NEWControl board
with Modbus
communication protocol
Air Conditioning
SkyStarSkyStar ECM
Cassette Fan Coil Units
Quality management systemsISO 9001 – Cert. n° 0545/5
www.eurovent-certification.comwww.certiflash.com
Sabiana take part to the Eurovent program of fan coil performance certification.The official figures are published in the web sitewww.eurovent-certification.com and in the web site www.certiflash.com.The tested performances are:
• Fan absorption • Water pressure drop • Sound power
• Heating emission (2 pipe units) at the following conditions: - Entering water temperature +50°C - Entering air temperature +20°C - Water flow rate as for the cooling conditions
• Heating emission (4 pipe units) at the following conditions: - Water temperature +70°C E.W.T. +60°C L.W.T. - Entering air temperature +20°C
• Cooling total emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb
• Cooling sensible emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb
CONTENTS
• SkyStar • Introduction Page 3 • Main components Page 4 • EUROVENT Certifications Page 5 • Emissions Page 6 • Water side pressure drop Page 9 • Working conditions Page 9 • Dimensions and weights Page 10 • Air throw Page 12 • Fresh air supply e Air distribution Page 13 • Accessories Page 14 • CRYSTALL electrostatic filter Page 16 • Wall electronic controls Page 20 • FreeSabiana wireless control system Page 24 • Controls for SK−MB versions Page 26 • Electric heater SK−E Page 27
• SkyStar ECM • Introduction Page 28 • Main components Page 29 • EUROVENT Certifications Page 30 • Emissions Page 31 • Water side pressure drop Page 33 • Working conditions Page 33 • Dimensions and weights Page 34 • Air throw Page 36 • Accessories Page 37 • SK−ECM configuration Page 39 • Wall electronic control Page 40 • Controls for SK−ECM−MB versions Page 42
• SkyStar / SkyStar ECM • MB power electronic board Page 43 • T-MB wall mounted control Page 44 • RT03 infra-red remote control Page 45 • PSM-DI multifunction control Page 47 • Sabianet management system Page 48 • PSM-DI and Sabianet accessories Page 48
• SkyStar MCT • Introduction Page 51 • Dimensions and weights Page 52 • Assembly diagram Page 53 • Components of the casing e Valve kit Page 54
MD-600Version
Innovating and beautiful design, seven different sizes, high control flexibility, easy maintenance: thenew SkyStar chilled water cassette is the result of an extended technical and design developmentaimed at achieving the highest level in terms of performance, silent operation and controlpossibilities.
The air diffuser has an highly attractive aesthetical appearance, very innovative, and is also ableto offer the best air distribution performance thanks to long computer studies and laboratory tests.The standard colour is RAL 9003, other colours available on request.
The 4 smaller sizes are designed to fit into 600x600 mm false ceiling standard modules. The 3bigger sizes have a dimension of 800x800 mm which allows the best outcome in terms of quiet-ness and of price/performance ratio for these high capacity models.
Every unit can be supplied with 1 battery (2 pipe system) and a possible electric heater or with2 batteries (4 pipe system). Each model can have fresh air intake and a remote air diffuser canbe connected to the unit.
The condensate pump is integralwith the unit, is very quiet and hasa maximum head of 650 mm.
In addition to the temperature andspeed standard controls, automaticspeed selection is also available. Morethan one unit can be connected toa single control, and the unit controlpanel can be installed in a position thatfacilitates the maintenance operation.Every unit can also be operated by themeans of an infra-red remote control.The SkyStar cassettes can also beconnected to the most commonautomatic building managementsystems.
It is also possible to use a completelywireless electronic control systembased on radio communication calledFree Sabiana, with great advantagesin terms of installation flexibility andmaximum precision in measuringroom temperature.
Finally, each unit can be equippedwith a low energy consumption electricmotor that is controlled by an invertercard that makes possible continuousair flow variations.
3
SkyStarIntroduction
4
INTAKE GRID AND DISTRIBUTION OF THE AIRIntake grids, frame and adjustable air distribution louvers on each side, made from ABS.HTA version : white ABS, RAL 9003HTB version : with intake grid, frame and louvers, choice of one colour onlyHTC version : with intake grid and louvers, choice of one colour, plus white ABS frame RAL 9003HTD version : with louvers, choice of one colour, while the grid and frame are made from ABS, RAL 9003MD-600 version : metal diffuser painted in RAL 9003 white colour with 600x600 dimension to perfectly fit into the false ceiling standard modules without overlapping parts (800x800 model is not available).
CASINGIs made from galvanized steel with inside thermal insulation with polyolefin (PO) foam (class M1) andoutside anti-condensate lining.
CONTROL PANELMade of an external box with the control electronic board with an easily accessible terminal board.
FAN ASSEMBLYThe fan assembly, which is mounted on anti-vibrating supports, is extremely silent.The radial fan has been designed to optimise performance, using wing profile blades with a shape thatreduce turbulence, increasing efficiency and reducing noise.The single air inlet radial fan is connected to a 6 speed electric motor with single phase 230V/50Hz supply,class B insulation and integrated Klixon thermal contact for motor protection.The units are supplied with 3 standard speeds connected and it is possible to change them on site ifnecessary.
HEAT EXCHANGERMade of copper tubes with bonded aluminium fins for maximum transfer contact.The batteries are with 1, 2 or 3 rows for 2 pipe models and 2+1 rows for 4 pipe models (the heating rowis on the inside part of the battery).For 4 pipe systems two versions are available:SK 04, SK 14, SK 24, SK 34, SK 44, SK 54, SK 64 supply an higher heating emission;SK 26, SK 36, SK 56, SK 66 supply an higher cooling emission.The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminiummay be subject to corrosion.
CONDENSATE COLLECTION TRAYHigh density ABS polystyrene foam condensate tray, shaped in order to optimize the air diffusion, fireretardant rating B1 to DIN 4102.
AIR FILTERSynthetic washable filter, easily removable.
CONDENSATE PUMPFloat switch centrifugal pump with 650 mm of maximum head, integral to the unit and wired to the controlpanel on the outside of the casing.
VALVE SETTwo or three way valves for ON/OFF operation, with pipe mounting kit and thermostatic actuator.
SkyStarMain components
3101,841,352,223164,94,1332425
0,11
4202,341,752,904027,66,3403132
0,15
5202,682,043,354619,78,2453644
0,20
3202,251,572,563874,63,5332425
0,11
5003,342,393,935749,47,3453644
0,20
7104,333,185,2374515,111,4534468
0,32
4302,942,083,435067,56,7413232
0,15
6103,882,814,6366712,411,2494057
0,27
8805,023,746,1786319,717,7595090
0,45
6304,213,035,1272410,96,7332433
0,15
8204,913,586,0384514,39,9403148
0,23
11406,164,597,77106021,615,1483977
0,36
7105,313,465,619139,47,9342542
0,18
9706,784,487,34116614,712,4403163
0,28
15009,516,48
10,71163626,923,05344
1200,53
7105,313,716,139139,47,9342542
0,18
12808,456,0910,30145321,818,6483995
0,42
182011,108,2514,00190935,630,658491700,74
3101,271,011,622194,54,0332425
0,11
4201,631,322,122807,06,0403132
0,15
6101,981,642,6434010,09,0494057
0,27
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 31 2 3
1,4 3,0 4,02,1 2,1 4,00,8820 x 820 x 303575 x 575 x 275
SpeedAir flow m3/hCooling total emission (E) kWCooling sensible emission (E) kWHeating (E) kWWater flow l/h�P Cooling (E) kPa�P Heating (E) kPaSound power Lw (E) dB(A)Sound pressure Lp (*) dB(A) W AWater content lDimensions mm
MODEL
Fan (E)
SK 12 SK 22 SK 32 SK 42 SK 52 SK 62SK 02
3101,511,152606,0
1,961696,5332425
0,11
4201,961,5533710,02,5421910,5403132
0,15
6102,331,9040113,53,0326114,5494057
0,27
3101,851,343184,6
2,432095,7332425
0,11
4202,361,714066,93,022608,5403132
0,15
5202,701,984648,8
3,4629810,8453644
0,20
3201,851,343184,62,432095,7332425
0,11
5002,651,984568,8
3,4629810,8453644
0,20
7103,342,5657413,44,4037816,6534468
0,32
3202,091,493594,01,981703,6332425
0,11
5003,062,245267,0
2,712336,0453644
0,20
7103,932,9567610,53,352889,0534468
0,32
4302,361,754067,2
3,102678,8413232
0,15
6103,022,2951911,23,9734113,8494057
0,27
8803,812,9765517,04,9542620,5595090
0,45
4302,721,974686,0
2,462125,0413232
0,15
6103,532,626079,03,062637,8494057
0,27
8804,533,4677914,03,7932611,0595090
0,45
SpeedAir flow m3/hCooling total emission (E) kWCooling sensible emission (E) kWWater flow l/h�P Cooling (E) kPaHeating (E) kWWater flow l/h�P Heating (E) kPaSound power Lw (E) dB(A)Sound pressure Lp (*) dB(A) W ACooling water content lHeating water content lDimensions mm
Fan (E)
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
575 x 575 x 275
1,00,6
1,40,7
1,40,7
1,70,5
1,40,7
1,70,5
MODEL SK 04 SK 14 SK 24 SK 26 SK 34 SK 36
6304,142,967128,8
5,915089,8332433
0,15
8205,033,6586512,57,1961814,0403148
0,23
11406,344,69109018,99,1078321,4483977
0,36
7104,523,2577710,36,4555511,5342542
0,18
9705,664,1597415,48,1069717,4403163
0,28
15007,715,83132626,911,0094629,95344
1200,53
7104,993,538589,05,234506,5342542
0,18
9706,334,55108914,06,425529,2403163
0,28
15008,776,49150825,08,5673615,353441200,53
7104,523,2577710,36,4555511,5342542
0,18
12806,935,18119222,19,9885825,3483995
0,42
18208,896,84152934,7
12,70109238,85849
1700,74
7104,993,538589,0
5,234506,5342542
0,18
12807,845,73134820,07,7466613,0483995
0,42
182010,207,68175432,09,8084319,55849
1700,74
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
820 x 820 x 303
3,01,4
3,01,4
3,61,1
3,01,4
3,61,1
SpeedAir flow m3/hCooling total emission (E) kWCooling sensible emission (E) kWWater flow l/h�P Cooling (E) kPaHeating (E) kWWater flow l/h�P Heating (E) kPaSound power Lw (E) dB(A)Sound pressure Lp (*) dB(A) W ACooling water content lHeating water content lDimensions mm
Fan (E)
MODEL SK 44 SK 54 SK 56 SK 64 SK 66
5
Technical features
EUROVENT Certification
www.eurovent-certification.comwww.certiflash.com
(E) = Eurovent certified performance. (*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.
2 pipe units. The following standard rating conditions are used:
COOLINGEntering air temperature: + 27°C d.b., + 19°C w.b.Water temperature: + 7/12°C
HEATINGEntering air temperature: + 20°CWater temperature: + 50°Cwater flow rate as for the cooling conditions
4 pipe units. The following standard rating conditions are used:
COOLINGEntering air temperature: + 27°C d.b., + 19°C w.b.Water temperature: + 7/12°C
HEATINGEntering air temperature: + 20°CWater temperature: + 70/60°C
38631023748241735678759341290370252011188657341683114687620151471876
2,241,801,382,802,422,074,573,452,395,254,083,026,505,034,279,786,675,0911,728,555,09
2031641262662321984403342355043942946244864159516555051132834505
2,371,911,463,102,692,315,123,892,735,864,583,427,265,654,8211,067,625,8713,179,705,87
298239183377327279619467326709552410878681578132790669415861161694
3,462,782,134,393,803,257,195,433,798,256,424,7710,217,926,7215,4310,548,0718,4513,508,07
39331524048842236079559841591470952411308747411699115588220371484882
4,563,662,805,684,914,199,256,964,8310,638,256,1013,1410,168,6119,7613,4310,2523,6817,2610,25
488391298599513441972730505111886663913831067903207114031068248618071068
5,674,553,476,975,965,1211,308,485,8713,0010,077,4316,0812,4110,5024,0816,3212,4228,9121,0112,42
6104203105204203107105003208806104301140820630150097071018201280710
HighMedLowHighMedLowHighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
Model SpeedAirflow
EWT 45 - LWT 40°C EWT 50 - LWT 40°C EWT 60 - LWT 50°C EWT 70 - LWT 60°C EWT 80 - LWT 70°C
l/hm3/h kW l/h kW l/h kW l/h kW l/h kW
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
SK 12
SK 22
SK 32
SK 42
SK 52
SK 62
SK 02
6104203105204203107105003208806104301140820630150097071018201280710
421346269554482417926715508104983563312641003858194313741070227717221070
2,452,011,573,222,802,425,384,152,956,104,853,687,355,834,9911,307,996,2213,2410,016,22
1,831,481,142,221,911,643,642,771,944,173,262,445,003,923,327,595,274,069,016,684,06
34028021946240331774557538786366750610608457221635116691319091454913
1,981,631,272,682,341,844,333,342,255,023,882,946,164,914,219,516,785,3111,108,455,31
1,641,321,012,041,751,353,182,391,573,742,812,084,593,583,036,484,483,468,256,093,71
254210165362317276617483349694559430840674580130193974015111162740
1,471,220,962,101,841,613,592,812,034,033,252,504,883,923,377,575,464,308,786,754,30
1,451,160,891,751,501,292,872,181,533,292,571,923,953,092,625,994,153,207,115,273,20
1991601232522201884203192254793762835734533848806124341044775434
1,160,930,711,471,281,092,441,861,312,792,191,653,332,632,235,123,562,526,074,512,52
1,160,930,711,471,281,092,441,861,312,792,191,653,332,632,235,123,562,526,074,512,52
HighMedLowHighMedLowHighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
EWT 5 - LWT 10°C EWT 7 - LWT 12°C EWT 9 - LWT 14°C EWT 12 - LWT 17°CWaterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Model SpeedAirflow
l/h kW kW l/h kW kW l/h kW kW l/h kW kWm3/h
SK 12
SK 22
SK 32
SK 42
SK 52
SK 62
SK 02
7/12 °C10/15 °C14/18 °C
KKK
0,90,720,5
0,940,780,58
1,060,90,72
7/12 °C10/15 °C14/18 °C
KKK
0,820,560,35
0,890,630,41
1,110,820,52
Water (°C) Air (°C) 25-18 26-18.5 28-20 Water (°C) Air (°C) 25-18 26-18.5 28-20Total emission Sensible emission
6
SkyStarEmission
Cooling emission of 1 battery units (2 pipe installation)Entering air temperature: +27°C d.b. +19°C w.b.
Heating emission of 1 battery units (2 pipe installation)Entering air temperature: +20°C
Note:
the correctionfactors are indicative,as they areaverage values.
Emission correction factors for different working conditions.Multiply the factors by the emission figures in the 7-12°C table above.
Model SpeedAirflow
EWT 45 - LWT 40°C EWT 50 - LWT 40°C EWT 60 - LWT 50°C EWT 70 - LWT 60°C EWT 80 - LWT 70°C
l/hm3/h kW l/h kW l/h kW l/h kW l/h kW
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
2562151662832471963512771964023172477716095019296865471074845547
1,491,250,961,651,441,142,041,611,142,341,841,444,483,542,915,403,993,186,244,913,18
13411387149130103184146103211166130410324267493365291569449291
1,561,311,011,731,511,202,141,691,202,451,941,514,763,773,115,734,253,396,615,223,39
197166128218191151270214151310244191596471388718531423829653423
2,291,931,492,542,221,763,142,481,763,602,842,226,935,484,518,346,174,929,647,604,92
2612191692982602093782982094263412677836185089466975551092858555
3,032,541,963,463,022,434,403,462,434,953,973,109,107,195,9111,008,106,4512,709,986,45
325272210358312247444350247510401312970766629117086468613531064686
3,783,172,444,173,632,875,174,072,875,934,673,6311,288,907,31
13,6010,047,98
15,7412,377,98
6104203105204203107105003208806104301140820630150097071018201280710
HighMedLowHighMedLowHighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
SK 14
SK 24
SK 34
SK 44
SK 54
SK 64
SK 04
HighMedLowHighMedLowHighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
490410314569465398718569398791632510129910278421588115892018361423920
2,852,381,823,312,712,314,183,312,314,603,672,977,555,974,899,236,735,3510,678,275,35
2,121,731,292,261,831,552,912,261,553,232,532,015,124,003,246,354,533,567,435,643,56
4013372604654053185744553186565204051090866713132797477815291191778
2,331,961,512,702,361,853,342,651,853,813,022,366,345,034,147,715,664,528,896,934,52
1,901,551,151,981,701,342,561,981,342,972,291,754,693,652,965,834,153,256,845,183,25
30726020137430926746737426751241333786469157210467756231199942623
1,781,511,172,181,801,552,722,181,552,982,401,965,024,023,336,084,503,626,975,483,62
1,691,371,021,791,441,222,301,791,222,562,001,594,043,152,565,023,572,815,984,462,81
2391961482602101773302601773662882315864623747,26524411849646411
1,391,140,861,511,221,031,921,511,032,131,671,353,412,682,174,223,052,394,943,752,39
1,391,140,861,511,221,031,921,511,032,131,671,353,412,682,174,223,052,394,943,752,39
6104203105204203107105003208806104301140820630150097071018201280710
EWT 5 - LWT 10°C EWT 7 - LWT 12°C EWT 9 - LWT 14°C EWT 12 - LWT 17°CWaterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Model SpeedAirflow
l/h kW kW l/h kW kW l/h kW kW l/h kW kWm3/h
SK 14
SK 24
SK 34
SK 44
SK 54
SK 64
SK 04
7/12 °C10/15 °C14/18 °C
KKK
0,90,720,5
0,940,780,58
1,060,90,72
7/12 °C10/15 °C14/18 °C
KKK
0,820,560,35
0,890,630,41
1,110,820,52
Water (°C) Air (°C) 25-18 26-18.5 28-20 Water (°C) Air (°C) 25-18 26-18.5 28-20Total emission Sensible emission
7
SkyStarEmission of 4 pipe unitswith standard cooling battery
Note:
the correctionfactors are indicative,as they areaverage values.
Emission correction factors for different working conditions.Multiply the factors by the emission figures in the 7-12°C table above.
Cooling emission of 2 battery units (4 pipe installation)Entering air temperature: +27°C d.b. +19°C w.b.
Heating emission of 2 battery units (4 pipe installation)Entering air temperature: +20°C
710500320880610430150097071018201280710
279226165315255205720541441824651441
1,621,320,961,831,481,194,183,142,564,793,792,56
13911383156127103493365291569449291
1,611,320,971,821,481,204,333,272,676,615,223,39
213173127241195157554416340633501340
2,482,011,472,802,271,836,444,843,957,365,833,95
288233170326263212736552450843666450
3,352,711,983,793,062,468,566,425,239,807,745,23
3632942144113322669196895611053831561
4,223,422,494,783,863,1010,698,016,5212,249,666,52
SK 26HighMedLow
SK 36HighMedLow
SK 56HighMedLow
SK 66HighMedLow
Model SpeedAirflow
EWT 45 - LWT 40°C EWT 50 - LWT 40°C EWT 60 - LWT 50°C EWT 70 - LWT 60°C EWT 80 - LWT 70°C
l/hm3/h kW l/h kW l/h kW l/h kW l/h kW
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
710500320880610430150097071018201280710
812629425940729557180412911012210516071012
4,723,662,475,464,243,2410,497,505,8912,249,345,89
3,292,511,663,862,932,217,255,083,948,576,413,94
6765263597796074681508108985817541348858
3,933,062,094,533,532,728,776,334,9910,207,844,99
2,952,241,493,462,621,976,494,553,537,685,733,53
528415287606477370118986768913751066689
3,072,411,673,522,772,156,915,044,007,996,204,00
2,601,971,313,052,311,735,724,003,106,775,053,10
378288192442337256836587459987739459
2,201,671,122,571,961,494,863,412,675,744,302,67
2,201,671,122,571,961,494,863,412,675,744,302,67
SK 26HighMedLow
SK 36HighMedLow
SK 56HighMedLow
SK 66HighMedLow
EWT 5 - LWT 10°C EWT 7 - LWT 12°C EWT 9 - LWT 14°C EWT 12 - LWT 17°CWaterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Model SpeedAirflow
l/h kW kW l/h kW kW l/h kW kW l/h kW kWm3/h
Cooling emission of 2 battery units (4 pipe installation)Entering air temperature: +27°C d.b. +19°C w.b.
Heating emission of 2 battery units (4 pipe installation)Entering air temperature: +20°C
7/12 °C10/15 °C14/18 °C
KKK
0,90,720,5
0,940,780,58
1,060,90,72
7/12 °C10/15 °C14/18 °C
KKK
0,820,560,35
0,890,630,41
1,110,820,52
Water (°C) Air (°C) 25-18 26-18.5 28-20 Water (°C) Air (°C) 25-18 26-18.5 28-20Total emission Sensible emission
8
SkyStarEmission of 4 pipe unitswith enhanced cooling battery
Note:
the correctionfactors are indicative,as they areaverage values.
Emission correction factors for different working conditions.Multiply the factors by the emission figures in the 7-12°C table above.
°CK
20
0,94
30
0,90
40
0,86
50
0,82
60
0,78
70
0,74
80
0,70
°CK
40
1,14
50
1,08
60
1,02
70
0,96
80
0,90
°CK
20
0,94
30
0,90
40
0,86
50
0,82
60
0,78
70
0,74
80
0,70
Water flow
Air flow
Supply
MAX. working pressure8 barsSuitable relative humidity15 - 75%Single phase 230V 50Hz
MIN. entering water temperature: + 5°CMAX. entering water temperature: + 80°CMIN. entering air temperature: 6°CMAX. entering air temperature: 40°C
Installation MAX. height: See table on page 12
Pressure dropfor mean water temperature of 10°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Pressure dropfor mean water temperature of 65°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Working conditions
Pressure dropfor mean water temperature of 10°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Pressure dropfor cooling battery
Pressure dropfor heating battery
2 pipe installation
4 pipe installation
9
SkyStarWater side pressure drop
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
790 350 750 150
A B C Dmm
30 246 3
kg kg
Weightspacked unit
Weightsunpacked unit
SK 02 - 12SK 04 - 14SK 22 - 24 - 26SK 32 - 34 - 36
28 22
UNIT DIFFUSER
kg kg
ModelWeights
packed unitWeights
unpacked unit
Packed unitDimensions
MD-600METAL DIFFUSER
(receiver kitIRC-MD code 9060178for MD diffuserfor infra-red units)
SK 02-04 / SK 12-14 / SK 22-24-26 / SK 32-34-36 (Version 600 x 600)
10
SkyStarDimensions and weights
2 pipe units- 3. Flow, heating/cooling 1/2”
- 4. Return, heating/cooling 1/2”
4 pipe units- 1. Flow, heating 1/2”- 2. Return, heating 1/2”- 3. Flow, cooling 1/2”- 4. Return, cooling 1/2”
Packed unitDimensions
1050 400 1000 200
A B C Dmm
47 3910 6
kg kg
Weightspacked unit
Weightsunpacked unit
SK 42SK 44SK 52 - 54 - 56SK 62 - 64 - 66
44 36
UNIT DIFFUSER
kg kg
ModelWeights
packed unitWeights
unpacked unit
PACKED UNIT
SK 42-44 / SK 52-54-56 / SK 62-64-66 (Version 800 x 800)
11
SkyStarDimensions and weights
UNIT DIFFUSER
2 pipe units- 3. Flow, heating/cooling 3/4”
- 4. Return, heating/cooling 3/4”
4 pipe units- 1. Flow, heating 1/2”- 2. Return, heating 1/2”- 3. Flow, cooling 3/4”- 4. Return, cooling 3/4”
SpeedAir throw L m
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 33,0 3,5 3,8 3,0 3,8 4,5 3,5 4,2 5,0 3,2 3,7 4,3 3,4 4,0 5,0 3,4 4,6 5,5
Model SK 02-04-12-14 SK 22-24-26 SK 32-34-36 SK 42-44 SK 52-54-56 SK 62-64-66
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 33,32,22,5
3,92,62,9
4,22,83,1
3,32,22,5
4,22,83,1
4,83,23,6
3,92,62,9
4,53,03,4
5,23,43,9
3,52,22,7
4,12,63,2
4,83,03,8
3,82,43,0
4,62,83,6
5,43,44,2
3,82,43,0
5,13,14,0
5,83,64,6
SpeedAir throw L mHeight H mDistance B m
Model SK 02-04-12-14 SK 22-24-26 SK 32-34-36 SK 42-44 SK 52-54-56 SK 62-64-66
12
SkyStarAir throw
The air throw indicated in the tables must only be considered the maximum value, as it maychange significantly in relation to the dimensions of the room in which the appliance is installedand the positioning of the furniture in the room.
The useful throw L refers to the distance between the unit and the point where the air speedis 0.2 m/sec; if the louver has a gradient of 30° (recommended in cooling mode), the so-called“Coanda” effect will occur, illustrated in the first figure, while at a gradient of 45° (recommendedin heating mode), there will be a downwards throw, as illustrated in the second figure.
With adjustableair diffusion louvers at 30°
With adjustableair diffusion louvers at 45°
NOTE:On heating it must be payed attention to rooms where the floor temperatureis particularly low (for example less than 5°C).In this situation the floor can cool the lower layer of air to a level that stopthe uniform diffusion of the hot air coming from the unit,decreasing the throw figures shown in the table.
13
SkyStar
Spigot
for air distribution
MAIN AIR INLET
AIR INTAKE
Two air outlets are providedon the side of the unit for connectionto separate supply air outlets.
They can be used to supply air fromthe fan coil unit to distant areas of a roomor even to a different room.
The total air flow does not change.
The air flow at high speed dependingon the air duct pressure drop is shownin the tables below.
Note: all air ducts must be insulatedin order to avoid condensation.
Air distribution - Air distribution connection
No. used outlets = 1 No. used outlets = 2
Air flow (m3/h)
Air flow (m3/h)
Air flow (m3/h)
Air flow (m3/h)
Pre
ssur
e dr
op (
Pa)
Pre
ssur
e dr
op (
Pa)
Pre
ssur
e dr
op (
Pa)
Pre
ssur
e dr
op (
Pa)
The cassette is fittedwith inlets for fresh air to be mixedwith return air inside the unit (Fig. 3).
The fresh air flow is limited to 20%of the total fan coil air flow at medium speedand 100 m3/h for each treated air inlet.
The units feature fresh air inletson three corners (no inlets on the fourth cornerbecause of the condensate pump inside the unit).
The fresh air inlets are designed for the insertion of standard 110 x 55 mm rectangular ducts.
The air duct is connected quickly and easily. After removing the blank and the insulation inside the unit,the mounting plate is rolled back and the air duct with its V-shaped sectionmust be pushed into the unit (see Figures below). The duct is then fixed to the mounting plate.
Note: the fresh air must be filtered.
Accessory “Fresh air connection” - Identification CAP - Code 6078005 (see page 14)
AIR DISTRIBUTION
AIR INTAKE
Fresh
air connection
MAINAIR INLET
AIR INTAKE
1 2 3 4
Fresh air supply - Fresh air connection
Fresh air kitThis is used to introduce primary air into the environment directly through the diffuser. The kit includes a flow separatorto be fitted inside the cassette, and a circular fitting for connection to the flexible system ducting. The flow of air is sentdirectly to just one of the outlet louvers, without passing through the coil. The
air flow of fresh air introducedinto the environment dependon the inlet static pressure.
14
SkyStarAccessories
PRT 800
SK 4-5-6
9079231
PRT 600
SK 0-1-2-3
9079230
IDENTIFICATION
MODEL
CODE
SK 0-1-2-3 SK 4-5-6
160200300400500
80120160200240
m3/hm3/h
38152536
38152536
PaPa
The diameter of the fittingis 150 mm for SK 0 - 1 - 2 - 3and 180 mm for SK 4 - 5 - 6.
The diameter of the fittingis 150 mm for SK 0 - 1 - 2 - 3and 180 mm for SK 4 - 5 - 6.
Units with remote electric boardOn request the Skystar cassettes are available with electric control panel reachable from below and with the electricboard that can be placed in a remote position. In this case the units are supplied with an electronic connecting controlpanel, fitted to the bottom side on the 4 smallest sizes and to the lateral side on the 3 biggest sizes.The electronic control panel is connected to the fan motor, to the condensate pump and to the condensate level control.A 6 m wire is also supplied with integral plug-in connections toconnect the unit with the remote electric board that can be installedin a suitable and comfortable position, where the power and systemconnections can be made easily.This feature is not available for units with electric heater or infra-red remote control.
Fresh air connectionSee page 13.
Air distribution connectionSee page 13.
IDENTIFICATION CODE
CAP 6078005
CDA 800 9079233
CDA 600 9079232
IDENTIFICATION CODE
Correlation between flow-rate / static pressure
Rated pressure:
Max. ambient temperature:
Max. water flow temperature:
Power:
Rating:
Protection:
Travel time:
Max. glycol content of water:
16 bar
50 °C
110 °C
230 V - 50/60 Hz
3 VA
IP 43
approx. 3 min.
50%
3 ways 2 ways
3 ways 2 ways
15
SkyStarAccessories
Valve set, 2 or 3 ways, ON-OFF, with thermoelectric actuator.The set includes connection pipes.
Note: The main battery lockshield valve connection is 1/2” female (Kvs 2) for SK0 - SK1 - SK2 - SK3 sizes and 3/4” female (Kvs 3,5) for SK4 - SK5 - SK6 sizes, the auxiliary battery valve connection is 1/2” female (Kvs 2).
Note: The maximum pressure drop accross the fully open valve should not exceed 25 kPa for cooling operation and 15 kPa for heating operation.
Technical data: Valves characteristics
Valves pressure drop
Waterflow (l/h)
Δp - kPa
* maximum pressure difference for valve to close ** external thread, flat sealNote: 3 way valves with simplified kit and 1” connection have conical seal.
Batterytype
Main
Model
Auxiliary
02-12-22-32
04-14-24-26-34-36
42-52-62
44-54-56-64-66
04-14-24-26-34-36
44-54-56-64-66
2 way valves 3 way valves
Kvs
m3/h�pmax
kPa *Valve **
connectionKvs
m3/h�pmax
kPa *Valve **
connection
2,8
5,2
2,8
50
60
50
3/4"
1"
3/4"
2,5
4,5
2,5
50
50
50
3/4"
1"
3/4"
ON-OFF valves with thermoelectric actuatorVALVE WITH MICROMETRIC LOCKSHIELD VALVE
VALVE WITH SIMPLIFIED KIT
Cassette SkyStar can be equipped with the innovativeplate type electrostatic filter, Crystall, combining airtreatment and purifying in a single product.The electronic filter is patented and certified accordingto Standard UNI 11254.
Introduction
16
SkyStar
Dimensions
SK 0 / 1 / 2 / 3(Model 600 x 600)
SK 4 / 5 / 6(Model 800 x 800)
CRYSTALL
When the polluted air goes through themechanical pre-filter the particles � 50 μ areeliminated (powder, insects, etc).
Then the smallest particles (50 ÷ 0.01 μm) areexposed to an intensive ionizing field and are polarized (Phase 1).
The charged particles passing through the second filter section, arepushed back by the anode and attracted to the collection surfacesby a strong, induced magnetic field (Phase 2).
The air which leaves the unit is free from polluting particles.INLET
OF POLLUTED AIR
OUTLETOF CLEAN AIR
PHASE
2
PHASE
1
Air withoutparticles < 1 μm
Air withoutparticles ≥ 50 μm
Pre-filter
Electrostaticfilter
Collectionsurface
Inductedanode
Polarizedelectrode
Ionic field
Eliminationof the biggestparticles
houμm
El t t ti
ha
Air withparticles < 1 he
are
Operating principleof the electrostatic filter
The expression Indoor Air Quality (IAQ) covers all the procedures and methodologies used to improve thequality of the air we breathe in the places where we live and work, from all points of view, from temperatureto cleanliness, to relative humidity, etc. (EN 15251 and EN 13779). Thanks to its new patented electronic filter,the Crystall electrostatic filter totally eliminates the pollutants present in the air, including tobacco smoke,dust (PM10, PM2.5), fibres, microbiological substances such as bacteria, fungi, etc., which are harmful to humanhealth (source: OMS 2009). Purifying the air means not only greater well-being, but also energy saving, as thefresh air changes that are required to restore ideal climatic conditions and that entail greater consumption, aresignificantly reduced (it is sufficient to enter the quantity of air required to restore the optimum level of CO
2 - source:
EN 1379:2008). Moreover, according to the UNI 10339rev, air recirculated by the Crystall appliance can beconsidered as fresh air, to be added to the minimum requirements (0,5 ls/m2). Purifying the air with the SabianaCrystall appliance also entails no reduction of living room space, as the dimensions of the fan convectorare practically unchanged (just 3 cm higher). The positioning of the electronic filter allows simple and effectivemaintenance and, as it is easy to wash, its working life is practically unlimited. The modularity of the filtercomponents and their ease of mounting make the system extremely competitive in terms of cost comparedwith other types of filters present on the market. In spring and autumn, if air conditioning/heating is not required,the appliance acts simply as an air purifier.
Indoor air quality (IAQ)
THE AMBIENT CONDITION IS ACCEPTABLE WHEN:• Microclimatic parameters are normal• 80% of people are satisfied by the quality of air• Specific internal contaminants are not in harmful concentrations
“Guidelines for the protection and promotion of health in confined areas O.G.No. 276 dated 27 Nov 01 ordinary supplement no. 252”
The method for obtaining the air quality required in confined areas and thus succeeding in ensuring that thecontaminants present are in concentrations less than those considered dangerous to health are:Prescriptive approach: ventilation of the internal area using only properly filtered fresh air, in the quantity and quality needed to dilute the internal contaminants in order to reach the required maximum acceptable concentration values (see WHO limits).
Performance approach: ventilation with fresh air and recirculated air from the same area, both properly filtered, in the quantity and quality needed to dilute the internal contaminants in order to reach the required maximum acceptable concentration values (see WHO limits).
Standards and legislation
17
SkyStarCRYSTALL
High
Medium
Low
not classified
(l.s. per person) + (l.s. per m2)
(l.s. per person) + (l.s. per m2)
(l.s. per person) + (l.s. per m2)
not classified
Total fresh air volume variesbased on the intended use
of the confined area
UNI EN 13779:2008
IDA 1
IDA 2
IDA 3
IDA 4
> 15
10 − 15
6 − 10
< 6
20
12,5
8
5
PR
ES
CR
IPT
IVE M
ET
HO
D CATEGORYTIPICAL RANGE DEFAULT VALUE
RATE OF FRESH AIR
l.s. person
l.s. person
l.s. person
l.s. person
UNIT
UNI EN 10339REV
RATE OF FRESH AIRCATEGORY
WHO publicized valuesand legislative acts expressed
in μg/m3, PPM, etc.5 - 6
The volume of air to be consideredis based on the internal production
and the imposed concentration limitsin the confined area
ConcentrationLimit
Minimum fresh airl.s. person
Quantity of recirculated airprovided that it is filtered like fresh air
PE
RF
OR
MA
NC
E M
ET
HO
D
UNI EN 13779:2008IDENTIFICATION AND QUANTIFICATION OF THE REFERENCE POLLUTANT (PM OR GAS)
WHO publicized valuesand legislative acts expressed
in μg/m3, PPM, etc.
The minimum volume of air inputvaries based onthe intended use
of the confined area
The volume of air to be consideredis based on the internal production
and the imposed concentration limitsin the confined area
ConcentrationLimit
Minimum fresh airl.s. person
Quantity of recirculated airprovided that it is filtered like fresh air
UNI EN 10339REV
IDENTIFICATION AND QUANTIFICATION OF THE REFERENCE POLLUTANT (PM OR GAS)
18
SkyStarCRYSTALL
UNI EN 13779:2008 and UNI 10339rev StandardsThe example reproduced at the bottom of the page shows how, with adequate air filtering, it is possible todecrease considerably the quantity of fresh air to be brought into the environment (up to 3-4 times less); thethermal energy dissipated due to ventilation is in fact in direct proportion to the number of air changes, asindicated in the following equation: Qv = ΔT · R · D · C · Vol. 3600Qv = Thermal energy lost for ventilation - WattΔT = Indoor-Outdoor difference (T) - °CR = A.C.H.D = Air density - Kg/m3
C = Specific air heat - J/Kg-°CVol = Room size - m3
Fresh air flow rates according to the performance approach
The quantity and quality of recirculated air and outdoor air to be added is better specified in the prescriptive andperformance approach in Standards UNI EN 13779:2008 and soon to be released UNI 10339rev according tothe following simplified tables.
The Crystall electrostatic filtering system consists of two parts: the first is a plate type electronicactive filter and is fitted in the return air section of the cassette, while the second is an electroniccontrol and regulation board, fixed on the structure.All electrical connections are made during production. The installation of the SkyStar Sabianacassette fan coil unit incorporating the Crystall electronic filter is therefore similar to that of anormal unit: the only difference is the installation height, for which the filter dimensions musttaken into account.Crystall filters are not suitable for ECM and electric heater versions.
Active plate type electronic filter
The filtering element consists of two sections:the first consists of electrodes and insulatingelements, forming a self-supporting ionisingframe, while the second consists of speciallight aluminium fins (collector).The two sections are installed above the return airgrille to make the extraction and maintenanceof the filter easier.Accessibility to sections to be cleaned is ensuredby easy-open plastic closures.The collector can be cleaned by washing withwater and ordinary detergents or steam jets(please consult the maintenance manual forfurther details).
Electronic board
Controls and regulates all functions of theelectrostatic filter.It is appropriately protected against any operatingdefects of the electrostatic filter. It supplies aconstant voltage to the electrodes when the mainssupply voltage varies (± 15%).The supply transformer is constructed with itsprimary and secondary coils physically separatedand wound onto separate cores.The energy consumption of the filter group is25 W (to which the electrical consumption of theCassette must be added).
Control and regulation commands
Units with Crystall electrostatic filter can becontrolled and regulated by the series of IAQcontrols that are already provided for CRCCarisma fan coils.
Construction features
19
SkyStarCRYSTALL
1 - Diffuser with return air grid2 - Active plate type electrostatic filter3 - Plastic opening4 - Insulation5 - Filter containment frame6 - Electronic board7 - Cassette
Dimensions: 133x93x37 mm
Dimensions: 133x93x37 mm
Dimensions: 133x93x37 mm
20
Wall electronic controls
If using the Skystar Cassette fan coils with electronic controllers,the voltage values at the autotransformer terminals
must be kept in consideration (transformer return voltages).These values may reach 500 Vac.
• ON-OFF switch.• Manual 3 speed switch.• Manual Summer/Winter switch.• Electronic room thermostat for fan control (ON-OFF).• Electronic room thermostat for valve control (ON-OFF) (the fan keeps working).• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater in the SK-E version.• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).The latter case needs the adjustment of the jumper on the control board (see the instruction leaflet supplied with the control).
IDENTIFICATION CODE
TMO-T 9060161
• Manual 3 speed switch.• Without thermostatic control.• It can not control the valves.
IDENTIFICATION CODE
MO-3V 9060160
• ON-OFF switch.• Manual 3 speed switch.• Manual Summer/Winter switch.• Electronic room thermostat for fan control (ON-OFF).• Electronic room thermostat for valve control (ON-OFF) (the fan keeps working).• It allows to control the low temperature cut-out thermostat (TMM).• It allows to control the chilled water valve (ON-OFF) and the electric heater in the SK-E version.
IDENTIFICATION CODE
CR-T 9066330
Dimensions: 128x75x25 mm
Dimensions on the wall: 133x93x27 mmDimensions in the DIN 503 box: 133x93x18 mm
Dimensions: 118x87x8 mm
Dimensions: 133x93x37 mm
21
SkyStarWall electronic controls
2 pipes units only.
• ON-OFF switch.• 3 speed switch.• Manual Summer/Winter switch.• Thermostatic control on the fan.• Thermostatic control on the valve and continuous fan operation.• Simultaneous thermostatic control of the valve and fan.• Cannot be used with speed switch (master-slave).
IDENTIFICATION CODE
T2T 9060174
To be installed on the wall or in the DIN 503 box.
• Manual or automatic speed switch.• Manual or centralized Summer/Winter switch.• Electronic thermostat for fan control (ON-OFF).• Electronic thermostat for valve control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat (TME) (not to be used with SK-E models).• It allows to control the chilled water valve (ON-OFF) and the electric heater in the SK-E version.• It allows to control the fan and the electric heater.• It allows to control up to 10 units with SEL-DI speed switch.
N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).
IDENTIFICATION CODE
TMO-DI 9060165
The TMO-503-SV2 control for fan coils with valves, is designed to be installed in a DIN 503 wall box.It is easy to use, it has a big and clear display, and a great precision.The control is supplied integral with the external frame, but it is possible to use frames of the mostknown brand on the market (BTicino, Vimar, AVE, Gewiss).The highest working electric absorbtion is 200 W.If the fan coil has an higher absorbtion or more units are connected to the same control, the speedswitch SEL-S must be installed.
• Manual or automatic speed switch.• Manual Summer/Winter switch.• Electronic thermostat for valves control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat, included with the control.
N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).
IDENTIFICATION CODE
TMO-503-SV2 9060173
• ON-OFF switch.• Manual or automatic 3 speed switch.• Summer/Winter switch.• Electronic room thermostat for fan control (ON-OFF).• Electronic room thermostat for valve control (ON-OFF) (the fan keeps working).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater in the SK-E version.• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).The latter case needs the adjustment of the jumper on the control board (see the instruction leaflet supplied with the control).
N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).
IDENTIFICATION CODE
TMO-T-AU 9060164
22
SkyStarSpeed switches
• Speed switch (Slave).• It allows to control up to 8 units with only one centralized wall control (1 speed switch for each unit).• For controls CR-T, TMO-T, TMO-T-AU and TMO-503-SV2.
• Speed switch (Slave) for TMO-DI• It allows to control up to 10 units with only one TMO-DI centralized wall control.
TME low temperature cut-out thermostatSuitable for wall controls only (not infra-red remote control). To be fitted between the coil fins;when connecting the control, the TME probe cable must be separated from the power supply wires.To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI.It stops the fan when the water temperature is lower than 38°Cand it starts the fan when is higher than 42°C.
Change-Over CH 15-25Suitable for wall controls only (not for infra-red remote control).Automatic summer/winter switchto be installed in contact with the water circuit.For 2-tube installations only (not to be used with 2 way valve).To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI.
TMM low temperature cut-out thermostatTo be installed in contact with the hot water circuit.To be used only with CR-T control.For units working on heating only.It stops the fan when the water temperature is lower than 30°Cand it starts the fan when is higher than 38°C.
BLACK
RED
BROWN
RED
IDENTIFICATION CODE
CH 15-25 9053049
IDENTIFICATION CODE
TME 3021091
IDENTIFICATION CODE
SEL-S 9079110
IDENTIFICATION CODE
SEL-DI 9060139
Wall electronic control accessories
IDENTIFICATION CODE
TMM 9053048
CO
NT
RO
L C
OD
ES
CO
NT
RO
LO
PE
RA
TIO
NS
CO
NT
RO
LID
EN
TIF
ICA
TIO
N9060174T2T
TMO-DI
TMO-503-SV2
TMO-T-AU
TMO-T
CR-T
9060165
9060173
9060164
9060161
9066330
MO-3V 9060160
Inst
alla
tion
of e
lect
roni
c lo
w t
empe
ratu
re C
UT
-OU
T t
herm
osta
t (T
ME
)
Roo
m t
herm
osta
t fo
r fa
n an
d el
ectr
ic h
eate
r co
ntro
l
Roo
m t
herm
osta
t fo
r ch
illed
wat
er v
alve
(S
UM
ME
R)
and
elec
tric
hea
ter
(WIN
TE
R)
cont
rol
(in w
inte
r on
ly t
he e
lect
ric h
eate
r is
wor
king
)
Sim
ulta
neou
s th
erm
osta
tic c
ontr
ol o
f th
e va
lves
and
fan
Roo
m t
herm
osta
t fo
r 2
valv
e co
ntro
l (4
pipe
inst
alla
tion)
Roo
m t
herm
osta
t fo
r 1
valv
e co
ntro
l (2
pipe
inst
alla
tion)
Roo
m t
herm
osta
t fo
r fa
n co
ntro
l (O
N-O
FF
)
Aut
omat
ic S
umm
er/W
inte
r sw
itch
with
neu
tral
zon
e fo
r 4
pipe
inst
alla
tion
with
2 v
alve
s
Rem
ote
cent
raliz
ed S
umm
er/W
inte
r sw
itch
or b
y an
aut
omat
ic c
hang
e-ov
er f
itted
on
the
wat
er p
ipe
Sum
mer
/Win
ter
switc
h
Man
ual/A
utom
atic
3 s
peed
sel
ectio
n
Man
ual 3
spe
ed s
witc
h
ON
-OF
F s
witc
h fo
r el
ectr
ic h
eate
r
ON
-OF
F s
witc
h
Inst
alla
tion
of b
imet
allic
low
tem
pera
ture
CU
T-O
UT
the
rmos
tat
(TM
M)
Electrical diagramsare shown on the installation, use and maintenance manual
23
SkyStarControl functions
24
SkyStarFreeSabiana wireless control system
FreeSabiana
Free Sabiana is an innovative, fully wireless, electronic system for use withfan coil units, based on radio communication.
This technology provides installation flexibility and a more accuratemeasurement of the room temperature. The probe can be moved untilthe most suitable position is found, without the worry of changes in theenvironment layout and of its furniture and also without mounting it on a wall.If a new fan coil unit is added, no electrical wiring for the control system is
required: just define the control unit and the probe which regulates it. The improved measurement accuracy derivesfrom the possibility to position the probe near the typical location of the user: this enables to keep the temperatureexactly at the required value with more energy savings compared with a traditional measurement system.
Transmission is based on communication protocol IEE802.15.4, the most suitable way to transmit a relatively lowamount of information with very low consumption and high reliability.
The system has been certified by a leading independent body, officially recognized by the EU authorities and itssale has been authorized in all the EU and EFTA countries.
required: just define the control unit and
Control unit with support
Power unit
Probe with support
A remote control which features a button panel andLCD display and can be wall mounted or positionedon a dedicated table support.It enables the control of all the operating variables ofthe fan coil units in different configurations. The controlis battery powered.The temperature and the operating speed of the fancoil unit are set with two large buttons featuring userfriendly graphics.
A power unit to be installed on the fan coil (fan coilinterface).It controls the fan and the valves of the fan coil. Thepower unit is connected to the electric supply.The power unit receives the information required tocontrol the fan coil both from the remote control andlocally, such as the temperature of the coil.
A room temperature probe, which can be wallmounted or positioned on a dedicated table support.It is a battery powered device, able to measure the airtemperature in the spot where it is positioned, generatingtemperature information which is communicated to theother devices.
Main components
Free Sabiana includes 3 main components:
❍
❍
❍
Power unit fitted on the unit
Power unit not fitted on the unit
DESCRIPTION
Free-Usm 9079107
Free-Ups 9060570
IDENTIFICATION CODE
Temperature probe
DESCRIPTION
Free-Sen 9060573
IDENTIFICATION CODE
Remote control
DESCRIPTION
Free-Com 9060572
IDENTIFICATION CODE
25
SkyStarFreeSabiana wireless control system
The power unit controlsthe fan and the valves of the fan coil.The power unit receives the informationrequired to control such unitsboth from the remote control and locally.
This device is able to measurethe temperature of the air in the spotwhere it is positioned and to transmit itby means of radio communication tothe other devices in the system.It is battery powered and can befreely positioned in the area
to be air-conditioned.
On-off statusSummer operationWinter operationAutomatic season changeElectric heaterCrystall filterRoom temperature(with decimal accuracy)
Fan operating speedRequired/measured temperatureTimerClockTransmission signalBattery level
❍ Fan coil on/off switching❍ Fan speed selection (high - medium - low - automatic)❍ Summer/winter operation selection❍ Valve on/off❍ Real time clock setting❍ Temperature setting❍ Daily switch on/off setting (timer function)❍ Enable/disable the timer function❍ Activation of the (eventual) electrostatic filter❍ Activation of the (eventual) electric heater
The control enables:
Main features of the remote control
Main information displayed:
Main features of the power unit to be installed on the fan coil
Main features of the temperature probe
12 10 11 138
1 2 3 7 4 5 6
9
1
2
3
4
5
6
7
8
9
10
11
12
13
❍ Fan on/off at a set speed❍ Fan speed change (fan on/off)❍ Water valve/s on/off (1 valve for 2 tube system - 2 valves for 4 tube system)
❍ Fan speed change operating the water valve/s❍ Control of the electric heater as main heating unit or as integration to the battery supplied with hot water❍ Control of the operation of the electrostatic filter (in parallel to the fan)
❍ Management of the dead zone function for 4-tube systems❍ Available functional inputs: • Consent for remote on/off • Consent for remote Summer/Winter switch (centralized)
• Consent for the activation of the Energy Saving function with setting change • Minimum probe • Probe for season change
It enables the following main actions:
❍ Measured environment temperature❍ Transmission signal❍ Clock❍ Battery status
Display:
T
It enables the foll
T
It enables the fol
TT
RT03 infra-red remote control
PSM-DI multifunction control
Sabianet software
Sabianet screenshot
PC
T-MB wall mounted control
All the controls for the ECM version and their functionsare described in detail from Page 43.
All the SkyStar units can be supplied in MB version. This version includesa wide range of controls, including the infra-red remote control, which allows managing one single unit
or several units by using the Modbus RTU - RS 485 communication protocol.
Units can be managed according to the Master/Slave logic (up to 20 units)or by supervisory components.
The system consists in a MB power board (mounted on models SK–MB and SK–ECM–MB)and a series of devices, such as the T-MB wall mounted control, the RT03 infra-red remote control,
the PSM-DI multifunction control and the Sabianet supervisory program.
26
SkyStarControls for SK–MB versions
27
SkyStar
The SkyStar 2 pipe models are available with electric heater that is controlled in place of the heating battery valve.
The electric heater is controlled in place of the hot water valve and not as integration to it.
The heater is hermetically sealed and supplied inside the battery pipes and therefore can be only factory mounted.
The electric heaters of the SK 12-22-32 units are for single phase 230V supply.
The electric heaters of the SK 42-52-62 units are for three phase 400V supply.
A specific electronic board is fitted in the unit control panel and it is connected to the heater and to the safetythermostat.
When the safety thermostat operates, it keeps open the heater supply relays on the electronic board.
The rearmement is by electric means, cutting off the supply to the unit.
Note: the cooling emission of the units is 95% of the emission in the tables of page 6.
Electric diagrams
LEGEND
IG = Main switchTS = Safety thermostatR1 = Heater 1R2 = Heater 2R3 = Heater 3
Electric heater SK-E
Model
Emission
Supply
Number and Dia. of connecting wires
SK 12-E SK 22-E / SK 32-E SK 42-E / SK 52-E / SK 62-E
1500 Watt
230V ~
3 x 1,5 mm2
2500 Watt
230V ~
3 x 2,5 mm2
3000 Watt
400V ~
5 x 1,5 mm2
Control
Control
Cleancontact
Cleancontact
Fuse
FuseFuseFuse
MODELSSK 12/22/32
MODELSSK 42/52/62
Max. ambient temperature for Cassette unit with electric coil in heating mode: 25°C
Cassette unit operating limits with electric coil
The SkyStar ECM series uses an innovative brushless synchronous permanent magnet electricmotor controlled by an inverter card that is directly installed on the unit.
The air flow can be varied continuously with a 1-10 V signal from Sabiana controls or byindependent contollers (programmable controllers with a 1-10 V output).
The extreme efficiency, also at a low speed, makes possible a great reduction in electricconsumption (more than 75% less in comparison to a traditional motor) with absorptionvalues, under normal operating conditions, that are no greater than 10 Watt in the entire range.
The brushless motor is characterised by a constant synchronous speed, independently of theapplied load, that depends only on the motor power supply frequency, which is modulated bythe inverter. It consumes less because:
• The motor always works at its point of maximum efficiency.
• In the brushless motor, the rotor’s permanent magnets generate the magnetising power autonomously.
• The motor always operates at the synchronous speed, as a result there are no induced currents that reduce efficiency.
The main advantages are:
• Large reduction in energy consumption, thanks to an optimal response to the thermal load of the environment during every moment of the day.
• Operating silence at all rotation speeds.
• Ability to operate at any rotation speed.
Introduction
SkyStar ECM
28
SkyStarSkyStar ECM
= SK = SK-ECM
MOTOR ABSORPTION
INTAKE GRID AND DISTRIBUTION OF THE AIRIntake grids, frame and adjustable air distribution louvers on each side, made from ABS.HTA version : white ABS, RAL 9003HTB version : with intake grid, frame and louvers, choice of one colour onlyHTC version : with intake grid and louvers, choice of one colour, plus white ABS frame RAL 9003HTD version : with louvers, choice of one colour, while the grid and frame are made from ABS, RAL 9003MD-600 version : metal diffuser painted in RAL 9003 white colour with 600x600 dimension to perfectly fit into the false ceiling standard modules without overlapping parts (800x800 model is not available).
CASINGIs made from galvanized steel with inside thermal insulation with polyolefin (PO) foam (class M1) andoutside anti-condensate lining.
CONTROL EQUIPMENTSK–ECM version It consists of the pump control circuit board and the inverter circuit board.
SK–ECM–MB version It consists of the MB electronic board (that integrates pump control) and the inverter board.
FAN ASSEMBLYThe fan assembly, which is mounted on anti-vibrating supports, is extremely silent.The radial fan has been designed to optimise performance, using wing profile blades with a shape thatreduce turbulence, increasing efficiency and reducing noise.The fans are connected to a three phase permanent magnet brushless electronic motor that is controlledwith reconstructed current according to a BLAC sinusoidal wave.The inverter board that controls the motor operation is powered by 230 Volt, single-phase and, with aswitching system, it generates a three-phase frequency modulated, wave form power supply.The electric power supply required for the machine is therefore single-phase with voltage of 230 - 240 Vand frequency of 50 - 60 Hz.
HEAT EXCHANGERMade of copper tubes with bonded aluminium fins for maximum transfer contact.The batteries are with 2 or 3 rows for 2 pipe models and 2+1 rows for 4 pipe models (the heating row ison the inside part of the battery).For 4 pipe systems two versions are available:SK 14 and SK 44 supply an higher heating emission;SK 26, SK 36, SK 56 supply an higher cooling emission.The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminiummay be subject to corrosion.
CONDENSATE COLLECTION TRAYHigh density ABS polystyrene foam condensate tray, shaped in order to optimize the air diffusion, fireretardant rating B1 to DIN 4102.
AIR FILTERSynthetic washable filter, easily removable.
CONDENSATE PUMPFloat switch centrifugal pump with 650 mm of maximum head, integral to the unit and wired to the controlpanel on the outside of the casing.
VALVE SETTwo or three way valves for ON/OFF operation, with pipe mounting kit and thermostatic actuator.
29
SkyStarSkyStar ECMSkyStar ECM
Main components
3,0 4,01,4 2,1 2,1820 x 820 x 303575 x 575 x 275
7105,293,695,899099,47,2342510
11307,725,538,83132818,514,9473832
177010,757,94
12,73184833,628,85748
108
6304,213,035,1172310,98,7332410
8705,153,776,3588515,612,8393017
11656,334,728,01108922,719,5483933
3602,561,812,964415,94,737287
6103,872,814,6366612,410,5504121
8805,023,746,286419,717,7605162
1 2 31 2 31 2 3
MODEL SK-ECM 12 SK-ECM 22 SK-ECM 32 SK-ECM 42 SK-ECM 52
3102,241,572,553854,63,633245
4453,052,173,585249,46,6433411
7104,333,185,2474415,113,1544531
1 2 33101,841,352,223174,9433245
3802,171,612,673736,65,539308
5352,752,093,4447310,18,7473816
1 2 3SpeedAir flow m3/hCooling total emission (E) kWCooling sensible emission (E) kWHeating (E) kWWater flow l/h�P Cooling (E) kPa�P Heating (E) kPaSound power Lw (E) dB(A)Sound pressure Lp (*) dB(A)Fan (E) WWater content lDimensions mm
1,13,6
1,43,0
0,51,7
0,51,7
0,71,4
820 x 820 x 303575 x 575 x 275
7104,983,528568,85,224496,5342510
11307,175,2
123317
7,1661611473832
17709,877,4
169730,19,51818185748
108
6304,33,087409,46,1452810,5332410
8705,283,8490813,67,5464915,5393017
11656,514,83112019,89,3680522,5483933
3602,381,714094,12,21894,537287
6103,532,626088,43,062637,5504121
8804,533,4677913,13,7932611605162
1 2 31 2 31 2 3
MODEL SK-ECM 14 SK-ECM 26 SK-ECM 36 SK-ECM 44 SK-ECM 56
3102,091,493593,51,981703,533245
4452,812,044835,72,532175,5433411
7103,932,9567610,53,35288
9544531
1 2 33101,851,343184,62,432095,733245
3802,181,63756,22,852457,639308
5352,772,084769,53,6231111,7473816
1 2 3SpeedAir flow m3/hCooling total emission (E) kWCooling sensible emission (E) kWWater flow l/h�P Cooling (E) kPaHeating (E) kWWater flow l/h�P Heating (E) kPaSound power Lw (E) dB(A)Sound pressure Lp (*) dB(A)Fan (E) WCooling water content lHeating water content lDimensions mm
30
2 pipe units. The following standard rating conditions are used:
COOLINGEntering air temperature: + 27°C d.b., + 19°C w.b.Water temperature: + 7/12°C
HEATINGEntering air temperature: + 20°CWater temperature: + 50°Cwater flow rate as for the cooling conditions
Technical features
4 pipe units. The following standard rating conditions are used:
COOLINGEntering air temperature: + 27°C d.b., + 19°C w.b.Water temperature: + 7/12°C
HEATINGEntering air temperature: + 20°CWater temperature: + 70/60°C
EUROVENT Certification
SkyStarSkyStar ECMSkyStar ECM
Condensate pump absorption: 8 W
(E) = Eurovent certified performance.
* = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.
www.eurovent-certification.comwww.certiflash.com
7/12 °C10/15 °C14/18 °C
KKK
0,90,720,5
0,940,780,58
1,060,90,72
7/12 °C10/15 °C14/18 °C
KKK
0,820,560,35
0,890,630,41
1,110,820,52
Water (°C) Air (°C) 25-18 26-18.5 28-20 Water (°C) Air (°C) 25-18 26-18.5 28-20Total emission Sensible emission Note:
the correctionfactors are indicative,as they areaverage values.
Emission correction factors for different working conditions.Multiply the factors by the emission figures in the 7-12°C table above.
493383318749512365886663423115291273418171262842
2,872,221,854,362,982,125,153,852,466,705,304,2710,567,344,90
2722131784202902094943732416425124151015713481
3,172,482,074,893,382,435,754,342,817,475,954,8211,818,295,60
3302572145053472495954482887746154971222854574
3,832,992,495,874,042,906,925,203,359,007,155,7814,219,936,67
3873002505894042896965223359047175781428994666
4,493,492,916,854,703,368,096,073,8910,518,346,7216,6011,567,74
500387322758517368896670427116592274118371274849
5,824,513,758,816,014,28
10,427,794,96
13,5410,728,61
21,3714,829,87
535380310710445310880610360116587063017701130710
SpeedAirflow
ECMModel
HighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
EWT 45 - LWT 40°C EWT 50 - LWT 40°C EWT 55 - LWT 45°C EWT 60 - LWT 50°C EWT 70 - LWT 60°C
l/hm3/h kW l/h kW l/h kW l/h kW l/h kW
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
SK 12
SK 22
SK 32
SK 42
SK 52
570448379888621453103579352013041055859221015741068
3,322,602,25,173,612,636,024,613,027,586,134,9912,859,156,21
2,331,801,513,552,431,754,183,152,025,274,213,398,886,184,12
473373317744524385864666441108988572318481328909
2,752,171,844,333,052,245,023,872,566,335,154,2110,757,725,29
2,091,611,353,182,171,573,742,811,814,723,773,037,945,533,69
36829325058841931167852835485770157614561059734
2,141,701,453,422,431,813,943,072,064,984,073,358,476,164,27
1,841,421,182,801,911,383,302,481,594,173,322,677,004,863,24
2662071744102812044823632356044833921031718482
1,541,211,012,381,631,182,802,111,373,512,812,285,994,182,80
1,541,211,012,381,631,182,802,111,373,512,812,285,994,182,80
535380310710445310880610360116587063017701130710
SpeedAirflow
ECMModel
HighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
EWT 5 - LWT 10°C EWT 7 - LWT 12°C EWT 9 - LWT 14°C EWT 12 - LWT 17°CWaterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
l/h kW kW l/h kW kW l/h kW kW l/h kW kWm3/h
SK 12
SK 22
SK 32
SK 42
SK 52
31
SkyStarSkyStar ECMSkyStar ECM
Emission
Cooling emission of 1 battery units (2 pipe installation)Entering air temperature: +27°C d.b. +19°C w.b.
Heating emission of 1 battery units (2 pipe installation)Entering air temperature: +20°C
7/12 °C10/15 °C14/18 °C
KKK
0,90,720,5
0,940,780,58
1,060,90,72
7/12 °C10/15 °C14/18 °C
KKK
0,820,560,35
0,890,630,41
1,110,820,52
Water (°C) Air (°C) 25-18 26-18.5 28-20 Water (°C) Air (°C) 25-18 26-18.5 28-20Total emission Sensible emission Note:
the correctionfactors are indicative,as they areaverage values.
Emission correction factors for different working conditions.Multiply the factors by the emission figures in the 7-12°C table above.
57244837881257642594072948613411081877203514671010
3,322,612,204,723,352,475,464,242,827,796,295,1011,838,535,87
2,321,791,503,292,281,663,862,931,915,404,303,458,265,823,93
476375318676483359779608409112090874016971233856
2,772,181,853,932,812,094,533,532,386,515,284,309,877,174,98
2,081,601,342,952,041,493,462,621,714,833,843,087,405,203,52
3722962525283822876064773258827195901332979687
2,171,721,463,072,221,673,522,771,895,134,183,437,745,693,99
1,831,411,182,601,791,313,052,311,504,263,382,716,534,583,09
264206172378262192442337221619497398951672457
1,541,201,002,201,531,122,571,961,293,62,892,325,533,902,66
1,541,201,002,201,531,122,571,961,293,62,892,325,533,902,66
535380310710445310880610360116587063017701130710
SpeedAirflow
ECMModel
HighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
EWT 5 - LWT 10°C EWT 7 - LWT 12°C EWT 9 - LWT 14°C EWT 12 - LWT 17°CWaterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
Waterflow
Totalemission
Sensibleemission
l/h kW kW l/h kW kW l/h kW kW l/h kW kWm3/h
SK 14
SK 26
SK 36
SK 44
SK 56
305241205279211165315255184793639521800603440
1,781,401,191,621,230,961,831,481,074,613,723,034,653,502,56
1611271081391068315612793421340278413312229
1,871,481,261,611,230,971,821,481,084,903,963,234,803,632,67
198156133176133105198161117517417340514388284
2,301,821,552,041,551,222,311,871,366,014,853,965,974,513,30
236186158213161127241195141613494403615464339
2,742,161,842,481,871,472,802,271,647,135,754,687,155,393,94
311245209288217170326263189805649528818616449
3,622,852,433,352,531,983,793,062,209,367,546,149,517,165,22
535380310710445310880610360116587063017701130710
SpeedAirflow
ECMModel
HighMedLowHighMedLowHighMedLowHighMedLow
HighMedLow
EWT 45 - LWT 40°C EWT 50 - LWT 40°C EWT 55 - LWT 45°C EWT 60 - LWT 50°C EWT 70 - LWT 60°C
l/hm3/h kW l/h kW l/h kW l/h kW l/h kW
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
Waterflow Emission
SK 14
SK 26
SK 36
SK 44
SK 56
SkyStar ECM
32
SkyStarSkyStar ECM
Cooling emission of 2 battery units (4 pipe installation)Entering air temperature: +27°C d.b. +19°C w.b.
Heating emission of 2 battery units (4 pipe installation)Entering air temperature: +20°C
Emission of 4 pipe unitswith standard and enhanced cooling battery
Water flow
Air flow
Supply
MAX. working pressure8 barsSuitable relative humidity15 - 75%Single phase 230V 50Hz
MIN. entering water temperature: + 5°CMAX. entering water temperature: + 80°CMIN. entering air temperature: 6°CMAX. entering air temperature: 40°C
Installation MAX. height: See table on page 12
°CK
20
0,94
30
0,90
40
0,86
50
0,82
60
0,78
70
0,74
80
0,70
°CK
20
0,94
30
0,90
40
0,86
50
0,82
60
0,78
70
0,74
80
0,70
°CK
40
1,14
50
1,08
60
1,02
70
0,96
80
0,90
Pressure dropfor mean water temperature of 10°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Pressure dropfor mean water temperature of 65°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Working conditions
Pressure dropfor mean water temperature of 10°C,
for different temperatures multiply the pressure drop figureby the K correction factors in the table.
Pressure dropfor cooling battery
Pressure dropfor heating battery
2 pipe installation
4 pipe installation
33
SkyStarSkyStar ECMSkyStar ECM
Water side pressure drop
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
Water flow (l/h)
Pre
ssur
e dr
op (
kPa)
790 350 750 150
A B C Dmm
30 246 3
kg kg
Weightspacked unit
Weightsunpacked unit
SK 12 SK 14 SK 22 - 26 SK 32 - 36
28 22
UNIT DIFFUSER
kg kg
ECM ModelWeights
packed unitWeights
unpacked unit
Packed unitDimensions
SK 12-14 / SK 22-26 / SK 32-36 (Version 600 x 600)
SkyStar ECM
34
SkyStarSkyStar ECM
Dimensions and weights
MD-600METAL DIFFUSER
(receiver kitIRC-MD code 9060178for MD diffuserfor infra-red units)
2 pipe units- 3. Flow, heating/cooling 1/2”
- 4. Return, heating/cooling 1/2”
4 pipe units- 1. Flow, heating 1/2”- 2. Return, heating 1/2”- 3. Flow, cooling 1/2”- 4. Return, cooling 1/2”
UNIT DIFFUSER
1050 400 1000 20010 6
Packed unitDimensions
A B C Dmm
47 39
kg kg
Weightspacked unit
Weightsunpacked unit
SK 42 SK 44 SK 52 - 56
44 36
UNIT DIFFUSER
kg kg
ECM ModelWeights
packed unitWeights
unpacked unit
PACKED UNIT
SK 42-44 / SK 52-56 (Version 800 x 800)
35
SkyStar ECMSkyStar ECM
Dimensions and weights
2 pipe units- 3. Flow, heating/cooling 3/4”
- 4. Return, heating/cooling 3/4”
4 pipe units- 1. Flow, heating 1/2”- 2. Return, heating 1/2”- 3. Flow, cooling 3/4”- 4. Return, cooling 3/4”
1 2 33,32,22,5
3,92,62,9
4,22,83,1
1 2 33,32,22,5
4,22,83,1
4,83,23,6
1 2 33,92,62,9
4,53,03,4
5,23,43,9
1 2 33,52,22,7
4,12,63,2
4,83,03,8
1 2 33,82,43,0
4,62,83,6
5,43,44,2
SK 12-14 SK 22-26 SK 32-36 SK 42-44 SK 52-56SpeedAir throw L mHeight H mDistance B m
ECM Model
1 2 33,0 3,5 3,8
1 2 33,0 3,8 4,5
1 2 33,5 4,2 5,0
1 2 33,2 3,7 4,3
1 2 33,4 4,0 5,0
SK 12-14 SK 22-26 SK 32-36 SK 42-44 SK 52-56SpeedAir throw L m
ECM Model
NOTE: On heating it must be payed attention to rooms where the floor temperature is particularly low (for example less than 5°C). In this situation the floor can cool the lower layer of air to a level that stop the uniform diffusion of the hot air coming from the unit, decreasing the throw figures shown in the table.
SkyStar ECM
36
SkyStarSkyStar ECM
The air throw indicated in the tables must only be considered the maximum value, as it maychange significantly in relation to the dimensions of the room in which the appliance is installedand the positioning of the furniture in the room.
The useful throw L refers to the distance between the unit and the point where the air speedis 0.2 m/sec; if the louver has a gradient of 30° (recommended in cooling mode), the so-called“Coanda” effect will occur, illustrated in the first figure, while at a gradient of 45° (recommendedin heating mode), there will be a downwards throw, as illustrated in the second figure.
Air throw
With adjustableair diffusion louvers at 30°
With adjustableair diffusion louvers at 45°
Fresh air kitThis is used to introduce primary air into the environment directly through the diffuser. The kit includes a flow separatorto be fitted inside the cassette, and a circular fitting for connection to the flexible system ducting. The flow of air is sentdirectly to just one of the outlet louvers, without passing through the coil. The
air flow of fresh air introducedinto the environment dependon the inlet static pressure.PRT 800
SK 4-5-6
9079231
PRT 600
SK 0-1-2-3
9079230
IDENTIFICATION
MODEL
CODE
SK 1-2-3 SK 4-5
160200300400500
80120160200240
m3/hm3/h
38152536
38152536
PaPa
The diameter of the fittingis 150 mm for SK 1 - 2 - 3and 180 mm for SK 4 - 5.
The diameter of the fittingis 150 mm for SK 1 - 2 - 3and 180 mm for SK 4 - 5.
Fresh air connectionSee page 13.
Air distribution connectionSee page 13.
IDENTIFICATION CODE
CAP 6078005
CDA 800 9079233
CDA 600 9079232
IDENTIFICATION CODE
Correlation between flow-rate / static pressure
37
SkyStarSkyStar ECMSkyStar ECM
Accessories
Rated pressure:
Max. ambient temperature:
Max. water flow temperature:
Power:
Rating:
Protection:
Travel time:
Max. glycol content of water:
16 bar
50 °C
110 °C
230 V - 50/60 Hz
3 VA
IP 43
approx. 3 min.
50%
Batterytype
Main
ECMModel
Auxiliary
12 - 22 - 32
14 - 26 - 36
42 - 52
44 - 56
14 - 26 - 36
44 - 56
2 way valves 3 way valves
Kvs
m3/h�pmax
kPa *Valve **
connectionKvs
m3/h�pmax
kPa *Valve **
connection
2,8
5,2
2,8
50
60
50
3/4"
1"
3/4"
2,5
4,5
2,5
50
50
50
3/4"
1"
3/4"
* maximum pressure difference for valve to close ** external thread, flat sealNote: 3 way valves with simplified kit and 1” connection have conical seal.
SkyStar ECM
38
SkyStarSkyStar ECM
Valve set, 2 or 3 ways, ON-OFF, with thermoelectric actuator.The set includes connection pipes.
Note: The main battery lockshield valve connection is 1/2” female (Kvs 2) for SK1 - SK2 - SK3 sizes and 3/4” female (Kvs 3,5) for SK4 - SK5 sizes, the auxiliary battery valve connection is 1/2” female (Kvs 2).
Note: The maximum pressure drop accross the fully open valve should not exceed 25 kPa for cooling operation and 15 kPa for heating operation.
Technical data: Valves characteristics
Val
ves
pre
ssu
re d
rop
3 ways 2 ways
3 ways 2 ways
ON-OFF valves with thermoelectric actuator
Δp - kPa
Waterflow (l/h)
VALVE WITH MICROMETRIC LOCKSHIELD VALVE
VALVE WITH SIMPLIFIED KIT
LEGEND
SEP = Pump control boardBLAC = Inverter board
M = Electronic motorCONTROLLER = Controller
For this cassette configuration, the 1-10 Vdc signal, which controls the inverter, must be suppliedby a controller with the following signal specifications:
• Impedance < 100 �;
• Maximum speed 10Vdc;
• Fan OFF with V < 0.9Vdc.
39
SkyStarSkyStar ECMSkyStar ECM
SK–ECM configuration
SK–ECM electric diagram
SkyStar ECM
40
SkyStarSkyStar ECM
Power unit to be installedon the fan coil (fan coil interface).It controls the fan and the valves of the fan coil.The power unitis connected to the electric supply.The power unit receivesthe information required from the control.
Power unit for CR-T-ECM remote control (fitted on the unit)
Power unit for CR-T-ECM remote control (not fitted on the unit)
DESCRIPTION
UPM-ECM 9066341
UPS-ECM 9066340
IDENTIFICATION CODE
Dimensions: 133x93x37 mm
Wall electronic control
The control must always be connected with UPM-ECM power unit (fitted on the unit)or with UPS-ECM power unit (not fitted on the unit).
• It allows to control up to 16 units (one power unit for each unit).• ON-OFF switch.• Manual 3 speed switch or automatic continuous speed control.• Manual Summer/Winter switch.• Continuous speed control based on the difference between ambient temperature and Set temperature (speed switch in Auto position).• Electronic room thermostat for fan or valve control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control low temperature cut-out thermostat (NTC).• It allows to control summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).
IDENTIFICATION CODE
CR-T-ECM 9066342
Control power absorption: 1,5 VA
RED
BLACK
41
SkyStarSkyStar ECMSkyStar ECM
To be fitted between the coil fins.When connecting the control,the NTC probe cable must be separated from the power supply wires.To be used with CR-T-ECM control.It stops the fan whenthe water temperature is lower than 28°Cand it starts the fan when is higher than 33°C.
NTC low temperature cut-out thermostat
CR-T-ECM wall electronic control accessories
Automatic summer/winter switchto be installed in contact with the water circuit.For 2-tube installations only(not to be used with 2 way valve).To be used with CR-T-ECM control.
Change-Over CH 15-25
IDENTIFICATION CODE
NTC 3021090
IDENTIFICATION CODE
CH 15-25 9053049
42
SkyStar
All the SkyStar ECM units can be supplied in MB version. This version includesa wide range of controls, including the infra-red remote control, which allows managing one single unit
or several units by using the Modbus RTU - RS 485 communication protocol.
Units can be managed according to the Master/Slave logic (up to 20 units)or by supervisory components.
The system consists in a MB power board (mounted on models SK–MB and SK–ECM–MB)and a series of devices, such as the T-MB wall mounted control, the RT03 infra-red remote control,
the PSM-DI multifunction control and the Sabianet supervisory program.
SkyStar ECMSkyStar ECM
Controls for SK–ECM–MB versions
RT03 infra-red remote control
PSM-DI multifunction control
Sabianet software
Sabianet screenshot
PC
T-MB wall mounted control
43
SkyStar
The MB power electronic board,mounted as per standard on the SK–MBand SK–ECM–MB versions, is set to carry outdifferent functions and adjustment modes,in order to meet the installation requirements.
These modes are selectedby setting the configuration dip switcheson the board.
• 2/4 pipe system.
• Fan ON/OFF thermostatic control.
• Valve ON/OFF thermostatic control and continuous ventilation.
• Valve and simultaneous ventilation ON/OFF thermostatic control.
• Fan operation control depending on the coil temperature (cut-out T3 probe fitted), which can be activated only in heating mode or heating and cooling mode.
• Automatic switch of the operating mode by means of T2 water probe (optional) applied on the 2 pipe system.
• Seasonal switch by means of remote contact.
• ON/OFF of the fan coil by means of the remote contact (window or clock contact).
• Electric heater control.
By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°Cand started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside thecoil exceeds 22°C and starts when it drops below 18°C.
The following connections are located on the power board:
• Receiver for infra-red remote control.
• T-MB wall mounted control.
• RS 485 serial connection to manage several fan coils in Master/Slave configuration or to create a supervisory network.
MB power electronic board
MB controls
SkyStar ECMSkyStar / SkyStar ECM
44
SkyStarSkyStar ECMSkyStar / SkyStar ECM
Wall mounted control with displaythat allows controlling one or more unitsin Master/Slave mode. The control is equippedwith internal sensor to detect the room temperature,which can be defined as a prioritycompared to the return air sensor on the fan coil.
The T-MB control features the following functions:
• Switch the appliance ON and OFF.
• Temperature set.
• Modify the set point (when used as a +/- 3° variation of the set point configured from Sabianet supervisory program).
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection depending on the air temperature).
• Time setting.
• Weekly ON/OFF program.
• Display and change of the fan coil operation parameters.
Wall mounted control (to be used only with SK–MB and SK–ECM–MB version)
DESCRIPTION
T-MB 9066331E
IDENTIFICATION CODE
T-MB wall mounted control
MB controls
45
SkyStarSkyStar ECMSkyStar / SkyStar ECM
The infra-red remote control allows setting by a remote position the fan coil operation parameters.
The RT03 infra-red remote control features the following functions:
• Switch the appliance ON and OFF.
• Temperature set.
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection depending on the air temperature).
• Time setting.
• 24 hours ON/OFF program.
RCS-RT03
RCS
RS
RT03
9079117
9079116
9066338
3021203
RT03 infra-red remote control with receiver supplied with separate packaging(to be used only with SK–MB and SK–ECM–MB version)
Receiver for RT03 infra-red remote control supplied with separate packaging(to be used only with SK–MB and SK–ECM–MB version)
Receiver for RT03 infra-red remote control and MDA metal diffusersupplied with separate packaging (to be used only with SK–MB and SK–ECM–MB version)
RT03 infra-red remote control supplied with separate packaging(to be used only with SK–MB and SK–ECM–MB version)
DESCRIPTION IDENTIFICATION CODE
RT03 infra-red remote control
MB controls
g
• 24 hours ON/OFF program.24 hours ON/OFF program.
INSTALLATION EXAMPLE
WITH INFRA-RED REMOTE CONTROL
IDENTIFICATION CODE
RT03 3021203
IDENTIFICATION CODE
RCS 9079116
IDENTIFICATION CODE
RCS-RT03 9079117
46
SkyStar
The T2 sensor can be combined with MB boards to be placed on the water supply pipe upstream 3 way valves(not to be used with 2 way valve).
The T2 sensor must be used as described below:
- Change-Over for 2-pipe system for the automatic switch of the operating mode. If water temperature is lower than 20°C, cooling mode is set; on the other hand, if water temperature exceeds 30°C, heating mode is set.
- It can be used on units with electric heater and hot water supply. The T2 priority probe activates the electric heater or water valve, depending on the water temperature detected. If water temperature exceeds 34°C, the water valve ON-OFF control is activated; on the other hand, if water temperature is lower than 30°C, the electric heater is activated.
IdentIfIcatIon code
T2 9025310
T2 accessory for units with MB electronic board
A group of SkyStar MB can be connected via a serial link and can consequently be managed at the same timeby just one T-MB wall mounted control or RT03 infra-red remote control. Using the special jumper present onthe MB board, one unit must be configured as the master, and all the others as slaves. It is clear that the remotecontrol must be pointed at the receiver on the master unit. To avoid problems, it is recommended to install andconnect the receiver only on the master unit.
With RT03 infra-red remote control
One control for each cassette One control for more cassettes (20 units max.)(MaxiMuM total length of the connection cable = 800 m)
With T-MB wall mounted control
One control for each cassette(MaxiMuM length of the connection cable = 20 m)
One control for more cassettes (20 units max.)(MaxiMuM total length of the connection cable = 800 m)
MB controls
SkyStar ECMSkyStar / SkyStar ECM
47
SkyStar
Another option available for the serial communication betweenthe units is the possibility to connect up to 60 Cassette units inseries and manage them with just one wall mounted PSM-DIcontroller. The wall mounted controller can be used to set theoperating mode for each individual unit connected, displaythe operating conditions of each individual unit, and set theON/OFF time sets for each day of the week (the programcan be set for all the units and for a maximum of two groupsof units).If more than 60 units need to be connected, two or morecontrollers must be used. Each wall mounted controller onlymanages the units it is connected to.The PSM-DI control is used to manage a series of fan coils,up to a maximum of 60 units (the maximum length of the RS 485connection cable must not exceed 800 m), from one single control point.
The PSM-DI control communicates via a serial line with all the units connected, with the possibility of controllingthem all together or individually. In fact, the unique address of each individual fan coil means that all the units canbe called at the same time, or the individual unit called, to perform the following functions:
- display the current operating mode, the fan speed, the set point;
- display the room temperature measured on the individual unit;
- turn all the units ON and OFF at the same time or alternatively each unit individually;
- change the operating mode (fan only, heating, cooling, automatic changeover);
- change the set point;
- modify the values and operation parameters of the fan speed.
Each function can then be sent to all the units connected, or alternatively to each individual unit.
Different set points or operating modes can be set for each individual unit.
The PSM-DI panel can also be used for the time management of the units over the week. Four ON times and fourOFF times can be set on the units for each day of the week. A different Temperature set that will be considered asOperation set for all connected appliances, can be set for each event. If the Temperature set is not entered for theindividual event, it must be set during programming for each individual unit or for the entire network.
Units without receiver or with receiver can be connected within the network: the former can receive instructions onlyfrom the PSM-DI wall mounted panel; while the latter can receive information from both the wall mounted panel(PSM-DI) and infra-red remote control. Use the infra-red remote control to force ON mode of the individual unit,if ON/OFF daily time programming has been set. The unit will regain the settings from the PSM-DI panel duringexecution of successive start-up program.
The PSM-DI panel cannot be usedtogether with the Sabianet management program (see next page).
Note: set the configuration Dip Switches of each fan coil as illustrated in the remote control use manual, based on the required solutions.
Note: the RS 485 network’s overall length must not exceed 700/800 metres.
Multifunction control (to be used only with SK–MB and SK–ECM–MB version)
DESCRIPTION
PSM-DI 3021293
IDENTIFICATION CODE
PSM-DI multifunction control
MB controls
SkyStar ECMSkyStar / SkyStar ECM
“MO
NIT
OR
ING
” S
CR
EE
N
48
SkyStarSkyStar ECMSkyStar / SkyStar ECM
Sabianet is a centralised control system for networks of Sabiana MB fan coils,based on software that runs on LINUX™.The Sabianet software offers a practical and economical solution for managingthe units, with the simple click of the mouse.The main characteristics include simplicity of use, an extremely complete andfunctional weekly program, and the possibility to access the historical operating datafor each individual appliance connected.
The program exploits all the potential of our units with remote controls, representing an additionto the latter.
The Sabianet program is a control tool that can be used as a replacement for the remote control, orin parallel, however the settings made using Sabianet can have priority over those made using theremote control.
The program can be used to:- Create uniform groups (groups of units on individual floors, in offices or rooms).- Save weekly programs configured for different types of operation (summer, winter, mid seasons, closing periods etc.); these can then be recalled and activated with a simple click of the mouse. Weekly on/off cycles can be set for individual units or groups of units.- Set the operating conditions for each individual unit or groups of units (operating mode, fan speed, temperature setting).- Set the set point limits for each individual unit or groups of units.- Switch each individual unit or groups of units ON or OFF.
dg d
ng
or er
data
an addition
the remote control, orthose made using the
The main program screen can display and interact with the entire network of units. An individual unit, a group ofunits or the entire network can be called so as to make modifications to the operating mode and the set point. Theuser can then check the operating status of each individual unit, read the room temperature, the coil temperatureand the operating status of the condensate drain pump or any alarms.
Hardware/software supervisory system(to be used only with SK–MB and SK–ECM–MB version)
DESCRIPTION
Sabianet 9079118
IDENTIFICATION CODE
Sabianet program for managing a network of Sabiana MB fan coils
Management system for a network of fan coils
“EV
EN
T M
AN
AG
EM
EN
T”
SC
RE
EN
49
SkyStarSkyStar ECMSkyStar / SkyStar ECM
Time bands are available for each day of the week. The time and the type of operation to be performed by the unitcan be set for each band. The time and the operating parameters can then be displayed before being sent to theunit and implemented.
The “Weekly Program” can be used to set the unit operating parameters for each day of the week. Up to 20 differentweekly programs can be set.
The icon of the terminal unitprovides the following information:
- Unit name ( C01000001)
- Set temperature ( TSET )
- Room temperature ( TA )
- Unit status: ON or OFF
- Mode: • Summer • Auto
• Winter • Fan only
- Fan speed: • Low • High
• Medium • AutoFan
The “MONITORING” SCREEN shows the units thatare connected to the network and scanned by the program.
Displaying a unit
Management system for a network of fan coils
USB-RS 485
Outputsfor system
Powerinput
CONVERTER
RS 485
Outputsfor system
Powerinput
Outputsfor system
Powerinput
MC2 Jumperto be closed.
End of network.
Cassetteunit
Cassetteunit
Cassetteunit
SABIANET
60 units max. (*)
50
SkyStarSkyStar ECMSkyStar / SkyStar ECM
SIOS is a board equipped with 8 relays with potential free contact to control the activationor deactivation of remote electric utilities. Moreover, the board has 8 digital inlets todisplay the actuators or external consents, such as motor or other. The SIOS boardscan be connected:
- inside a network managed by Sabianet;
- to a PSM-DI panel (one SIOS for each PSM-DI panel).
The Router-S is an electronic board that:
- allows creating networks with more than 60 units (minimum 2 Router-S are required) or to divide the network (per floor, building, etc.);
- it allows creating a Master/Slave sub-network to be controlled as an indipendent group.
The Router-S can be used only inside a network managed by Sabianet.
The number of Router-S to be used is: - up to 60 units: no Router-S - from 61 to 120 units: 2 Router-S - every 60 subsequent units: 1 additional Router-S
IDENTIFICATION CODE
SIOS 3021092
IDENTIFICATION CODE
Router-S 3021290
PSM-DI and Sabianet accessories
PC Sabianet Software
Connectionof a Cassette SkyStar SK–MBor SK–ECM–MB network
(*) In the event of more than 60 units, add one or more Router-S (see below).
RS 485 serial connection cable
Shielded cable to be used:Belden 9841, RS-485, 1x2x24 AWG SFTP, 120 Ohm
Management system for a network of fan coils
51
Introduction
The MCT version has been designed for all environments where false ceilings are not featuredor cannot be constructed.The cover cabinet fits perfectly to the air intake and outlet diffuser, maintaining the appealingdesign that defines the SkyStar series. The water fittings can be turned to point upwards.
The MCT series includes 7 models, with an installation height of up to 5 m, thanks to the highlyflexible adjustment of the air distribution louvers.
All the technical specifications described on the previous pages remain the same, while keepingin mind that:- the MCT series features one coil only (two pipe systems)- there is no possibility of fresh air intake- there is no possibility of additional electric heater
The MCT version features a special casing delivered in separate packaging; this must only befitted after having installed the SkyStar unit and completed the water and electrical connections.
SkyStar MCTSkyStar MCT
SkyStar MCT
Dimensions and Weights
SK 02-MCT / SK 12-MCT / SK 22-MCT / SK 32-MCT
Casing code: 9079240
Casing weight: 5 kg (7,5 kg with the packaging)
SK 42-MCT / SK 52-MCT / SK 62-MCT
Casing code: 9079250
Casing weight: 10,5 kg (13,5 kg with the packaging)
Warning: the electrical and water connections must enter the unit from above and must not interfere with the casing.
52
SkyStarSkyStar MCT
53
SkyStarSkyStar MCTSkyStar MCT
Assembly diagram
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right, whilstmaintaining the essential characteristics of the types described and illustrated, to make, at any time, without therequirement to promptly update this piece of literature, any changes that it considers useful for the purpose ofimprovement or for any other manufacturing or commercial requirements.
Components of the casing:
Valve kit
The casing includes:
A – 4 corner covers
B – 4 bottom brackets
C – 4 top brackets
D – Condensate collection tray
E – Hardware (45 3.9x9.5mm TCX screws)
F – Instruction sheet
The valve fittings allow the water pipes to be connected from above.
For the specifications of the valves, see page 15.
SK 02-MCT / SK 12-MCTSK 22-MCT / SK 32-MCT
Code 9079155
SK 42-MCTSK 52-MCT / SK 62-MCT
Code 9079156