aged.

Do not try to repair or reconstructby yourself.

Do not use for the purpose of storage offood, art work, precise equipment,breeding, or cultivation.

CAUTIONTake fresh air occasionally especiallywhen gas appliance is running at the same time.

PROHIBITIONSTRICT

ENFORCEMENT

Do not operate the switch with wet hand.

PROHIBITION

PROHIBITION

11

PROHIBITION PROHIBITION

PROHIBITION

Do not install the unit near a fireplaceor other heating apparatus.

Check good condition of the installation stand

Do not pour water onto the unitfor cleaning

PROHIBITION

Do not place animals or plants inthe direct path of the air flow

Do not place any objects on orclimb on the unit.

Do not place flower vase or watercontainers on the top of the unit.

Do not insert objects into the airinlet or outlet.

PROHIBITION

PROHIBITION

PROHIBITION

Air Conditioner Edition:2006/1/10

Page 20: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Parts and Functions

12

OUTLET CONNECTING PIPING AND ELECTRICAL WIRING

INLET DRAIN HOSE

For multi-split type, the power plug is on the outdoor unit.

1

2

3

4

Indoor unit

Outdoor unit

Display boardInlet

Air Purifying Filter

Vertical flap(adjust up and down air flow. Don't adjust it manually)

Horizontal louver

Air filter(inside)

Inlet grille

Power plug

(adjust left and right air flow)

(inside)

Outlet

Anion generator(inside)

HSU-07HV03/R2HSU-09HV03/R2

HSU-12HV03/R2HSU-18HV03/R2

HSU-22HV03/R2H2SM-18HV03/R2H2SM-(9+12)HV03/R2

Air Conditioner Edition:2006/1/10

Page 21: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Parts and Functions

When the remote controller appears abnormal,use a sharp pointed article to press this button to reset the remote controller normal.

1.RESET

Used to select TIMER ON, TIMER OFF, TIMER ON-OFF.

3. TIMER button

Used to set correct time.4. CLOCK button

Used to select sleep mode.5. SLEEP button

6. MODE button

AUTO COOL DRY FAN HEAT

Used to set clock and timer setting.7. HOUR button

Used to set healthy operation.8. HEALTH button

Used for unit start and stop.9. ON/OFF button

10. TIMER ON display11. FAN SPEED display

LOW HIMED AUTO

12. LOCK display13. SWING UP/DOWN display14. SLEEP display15. HEALTH display

Used to select your desired temperature.

Operation mode AUTO HEAT FANCOOL DRY

Remote controller

16. Operation mode display

Display board

18. Left/right air flow display

Remote controller: to display the TEMP. setting.19. TEMP display

20. TIMER OFF display21. TIMER display22. TEMP button

Used to select fan speed: LOW,MED, HI, AUTO.23. FAN button

Used to set the health airflow mode.24. HEALTH AIRFLOW button

25. SWING UP/DOWN buttonUsed to select up or down air sending direction.

26. SWING LEFT/RIGHT buttonUsed to select left/right air flow.

Used to confirm timer and clock settings.27. SET button

Used to lock buttons and LCD display. If pressed, the other buttons will be disabled and the lock condition display appears. Press it once again, lock will be canceled and lock condition display disappears.

28. LOCK

13

29. Ambient temp.display

19

28

16 1429 1510 20

17.Singal sending display

2.LIGHT buttonControl the lightening and extinguishing of the indoor LCD display board.

NOTE: Cooling only unit do not have functions and displays related with heating.

When receiving the remote control signal, display the set temperature and in the rest time the room temperature is displayed and this room temperature is only for reference.

Air Conditioner Edition:2006/1/10

Page 22: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Remove the batteries in case unit won't be in usage for a long period. If there are any display after taking-out, just need to press reset key.

Parts and FunctionsClock Set

When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows:

Remote controller's operation

3. After time setting is confirmed, press SET, "AM" or "PM" stop flashing, while clock starts working.

2. Press or to set correct time. Each press will increase or decrease 1 min. If the button is kept depressed, time will change quickly.

1. Press CLOCK button,"AM" or "PM" flashes.

When in use, put the signal transmission head directly to the receiver hole on the indoor unit.

The distance between the signal transmission head and the receiver hole should be within 7m without any obstacle as well.

Don't throw or knock the remoter controller.

When electronic-started type fluorescent lamp or change-over type fluorescent lamp or wireless telephone is installed in the room, the receiver is apt to be disturbed in receiving the signals, so the distance to the indoor unit should be shorter.

Loading of the battery

Load the batteries as illustrated right2 R-03 (7#) batteries

Remove the battery cover:Slightly press" "area and push down the coveras illustrated.

Load the battery:Be sure that the loading is in line with the "+" / "-".request as illustrated on the bottom of the case.

Put on the cover again.

Confirmation indicator:After pressing power ON/OFF, if no display, reload the batteries.

Note:Full display or unclear display during operation indicates the batteries have been used up.Please change batteries.Used two new same-typed batteries when loading.If the remote controller can't run normally during operation, please remove the batteries and reload several minutes later.

Hint:

Air Conditioner Edition:2006/1/10

zhanglizhi
14
Page 23: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Operation

15

2.Health anion function

Air conditioner starts health anion function operation.For twice press, disappears,the operation stops.

BRIEF INTRODUCTION TO HEALTH ANION FUCTIONThe anion generator in the air conditioner can generate a lot of anion effectively balance the quantity of position and anion in the air and also to kill bacteria and speed up the dust sediment in the room and finally clean the air in the room.

When the fan in the indoor unit does not work, the health lamp lights up, but the anion generator does not release anion.

When indoor fan motor is running, it has healthyprocess function. (It's available under any mode)

Press ON/OFF on the remote controller, unit starts.

Press HEALTH button. For each press, is displayed.

1.Unit start

HEALTH operation

Remote controller

Air Conditioner Edition:2006/1/10

Page 24: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Auto Operation

Operation

16

About Auto OperationUnder the mode of auto operation, air conditioner willautomatically select Cool or Heat operation accordingto room temperature.

1. Unit start Press ON/OFF on the remote controller, unit starts.

2.Select operation modePress MODE button. For each press, operation modechanges as follows:

Remote controller:

Then Select Auto operation

AUTO COOL DRY FAN HEAT

On the displaying board,colorful displaying bar will be white.

Press FAN button. For each press, fan speed changes asfollows:Remote controller:

Press TEMP. button

Every time the button is pressed, temp.setting increase 1oC,if kept depressed, it will increase rapidlyEvery time the button is pressed, temp.setting decrease 1oC,if kept depressed, it will decrease rapidly

Select a desired temperature.

4.Fan speed selection

3.Select temp.setting

5.Unit stop

Air conditioner is running under displayed fan speed.When FAN is set to AUTO, the air conditionerautomatically adjusts the fan speed according to roomtemperature.

Press ON/OFF button, the unit stops.

Remote controller

LOW MED HI AUTO

Air Conditioner Edition:2006/1/10

Page 25: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Cool Operation

2.Select operation mode

Press FAN button. For each press, fan speed changes asfollows:

Press MODE button. For each press, operation modechanges as follows:Remote controller:

Remote controller:

Then Select COOL operation

Press TEMP. button

Every time the button is pressed, temp.setting increase 1oC,if kept depressed, it will increase rapidlyEvery time the button is pressed, temp.setting decrease 1oC,if kept depressed, it will decrease rapidlySelect a desired temperature.

4.Fan speed selection

3.Select temp.setting

5.Unit stop

Air conditioner is running under displayed fan speed.When FAN is set to AUTO, the air conditionerautomatically adjusts the fan speed according to roomtemperature.

Press ON/OFF button, the unit stops.

AUTO COOL DRY FAN HEAT

1. Unit start Press ON/OFF on the remote controller, unit starts.

Operation

17

On the displaying board,colorful displaying bar will be blue.

Remote controller

LOW MED HI AUTO

Air Conditioner Edition:2006/1/10

Page 26: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

2.Select operation mode

Press FAN button. For each press, fan speed changes asfollows:

Press MODE button. For each press, operation modechanges as follows:Remote controller:

Remote controller:

Then Select DRY operation

Press TEMP. buttonEvery time the button is pressed, temp.setting increase 1oC,if kept depressed, it will increase rapidlyEvery time the button is pressed, temp.setting decrease 1oC,if kept depressed, it will decrease rapidlySelect a desired temperature.

4.Fan speed selection

3.Select temp.setting

5.Unit stopPress ON/OFF button, the unit stops.

AUTO COOL DRY FAN HEAT

Operation

Dry Operation

1. Unit start Press ON/OFF on the remote controller, unit starts.

18

On the displaying board,colorful displaying bar will belight blue

Air conditioner is running under displayed fan speed.In DRY mode, when room temperature becomeslower than temp.setting+2oC,unit will run intermittently at LOW speed regardless of FAN setting.

Remote controller

LOW MED HI AUTO

Air Conditioner Edition:2006/1/10

Page 27: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Fan Operation

2.Select operation mode

Press FAN button. For each press, fan speed changes asfollows:

Press MODE button. For each press, operation modechanges as follows:Remote controller:

Remote controller:

Then Select FAN operation

3.Fan speed selection

4.Unit stop

About FAN operationIn FAN operation mode, the unit will not operate inCOOL or HEAT mode but only in FAN mode ,AUTO isnot available in FAN mode.And temp.setting is disabled.In FAN mode,SLEEP operation is not available.

Press ON/OFF button, the unit stops.

AUTO

LOW MED HI

COOL DRY FAN HEAT

Operation

1. Unit startPress ON/OFF on the remote controller, unit starts.

19

On the displaying board,colorful displaying bar will be pink.

Remote controller

Air Conditioner Edition:2006/1/10

Page 28: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Operation

2.Select operation mode

Press FAN button. For each press, fan speed changes asfollows:

Press MODE button. For each press, operation modechanges as follows:Remote controller:

Remote controller:

Then Select HEAT operation

Press TEMP. buttonEvery time the button is pressed, temp.setting increase 1oC,if kept depressed, it will increase rapidlyEvery time the button is pressed, temp.setting decrease 1oC,if kept depressed, it will decrease rapidlySelect a desired temperature.

4.Fan speed selection

3.Select temp.setting

5.Unit stopPress ON/OFF button, the unit stops.

AUTO COOL DRY FAN HEAT

Heat Operation

1. Unit start Press ON/OFF on the remote controller, unit starts.

20

Air conditioner is running under displayed fan speedIN HEAT mode, warm air will blow out after a short periodof the time due to cold-draft prevention function.When FAN is set to AUTO, the air conditionerautomatically adjusts the fan speed according to roomtemperature.

On the displaying board,colorful displaying bar will be red

Remote controller

LOW MED HI AUTO

Air Conditioner Edition:2006/1/10

Page 29: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

2.Up and down air flow direction

Vertical flap

Pos.1

Pos.1 Pos.2 Pos.3 Pos.4 Pos.6

Pos.5 Pos.4 Pos.3 Pos.2 Pos.1 Pos.6

Pos.1 Pos.2 Pos.3 Pos.4 Pos.5 Pos.6

Pos.2

Pos.3

Pos.4

Pos.5

Pos.6 (Auto swing)

For each press of button, air flow direction on remote controller displays as follows according to different operation modes:

remote controller:COOL/DRY/FAN:

remote controller:

remote controller:

The vertical flap will swing according to the above positions

HEAT:

AUTO:

1.Status display of air sending

Horizontal louvers

Pos.1

Pos.2

Pos.3

Pos.4

Pos.5

Pos.6

Pos.7

Pos.8

3.Left and right air flow direction

For each press of button, remote controller displays as follows :remote controller:

Pos.1 Pos.2 Pos.3 Pos.4 Pos.5 Pos.6 Pos.7 Pos.8

The horizontal louvers will swing according to the above positions.

Note:When restart after remote turning off, the remote controller will automatically memorize the previous set swing position.

21

Air Flow Direction Adjustment

Operation

Air Conditioner Edition:2006/1/10

Page 30: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

If the wind speed is high or middle beforesetting for the sleep, set for lowing the wind speed after sleeping. If it is low wind, no change.

5.Set the wind speed change when sleeping

Before going to bed, you can simply press theSLEEP button and unit will operate in SLEEPmode and bring you a sound sleep.

Use of SLEEP functionAfter the unit starts, set the operation status,then press SLEEP button before which theclock must be adjusted and time being set.

Operation Mode1. In COOL,DRY mode 1 hours after SLEEP mode starts, temp. will become 1OC higher than temp. setting. After another 1 hours, temp. rises by 1OC further. The unit will run for further 6 hours then stops. Temp. is higher than temp. setting so that room temperature won't be too Iow for your sleep.

Remote Controller

SLEEP operation starts SLEEP operation stops

SLEEP operation starts

SLEEP operation stops

Approx.6hrs

1 hr

1 hr

1 hr

3 hrs

3 hrs

Rises 1OC

Rises 1OC

Rises 1OC

Temp.setting

Temp.setting

Unit stop

Unit stop

In COOL, DRY mode

In HEAT mode

Decreases 2OC

Decreases 2OC

1 hr

Sleep Operation

2.

3.

In HEAT mode1 hours after SLEEP mode starts, tempwill become 2OC lower than temp.setting. After another 1 hours, tempdecrease by 2 OC further. After moreanother 3 hours, temp. rises by 1OCfurther. The unit will run for further 3hours then stops. Temp. is lower thantemp. setting so that room temperaturewon't be too high for your sleep.

In AUTO modeThe unit operates in corresponding sleepmode adapted to the automatically selected operation mode.

4. In FAN mode It has no SLEEP function.

Operation

22

6.Note to the compensation for the power out: press the sleep button ten times in five seconds and enter this function after hearing four sounds. And press the sleep button ten times within five seconds and leave this function after hearing two sounds.

With the power-out compensation, when settingthe TIMER ON, TIMER OFF and TIMER ON/OFF, itís memorized as shutdown status when resumingafter power out.

NOTE:

Air Conditioner Edition:2006/1/10

Page 31: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Remote Controller

Timer On/Off Operation

Operation

Hints: After replacing batteries or a power failure happens, time setting should be reset. Remote controller possesses memory function, when use TIMER mode next time, just press SET button after mode selecting if time setting is the same as previous one.

23

Set clock correctly before starting TIMER operation.1. After unit starts, select your desired operation mode Operation mode will be displayed on LCD.

2. Timer mode selection Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows: Remote controller:

BLANK

TIMER ON TIMER OFF TIMER ON-OFF

Then select your desired TIMER mode (TIMER ON orTIMER OFF). " "or " "will flash.

3.Time settingPress HOUR button. Every time the button is pressed, time setting increases 1 min, if kept depressed, it will increase rapidly. Every time the button is pressed, time setting decreases 1 min, if kept depressed, it will decrease rapidly. It can be adjusted within 24 hours.

4.Confirming your settingAfter setting correct time, press SET button to confirm" "or" "on the remote controller stops flashing.Time displayed: Unit starts or stops at x hour x min.(TIMER ON or TIMER OFF).

5.Cancel TIMER modeJust press TIMER button several times until TIMERmode disappears.

Air Conditioner Edition:2006/1/10

Page 32: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Remote Controller

Timer On-Off Operation

Operation

Just press TIMER button several times until TIMER de disappears.According to the Time setting sequence of TIMER ONor TIMER OFF, either Start-Stop or Stop-Start can beachieved.

Set clock correctly before starting TIMER operation.1. After unit starts, select your desired operation mode Operation mode will be displayed on LCD.

2. Timer mode selection Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows: Remote controller:

Then select your desired TIMER mode (TIMER ON - OFF). " "will flash.

3.Time settingPress HOUR button. Every time the button is pressed, time setting increases 1 min, if kept depressed, it will increase rapidly. Every time the button is pressed, time setting decreases 1 min, if kept depressed, it will decrease rapidly. It can be adjusted within 24 hours.

4.Timer confirming for TIMER ONAfter setting correct time, press TIMER button to confirm" " on the remote controller stops flashing." " starts flashing.Time displayed: Unit starts or stops at x hour x min.

5.Time setting for TIMER OFF

6.Time confirming for TIMER OFF

To cancel TIMER mode

Just press HOUR button ,follow the same procedure in "Time setting for TIMER ON"

After time setting,press SET button to confirm." " on the remote controller stops blinking.Time displayed:Unit stops at x hour x min.

24

BLANK

TIMER ON TIMER OFF TIMER ON-OFF

Air Conditioner Edition:2006/1/10

Page 33: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

1.Press ON/OFF to starting

Operation

The liquid crystal will display the working state of last time(Except timer, sleeping, power/soft and health airflow).Setting the comfort work conditions.

2.The setting of health airflow function1).Press the button of health airflow, appears on thedisplay. The nether inlet and outlet grills of the air condit-ioner are closed and the airflow is blown horizontally from the above inlet and outlet grills. Avoid the strong airflow blows direct to the body.2).Press the button of health airflow again, appears onthe display. The above inlet and outlet grills of the air cond-itioner are closed and the airflow is blown vertically from the nether inlet and outlet grills. Avoid the strong airflow blows direct to the body.

Note:1 .After setting the health airflow function, the position of inletand outlet grills is fixed.2.In heating, it is better to select the mode.3.In cooling, it is better to select the mode.4.In cooling and dry, using the air conditioner for a long timeunder the high air humidity, a phenomenon falling drips ofwater occurs at the outlet grille .5.Select the appropriate fan direction according to the actualconditions.

3.The cancel of the health airflow functionPress the button of health airflow again, both the inlet andoutlet grills of the air conditioner are opened, and the unit goes on working under the condition before the setting of health airflow function.After stopping, the outlet grille will close automatically.Notice: Cannot pull direct the outlet grille by hand. Otherwise,the grille will run incorrectly. If the grille is not run correctly, stop for a minute and then start, adjusting by remote controller.

25

Health airflow Operation

Remote controller

Air Conditioner Edition:2006/1/10

Page 34: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

When the remote controller is manipulated, it gets the system back to the normal operation mode.

Emergency and Test Operation

Operation

Emergency operation:Use this operation only when the remote controlleris defective or lost.When the emergency operation switch ispressed,the" Pi "sound is heard once, which meansthe start of this operation.In this operation, the system automatically selectsthe operation modes, cooling or heating, accordingto the room temperature.

Test operation:Test operation switch is the same as emergency switch.

Use this switch in the test operation when the roomtemperature is below 16OC, do not use it in the normaloperation.

Continue to press the test operation switch for more than 5 seconds. After you hear the "Pi" sound twice, release your finger from the switch: the cooling operation starts with the air flow speed "Hi".

Removal of the restriction of emergency or test operation Press the emergency operation switch once more, or manipulate through the remote controller; the "Pi" sound, the emergency or test operation is terminated.

It is not possible to operate in dry mode.

Temperature Operation mode

Designatedtemperature

Timermode Air flow

ABOVE 21OC

BELOW 21OC

COOLING

HEATING 24OC

24OC NO

NO

AUTOMATIC

AUTOMATIC

After 30 minutes, test operation ends automatically.

26

Air Conditioner Edition:2006/1/10

Page 35: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

For Smart Use of The Air Conditioner

Setting of proper room

temperature

Close doors and windows

during operation

If the unit is not to be used

for a long time, turn off the

power supply main switch.

Use the timer effectively

Use the louvers effectively

Do not block the air inlet

or outlet

Maintenance

Propertemperature

During cooling operationprevent the penetration ofdirect sunlight withcurtain or blind

27

OFF

Air Conditioner Edition:2006/1/10

Page 36: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

For Smart Use of The Air Conditioner

WARNING

Air Filter cleaningOpen the inlet grille by pulling it upward.

Remove the filter.

Clean the filter.

Attach the filter.

Close the inlet grille.

Push up the filter's center tab slightly until it is releasedfrom the stopper, and remove the filter downward.

Use a vacuum cleaner to remove dust, or wash the filter withwater.After washing, dry the filter completely in the shade.

Attach the filter correctly so that the "FRONT" indication is facing to the front.Make sure that the filter is completelyfixed behind the stopper.If the right and left filters are notattached correctly, that may cause defects.

Remote Controller

Do not use the following for cleaning

Do not use water, wipe the controller with a dry cloth.Do not use glass cleaner or chemicalcloth.

Gasoline,benzine, thinner or cleanser maydamage the coating of the unit.

Hot water over 40OC(104OF) may cause discoloring or deformation.

Wipe the air conditioner by using a soft anddry cloth.For serious stains,use a neutraldetergent diluted with water.Wring the waterout of the cloth before wiping.then wipe offthe detergent completely.

Indoor BodyBefore maintenance,be sure to turn off the system and the circuit breaker.

Maintenance

Once every two weeks

28

Air Conditioner Edition:2006/1/10

Page 37: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

29

Note: the bacteria-killing mediums placed on the left side. the multi-lights touching intermediary is placed on the right side.

Maintenance

1.Open the lnlet Grille

2.Detach the standard air filter

3.Attach old Air Purifying Filter

4.Attach the standard air filter(Necessary installation)

5.Close the Inlet GrilleClose the Grille surely

Open the inlet grille by pushing each ends ofthe inlet grille upward.(use thumbs to pushup)

Slide the knob slightly upward to release thefilter, then withdraw it.

Put air purifying filter appliances into the right and left filter frames.

Detach old Air Purifying Filter

Replancement of Air Purifying Filter

NOTE:

The green aspect of the bacteria-killing medium air purifying filter will face outside, the white aspect will face to the machine.

The photocatalyst air purifying filter and the bacteria-killing medium air purifying filterwill be used based on real situation.The photocatalyst air purifying filter will be solarized in fixed time. In normal family, it will be solarized every 6 months. The solarization time will last no less than 8 hours under the state of abundant sun.

The bacteria-killing medium air purifying filter is available for a long time and neednít to be changed. But it must be noticed to use the vacuum cleaner frequently to adsorb the dusts covering the purifying filter lest the covering dusts effect the function of thebacteria-killing medium air purifying filter. (It is strictly prohibited for the bacteria-killing medium air purifying filter to be washed)

Air Conditioner Edition:2006/1/10

Page 38: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

To Keep Your Air conditioner in Good Conditionafter Season.

Operate in cooling mode for 2-3 hours.

Put off the power supply cord.

Take out the batteries from the wireless remote controller.

Cleaning the body.

To prevent breeding mold or bad smell, be sure tooperate at the designated temperature or 30OC,coolingmode and High speed fan mode for 2-3 hours.

Maintenance

30

Air Conditioner Edition:2006/1/10

Page 39: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Before Setting in High season

Cleaning the standard air filter.

Connecting the earthing cable.

Do not block the air inlet or outlet.

Plug-in

Caution

CautionAfter brush away dust at the plug, insert theplug of the power supply cord into the outletcompletely.In case of suing exclusive circuitbreaker,switch on the circuit breaker. NO WET HAND

EARTHING

Operation without filter may cause troubles.Be sureto attach both right and left filters prior to the operation.Each of them are of different shapes.

Incomplete earthing may cause an electric shock.

Maintenance

31

Air Conditioner Edition:2006/1/10

Page 40: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Is the air filter dirty? Normally it should becleaned every 15 days.Are there any obstacles before inlet and outlet?Is temperature set correctly?Are there some doors or windows left open?Is there any direct sunlight through thewindow during the cooling operation?(Usecurtain)Are there too much heat sources or too manypeople in the room during cooling operation?

Cause or check pointsPhenomenon

The system does not restartimmediately.

Noise is heard:

Smells are generated.

Mist or steam are blown out.

Does not work at all.Multiplecheck

NormalPerformanceinspection

Poor cooling

Before asking for service, check the following first.

When unit is stopped, it won't restartimmediately until 3 minutes have elapsedto protect the system.When the electric plug is pulled out andreinserted, the protection circuit will workfor 3 minutes to protect the air conditioner.

During unit operation or at stop, a swishingor gurgling noise may be heard. At first 2-3minutes after unit start, this noise is morenoticeable. (This noise is generated byrefrigerant flowing in the system.)During unit operation, a cracking noise maybe heard. This noise is generated by thecasing expanding or shrinking because oftemperature changes.Should there be a big noise from air flow inunit operation, air filter may be too dirty.

This is because the system circulates smellsfrom the interior air such as the smell offurniture, cigarettes.

During COOL or DRY operation, indoor unitmay blow out mist. This is due to the suddencooling of indoor air.

Is power plug inserted?Is there a power failure?Is fuse blown out?

32

Trouble shooting

Air Conditioner Edition:2006/1/10

Page 41: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2005/11/18

ELECTRICAL CONTROLL

33

zhanglizhi
zhanglizhi
Page 42: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

2. Run mode:(Tr: inlet air temperature,Ts:the set temperature) 2.1 automatic run mode The background lighting of the LCD is white 1) cooling only type automatic run mode:

When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts+3℃ Choose Cooling mode Tr<Ts-3℃ Choolse Blowing Mode The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, it will switch to blowing mode when Tr<Ts-3℃; if the system is currently under blowing mode, it will in turn switch to cooling mode when Tr > Ts+3℃. The switching mode as below, 2) cold/warm type run mode: When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts-3℃ Choose Cooling Mode Tr<Ts-3℃ Choose Heating Mode

The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, the compressor will stop functioning if the temperature lowers to such a degree that requires so; then it will recheck the temperature 15 minutes later: it will switch to the heating mode if the temperature is Tr<Ts-3℃,or it will still stay in cooling mode(including blowing mode). if the system is currently under heating mode, the compressor will stop running if the temperatur lowers to such a degree that requires so, then it will recheck teh temperatur 15 minutes later: it will switch to the cooling mode if the temperature is Tr>Ts+3℃.

2.2 Cooling run mode: (Tr: inlet air temperature,Ts:the set temperature) The background lighting of the LCD is blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Compressor can’t be controlled by temperature sensor within 2 minutes after it starts. Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan motor run at

fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr > Ts, outdoor fan motor and compressor are working again.

If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressor’s state will not change. wind speed control: (the temperature difference is 1℃)

auto: when Tr>=Ts+3℃, the wind speed is high; when Ts+1℃≤Tr<Ts+3℃, the wind speed is medium. When Tr<Ts+1℃, the wind speed is low. When temperature sensor is off, the fan motor runs at low speed. when the wind speed changes from low to higher, there is no delay, and when it changes from high to lower, there is a 3-minutes delay before conversion.

Manual operation: When unit is on the wind speed can be set to high, medium, low or automatic as required (execute instruction 2 seconds later after receiving remote signal)

Air Conditioner Edition:2006/1/10

zhanglizhi
34
Page 43: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

compressor control:The compressor can’t be controlled by temperature sensor within 2 minutes after startup and can be only restarted at least 3 minutes later after shutdown. There is no 3-minute protection with power on for the first time (over 3 minutes with power off). The compressor

must stands by for 3 minutes before it is restarted after shutdown.

There is no 2-minute limit when changing the temperature setting or shutting down the machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the compressor startup. Controlling the position of air door: set the position of air door as required. Protection of expiration of current peak value is available: Current cross detection is available in order

to avoid burning out the compressor when the current is too big. The action character as follows:

The compressor can’t be detected in 60 seconds after startup. when current is above “CT 1.6 V” and lasts 3 seconds, the system enter protection mode and shut off compressor with outdoor air blower and indoor fan motor controlled as the temperature sensor is off. After 3 minutes the machine can be started again.

Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Timer on, Timer off and sleep control are available. 2.3 Dehumidifying mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is aquamarine blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ control character:

When Tr (indoor temperature) > Ts (temperature setting) +2℃, compressor and outdoor fan motor run continuosly with indoor fan motor runnig in accordance with the wind speed setting.

When Tr ranges from Ts to Ts +2℃, outdoor fan motor and compressor are on for 10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after shutdown of compressor and gives breeze in other time.

When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor fan motor enter breeze mode 3 minutes later after shut down of compressor.

When all the ranges alternate, there is ±1℃ difference. Wind speed control: Automation: When Tr >= Ts + 5℃, the wind speed is high. When Ts+3℃≤ Tr <Ts+5℃, the wind speed is medium.

When Ts+2℃≤ Tr <Ts+3℃, the wind speed is low. When Ts≤ Tr <Ts+2℃, the machine gives breeze intermittently.

When Tr < Ts, the indoor fan motor is shut off. in 3 minutes When Tr < Ts, the machine gives breeze after 3 minutes

Manual operation: When the temperation sensor is off or the Indoor fan motor runs intermittently, the indoor fan motor can not be operated by hand (compelling automatic operation), along with

Air Conditioner Edition:2006/1/10

zhanglizhi
35
Page 44: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

the indoor fan motor can be operated in cooling mode. While controlling fan motor by hand in cooling mode, the cooling ranges include wind speed setting and refriferation range, others are the same as fan motor in automation mode.

compressor control:The compressor can’t be controlled by temperature sensor in 2 minutes after startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minutes protection with power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes later after shutdown.

There is no 2-minutes limit when changing the temperature setting or shutting off the machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor startup. Controlling the position of air door: set the position of air door as required. Protection of expiration of current peak value is available: Current cross detection is available in order

to avoid burning out the compressor when the current is too big. The action character as follows:

The compressor can’t be detected in 60 seconds after startup. when current is above “CT 1.6 V” and lasts 3 seconds, the system enter protection mode and shut off compressor with outdoor air blower and indoor fan motor controlled as the temperature sensor is off. After 3 minutes the machine can be started again.

Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Timer on, Timer off and sleep control are available. 2.4 Heating mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is red Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Control Character: When Tr ≤ Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan motor runs as

in cold blast avoidance mode, and 4℃of compensation is added after compressor is started. When Tr>Ts+5℃, compressor is off, and the indoor fan motor runs as in cold blast avoidance

mode. When Tr<Ts+5℃, compressor, four-ways valve and outdoor fan motor is on, and the indoor fan

motor runs as in the mode of avoiding cold blast. Control of indoor fan motor:

Manual operation: The wind speed can be set to high, medium, low or automatic as required. Automatic operation: When Tr < Ts, the wind speed is high; When Ts=<Tr<Ts+2℃, the wind speed is medium. When Tr>= Ts+2℃, the wind speed is low.

Control of air door: setting the position of air door as required. compressor control:The compressor can’t be controlled by temperature sensor in 2 minutes after

startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minute protection with power on for the first time (over 3 minutes with power off). The compressor must

Air Conditioner Edition:2006/1/10

zhanglizhi
36
Page 45: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

be started again 3 minutes later after shutdown. There is no 2-minutes limit when changing the temperature setting or shutting off the machine through

the remote controller, and the machine can be shut down immediately. Avoiding electrical shock: outlet air is available 2 seconds later after startup. Timer on, Timer off and sleep control are available. Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts runnig 10

seconds earlier than compressor does. After compressor stops runnig, the 4-way valve continues running for 2 minutes and 30 seconds then stops. If changing the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and compressor is started 3 minutes later.

Cold blast avoidance mode: (1)Compressor is interrupted during the defrosting operation and continues to run after defrosting is

completed. When the indoor exchanging temperature is below 23℃, the indoor fan motor is off. When the indoor exchanging temperature is above 23℃, the indoor fan motor is running at weak speed.

(2)If the temperature of coil pipe can’t be above 38℃ 4 minutes later after startup, fan motor is running at the preset wind speed.

(3) If the temperature of coil pipe is above 38℃ in 4 minutes after start up, fan motor is running at the preset wind speed immediately.

(4)If coil pipe descends to the temp. lower than 38℃ from 38℃. fan motor still running at the preset wind speed.

(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil pipe is above 23℃, fan motor enter breeze mode; and if the temperature of coil pipe is below 20℃, fan motor stops running.

(6)Shut down the unit and indoor fan motor stops running. High temperature protection and high temperature expiration protection:

High temperature prevention: When the temp. of coil pipe is above 64℃, the outdoor fan motor stops.When the temp descends to 60℃, the outdoor fan motor is restarted and fan speed invertage frequence is more than 45 seconds. High temperature expiration prevention: When the temp. of coil pipe is above 73℃,compressor and outdoor fan motor stop running 2 seconds later, and inlet air runs as the temp. sensor is off. When compressor stands by for 3 minute and the temp. of coil pipe is below 64℃, the unit can be started again.

Current protection and current expiration protection: (Not detecting within 60 seconds after startup) Current protection: If current detected is above

(HSU-12HV03/R2:5.8A;HSU-09HV03/R2:4.5A;HSU-07HV03/R2:4.2A) and lasts 10 senconds continuously, outlet air stops. If current detected is below (HSU-12HV03/R2:5.2A;HSU-09HV03/R2:4.2A;HSU-07HV03/R2:3.8A) , outlet air is regained 。 Current peak expiration protection: If current detected is above (HSU-12HV03/R2:9.5A;HSU-09HV03/R2:8.5A;HSU-07HV03/R2:8.5A) , 3 seconds later the system enter current cross protection, compressor and air outlet stop and start again 3 minuts later, and air inlet runs as the temperature sensor is off.(different mode has the different CT value)

Overcooling protection: One and a half minute later after compressor starts, if the temperature of coil pipe is below -4℃,

compressor and air outlet stop, and air inlet runs according to the temp. setting. Compressor can be

Air Conditioner Edition:2006/1/10

zhanglizhi
37
Page 46: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

restarted 3 minutes later. Defrosting: 1.Entry conditions of defrosting:

A. Indoor unit enter overload protection and air outlet stops when air outlet has been restarted and runs over 10 minutes, and compressor runs over 45 minutes in total and over 20 minutes continuously, and the temp. of indoor coil pipe is below 38℃.

B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe decreases 1℃ per 6 minutes and this operation repeats 3 times, and the temp. of coil pipe is below 38℃, then 5 minutes later . the system enters defrosting mode.

C. When compressor runs over 3 hours in total and over 20 minutes continuously and after the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

D. The difference between the temp. of indoor coil pipe and the indoot temp. is below 16℃ and lasts 5 minutes, compressor runs over 45 minutes in total and over 20 minutes continuously, the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

2.Exit conditions of defrosting: Defrosting time is higher than 12 minutes (compressor is on), or CT current is above (8.5A).

During the defrosting, if current peak value is cut off, the unit quit the defrosting mode. But the protection of expiration of current peak value is unavailable with 60 senconds after compressor is started.

During the defrosting and 2 minutes after the defrosting, abnormality of temp. sensor isn’t detected.

After quiting the defrosting mode, the fan motor enter cooling prevention mode. 3.Defrosting oscillogram:

Automatic temperature compensation of heating:

1. Conditions: Halt time of compressor is below 5 minutes. 2. Operation rules: 1) Ts=Tr + 5℃ + (Tr – Td (temperature detected)[the moment of startup]) 2)Tr – Td[the moment of startup] ≤ 2℃ Note: the two items above is disable when starting for the first time.

Air Conditioner Edition:2006/1/10

zhanglizhi
38
Page 47: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

3)Press “-“ button in the remote controller, and then restore Ts = Tr + 5℃. Press “+” button in the remote controller, and then operate according to automatic

compensation setting 4)If Tr – Td [before compressor starts] ≤0℃, and then operate according to

Ts = Tr + 5℃. 3. If air door in ”health airflow mode” and blow up, the temp. setting of heating is added by 2℃ in

the base of beginnig. 4.Control function: 4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum time unit is 1

minute. After setting, a pattern of clock displaied on the LCD, and it is off when timer setting is completed. There are several timer mode as follows.

Timer on: The pattern of clock displaied on the LCD,the background light is off, and unit behaves with halt status. Timer on is completed, and then unit starts running with the pattern of clock disappeared,and the background light is on. The unit starts with the last setting receiving timer signals, and sleep setting is not allowed.

Timer off: Unit working, the pattern of clock displaied on the LCD; When reaching time setting, unit enters shutdown mode, and sleep function can be set. If timer off and sleep are set synchronously, the one which time is short run first. Executing shutdown instruction clear timer and sleep function.

Timer on and timer off can be set synchronously. when they are completed, 4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD

In cooling/defrosting mode, the temp. setting increases 1℃ one hour later after startup. After another hour the temp. setting increase by more 1℃ and then run continuously for another 6 hours and then close.

In heating mode, the temp. setting decrease 2℃ one hour after startup. After another hour the temp. setting decrease by more 2℃. After 3 hours the temp. setting rise by 1℃and then run continuously for another 3 hours and then close.

If the wind speed is set to high or medium before going to bed, the wind speed shifts to medium or low. If the wind speed is set to low before going to bed, the wind speed keep unchanged.

4.3 Protection of malfunction of temperature sensitive resistance. The temperature sensitive resistor is short circuit or open circuit, the machine doesn’t work. During defrosting, don’t detect if the temperature sensor short circuit or open circuit. Detect the temperature of coil pipe is below -40℃, then think the temperation circuit of coil

pipe is open. Detect the temperature of coil pipe is above 95℃, then think the temperation circuit of coil pipe

is short . Detect the temperature of inlet air is below -20℃, then think the temperation circuit of inlet air

is open. Detect the temperature of inlet air is above 90℃, then think the temperation circuit of inlet air

is short. 4.4 Emergency switch imput:

Press the switch of emergency operation, then buzzer rings once and unit enters the automatic operation mode. (emergency operation)

Air Conditioner Edition:2006/1/10

zhanglizhi
39
Page 48: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter enter test run mode.

Press the switch again, and then closes. The unit can receive remote control. Enter emergency operation from timer mode, then timer is cancelled. Test run:

1) The temperature sensor of inlet air doesn’t work, and compressor starts (but subject to the limit of -minute delay excluding the first time), and high wind, cooling, and air door is open.The indoor fan motor runs, running indicator lights up, compressor relay and the one of outdoor fan motor is closed

2) During test run: The prevention of freezing of evaporator doesn’t work. Over current control doesn’t work. The control of current peak expiration doesn’t work. Temperature control doesn’t work. Temperature expiration control doesn’t work. The test run is over after 30 minutes,then the unit turn off

4.5 Executive function after 2 seconds by remoter control: After receiving remote control signal, the mainboard doesn’t enter the corresponding

instruction task until 2 seconds elapse.

The memory function of power down is available, and the auto recovery function of power on is optional. (In auto, heating, cooling, or defrosting status, press the “sleeping” button 10 times within 5 seconds, and the auto recovery function of power on can be set on/off. If the buzzer rings 4 times, the the auto recovery function of power on is available; If the buzzer rings 2 times, the the auto recovery function of power on is unavailable.)

4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and the impulse from fan motor is not detected, then stop outputting voltage to indoor fan motor, send alarm signals. 4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30℃, and press the sleeping

button for 6 times within 5 seconds, and after the buzzer rings 3 times, the air conditioner enter manual defrosting mode, which is the same as heating defrosting.

Air Conditioner Edition:2006/1/10

zhanglizhi
40
Page 49: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

2. Run mode:(Tr: inlet air temperature,Ts:the set temperature) 2.1 automatic run mode The background lighting of the LCD is white 1) cooling only type automatic run mode:

When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts+3℃ Choose Cooling mode Tr<Ts-3℃ Choose Blowing Mode The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, it will switch to blowing mode when Tr<Ts-3℃; if the system is currently under blowing mode, it will in turn switch to cooling mode when Tr > Ts+3℃. The switching mode as below, 2) cold/warm type run mode: When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts-3℃ Choose Cooling Mode Tr<Ts-3℃ Choose Heating Mode

The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, the compressor will stop functioning if the temperature lowers to such a degree that requires so; then it will recheck the temperature 15 minutes later: it will switch to the heating mode if the temperature is Tr<Ts-3℃,or it will still stay in cooling mode(including blowing mode). if the system is currently under heating mode, the compressor will stop running if the temperatur lowers to such a degree that requires so, then it will recheck teh temperatur

Air Conditioner Edition:2006/1/10

zhanglizhi
41
Page 50: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

15 minutes later: it will switch to the cooling mode if the temperature is Tr>Ts+3℃.

2.2 Cooling run mode: (Tr: inlet air temperature,Ts:the set temperature) The background lighting of the LCD is blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Compressor can’t be controlled by temperature sensor within 2 minutes after it starts. Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan

motor run at fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr > Ts, outdoor fan motor and compressor are working again.

If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressor’s state will not change.

wind speed control: (the temperature difference is 1℃) auto: when Tr>=Ts+3℃, the wind speed is high;

when Ts+1℃≤Tr<Ts+3℃, the wind speed is medium. When Tr<Ts+1℃, the wind speed is low. When temperature sensor is off, the fan motor runs at low speed. when the wind speed changes from low to higher, there is no delay, and when it changes from high to lower, there is a 3-minutes delay before conversion.

Manual operation: When unit is on the wind speed can be set to high, medium, low or automatic as required (execute instruction 2 seconds later after receiving remote signal)

compressor control:The compressor can’t be controlled by temperature sensor within 2 minutes after

startup and can be only restarted at least 3 minutes later after shutdown. There is no 3-minute

protection with power on for the first time (over 3 minutes with power off). The compressor must

stands by for 3 minutes before it is restarted after shutdown. There is no 2-minute limit when changing the temperature setting or shutting down the

machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the compressor startup.

Controlling the position of air door: set the position of air door as required. Protection of expiration of current peak value is available: Current cross detection is

available in order to avoid burning out the compressor when the current is too big. The action

character as follows: The compressor can’t be detected in 60 seconds after startup. when current is above

“CT 1.6 V” and lasts 3 seconds, the system enter protection mode and shut off compressor with

outdoor air

Air Conditioner Edition:2006/1/10Air Conditioner Edition:2006/1/10

zhanglizhi
42
Page 51: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

blower and indoor fan motor controlled as the temperature sensor is off. After 3 minutes the

machine can be started again. Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat

exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Timer on, Timer off and sleep control are available. 2.3 Dehumidifying mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is aquamarine blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ control character:

When Tr (indoor temperature) > Ts (temperature setting) +2℃, compressor and outdoor fan motor run continuosly with indoor fan motor runnig in accordance with the wind speed setting.

When Tr ranges from Ts to Ts +2℃, outdoor fan motor and compressor are on for 10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after shutdown of compressor and gives breeze in other time.

When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor fan motor enter breeze mode 3 minutes later after shut down of compressor.

When all the ranges alternate, there is ±1℃ difference. Wind speed control: Automation: When Tr >= Ts + 5℃, the wind speed is high. When Ts+3℃≤ Tr <Ts+5℃, the wind speed is medium.

When Ts+2℃≤ Tr <Ts+3℃, the wind speed is low. When Ts≤ Tr <Ts+2℃, the machine gives breeze intermittently.

When Tr < Ts, the indoor fan motor is shut off. in 3 minutes When Tr < Ts, the machine gives breeze after 3 minutes

Manual operation: When the temperation sensor is off or the Indoor fan motor runs intermittently, the indoor fan motor can not be operated by hand (compelling automatic operation), along with the indoor fan motor can be operated in cooling mode. While controlling fan motor by hand in cooling mode, the cooling ranges include wind speed setting and refriferation range, others are the same as fan motor in automation mode.

compressor control:The compressor can’t be controlled by temperature sensor in 2 minutes after

startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minutes protection with power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes later after shutdown.

There is no 2-minutes limit when changing the temperature setting or shutting off the

Air Conditioner Edition:2006/1/10

zhanglizhi
43
Page 52: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor startup.

Controlling the position of air door: set the position of air door as required. Protection of expiration of current peak value is available: Current cross detection is

available in order to avoid burning out the compressor when the current is too big. The action

character as follows: The compressor can’t be detected in 60 seconds after startup. when current is above

“CT 1.6 V” and lasts 3 seconds, the system enter protection mode and shut off compressor with

outdoor air blower and indoor fan motor controlled as the temperature sensor is off. After 3

minutes the machine can be started again.

Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat

exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Timer on, Timer off and sleep control are available. 2.4 Heating mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is red Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Control Character: When Tr ≤ Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan

motor runs as in cold blast avoidance mode, and 4℃of compensation is added after compressor is started.

When Tr>Ts+5℃, compressor is off, and the indoor fan motor runs as in cold blast avoidance mode.

When Tr<Ts+5℃, compressor, four-ways valve and outdoor fan motor is on, and the indoor fan motor runs as in the mode of avoiding cold blast.

Control of indoor fan motor: Manual operation: The wind speed can be set to high, medium, low or automatic as

required. Automatic operation: When Tr < Ts, the wind speed is high; When Ts=<Tr<Ts+2℃, the wind speed is medium. When Tr>= Ts+2℃, the wind speed is low.

Control of air door: setting the position of air door as required. compressor control:The compressor can’t be controlled by temperature sensor in 2

Air Conditioner Edition:2006/1/10

zhanglizhi
44
Page 53: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

minutes after startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minute protection with power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes later after shutdown.

There is no 2-minutes limit when changing the temperature setting or shutting off the machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outlet air is available 2 seconds later after startup. Timer on, Timer off and sleep control are available. Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts

runnig 10 seconds earlier than compressor does. After compressor stops runnig, the 4-way valve continues running for 2 minutes and 30 seconds then stops. If changing the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and compressor is started 3 minutes later.

Cold blast avoidance mode: (1)Compressor is interrupted during the defrosting operation and continues to run after

defrosting is completed. When the indoor exchanging temperature is below 23℃, the indoor fan motor is off. When the indoor exchanging temperature is above 23℃, the indoor fan motor is running at weak speed.

(2)If the temperature of coil pipe can’t be above 38℃ 4 minutes later after startup, fan motor is running at the preset wind speed.

(3) If the temperature of coil pipe is above 38℃ in 4 minutes after start up, fan motor is running at the preset wind speed immediately.

(4)If coil pipe descends to the temp. lower than 38℃ from 38℃. fan motor still running at the preset wind speed.

(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil pipe is above 23℃, fan motor enter breeze mode; and if the temperature of coil pipe is below 20℃, fan motor stops running.

(6)Shut down the unit and indoor fan motor stops running. High temperature protection and high temperature expiration protection:

High temperature prevention: When the temp. of coil pipe is above 65℃, the outdoor fan motor stops.When the temp descends to 60℃, the outdoor fan motor is restarted and fan speed invertage frequence is more than 45 seconds. High temperature expiration prevention: When the temp. of coil pipe is above 72℃,compressor and outdoor fan motor stop running 2 seconds later, and inlet air runs as the temp. sensor is off. When compressor stands by for 3 minute and the temp. of coil pipe is below 64℃, the unit can be started again.

Current protection and current expiration protection: (Not detecting within 60 seconds after startup)

Current protection: If current detected is above (CT1) and lasts 10 senconds continuously, outlet air stops. If current detected is below (CT2) , outlet air is regained。Current peak expiration protection: If current detected is above (CT3) , 3 seconds later the system enter current cross protection, compressor and air outlet stop and start again 3 minuts later, and air inlet runs as the temperature sensor is

Air Conditioner Edition:2006/1/10

zhanglizhi
45
Page 54: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

off.(different mode has the different CT value) Overcooling protection: One and a half minute later after compressor starts, if the temperature of coil pipe is

below -4℃, compressor and air outlet stop, and air inlet runs according to the temp. setting. Compressor can be restarted 3 minutes later.

Defrosting: 1.Entry conditions of defrosting:

A. Indoor unit enter overload protection and air outlet stops when air outlet has been restarted and runs over 10 minutes, and compressor runs over 45 minutes in total and over 20 minutes continuously, and the temp. of indoor coil pipe is below 38℃.

B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe decreases 1℃ per 6 minutes and this operation repeats 3 times, and the temp. of coil pipe is below 38℃, then 5 minutes later . the system enters defrosting mode.

C. When compressor runs over 3 hours in total and over 20 minutes continuously and after the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

D. The difference between the temp. of indoor coil pipe and the indoot temp. is below 18℃ and lasts 5 minutes, compressor runs over 45 minutes in total and over 20 minutes continuously, the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

2.Exit conditions of defrosting: Defrosting time is higher than 12 minutes (compressor is on), or CT current is above

(CT1). During the defrosting, if current peak value is cut off, the unit quit the defrosting

mode. But the protection of expiration of current peak value is unavailable with 60 senconds after compressor is started.

During the defrosting and 2 minutes after the defrosting, abnormality of temp. sensor isn’t detected.

After quiting the defrosting mode, the fan motor enter cooling prevention mode. 3.Defrosting oscillogram:

Air Conditioner Edition:2006/1/10

zhanglizhi
46
Page 55: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Automatic temperature compensation of heating:

1. Conditions: Halt time of compressor is below 5 minutes. 2. Operation rules: 1) Ts=Tr + 5℃ + (Tr – Td (temperature detected)[the moment of

startup]) 2)Tr – Td[the moment of startup] ≤ 2℃ Note: the two items above is disable when starting for the first time. 3)Press “-“ button in the remote controller, and then restore Ts = Tr + 5℃.

Press “+” button in the remote controller, and then operate according to automatic compensation setting

4)If Tr – Td [before compressor starts] ≤0℃ , and then operate according to

Ts = Tr + 5℃. 4.Control function: 4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum

time unit is 1 minute. After setting, a pattern of clock displaied on the LCD, and it is off when timer setting is completed. There are several timer mode as follows.

Timer on: The pattern of clock displaied on the LCD,the background light is off, and unit behaves with halt status. Timer on is completed, and then unit starts running with the pattern of clock disappeared,and the background light is on. The unit starts with the last setting receiving timer signals, and sleep setting is not allowed.

Timer off: Unit working, the pattern of clock displaied on the LCD; When reaching time setting, unit enters shutdown mode, and sleep function can be set.

Air Conditioner Edition:2006/1/10

zhanglizhi
47
Page 56: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

If timer off and sleep are set synchronously, the one which time is short run first. Executing shutdown instruction clear timer and sleep function.

Timer on and timer off can be set synchronously. when they are completed, 4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD

In cooling/defrosting mode, the temp. setting increases 1℃ one hour later after startup. After another hour the temp. setting increase by more 1℃ and then run continuously for another 6 hours and then close.

In heating mode, the temp. setting decrease 2℃ one hour after startup. After another hour the temp. setting decrease by more 2℃. After 3 hours the temp. setting rise by 1℃and then run continuously for another 3 hours and then close.

If the wind speed is set to high or medium before going to bed, the wind speed shifts to medium or low. If the wind speed is set to low before going to bed, the wind speed keep unchanged.

4.3 Protection of malfunction of temperature sensitive resistance. The temperature sensitive resistor is short circuit or open circuit, the machine

doesn’t work. During defrosting, don’t detect if the temperature sensor short circuit or open

circuit. Detect the temperature of coil pipe is below -40℃, then think the temperation

circuit of coil pipe is open. Detect the temperature of coil pipe is above 95℃, then think the temperation

circuit of coil pipe is short . Detect the temperature of inlet air is below -20℃, then think the temperation

circuit of inlet air is open. Detect the temperature of inlet air is above 90℃, then think the temperation

circuit of inlet air is short. 4.4 Emergency switch imput:

Press the switch of emergency operation, then buzzer rings once and unit enters the automatic operation mode. (emergency operation)

If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter enter test run mode.

Press the switch again, and then closes. The unit can receive remote control. Enter emergency operation from timer mode, then timer is cancelled.

Test run:

1) The temperature sensor of inlet air doesn’t work, and compressor starts (but subject to the limit of -minute delay excluding the first time), and high wind, cooling, and air door is open.The indoor fan motor runs, compressor relay and the one of outdoor fan motor is closed

2) During test run: The prevention of freezing of evaporator doesn’t work. Over current control doesn’t work. The control of current peak expiration doesn’t work.

Air Conditioner Edition:2006/1/10

zhanglizhi
48
Page 57: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Temperature control doesn’t work. Temperature expiration control doesn’t work. The test run is over after 30 minutes,then the unit turn off

4.5 Executive function after 2 seconds by remoter control: After receiving remote control signal, the mainboard doesn’t enter the

corresponding instruction task until 2 seconds elapse.

The memory function of power down is available, and the auto recovery function of power on is optional. (In auto, heating, cooling, or defrosting status, press the “sleeping” button 10 times within 5 seconds, and the auto recovery function of power on can be set on/off. If the buzzer rings 4 times, the the auto recovery function of power on is available; If the buzzer rings 2 times, the auto recovery function of power on is unavailable.)

4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and the impulse from fan motor is not detected, then stop outputting voltage to indoor fan motor, send alarm signals. 4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30℃, and press the

sleeping button for 6 times within 5 seconds, and after the buzzer rings 3 times, the air conditioner enter manual defrosting mode, which is the same as heating defrosting.

Air Conditioner Edition:2006/1/10

zhanglizhi
49
Page 58: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

2. Run mode:(Tr: inlet air temperature,Ts:the set temperature) 2.1 automatic run mode The background lighting of the LCD is white 1) cooling only type automatic run mode:

When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts+3℃ Choose Cooling mode Tr<Ts-3℃ Choose Blowing Mode The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, it will switch to blowing mode when Tr<Ts-3℃; if the system is currently under blowing mode, it will in turn switch to cooling mode when Tr > Ts+3℃. The switching mode as below, 2) cold/warm type run mode: When the system runs under "automatic" mode for the first time, it will determine the operating mode according to the follows, Tr≥Ts-3℃ Choose Cooling Mode Tr<Ts-3℃ Choose Heating Mode

The system will shift its operating mode between the above mentioned two to changes of the indoor temperature. If the system is currently under cooling mode, the compressor will stop functioning if the temperature lowers to such a degree that requires so; then it will recheck the temperature 15 minutes later: it will switch to the heating mode if the temperature is Tr<Ts-3℃,or it will still stay in cooling mode(including blowing mode). if the system is currently under heating mode, the compressor will stop running if the temperatur lowers to such a degree that requires so, then it will recheck teh temperatur

Air Conditioner Edition:2006/1/10

zhanglizhi
50
Page 59: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

15 minutes later: it will switch to the cooling mode if the temperature is Tr>Ts+3℃.

2.2 Cooling run mode: (Tr: inlet air temperature,Ts:the set temperature) The background lighting of the LCD is blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Compressor can’t be controlled by temperature sensor within 2 minutes after it starts. Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan

motor run at fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr > Ts, outdoor fan motor and compressor are working again.

If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressor’s state will not change.

wind speed control: (the temperature difference is 1℃) auto: when Tr>=Ts+3℃, the wind speed is high;

when Ts+1℃≤Tr<Ts+3℃, the wind speed is medium. When Tr<Ts+1℃, the wind speed is low. When temperature sensor is off, the fan motor runs at low speed. when the wind speed changes from low to higher, there is no delay, and when it changes from high to lower, there is a 3-minutes delay before conversion.

Manual operation: When unit is on the wind speed can be set to high, medium, low or automatic as required (execute instruction 2 seconds later after receiving remote signal)

compressor control:The compressor can’t be controlled by temperature sensor within 2 minutes after

startup and can be only restarted at least 3 minutes later after shutdown. There is no 3-minute

protection with power on for the first time (over 3 minutes with power off). The compressor must

stands by for 3 minutes before it is restarted after shutdown. There is no 2-minute limit when changing the temperature setting or shutting down the

machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the compressor startup.

Controlling the position of air door: set the position of air door as required. Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat

exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Air Conditioner Edition:2006/1/10

zhanglizhi
51
Page 60: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Timer on, Timer off and sleep control are available. 2.3 Dehumidifying mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is aquamarine blue Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ control character:

When Tr (indoor temperature) > Ts (temperature setting) +2℃, compressor and outdoor fan motor run continuosly with indoor fan motor runnig in accordance with the wind speed setting.

When Tr ranges from Ts to Ts +2℃, outdoor fan motor and compressor are on for 10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after shutdown of compressor and gives breeze in other time.

When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor fan motor enter breeze mode 3 minutes later after shut down of compressor.

When all the ranges alternate, there is ±1℃ difference. Wind speed control: Automation: When Tr >= Ts + 5℃, the wind speed is high. When Ts+3℃≤ Tr <Ts+5℃, the wind speed is medium.

When Ts+2℃≤ Tr <Ts+3℃, the wind speed is low. When Ts≤ Tr <Ts+2℃, the machine gives breeze intermittently.

When Tr < Ts, the indoor fan motor is shut off. in 3 minutes When Tr < Ts, the machine gives breeze after 3 minutes

Manual operation: When the temperation sensor is off or the Indoor fan motor runs intermittently, the indoor fan motor can not be operated by hand (compelling automatic operation), along with the indoor fan motor can be operated in cooling mode. While controlling fan motor by hand in cooling mode, the cooling ranges include wind speed setting and refriferation range, others are the same as fan motor in automation mode.

compressor control:The compressor can’t be controlled by temperature sensor in 2 minutes after

startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minutes protection with power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes later after shutdown.

There is no 2-minutes limit when changing the temperature setting or shutting off the machine

through the remote controller, and the machine can be shut down immediately. Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor

startup. Controlling the position of air door: set the position of air door as required. Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat

exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut off when the temperature of the indoor coil pipe is or below 0℃ and the compressor runs for over 5 minutes. When the temperature of the indoor

Air Conditioner Edition:2006/1/10

zhanglizhi
52
Page 61: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes delay)

Timer on, Timer off and sleep control are available. 2.4 Heating mode: (Tr: inlet air temperature,Ts:the set temperature)

The background lighting of the LCD is red Temperature control range : 16℃—30℃ Temperature control precision: ±1℃ Control Character: When Tr ≤ Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan

motor runs as in cold blast avoidance mode, and 4℃of compensation is added after compressor is started.

When Tr>Ts+5℃, compressor is off, and the indoor fan motor runs as in cold blast avoidance mode.

When Tr<Ts+5℃, compressor, four-ways valve and outdoor fan motor is on, and the indoor fan motor runs as in the mode of avoiding cold blast.

Control of indoor fan motor: Manual operation: The wind speed can be set to high, medium, low or automatic as

required. Automatic operation: When Tr < Ts, the wind speed is high; When Ts=<Tr<Ts+2℃, the wind speed is medium. When Tr>= Ts+2℃, the wind speed is low.

Control of air door: setting the position of air door as required. compressor control:The compressor can’t be controlled by temperature sensor in 2

minutes after startup and also can’t be started again at least 3 minutes later after shutdown. There are 3-minute protection with power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes later after shutdown.

There is no 2-minutes limit when changing the temperature setting or shutting off the machine through the remote controller, and the machine can be shut down immediately.

Avoiding electrical shock: outlet air is available 2 seconds later after startup. Timer on, Timer off and sleep control are available. Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts

runnig 10 seconds earlier than compressor does. After compressor stops runnig, the 4-way valve continues running for 2 minutes and 30 seconds then stops. If changing the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and compressor is started 3 minutes later.

Cold blast avoidance mode: (1)Compressor is interrupted during the defrosting operation and continues to run after

defrosting is completed. When the indoor exchanging temperature is below 23℃, the indoor fan motor is off. When the indoor exchanging temperature is above 23℃, the indoor fan motor is running at weak speed.

(2)If the temperature of coil pipe can’t be above 38℃ 4 minutes later after startup, fan motor is running at the preset wind speed.

Air Conditioner Edition:2006/1/10

zhanglizhi
53
Page 62: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

(3) If the temperature of coil pipe is above 38℃ in 4 minutes after start up, fan motor is running at the preset wind speed immediately.

(4)If coil pipe descends to the temp. lower than 38℃ from 38℃. fan motor still running at the preset wind speed.

(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil pipe is above 23℃, fan motor enter breeze mode; and if the temperature of coil pipe is below 20℃, fan motor stops running.

(6)Shut down the unit and indoor fan motor stops running. High temperature protection and high temperature expiration protection:

High temperature prevention: When the temp. of coil pipe is above 58℃, the outdoor fan motor stops.When the temp descends to 55℃, the outdoor fan motor is restarted and fan speed invertage frequence is more than 45 seconds. High temperature expiration prevention: When the temp. of coil pipe is above 68℃,compressor and outdoor fan motor stop running 2 seconds later, and inlet air runs as the temp. sensor is off. When compressor stands by for 3 minute and the temp. of coil pipe is below 46℃, the unit can be started again.

Overcooling protection: One and a half minute later after compressor starts, if the temperature of coil pipe is

below -4℃, compressor and air outlet stop, and air inlet runs according to the temp. setting. Compressor can be restarted 3 minutes later.

Defrosting: 1.Entry conditions of defrosting:

A. Indoor unit enter overload protection and air outlet stops when air outlet has been restarted and runs over 10 minutes, and compressor runs over 45 minutes in total and over 20 minutes continuously, and the temp. of indoor coil pipe is below 38℃.

B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe decreases 1℃ per 6 minutes and this operation repeats 3 times, and the temp. of coil pipe is below 38℃, then 5 minutes later . the system enters defrosting mode.

C. When compressor runs over 3 hours in total and over 20 minutes continuously and after the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

D. The difference between the temp. of indoor coil pipe and the indoot temp. is below 18℃ and lasts 5 minutes, compressor runs over 45 minutes in total and over 20 minutes continuously, the temp. of indoor coil pipe is below 38℃, the system enters defrosting mode.

2.Exit conditions of defrosting: Defrosting time is higher than 12 minutes (compressor is on)

During the defrosting, if current peak value is cut off, the unit quit the defrosting mode. But the protection of expiration of current peak value is unavailable with 60 senconds after compressor is started.

During the defrosting and 2 minutes after the defrosting, abnormality of temp.

Air Conditioner Edition:2006/1/10

zhanglizhi
54
Page 63: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

sensor isn’t detected. After quiting the defrosting mode, the fan motor enter cooling prevention mode.

3.Defrosting oscillogram:

Automatic temperature compensation of heating:

1. Conditions: Halt time of compressor is below 5 minutes. 2. Operation rules: 1) Ts=Tr + 5℃ + (Tr – Td (temperature detected)[the moment of

startup]) 2)Tr – Td[the moment of startup] ≤ 2℃ Note: the two items above is disable when starting for the first time. 3)Press “-“ button in the remote controller, and then restore Ts = Tr + 5℃.

Press “+” button in the remote controller, and then operate according to automatic compensation setting

4)If Tr – Td [before compressor starts] ≤0℃ , and then operate according to

Ts = Tr + 5℃. 4.Control function: 4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum

time unit is 1 minute. After setting, a pattern of clock displaied on the LCD, and it is off when timer setting is completed. There are several timer mode as follows.

Timer on: The pattern of clock displaied on the LCD,the background light is off, and unit behaves with halt status. Timer on is completed, and then unit starts running with the pattern of clock disappeared,and the background light is on. The unit starts with the last setting receiving timer signals, and sleep setting is

Air Conditioner Edition:2006/1/10

zhanglizhi
55
Page 64: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

not allowed. Timer off: Unit working, the pattern of clock displaied on the LCD; When

reaching time setting, unit enters shutdown mode, and sleep function can be set. If timer off and sleep are set synchronously, the one which time is short run first. Executing shutdown instruction clear timer and sleep function.

Timer on and timer off can be set synchronously. when they are completed, 4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD

In cooling/defrosting mode, the temp. setting increases 1℃ one hour later after startup. After another hour the temp. setting increase by more 1℃ and then run continuously for another 6 hours and then close.

In heating mode, the temp. setting decrease 2℃ one hour after startup. After another hour the temp. setting decrease by more 2℃. After 3 hours the temp. setting rise by 1℃and then run continuously for another 3 hours and then close.

If the wind speed is set to high or medium before going to bed, the wind speed shifts to medium or low. If the wind speed is set to low before going to bed, the wind speed keep unchanged.

4.3 Protection of malfunction of temperature sensitive resistance. The temperature sensitive resistor is short circuit or open circuit, the machine

doesn’t work. During defrosting, don’t detect if the temperature sensor short circuit or open

circuit. Detect the temperature of coil pipe is below -40℃, then think the temperation

circuit of coil pipe is open. Detect the temperature of coil pipe is above 95℃, then think the temperation

circuit of coil pipe is short . Detect the temperature of inlet air is below -20℃, then think the temperation

circuit of inlet air is open. Detect the temperature of inlet air is above 90℃, then think the temperation

circuit of inlet air is short. 4.4 Emergency switch imput:

Press the switch of emergency operation, then buzzer rings once and unit enters the automatic operation mode. (emergency operation)

If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter test run mode.

Press the switch again, and then closes. The unit can receive remote control. Enter emergency operation from timer mode, then timer is cancelled.

Test run:

1) The temperature sensor of inlet air doesn’t work, and compressor starts (but subject to the limit of -minute delay excluding the first time), and high wind, cooling, and air door is open.The indoor fan motor runs, compressor relay and the one of outdoor fan motor is closed

2) During test run:

Air Conditioner Edition:2006/1/10

zhanglizhi
56
Page 65: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

The prevention of freezing of evaporator doesn’t work. Over current control doesn’t work. The control of current peak expiration doesn’t work. Temperature control doesn’t work. Temperature expiration control doesn’t work. The test run is over after 30 minutes,then the unit turn off

4.5 Executive function after 2 seconds by remoter control: After receiving remote control signal, the mainboard doesn’t enter the

corresponding instruction task until 2 seconds elapse.

The memory function of power down is available, and the auto recovery function of power on is optional. (In auto, heating, cooling, or defrosting status, press the “sleeping” button 10 times within 5 seconds, and the auto recovery function of power on can be set on/off. If the buzzer rings 4 times, the auto recovery function of power on is available; If the buzzer rings 2 times, the auto recovery function of power on is unavailable.)

4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and the impulse from fan motor is not detected, then stop outputting voltage to indoor fan motor, send alarm signals. 4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30℃, and press the

sleeping button for 6 times within 5 seconds, and after the buzzer rings 3 times, the air conditioner enter manual defrosting mode, which is the same as heating defrosting.

5.express mode of malfunction:

Air Conditioner Edition:2006/1/10

zhanglizhi
57
Page 66: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Error Codes and Description Code indication

indoor Description

Reference Page

E1 Room temperature sensor failure

E2 Heat-exchange sensor failure

E4 Indoor EEPROM error/Humidity sensor malfunction Indoor Malfunction

E14 Indoor fan motor malfunction

Trouble Shooting E1: Room temperature sensor failure CN8 E2: Heat-exchange sensor failure CN8

E4: Indoor EEPROM error: Replace the PCB of indoor unit

YES

NO

YES

whether terminal CN8 on

indoor PCB contact wellt?

Pull out the terminals on the indoor mainboard and

reinsert them

Pull the sensor out of the mainboard

1) Measure the value of resistance Between its tw o

jumpers

2) Measure the temperature at the room temperature

sensing head.

Check the value of the

sensor to see whether the

sensor is damaged or not?

NO Sensor is broken,replace it with new sensor

The indoor PCB is broken, replace with new indoor PCB

Air Conditioner Edition:2006/1/10

zhanglizhi
58
Page 67: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

E14 :Indoor fan motor malfunction

Yes

Yes

YES

NO

whether terminal CN7

and CON12 on indoor PCB

well inserted or not?

Pull out and reinsert the terminals

Electrify the machine again and turn it on in the cooling operation,

Measure voltage between the positions 1 ( red wire) and 5( black

wire) of Terminal CON12 on the indoor PCB

NO the indoor pcb is damaged and need replace . the voltage is about

90-200vac

check whether motor

can run when

turn on the unit

the indoor motor is damaged and need

replace

NO

When motor is running Measure

whether there is voltage

pulse(0-5VDC) between the

positions 2 (middle wire) and

3( black wire) of Terminal

CN7on the indoor PCB

the indoor motor is damaged and need

replace

the indoor pcb is damaged and need replace

NO

Air Conditioner Edition:2006/1/10

zhanglizhi
59
Page 68: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner

TROUBLE SHOOTING

60

Edition:2006/1/10

Page 69: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10

zhanglizhi
zhanglizhi
61
Page 70: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner

INSTALLATION

62

Edition:2006/1/10

Page 71: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Installation Manual of Room Air Conditioner

The models adopt HFC free refrigerant R410A

mor

e th

an 5

cm

The marks from to in the figure are the parts numbers.

The distance between the indoor unit and the floor should bemore than 2m.

more than 10cm

Read this manual before installation

1.Driver2.Hacksaw3.Hole core drill4.Spanner(17,19 and 26mm)

5.Torque wrench(17mm,22mm,26mm)6.Pipe cutter7.Flaring tool8.Knife

9.Nipper 12.Reamer10.Gas leakage detector or soap-and-water solution11.Measuring tape

Explain sufficiently the operating means to the useraccording to this manual.

A G

No. Accessory parts

Remote controller

R-03 dry battery

Mounting plate

Drain hose

ScrewPlastic cap

Drain-elbow

Cushion

21

2

3

4

5

6

7

4

2

2

8

1

4

Number ofarticles

Accessory parts

4X25

Indoor unit A

Indoor unit B

more than 10cm

more than 60cmmore than 15cm

more than 10cm

Attention must be paid tothe rising up of drain hose

C

more than 10cm

Drawing for the installation of indoor and outdoor units

Necessary Tools for Installation

A

B

C

D

E

F

G

Optional parts for piping

Mark Parts name

Non-adhesive tape

Adhesive tape

Saddle(L.S) with screws

Connecting electric cablefor indoor and outdoor

Drain hose

Heating insulating material

Piping hole cover

Arrangement of piping directions

Rear left

Rearright

Left

BelowRight

Air Conditioner Edition:2006/1/10

zhanglizhi
63
Page 72: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Fixing of outdoor unit

Indoor Unit Selection of Installation Place

Power Source

Selection of pipe

Outdoor Unit

Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.

When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nailsor wires in consideration of earthquake and strong wind.

If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Place, robust not causing vibration, where the body can be supportedsufficiently.Place, not affected by heat or steam generated in the vicinity, whereinlet and outlet of the unit are not disturbed.Place, possible to drain easily, where piping can be connected with theoutdoor unit.Place, where cold air can be spread in a room entirely.Place, nearby a power receptacle, with enough space around. (Referto drawings).Place where the distance of more than lm from televisions, radios,wireless apparatuses and fluorescent lamps can be left.In the case of fixing the remote controller on a wall, place where theindoor unit can receive signals when the fluorescent lamps in the roomare lightened.

Place, which is less affected by rain or direct sunlight and issufficiently ventilated.Place, possible to bear the unit, where vibration and noise arenot increased.Place, where discharged wind and noise do not cause anuisance to the neighbors.Place, where a distance marked is available as illustratedin the above figure.

Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.

Install an exclusive branch circuit of the power.

A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

To this unit, both liquid and gas pipes shall be insulated

as they become Iow temperature in operation.

Use optional parts for piping set or pipes covered with

equivalent insulation material.

The thickness of the pipe must be 0.8 mm at least.

Liquid pipe( )

Gas pipe( )

64

6.35mm(1/4")

9.52mm(3/8")

6.35mm(1/4")

12.7mm(1/2")

Floor fixing dimensionsof the outdoor unit(Unit:mm)

For 07,09,12 For 18,22

HSU-09HV03/R2HSU-07HV03/R2HSU-12HV03/R2

HSU-18HV03/R2HSU-22HV03/R2

Floor fixing dimensionsof the outdoor unit(Unit:mm)

500140 140

256

583 113.5113.5

319.

5

Floor fixing dimensionsof the outdoor unit(Unit:mm)

Air Conditioner Edition:2006/1/10

Page 73: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Indoor unit1.Fitting of the Mounting Plate and Positioning of the wall Hole

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

When the mounting plate is first fixed

When the mounting plate is fixed side bar and lintel

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.3. Find the wall hole location A using a measuring tape

Refer to the previous article, " When the mounting plate is first fixed ", for theposition of wall hole.

Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten

the plate to the fixed mounting bar.

Make a hole of 70 mm in diameter,

slightly descending to outside the wall.

Install piping hole cover and seal it

off with putty after installation

(Section of wall hole) Piping hole pipe

Outdoor side

Thicknessof wall

Indoor side

Wall hole

70mm

3.Installation of the Indoor Unit

Drawing of pipe

[ Rear piping ]Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left Left-rear piping ]In case of left side piping, cut away, with a nipper, the lid for left piping.In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rearpiping which is marked on heat insulation materials.

65

G

A=80mm

35

Fit the level line

Air Conditioner Edition:2006/1/10

Page 74: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

4.Connecting the indoor/outdoor Electric Cable

Fixing the indoor unit body

Removing the wiring cover

[Other direction piping]

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe accordingto the position of wall hole. When bending, be careful not to crash pipes.Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulationof connecting part specially.

Hang surely the unit body onto the upper notches of themounting plate. Move the body from side to side to verifyits secure fixing.In order to fix the body onto the mounting plate,hold upthe body aslant from the underside and then put it downperpendicularly.

Remove terminal cover at right bottom corner of indoor unit, thentake off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.2. Pull out the cable on the front side, and connect the cable making a loop.

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

66

Lid for right piping

Lid for under pipingLid for left piping

Fix with adhesive tape

Heat insulationmaterial

Drain hose

Piping

Indoor/outdoor electric cable

Pipe supporting plate

Air Conditioner Edition:2006/1/10

Page 75: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is H05RN-F or H07RN-F.2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.3. The wiring method should be in line with the local wiring standard.4. After installation, the power plug should be easily reached.

67

5.Easily-demount cleaning of indoor unit1.Top inlet can be taken down

Open the inlet grille, press the claw of the clip on the unit,then take down the top inlet.(according to figure 1)

2.Vertical flap can be taken downOverturn the vertical flap, press the claw of the clip ,then take down vertical flap.(according to figure 2)

3.Horizontal louvers can be taken downAfter taking down vertical flap.Horizontal louvers are appeared,draw the middle louver,and take down the horizontal louvers .(according to figure 3)

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.Pull the cable slightly to make sure the cables have been properly inserted and tightened.After the cable connection, never fail to fasten the connected cable with the wiring cover.Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not be carried out and will cause defect.

Figure 3

HSU-07HV03/R2

YEL/GRN

BLK WHT

REDBR

YEL/GRN

BR

RED

BLK

WHT

Indoor unit Outdoor unit

HSU-09HV03/R2

claw of the clip

Figure 1

Figure 2

Figure 2

Daff

Indoor unit

Outdoor unit

YEL/GRN

BLK WHTYEL/GRN

WHT

BLK 1(L)2(N

)

REDBR

RED

BR

HSU-18HV03/R2HSU-22HV03/R2

Air Conditioner Edition:2006/1/10

HSU-12HV03/R2

Page 76: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Outdoor unit1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radiusshould be 30 to 40 mm or longer.Connecting the pipe of gas side first makes working easier.The connection pipe is specialized for R410A.The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe hasto be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerantmust be conducted by professional air conditioner engineer. Before adding additional refrigerant,perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then chargeadditional refrigerant.

Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.)

Drawing for the installation of indoor and outdoor units

Insert the cable according to terminal number in the same manner as the indoor unit.

Fix the cable with a clamp.

68

Half union Flare nut

SpannerTorque wrench

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter ( )

Liquid side 6.35mm(1/4")

Gas side 9.52mm(3/8")

Fastening torque

18N.m

40N.m

Gas side 12.7mm(1/2") 55N.m

HSU-12HV03/R2HSU-12HV03/R2

Air Conditioner Edition:2006/1/10

Page 77: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

6.Purging Method:To use vacuum pump

Detach the service port's cap of 3-way valve, the

valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose

(Iow) for gaugemanifold. Then connect the projection

of charge hose (center) for gaugemanifold into

vacuum pump.

3-way valveGas Side

2-way valve

2-way valve

Service port cap

Gaugemanifold(for R410A)

Vacuum pump(for R410A)

Open

Close

Liquid Side

Open the handle at Iow in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (Iow)

reach vacuum condition in a moment, check again.

Vacuumize for over 15min. And check the level gauge

which should read -0.1 MPa (-76 cm Hg) at Iow

pressure side. After the completion of vacuumizing,

close the handle 'Lo' in gaugemanifold and stop the

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

flaring work again, the return to the beginning of .

Open the valve rod for the 2-way valve to an angle of

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make

the inspection of gas leakage.

No gas leakage?

In case of gas leakage, tighten

parts of pipe connection. If

leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise

until hitting lightly.

To prevent the gas leakage, turn the service port's

cap, the valve rod's cap for 2-way valve and 3-way's

a little more than the point where the torque increases

suddenly.

After attaching the each caps, check the gas leakage

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to

discharge all the refrigerant. Vacuumize first, then charge the liquid

refrigerant into air conditioner according to the amount marked on

the name plate.

2.Please do not let other cooling medium, except specified one (R410A),

or air enter into the cooling circulation system. Otherwise, there will be

abnormal high pressure in the system to make it crack and lead to

personal injuries.

If it does not stop gas leakage, dischargewhole refrigerants from the service port.After flaring work again and vacuumize,fill up prescribed refrigerant from the gascylinder.

Anti countercurrent joint

3-way valve

2-way valve

7

6

6

6

1

2

3

1

3

4

5

6

7

8

69

3-way valve2-way valve

3-way valve

2-way valve

HSU-09HV03/R2

HSU-12HV03/R2

HSU-07HV03/R2

HSU-18HV03/R2

HSU-22HV03/R2

Tube(for R410A)

3-way valve

Valve rod cap

Valve rod cap7

7

Open

90O

3-way valve

2-way valve

Air Conditioner Edition:2006/1/10

Page 78: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

1.Cut pipe

3.Insert the flare nut

4.Flare pipe

It becomes highmidway.

The end is immersedin water.

It waves. The gap with the groundis too small

Less than 5cm

There is the bad smellfrom a ditch

2.Remove burs 0~0.5mm 1.0~1.5mm 1.5~2.0mm

Flare tool for R410A

Clutch-type

Conventional flare tool

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

1.Power Source Installation

2.Cutting and Flaring Work of Piping

3.On Drainage

Check for Installation and Test Run

Check Items for Test Run

The power source must be exclusively used for air conditioner. (Over I0A)In the case of installing an air conditioner in a moist place, please install anearth leakage breaker.For installation in other places, use a circuit breaker as far as possible.

Pipe cutting is carried out with a pipe cutter and burs must be removed.After inserting the flare nut, flaring work is carried out.

Please install the drain hose so as to be downward slope without fail.Please don't do the drainage as shown below.

Please pour water in the drain pan of the indoor unit, and confirm that drainage iscarried out surely to outdoor.In case that the attached drain hose is in a room, please apply heat insulationto it without fail.

Please kindly explain to our customers how to operate through the instruction manual.

Gas leak from pipe connecting?Heat insulation of pipe connecting?Are the connecting wirings ofindoor and outdoor firmly insertedto the terminal block?Is the connecting wiring of indoorand outdoor firmly fixed?

Is drainage securely carried out?Is the earth line securelyconnected?Is the indoor unit securely fixed?Is power source voltage abidedby the code?Is there any noise?

Put check mark in boxes

Is the lamp normally lighting?Are cooling and heating (whenin heat pump) performed normally?Is the operation of room temperatureregulator normal?

Flare tooling die

Correct Incorrect

Lean Damage of flare Crack Partial Too outside

70

A

A

Air Conditioner Edition:2006/1/10

Page 79: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2005/1/10

CIRCUIT AND WIRING DIAGRAM

zhanglizhi
71
Page 80: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

72

D

C

B

A

R54

2W/78K

R171 0 k

C12102

C13104

C16102

12345CN3

13 2

XT18M

DOWN STEP

LEFT STEP RIGHT STEP

FAR IN

FAR OUT

PG BACK

R1510k

R 2 4

10K

IC9

TLP521

R184.7k

R41 1K

R 4 2 10K+ 5

C5 102

R 3 0

10K

R 2 8 1K

R27 1 0 K

+5

R29 10K

Q22SC2412

Q12SC2412

FAR

12

CN9

12 ZJ1

123

CN7

+5

FAN BACKC43103

+5VR50 5 1 K

R14 1K

+ 5

IC10

TLP3526

123

CON12 C392UF 450V +12V

R57680

FAN

R83

1W-120O

PG OUT

345

678 1

2

IC2

24C01A

+5

E 6 4.7UF/50V

E 7 4.7UF/50V

1234

CN8

R44 1K

R45 1K

R35 3.3K 1%

R34 20K 1%

+ 5

PG OUT

ROOMPIPE

ZJ/SHORT

C2 104

R46

1KC151 0 2

C10102 C9

102

Q4

2SC2412

SDASCL

1 2 3 4 5 6 7 89

10

11

12

13

14

15

16

IC42003

1 2 3 4 5 6 7 89

10

11

12

13

14

15

16

IC52003

1 2 3 4 5 6 7 89

10

11

12

13

14

15

16

IC32003

BADCBA

C

CD

B

A

CD

BA

UP STEP

+12

+12

+12

+ 1 2

C4104

+5

C6

103/

50V

+5

E5100u/16v

C18104/50V

+ 5

WHITE

R22 22K

C37104

R40 4.7K

R654.7k

C17103/50v

STF

FLZ

RL3G5N-1A

RL1G4A-1A-P

+12

COMP

1

CON21220VL

RL4

G5N-1A

RL5

JAQ-1 12VWFJ

STF

D10

RLS4148

1

CON20COMP

COMP

FLZ

WFJ

R20 22KR19 4.7K

+5

R43 1K

R39

1 K

R38

3 9 0

C8102

E3

470U/16V

CT1

VR1

D5

IN4148

+5

BD2W04

R10 10K

BUZZ

1234

CN6

R 3 6 1K

R 3 7 10K +5V

R8 10K

+5VR7 10K

C14104

BUZ1

BEEP-PKM13EPY-4002

Q52SC2412

R11

10KR49100

R9 4.7K

R11M

+5V

REC

R64

1 0 K

R56

1K

Q8 2SB1182

+12V

HXF

R31

10K

+12V

C41102

D2 RLS4148

R2 10K

R3 1K

C11 0 2

YJKG

+5V

Q32SC2412

R23 4.7K

12345 CN4

02 IRQ

07

08 PTF4/TBCH0

PTF3/TBCH3

48

49

PTH1/KBD3

PTH1/KBD4

03 RST

21 VSS GND

GNDAVSS/VRE45

60 PTC0

PTF710

13 PTE0/TXD NET OUT

56 VSSA GND

14 PTE1/RXD NET IN

PTE2/TACH01525

PTG2/KBD2 STFPTE3/TACH116

17 PTE4/SS COMP OUT181920

PTE5/MISOPTE6/MOSIPTE7/SPSCK

HXF/JYFLZW F J

PTC401

1 2 3 4 5 6 7 8 9 10CN2

26 PA0 UP A27

PA1 UP B28 PA2 UP C29 PA3 UP D30 PA4 DOWN A 31 PA5 DOWN B32 PA6 DOWN C33 PA7 DOWN D38 PTB4 LEFT D

(COOL/HEAT)

(LARGE/ SMALL)

12

CN10

DOOR

R33 10K

R32 1 K

+5v

C21102

50 PTD4 DOOR

34PTB0/ATD0CT

35PTB1/ATD1ZJ/SHORT

394041424346

PTB5/ATD5PTD6/ATD6PTB7/ATD7PTD0PTD1PTD2

LEFT CLEFT BLEFT ARIGHT DRIGHT CRIGHT B

47PTD3RIGHT A

VDDAREF 44

0605PTF1/TACH3

PTF2/TBCH2EE DATAEE SCL

57CGMXFC

5455

VDDAVREFH

59

58

OSC1

OSC2

51PTD5HEALTHRUN PTD6/TACLK 52

53626364

PTD7PTC2/MCLKPTC3PTC5

PTF0/TACH2 04REC

REDBLUEGREENPOW

22

3637PTB3/ATD3

PTB2/ATD2

VDD

PIPEROOM

09 NC

61

23

24

PTC1

PTG1/KBD1PTG0/KBD0

CON18 CON19、 220N1

23

CON13

1

CON14(RED)

FLZ

JZKZ

C11104

C19104

C20104

HXF

RL2

OEG-SS-112DM

DJR

1

CON16(BLUE)DJR

MC68HC908AB32

+12v

R 1 2 1 K R 1 3

1K

Q7S9013

Q6S90131

23

CN12

+12v

R2522K

R 2 64.7K

5v

1 11 2 PTF5

PTF6Ultraviolet_AUltraviolet_C

Ultraviolet_Control

E11UF/16V

R4822K

C7

104/

50V

C3103

C42104/50V

C29104/50v

R53 1 K

SW1

220V

-L22

0V-N

D

R594.7K

1

CON15

FLZ

220V-N

220V-L

STF

WFJ

A12V

C

R 6 6 27

C44103/50V

C45103/50V

C23103/50VC24103/50VC25102/50VC26102/50VC27102/50V

C22102/50V

C47103/50V

E13100u/16v

R69 100R68 100R67 100R70 330R71 330R72 330

6 4

6 3

6 2

5 3

5 2

5 1

E12100u/25v

1CON21

220VL

FUSE1

T3.15A

C40104/275V

LX1

ZE1S14K350

1

2

3

4

C48104/50V

IC8 Q817C

L1 20UH12VIC7

7805+5

T1TRAN1-3

C33 222/300VAC

E4220U/16V

E101000U/25V

E922U/25V

D6UF4007

D8 UF302

R601.3 2WΩ

R614.7K

R55560

D111N4007

C 2 8104

R52 3 .6Ω/ 3WR51

47K/2W

R58 27C30102

C31472/1KV

C 3 5104

D710V/0.5V

E822U/450V

220V-L

220V-N

E11470U/25V

C36104

IC13STD2NBP60

AD

J1

FB2

CS

3

GN

D4

DR

V5

Vcc

6N

C7

HV

8

IC6 NCP1200P60

R7515

R6239K

D9

D13 D14

D12

SC

D

R7610K

E14100U/16V

C34104

12345678910

TO DISPCON5-1

R85 330

C38102/50V

6 1

TIM

B3P5-VH-3/MOL-35979-0314

( BLUE)

R161 0 k

+ 5

D15

RLS

4148

Q9

2SC2412

DJR

R21 4.7K

SW2

R734.7K

R84

4.7K

D1615V/1W

L2 125UH

C50

0.01uF/275V

Air Conditioner Edition:2006/1/10

zhanglizhi
CIRCUIT DIAGRAM FOR INDOOR UNIT
zhanglizhi
HSU-07/09/12HV03/R2
zhanglizhi
Page 81: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

UV Light

Heater

7

CT

FUSE

8

Fan Motor

LCD Board

B BLACK

W WHITE

Y/G YELLOW/GREEN

BR BROWN

BL BLUE

R RED

POWER SUPPLY

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR INDOOR UNIT
zhanglizhi
HSU-07HV03/R2
zhanglizhi
73
Page 82: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR OUTDOOR UNIT
zhanglizhi
HSU-07HV03/R2
zhanglizhi
74
Page 83: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

UV Light

Heater

7

CT

FUSE

8

Fan Motor

LCD Board

B BLACK

W WHITE

Y/G YELLOW/GREEN

BR BROWN

BL BLUE

R RED

POWER SUPPLY

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR INDOOR UNIT
zhanglizhi
HSU-09HV03/R2
zhanglizhi
75
Page 84: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR OUTDOOR UNIT
zhanglizhi
HSU-09HV03/R2
zhanglizhi
76
Page 85: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

UV Light

Heater

7

CT

FUSE

8

Fan Motor

LCD Board

B BLACK

W WHITE

Y/G YELLOW/GREEN

BR BROWN

BL BLUE

R RED

POWER SUPPLY

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR INDOOR UNIT
zhanglizhi
HSU-12HV03/R2
zhanglizhi
77
Page 86: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Air Conditioner Edition:2006/1/10

zhanglizhi
WIRING DIAGRAM FOR OUTDOOR UNIT
zhanglizhi
HSU-12HV03/R2
zhanglizhi
78
Page 87: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

CIRCUIT DIAGRAM HSU-18HV03/R2

R17

10k

C12 102

C13104

C16102

12345CN3

13 2

XT18M

down louver motor

left louver motor right louver motor

centralize control IN

centralize control OUT

PG-FB

R4710k

R24

10K

R183k

R41 1K

R42 10K+5

C5 102

R30

10K

R28 1K

R27 10K

+5

R29 10K

Q22SC2412

Q12SC2412

centralize control

12 ZJ1

123

CN7

+5

PG-FB

C43103

+5VR50 51K

R14 1K

+5

IC10

TLP3526

123

CON12 C392UF 450V +12V

R57680

FAN

RC1

0.01U*120/300V

PG-OUT

345

678 1

2

IC2

24C01A

+5

E6 4.7UF/50V

E7 4.7UF/50V

1234

CN8

R44 1K

R45 1K

R35 3.3K 1%

R34 20K 1%

+5

PG-OUT

room temp.pipe temp.

short time/self test

C2 104

R46

1KC15102

C10102

C9102

Q4

2SC2412

SDASCL

1 2 3 4 5 6 7 8910111213141516

IC42003

1 2 3 4 5 6 7 8910111213141516

IC52003

1 2 3 4 5 6 7 8910111213141516

IC32003

BADCBA

C

CD

B

A

CD

BA

up louver motor

+12

+12

+12

+12

C4104

+5

C6104/50V

+5

E5100u/16v

C18104/50V

+5

(W)

R22 22K

R21 4.7K

R40 10K

C17

103/50v

4-way valve

anion

RL3G5N-1A

RL1

G4A-1A-P

+12

compressor

1

CON21220VL

RL4

G5N-1A

RL5

JAQ-1 12Vout fan

4-way valve

D10RLS4148

1

CON20compressor

compressor

ANION

OUT FAN

3-min delay

R20 22KR19 4.7K

+5

R43 1K

R39

1K

R38

390

C8102

E3

470U/16V

CT1

VR1

D5

IN4148

+5

BD2

W04

R10 10K

buzzer

buzzer 2

1234

CN6

network (R)

R36 1K

R37 10K +5V

R8 10K

+5VR7 10K

C14104

BUZ1

Q52SC2412

R11

10K

R49100

R9 4.7K

R11M

123456789

CN5-1,

+5V

remote REC

R31

10K

+12V

C41102

D2 RLS4148

R2 10K

R3 1K

C1102

manual switch

+5V

Q32SC2412

R23 4.7K

12345 CN4

02

07

08

cross zero

48

49

03 reset

21 VSS GND

GNDAVSS/VRE45

60

10

13 network OUT

56 VSSA GND

14 network IN

15

25 ST OUT

1617 compressor181920

fresh air anionoutdoor fan

01

1 2 3 4 5 6 7 8 9 10CN2

26 up A

27 up B

28 up C29 up D

30 down A31 down B32 down C33 down D38 left D

function select

model select

12

CN10

door switch

R33 10K

R32 1K

+5v

C21102

50 door switch

34curient test

35short time/self test

394041424346

left Cleft Bleft Aleft D

right Cright B

47right A

44

0605EE date

EE clock

57CGMXFC

5455

VDDAVREFH

59

58CX2

CX1

51LCSWRL 52

5362636404remote REC

red lampblue lamp

green lampDAL

22

3637

VDD

pipe temp.room temp.

09 none

61 none

61

23

24

none

none

none

220N 1

2

3

CON13

1

CON14(R)

FLZ

C11

104

C19104

C20104

O2 MC68HC908AB32

+12v

R2522K

R264.7K

5v

1112

UV light class AUV light class C

E11UF/16V

R4822KR734.7K

display select 1

display select 2

C7103/50V

C3103

C29104/50v

R53 1K

SW1

manual switch

220V

-L

220V

-N

D

R594.7K

1

CON15(W)

FLZ

220V-N

220V-L

STF

WFJ

R66 27

C46101/50V

C32

101/50V

C23103/50VC24103/50VC25102/50VC26102/50VC27102/50V

C22103/50V

C47103/50V

E13100u/16v

R69 100R68 100R67 100R70 330R71 330R72 330

64

63

62

53

52

51

E12100u/25v

1

CON21

220VL

FUSE1

T3.15A

C40104/275V

LB2271electrical source

ZE1S14K350

1

2

3

4

12V IC7

7805

+5

T1TRAN1-3

E4

220U/16V

E101000U/35V

C28104

C35104

220V-L

220V-N

D11

D13 D14

D12

E14

100U/25VC36104

D94007

E11470U/25V

C34104

+5V

L1

AO42-20uH

SW2

Q4

2SC2412

R15

10k

Air Conditioner Edition:2006/1/10

zhanglizhi
79
Page 88: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

WIRING DIAGRAM FOR INDOOR UNIT HSU-18HV03/R2

CN4

CN2

SW1 CN8

LCD Board

1

6

CN7

R

BL

POWER SUPPLY

BR

TO THE OUTDOOR UNIT

Y/G

W3RB

Y/G

4BR

C0N14

R

W

BW

C0N20

BR

4

CON13

C0N15

CON21

250VAC

FUSE1T3.15A

CON12

8Y/GFan Motor

W WHITE

Y/G YELLOW/GREEN

R RED

BL BLUE

BR BROWN

B BLACK

2

CN9

CN5-1

CN3

Air Conditioner Edition:2006/1/10

zhanglizhi
80
Page 89: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

WIRING DIAGRAM FOR OUTDOOR UNIT HSU-18HV03/R2

Air Conditioner Edition:2006/1/10

zhanglizhi
81
Page 90: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

CIRCUIT DIAGRAM HSU-22HV03/R2

R17

10k

C12 102

C13104

C16102

12345CN3

13 2

XT18M

down louver motor

left louver motor right louver motor

centralize control IN

centralize control OUT

PG-FB

R4710k

R24

10K

R183k

R41 1K

R42 10K+5

C5 102

R30

10K

R28 1K

R27 10K

+5

R29 10K

Q22SC2412

Q12SC2412

centralize control

12 ZJ1

123

CN7

+5

PG-FB

C43103

+5VR50 51K

R14 1K

+5

IC10

TLP3526

123

CON12 C392UF 450V +12V

R57680

FAN

RC1

0.01U*120/300V

PG-OUT

345

678 1

2

IC2

24C01A

+5

E6 4.7UF/50V

E7 4.7UF/50V

1234

CN8

R44 1K

R45 1K

R35 3.3K 1%

R34 20K 1%

+5

PG-OUT

room temp.pipe temp.

short time/self test

C2 104

R46

1KC15102

C10102

C9102

Q4

2SC2412

SDASCL

1 2 3 4 5 6 7 8910111213141516

IC42003

1 2 3 4 5 6 7 8910111213141516

IC52003

1 2 3 4 5 6 7 8910111213141516

IC32003

BADCBA

C

CD

B

A

CD

BA

up louver motor

+12

+12

+12

+12

C4104

+5

C6104/50V

+5

E5100u/16v

C18104/50V

+5

(W)

R22 22K

R21 4.7K

R40 10K

C17

103/50v

4-way valve

anion

RL3G5N-1A

RL1

G4A-1A-P

+12

compressor

1

CON21220VL

RL4

G5N-1A

RL5

JAQ-1 12Vout fan

4-way valve

D10RLS4148

1

CON20compressor

compressor

ANION

OUT FAN

3-min delay

R20 22KR19 4.7K

+5

R43 1K

R39

1K

R38

390

C8102

E3

470U/16V

CT1

VR1

D5

IN4148

+5

BD2

W04

R10 10K

buzzer

buzzer 2

1234

CN6

network (R)

R36 1K

R37 10K +5V

R8 10K

+5VR7 10K

C14104

BUZ1

Q52SC2412

R11

10K

R49100

R9 4.7K

R11M

123456789

CN5-1,

+5V

remote REC

R31

10K

+12V

C41102

D2 RLS4148

R2 10K

R3 1K

C1102

manual switch

+5V

Q32SC2412

R23 4.7K

12345 CN4

02

07

08

cross zero

48

49

03 reset

21 VSS GND

GNDAVSS/VRE45

60

10

13 network OUT

56 VSSA GND

14 network IN

15

25 ST OUT

1617 compressor181920

fresh air anionoutdoor fan

01

1 2 3 4 5 6 7 8 9 10CN2

26 up A

27 up B

28 up C29 up D

30 down A31 down B32 down C33 down D38 left D

function select

model select

12

CN10

door switch

R33 10K

R32 1K

+5v

C21102

50 door switch

34curient test

35short time/self test

394041424346

left Cleft Bleft Aleft D

right Cright B

47right A

44

0605EE date

EE clock

57CGMXFC

5455

VDDAVREFH

59

58CX2

CX1

51LCSWRL 52

5362636404remote REC

red lampblue lamp

green lampDAL

22

3637

VDD

pipe temp.room temp.

09 none

61 none

61

23

24

none

none

none

220N 1

2

3

CON13

1

CON14(R)

FLZ

C11

104

C19104

C20104

O2 MC68HC908AB32

+12v

R2522K

R264.7K

5v

1112

UV light class AUV light class C

E11UF/16V

R4822KR734.7K

display select 1

display select 2

C7103/50V

C3103

C29104/50v

R53 1K

SW1

manual switch

220V

-L

220V

-N

D

R594.7K

1

CON15(W)

FLZ

220V-N

220V-L

STF

WFJ

R66 27

C46101/50V

C32

101/50V

C23103/50VC24103/50VC25102/50VC26102/50VC27102/50V

C22103/50V

C47103/50V

E13100u/16v

R69 100R68 100R67 100R70 330R71 330R72 330

64

63

62

53

52

51

E12100u/25v

1

CON21

220VL

FUSE1

T3.15A

C40104/275V

LB2271electrical source

ZE1S14K350

1

2

3

4

12V IC7

7805

+5

T1TRAN1-3

E4

220U/16V

E101000U/35V

C28104

C35104

220V-L

220V-N

D11

D13 D14

D12

E14

100U/25VC36104

D94007

E11470U/25V

C34104

+5V

L1

AO42-20uH

SW2

Q4

2SC2412

R15

10k

Air Conditioner Edition:2006/1/10

zhanglizhi
82
Page 91: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

WIRING DIAGRAM FOR INDOOR UNIT HSU-22HV03/R2

TERMINAL BLOCK

CN7

Y/G

TO THE OUTDOOR UNIT

W B R

3 4

BL

5

BR

(C0N25)

C0N14

C0N20 5

CON13CON21

C0N15

250VAC

FUSE1T3.15A

CON12

1Y/GFan Motor

W WHITE

Y/G YELLOW/GREEN

B BLACK

R RED

BL BLUE

BR BROWN

3

CN5-1

SW1(CN11)

CN3 CN4

CN2

CN8

DISPLAYRECEIVER

4

Central control

CN9

2

Air Conditioner Edition:2006/1/10

zhanglizhi
83
Page 92: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

WIRING DIAGRAM FOR OUTDOOR UNIT HSU-22HV03/R2

WIRING DIAGRAM OF OUTDOOR UNIT

Air Conditioner Edition:2006/1/10

zhanglizhi
84
Page 93: SERVICE MANUAL - klimatik-bgklimatik-bg.com/images/HSU-7-9-12-14-18-22.pdfSERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING

Sincere Forever

Haier Group Haier Industrial Park, No.1, Haier Road

266101, Qingdao, China

http://www.haier.com