December 17, 2013
Smart Grid Information Sharing Webcast: Synchrophasor Communications Infrastructure
Paul Myrda
Technical Executive [email protected]
Scott Sternfeld
Project Manager [email protected]
2 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Objectives of the Project
• Improve understanding of latency in a synchrophasor based control system – Implemented with C37.118 and IEC 61850 GOOSE
messaging – Multiple vendor equipment/components – Three scenarios
• Unicast • Unicast + PDC • Multicast
• Apply lessons learned to possible implementations
3 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Why?
• Understand latency contributions by the network, transport protocols, different vendor equipment and system
• Create awareness for approaches and methods that can be used to minimize the latency Understand issues affecting deployment of automated and
semi-automated closed-loop distributed control systems
4 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Questions:
• What are current system latency times measured from deployed systems?
• Sample architecture: – Event transmitted by PMU – Through substation PDC – Through utility “centralized” PDC – To ISO application (possibly through an ISO PDC)
• Can optimizations be applied?
5 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Simplified Control Signal Diagram
PMU A Event & Time Monitor
1
4
3 2
PMU BGOOSE
C37.118Legend
6 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Test Bed Control Loop – Timing Arrangement
PMU A
Event & Time Monitor
1
4
2
PMU B
Phasor Data Concentrator
3
IRIG-B
NTP
194:10:45:15GPS Time Clock
7 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Configuration- IP Unicast with PDC
PMU A
Event & Time Monitor
1
4
2
PMU B
Phasor Data Concentrator
3
GOOSEC37.118Legend
8 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Configuration- IP Unicast without PDC
Legend
GOOSEC37.118
PMU A
Event & Time Monitor
1
4
2
PMU B
3
9 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Configuration- IP Multicast
PMU A
Event & Time Monitor
1
4
2
PMU B
3
GOOSEC37.118Legend
10 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Timing Determination
1 1.1 2 2.1 3 3.1 3.2 4 4.1 5
PMU A Button
Pressed PMU A E&TM
E&TM GOOS
E xmit
PMU A GOOSE rcvd
PMU A Trigger
PMU A GOOS
E xmit
PMU B GOOS
E rcvd
PMU B Status Chang
e
E&TM
Timing Interval
Legend
GOOSEC37.118
11 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Test Bed Control Loop 1588 Timing
PMU A
Event & Time Monitor
1
4
2
PMU B
Phasor Data Concentrator
3
IEEE 1588 v2194:10:45:15GPS Time Clock
IEEE 1588 v2
12 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Testbed Network Diagram
knx-sw2
PMU - B
Hist I/F
Wide Area Connectivity with PMOD tool for propagation, loss,
jitter, OOO simulation as necessary
E&TM TCPdump
llnx-sw2
knx-sw1
LNX Router
PMOD
KNX Router
PDC
“KNX substation”
“LNX substation”
PMU A
KNX and LNX substations: • Layer 3 for C37.118 messages • Layer 2 for GOOSE messages • VLAN filtering for Layer 2 traffic
13 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Test A: Latency Measurements PMU sampling rate: 60 Samples/Second
0
2
4
6
8
10
12
14
0.033 0.066 0.099 0.132 0.165 0.198 0.231 0.264 0.297 0.330 0.363 0.396 0.429 0.462
Freq
. of o
ccur
renc
e
Latency
IP Mcast IP Ucast+PDC IP Ucast
14 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Test B: Latency Measurements PMU sampling rate: 60 Samples/Second
0
10
20
30
40
50
60
0.033 0.066 0.099 0.132 0.165 0.198 0.231 0.264 0.297 0.330 0.363
Freq
. of o
ccur
renc
e
Latency
IP Mcast IP Ucast+PDC IP Ucast
• Reduced buffers • Default configurations modified
15 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Test C: Latency Measurements PMU sampling rate: 30 Samples/Second
0
5
10
15
20
25
30
35
40
45
50
0.033 0.066 0.099 0.132 0.165 0.198 0.231 0.264 0.297 0.330 0.363
Freq
. of o
curr
ence
Latency
IP Mcast IP Ucast+PDC IP Ucast
• Reduced buffers • Default configurations modified
16 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Optimizations - Buffering
17 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Optimizations/Configurations - PDC
18 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Summary Table of Test Results – Mode
Mode Samples / Cycle
IP Unicast
IP Unicast w/PDC
IP Multicast Configuration
Test A 60 .283 .100 .233 Initial Configuration
Test B 60 .033 .050 .050 Modified Config 1
Test C 30 .033 .066 .033 Modified Config 1
• Test A: Buffers were significant compared to measurement window
• Tests B/C: PDC adds very minor delay
• Test C: Test network was not complex enough to differentiate IP Multicast from IP Unicast
19 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Conclusions/Observations
• Difficult to accurately measure latency and know the contributing components in the system
• Significant improvements in latency achieved through device settings, network traffic configuration, software interfaces – Network traffic, use of VLANs – Proper set up of buffers and subsystems in software components – Distance (propagation delays), PDC marginally add to overall latency Need to understand the intricacies of all the equipment
• Still some unexplained latency behavior (variation and trends up/down) – Non real-time OS, use of virtual machines, other?
• Much more to learn, but understand the test bed better and have it working!
20 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Future Testing Areas
• IEC 61850-90-5
• Security overlay on WAN link
• Additional network traffic/loading – Add alt vendor PMUs (additional traffic and PDC wait time)
• WAN propagation delays
• Network impairment / availability
• Traffic prioritization / isolation
• IEEE 1588 / PTP synchronization to windows servers
• Upgrade to PI Server 2012
21 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Questions:
• What are the PMU latency measurements between your utility and the ISO?
• Is YOUR PMU architecture or WAMPAC system optimized to reduce latency?
Technical Update, Aug 2013: 3002000604 Synchrophasor
Communication Infrastructure: Impacts on Latency Part II Paul Myrda
Technical Executive [email protected]
Scott Sternfeld
Project Manager [email protected]
22 © 2013 Electric Power Research Institute, Inc. All rights reserved.
Together…Shaping the Future of Electricity