Upload
sindhu-s-nathan
View
212
Download
0
Tags:
Embed Size (px)
Citation preview
HYBRID FILTER FOR POWER QUALITY
IMPROVEMENT
A PROJECT REPORT
submitted by
SINDHU.S (CB207PE019)
in partial fulfillment for the award of the degree of
MASTER OF TECHNOLOGY
IN
POWER ELECTRONICS
AMRITA SCHOOL OF ENGINEERING, COIMBATORE
AMRITA VISHWA VIDYAPEETHAM
COIMBATORE 641 105
JULY 2009
AMRITA VISHWA VIDYAPEETHAM
AMRITA SCHOOL OF ENGINEERING, COIMBATORE, 641105
BONAFIDE CERTIFICATE
This is to certify that the project report entitled “HYBRID FILTER FOR POWER
QUALITY IMPROVEMENT” submitted by SINDHU.S (REGNO: CB207PE019)
in partial fulfillment of the requirements for the award of the Degree of Master of
Technology in POWER ELECTRONICS is a bonafide record of the work carried
out under my guidance and supervision at Amrita School of Engineering,
Coimbatore.
SIGNATURE SIGNATURE Mrs.M.R.Sindhu Dr.T.N.P.Nambiar Assistant Professor Chairperson Department of Electrical Department of Electrical and Electronics Engineering and Electronics Engineering This project report was evaluated by us on………….. INTERNAL EXAMINER EXTERNAL EXAMINER
Dedicated To ….
My Son Adithya
AMRITA VISHWA VIDYAPEETHAM
AMRITA SCHOOL OF ENGINEERING, COIMBATORE
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
ENGINEERING (POWER ELECTRONICS)
DECLARATION
I, SINDHU.S (Reg. No: CB207PE019) hereby declare that this project report,
entitled “HYBRID FILTER FOR POWER QUALITY IMPROVEMENT", is a
record of the original work done by me under the guidance of Mrs. M.R.Sindhu,
Assistant Professor, Department of Electrical and Electronics Engineering, Amrita
School of Engineering, Coimbatore and that this work has not formed the basis for
the award of any degree/ diploma/ associateship/ fellowship or a similar award, to any
candidate in any University, to the best of my knowledge.
Signature of the student Place: Coimbatore Date:
COUNTERSIGNED
Mrs. M.R.Sindhu
Assistant Professor
Department of Electrical and Electronics Engineering,
Amrita School of Engineering, Coimbatore
ACKNOWLEDGEMENT
I express my sincere gratitude to my guide Mrs. M.R.Sindhu, Assistant
Professor, Electrical and Electronics Engineering Department, for her valuable help,
timely guidance and supervision throughout my project work.
I express my sincere thanks to Dr T. N. P. Nambiar, Chairperson, Electrical
and Electronics Engineering Department, for his guidance, supervision and support
throughout the course of this project.
I am thankful to Prof.A.T.Devarajan, Asst. Professor, Electrical and
Electronics Engineering Department, for his valuable suggestions during the entire
course of the project.
I express my thanks to the all the staffs of EEE department, Electrical
Machines Lab and Power Electronics Lab for their kind help and co-operation.
I express my sincere gratitude to my family, for their unending support, love
and encouragement especially, the sacrifices done by my dear son, Adithya. Finally I
express my bows to all of those who are remotely involved in this project.
Above all, I thank Almighty for giving me the strength, courage and blessings
to complete this project.
i
ABSTRACT
The effect of harmonics and power quality problems were introduced into the power
system with the usage of switching converters and other power electronic devices.
Since then, many works have been done to solve these power quality problems and
provide clean power to the customers. Passive tuned filters were the initial step taken
towards this. It consists of tuned LC filters for removing specific harmonic
component or blocking a band of harmonic frequencies generated by the nonlinear
loads. Low cost is a great benefit of these filters. But the installation of passive filters
may result in resonance between the impedance of passive filter and the system
resulting in amplifying the harmonics of source current. Resonance, Fixed
compensation and huge size in passive filters were overcome in active power filters.
Active power filter introduces equal and opposite harmonics and/or reactive
components in to the three phase system so that clean power at unity power factor is
drawn from supply mains. However, depending upon the amount and nature of
compensation demanded, the size and hence the cost of active filters in a practical
industry is too high.
Hybrid power filter topologies have been developed to solve the problems of
harmonic currents and reactive power effectively. Using low cost passive filters in the
hybrid active filter, the power rating of active converter is reduced compared with
that of pure active filters. Hybrid power filters retain the advantages of active filters
and do not have the drawbacks of passive and active filters. This topology lends itself
to retrofit applications with existing passive filters. The hybrid filters are cost-
effective and become more practical in industry applications. This thesis presents simulation studies and hardware testing of a hybrid power
filter using a combination of shunt active power filter and passive filter. The active
power filter employs Icosφ algorithm as control algorithm. The effectiveness of
hybrid power filter is evident from the simulation and hardware results presented in
thesis.
TABLE OF CONTENTS
CHAPTER TITLE PAGE NO
ABSTRACT i
LIST OF FIGURES v
LIST OF TABLES vii
LIST OF SYMBOLS viii
LIST OF ABBREVATIONS ix
1 INTRODUCTION 1
1.1 Power quality improvement 2
1.2 Scope of the work 2
1.3 Organization of the thesis 3
2 LITERATURE SURVEY 4
2.1 Introduction 4
2.2 Literature review 4
2.2.1 Passive filter 5
2.2.2 Active filter 5
2.2.3 Hybrid filter 6
2.3 Conclusion 9
3 POWER SYSTEM HARMONICS – SOURCES 10
AND EFFECTS
3.1 Introduction 10
3.2 Sources of harmonics 10
3.2.1 Transformer 11
3.2.2 Rotating machines 11
3.2.3 Arc furnaces 12
3.2.4 Fluorescent lights 12
3.2.5 Static var converters 12
3.2.6 Cycloconverters 12
3.3 Effects of harmonic distortion 12
CHAPTER TITLE PAGE NO
3.3.1 Thermal losses in a harmonic 13
environment
3.3.2 Resonances 14
3.3.3 Effects of harmonics on rotating 14
Machines
3.4 Conclusion 15
4 POWER SYSTEM HARMONICS – 16
MITIGATION TECHNIQUES
4.1 Power quality improvement techniques 16
4.2 Passive filters 16
4.2.1 Single tuned filters 17
4.2.2 Double tuned filters 17
4.3.3 Automatically tuned filters 17
4.3.4 Damped filters 18
4.3 Active filters 19
4.3.1 Series active filter 20
4.3.2 Shunt active filter 20
4.3.3 Control algorithm 21
4.3.3.1 Instantaneous PQ theory 21
4.3.3.2 Synchronous detection algorithm 22
4.3.3.3 DC bus voltage algorithm 24
4.3.3.4 Icosφ algorithm 25
4.4 Hybrid filter 27
4.5 Conclusion 29
5 COMPARISON OF ACTIVE FILTERING 30
ALGORITHMS – SIMULATION RESULTS
5.1 Introduction 30
5.2 Simulation model requirements 30
5.3 Simulation of the full controlled converter feeding 32
an RL load without shunt active power filter
CHAPTER TITLE PAGE NO
5.4 Simulation of Shunt Active Filter under 35
Balanced Source and Balanced Load
Conditions
5.4.1 Simulation of Instantaneous PQ 35
Theory
5.4.2 Simulation of the Synchronous 39
Detection Algorithm
5.4.3 Simulation of DC bus voltage 42
algorithm
5.4.4 Simulation of Icosφ algorithm 45
5.5 Simulation of shunt Active Filter using Icosφ 48
under Unbalanced Source and Balanced Load
conditions
5.6 Simulation of shunt Active Filter using Icosφ 51
algorithm under Balanced Source and unbalanced
load Conditions
5.7 Conclusion 54
6 SIMULATION OF HYBRID POWER FILTER 55 6.1 Introduction 55
6.2 Simulation of the full controlled converter feeding 55
an RL load with out filter
6.3 Simulation of the full controlled converter feeding 58
an RL load with passive filter
6.4 Simulation of the full controlled converter feeding 63
an RL load with shunt active power filter
6.5 Simulation of the full controlled converter feeding 67
an RL load with hybrid filter
6.6 Conclusion 71
7 HARDWARE SETUP – DESIGN AND 72
MODELLING OF HYBRID FILTER
7.1 Introduction 72
CHAPTER TITLE PAGE NO
7.2 Hardware implementation – laboratory 73
prototype
7.3 Control circuit design and test results 75 7.3.1 Fundamental detection of load 75
current
7.3.1.1 Op-amp based circuit of 76
biquad filter
7.3.2 Zero crossing detection 76
7.3.3 Sample and hold circuit 77
7.3.4 The multiplication circuit 78
7.3.5 The subtractor circuit 78
7.3.6 The comparator circuit for 79
PWM generation
7.3.7 Isolation and amplification 79
circuit
7.4 Conclusion 80
8 HARDWARE IMPLEMENTATION OF HYBRID 81
POWER FILTER – UNDER DIFFERENT SOURCE
AND LOAD CONDITIONS
8.1 Introduction 81
8.2 Experimental results 81
8.1.1 Balanced source and balanced load 81
condition
8.1.2 Distorted source and a balanced load 85
condition
8.1.3 Balanced source and unbalanced load 88
condition
8.3 Conclusion 91
9 CONCLUSION AND SCOPE FOR FUTURE WORK 93
9.1Scope and future work 94
CHAPTER TITLE PAGE NO
REFERENCES 95
APPENDICES 98
Appendix-1 Details of load, Passive filter and 98
inverter
Appendix-2 Datasheet 99
Appendix-3 Photograph of 113
experimental set up
ii
LIST OF FIGURES FIGURE TITLE PAGE NO:
2.1 Hybrid filters- Classification 7
4.1 Transformation from (a) two single 17
tuned filters to (b) double tuned filters
(c) the impedance versus frequency of
filter double tuned for 5th and 7th.
4.2 High pass damped filters: (a) first order 18
(b) second order (c) third order (d) C-type
4.3 (a) Voltage fed PWM inverter (b) Current 19
fed PWM inverter
4.4 (a) Series Active filter (b) Shunt Active filter 20
4.5 Block diagram for implementing Instantaneous 22
PQ theory
4.6 Block diagram for implementing Synchronous 23
Detection Algorithm
4.7 Block diagram for implementing DC Bus Voltage 24
Algorithm
4.8 Basic block diagram of Icosφ algorithm 26
4.9 Basic set up of three phase shunt hybrid filter 27
5.1 Basic block diagram for the implementation of 31
shunt active filter
5.2 Basic block diagram for full controlled converter 32
feeding an RL load
5.3 Source voltage, load current, source current in phase A 33
at α=0° without filter.
5.4 Source current spectrum at α=0° without filter 33
5.5 Source voltage, load current, source current in phase A 34
at α=30° without filter
5.6 Source current spectrum at α=30° without filter 34
iii
FIGURE TITLE PAGE NO:
5.7 Basic setup for shunt active filtering with 36
Controller
5.8 Source voltage, load current, source current 37
in phase A at α=0° with Active Power Filter
using IRPT control algorithm
5.9 Source current spectrum at α=0° with Instantaneous 37
Reactive PQ theory
5.10 Source voltage, load current, source current in 38
phase A at α=30° with Active Power Filter using
IRPT control algorithm
5.11 Source current spectrum at α=30° with Instantaneous 38
Reactive PQ theory
5.12 Source voltage, load current, source current in 40
phase A at α=0° with Active Power Filter using
Synchronous Detection algorithm
5.13 Source current spectrum at α=0° with Synchronous 40
Detection algorithm
5.14 Source voltage, load current, source current in 41
phase A at α=30° with Active Power Filter using
Synchronous Detection algorithm
5.15 Source current spectrum at α=30° with Synchronous 41
Detection algorithm
5.16 Source voltage, load current, source current 43
in phase A at α=0° with Active Power Filter using
DC Bus Voltage algorithm
5.17 Source current spectrum at α=0° with DC Bus 43
Voltage algorithm
5.18 Source voltage, load current, source current in 44
phase A at α=0° with Active Power Filter using
DC Bus Voltage algorithm
iv
FIGURE TITLE PAGE NO:
5.19 Source current spectrum at α=30° with 44
DC Bus Voltage algorithm
5.20 Source voltage, load current, source current 46
in phase A at α=0° with Active Power Filter
using with Icosφ algorithm
5.21 Source current spectrum at α=0° with Icosφ 46
algorithm
5.22 Source voltage, load current, source current in 47
phase A at α=30° with Active Power Filter using
with Icosφ algorithm
5.23 Source current spectrum at α=30° with Icosφ 47
algorithm
5.24 Source voltage, load current, source current in 49
phase A at α=0° with Active Power Filter using
with IcosΦ algorithm
5.25 Source current spectrum at α=0° with Icosφ 49
algorithm for unbalanced source and balanced
load condition
5.26 Source voltage, load current, source current 50
in phase A at α=30° with Active Power Filter
using with IcosΦ algorithm
5.27 Source current spectrum at α=30° for unbalanced 50
source and balanced load condition
5.28 Source voltage, load current, source current in 51
phase A at α=0° with Active Power Filter using
with Icosφ algorithm
5.29 Source current spectrum at α=0° with Icosφ algorithm 52
for balanced source and unbalanced load condition
5.30 Source voltage, load current, source current in 52
phase A at α=30° with Active Power Filter using
with Icosφ algorithm
v
FIGURE TITLE PAGE NO:
5.31 Source current spectrum at α=30° with 53
Icosφ algorithm for balanced source
and unbalanced load condition
6.1 Basic simulation setup for full controlled 55
converter feeding an RL load
6.2 Source voltage, load current, source current 56
in phase A at α=0° without filter
6.3 Source current spectrum at α=0° without 57
filter
6.4 Source voltage, load current, source current 57
in phase A at α=30° without filter
6.5 Source current spectrum at α=30° without 58
filter
6.6 Matlab simulation of the full controlled converter 60
feeding RL load with passive filters
6.7 Source voltage, load current, source current 61
in phase A at α=0° with Passive filter
6.8 Source current spectrum at α=0° Passive filter 62
6.9 Source voltage, load current, source current
in phase A at α=30° with Passive filter
6.10 Source current spectrum at α=30° without 62
Passive Filter
6.11 Matlab simulation of the full controlled converter 63
feeding RL load with Active Power filter
6.12 Source voltage, load current and source current in 64
phase A at α =0° with Active Power Filter
6.13 Source current spectrum at α =0° with Active Power 65
Filter
6.14 Source voltage, load current and source current in 65
phase A at α =30° with Active Power Filter
vi
FIGURE TITLE PAGE NO:
6.15 Source current spectrum at α =30° with 66
Active Power Filter
6.16 Matlab simulation of the full controlled 67
converter feeding RL load with Hybrid Filter
6.17 source voltage, load current and source current 68
in phase A at α =0° with Hybrid Filter
6.18 Source current spectrum at α =0° with Hybrid 69
Filter
6.19 source voltage, load current and source current 69
in phase A at α =30° with Hybrid Filter
6.20 Source current spectrum at α =30° with Hybrid 70
Filter
7.1 Basic Block diagram of three phase hardware setup 73
7.2 Basic setup for hardware using passive filters 74
7.3 The block diagram of the Icosφ analog controller 75
for phase A.
7.4 Op-amp circuit of the biquad filter 76
7.5 Negative zero crossing detection circuit 77
with monostable multivibrator
7.6 sample and hold circuit for getting Icosφ value 77
7.7 The multiplier circuit for producing desired 78
source current
7.8 The subtractor circuit for producing compensation 78
current.
7.9 The comparator circuit for PWM generation 79
7.10 The isolation and amplification circuit 80
8.1 Diode bridge rectifier load with active filter: 82
(a) Source voltage and load current (phase A)
(b) Load current and reference compensation
current (phase A)
vii
FIGURE TITLE PAGE NO:
8.2 Diode bridge rectifier load: Reference 82
Compensation current and actual compensation
current in closed loop (phase A)
8.3 Diode bridge rectifier load with hybrid filter 83
(shunt active and shunt passive): (a) Load current
and reference compensation current (phase A)
(b)Reference compensation current and actual
compensation current in (phase A)
8.4 a) source voltages b) source current without 84
filtering c) source current with hybrid filter
for balanced source and load condition
8.5 a) a-phase voltage and current without filtering 84
b) a-phase voltage and current with hybrid
filtering for balanced source and load condition
8.6 THD % of Source current spectrum (a) without 85
filtering (b) with active filter for balanced source and
load condition
8.7 THD % of Source current spectrum (a) With passive 85
filter (b) with hybrid filter for balanced source and
load condition
8.8 a) source voltages b) source current without 86
filtering c) source current with hybrid filter
filtering for distorted source and balanced load
condition
8.9 a) a-phase voltage and current without filtering 86
b) a-phase voltage and current with hybrid
filtering for distorted source and balanced load
condition
viii
FIGURE TITLE PAGE NO:
8.10 THD % of Source current spectrum (a) without 87
filtering (b) with active filter for distorted source
and balanced load condition
8.11 THD % of Source current spectrum (a) With passive 87
filter (b) with hybrid filter for distorted source and
balanced load condition
8.12 a) source voltages b) source current without filtering 88
c) source current with hybrid filter for balanced
source and unbalanced load condition
8.13 a) a-phase voltage and current without filtering 89
b) a-phase voltage and current with hybrid filtering
for balanced source and unbalanced load condition
8.14 THD % of Source current spectrum (a) without 89
filtering (b) with active filter for balanced source
and unbalanced load condition
8.15 THD % of Source current spectrum (a) With passive 90
filter (b) with hybrid filter for balanced source and
unbalanced load condition
ix
LIST OF TABLES
TABLES TITLE PAGE NO:
5.1 %THD in the mains currents before and after 48
shunt compensation for two firing angles α=0°
and α=30°
5.2 %THD in the mains currents before and after 53
shunt compensation under Balanced/ Unbalanced
Source and Balanced/unbalanced Load Conditions
using Icosφ algorithm
6.1 parameter values of passive filter for simulation 61
6.2 Simulation of the three phase system with 70
passive filter, active filter and hybrid filter
8.1 Comparison of source current spectrum with and 90
without hybrid filter under balanced source and
load condition (50V/phase)
8.2 Comparison of source current spectrum with and 91
without hybrid filter under distorted source and
load condition (50V/phase)
8.3 Comparison of source current spectrum with and 91
without hybrid filter under balanced source and
unbalanced load condition (50V/phase)
x
LIST OF SYMBOLS ea,eb,ec or va,vb,vc Three phase instantaneous mains voltages.
iLa,iLb,iLc Three phase instantaneous load currents
PL Instantaneous real power
qL Instantaneous reactive power
pL Ripple (AC) in real power
Ripple in reactive power
icα, icβ or icαβ Reference compensation currents in αβ plane
i∗ca, i∗cb, i∗cc or i∗cabc Three phase reference compensation currents
P Instantaneous three phase power
Pdc Average value of three phase power
Pa, Pb, Pc Average power in each phase
Ea, Eb, Ec Three phase mains voltage amplitudes
Etot Sum of Ea, Eb, Ec
ima, imb, imc Three phase desired main currents
Vm Phase voltage magnitude
ω Fundamental frequency in rad/sec
ILa1, ILb1, ILc1 Fundamental component of load current in each
phase
I.cosφ real component of fundamental component of load
current
Φ phase angles of fundamental load current
desired amplitude of source current
Ua,Ub,Uc Unit amplitude phase voltages in the three phases
isa(ref), isb(ref), isc(ref) Three phase desired (reference) mains currents
ia(comp), ib(comp), ic(comp) Three phase reference compensation currents
THD Total harmonic distortion
1
CHAPTER I
INTRODUCTION
The solid state power conversion is rapidly increasing due to wide
application of adjustable speed drives (ASDs), arc furnaces, bulk rectifiers, TV
sets, fax machines, computers, fluorescent tubes and microwave ovens, etc. Apart
from this a large number of solid state power converters such as diode bridge
rectifiers and thyristor rectifiers are used in the numerous industrial applications
and transmission/distribution networks. All these breeds of power converters are
nonlinear in nature and cause serious problems of current harmonics, poor power
factor, non sinusoidal supply voltage, reactive power burden and low system
efficiency. Hence, due to these serious issues there has been an increasing interest
in the subject of power quality and in the equipments which can suppress supply
harmonics, improve power factor and balance the input supply.
The various power quality problems are voltage sags and swells, voltage
transients, voltage flicker, harmonic distortions, voltage spikes etc. The overall
degradation in the electric power utility affects sensitive loads such as computers,
automated processing in industries and other microprocessor controlled medical
equipments risking the loss of valuable data. With growing awareness about these
problems, the power system utilities, industries and commercial establishments
started protecting themselves by investing in sophisticated protection equipment
for harmonic mitigation. The IEEE 519, IEC-6100, EN-50160 are some of the
standards defining power quality issues [4]. All these standards give an account of
harmonic generation and stipulated limits in the system in the presence of static
converters such as arc furnaces, static VAR compensator, inverters, switched
mode power supplies, pulse width modulated drives etc. The effects of harmonics
on various equipments are also described with guidelines for the measurement and
analysis of harmonics.
2
1.1 POWER QUALITY IMPROVEMENT
The quality of electric power received by the customer has always been a great
concern as reliability of electric supply. The term “Power Quality” is associated
with the fact that the consumer is bound to receive clean power, which provides
balanced, undistorted voltages of constant amplitude at a specified frequency i.e.;
the power quality is associated with the delivery of a sufficiently high grade of
electrical service [5]. It should have regulated voltage as well as steady current
waveforms without dips and surges and should maintain the desired load
frequency. The current and voltage waveforms are expected to be sinusoidal and
at unity power factor.
Conventionally harmonic distortion has been dealt-with by establishing banks
of tuned passive filters. Tuned passive filters have advantages of being simple to
design, cheap and reliable. However, they are limited by drawbacks such as fixed
compensation, resonance and huge size. Active filters were developed to mitigate
problems of passive filters. They are more effective in harmonic compensation
and improved performance. But pure active filters have high cost and require
comparatively high power converter ratings. Hybrid power filters, inheriting the
advantages of both passive filters and active filters provide improved performance
with a reduction in the overall cost of the power circuit.
1.2 SCOPE OF THE WORK
This work deals with power quality improvement by means of hybrid power
filter in which the shunt active power filter uses Icosφ control algorithm. Initially,
simulation and comparative study of existing shunt active filter algorithms in
Matlab simulation platform were carried out to verify the effectiveness of the
control algorithm under balanced source and balanced load conditions. Also, the
simulations of the control algorithm have been carried out for unbalanced source
and unbalanced non-linear load conditions. Finally simulation and hardware
testing of hybrid power filter under various source and load conditions was also
developed.
3
1.3 ORGANIZATION OF THE THESIS
The thesis is presented as 11 chapters. The chapter 1 brief introduction to the
thesis work ands scope of the work Chapter 2 covers the literature survey which is
a collection of research works done in areas of passive filter, active filter, hybrid
filter, control techniques etc. Chapter 3 describes sources of harmonics and
effects. Chapter 4 describes the mitigation techniques. In chapter 5, using
simulations a comparative study of the commonly used control algorithms is done.
Design of passive filter and simulation of hybrid power filter and results are
included in chapter 6. The hardware setup of hybrid filter is given in chapter 7. In
chapters 8, hardware implementation results of hybrid filter with diode bridge
rectifier load under different conditions including balanced/unbalanced source and
balanced/unbalanced load are presented. Chapter 9 gives the conclusion of the
work.
4
CHAPTER II
LITERATURE SURVEY
2.1 INTRODUCTION
Solid-state conversion of AC power using diodes and thyristors is widely adopted
to control a number of processes such as adjustable speed drives (ASD), furnaces,
chemical processes such as electroplating etc., power supplies, welding, heating
etc. These solid-state converters are also used in power industries such as
transmission systems, battery energy storage systems and interfacing renewable
energy electricity generating systems. Some of these solid-state controllers draw
harmonic currents and reactive power from the AC mains and behave as nonlinear
loads. Moreover, in three-phase AC mains, they also cause unbalance and poor
efficiency of the systems. Initially, lossless passive filters (LC) have been used to
reduce harmonics, and capacitors have been chosen for power-factor correction of
these nonlinear loads. But passive filters have the demerits of fixed compensation,
large size, detuning [15] and resonance with the supply system.
2.2 LITERATURE REVIEW
In recent years, the increasing application of power electronic equipments which
results in the generation of harmonic current components and causes higher
distortion levels throughout power systems. Harmonic resonance may cause
serious problems such as overvoltage in power systems. Because of such severity
of power quality problems, several standards have been developed [3] and are
being enforced on consumers, manufacturers and utilities. Moreover the power
community has become more conscious of these power quality problems and
numbers of technology options have been reported in the literature and research
publications. Detailed analysis of sources, effects and mitigation of harmonics
have been done and which is given in chapter 3 and 4.
5
2.2.1 PASSIVE FILTERS
Passive filters are widely used in power systems for harmonic mitigation. Passive
filters are classic methods for power quality improvement of distribution systems
consist of series LC tuned for removing a specific harmonic or blocking a
bandwidth of severe harmonics of nonlinear load current. These filters have low
impedances for the tuned frequencies such as 5th and 7th and for these
frequencies, the lower impedance of the filter in comparison with system
impedance, the better filtering characteristics of the passive filter. These devices
have advantages of being simple to design, cheap and reliable. However, shunt
passive filters have the following inherent problems which discourage their
application [21-23]:
Mistuning due to component tolerances of the inductors and capacitors,
variation of component values will strongly affect the filtering
characteristics.
The source impedance strongly influences filtering characteristics of the
shunt passive filter.
The shunt passive filter acts as a sink to the harmonic current flowing
from the source. In the worst case, the shunt passive filter falls in series
resonance with the source impedance.
At a specific frequency, a parallel resonance occurs between the source
impedance and the shunt passive filter, which is the so-called harmonic
amplification.
2.2.2 ACTIVE FILTER
Active power filters are one of the most important remedial measures to solve
power quality problems. Configurations of active filters can be classified based on
converter type, topology, and the number of phases. The converter type can be
either CSI or VSI bridge structure. The topology can be shunt, series, or a
combination of both. The third classification is based on the number of phases,
such as two-wire (single phase) and three- or four-wire three-phase systems [7,
20].
6
The control scheme used to generate the compensation signals forms the heart of
the active filtering unit. Instantaneous PQ theory [7], synchronous detection
algorithm [8], DC bus voltage algorithm [9] and synchronous reference frame
theory [10] are some of the widely used three-phase shunt active filtering
algorithms. Existing control schemes still require fine-tuning to make the
computations and circuit implementation as simple and rugged as possible. A
simple and effective control circuit enhances the speed of response and efficiency
of the filter. Icosφ algorithm is such a simple current compensation algorithm to
compensate for harmonics and reactive power in three-phase shunt active filters
[12, 13]. The active filter is expected to provide reactive power compensation
along with harmonic compensation in the case of non-linear reactive loads such as
thyristor converters, ac voltage regulators, etc. in the Icosφ algorithm, the
compensation currents are based on the active part of the load current [1].
Active filters (AFs) [7, 20] in shunt and series configurations can be used to
compensate for different types of nonlinear loads. However, they have the
drawback that their rating is sometimes very close to load (up to 80%) in some
typical applications and thus it becomes a costly option for power quality
improvement in a number of situations. Moreover, a single active filter does not
provide a complete solution for compensation in many cases of nonlinear loads
due to presence of both voltage and current power quality problems. Because of
the higher rating of AFs and cost considerations, the acceptability of AFs by users
has been limited in practical situations. In response to these factors, a series of
hybrid filters has been evolved and extensively used in practice as a cost-effective
solution for the compensation of nonlinear loads. Moreover, these hybrid filters
(HFs) are found to be more effective in providing complete compensation of
various types of nonlinear loads.
2.2.3 HYBRID FILTERS
Hybrid filters are combination of more than one active filter or passive filter. It is
quite popular because the solid state devices used in the active part can be of
reduced size and cost (about 5% of load size).Here, generally, passive filters are
7
used to eliminate lower order harmonics. The higher order harmonic currents,
which are much less compared to lower order harmonics, are eliminated by active
filter. According to research publications on hybrid filters [3], hybrid filters can be
classified based on a number of elements in topology, supply system and types of
converters used in their circuits, as shown in Fig.13.
Fig.2.1: Hybrid filters- Classification
The number of elements in the topology can either be two, three or more, which
may either be active filters or passive filters. The supply system can be single
phase 2 wire, three phase 3 wire or three phase 4 wire to feed variety of nonlinear
loads. Voltage source inverters (VSI) or current source inverters (CSI) can be
used to realise the active filters as part of hybrid filters with appropriate control.
Main classification of hybrid filters is made on the basis of supply system, with
topology of filters as sub-classification.
Control scheme of hybrid filter require a control scheme, which has three major
stages. The first stage includes sensing of instantaneous current and voltage
signals such as AC voltage at the point of common coupling, injected voltages by
series active filter element, AC currents injected by shunt active filter element,
DC bus voltage or current depending on use of VSI or CSI in the implementation
of active filter by means of isolation amplifier or hall effect sensors. Second stage
is derivation of compensating signals. Control techniques based on time domains
8
are simple to implement and result in fast dynamic response due to instantaneous
derivation of compensation commands and nowadays they are only used in hybrid
filters. Many time domain control approaches such as instantaneous p – q theory,
synchronous reference frame theory, synchronous detection method etc. are used
to derive the compensating voltages in the case of series active filter or
compensating currents in the case of shunt active filters. The derived
compensating command signals are compared with sensed feedback signals and
error is processed in PWM controller to generate digital gating signals. These
digital (low/high) gating signals are buffered, isolated and amplified to feed the
gate of the solid state switching devices of active filter used in hybrid filters.
Selection of components of hybrid filters is important to attain high level
performance. There are a number of components in hybrid filters, such as passive
filter elements, active filter elements, control scheme employing sensors,
processor, isolation amplifier circuits, interfacing circuits, injection transformers
etc.
Passive filter consists of several AC capacitors, inductors and a small resistor to
be used in damped high pass filter. These inductors must have a quality factor as
high as possible to reduce the losses in the system and they must be designed in
such a way that they must not saturate in the whole current operating range. In
passive filters, capacitor is decided by the required reactive power in the system,
inductor is calculated by tuning it to particular harmonic frequency. Resistance of
the filter is calculated reducing the losses to optimum value of quality factor.
Another important component in the hybrid filter is the active filter element,
which is realised using VSI with ripple filter on AC side. Solid state switching
device used is a MOSFET for small ratings, an IGBT for medium power ratings
and a GTO for exceptionally high power ratings. Major component is a processor,
which receives the input signals, computes the algorithm and generates optimised
PWM signals. One of the major reasons for the advance of hybrid filter
technology consisting active filter elements is the development of fast self
commutating solid state devices such as MOSFET, IGBT etc. An improved low
cost sensor technology, compact isolation amplifiers and evolution of
9
microelectronics have made hybrid filters affordable. The development of low
cost, high accuracy and fast digital signal processors, microcontrollers and
application specific integrated circuits (ASICs) has made possible the
implementation of complex control algorithms for real time control at an
acceptable price
2.3 CONCLUSION
This chapter gives review of different types of filters used to mitigate distortion
and unbalance in power supply. The earliest type of filters were shunt /series
passive filters connected at PCC which provide a low/high impedance path to the
selected harmonics, preventing most of the selected harmonics from appearing at
the source. But they have drawbacks such as resonance, fixed compensation, high
no load losses, bulky size etc. As a better option of complete compensation of
distortions, active power filters have been researched and developed. Many
mature control algorithms are available in literature for the control of three-phase
active filters. Most of them use tedious computations and complex circuits and
hence highly expensive and slow in response. Hence as a better and economical
option, combination of passive and active filters, named hybrid filters, are
implemented. Hybrid filters allow designing active filters for only a fraction of
total load power, reducing costs and increasing overall system efficiency.
10
CHAPTER III
POWER SYSTEM HARMONICS - SOURCES AND EFFECTS
3.1 INTRODUCTION
Harmonics in power systems have been known since the adoption of alternating
current as means for electrical energy transmission. They have been magnified
with the increased use of non-linear devices. A non-linear device produces a non-
sinusoidal current when applied with a sinusoidal voltage and vive versa. The
harmonic sources can be broadly classified in to major and minor sources. Prior to
the appearance of power semiconductors, the main sources of waveform distortion
were electric arc furnaces, the accumulated effect of fluorescent lamps, and to a
lesser extent electrical machines and transformers. The increasing use of power
electronic devices for the control of power apparatus and systems has been the
reason for the greater concern about waveform distortion in recent times.
3.2 SOURCES OF HARMONICS
The sources of power quality issues can be broadly classified to two categories:
nonlinear loads, power system equipment and components, subsystems of
transmission and distribution systems [15]. In the former category, thyristor
converters, UPS, pulse modulated load, ASDs, arc furnaces, welding machines,
static var compensators, inverters, SMPS, fluorescent and other gas discharge
lighting, etc. In the latter category, grounding systems and resonance problems
can be included. Huge amounts of harmonic currents are generated by single
phase power electronic loads such as desktop computers, TVs, Fax Machines,
Copiers, Microwave ovens, heat pumps and electric vehicle battery chargers, etc.
The switching or commutation of power semiconductor devices generates voltage
or current transients that are characterized by a whole spectrum of frequencies.
During turn on or turn off, sudden collapse of electromagnetic field takes place
and EMI generated.
11
The most common power electronic aid is the single-phase rectifier, used to
power most modern office and domestic appliances. Although the individual
ratings are always small, their combined effect can be an important source of
waveform distortion [14]. The sources of harmonics can be classified as
(1) Traditional types
a. Transformers
b. Rotating machines
c. Arc furnaces
(2) Modern types
a. Fluroscent lamps
b. Thyristor-controlled devices which include
i. Rectifiers
ii. Inverters
iii. Static VAR compensators
iv. Cycloconverters
v. HVDC transmission
3.2.1 TRANSFORMER
Power transformers are sources of harmonics since they use magnetic materials
that are operated very close to and often in the non-linear region for economic
purposes. This result in the transformer magnetizing current being non-sinusoidal
and containing harmonics (mainly third harmonics) even if the applied voltage
were sinusoidal. In the three-phase transformers a delta or ungrounded wye
connection blocks the flow of zero sequence triplen harmonics currents.
3.2.2 ROTATING MACHINES
Rotating machines are considered as sources of harmonics because the windings
are embedded in slots which can never be exactly sinusoidal distributed so that the
mmf is distorted. Large generators are usually connected to power grid through
delta-connected transformers thus blocking the flow of third harmonic current.
Generally, harmonics produced by rotating machines are considered negligible
compared to those produced by other sources.
12
3.2.3 ARC FURNACES
The voltage-current characteristics of electric arcs are highly nonlinear. Following
arc ignition the voltage decreases due to the short-circuit current, the value of
which is only limited by the power system impedance. The main harmonic
sources in this category are the electric arc furnace, discharge type lighting with
magnetic ballasts, and to a lesser extent arc welders.
3.2.4 FLUORESCENT LIGHTS
In a fluorescent lamp, the voltage builds up in each half cycle till ignition occurs.
The lamp then appears as a negative resistance, the current limited by the non-
linear reactive ballast. The current is thus distorted.
3.2.5 STATIC VAR COMPENSATORS
Static VAR compensators are balanced three-phase devices that use SCR’s to
control the conduction time of shunt capacitors or inductors during each half cycle
in order to maintain a desired terminal voltage. Thus, non sinusoidal “chopped ”
currents are produced.
3.2.6 CYCLOCONVERTERS
A cycloconverter is a variable frequency a.c. motor drive composed of two three-
phase bridges supplying a single-phase output. It converts ac power at a higher
frequency to one at a lower frequency. With a line frequency of 50 Hz, the
cycloconverter output frequency can be varied from 0 to 10 Hz. The speed of
cycloconverter-driven large slow-speed synchronous motors can be continuously
varied between zero and 15 rpm.
3.3 EFFECTS OF HARMONIC DISTORTION
The main effects of voltage and current harmonics within the power system are:
• the failure of capacitor banks due to dielectric breakdown or reactive power
overload
13
• interference with ripple control and power line carrier systems
• causing mis-operation of systems which accomplish remote switching, load
control and metering
• dielectric breakdown of insulated cables resulting from harmonic over
voltages
• inductive interference with communications systems
• errors in meter reading
• signal interference and relay malfunction particularly in solid state and
microprocessor based control systems
• mechanical oscillations of induction and synchronous machines
• unstable operation of firing circuits based on zero crossing detecting or
latching
• excessive heating of transformers due to frequency dependent core
• change in TV picture size and brightness if harmonics affect the peak
voltage
• effects on computer and computerised automation production.
Among the possible external effects of harmonics are degradation in
communication systems performance, excessive audible noise and harmonic-
induced voltage and currents. Harmonics have the effect of increasing equipment
losses and thus the thermal stress.
3.3.1 THERMAL LOSSES IN A HARMONIC ENVIRONMENT
Harmonics have the effect of increasing equipment copper, iron and dielectric
losses and thus the thermal stress. The per unit increase in copper loss is
determined by the current distortion factor alternatively voltage distortion factor
both being equal for pure resistance. Iron Losses are those losses taking place in
an iron core which is magnetized by an applied excitation or by rotating in a
magnetic field. These losses consist of hysteresis loss and eddy current loss and
result in reducing the efficiency and increasing the core temperature thus limiting
the output. Hysteresis loss is due to reversal of magnetization of an iron core and
depends on the volume and quality of used magnetic material, maximum value of
flux density and frequency of electric current. Eddy current loss is associated with
14
flow of eddy current induced in the armature core of a rotating machine as a result
of its rotation in the magnetic field or in the core of a transformer as a result of ac
excitation. The dielectric loss in a capacitor or insulation loss in a cable is due to
the fact that it is not an ideal capacitor whose current leads the voltage by a factor
of 90o.
3.3.2 RESONANCES
The presence of capacitors, such as those used for power factor correction, can
result in local system resonances, which lead in turn to excessive currents and
possibly subsequent damage to the capacitors. Parallel resonance results in high impedance at the resonant frequency being
presented to the harmonic source. Parallel resonances can occur in a variety of
ways, the simplest perhaps being that where a capacitor is connected to the same
busbar as the harmonic source. A parallel resonance can then occur between the
system impedance and the capacitor.
The concern with series resonance is that high capacitor currents can flow for
relatively small harmonic voltages.
3.3.3 EFFECTS OF HARMONICS ON ROTATING MACHINES
Non-sinusoidal voltages applied to electrical machines may cause overheating.
Motors are not normally derated so long as the harmonic distortion remains within
the 5% normally recommended by the regulations. Above that limit they will
often experience excessive heating problems.
Harmonic voltages or currents give rise to additional losses in the stator windings,
rotor circuits, and stator and rotor laminations. The losses in the stator and rotor
conductors are greater than those associated with the d.c. resistances because of
eddy currents and skin effect.
The effects of harmonics on various power system equipments are discussed
in [14]. The oscillatory transient can lead to transient over voltage and consequent
damage to power line insulators. Short duration voltage variations such as voltage
sags or voltage swells can cause loss of production in automated processes.
Voltage imbalance can cause temperature rise in motors and can even cause a
15
large motor to trip. Inter-harmonic voltages can upset the operation of fluorescent
lamps and television receivers. DC offsets can cause saturation in the power
transformer magnetic circuits. A notch can damage capacitive components
connected in shunt due to high rate of voltage rise at the notches. Voltage flickers
may adversely effect human health as the high frequency flickering of light bulbs,
fluorescent tubes or television screen can cause strain on the eyes resulting in
headache and migraine. The voltage flicker can also reduce the lifespan of
electronic equipment, lamps etc.
3.4 CONCLUSION
Harmonic sources in power system and their effects are studied.
16
CHAPTER IV
POWER SYSTEM HARMONICS - MITIGATION
TECHNIQUES
4.1 POWER QUALITY IMPROVEMENT TECHNIQUES
The power quality improvement techniques can be classified into precautionary
(preventive) solutions and corrective (remedial solutions).Phase cancellation or
harmonic control in power converters, usage of low distortion loads etc. are
preventive solutions. Usage of harmonic filters for elimination of harmonics and
unbalance are corrective solutions. Harmonic elimination is done commonly using
passive and active filter. The combination of active and passive filter is known as
hybrid filer.
4.2 PASSIVE FILTERS
The passive filter consists of capacitors and inductors which are connected in
shunt with power system. The passive filter is tuned to a desired frequency which
is to be filtered out from the power system. At resonance condition, tuned
frequency components will be bypassed. Conventionally tuned passive LC filters
have been used to compensate a portion of reactive power and harmonics in
power system. A number of configurations are suggested such as single tuned,
double tuned, triple tuned, quadruple tuned, damped, auto tuned etc. Series
passive filters are required to prevent a particular component from entering
selected plant components or parts of a power system which offers large
impedance to the relevant frequency component. Shunt passive filters offer very
low impedance to the harmonic frequencies and prevents from entering rest of the
system. The sharpness of tuning of filter is denoted by Q-factor. For tuned filters,
Q-factor is recommended in the range 30 – 60 and for damped filters it is 0.5 -
5.But variations in filter capacitance and inductance due to ageing and
temperature, may cause detuning from nominal tuned frequency. Passive filter
are of various configuration which explained below.
17
4.2.1 SINGLE TUNED FILTERS
A single tuned filter is a series RLC circuit in Figure 1 tuned to the frequency of
one harmonic (generally a lower characteristic harmonic). Its impedance is given
by Z 1= R+ j (ωL -1/ ωC) and which at the resonant frequency (fn) reduces to R.
There are two basic design parameters to be considered prior to the selection of R,
L and C. These are the quality factor (Q), and the relative frequency deviation (δ),
already defined.
In order to express the filter impedance in terms of Q and δ, the following
relationships apply:
ω= ωn(1 + δ) , where ωn=1/√ (LC). The reactance of inductor or capacitor in ohms
at the tuned frequency is X0= ωnL=1/(ωnC).
4.2.2 DOUBLE-TUNED FILTERS
Double tuned filter have the advantage of reducing the power loss at fundamental
frequency and recommended for high voltage applications, because of the
reduction in number of inductors subjected to full line impulse voltages and
shown in Fig.1.
Fig.4.1: Transformation from (a) two single tuned filters to (b) double tuned filters
(c) the impedance versus frequency of filter double tuned for 5th and 7th.
4.2.3 AUTOMATICALLY TUNED FILTERS
Automatically tuned filters use a control system to measure reactive power and
hence control the value of inductance and capacitance based on sign and
magnitude of reactive power. In tuned filter design it is advantageous to reduce
18
the maximum frequency deviation. This can be achieved by making the filters
tunable by either automatically switching the capacitance or by
varying the inductance. A range of ±5% is usually considered adequate. It has
advantages such as low inductor rating and small capacitor rating.
4.2.4 DAMPED FILTERS
For filtering a range of harmonic frequencies, damped filters are recommended,
which is shown in Fig4.2. The damped filter offers several advantages:
(1) Its performance and loading are less sensitive to temperature variation,
frequency deviation, component manufacturing tolerances, loss of capacitor
elements, etc.
(2) It provides low impedance for a wide spectrum of harmonics without the need
for subdivision of parallel branches, which increases switching and maintenance
problems.
(3) The use of tuned filters often results in parallel resonance between the filter
and system admittances at a harmonic order below the lower tuned filter
frequency, or in between tuned filter frequencies. In such cases the use of one or
more damped filters is a more acceptable alternative.
Fig 4.2: High pass damped filters: (a) first order (b) second order (c) third order
(d) C-type
The main disadvantages of the damped filter are as follows:
(4) To achieve a similar level of filtering performance the damped filter needs to
be designed for higher fundamental VA ratings, though in most cases a good
performance can be met within the limits required for power factor correction.
(5) The losses in the resistor and reactor are generally higher.
19
4.3 ACTIVE FILTER
Practically passive filters suffer from drawbacks as dependence of filtering
characteristics on source impedance, detuning, parallel/series resonance between
power system, high no load losses, bulky size and fixed compensation. It cannot
solve random variations in the load current waveform. To overcome the
difficulties explained with the passive filters, active filters have been developed,
which provide dynamic and adjustable solutions to power quality issues. Active
filters compensate harmonic components of load current by injecting equal but
opposite harmonics i.e. mains only need to supply the fundamental component of
load current. The design complexity and high cost of losses of the conventional
passive filters, as well as their restricted capability to eliminate inter-harmonics
and non-characteristic harmonics, has encouraged the development of harmonic
compensation by means of power electronic devices, and commonly referred to as
active filters.
These active filter circuitries have been developed employing modern fast
switching power devices with turn off capability like insulated gate bipolar
transistors (IGBTs). The converters commonly used in active filters are current
fed PWM modulation inverter and voltage fed PWM inverter, which is shown in
Figure 4.3. Voltage fed PWM inverter is more dominant, since it is lighter,
cheaper and expandable to multilevel and multistep versions, to enhance the
performance with lower switching frequencies.
Fig 4.3(a): Voltage fed PWM inverter Fig 4.3(b): Current fed PWM inverter
20
According to their connection to the network, active filters can be of the series
type, as shown in figure 4.4 (a), to prevent the transfer of harmonic current, or of
the shunt type, shown in Figure 4.4(b), to reduce the harmonic content in the
network.
Fig 4.4 (a) Series Active filter Fig 4.4 (b): Shunt Active filter
4.3.1 SERIES ACTIVE FILTER An active series filter is connected in series with the mains using a matching
transformer to eliminate voltage harmonics and to balance and regulate terminal
voltage of the load or line and shown in Fig 4.4(a). It also helps to damp out
harmonic propagation caused by resonance with line impedance and passive shunt
compensators. Series active filters are less common industrially than parallel
active filters. It is because of the main drawback of series circuits, that they have
to handle high load currents, which increases their current rating considerably.
This category of filters are mainly used to improve the quality of system voltage,
which is important for voltage sensitive devices such as superconducting magnetic
energy storage and power system protection devices.
4.3.2 SHUNT ACTIVE FILTER
Shunt active filters have the advantage of carrying only the compensation current
plus a small amount of active fundamental current supplied to compensate system
losses and shown in Fig 4.4(b). They can be made suitable for a wide range of
power ratings, by connecting several filters in parallel to supply higher currents.
21
Shunt active filters can be again subdivided into standard inverter, switched
capacitor, lattice structured and voltage regulator filters.
4.3.3 CONTROL ALGORITHM
The active filtering algorithm computes the reference compensation signals to be
generated by the active power filter (APF) to provide reactive power / harmonic /
unbalance compensation. The choice of the control algorithm therefore decides
the accuracy and the speed of response of the filter. The calculation steps involved
in the control technique have to be simple and minimal to make the control circuit
compact and reliable. Instantaneous PQ theory [8], synchronous detection
algorithm [9], DC bus voltage algorithm [10], synchronous reference frame theory
[11] etc. are some of the widely used three-phase active filtering algorithms.
4.3.3.1 INSTANTANEOUS PQ THEORY
In this algorithm proposed by Akagi [8], the three phase mains voltages and load
currents of the system are sensed and converted into the α − β (two) phase plane
using Park’s transformation.
Where ea, eb, ec are the three phase mains voltages.
where iLa, iLb, iLc are the three-phase load currents.
The instantaneous real power pL and the instantaneous imaginary power
consumed by load current are derived as,
where pL and qL contain a DC term and an AC term.
22
They can be represented as,
For harmonic elimination and reactive power compensation, the ripple in the real
power and the whole of reactive power are to be supplied by the active filter. The
reference compensation currents are therefore derived as,
Applying inverse Park’s transformation on the above signals gives the reference
compensation currents in the three-phases as,
Fig 4.5: Block diagram for implementing Instantaneous PQ theory
4.3.3.2 SYNCHRONOUS DETECTION ALGORITHM
The synchronous detection algorithm [9] computes the loading on individual
phases of the system, from the three phase mains voltages and load currents as:
23
The average value of ‘P’ then computed as Pdc, by passing ‘P’ through a low pass
filter. Pdc is divided among the three phases of the system as:
where Ea, Eb, Ec are the amplitude three phase main voltages and Etot is the sum
Ea, Eb, Ec.
With objective of achieving unity power factor at the source end, the desired
mains currents in the three phases are computed as:
The reference compensation signals are therefore the differences between the
desired mains currents and the actual load currents. i.e.
i *ca= ima−iLa; i*cb= imb−iLb ;
i *cc= imc−iLc
Fig.4.6: Block diagram for implementing Synchronous Detection Algorithm
24
4.3.3.3 DC BUS VOLTAGE ALGORITHM
The DC Bus Voltage Algorithm [10] is based on the idea that active power filter
forces the mains current to be sinusoidal and in phase with the main voltage, in
spite of the load characteristics. The magnitude of the mains current is related to
the power balance in the system. Any power unbalance affects the average voltage
of the DC link capacitor of the inverter. The change in the average voltage of the
DC link capacitor from its set value is fed to PI controller, whose output gives the
corresponding amplitude of the desired mains currents. The output of the PI
controller is multiplied with unit amplitude sinusoidal reference waves in phase
with the mains voltage, in order to get the desired mains currents. The actual
mains currents are detected and compared with desired values at a current mode
controller to generate the switching patterns for the APF.
Fig.4.7: Block diagram for implementing DC Bus Voltage Algorithm
25
4.3.3.4 Icosφ ALGORITHM
In the Icosφ algorithm [1], the desired mains current is assumed to be the product
of the magnitude Icosφ and a unit amplitude sinusoidal wave in phase with the
mains voltage. The source is required to supply only the active portion of the load
current as the shunt active power filter is expected to provide compensation for
the harmonic and reactive portion of the three-phase load current, and also for any
imbalance in the three-phase load currents. Hence, only balanced currents will be
drawn from the mains which will be purely sinusoidal and in phase with the mains
voltages. Fig 4.8 gives the block diagram for implementing the algorithm.
The reference compensation currents for the shunt active filter are thereby
deduced as the difference between the actual load current and the desired source
current in each phase. i.e.
where, the desired (reference) source currents in the three phases are given as,
Ua, Ub and Uc are the unit amplitude templates of the phase to ground source
voltages in the three phases respectively where
26
Fig 4.8: Basic block diagram of Icosφ algorithm
For any phase load current can be written as, imsin(wt-φ). Fundamental component
of load current is getting after low pass filtering operation. Low pass filtering is
done using biquad filter and its output is fundamental component of load current
which is 90° phase shifted and so fundamental form can be written as imsin(wt –
φ- 90o). At the time of the zero crossing of the input voltage ωt becomes 180° and
fundamental component of load current at that time becomes Icosφ. This value is
the magnitude of active component of load current.
However, the rating of active filters is very close to load (up to 80%) and
hence cost of shunt active filters is high and they are difficult to implement in
large scale. Additionally, the efficiency of active filter is determined by its control
algorithm. The above reasons led to different solutions to improve the practical
utilisation of active filters. One of them is to use a combined system of passive
filters and active filters as hybrid filters.
27
4.4 HYBRID FILTER
Hybrid filters are combination of more than one active filter or passive filter. It is
quite popular because the solid state devices used in the active part can be of
reduced size and cost (about 5% of load size).Here, generally, passive filters are
used to eliminate lower order harmonics. The higher order harmonic currents,
which are much less compared to lower order harmonics are eliminated by active
filter. Hybrid filters allow designing active filters for only a fraction of total load
power, reducing costs and increasing overall system efficiency. Figure 4.9 shows
the basic set up of hybrid filter.
Fig 4.9: Basic set up of three phase shunt hybrid filter.
The number of elements in the topology can either be two, three or more, which
may either be active filters or passive filters. The supply system can be single
phase 2 wire, three phase 3 wire or three phase 4 wire to feed variety of nonlinear
28
loads. Voltage source inverters (VSI) or current source inverters (CSI) can be
used to realise the active filters as part of hybrid filters with appropriate control.
Main classification of hybrid filters is made on the basis of supply system, with
topology of filters as sub-classification.
Each category of above hybrid configurations can be classified to
(i) hybrid of two passive elements
(ii) hybrid of three passive elements
(iii) hybrid of one active and one passive filter
(iv) hybrid of three elements- two passive with one active
(v) one passive with two active filter elements
(vi) hybrid of two active elements
(vii) hybrid of three active filter elements
The hybrid filters of more than three elements are rarely used because of cost and
complexity considerations
Control scheme of hybrid filter require a control scheme, which has three major
stages. The first stage includes sensing of instantaneous current and voltage
signals such as AC voltage at the point of common coupling, injected voltages by
series active filter element, AC currents injected by shunt active filter element,
DC bus voltage or current depending on use of VSI or CSI in the implementation
of active filter by means of isolation amplifier or hall effect sensors. Second stage
is derivation of compensating signals.
Control techniques based on time domains are simple to implement and result in
fast dynamic response due to instantaneous derivation of compensation
commands and nowadays they are only used in hybrid filters. Many time domain
control approaches such as instantaneous p – q theory, synchronous reference
frame theory, synchronous detection method etc. are used to derive the
compensating voltages in the case of series active filter or compensating currents
in the case of shunt active filters. The derived compensating command signals are
compared with sensed feedback signals and error is processed in PWM controller
to generate digital gating signals. These gating signals are buffered, isolated and
amplified to feed the gate of the solid state switching devices of active filter used
in hybrid filters. Selection of components of hybrid filters is important to attain
29
high level performance. There are a number of components in hybrid filters, such
as passive filter elements, active filter elements, control scheme employing
sensors, processor, isolation amplifier circuits, interfacing circuits, injection
transformers etc.
4.5 CONCLUSION
Harmonic mitigation techniques are studied. Active filters can be discussed as a
well-established means of mitigation techniques of power quality problems in
retrofit systems even though rating and cost is high. This drawback is usually
solved by using a hybrid filter which used conventional tuned passive filters in
conjunction with the active filters so that the dominant lower order harmonics are
eliminated by passive filters. The remaining harmonics are compensated by the
active filter.
30
CHAPTER V
COMPARISON OF ACTIVE FILTER ALGORITHMS –
SIMULATION RESULTS
5.1 INTRODUCTION
The active filtering algorithm computes the reference compensation signals to be
generated by the active power filter (APF) to provide reactive power / harmonic /
unbalance compensation. The choice of the control algorithm therefore decides
the accuracy and the speed of response of the filter. Instantaneous PQ theory [8],
synchronous detection algorithm [9], DC bus voltage algorithm [10], Icosφ
algorithm [1] etc. are some of the widely used three-phase active filtering
algorithms.
Simulation is a simple and inexpensive way of checking the validity of any design
or concept before actually building a hardware prototype. MATLAB from
mathworks Inc. [19] is the one of the mostly used simulation packages.
MATLAB/SIMULINK is the main simulation part of this multi domain software
package. Simulink has become the most widely used software package for
modeling and simulating dynamic systems. It includes block sets specific to
power systems, control systems, mechanical systems and mathematical systems.
SimPowerSystem is the toolbox used for simulation of power system. It includes a
vast library of all the elements, machines, voltage sources, measurements and
power electronic components used in any power system. It also includes a huge
collection of demos on the state-of-the-art techniques used in power systems.
5.2 SIMULATION MODEL REQUIREMENTS
The three-phase system to be modeled in simulation consists of the following
components/ subsystems.
1. A three phase, three wire symmetrical, balanced, ac voltage supply with
source impedance
2. A three-phase fully controller thyristor bridge rectifier feeding RL load
31
3. A three-phase voltage source inverter (VSI) of suitable rating to act as the
shunt active filter with suitable value of DC link capacitance based on the
design.
4. Three-phase reactance with appropriate design
5. Voltage sensors for sensing the phase voltage in each phase. Current sensors
for sensing the load current and source current in each phase.
6. Computation of reference compensation current.
7. Generation of firing pulses for the active filter devices
The figure 5.1 shows the basic set up to be implemented in simulation.
Fig. 5.1: Basic block diagram for the implementation of shunt active filter.
The three phase inductive source block is being used for a three phase source with
suitable source impedance. The universal bridge block can be programmed as a
controlled or uncontrolled converter is being used as a non linear load. The
32
synchronized six pulse generator is used as the firing circuit block for the non
linear load where firing angle α can be suitably selected for the required mode of
operation.
5.3 SIMULATION OF THE FULL CONTROLLED CONVERTER
FEEDING AN RL LOAD WITHOUT SHUNT ACTIVE POWER FILTER
A full controlled converter can be operated for different values of triggering angle
α. For simulation, 15 kW RL load is considered. Resistance value (R) is
calculated as 20Ω and inductance value (L) is 80mH. Source and line impedance
(Ls) become 0.5633 and 1.83mH respectively.
The figure 5.2 shows Matlab simulation model. Figure 5.3 to 5.6 shows
waveforms of source voltage, source current, load current and %THD in source
current for different firing angles of thyristor converter load.
Fig 5.2: Basic block diagram for full controlled converter feeding an RL load.
Case A: at α =0°
When triggering angle α is zero thyristor converter will act as a diode bridge
rectifier. The waveform obtained from simulation shows that source current is
contaminated with lots of harmonics. From source current spectrum it can be
found that %THD is 18.45.
33
Fig 5.3: Source voltage, load current, source current in phase A at α=0° without
filter
Fig 5.4: Source current spectrum at α=0° without filter.
34
Case B: at α=30°
When triggering angle increases to 30°, total harmonic distortion also increases to
25.91 %. This means that when α increase, current waveform will be
contaminated with more harmonic contents.
Fig 5.5: Source voltage, load current, source current in phase A at α=30° without
filter.
Fig 5.6: Source current spectrum at α=30° without filter.
35
5.4 SIMULATION OF SHUNT ACTIVE FILTER UNDER BALANCED
SOURCE AND BALANCED LOAD CONDITIONS
A balanced source is one that provides balanced sinusoidal voltages in the three
phases that are equal in magnitude and displaced exactly by 1200 in phase from
each other. The supply currents
will be balanced but wave shape will be depending on the type of load ,the source
is connected to. The three phase load is said to be balanced when the three phase
currents drawn from the supply are equal. Figure 5.5 to 5.8 shows waveforms of
source voltage, source current, load current and %THD in source current for
different firing angles of thyristor converter load.
5.4.1 SIMULATION OF INSTANTANEOUS PQ THEORY
The system considered for simulation is a three phase source supplying a three
phase on-linear load, which under normal conditions draws harmonic-rich
balanced three phase currents. A three phase, VSI based shunt active power filter
is connected through a large inductance to the system for compensating for
harmonics and reactive power required by the load, so the source will be
supplying only sinusoidal currents.
A 230V, 50 Hz balanced three phase source with suitable source impedance and a
thyristor converter feeding an R-L load is chosen as the non-linear load. The firing
angle α can be varied as required.
The simulation is done for two different load conditions:
Three phase diode rectifier feeding a resistance.
Three phase thyristor controlled converter feeding a resistance(α=30o,
α=60o)
The simulation circuit for the diode rectifier load is given in Figure 5.7. The
thyristor converter load block with firing angle set to 0o acts as the diode rectifier.
The reference compensation signals are generated by Instantaneous PQ control
scheme. This controller uses 10 multipliers and 2 divider blocks in addition to the
Park’s transformation blocks for the generation of the compensation signals. The
36
three phase main voltages “eabc” and the load currents “iLabc” are sensed and
passed through Park’s transformation block to yield e(αβ) and IL(αβ) respectively.
From e(αβ) and IL(αβ), the instantaneous values of real power and imaginary power
are derived. These are then split in to their DC and AC terms. The ripple in real
power and whole of imaginary power are used to generate ic(αβ) signals to inverse
Park’s transformation block.
Figure 5.8 to 5.11 shows waveforms of source voltage, source current, load
current and %THD in source current for different firing angles of thyristor
converter load.
Fig 5.7: Basic setup for shunt active filtering with controller.
Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became almost pure sine wave i.e., harmonic currents needed
by converter is provided by shunt active filter. Now source has to supply only real
component of load current and remaining reactive components and harmonics
required by the load current is supplied by shunt active filter. The total harmonic
37
distortion without controller at α =0° is 18.45 % and with controller it is reduced
to 3.40%.i.e. THD value is within the allowable limit.
Fig 5.8: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using IRPT control algorithm.
Fig 5.9: Source current spectrum at α=0° with Instantaneous PQ theory.
38
Case B: at α =30°
Total harmonic distortion with controller at α=30° is 9.60% whereas without
controller it was 25.91 %. Very clearly, this value is not with in IEEE standards
Fig 5.10: Source voltage, load current, source current in phase A at α=30° with
Active Power Filter using IRPT control algorithm
Fig 5.11: Source current spectrum at α=30° with Instantaneous Reactive PQ
theory.
39
LIMITATIONS OF IRPT
This algorithm involves complex calculations and complicated circuitry. The
IRPT controller uses 10 multiplier and 2 divider blocks in addition to the park’s
transformation blocks for the generation of compensation currents. But this
approach is applicable only for balanced three phase system and source voltage
waveform is a pure sine wave.
5.4.2 SIMULATION OF THE SYNCHRONOUS DETECTION
ALGORITHM
The controller consists of 6 multipliers in addition to the low pass filter and power
distributor blocks. The real power drawn from the three phases is calculated from
Ea, Eb, Ec and ILa, ILb, ILc signals. The real power is sent to a low pass filter to
obtain its average value Pdc. The average power is divided equally among the
three phases. The desired main currents are derived from the average power. The
active filter reference currents are then calculated as difference between the main
currents and the actual load currents using comparator block. Figure 5.12 to 5.15
shows waveforms of source voltage, source current, load current and %THD in
source current for different firing angles of thyristor converter load.
Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., harmonic currents needed by converter
is provided by shunt active filter. Now source has to supply only real component
of load current and remaining reactive components and harmonics required by the
load current is supplied by shunt active filter. The total harmonic distortion
without controller at α =0° is 18.45 % and with controller it is reduced to
1.30%.i.e. THD value is within the allowable limit.
40
Fig 5.12: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using Synchronous Detection algorithm
Fig 5.13: Source current spectrum at α=0° with Synchronous Detection algorithm
41
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 1.49% whereas without
controller it was 25.91 % and source current became pure sine wave in phase with
source voltage.
Fig 5.14: Source voltage, load current, source current in phase A at α=30° with
Active Power Filter using Synchronous Detection algorithm
Fig 5.15: Source current spectrum at α=30° with Synchronous Detection
algorithm
42
LIMITATIONS OF SD ALGORITHM:
The control circuit consists of 6 multiplier blocks in addition to low pass filter and
power distribution blocks. But it suffers from the drawbacks such as (i)
effectiveness of the algorithm depends on harmonic contents in voltage signal (ii)
assumption is made that three phase currents are balanced.
.
5.4.3 SIMULATION OF THE DC BUS VOLTAGE ALGORITHM
The three phase source voltages and currents are sampled and the unit vectors
required for generating the reference currents is derived from the source voltage
signals after filtering and processing of those signals. The error between the reference
DC bus voltage and the actual DC bus voltage is found and it is passed through a PI
controller to generate the amplitude of the desired mains current. The unit vectors
obtained is then multiplied with the amplitude of the desired mains current to
generate the three phase reference mains currents. These reference mains currents act
as one of the inputs to the hysteresis controller and the other input to it is the actual
mains current. The switching gate pulses are generated on comparison of these two
inputs. . Figure 5.16 to 5.19 shows waveforms of source voltage, source current,
load current and %THD in source current for different firing angles of thyristor
converter load.
Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., harmonic currents needed by converter
is provided by shunt active filter. Now source has to supply only real component
of load current and remaining reactive components and harmonics required by the
load current is supplied by shunt active filter. The total harmonic distortion
without controller at α =0° is 18.45 % and with controller it is reduced to
1.80%.i.e. THD value is within the allowable limit.
43
Fig 5.16: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using DC Bus Voltage algorithm
Fig 5.17: Source current spectrum at α=0° with DC Bus Voltage algorithm
44
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 2.79% whereas without
controller it was 25.91 % and source current became pure sine wave in phase with
source voltage.
Fig 5.18: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using DC Bus Voltage algorithm
Fig 5.19: Source current spectrum at α=30° with DC Bus Voltage algorithm
45
5.4.4 SIMULATION OF Icosφ ALGORITHM
In MATLAB/SIMULINK model, the three phase V-I measurement block is used
to measure the three phase voltage and load current. Low pass filter gives
fundamental component of load current which is 90° phase shifted. Unit
amplitude sine wave is produced in phase with respective phase voltages. At the
time of zero crossing of the phase voltages, using sample and hold circuit, Icosφ
value is extracted. The desired source current is computed, using product block,
after multiplication of unit amplitude sine wave with Icosφ value. Reference
compensation currents are computed as the difference between the actual load
currents and desired source currents using subtractor blocks. The actual filter
output currents and reference compensation currents are fed to a hysteresis
controller block with a suitable hysteresis band to generate the firing signals for
the active power filter devices. Figure 5.20 to 5.23 shows waveforms of source
voltage, source current, load current and %THD in source current for different
firing angles of thyristor converter load.
Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., harmonic currents needed by converter
is provided by shunt active filter. Now source has to supply only real component
of load current and remaining reactive components and harmonics required by the
load current is supplied by shunt active filter. The total harmonic distortion
without controller at α =0° is 18.45 % and with controller it is reduced to
0.91%.i.e. THD value is within the allowable limit.
46
Fig 5.20: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using with Icosφ algorithm
Fig 5.21: Source current spectrum at α=0° with Icosφ algorithm
47
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 1.29% whereas without
controller it was 25.91 % and source current became pure sine wave in phase with
source voltage. For unbalanced source, the total THD is reduced from 25.5% to
1.42%.
Fig 5.22: Source voltage, load current, source current in phase A at α=30° with
Active Power Filter using with Icosφ algorithm
Fig 5.23: Source current spectrum at α=30° with Icosφ algorithm
48
Table 5.1: %THD in the mains currents before and after shunt compensation
for two firing angles α=0° and α=30°
α=0° α=30°
Without APF
18.45% 25.91%
With
APF
IRPT 3.40% 9.60%
Synchronous
Detection 1.30% 1.49%
DC Bus Voltage
Algorithm 1.80% 2.79%
Icosφ Algorithm 0.91% 1.29%
5.5 SIMULATION OF SHUNT ACTIVE FILTER USING Icosφ
ALGORITHM UNDER BALANCED/UNBALANCED SOURCE AND
BALANCED/UNBALANCED LOAD CONDITIONS
An unbalanced source used is one in which a 30% amplitude unbalance is
introduced in phases a, b and c, respectively. The unbalance is reflected on the
load currents in the three phases too. However, the active filter is expected to
balance the three phase source currents effectively.
Figure 5.24 to 5.27 shows waveforms of source voltage, source current, load
current and %THD in source current for different firing angles of thyristor
converter load under unbalanced source and balanced load conditions.
49
Case A: at α =0°.
Fig 5.24: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using with IcosΦ algorithm
Fig 5.25: Source current spectrum at α=0° with Icosφ algorithm for unbalanced
source and balanced load condition
50
Case B: at α =30°
For unbalanced source and balanced load condition, the total THD is reduced
from 25.5% to 1.34%.
Fig 5.26: Source voltage, load current, source current in phase A at α=30° with
Active Power Filter using with IcosΦ algorithm
Fig 5.27: Source current spectrum at α=30° for unbalanced source and balanced
load condition
51
5.6 SIMULATION OF SHUNT ACTIVE FILTER USING Icosφ
ALGORITHM UNDER BALANCED SOURCE AND UNBALANCED
LOAD CONDITIONS
An unbalance in load is introduced by connecting three different resistances of
100 Ω, 150 Ω and 50 Ω values in series with a, b and c phase voltage sources on
the AC side of the non linear load.
Figure 5.28 to 5.31 shows waveforms of source voltage, source current, load
current and %THD in source current for different firing angles of thyristor
converter load under balanced source and unbalanced load conditions. Table 1.2
compares the %THD values of the main current for both types of load conditions
when shunt compensation is provided by Icosφ control schemes.
Case A: at α =0°.
In the IcosΦ algorithm, the unbalance in load is taken care of in the determination
of the reference compensation currents itself. The magnitudes of the active
portions of the fundamental load current in the three phases are detected and
average of these values is taken as the amplitude of the desired mains current.
This makes sure that the magnitudes of the desird source currents in all the three
phases remain the same even in case of load unbalance. the total THD is reduced
from 25.5% to 1.27%.
Fig 5.28: Source voltage, load current, source current in phase A at α=0° with
Active Power Filter using with Icosφ algorithm
52
Fig 5.29: Source current spectrum at α=0° with Icosφ algorithm for balanced
source and unbalanced load condition
Case B: at α =30°
For balanced source and unbalanced load codition, the total THD is reduced from
25.5% to 1.88%.
Fig 5.30: Source voltage, load current, source current in phase A at α=30° with
Active Power Filter using with Icosφ algorithm
53
Fig 5.31: Source current spectrum at α=30° with Icosφ algorithm for balanced
source and unbalanced load condition
Table 5.2: %THD in the mains currents before and after shunt compensation
under Balanced/ Unbalanced Source and Balanced/unbalanced Load
Conditions using Icosφ algorithm
Conditions α =0° α =30°
Without APF(THD in
source current)
With
APF
(THD
in
source
current)
Without APF(THD in
source current)
With
APF(THD
in source
current)
Phase
a
Phase
b
Phase
c
Phase
a
Phase
b`
Phase
c
Balanced
Source
27.81% 27.87 27.77% 0.91% 28.37% 28.50% 28.53% 1.29%
Unbalanced
source
24.81% 23.9% 33.17% 0.92% 27.08% 24.37% 36.58% 1.34%
Unbalanced
load
16.13% 20.63% 16.84% 1.27% 33.2% 29.85% 27.06% 1.86%
54
5.7 CONCLUSION
From the simulation results, it can be seen that Icosφ algorithm has been more
effective than other three schemes for shunt active value filtering. It has been
found to yield comparable or rather marginally better results as compared to the
existing algorithms in addition to being simpler than other algorithms.
Icosφ algorithm has been simulated under conditions generally prevailing in three
phase system such as a balanced three- phase voltage supply feeding a balanced
non-linear load, an unbalanced supply feeding a balanced non-linear load and a
balanced three-phase supply feeding an unbalanced load. Here also, Icosφ
algorithm made the source currents to be balanced, sinusoidal and unity power
factor currents. The source current THD% has been brought down to best value in
the case of Icosφ algorithm, which is very much with in the levels set by IEEE
standards.
The source current THD% has been brought down to a value ≤3% with the
individual harmonics less than 2%, in the case of Icosφ algorithm, which is very
much with in the levels set by IEEE standards. Hence Icosφ algorithm is the
control algorithm for the active filter used in implementing the hybrid filter.
55
CHAPTER VI
SIMULATION OF HYBRID POWER FILTER
6.1 INTRODUCTION
Hybrid active filters inherit the efficiency of passive filters and the improved
performance of active filters, and thus constitute a viable improved approach for
harmonic compensation. Active filters were developed to mitigate problems of
passive filters. They are more effective in harmonic compensation and improved
performance. But pure active filters are highly expensive and require
comparatively high power converter ratings. Hybrid filters, combination of both
passive filters and active filters, provide improved performance and cost-effective
solutions. Both the active filter and passive filters are connected in parallel with
the non-linear load, together contributes for harmonic and reactive compensation.
This topology lends itself to retrofit applications with existing passive filters.
6.2 SIMULATION OF THE FULL CONTROLLED CONVERTER
FEEDING AN RL LOAD WITHOUT FILTER
A fully controlled thyristor converter can be operated for different values of
triggering angle α. For simulation, a full controlled converter feeding 15 kW RL
load is considered. Resistance value (R) is calculated as 20Ω and inductance value
(L) is 80mH. Source and line impedance can be assumed as 0.08 p u and thus
source resistance (Rs) and source impedance (Ls) become 0.5633 Ω and 1.83mH
respectively.
Fig 6.1: Basic simulation setup for full controlled converter feeding an RL load.
56
The figure 6.1 is the basic set up for simulation. Figure 6.2 shows waveforms of
source voltage, source current, load current and figure 6.3 shows %THD in source
current for firing angle α =0° of thyristor converter load.
Case A: at α = 0°
When triggering angle α is zero thyristor converter will act as a diode bridge
rectifier. The waveform obtained from simulation shows that source current is
contaminated with lots of harmonics. From source current spectrum it can be
found that %THD is 18.45.
Fig 6.2: Source voltage, load current, source current in phase A at α=0° without
filter.
57
Fig 6.3: Source current spectrum at α=0° without filter.
Case B: at α=30° When triggering angle increases to 30°, total harmonic distortion also increases to
25.91 %. This means that when α increase, current waveform will be
contaminated with more harmonic contents. Figure 6.5 shows the current
spectrum analysis.
Fig6.4: Source voltage, load current, source current in phase A at α=30° without
filter.
58
Fig 6.5: Source current spectrum at α=30° without filter.
6.3 SIMULATION OF THE FULL CONTROLLED CONVERTER
FEEDING AN RL LOAD WITH PASSIVE FILTER
The passive filter is designed as follows: The reactive power requirement of the
load is calculated. The 5th and 7th order of harmonic shunt filters are designed to
sink in respective harmonic currents. The capacitors for the passive filter are
designed to supply the specified percentage of the reactive power requirement of
the load. The Icosφ algorithm thereby generates the reference compensation
currents for the active power filter each time, with the remaining harmonics and
the reactive contents in the source current after the insertion of passive tuned
filters.
The total VAR requirement is calculated under the worst possible condition of a
given load. The passive filter design is done based on the % VAR to be supplied
by the passive filter. The passive filter element values (R, L and C) are calculated
per phase as follows.
VAR supplied by passive filters per phase, VARp(ph) =(VARp)/3
This can be equated to V2/Xc where V is per phase (rated) voltage across the
passive filter and XC = capacitive reactance per phase
VARp(ph)=V2/Xc=V2. ω.C which gives,
C = VARp(ph)/V2.ω. (6.1)
59
Where C is the capacitance
VARp(ph) is the reactive power per phase
and ω=2.π.f
where f= frequency(50Hz).
Only the 5th and 7th order harmonic passive filters have been chosen for the
simulation study. These filters sink in the 5th and 7th order harmonics from the
three-phase system in addition to supplying the %VAR as specified. VARp(ph) is
shared between one 5th order and one 7th order passive filter in each phase. The
inductances (Lh) of these filters are calculated as follows.
Lh = 1/( ωh2.C) (6.2)
where ωh is the specific harmonic frequency to be absorbed by the filter. (ω5 for
5th and ω7 for 7th).
For a given Q factor , where Q=XLh/Rh
Resistance Rh= ω.Lh/Q. (6.3)
For each VAR supply, the value of C varies. For each value of C, Lh for each ‘h’
varies. For each Lh value, Rh is calculated based on the Q factor value. Thus C, Lh
and Rh design values of each harmonic order passive filter, are mutually
dependent on each other and also on the chosen values of the parameters such as
VAR and Q factor.
The figure 6.6 is the basic set up for simulation of three-phase system with
thyristor controlled converter compensated by passive filter. Figure 6.7 to 6.10
shows waveforms of source voltage, source current, load current and %THD in
source current for different firing angles of thyristor converter load.
60
Fig 6.6: Matlab simulation of the full controlled converter feeding RL load with
passive filters
61
Table 6.1 parameter values of passive filter for simulation
Harmonic Resistor Inductor Capacitor
5th 0.0314Ω 10mH 40µF
7th 0.0160Ω 5.1mH 40µF
Case A: at α =0°. Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., the passive filter sinks the 5th and 7th
harmonic currents by providing a low impedance path. The total harmonic
distortion without controller at α =0° is 18.47 % and with controller it is reduced
to 1.62%.
Fig 6.7: Source voltage, load current, source current in phase A at α=0° with
Passive filter
62
Fig 6.8: Source current spectrum at α=0° with Passive Filter.
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 2.44% whereas without
controller it was 25.91 %
Fig 6.9: Source voltage, load current, source current in phase A at α=30° with
Passive filter
63
Fig 6.10: Source current spectrum at α=30° with Passive Filter.
6.4 SIMULATION OF THE FULL CONTROLLED CONVERTER
FEEDING AN RL LOAD WITH SHUNT ACTIVE POWER FILTER
The main purpose of using Icosφ control algorithm is to reduce the current
harmonic distortion. This section discusses the effects of shunt active filter with
Icosφ controller. The figure 6.10 shows the basic Icosφ for shunt active
filtering. Figure 6.11 to 6.14 shows waveforms of source voltage, source current,
load current and %THD in source current for different firing angles of thyristor
converter load.
64
Fig 6.11: Matlab simulation of the full controlled converter feeding RL load with
Active Power filter .Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., harmonic currents needed by converter
is provided by shunt active filter. Now source has to supply only real component
of load current and remaining reactive components and harmonics required by the
load current is supplied by shunt active filter. The total harmonic distortion
without controller at α =0° is 18.47 % and with controller it is reduced to
0.91%.i.e. THD value is within the allowable limit.
65
Fig 6.12: source voltage, load current and source current in phase A at α =0° with
Active Power Filter.
Fig 6.13: Source current spectrum at α =0° with Active Power Filter.
66
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 1.29% whereas without
controller it was 25.91 % and source current became pure sine wave in phase with
source voltage.
Fig 6.14: source voltage, load current and source current in phase A at α =0° with
Active Power Filter.
Fig 6.15: Source current spectrum at α =30° with Active Power Filter.
67
6.5 SIMULATION OF THE FULL CONTROLLED CONVERTER
FEEDING AN RL LOAD WITH HYBRID FILTER
Hybrid system uses a passive filter connected in shunt to remove the lower order
harmonics and a shunt active filter is connected to remove the remaining
harmonics. The shunt active filer uses the Icosφ control algorithm. The figure
6.15 is the basic set up for simulation.
Fig 6.16: Matlab simulation of the full controlled converter feeding RL load with
Hybrid Filter
68
Case A: at α =0°.
Comparing the wave forms with and without controller at α =0°, it can be seen
that source current became sine wave i.e., 5th and 7th are removed by passive filter
connected in shunt and remaining harmonic currents needed by converter is
provided by shunt active filter. The total harmonic distortion without controller at
α =0° is 18.45 % and with controller it is reduced to 0.47%.i.e. THD value is
within the allowable limit. Figure 6.17 to 6.20 shows waveforms of source
voltage, source current, load current and %THD in source current for different
firing angles of thyristor converter load using hybrid filter.
Fig 6.17: source voltage, load current and source current in phase A at α =0° with
Hybrid Filter
69
Fig 6.18: Source current spectrum at α =0° with Hybrid Filter.
Case B: at α =30°
Total harmonic distortion with controller at α=30° is only 0.64% whereas without
controller it was 25.91 % and source current became pure sine wave in phase with
source voltage.
Fig 6.19: source voltage, load current and source current in phase A at α =30°
with Hybrid Filter
70
Fig 6.20: Source current spectrum at α =30° with Hybrid Filter.
Table 6.2 Simulation of the three phase system with passive filter, active filter
and hybrid filter
Parameters Without filter With Passive
filter
With Active
filter
With Hybrid
filter
α = 0o α = 30o α = 0o α = 30o α = 0o α = 30o α = 0o α =30o
Fundamental
source
current in
rms (A)
16.87 14.5 21.47 17.04 18.04 14.96 18.55 15.92
THD in
Source
Current (%)
18.45 25.91 1.62 2.44 0.91 1.29 0.47 0.64
Time Delay
(in ms)
5 5 20 20 20 20
71
6.6 CONCLUSION
Using the proposed hybrid filter structure consisting of combination of shunt
active power filter and 5th and 7th shunt passive filters has the best performance
in harmonic reduction. The active filter is then required to compensate only for
the remaining harmonics which the passive filter has not removed. Thus the rating
and cost of the active power filter has been reduced. Thus the use of active power
filters for power quality improvement in retrofit systems is thus justified. The
results prove the efficiency of the hybrid filter in reducing the current harmonics.
72
CHAPTER VII
HARDWARE SETUP – DESIGN AND MODELLING OF
HYBRID FILTER
7.1 INTRODUCTION
The earliest type of filters were shunt /series passive filters connected at
PCC which provide a low/high impedance path to the selected harmonics,
preventing most of the selected harmonics from appearing at the source. But they
have drawbacks such as resonance, fixed compensation, high no load losses,
bulky size etc. As a better option of complete compensation of distortions, active
power filters have been researched and developed. Many mature control
algorithms are available in literature for the control of three-phase active filters.
Most of them use tedious computations and complex circuits and hence highly
expensive and slow in response. Hence as a better and economical option,
combination of passive and active filters, named hybrid filters, are implemented.
It is quite popular because the solid state devices used in the active part can be of
reduced size and cost. Here, generally, passive filters are used to eliminate lower
order harmonics. The higher order harmonic currents, which are much less in
magnitude compared to lower order harmonics, are eliminated by active filter.
Hybrid filters allow designing active filters for only a fraction of total load
power, reducing costs and increasing overall system efficiency. Based on reactive
power requirement of the system under the present / rated load condition, passive
LC filters lower order harmonic frequency can be designed and inserted. The
active filter is controlled by using Icosφ algorithm, which can be easily
implemented using analog circuit. The main advantages of using analog circuits
are easy availability, cost effectiveness of analog circuits for implementing any
mathematical function and very quick response with simple implementation
aspects. Based on reactive power requirement of the system under the present /
rated load condition, passive LC filters lower order harmonic frequency can be
designed and inserted.
73
Fig 7.1: Basic Block diagram of three phase hardware setup.
7.2 HARDWARE IMPLEMENTATION – LABORATORY
PROTOTYPE A voltage source inverter assembly, which consists of a
three phase IGBT based inverter along with large DC link capacitor, is
being used as the shunt active filter. DC link capacitor of 1650mF / 800V
is used for maintains steady voltage required by the inverter. Appendix 1
gives the details of the SEMIKRON make inverter. Different
combinations of inductor blocks are used as coupling inductor according
to the requirement of the non linear load. LEM Hall effect voltage sensors,
namely, LV 25-P and current sensor LA 25-NP have been used for
sensing phase voltages, load currents and active filter output currents.
Appendix 2 gives the data sheets of the sensors.
74
The passive filter design is done based on reactive power requirement. Since
most of the power system equipments are bilateral, even order harmonics will
not be present in power system. Therefore, to reduce the predominant
harmonics of 5th and 7th order harmonics to a great extent, 6th order harmonic
shunt passive filter is designed. The capacitor value, inductance value and
resistance value of the 6th harmonic order passive filter, are mutually depend
on each other and also on the chosen values of the parameters such as VAR
and Q factor. For this loading condition, the combination of 5mH-80µF is
selected as the most optimised filter. The passive filter is designed for 100%
VAR compensation and it is tuned to the sixth harmonic. A three phase diode
bridge rectifier, of current rating 16 A, feeding single phase, 230V ,3kW
resistive load is used as a non linear load for testing the control circuit. The
figure 7.2 shows the basic hardware setup.
7.2: Basic setup for hardware using passive filters
75
7.3 CONTROL CIRCUIT DESIGN AND TEST RESULTS
The modules of analog circuit controller used with shunt active power filter are
shown in figure 7.3.
Fig 7.3: The block diagram of the Icosφ analog controller for phase A. 7.3.1 FUNDAMENTAL DETECTION OF LOAD CURRENT
Low pass filtering for extracting fundamental component of load current is the
main operation to be done by the controller. Low pass filtering is done by the
biquad filter. The advantages of using biquad filter, rather than other low pass
filters, are it is easy to design, it gives unity gain and it also gives exact 90° phase
shift. Following session gives the design of biquad filter.
76
7.3.1.1. OP-AMP BASED CIRCUIT OF BIQUAD FILTER
To obtain op-amp circuit implementation a miller integrator circuit having time
constant CR=1/ω0 and replace summer block with an op-amp summing circuit.
The resulting circuit, known as Kervin-Huelsman-Newcomb or KHN biquad after
its inventors is shown figure 7.4.
Fig 7.4: Op-amp circuit of the biquad filter
For given values of K, Q and ω0 the design of circuit are straight forward. Expressing the output of the summer in terms of its inputs, Vhp can be written as,
----------------- (4)
------ (5)
Equating last terms of right hand side of the equation (4) and (5), Rf/R1=1. Again
equating second to last term of the right hand side of the equations (4) and
(5),R3/R2=2Q-1 .Finally equating coefficients of Vi, K=(2-1)/Q
7.3.2 ZERO CROSSING DETECTION
This circuit includes the comparator circuit with monostable multivibrator
74LS123 used for getting sharp output pulses at negative zero crossing of the
77
phase voltage. Figure 7.5, shows the simulation and outputs. Truth table of
74LS123 is selected in such a way that when input pin get transition from high to
low. Pulse width of the output of multivibrator is decided by the values of Rext and
Cext.
Fig 7.5: Negative zero crossing detection circuit with monostable multivibrator.
7.3.3 SAMPLE AND HOLD CIRCUIT
The sample and hold circuit (LF 398) gives the Icosφ value. This has got two
inputs, one is from the biquad filter and other is from monostable multivibrator.
The output is Icosφ which is getting at instant of negative of zero crossing voltage
and output is given to multiplier circuit. The circuit is shown in figure 7.6
78
Fig 7.6: The sample and hold circuit for getting Icosφ value.
7.3.4 THE MULTIPLICATION CIRCUIT
AD 633 JN is used as multiplier for multiplying IcosØ value and unit amplitude
sine wave. The output of the multiplier is the desired source current. The
multiplier circuit connection is shown in figure 7.7.
Fig 7.7: The multiplier circuit for producing desired source current.
7.3.5 THE SUBTRACTOR CIRCUIT
The subtracting circuit is formed as shown in figure 7.8 with two IC 741op-amps.
The load current and reference source current were given as input and verified the
output.
79
Fig 7.8: The subtractor circuit for producing compensation current.
7.3.6 THE COMPARATOR CIRCUIT FOR PWM GNERATION
The comparator circuit is used for producing PWM pulses for inverter. This
circuit compares reference compensation current and actual filter current. When
reference filter current is more than actual filter current, output of the comparator
is high and vice versa. The comparator is realized using op-amp 741 and IC
4049B. The 4049B is used for inverting comparator low output.
Fig 7.9: The comparator circuit for PWM generation
80
7.3.7 ISOLATION AND AMPLIFICATION CIRCUIT
The isolation circuit is provided for the isolation between power circuit and
controller circuit. The optocoupler 6N136 is used for isolation. The Semikron
make Inverter needs +15V in the gate of the IGBT. Normal PWM is less than 15V
and it is not sufficient to drive the gate of the Semikron make Inverter. The
transistor amplifier BC 547 is using for amplifying PWM pulses. The circuit
diagram is shown in figure 7.10
Fig 7.10: The isolation and amplification circuit.
7.4 CONCLUSION
This chapter describes the hardware setup of the shunt active filter along with
three phase non-linear load. The tuned passive filter is designed and inserted for
partial compensation. The analog circuit for Icos φ control algorithm has been
designed. The hardware testing results prove that the active filter and passive filter
are working satisfactorily, which are included in Chapter VIII.
81
CHAPTER VIII
HARDWARE IMPLEMENTATION OF HYBRID POWER
FILTER – UNDER DIFFERENT SOURCE AND LOAD
CONDITIONS
8.1 INTRODUCTION
The hybrid power filter has been designed and implemented for balanced
/unbalanced/distorted three phase source conditions with balanced/unbalanced
three-phase load. Also, the three-phase hybrid power filter results are compared
with that of passive filter and active filter results under various source/load
conditions.
A balanced source is one that provides balanced sinusoidal voltages in the three
phases that are equal in magnitude and displaced exactly by120o in phase from
each other. Unbalanced load currents in a three-phase system, is a common
phenomenon and should be considered as an operating condition that may vary
frequently. The supply current will be balanced or unbalanced depending on the
operating conditions, but the wave shape will depend on the type of load. Here,
the three phase diode bridge rectifier is considered as a non-linear load and this
introduces higher level of current harmonics. In this chapter, effectiveness of
hybrid power filter for compensating current harmonics is covered
8.2 EXPERIMENTAL RESULTS
8.2.1. BALANCED SOURCE AND BALANCED LOAD CONDITION
The experimental results on a scaled down balanced three phase system
connected to diode bridge rectifier feeding a resistive load (230V, 3kW) are
presented in this section. The Icosφ controller senses load current, supply voltage
and generate PWM pulses to IGBT inverter. The shunt active power filter is
connected to three phase supply at point of common coupling through 10mH,
coupling reactance.
82
The passive filter is designed for 100% VAR compensation and it is tuned to the
sixth harmonic so as to avoid resonance condition and to sink both 5th and 7th
harmonic currents to certain extent. This will reduce the size of the passive filter
and hence loading on the source also.
A scaled down three phase supply of 50V/phase is connected to a diode bridge
rectifier load and the reduction in source current harmonics are obtained with the
help of active filter and hybrid filter. The results obtained in DSO are shown in
Fig.8.1 to Fig.8.3.
Fig 8.1: Diode bridge rectifier load with active filter: (a) Source voltage and load
current (phase A) (b) Load current and reference compensation current (phase A).
.
Fig 8.2: Diode bridge rectifier load: Reference compensation current and actual
compensation current in closed loop (phase A).
83
Fig 8.3: Diode bridge rectifier load with hybrid filter (shunt active and shunt
passive): (a) Load current and reference compensation current (phase A)
(b) Reference compensation current and actual compensation
current in (phase A)
The tests results are also analyzed using FLUKE make power quality analyzer.
The hybrid power filter, combination of shunt active and shunt passive filters,
reduces total harmonic distortion in source current. Passive filter reduces the
lower order (5th and 7th) harmonics and a shunt active power filter injects the
remaining harmonics in source current .Relevant results are shown in figures 8.4
to 8.7
84
Fig.8.4: a) source voltages b) source current without filtering c) source current
with hybrid filter
Fig.8.5: a) a-phase voltage and current without filtering b) a-phase voltage and
current with hybrid filtering
85
Fig 8.6: THD % of Source current spectrum (a) without filtering (b) with active
filter for balanced source and balanced load
Fig 8.7: THD % of Source current spectrum (a) With passive filter (b) with hybrid
filter for balanced source and balanced load
8.2.2. DISTORTED SOURCE AND A BALANCED LOAD CONDITION
The distorted source voltages are applied across a diode bridge rectifier feeding a
resistive load. When there is distortion in the supply voltages, the fundamental
components are first derived using suitably tuned second order low pass filters to
86
make the voltages balanced and sinusoidal. The unit sine wave of these balanced
voltages are used as templates as required by the Icosφ algorithm to generate
compensation currents. The hardware set up for this experiment has already been
described in section 8.0 which is used for balanced source and load conditions. he
results are shown from figures 8.8 and 8.11.
Fig.8.8: a) source voltages b) source current without filtering c) source current
with hybrid filter
Fig.8.9: a) a-phase voltage and current without filtering b) a-phase voltage and
current with hybrid filtering
87
Fig 8.10: THD % of Source current spectrum (a) without filtering (b) with active
filter for distorted source and balanced load
Fig 8.11: THD % of Source current spectrum (a) With passive filter (b) with
hybrid filter for distorted source and balanced load
88
8.2.3. BALANCED SOURCE AND UNBALANCED LOAD CONDITION:
The balanced three phase supply is connected to the diode rectifier with a
resistance of 25Ω connected in series with a-phase supply line and 52Ω connected
in series with c-phase supply line on the AC side for introducing unbalance in the
load currents in the three phases. In the IcosΦ algorithm, the unbalance in load is
taken care of in the determination of reference currents itself as explained in
section 3.1 in chapter 3. The shunt active filter using the Icosφ algorithm makes
sure that the source currents in all the same phases remain balanced even in case
of load unbalance.
The active filter along with the passive filter reduces the THD and the results are
shown in fig 8.12 to 8.15.
Fig.8.12: a) source voltages b) source current without filtering c) source current
with hybrid filter
89
Fig.8.13: a) a-phase voltage and current without filtering b) a-phase voltage and
current with hybrid filtering
Fig 8.14: THD % of Source current spectrum (a) without filtering (b) with active
filter for balanced source and unbalanced load
90
Fig 8.15: THD % of Source current spectrum (a) With passive filter (b) with
hybrid filter for balanced source and unbalanced load
Table 8.1: Comparison of source current spectrum with and without hybrid filter
under balanced source and load condition (50V/phase)
UNDER BALANCED SOURCE AND BALANCED LOAD CONDITION
Supply Voltage=50V/phase
THD(%
)
H5 (%) H7 (%) H11 (%) H13 (%)
WITHOUT
HYBRID
FILTER
R 29.8 24.8 9.0 9.1 5.1
Y 29.7 24.4 9.4 9.0 5.3
B 28.7 23.3 9.8 8.2 6.0
WITH
HYBRID
FILTER
R 3.6 2.7 2.9 0.9 0.2
Y 3.8 2.7 2.3 0.8 0.2
B 3.9 3.0 2.3 0.5 0.2
91
Table 8.2: Comparison of source current spectrum with and without hybrid filter
under distorted source and balanced load condition (50V/phase)
UNDER DISTORTED SUPPLY AND BALANCED LOAD CONDITION
Supply Voltage=50V/phase
THD(%
)
H5 (%) H7 (%) H11
(%)
H13
(%)
WITHOUT
HYBRID
FILTER
R 29.4 22.8 11.5 9.1 6.1
Y 29.2 22.4 11.7 9.2 6.0
B 29.1 22.5 11.5 9.1 6.0
WITH
HYBRID
FILTER
R 3.4 1.9 1.7 0.6 0.1
Y 3.3 2.0 1.2 0.3 0.2
B 3.8 2.5 2.0 0.7 0.2
Table 8.3: Comparison of source current spectrum with and without hybrid filter
under balanced source and unbalanced load condition (50V/phase)
UNDER BALANCED SOURCE AND UNBALANCED LOAD
CONDITION
Supply Voltage=50V/phase
THD(%
)
H5 (%) H7 (%) H11
(%)
H13
(%)
WITHOUT
HYBRID
FILTER
R 19.5 11.8 5.6 2.1 1.7
Y 16.1 8.1 8.2 2.1 1.9
B 24.8 19.1 5.0 1.3 1.0
WITH
HYBRID
FILTER
R 4.0 3.2 1.5 0.5 0.2
Y 3.3 2.8 1.2 0.5 0.2
B 3.7 3.3 1.5 0.5 0.1
92
8.3 CONCLUSION
Three phase diode bridge rectifier load produces lot of current harmonics and it is
injected in to supply mains. Total input current THD, has been above the
allowable limit and total input power factor was also reduced. After hybrid
filtering, the %THD has been reduced to allowable limit.
The three-phase hybrid filtering system works quite efficiently under balanced
source and balanced load conditions. The Total Harmonic Distortion (THD) in the
source current is with in 4% which conforms to IEEE power quality standards.
Unbalance in the three phase load currents drawn by non-linear loads is tested
with hybrid filtering techniques. This filtering technique has been found to be
very effective in this operating condition with the source current THD remaining
within 5% in this case as well.
93
CHAPTER IX
CONCLUSION AND SCOPE OF FUTURE WORK
9.1 CONCLUSION
Power quality problems such as harmonics injection, poor power factor,
unbalance and reactive power burden lead to low system efficiency. The power
quality problems are caused invariably by power electronic converters and other
non-linearities present in the power system. Passive, active and hybrid filters are
the three main solutions to mitigate power quality problems in retrofit systems.
Passive filter, filter out desired harmonic frequency component, but it may cause
resonance, detuning, fixed compensation etc. A number of research works are
carried out in active filters, but their rating and cost will be too high. Hence hybrid
filters, a combination of active and passive filter, are suggested for harmonic
compensation as more effective, economical and resonant free solution.
Standard active filter control algorithms such as instantaneous PQ theory,
synchronous detection algorithm, and DC bus voltage algorithm are
studied. Using MATLAB/SIMULINK software, models for the same have
been created and simulated.
Icosφ control algorithm has been studied and shunt active power filter
using this algorithm was simulated in Matlab with 3-phase thyristor
converter feeding RL load. It has been found to yield comparable or rather
marginally better results as compared to existing algorithms under various
source and load conditions, in addition to being simpler than the existing
power filtering algorithms.
Tuned passive filters were designed and simulated in Matlab along with
shunt active filter. The passive filter was designed to filter out the lower
order harmonics, mainly the fifth and the seventh harmonics thereby
reducing the rating of the active power filter.
The prototype of three-phase hybrid filter connected to a three phase
system with diode bridge rectifier feeding a resistive load has been
developed in the laboratory. It uses a shunt connected passive filter in each
94
phase to filter out the tuned frequency harmonics and the remaining
harmonics were filtered by the shunt connected active filter which used the
Icosφ control algorithm. The prototype has been tested for different system
and load conditions such as balanced supply and balanced load, distorted
source voltage and balanced load and also on balanced supply and
unbalanced load condition.
The three-phase hybrid filtering system works quite efficiently under
balanced source and balanced load conditions. The Total Harmonic
Distortion (THD) in the source current is with in 4% which conforms to
IEEE power quality standards.
Unbalance in the three phase load currents drawn by non-linear loads is
tested with hybrid filtering techniques. This filtering technique has been
found to be very effective in this operating condition with the source
current THD remaining within 5% in this case as well.
The three-phase system is tested under distorted source voltages. Here
also, the THD is found to be less than 5% with individual harmonics less
than 3%
The implementation results show that effective current harmonics is
reduced using hybrid power filter.
9.2 SCOPE OF FUTURE WORK
The traditional passive filters will be permanently connected to system and
draws large amount of source current even at light load conditions. By
using auto-tuned filters, the passive filter components can be controlled
according to load variations. The selection of filter parameters,
capacitance and inductance, can be done with the help of a properly tuned
knowledge base, using Artificial Neural Networks, to provide fast
compensation using digital controller.
Fuzzy techniques can be used for more fast and effective compensation.
The Icosφ algorithm can be implemented digitally so that problems of
analog circuits such as ageing, tolerance etc can be avoided.
95
REFERENCES
[1] Manjula G.Nair and G. Bhuvaneswari, “Design, Simulation and Analog
Circuit Implementation of a Three-phase Shunt Active Filter using the Icos Ǿ
Algorithm” IEEE PEDS 2005.
[2] Bor-Ren Lin .et.al. "Analysis and operation of hybrid active filter for harmonic
elimination", Electric Power Systems Research 2002, Vol.62, pp.191-200
.
[3] B. Singh, V. Verma, A. Chandra and K. Al-Haddad, "Hybrid filters for power
quality improvement"IEE Proc.-Gener. Transm. Distrib., Vol. 152, No. 3, May
2005
[4] IEEE Guide for harmonic control and reactive compensation of Static Power
Converters, IEEE Standard 519-1992.
[5] Power quality files available (on-line) at: http://www.e-shikshalaya.com
[6] H.L.jou, J.C.Wu and H.Y.chu, “New single phase active power filter” IEE
Proc.-Electr. Power Appl., Vol. 141, No. 3, May 1994.
[7] Bhim Singh, Kamal Al-Haddad and Ambrish Chandra, “A Review of Active
Filters for Power Quality Improvement” IEEE Transactions On Industrial
Electronics, Vol. 46, No. 5, October 1999.
[8] H. Akagi, Y. Kanazawa & A. Nabae, "Instantaneous reactive power
compensators comprising switching devices without energy storage components”,
IEEE Trans. Industry Applications, Vol. 20(3), pp. 625-630, 1984.
[9] C.L. Chen, C.E. Lin & C.L. Huang, "Reactive and harmonic current
compensation for unbalanced three-phase systems using the synchronous
detection method”, Electric Power systems Res., Vol. 26, pp.l63-170, 1993.
96
[10] H. L. Jou, "Performance comparison of the three-phase-active-power filter
Algorithms", in Proc. IEE Conf. on Generation, Transmission, Distribution, pp.
646-652, 1995.
[11] S. Bhattacharya & D. Divan, "Synchronous frame based controller
implementation for a hybrid series active power filter system”, in Proc. 13th IAS
Annual meeting, pp.2531-2540, 1995.
[12] G. Bhuvaneswari & M.G.Nair, "A novel current compensation technique for
shunt active power filters", in Proc. IASTED Conf On Power and Energy
systems, pp. 109-113, 2003.
[13] G. Bhuvaneswari, Manjula G.Nair, “Comparison of Synchronous Detection
and Icosφ Shunt Active Filtering Algorithms”, IEEE 2006.
.
[14] Jos Arrillaga and Neville R. Watson, “power system harmonics”, John Wiley
& Sons Ltd, 2nd edition, 2003.
[15] George. J. Wakileh, “Power System Harmonics-Fundamentals, Analysis and
Filter Design”, Springer International Edition, 2001.
[16] Akagi. H., Navea. A. and Atoh.S, “Control strategy of active power filters
using multiple voltage-source PWM converters”, Trans. IEEE Industry
Applications, IA22 (3), 460–5,1996.
[17] Hayafune.K, Ueshiba.T, Masada.E and Ogiwara.Y, “Microcomputer
controlled active power filter”, International Conference on Industrial Electronics,
Control and Instrumentation”, Tokyo, pp. 1221–26,1984.
[18] Detjen.O, Jacobs.J, De Doncker.R.W and Mall.H.G, “A new hybrid filter to
dampen resonances and compensate harmonic currents in industrial power
97
systems with power factor correction equipment”, Trans. IEEE Power
Electronics, 16(6), 821–7, 2001.
[19] MATLAB/SIMULINK User’s Guide, The MathWork Inc., USA.
[20] M.EI-Habrouk, M.K.Darwish and P.Mehta, “Active power filters: a review”,
IEEE Proc.-Electr. Power Appl., Vol. 147, No. 5, May 2000.
[21] Z.P.Fang, H.Akagi, A.Nabae, "A New Approach to Harmonic Compensation
in Power Systems-a Combined System of Shunt Passive and Series Active
Filters", IEEE Trans, Industry applications. Vo1.26, No.6, Nov/Dec 1990, pp983-
990. [22] F.Z.Peng, H.Akagi and A. Navae, "Compensation Characteristics of the
Combined System of Shunt Passive and Series Active Filters", IEEE-T Ind.
Applications, vol. IA-29, no.1, JadFeb 1993, pp141-151.
[23] H.Fujita, H.Akagi, "A Practical Approach to Harmonic Compensation in
Power Systems-Series Connection of Passive and Active Filters", IEEE-T
industry Applications 1991, pp1020-1025.
98
APPENDIX –1
Three phase IGBT based inverter, 20 KVA, 10A, 20 KHZ PWM –Semikron make
Voltage Source Inverter (VSI)
DC link capacitor of 1650 µfd / 800V.
Three phase diode bridge rectifier having current rating of 16A.
Non-linear loads
400V, 5A, 10mH each in three phase phases.
Coupling Inductance
R =50ohms, 5A; L=5mH,5A; C=80µfd / 440V for each of the three phases
Passive Filter components
99
APPENDIX – 2
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
APPENDIX-3
Photograph of Experimental Setup
Active filter with controller -Hardware
Passive Filter – Hardware circuit