Page 1: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD203 Remote Terminal Unit

Power Automation

CatalogSICAM 2.3.1 ⋅ 2001

Page 2: SICAM MicroRTU 6MD203 Remote Terminal Unit
Page 3: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD2030 Remote Terminal Unit

SICAM microRTU

Description 2

Scope of performance 3

Parameters 4 to 6

7

Technical data 7 and 8

9

10 and 11

Supersedes CatalogSICAM 2.3.1 ⋅ 1999

Siemens AG 2001

Siemens SICAM 2.3.1 ⋅ 2001 1

The SICAM microRTU belongsto the family of SICAM devicesnotable for their combination ofprogrammable controller andtelecontrol unit.

The SICAM microRTU is atelecontrol unit based onSIMATIC S7-200 and can be usedoptimally for small volumes of in-formation.Up to 64 data points can be proc-essed with the SICAMmicroRTU.

The SICAM microRTU can beused for general telecontrol tasksin public and industrial powersupply systems such as forconditioning and transmission ofindications, measured values,metered values and furthermorefor the output of pulse andpersistent commands.

Make use of the advantages

offered by the

SICAM microRTU:

�Attractively priced

�Useable for the automation ofgas and hydro-electric stationsas well as for the monitoringand control of electrical energysupply systems

�Minimum space requirementsby virtue of compact design

�Simplified installation thanksto the snap-on design ontostandard mounting rail andconnections with screw-typecontacts

�Speedy commissioning bypractical pre-assigned parame-ters

�Maintenance-free, no calibra-tion or adjustment required

�Stocking of spare parts is keptto a minimum as the same unitcan be used for gas/water andenergy areas

�Self-configuring to as large anextent as possible by the auto-matic updating of the hardwareconfiguration

�Easily adaptable to control cen-ters due to the internationallystandardized IEC 60870-5-101telecontrol protocol.

Fig. 1SICAM microRTUwith expansionmodule

Page

Selection andordering data

AccessoriesHandling

11

12

13

Conditions of saleand delivery

Spare parts

Catalog index

Accessories

SIP

052f

.tif

Page 4: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD2030 Remote Terminal Unit

� The system basis of theSICAM microRTU is theSIMATIC S7-200.The S7-224 and S7-226SIMATIC CPUs can beused for the SICAMmicroRTU.The table below containsthe most important data.

2 Siemens SICAM 2.3.1 ⋅ 2001

� S7-200-CPUs

Features S7-224 S7-226

Dimensions (w x h x d) 120.5 x 80 x 62 mm 196 x 80 x 62 mm

Power supply, integrated 24 V DC or 24 V DC or110 / 230 V AC 110 / 230 V AC

MemoryProgram (EEPROM) 8 K words 8 K wordsUser data 5 K words 5 K words

Inputs and outputs (I/O)Inputs 14 DI: 24 V DC 24 DI: 24 V DCOutputs 10 DO: 24 V DC, relays 16 DO: 24 V DC, relays

CommunicationNumber of interfaces 1 (RS485) 2 (RS485)Supported protocols:Interface 0 (Port 0) IEC 60870-5-101 IEC 60870-5-101

unbalanced mode unbalanced modeInterface 1 (Port 1) – PPI

To control center

Remoteterminal unitas “node”

ModemOperator station

Modem ModemCPU CPU

2-wire circuit

Fig. 3 Configuration with SICAM microRTU

SIP

051f

.tif

Fig. 2SICAM microRTUwith mounting railmodem

Description

Page 5: SICAM MicroRTU 6MD203 Remote Terminal Unit

Siemens SICAM 2.3.1 ⋅ 2001 3

Scope of performance

� Scope of performance 1

� The SICAM microRTU sup-ports the input/output func-tions listed in the tableopposite:

� Scope of performance 2

The processing functions

� Indications

− Input filter

The first 16 digital inputs canbe filtered: Range 0.2 ms to12.8 ms adjustable withSTEP 7 Micro / Win.

− Acquisition

The first 16 inputs are ac-quired in the 10 ms scan andstored in the messagebuffer in the correct sort or-der.

− Transmission

The transmission is imple-mented spontaneously or ondemand, using theTK1 / TK3 message type.

� Metered values

− Acquisition

Up to 4 metered values for amaximum metering fre-quency of 20 Hz.

− Restoring

The metered values can berelocated and transmittedvia an internal timer orTK101 metered-value inter-rogation command. It can beparameterized whether ornot the metered valueshould be deleted afterrestoring.

− Metered value

A 31 bit metered valuebuffer is available for eachmetered value.

� Measured values

− Monitoring of the analogmodules

Cyclic and/or on-demandtransmission using the TK9message type. Module dis-turbances affect the NT (nottopical) status of the mea-sured values messages.

� Commands

− Outputs

Impulse (1 out of n-monitor-ing) or continuous output.Command messages of thetype TK45 / TK46 are ex-pected for this purpose. De-pending on the qualifiers 0,1 and 2, it is possible toparameterize three com-mand output times. Continu-ous commands are possiblewith qualifier 3 (only TK 45).

� Maximum expansion

Optionally, a total of up to 32digital inputs and 32 digitaloutputs can be processedby application of expansionmodules.

� Scope of performance 3

The SICAM microRTU is ca-pable of implementing theIEC 60870-5-101 telecontrolprotocol in unbalancedmode.

The SICAM microRTUsupports the following func-tions:

� Process information inthe monitoring direction

− TK1: single-point indicationwithout time, quality identi-fications not supported

− TK 3: Double-point indica-tion without time, qualityidentifications not sup-ported

− TK 9: Measured value, nor-malized value without time,quality identifications: “nottopical for module distur-bances”.

− TK 15: Metered value with-out time, quality identifica-tion: CA-”counter adjus-ted”. After restoring, themetered value is deletedand then the CA bit will beset.

� Process information inthe control direction

− TK 45: single command

− TK 46: double command

� System information inmonitoring direction

− TK 70: initialization end

� System information incontrol direction

− TK 100: general interroga-tion command

− TK 101: metered value in-terrogation command

− TK 103: time synchroniza-tion.

� Scope of performance 4

� Operating mode control

This comprises:− A high-priority message

buffer list for organizationalinformation (start indica-tion, acknowledgements)

− A message buffer list forprocess information (bufferdepth >200 changes of in-dications)

− Interrogation list group 0(general interrogation) forindications and parame-terizable for metered andmeasured values

− Interrogation list group 1for measured values

− Metered value interroga-tion listEach of the interrogationlists is acknowledged follow-ing activation; the content istransferred via the messagebuffer, and finally an ac-knowledgement message issent.

� Parameters

� They are stored in the DB1data block and loaded intothe SIMATIC CPU by thePC in such a fashion thatno power failure can occur.

Function S7-224 S7-226 Transmissionacc. to IEC 60870-5-101

Integrated digital inputsSingle point indicationsDouble-point indicationsMetered values

14max. 14max. 7max. 4

24max. 24max 12max. 4

TK 1TK 3TK 15

Integrated digital outputsSingle commandsDouble commands

10max. 10max. 5

16max. 16max. 8

TK 45TK 46

Expansion modulesDigital inputsSingle point indicationsDouble-point indications

max. 16max. 16max. 8

max. 8max. 8max. 4

TK 1TK 3

Digital outputsSingle commandsDouble commands

max. 16max. 16max. 8

max. 16max. 16max. 8

TK 45TK 46

Analog inputsMeasured values, normalized

max. 16max. 16

max. 16max. 16 TK 9

Page 6: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD203 Remote Terminal Unit

Parameters

� Parameter structure V2

// *** Parameters for SICAM microRTU version 2 and higher ***//// ****************************************************//// VB1O-VB17-> License number// Input of license number (8 signs) in ASCI format:

e.g. ‘12345678’// Please take your license number from your product card//// ****************************************************//// VB20 Baud rate// 2 9600 Bd// 3 4800 Bd// 4 2400 Bd// 5 1200 Bd// 6 600 Bd// 7 300 Bd//// ****************************************************//// VB21------> Message receive diagnosis and transmission output (RTS output)// Bit 0 1: Q1.0 to be activated as RTS output, Q1.1 to be activated as receipt control// 0: Q1.0 and Q1.1 not to be activated during message traffic usable as command output//// ****************************************************//// VB22------> RTS lead time// 1-255 (*1Oms) corresponding to 10-2550 ms//// ****************************************************//// VB23------> RTS overtravel time// 0-255 (*1Oms) without or corresponding to 10-2550 ms//// ****************************************************//// VB3O------> Length of link address// permissible values are: 1,2 (octets)//// ****************************************************//// VW32------> Link address// depending on the length of the link address (VB3O)// L=1 octet: 1-254 (1-FEh)// L=2 octets: 1-65534 (1-FFFEh)//// ****************************************************//// VB34------> Length of ASDU address (Application Service Data Unit)// permissible values are: 1,2 (octets)//// ****************************************************//// VW36------> ASDU address// depending on the length of the ASDU address (VB34)// L=1 octet: 1-254 (1-FEh)// L=2 octets: 1-65534 (1-FFFEh)//// ****************************************************//// VB38------> Length of information object address// permissible values are: 1,2,3 (octets)//// ****************************************************//// VD40------> Basic address of process indications (SPI + DPI)// depending on the length of the information object address (VB38)// L=1 octet: 1-224// L=2 octets: 1-65504// L=3 octets: 1-16777184//// ****************************************************

4 Siemens SICAM 2.3.1 ⋅ 2001

Page 7: SICAM MicroRTU 6MD203 Remote Terminal Unit

� Parameter structure V2 (continued)

//// VD44------> Basic address for internal indications// Message buffer, buffer overflow -> indication is spontaneous, not listed in interrogation lists// depending on the length of the information object address (VB38)// L=1 octet 1-224// L=2 octets: 1-65504// L=3 octets: 1-16777184////****************************************************//// VD48------> Basic address metered values// depending on the length of the information object address (VB38)// L=1 octet: 1-252// L=2 octets: 1-65532// L=3 octets: 1-16777212//// ***************************************************//// VD52------> Basic address measured values// depending on the length of the information object address (VB38)// L=1 octet: 1-240// L=2 octets: 1-65520// L=3 octets: 1-16777200//// ***************************************************//// VD56------> Basic address commands (single command + double command)// depending on the length of the information object address (VB42)// L=1 octet: 1-224// L=2 octets: 1-65504// L=3 octets: 1-16777184//// ***************************************************//// VB60-VB63-> Activated single point indications// VB63: E0.0 - E0.7// VB62: E1.0 - E1.7// VB61: E2.0 - E2.7// VB60: E3.0 - E3.7//// ***************************************************//// VB64------> SPI list parameter

// Reserved, must have 0 assigned to it//// ***************************************************//// VB66-VB69-> Activated double point indications// VB69: E0.0 - E0.7// VB68: E1.0 - E1.7// VB67: E2.0 - E2.7// VB66: E3.0 - E3.7//// ***************************************************//// VW70------> Fault position suppression DPI in 100 ms intervals// 0 without// 1-32767 0.1 - 3276.7 sec// Accuracy +/-100 ms//// ***************************************************//// VB72------> DPI list parameter

// Reserved, must have 0 assigned to it.//// ***************************************************//// VB74------> Quantity of metered values// 0 No metered values// 1-4 Quantity of metered values (input 0.0-0.3)//// ***************************************************

Siemens SICAM 2.3.1 ⋅ 2001 5

Page 8: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD203 Remote Terminal Unit

Parameters

� Parameter structure V2 (continued)

// VB75------> Internal restoring interval for metered values// 0 No restoring// Restoring interval in minutes: the following values are permitted:// 1,2,3,4,5,6,10,12,15,20,30,60 min

//// ***************************************************//// VB76------> Metered value list parameters// Bit 0 -> Metered value transmitted spontaneously after restoring// Bit 1 -> Metered value in interrogation group 0 (general interrogation)//// Bit 4 -> After restoring metered value is reset via internal timer//// ***************************************************//// VB78-VB79-> Measured values released for transmission// VB78 MW 8-15// VB79 MW 0-7//// ***************************************************//// VB80------> Cyclic measured value transmission (time-controlled)// 0 No cyclical measured value transmission// 1-255 Trigger in sec//// ***************************************************//// VB81------> Measured value list parameter

// Bit 0 -> Measured value in interrogation group 0 (general interrogation)// Bit 1 -> Measured value in interrogation group 1//// ***************************************************//// VB82------> Allocation of time code to the command output time for qualifier 0// 0 not permissible// 1-255 100 ms-25.5 sec//// ***************************************************//// VB83------> Allocation of time code to the command output time for qualifier 1// 0 not permissible// 1-255 100 ms-25.5 sec//// ***************************************************//// VB84------> Allocation of time code to the command output time for qualifier 2// 0 not permissible// 1-255 100 ms-25.5 sec//// ***************************************************//// VW86------> Monitoring of time synchronization (in minutes)// Free// 0 without// 1-255 1 - 255 min with accuracy x + 1min//// ***************************************************//// VB88------> Time stamp in indication messages// Free//// *****************************************************

6 Siemens SICAM 2.3.1 ⋅ 2001

Page 9: SICAM MicroRTU 6MD203 Remote Terminal Unit

� Modem

� A V.23 modem is availablefor the SICAM microRTU inaccordance with the de-sign and the price of theunit. Possible modems aree.g. Induline IL2K4 or MD2.In the control center, it isalso possible, for example,to use an MD 100 modem.

� The electrical level of thecommunications interfaceon the S7-224/226 CPU isRS485. The Induline IL2K4and MD2 modem already in-corporates the RS485 inter-face.

� Diagnosis,trouble-shooting

� LED displaysIn addition to the LEDs onthe CPU and the expansionmodules (see SIMATICmanual), two digital outputsare used as follows:

− RTS, message transmis-sion LEDThe output Q1.0 has amessage transmissioncontrol function.

− EK, message receive LEDThe output Q1.1 has amessage receive controlfunction. When the func-tion is being applied, 2command outputs can notbe parameterized.This function should onlybe used with electronicoutputs.

� Buffer overflowReaction of overflow of theinternal buffers for the indi-cation acquisition.

− Reset of the SICAMmicroRTU

− TK1 error message tocontrol centerNote: metered valueprocessing remains unaf-fected

� Module disturbancesAnalog input:

− Failure of external auxiliarysupply

− Module fails (configurationerror)Response:

− “NT bit” is set (not topical),measured value remainsunchanged

� Commissioning (Fig. 4)

� AuxiliariesTogether with the requiredhardware such as S7-200components and modem,the following items are re-quired for the commission-ing of SICAM microRTU.

− Runtime software on dis-kette

− STEP 7-Micro/WIN as ofversion V2.1

− PC/PPI cable− PC or PG.

� Runtime softwareIt is possible to obtain an in-dividual license for this soft-ware. The software mayonly be loaded once onto aCPU. Each diskette is allo-cated its own registrationnumber which can be readfrom the CPU. In the eventof a malfunction, this num-ber is used to identify thesoftware.

� ParameterizingThe parameters in the DB1data block can be changedusing STEP 7-Micro/WIN.The parameters, their pur-pose and the default set-tings are contained in theSICAM microRTU manual.

� Supply configurations

The SICAM microRTU canbe supplied in the followingversions:

� SICAM microRTUproductThe SICAM microRTU issupplied in individual parts,for example consisting ofCPU, expansion modules,modem and a diskette con-taining the runtime software(SICAM RTC for microRTU).

� SICAM microRTUsystemThe SICAM microRTU issupplied as a completedevice, consisting ofa housing with the CPU,a modem, terminals and adiskette containing theruntime software (SICAMRTC for microRTU).Optionally: expansionmodule and buffer unit,installation and testing.

Siemens SICAM 2.3.1 ⋅ 2001 7

AccessoriesHandling

Fig. 4 Communicationwith SICAM microRTU

Personal Computer

RS232

PC/PPI-cable

S7-200-CPU

STEP 7-Micro/WIN

RS485

� General technical data

National and international directivesThe directives shown below were used for the definition ofthe relevant performance characteristics and technicaldata, as well as for the testing of the S7-200 productseries.− Underwriters Laboratories, Inc.: UL508 registered

(Industrial Control Equipment)− Canadian Standards Association: CSA C22.2

Number 142, tested (Process Control Equipment)− Factory Mutual Research: FM class 1, category 2,

dangerous goods groups A, B, C and D, T4A− VDE 0160: electronic devices for use in substations and

power plants− EC directive on low voltages− EN 61131-2: automation systems - requirements of the

devices

� CE Conformity

This product is in conformity with the directives of theCouncil of the European Communities on the approximati-on of the laws of the Member States relating to electro-magnetic compatibility (EMC Council directive 89/336/EEC)and concerning electrical equipment for use within speci-fied voltage limits (low-voltage directive 72/23/EEC).The product conforms to the international standardIEC 60 255 and the national standard DIN 57 435/Part 303.The device is designed for use in an industrial environmentaccording to the EMC standard specification.Conformity is proved by tests performed by Siemens AG inline with article 10 of the Council Directives in accordancewith the generic standards EN 50081 and EN 50082 forEMC directive and EN 60 255-6 for the low-voltage directi-ve.

Technical data

Page 10: SICAM MicroRTU 6MD203 Remote Terminal Unit

� SICAM microRTU

Power supplyRated voltage 24 V DC– Voltage range 20.4 to 28.8 V DC– Input current typically 85 mA, only CPU, maximum load current 900 mA– Electrically isolated noRated voltage 110/230 V AC– Voltage/frequency range 85 to 264 V AC / 47 to 63 Hz– Input power typically 4.5 VA, only CPU, max. power 50 VA– Electrically isolated yes, transformer, 1500 V AC, 1 min

InputsVoltage range for CLOSED 15 to 30 V DC, 35 V DC, voltage surge 500 msRated voltage for CLOSED 24 V DCRated current 7 mAElectrical isolation 500 V AC, 1 min

Electronic outputsVoltage range 20.4 to 28.8 V DCMaximum load current at 0 to 40 °C at 55 °C– For each individual output 0.75 A 0.5 A– For two adjacent outputs 1 A 0.75 A– Outputs overall 4 A 3 ASurge current 4 A, 100 msElectrical isolation 500 V AC, 1 minShort-circuit protection no

Relay outputsVoltage range 5 to 30 V DC / 250 V ACMax. load current 2 A / output, 8 A / conductorOvervoltage surge 7 A when contacts are closedService life 10 000 000 switching cycles without load

100 000 switching cycles under loadElectrical isolation– Coil to contact 1500 V AC, 1 min– Contact to contact 750 V AC, 1 min

Degree of protection IP20

Ambient temperatureDuring continuous operation 0 to 55 °C, max. 95 % humidity without condensationDuring transport/storage – 40 to + 70 °C

� Expansion module for measured values

InputsMaximum input voltage 30 V DCMaximum input current 32 mAResolution 12 bit A/D conversionElectrical isolation no

Power input 2 W

Inputs and outputs 4 analog inputs with common potential

Dimensions (w x h x d) 46 x 80 x 62 mm

Weight Approx. 100 g

Configuration switchInput ranges 0 to 5 V, 0 to 10 V, 0 to 20 mA

Technical data

8 Siemens SICAM 2.3.1 ⋅ 2001

SICAM microRTU6MD203 Remote Terminal Unit

Page 11: SICAM MicroRTU 6MD203 Remote Terminal Unit

� Order no.

SICAM microRTU Remote terminal unit including runtime software 6 MD 2 0 3 � - 0 ��0 � - 2 A A 0

Supply configuration

Product, supplied in individual parts 0System, supplied in individual parts, additionally with housing and built-in components 1

S7-224 processor: 14 indications, 10 commandsS7-226 processor: 24 indications, 14 commands

6ES7 214-1AD21-0XB0, 24 V DC, 24 V DC inputs1), 24 V DC outputs, electronic B6ES7 214-1BD21-0XB0, 110/230 V AC, 24 V DC inputs2), 24 V DC/250 V AC relay outputs C

6ES7 216-2AD21-0XB0, 24 V DC, 24 V DC inputs, 24 V DC outputs, electronic J6ES7 216-2BD21-0XB0, 110/230 V AC, 24 V DC inputs, 24 V DC/250 V AC relay outputs K

Number of analog inputs (EM231)without A1 EM231 module (4 measured values) B2 EM231 modules (8 measured values) C

3 EM231 modules (12 measured values) D4 EM231 modules (16 measured values) E

Modem

without modem 0IL2K4 RS485, V.23, 1200 bit/s, multidrop partyline, half-duplex, 2-wire with connection cable 1

STEP 7-Micro/WIN 32 V3.1 (32 bit version) 6ES7810-2BC01-0YX0

PC/PPI cable (RS232 RS485 converter) 6ES7901-3BF20-0XA0

Documentation

EnglishSICAM 2.3.1 Catalog SICAM microRTU E50001-K5602-A311-A3-7600Manual SICAM microRTU E50417-H8976-C057-A1System manual S7-200 6ES7298-8FA01-8BH0

GermanSICAM 2.3.1 Catalog SICAM microRTU E50001-K5602-A311-A3Manual SICAM microRTU E50417-H8900-C057-A1System manual S7-200 6ES7298-8FA01-8AH0

1) Current-sinking2) Current-sourcing

Selection andordering data

� � ��

Siemens SICAM 2.3.1 ⋅ 2001 9

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16Order No.

Page 12: SICAM MicroRTU 6MD203 Remote Terminal Unit

SICAM microRTU6MD203 Remote Terminals Unit

� SIMATIC modules Order No.

Expansion modules

Digital inputsModule for S7-224/-226EM221: Digital inputs, 8 x 24 V DC 6ES7 221-1BF21-0XA0

Digital outputsModule for S7-224/-226EM222: Digital outputs, 8 x relay outputs, 2 A 6ES7 222-1HF21-0XA0

Modem - CPU connecting cable

Modem - CPU connecting cable 6MD4301-0AD00

2.5 kV isolation with Phönix PLC relay (6.2 mm)

PLC-R-relay with gold-plated contacts for indications

PLC-RSC-24DC/21AU 24 V DC 29 66 26 5PLC-RSC-48DC/21AU 48 V DC 29 66 12 6PLC-RSC-60DC/21AU 60 V DC 29 66 14 2

PLC-RSC-120UC/21AU 110/120 V DC/AC 29 66 28 1PLC-RSC-230UC/21 AU 220/230 V DC/AC 29 66 29 4

PLC system connection for inputsPLC-V8/FLK14/IN, block for 8 inputs 22 96 55 3System cable 0.5 m 22 88 90 1System cable 1.0 m 22 88 91 4

PLC-R-relay with power contactmax. switching voltage 250 V DC/ACmax. breaking power at resistive load: 24 V DC at 140 W, 48 V DC at 20 W,60 V DC at 18 W, 110 V DC at 23 W, 220 V DC at 40 WPLC-RSC-24DC/21 24 V DC 29 66 17 1

PLC relay for high continuous currentmax. switching voltage 250 V DC/ACmax. breaking power at resistive load: 24 V DC at 144 W, 48 V DC at 144 W,60 V DC at 48 W, 110 V DC at 50 W, 220 V DC at 80 WPLC-RSC-24DC/21HC 29 67 62 0

PLC system connection for outputsPLC-V8/FLK14/OUT, block for 8 outputs 22 95 55 4System cable 0.5 m 22 88 90 1System cable 1.0 m 22 88 91 4

� Power supply

Power supply DC/DC, AC/DCDC/DC converter 48/60/110 V DC, 24 V DC; 2 A 6EP1732-0AA00AC/DC converter for UE: 110 to 230 V AC, 220 V DC, 24 V DC; 2.5 A 6EP1332-1SH12

Backup unitAC/DC converter for UE: 120/230 V AC, 24 V DC; 5 A 6EP1333-2BA00DC-USV module 15, input 24 V DC, output 24 V DC 6EP1931-2EC01Battery module (lead-acid) for DC-USV module 15, 24 V DC, 7 Ah 6EP1935-6ME01

� Modem

Modem IL2K4 at the SICAM microRTUIL2K4, V.23, 1200 bit/s, multidrop party line, RS485 6MD4500-0AB00

Modem MD 100 in the control centerMD100, V.23, 1200 bit/s, multidrop party line, RS232 6NH9810-2A

Accessories

10 Siemens SICAM 2.3.1 ⋅ 2001

Page 13: SICAM MicroRTU 6MD203 Remote Terminal Unit

� Programming, test Order No.

Interface cable RS485 - RS232

For connection to the PPI interface of the S7-200 to a PC. The cable is usedfor loading the CPU software into the S7-200 CPUs with STEP 7-Micro/WIN.PC/PPI cable; 5 m long, RS232/RS485 6ES7 901-3BF20-0XA0

Configuring tool for S7-200 CPU

STEP 7-Micro/WIN runs under WIN 95 or NT. It can be connected tothe S7-200 via the COM interface of a PC by means of the PC/PPI cable.Operation via PG 7xx and MPI interface is also possible.STEP 7-Micro/WIN 32 V3.1, individual license, CD-ROM 6ES7810-2BC01-0YX0Upgrade to V3.1, CD-ROM 6ES7810-2BC01-0YX3

Spare parts

Modem IL2K4 at the SICAM microRTU

IL2K4, V.23, 1200 bit/s, multidrop party line, RS485 6MD4500-0AB00

Analog module EM231

S7-224/-226: AI 4 x 12 bit, 0 to 20 mA, 0 to 5 V, 0 to 10 V 6ES7 231-0HC20-0XA0

Siemens SICAM 2.3.1 ⋅ 2001 11

Page 14: SICAM MicroRTU 6MD203 Remote Terminal Unit

� Conditions of Sale and Delivery

Subject to theGeneral Conditions of Supply and Delivery for Productsand Services of the Electrical and Electronic Industry andto any other conditions agreed upon with the recipients ofcatalogs.

� Export Regulations

In accordance with the present provisions of the GermanExport List and the US Commercial Control List, exportlicences are not required for the products listed in thiscatalog.An export licence may however be required due to country-specific application and final destination of the products.Relevant are the export criteria stated in the delivery noteand the invoice regarding a possible export and reexportlicence.Subject to change without notice.

� Dimensions

All dimensions in this catalog are given in mm.

� Trademarks

All product designations used are trademarks or productnames of Siemens AG or of other suppliers.

Responsible for:Technical contents: Manfred KrautschneiderSiemens AG, PTD PA 27, NürnbergGeneral editing: Claudia Kühn-SutionoSiemens AG, PTD CC T, Erlangen

The technical data, di-mensions and weightsare subject to changeunless otherwise statedon the individual pagesof this catalog.

The illustrations are forreference only.

We reserve the right toadjust the prices andshall charge the priceapplying on the date ofdelivery.

Conditions ofsale and delivery

Order No.: E50001-K5602-A311-A3-7600Printed in GermanyKGK 0501 12 En 102266 6101/D6171

12 Siemens SICAM 2.3.1 ⋅ 2001

Page 15: SICAM MicroRTU 6MD203 Remote Terminal Unit

Catalog index

� Catalog index of the Power Transmission and Distribution (Power Automation Division)

Title Designation- Order No.

Numerical Protection Systems and Bay Control Units

Operation and Evaluation Software for Numerical Protection Devices LSA 2.0.2 E50001-K5702-A121-A1-7600Relay Selection Guide LSA 2.0.3 E50001-K5702-A031-A2-76007SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-76007SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A2-76007SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-76007SJ512 Numerical Feeder Protection (Version V3.6) LSA 2.1.30 E50001-K5712-A411-A1-4A00SIPROTEC 7SJ531 Numerical Line and Motor Protection with Control Function LSA 2.1.9 E50001-K5712-A191-A4-76007SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A3-7600SIPROTEC 4 - 7SJ61/62/63 6MD63 Multifunction Protection Relay and Bay Controller SIP 3.1 E50001-K4403-A111-A1-4A00SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay SIP 3.2 E50001-K4403-A121-A1-7600SIPROTEC 7SJ602 Numerical Overcurrent, Motor and Overload Protection Relay SIP 3.3 E50001-K4403-A131-A1-7600SIPROTEC 7SJ601 Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600SIPROTEC 7SA511 Distance Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-76007SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-76007SA518/519 Overhead Control-Line Protection Relay (Version V3) LSA 2.1.14 E50001-K5712-A241-A2-7600SIPROTEC 4 - 7SA6 Distance Protection Relay for all Voltage Levels SIP 4.3 E50001-K4404-A131-A1-76003VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A2-76007SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-76007SD503 Line Differential Protection with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-76007SD511/512 Current Comparison Protection Relay (Version V3)for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-76007UT512/513 Differential Protection Relay (Version V3)for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600SIPROTEC 7RW600 Numerical Voltage, Frequency and Overexcitation Relay SIP 2.1 E50001-K4402-A111-A1-7600SIPROTEC 7SS50 Version V1.2 Busbar/Circuit-BreakerFailure Protection Relay (Summation Current Transformer Version) SIPROTEC 5.1 E50001-K4405-A111-A1-7600SIPROTEC 7SD60 Numerical Current Differential Protection Relayfor Two Pilot-Wire Link SIP 5.2 E50001-K4405-A121-A2-7600SIPROTEC 4 - 7SD610 Universal Differential Protection Relay for Two Line Ends SIP 5.4 E50001-K4405-A141-A1-7600SIPROTEC 7SS52 Distributed Numerical Busbar and Circuit-BreakerFailure Protection Relay LSA 2.2.7 E50001-K5722-A171-A1-7600Auxiliary Current Transformers 4AM50, 4AM51, 4AM52and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600Introduction to Earth-Fault Detection LSA 2.3.1 E50001-K5732-A111-A2-76007SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-76007XR96 Toroidal Current Transformer LSA 2.3.3 E50001-K5732-A131-A1-76007VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600Introduction to Generator Protection LSA 2.5.1 E50001-K5752-A111-A1-76007SK52 Motor Protection LSA 2.4.1 E50001-K5742-A111-A1-76007UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-76007UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-76007UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-76007UM516 Generator Protection Relay (Version V3) LSA 2.5.5 E50001-K5752-A151-A1-7600SIPROTEC 4 - 7UM611/612 Multifunction Generator Protection Relay SIP 6.1 E50001-K4406-A111-A1-7600SIPROTEC 4 - 7UM62 Multifunction Generator, Motor & TransformerProtection Relay SIP 6.2 E50001-K4406-A121-A1-76007VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-76007VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-76007SV7220 Power Supply Unit LSA 2.7.9 E50001-K5772-A191-A1-76007SV50 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.1 E50001-K5772-A111-A1-76007SV512 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.2 E50001-K5772-A121-A1-76007XV72 Test Switch LSA 2.6.2 E50001-K5762-A121-A1-76007VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600Communication for Protection DevicesCentralized and Remote Control of Siemens Protection Relays (Overview) SIPROTEC 8.1 E50001-K4408-A111-A1-7600Operating and Analysis Software DIGSI V3 LSA 2.8.2 E50001-K5782-A121-A1-7600DIGSI 4 - Software for Configuration and Operation of SIPROTEC 4 units SIP 8.2 E50001-K4408-A121-A1-7600DIGRA 4 - Software for the Visualization and Analysis of Fault Records SIP 8.3 E50001-K4408-A131-A1-76006MB252 Mini Bay Unit for Energy Automation with SICAM SIPROTEC 7.1 E50001-K4407-A111-A1-7600SIPROTEC 4 - 6MD66 Bay Control Unit SIP 7.2 E50001-K4407-A121-A1-7600Energy Automation

Substation SICAM RTU System SICAM 2.1.1 E50001-K5602-A111-A1-7600SICAM miniRTU 6MD202 Remote Terminal Unit SICAM 2.2.1 E50001-K5602-A211-A2-7600SICAM microRTU 6MD2030 Remote Terminal Unit SICAM 2.3.1 E50001-K5602-A311-A3-7600SICAM SAS Substation Automation System SICAM 3.1.1 E50001-K5603-A111-A1-7600PS20A-6EP8090 Power Supply Module SICAM 5.1.1 E50001-K5605-A111-A1-7600DI32-6MD1021 Digital Input Functional Module SICAM 5.2.1 E50001-K5605-A211-A1-7600AI32-6MD1031 Analog Input Functional Module SICAM 5.2.2 E50001-K5605-A221-A1-7600AI16-6MD1032 Analog Input Functional Module SICAM 5.2.3 E50001-K5605-A231-A1-7600Visualization System for SICAM SAS: SICAM WinCC SICAM 6.1.1 E50001-K5606-A111-A1-7600SICAM plusTOOLS Configuration System SICAM 6.2.1 E50001-K5606-A211-A1-7600

Siemens SICAM 2.3.1 ⋅ 2001 13

Page 16: SICAM MicroRTU 6MD203 Remote Terminal Unit

www.ev.siemens.de Order No.: E50001-K5602-A311-A3-7600

Published by