Smart Grid Monitoring by Duval

Embed Size (px)

Citation preview

  • 8/12/2019 Smart Grid Monitoring by Duval

    1/65

    1

    Smart Grid Monitoring of Transformersby DGA

    Michel Duval

    CIGRE Thailand, Bangkok 2013

  • 8/12/2019 Smart Grid Monitoring by Duval

    2/65

  • 8/12/2019 Smart Grid Monitoring by Duval

    3/65

    3

    Power Transformers

  • 8/12/2019 Smart Grid Monitoring by Duval

    4/65

    4

    Catastrophic Failures

  • 8/12/2019 Smart Grid Monitoring by Duval

    5/65

    55

    Failures in Service

    - The failure rate of power transformers in service (internalfailures needing repairs) typically is 0.3% per year.

    - For a population of 2000 transformers, this means 6transformers will fail in the next year.

    - Less than 1 will fail catastrophically.

    - 1994 will not fail.

    - 200 (i.e., 10% of the population at or above IEEE/IECcondition 1) will form abnormal amounts of gases becauseof faults.

  • 8/12/2019 Smart Grid Monitoring by Duval

    6/65

    66

    The Monitoring Dilemma

    - Nobody knows which 6 of the 2000 transformers will failnext year.

    - To identify them, all the transformers need to be monitored,including the 1800 operating normally, just for the purpose ofdetecting the 6 that will fail and need repairs and the lessthan 1 that may eventually fail catastrophically.

    - In economic terms, the cost of monitoring is justified as long

    as it does not exceed the cost of not detecting the 6 failuresand the catastrophic one (typically, >20M$).

  • 8/12/2019 Smart Grid Monitoring by Duval

    7/65

    77

    Smart Grid Monitoring

    - A smart grid is a modernized electrical grid that usesinformation and communications technology in anautomated fashion to improve the efficiency, reliability andsustainability of the production and distribution of electricity.

    - It implies a re-engineering of the electricity services industry.

    - It requires monitoring tools for evaluating on a real-timebasis the condition of electrical equipment, so as to optimizeasset utilization, system reliability and load capabilities

  • 8/12/2019 Smart Grid Monitoring by Duval

    8/65

  • 8/12/2019 Smart Grid Monitoring by Duval

    9/65

    99

    Basic Types of FaultsDetectable by DGA

    -PD: partial discharges of the corona-type in voids in paperinsulation, as a result of poor drying or impregnating with oil.

    -D1: low-energy discharges, such as partial discharges ofthe sparking-type in oil or paper, tracking on paper, smallarcing, arc-breaking activity in LTCs.

    -D2: high-energy discharges, e.g., flashovers, high-energy

    arcing, short-circuits with power follow through, withBuccholz alarms and tripping.

  • 8/12/2019 Smart Grid Monitoring by Duval

    10/65

    1010

    Basic Types of FaultsDetectable by DGA

    -T1: thermal faults of low temperature T < 300C, becauseof overloading, insufficient cooling, design problems.

    -T2: thermal faults of 300 700C, becauseof high circulating currents in core and coil, short circuits in

    laminations, often in oil only.

  • 8/12/2019 Smart Grid Monitoring by Duval

    11/65

    1111

    Additional Sub-Types of FaultsDetectable by DGA

    -S: stray gassing of oil (in oil only) at T

  • 8/12/2019 Smart Grid Monitoring by Duval

    12/65

    1212

    Additional Sub-Types of FaultsDetectable by DGA

    -T3/T2 in oil only: at T >700/ 300C, of minor concern aslong as they do not evolve into faults D1, D2 or C.

    -C: carbonization of paper at T >300C, potentially moredangerous (loss of insulating properties of paper).

  • 8/12/2019 Smart Grid Monitoring by Duval

    13/65

    1313

    DGA Diagnosis Methods

    -Key Gas, Rogers and IEC methods. Limitations are high %of wrong diagnosis (50%) or undiagnosed cases (30%),respectively.

    -Duval Triangle 1, allowing to detect the 6 basic types offaults (PD, D1, D2, T3, T2, T1 + DT).

    -Duval Triangles 4 and 5, allowing to detect the 5 sub-typesof faults (S, O, R, T3/T2 in oil, C), and to distinguish

    between faults of lesser concern in oil and more seriousfaults in paper.

  • 8/12/2019 Smart Grid Monitoring by Duval

    14/65

    1414

    Duval Triangles 1, 4 and 5

    Triangle 1

    Triangle 4 Triangle 5

  • 8/12/2019 Smart Grid Monitoring by Duval

    15/65

    151515

    Use of Triangles 4 and 5

    -Triangles 4 and 5 should never be used in case of faultsidentified with Triangle 1 as faults D1 or D2.

    -Triangle 4 should be used only for faults identified firstwith Triangle 1 as low temperature faults PD, T1 or T2, or

    when there is a high level of H 2.

    -Triangle 5 should be used only for faults identified firstas high temperature thermal faults T2 or T3.

    15

  • 8/12/2019 Smart Grid Monitoring by Duval

    16/65

    16

    Mixtures of Faults

    -mixtures of faults sometimes occur rather than pure faults and may be more difficult to identify with certainty.

    -for instance, mixtures of faults D1 and T3 may appear asfaults D2 in terms of gas formation.

  • 8/12/2019 Smart Grid Monitoring by Duval

    17/65

    17

    New Faults vs. Old Faults:

    -when a new fault appears, as evidenced by a change ingas pattern, a more precise identification of the new faultmay be obtained by subtracting the gas concentrationscorresponding to the old fault from those corresponding tothe new one (incremented values).

    -this, however, introduces additional uncertainty on thesubtracted value.

  • 8/12/2019 Smart Grid Monitoring by Duval

    18/65

    1818

    Interpretation of CO and CO 2

    -Until recently, CO and CO 2 were considered as goodindicators of paper involvement in faults. Recentinvestigations at CIGRE, however, have shown that this isnot always the case.

    -High concentrations of CO (>1000 ppm) and/or lowCO 2/CO ratios (

  • 8/12/2019 Smart Grid Monitoring by Duval

    19/65

    191919

    CO2

    and CO from Closed Transformers

    Ref: I.Hoehlein, CIGRE TF15 (2010)

    56 MVA, 220kV

    Manufactured 2006

    Rubber Bag

    19

  • 8/12/2019 Smart Grid Monitoring by Duval

    20/65

    2020

    Interpretation of CO and CO 2

    -High concentrations of CO (>1000 ppm) and low CO2/CO

    ratios (10,000 ppm), high CO 2/COratios (>20) and high values of furans (>5 ppm) are anindication of the slow degradation of paper at relatively low

    temperatures (

  • 8/12/2019 Smart Grid Monitoring by Duval

    21/65

    2121

    Interpretation of CO and CO 2

    -Low concentrations of CO and CO 2, below condition 1 ofIEC or IEEE (750 and 7500 ppm, respectively), correspondto normal gassing in transformers without faults.

    - Intermediate concentrations of CO, CO2

    and CO2/CO ratios

    may indicate a slow degradation of paper and intermediateDPs of paper, of no concern at all for the normal operationof the transformer.

  • 8/12/2019 Smart Grid Monitoring by Duval

    22/65

    2222

    Interpretation of CO and CO 2

    -Zero or very low rates of change of CO and CO 2 do notnecessarily mean the absence of a fault in paper. Localizedfaults in paper often do not produce detectable amounts ofCO and CO 2 against the usually high background of thesegases in service.

    -However, they do produce significant amounts of the otherhydrocarbon gases, allowing the detection of faults in paperwith Triangles 4 or 5.

  • 8/12/2019 Smart Grid Monitoring by Duval

    23/65

    2323

    Example of a Localized Fault in Paper

  • 8/12/2019 Smart Grid Monitoring by Duval

    24/65

    24242424

    CIGRE Risk of Failure vs. CO 2

    -The risk of failure is very low at high CO 2 values, which arestrongly correlated with paper degradation and low DPs ofpaper, suggesting that the risk of failure at low DPs of paper isalso very low, not very high as generally mentioned.

    -Indeed, large numbers of transformers have been observed atCIGRE to operate quite normally with DPs of paper < 200.

    -And no cases have been reported so far of transformers withDPs < 200 that failed because of the mechanical weakness ofpaper, even when subjected to external short-circuits.

    24

  • 8/12/2019 Smart Grid Monitoring by Duval

    25/65

    25252525

    Transformers at Risk of Failure

    -So, in a large majority of cases, low DPs of paper do notmean the end-of-life of transformers as generallyassumed.

    -The main concern with low DPs of paper is the shrinkage ofpaper and loosening of windings, not the mechanical (tensile)strength of paper. This can be mitigated by reclampingtransformers.

    -Transformers most at risk of failure are gassing transformersthat cannot be fixed.

    25

  • 8/12/2019 Smart Grid Monitoring by Duval

    26/65

  • 8/12/2019 Smart Grid Monitoring by Duval

    27/65

    27

    Typical / Condition 1 Values

    -Typical /condition 1 values of IEC/ IEEE correspond to agiven percentile (90%) of the population of DGA results

    -They mean that 90% of DGA results for dissolved gasesare below these 90% Typical values

    -They are used to concentrate maintenance efforts on the10% of the population with the highest gas levels and

    therefore most at risk

    l d l

  • 8/12/2019 Smart Grid Monitoring by Duval

    28/65

    28

    Typical / Condition 1 Values

    -Below typical/ condition 1 values, gas formation isconsidered not to be a concern for the equipment.

    -Below these values, it is recommended to use normalsampling frequency (monthly, semi-annual, etc.,..) and notto attempt a diagnosis.

    - Above these values, it is recommended to use increasedsampling frequency (e.g., monthly or weekly) and a DGA

    diagnosis may be attempted.

  • 8/12/2019 Smart Grid Monitoring by Duval

    29/65

    29

    90% Typical (Condition 1) Valuesfor Concentrations at IEC (2007), in ppm

    (vs. source)

  • 8/12/2019 Smart Grid Monitoring by Duval

    30/65

    30

    90% Typical (Condition 1) Valuesfor Concentrations at IEEE (2013), in ppm

    (vs. kV, MVA, age, %O 2)

  • 8/12/2019 Smart Grid Monitoring by Duval

    31/65

  • 8/12/2019 Smart Grid Monitoring by Duval

    32/65

    32

    Pre-failure (Condition 4) Values

    -CIGRE has evaluated the probability of having a failure-related event (PFS) in service vs. gas concentration andgassing rate.

    -Based on these PFS curves, pre-failure (condition 4)values have thus been established, as well as intermediateconditions 2 and 3.

  • 8/12/2019 Smart Grid Monitoring by Duval

    33/65

    33333333

    Risk of Failure vs. Gases Formed

    (PFS = Probabilityof Failure in Service)

    33

  • 8/12/2019 Smart Grid Monitoring by Duval

    34/65

    343434

    CIGRE/IEC Sampling Intervals vs.Concentrations in Service, in ppm

    34

  • 8/12/2019 Smart Grid Monitoring by Duval

    35/65

    353535

    CIGRE/ IEC Sampling intervals vs.Gassing Rates in Service, in ppm/month

    35

    Actions Recommended by IEC at

  • 8/12/2019 Smart Grid Monitoring by Duval

    36/65

    36

    Actions Recommended by IEC atConditions 1-4

    -Condition 1: increase oil sampling frequency for DGA

    -Conditions 2-3: consider complementary tests(infrared scans, acoustic tests, PD tests, effect of load).

    -Conditions 3-4: consider transformer inspection.

    -Condition 4: consider transformer repair or replacement.

    Transformer Parameters Influencing

  • 8/12/2019 Smart Grid Monitoring by Duval

    37/65

    37

    Transformer Parameters InfluencingConditions 1-4

    -CIGRE (2006)/ IEEE (2013):-Operating conditions (load, climate)-Age (new, old)-Type (power, core, shell, instrument, reactor).

    -MVA, voltage-Open or closed

    -CIGRE WG47 (2013):

    -Fault type

  • 8/12/2019 Smart Grid Monitoring by Duval

    38/65

    Effect of Type of Thermal Fault

  • 8/12/2019 Smart Grid Monitoring by Duval

    39/65

    3939

    on Condition 1 Values at CIGRE

    (ppm)

    (ppm)

    Effect of Type of Electrical Fault

  • 8/12/2019 Smart Grid Monitoring by Duval

    40/65

    4040

    ypon Condition 1 Values at CIGRE:

    (ppm)

    (after deletingC2H2 < 2 ppm)

    (ppm)

    Effect of Type of Fault

  • 8/12/2019 Smart Grid Monitoring by Duval

    41/65

    4141

    ypon Condition 4 values at CIGRE:

    (in ppm, using previous adjustment factors)

    Comparison with Cases of High Gas Levelsi h F il CIGRE

  • 8/12/2019 Smart Grid Monitoring by Duval

    42/65

    4242

    without Failure at CIGRE:

    (in ppm)

  • 8/12/2019 Smart Grid Monitoring by Duval

    43/65

    4343

    Monitoring with DGA

    -Monitoring off-line (by manual or laboratory DGA) is mostlyused but cannot detect faults occurring between two oilsamplings (e.g., every year, month or week).

    -On-line multi-gas or hydrogen monitors can detect abnormaland/or quick-developing faults occurring within days or hoursbetween oil samplings.

  • 8/12/2019 Smart Grid Monitoring by Duval

    44/65

    4444

    Abnormal and Quick-Developing Faults

    -Abnormal gassing (above condition 1 for concentrationsand gassing rates) will occur in 200 of the 2000transformers.

    -Quick-developing faults (above condition 4 for gassingrates) will typically occur in 20 to 40 of them.

    Detection of Quick-Developing Faults with a Multi-

  • 8/12/2019 Smart Grid Monitoring by Duval

    45/65

    4545

    Q p gGas Monitor in a 3-Phase GSU Transformer

    Day 2 16:00

    Day 2 20:00

    Day 3 00:00

    Day 3 04:00

    Day 2 12:00

    Day 3 12:00

    Day 3 16:00

    Day 3 08:00

    Day 23 04:00 toDay 24 08:00Followed bytransformer failure

    C2H2 = 800 ppm/day!

    700 MVA Transformer

  • 8/12/2019 Smart Grid Monitoring by Duval

    46/65

    4646

    C2H2 = 45 ppm/day!

    336 MVA Transformer

  • 8/12/2019 Smart Grid Monitoring by Duval

    47/65

    4747

    336 MVA Transformer (Placed in Service -1969)

    C2H4 = 300 ppm/day!

    1100 MVA Transformer

  • 8/12/2019 Smart Grid Monitoring by Duval

    48/65

    4848

    C2H4 = 300 ppm/day!

  • 8/12/2019 Smart Grid Monitoring by Duval

    49/65

    4949

    -Gassing rates were all significantly above condition 4values in the previous 4 examples.

    -The corresponding transformers were removed fromservice 1 to 3 days after looking at monitor readings, beforepotential catastrophic failure.

    -However, it might have been better to remove them fromservice earlier.

    -Without an on-line monitor, these transformers wouldpossibly have suffered catastrophic failures.

  • 8/12/2019 Smart Grid Monitoring by Duval

    50/65

    5050

    On-Line Monitoring with Multi-Gas Monitors

    - Multi-gas monitors will detect all types of faults, even intheir early stages at condition 1, and without false alarms.However, they are more expensive than hydrogen onlymonitors.

    - The recommendation of CIGRE (TB # 409, 2010) istherefore to use multi-gas monitors in critical transformers(GSU, nuclear, transmission) and in abnormally gassingtransformers.

  • 8/12/2019 Smart Grid Monitoring by Duval

    51/65

    5151

    Fault Detection with Hydrogen Monitors

    Note: for faults T3 in paper (C), curve for H 2 is a bit higher.Ref: Duval, TSUG 2013.

    Fault Detection with Hydrogen Monitors

  • 8/12/2019 Smart Grid Monitoring by Duval

    52/65

    5252

    Fault Detection with Hydrogen Monitors

    -Hydrogen monitors are most sensitive to stray gassing ofoil S (occurring in ~ 25% of cases), and to corona partialdischarges PD (occurring in only 0.3% of cases).

    -Such faults will commonly produce thousands of ppm of H 2without being a concern for the transformers. If the limit inhydrogen monitors is set at average condition 1 values forH2 (100 ppm or 7 ppm/month), this may result into manyfalse alarms.

  • 8/12/2019 Smart Grid Monitoring by Duval

    53/65

    5353

    Fault Detection with Hydrogen Monitors

    -Faults D1/D2 at dangerous condition 4 of CIGRE willproduce 0.5 ppm/day of C 2H2 together with only 1 or 2ppm/day of H 2.

    -If the limit for H 2 in the monitor is set at average condition 1(100 ppm), the monitor will detect these faults only in theirlate stages (condition 3 or 4), when dangerous levels of 25to 50 ppm of C 2H2 have already formed.

    -If it is set at 5 ppm over a period of 3 days, this may resultinto many false alarms.

    Fault Detection with Hydrogen Monitors

  • 8/12/2019 Smart Grid Monitoring by Duval

    54/65

    5454

    - In case of thermal faults T3/T2/T1/O the main gas formed is

    C2H4, CH 4 or C 2H6, together with 3 to 10 times less of H 2. Ifthe limit for H 2 is set at 100 ppm, the monitor will detectthese faults only in their late stages (condition 3 or 4).

    - Decreasing the limit for H 2 in the monitor (e.g., to 50 or 20

    ppm) will increase the number of false alarms due to faultsS or corona PD of lesser concern.

    - The recommendation of CIGRE (in TB # 409, 2010) istherefore to use hydrogen monitors in non-critical

    transmission and distribution transformers, and intransformers with no previous gassing history.

    Examples of On-Line Gas Monitors

  • 8/12/2019 Smart Grid Monitoring by Duval

    55/65

    55

    Examples of On Line Gas Monitors

    Multi-Gas Monitors

  • 8/12/2019 Smart Grid Monitoring by Duval

    56/65

    56

    Multi Gas Monitors

    Monitors of the chromatographic type:

    -after gas extraction, will separate individual gases on a GCcolumn, then measure them with GC detectors.

    -TM8, TM3 (Serveron)

    -Calisto 9 (Morgan Schaffer)

  • 8/12/2019 Smart Grid Monitoring by Duval

    57/65

    57

    Monitors of the Chromatographic-Type:

    -use the same standardized, NIST-traceable techniqueas laboratories.

    -provide automatic recalibration at fixed intervals aslaboratories do.

    -require some maintenance (change of carrier gas,calibration gas mixture, GC columns every 3 to 5 years).

  • 8/12/2019 Smart Grid Monitoring by Duval

    58/65

    58

    Monitors of the Infrared-Type:

    -after gas extraction, will measure directly individual gases withan infrared detector, and H 2 with a solid state sensor

    -Transfix 8, Transport-X 7 (GE-Kelman) use a photo-acoustic(PAS) detector.

    -LumaSense 9 uses a non-dispersive IR detector.

    M it f th i f d t

  • 8/12/2019 Smart Grid Monitoring by Duval

    59/65

    59

    Monitors of the infrared type:

    -do not require change of carrier gas and gas mixture.-cannot measure H 2 , O 2 by infrared, requiring the use ofrelatively inaccurate solid state sensors for that purpose.

    -some may need recalibration because of contaminationsin the ambient air (SF 6, oil vapours, solvents) and lampfade with time; some cannot be recalibrated in the field.

    -require change of infrared lamp ~ every 5 years.-contain several moving parts.

    Hydrogen Monitors

  • 8/12/2019 Smart Grid Monitoring by Duval

    60/65

    60

    -Hydran (GE): measures 100% of the H 2 + 18% of the COpresent in oil with a PTFE membrane and fuel cell detector.

    -Calisto 2 (Morgan Shaffer): measures H 2 only with a PTFEmembrane, GC and TCD detector.

    -TM1, Qualitrol, Weidmann: measure H 2 with an inorganicmembrane and an H 2Scan Pd solid state sensor.

    -TM1 (Serveron): improved version of H2Scan.

    Other Applications of DGA

  • 8/12/2019 Smart Grid Monitoring by Duval

    61/65

    6161

    Other Applications of DGA

    -DGA can also be used to detect faults in LTCs, using forexample Duval Triangle 2 for compartment types, and Triangles2a to 2e for in-tank types.

    -it can also be used for oils other than mineral oils, such asnatural esters (FR3, BioTemp), synthetic esters (Midel) andsilicone oils, using for example Duval Triangles 3.

    DGA in LTCs at IEC/ IEEE:

  • 8/12/2019 Smart Grid Monitoring by Duval

    62/65

    6262

    Duval Triangle 2 for compartment types Duval Triangles 2 for in-tank typesN1 (MR types M, D)N3 (MR types VR, VV)N4 (MR types R, V)N5 (MR types G, UZD)

    Duval Triangles 3 for Non-Mineral oils

  • 8/12/2019 Smart Grid Monitoring by Duval

    63/65

    636363

    Mineral oil

    FR363

    DGA in wind farm transformers at CIGRE

  • 8/12/2019 Smart Grid Monitoring by Duval

    64/65

    64646464

    64

    -Because they are usually Padmount transformers not

    designed for that purpose, many tend to form lots of gases,as a result of:

    -Corona PDs, because of poor oil impregnation.

    -Stray gassing of oil, because of abnormal overheating.

    Stray gassing of oil at CIGRE

  • 8/12/2019 Smart Grid Monitoring by Duval

    65/65

    65656565

    Stray gassing of oil at CIGRE

    -With mineral oil, H 2 at T200C.

    -With vegetable oils (e.g.,FR3), H 2 at T200C.

    65